ten times (10X) the diagonal length of the grounding system (rod X). A second probe (Y) is
placed in-line at a distance from rod X equal to the diagonal length of the grounding system.
At this point, a known current is applied across X & Z, while the resulting voltage is measured
across X & Y. Ohms Law can then be applied (R=V/I) to calculate the measured resistance.
Probe Y is then moved out to a distance of 2X the diagonal length of the grounding system, inline with X & Z, to repeat the resistance measurement at the new interval. This will continue,
moving probe Y out to 3X, 4X, ... 9X the diagonal length to complete the 3point test with a total
of nine (9) resistance measurements.
Many erroneous tests have been conducted where the technician only measured metallic loops
and not the true resistance-to-ground of the grounding system. The veracity of the Induced
Frequency Test has been questioned due to testing errors, however when properly applied to a
small to medium sized, self-standing grounding system, this test is rapid and reasonably accurate.
Test Application
The proper use of this test method requires the utility neutral to be connected to a wye-type
transformer. The oscillating voltage is induced into the grounding system at a point where it will
be forced into the soil and return through the utility neutral. Extreme caution must be taken at
this point as erroneous readings and mistakes are often made. The most common of these occur
when clamping on or inducing the oscillating voltage into the grounding system at a point where
a continuous metallic path exists back to the point of the test. This can result in a continuity test
being performed rather than a ground resistance test.
Understanding the proper field application of this test is vital to obtaining accurate results. The
induced frequency test can test grounding systems that are in use and does not require the
interruption of service to take measurements.
Ground Resistance Monitoring
Ground resistance monitoring is the process of automated timed and/or continuous resistance-to
ground measurement. These dedicated systems use the induced frequency test method to
continuously monitor the performance of critical grounding systems. Some models may also
provide automated data reporting. These new meters can measure resistance-to-ground and the
current that flows on the grounding systems that are in use. Another benefit is that it does not
require interruption of the electrical service to take these measurements.
Next
Our engineering manager David Stockin is the author of McGraw Hills NEC 2014
Grounding and Earthing Handbook which fully discusses above-grade wiring issues and belowgrade earthing issues related to electrical grounding in conjunction with Article 250 of the 2011
National Electrical Code. CLICK HERE 10% Off Any Electrical Grounding Service including
cell site grounding and telecommunications grounding, ground potential rise studies, grounding
system design, lightning strike analysis, grounding system evaluations, power quality monitoring
and load analysis and soil resistivity testing. CLICK HERE Ask the Experts Submit a question
regarding electrical grounding. CLICK HERE
HOME
GROUNDING SERVICES
COMPANY