Professional Documents
Culture Documents
Introduction
A water cooler is a device that cools and supplies water for drinking purposes. They are extensively
used for home as well as commercial applications. For home applications, they are more
commonly referred to as water dispensers, which along with cooling water also purify it. The
cooling capacities range from around 3 L/h to 5 L/h and they consume 100 W to 200 W power for
a family of five to six people. In the latest models, water heating systems are also being coupled
with water coolers to enhance their productivity. For commercial applications the cooling
capacities could range from 40 L/h for small establishments to 200 L/h for large commercial
establishments like hospitals, malls, railway stations, hostels and educational institutions.
(a)
(b)
Figure 1.1 (a) An USHA 3 L/h water dispenser for home applications (b) A 200 L/h large USHA
water cooler for commercial usage
Most of todays water coolers work on vapour compression cycle. R134a is widely used as the
refrigerant due to its low boiling point (-23oC) and very low ozone layer depletion potential. The
major components of vapour compression cycle are the compressor, condenser, expansion valve
and the evaporator. The diagrammatic representation of a typical single stage vapour compression
cycle is shown in Figure 1.
(a)
(b)
Figure 1.2 (a) A typical vapour absorption refrigeration cycle (b) Temperature-entropy diagram
of the vapour absorption refrigeration cycle
2
The temperature-enthalpy diagram of the cycle is shown in Figure 2. The circulating refrigerant
vapour enters the compressor at point 1 (shown in figure 3). In the compressor, the vapour is
compressed at nearly constant entropy and exits it at a higher temperature but still below vapour
pressure at point 2. From point 2 to 3, the vapour cools to the vapour pressure and then enters the
condenser, where it condenses to form liquid refrigerant. Between points 4 and 5, the vapour passes
through the expansion valve, its pressure decreases abruptly at a constant enthalpy. The resultant
liquid-vapour refrigerant enters the evaporator, where it boils by absorbing heat from water,
thereby cooling it.
Chapter 2
Compressors
A refrigeration compressor is a machine used to continuously draw the refrigerant vapour from the
evaporator, so that a low pressure and low temperature can be maintained in the evaporator at
which the refrigerant can boil by extracting heat from the refrigerated space. The compressor then
has to raise the pressure of the refrigerant to a level at which condensation can occur by rejecting
heat to the cooling medium in the condenser. It also continually circulates the refrigerant through
the refrigerating system. The compressor is driven by some prime mover.
2. Rotodynamic compressors
In rotodynamic compressors, the flow is continuous. The fluid is subject to flow processes
and the work is transferred by virtue of the change of momentum of stream of fluid flowing
at a high speed over blades or vanes attached to a rotor.
2.1.2 Based on the method of compression
1. Reciprocating compressors
4
The compressors in which the vapour refrigerant is compressed by the back and forth
motion of the piston are called reciprocating compressors.
2. Rotary compressors
The compressors in which the vapour refrigerant is compressed due to the movement of
blades are called rotary compressors.
3. Centrifugal compressors
The compressors in which rise of pressure of vapour refrigerant is done by a centrifugal
force are called centrifugal compressors.
2. Multi-stage compressors
In multi-stage compressors, vapour refrigerant is delivered at high pressures using two or
more cylinders placed in series. In these compressors, use of crankshaft seal is eliminated.
They are used for small capacity refrigeration systems like domestic refrigerators and home
freezers.
2. Hermetic compressors
In hermetic compressors, the direct drive, motor and compressor are all placed in the same
housing.
The compressors using both sides of the piston during compression are known as double
acting reciprocating compressors.
Screw compressors
Rotary screw compressors consist of two helically grooved rotors which rotate in a
housing. The male rotor consists of lobes and is normally the driving motor. The female
rotor has gullies and is normally the driven rotor. A four lobe male rotor will drive a six
gully female rotor at two third of its speed. As they are high speed rotary machines, a large
7
volume can be handled by them therefore they are found extremely suitably for large
capacity, low-temperature applications like central air conditioning plants.
Scroll compressors
Scroll compressors are valve-less positive displacement machines like rotary and screw
compressors. Because of their simplicity, they have become very popular with the industry
in recent years. Here the compression is achieved by two intermitting, spiral shaped scroll
members, one of which is a fixed screw and the other one is an orbiting scroll. The capacity
ranges from 1 to 14 TR.
2.5 Selection
The compressor chosen for the desired application, i.e. a medium capacity water cooler is a singleacting, reciprocating type, single-stage, hermetic sealed compressor.
The hermetic, reciprocating type compressor has been chosen for the desired application because
it offers several advantages as compared to its other counterparts. These are as follows:
The lubrication of hermetic compressors is simple as the motor and compressor operates
in a sealed space with the lubricating oil.
Reciprocating compressors are available in sizes as small as 1/12 KW which are used in
small domestic refrigerators and up to about 150KW.
The cost of a typical rotary screw compressor, in terms of initial purchase price and
installation, is generally less than a reciprocating compressor. However, provided that it is
properly maintained, a reciprocating compressor can be expected to last between two and
five times longer.
10
Chapter 3
Condensers
Condenser is a heat exchanger which removes heat of the hot refrigerant discharged from the
compressor, thus condensing the vapour refrigerant in the process. Condensation is the change of
the physical state of matter from gas phase into liquid phase. Condensation processes can be
classified into two types:
The hot vapour refrigerant which is condensed consists of the heat absorbed by the evaporator and
the heat of compression added by the mechanical energy of the compressor motor. The heat from
the hot vapour refrigerant is removed first by transferring it to the walls of the condenser tubes and
then from the tubes to the condensing medium, which may be air or water or a combination of
both.
Condensing of the gas to liquid state and release of the latent heat.
Since the phase in each stage is different, the design of each stage must be taken separately.
Generally sub-cooling part in the condensers is very less and is neglected. But in systems with
very high sub-cooling, sub-cooling cannot be neglected.
11
the shell and according to the capacity requirement, the refrigerant can flow inside or outside the
coil. Finned coils can also be used to increase the rate of heat transfer.
tubes in single to four passes. The condensed refrigerant collects at the bottom of the shell. The
coldest water contacts the liquid refrigerant so that some sub cooling can also be obtained.
14
3.3 Selection
For the required application, design of both water cooled and air cooled condensers will be carried
out. Among air-cooled condensers, the forced convection type condenser is selected because the
natural convection type has larger space requirements. Among the water-cooled condensers, the
shell and coil type condenser is selected for design because shell and tube type requires frequent
maintenance due to high fouling rate, whereas tube and tube type requires a very large length,
which increases the pressure losses beyond the permissible limits, which is undesirable.
16
Chapter 4
Evaporators
An evaporator is a heat exchanger in which refrigerant is evaporated, thereby cooling a fluid (here
water) circulating through the evaporator. The latent heat absorbed by the refrigerant cools the
water around it.
In pool boiling, the fluid is not forced to flow by a mover such as a pump, and any motion of the
fluid is due to natural convection currents and the motion of bubbles under the influence of
buoyancy.
During boiling four different regimes are observed: natural convection boiling, nucleate boiling,
transition boiling and film boiling.
1. Natural Convection Boiling (up to point A): During this stage the liquid is slightly
superheated and evaporates as it rises to the free surface. The motion of the fluid in this
case is purely due to natural convection currents.
17
2. Nucleate Boiling (between points A and C): The first bubbles start forming at A of the
boiling curve at various preferential sites of the heating surface. Point A is called onset of
nucleate boiling.
3. Transition boiling (between points C and D): As the heater temperature is increased beyond
C, the heat flux decreases. In transition boiling, both nucleate as well as film boiling occur.
4. Film boiling (beyond point D): In this region the heat transfer is completely covered by a
continuous vapour film. The heat transfer coefficients are low in this regime.
In flow boiling, the fluid is forced to move by an external source such as a pump as it undergoes a
phase change process. The boiling in this case exhibits the combined effects of convection and
pool boiling. The flow boiling can also be classified as either external flow boiling or internal flow
boiling.
External flow boiling over a plate or cylinder is similar to pool boiling, but the added
motion increases both the nucleate boiling heat flux and the critical heat flux considerably.
18
Internal flow boiling is much more complicated in nature because there is no free surface
for the vapour to escape, and thus both the liquid and the vapour are forced to flow together.
The two-phase flow in a tube exhibits different flow boiling regimes, depending on the
relative amounts of the liquid and the vapour phases. This complicates the analysis even
further.
Bare-Tube-Coil Evaporators
They were one of the first types of evaporators used. They consist of long run of coils,
through which the refrigerant flows. They are simple in construction and hence can be
easily fabricated and cleaned. However, they provide a very little contact area and hence
the length of the tube has to be very long even for low capacity refrigeration systems. They
are usually constructed of either steel pipe or copper tubing. Steel pipes are used for large
evaporators while copper tubing is for smaller evaporators. Common shapes are flat, oval
trombone and spiral.
(a)
(b)
Figure 4.2 Common designs of bare tube evaporators. (a) Flat zigzag coil (b) Oval trombone
19
Finned-Tube Evaporator
These consist of bare tubes or coils over which metal plates or fins are fastened. The fins,
serving as secondary heat absorbing surfaces, have the effect of increasing the overall
surface are of the evaporator, thereby improving its efficiency. The metal fins are
constructed of thin sheets of metal having good thermal conductivity. Fin spacing is kept
large for larger tubes and small for smaller tubes. Formation of frost drastically reduces
their performance, as the frost restricts the passage of fluid between the fins. Hence, they
should never be used for refrigeration temperatures below 0oC. They are primarily
designed for air-conditioning applications.
Plate-Surface Evaporator
These evaporators consist of formed tubing installed between two metal plates, which are
welded together at edges. In order to provide good thermal contact between the welded
plates and the tubing carrying is evacuated so that the pressure of the atmosphere exerted
on the outside surface of plates, holds the plates firmly against the tubing inside. These are
widely used as partitions in freezers, frozen food display cases, ice-cream cabinets, etc.
They are helpful when unusual peak load conditions are experienced frequently.
20
Shell-and-Tube Evaporator
The shell-and-tube evaporators are very efficient, require minimum floor space and head
space. They are easy to maintain, and hence are widely used in medium to large capacity
refrigeration systems. They consist of a shell and a large number of tubes arranged parallel
to each other. The shell diameters range from 150 mm to 1.5 m. The number of tubes may
vary from fifty to several thousand, each of length 1.5 m to 6 m. A series of baffles channels
the fluid throughout the shell side. The baffles create cross flow through the tube bundle
and increase the velocity of fluid, thereby increasing its heat transfer coefficient. The
velocity of fluid flowing perpendicular to the tubes should be at least 0.6 m/s to clean the
tubes and less than the velocity limit of the tube and baffle materials, to prevent erosion.
Shell-and-Coil Evaporator
These evaporators consist of a tank in which the fluid to be cooled is placed. A simple
coiled tube is used for cooling the fluid. The fluid in shell gives large amount of thermal
storage capacity and hence has can give good performance with small but infrequent peak
loads. Sometimes, the refrigerant is placed inside the shell and the fluid to be cooled flows
through the tube. These types of shell-and-coil evaporators can give instantaneous cooling.
They are mostly used at low capacities, e.g., for bakeries, photographic labs and to cool
drinking water.
Baudelot Evaporator
These evaporators are used to cool the fluid to near its freezing temperature. The fluid
circulates over the outside of vertical plates, which are easy to clean. The inside surface
of the plates is cooled by evaporating the refrigerant. The fluid to be cooled flows
uniformly from the top of the evaporator to the bottom. Insulation is usually provided to
prevent heat loss. They are mainly used for industrial applications and especially in dairy
industry.
22
Direct-Expansion Evaporator
The refrigerant evaporates inside the tubes of this evaporator. They are usually used with
positive displacement compressors like reciprocating compressors, rotary screw
compressors etc. The distribution of refrigerant is critical in these types of evaporators, as
any imbalance causes a drastic decrease in heat transfer coefficient. The number of passes
can be single or multiple. They are generally used for low to medium capacity refrigeration
applications.
Flooded Evaporator
The flooded type of evaporator is always completely filled with the refrigerant. The
evaporated vapour is taken away by the compressor. The inside surface of these
evaporators is always completely wetted with liquids and hence they have very high heat
transfer coefficient. However, they are bulky and require a large amount of refrigerant
charge. One variation of flooded shell-and-tube evaporator is spray shell-and-tube
evaporator. When the refrigerant pressure has an adverse effect on heat transfer coefficient,
the liquid is sprayed in the tubes, rather than flooding them.
24
4.3 Selection
For the required application, which is a medium capacity water cooler, shell and coil type
evaporator is chosen. The reasons which dictate the choice of shell and coil type evaporator are:
Since only one coil of larger diameter is used, the construction is easier. The single coiled
tube has only to be soldered inside the shell at opening and exit.
The coiled tubing is free to expand and contract with temperature changes because of its
spring action.
Shell and coil type evaporator is specifically used in applications where cleanliness is
required, e.g. bakeries, photographic laboratories, drinking water, etc. Since the application
involves drinking water which should not be contaminated while being refrigerated, this
type is thus chosen.
25
Chapter 5
Expansion Devices
Expansion devices are the devices which are used to lower the pressure of the refrigerant from the
high value at the compressor, condenser side to the low value at the evaporator side. There are
basically two functions of expansion devices:
To regulate the refrigerant flow rate from the high pressure liquid line into the evaporator
at a rate equal to the evaporation rate in the evaporator.
Fixed opening type, in which the flow area remains fixed. These include capillary tubes.
Variable opening type, in which the flow area changes with the changing mass flow rates.
These include Constant Pressure Automatic Expansion Valves, Thermostatic Expansion
Valves and Float type Expansion Valves.
The constant pressure valve is also called as the automatic expansion valve but this is the misnomer
since it is not automatic for it does not allow automatic control of the flow of refrigerant through
it. In the very earlier days only hand operated expansion valve or throttling valve was available,
however since this valve allowed automatic constant pressure in the evaporator, it was given the
name automatic expansion valve.
27
28
A low-side float valve maintains a constant liquid level in a flooded evaporator or a float chamber
attached to the evaporator. When the load on the system increases, more amount of refrigerant
evaporates from the evaporator. As a result, the refrigerant liquid level in the evaporator or the
low-side float chamber drops momentarily.
A high-side float valve maintains the liquid level constant in a float chamber that is connected to
the condenser on the high pressure side. When the load increases, more amount of refrigerant
evaporates and condenses. As a result, the liquid level in the float chamber rises momentarily.
5.2 Selection
For the medium capacity water cooler application, expansion valve selection is based on the type
of evaporator employed. A table showing different types of evaporators for various capacity ranges
and the expansion valves employed for the corresponding evaporator types. It can be seen that for
the required application, since power requirement is less than 10 kW, a shell and coil type
evaporator in conjunction with a thermostatic expansion valve is used.
29
A thermostatic expansion valve provides several advantages which make its use suitable. Some of
them are listed as follows:
It maintains the flow of the refrigerant to the evaporator as per the load inside. Thus the
refrigeration or the air conditioning plant can run to the optimum capacity as per the
requirements.
It keeps the evaporator fully active and helps getting the optimum cooling effect from it.
Since the entire refrigerant in the evaporator gets vaporized the chances of the liquid
refrigerant particles going to the compressor are reduced. This reduces the chances of the
breakdown of the compressor due to compression of the liquid.
Table 5.1 Summary of characteristics of various types of evaporators for different power
capacities and the corresponding expansion devices used
Type of
Evaporator
Capacity Range
(kW)
7-3500
Electronic Modulation
Valve
7-3500
Brazed Plate
2-700
Semi Welded
Plate
175-7000
90-7000
90-21100
180-35000
180-35000
Brazed-Plate
2-700
Semi Welded
Plate
175-7000
Flooded
35-350
Direct-Expansion
18-90
7-35
Subtype
Shell-and-Tube
Direct-Expansion
Shell-and-Tube
Flooded
Spray shell-tube
Baudelot
Shell-and-Coil
30
Chapter 6
Design procedure of a water cooler
Design of a water cooler involves design of various components, i.e. compressor, condenser,
evaporator and expansion device. During the study of these components, we have chosen the types
of these components. Now, the design of these components will follow.
With these assumptions, the Refrigeration Effect can be obtained. Dividing the energy required to
be removed from the water by the enthalpy difference across the evaporator will yield the mass
flow rate of the refrigerant. This mass flow rate can then be used for further design of individual
components of the system.
equation:
k=
p
ln (p s )
d
v
ln( vd )
s
where ps is the suction pressure in Pa, pd is the discharge pressure in Pa, vs is the
suction volume in m3/kg and vd is the discharge volume, m3/kg.
2.
31
k1
k
k
pd
w = ps vs (
) [( )
k1
ps
1]
3. Assume an appropriate clearance ratio (clearance ratio is less than 5% for well-designed
compressors):
=
vc
vsw
pd k
v = 1 + ( )
ps
5. Find out the compressor power consumption as:
W = m w
where m is the mass flow rate of the refrigerant and w is the compressor work.
6. Find out volumetric flow rate of compressor as:
Vr = m vs
7. Find out required compressor displacement rate
V
r
Vs =
v
where Vr is the volumetric flow rate of the refrigerant through the compressor, and v is
the volumetric efficiency of the compressor.
8. Assume some stroke to bore ratio, based on the following guidelines:
a. Vacuum pumps and high speed air compressors: < 0.5
b. Fluorocarbon compressors: = 0.8
c. Ammonia compressors: = 1.0
d. High pressure compressors: = 4.6
9. Assume suitable mean piston speed (1.5 m/s to 5 m/s) and find out rotational speed of
compressor as:
30Cm
N=
L
where Cm is the mean piston speed in m/s, N is the rotational speed of crank in rad/s, D
is the diameter of the compressor cylinder in m, L is the length of compressor cylinder in
m.
32
10. Find out bore of the cylinder (assuming single cylinder) as:
1/3
240 Vs
D=(
)
N
11. Find out the length of the cylinder as:
L= D
Twd = Twi +
LMTDdesuperheat =
Qsv
mw Cpw
Qc = mr (hti hto )
33
Twc = Twd +
LMTDdesuperheat =
Qc
mw Cpw
Tm =
Qc + Qsv
Q
(LMTD)
Where mw is mass flow rate of coolant stream, Cpw is heat capacity of coolant stream, Qc is heat
released during condensation, Qsv is heat released during desuperheating, Twi is inlet temperature
of coolant stream, Twd is temperature of coolant steam after desuperheating, Twc is temperature of
coolant stream after condensation, Tri is temperature of the refrigerant before desuperheating, Thi is
temperature of refrigerant before condensation, Tho is temperature of refrigerant after
condensation.
34
The overall heat transfer coefficient for a finned condenser is formulated as,
U0 =
1
A
A
A t
1
( o ) + ( Ao rfw ) + ( Ao ) + (
)
Ai hi
k
h
(A
i
i
r
b + Af f )
Where Ao is the outer surface area , Ai is the internal surface area,hi is heat transfer coefficient of
refrigerant, rfw is the resistance due to fouling, t is the thickness of tube, k is thermal conductivity
of metal, hr is heat transfer coefficient of air, Ab is bare area of tube, Af is area of fin, f is efficiency
of fin.
The refrigerant side heat transfer coefficient can be estimated from one of the following
correlations:
Chaddock and Chatos correlation
The average value of heat transfer coefficient over the legth of condenser is estimated as
k 3f f (f g )ghfg
ho = 0.555 [
]
Di f t
Where the modified enthalpy of evaporation is defined as, hfg = hfg + 3Cpf t/8 , k f is the
conductivity of fluid refrigerant, f is density of fluid refrigerant at saturation temperature, g is
density of gaseous refrigerant at dry saturation temperature, gis acceleration due to gravity, Di is
internal diameter of the tube, f is viscosity of fluid refrigerant at saturation temperature.
Shahs correlation
This correlation takes into consideration the effect of pressure of the refrigerant and also the
quality of mixture. This correlation can also be used for calculating local condensation heat
transfer coefficient. This equation is much similar to Dittus Boelter equation.
35
hi = hl [(1 x)
0.8
Kf
Di
p
pcritical
Where Di is internal diameter of the tube, x is dryness fraction, Ref is Reynold number of fluid
refrigerant, Prf is Prandtl number of fluid at saturation temperature, K f is the conductivity of
fluid refrigerant, p is pressure
Akers, Dean and Crosser relation
This equation is used for turbulent flow of refrigerant inside the tubes.
hl = 5.06(Rem )0.333 (Prf )0.333
Kf
Reg < 5X104
Di
Kf
Reg > 5X104
Di
f
Rem = Ref [1 + ( )
g
0.5
Where Di is internal diameter of the tube, x is dryness fraction, Ref is Reynold number of fluid
refrigerant, Prf is prandtl number of fluid at saturation temperature, K f is the conductivity of fluid
refrigerant, Reg is Reynold number of gaseous refrigerant,f is density of fluid refrigerant at
saturation temperature, g is density of gaseous refrigerant at dry saturation temperature.
36
U0 =
1
Ao
A
A t
1
) + ( Ao rfw ) + (A o ) + (
)
Ai hi
k
h
i
m
r s
Where Ao is the outer surface area , Ai is the internal surface area,hi is heat transfer coefficient of
refrigerant, rfw is the resistance due to fouling, t is the thickness of tube, k is thermal conductivity
of metal, hr is heat transfer coefficient of water, s is surface efficiency of fin
Now, heat transfer coefficient on the water side is given by,
hw D
DG 0.8 cp 0.4
= 0.023 ( ) (
)
k
k
where hw is heat transfer coefficient of water, D is hydraulic diameter of the tube, kis thermal
conductivity of water, Gis density of water, is viscosity of water, cp is specific heat of water.
1
1
A
t A
+ i + ( i ) + rfi
hi Ao ho k Am
1
1
A
t A
+ o + ( o ) + rfo
ho Ai hi k Am
37
where hi = inside heat transfer coefficient based on inside surface area in W/m2K
ho = outside heat transfer coefficient based on inside surface area, W/m2K
Ai = inside heat transfer surface area, m2
Ao = outside heat transfer surface area, m2
Am = mean heat transfer surface area, m2
k= thermal conductivity of the heat transfer material, W/m.K
t = thickness of heat transfer surface (tube wall thickness), m
rfi = fouling factor of fluid side based on inside surface area, (m2K)/W
rfo = fouling factor of fluid side based on outside surface area, (m2K)/W
6.4.2 Calculation of
The value of Tm can be found using the log mean temperature difference
Tm = F
(T1 Te ) (T2 Te )
T T
ln (T1 Te )
2
e
where
T1
T2
Te
x
The refrigerant boils inside the evaporator while flowing. Hence it can be considered to be an
aggregate of nucleate pool boiling and forced convection. Heat flux due to nucleate pool boiling
is calculated using pool boiling equation, while that due to forced convection can be found using
standard forced convection equations.
38
g(l v ) cpl Te
q = l hfg
(
)
Csf hfg Pr n
The corresponding heat transfer coefficient can be found using the relation
q = h(Ts Te )
Forced Convection Relations
Dittus and Boelter Equation: This equation gives heat transfer coefficient for forced convection
Nu = 0.019(Rel )0.8 Pr 0.3
Once heat transfer coefficients are found from the above two equations, the total heat transfer
coefficient can be found by adding them.
xhfg
L
Te = Ts Te
Ts = surface temperature of tubing, K
Te = evaporation temperature of the refrigerant, K
Pr = Prandtl number of the refrigerant
n = a constant (usually 1.7)
Csf = constant, 0.013 for halocarbons
Nu= Nusselt number,
hD
k
l vD
l
Find out the saturation pressures, psat (Te) and psat (Te + Ts) of the refrigerant at Te and
Te + Ts, either from standard refrigeration tables or using Antoines equation for R134a
2094
psat = e14.41T33.06
where psat is in kPa and T is in K
Based on the required deflection of spring, find out the area of the bellows:
Ab =
40
Fs
ps
Chapter 7
Conclusion
In the study done, the preliminaries of water cooler were performed. Design of water cooler
involves design of different components of the cooler, i.e. compressor, condenser, evaporator and
expansion device. To select the appropriate type of component, it is essential that the various types
available be studied, and then, based on their merits and demerits, and the required application, a
suitable type be selected for further procedure. This was done in the current study. After the study,
a reciprocating type compressor, shell and coil type water cooled condenser, a forced convection
type air cooled condenser, a shell and coil type evaporator and a thermostatic expansion valve were
selected as the most suitable types to be designed. An overview of the design procedure to be
carried out was highlighted. Based on this, the further design of the water cooler will be carried
out.
41
References
1. Arora, R.C. Refrigeration and air-conditioning . PHI Learning Private limited, 2010
2. Arora, C.P. Refrigeration and air-conditioning .3rd ed. Mc Graw Hill, 2010
3. Bell K.J., Mueller A.C. Heat transfer databooks Wolverine Tube, Inc. 2001 www.wlv.com
4. ASHRAE Handbook (2008): American society of heating refrigeration and air
conditioning engineers, Inc., Atlanta, Ga
5. Royce N. Brown compressor sizing and selection 3rd ed. Gulf professional
publishing 2005
6. Dossat R.J. Principles of refrigeration 5th ed. Prentice Hall 2001
7. Khurmi R.S., Gputa J.K. A textbook of refrigeration and air conditioning 5th ed.Euresia
Publishing House 2012
8. Ananthanarayanan Basics of refrigeration and air conditioning 4th ed. Mc Graw Hill, 2013
42