Professional Documents
Culture Documents
Department of Mechanical Engineering, National Chiao Tung University, Hsinchu 300, Taiwan
Department of Mechanical Engineering, Yuan Ze University, Taoyuan, Taiwan
a r t i c l e i n f o
a b s t r a c t
Article history:
Received 17 June 2014
Received in revised form
14 September 2014
Accepted 20 September 2014
Available online xxx
The present study examines the air side performance of the n-and-tube heat exchangers having semidimple vortex generator or plain n geometry. A total of eight samples are made and tested with the
corresponding n pitch (Fp) being 1.6 mm and 2.0 mm and the number of tube row (N) are 1 and 2. The
inlet air ow direction is also being tested upon the proposed semi-dimple VG. Test results indicate that
the heat transfer performance of the proposed semi-dimple VG with N 1 at a smaller n pitch of
1.6 mm is slightly higher than that of plain n geometry. For N 1 with a larger n pitch of 2.0 mm, the
semi-dimple VG is about 10% higher than that of plain n geometry. The difference in heat transfer
performance amid VG and plain n geometry becomes more pronounced with N 2 and is especially
evident when Fp 2.0 mm due to mixing contribution. In general, the difference between plain and
semi-dimple geometry becomes more conspicuous at a larger n pitch because of the comparatively
effectively swirled motion. Both geometries show a dependence on n pitch at N 1 but the effect is
almost negligible when N is increased to 2. The inlet air ow direction casts negligible inuence on the
heat transfer performance of semi-dimple VG. However, the friction factors for the opposite air ow
operation is lower than that of normal operation, especially in low Reynolds number region.
2014 Elsevier Ltd. All rights reserved.
Keywords:
Fin-and-tube heat exchanger
Semi-dimple
Vortex generator
Heat transfer
1. Introduction
In typical air-cooled heat exchanger applications, normally the
air-side thermal resistance accounted for nearly or more than 90%
of the total thermal resistance. Hence accommodation of large n
surface area is the generally adopted. In addition, protrusions or
interrupted surfaces can be mounted on at surfaces to provide
better heat transfer performance. The surfaces can be in the form of
continuous surfaces (e.g. plain, wavy) or interrupted (louver, slit,
offset, and the like). Some review articles by Wang [1,2] had
reviewed the patents of enhanced surfaces related to the n-andtube heat exchangers. From the 80 patents being surveyed, 90% of
them are related to the interrupted surfaces. However, interrupted
surface normally accompanied appreciable pressure drops.
Accordingly, one of the recent designs is to introduce the so-called
vortex generator (VG) which may ease the problem of signicant
pressure drop caused by highly interrupted surfaces. Through some
http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
1359-4311/ 2014 Elsevier Ltd. All rights reserved.
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
averaged. During the isothermal test, the variance of these thermocouples was within 0.2 C.
The pressure drop of the test coil was detected by a precision
differential pressure transducer, reading to 0.1 Pa. The air ow
measuring station was a multiple nozzle code tester based on the
ASHRAE 41.2 standard [23]. The working medium in the tube side
was hot water. The inlet water temperature was controlled by a
thermostat reservoir having an adjustable capacity up to 25 kW.
Both the inlet and outlet temperatures were measured by two precalibrated RTDs (Resistance temperature device, Pt-100 U). Their
accuracy was within 0.05 C. The water volumetric ow rate is
detected by a magnetic ow meter with 0.002 L/s resolution.
All the data signals are collected and converted by a data acquisition system (a hybrid recorder). The data acquisition system then
transmitted the converted signals through GPIB interface to the host
computer for further operation. During the experiments, the water
inlet temperature was held constant at 60.0 0.2 C, and the tube
side Reynolds number was approximately 38,000. Frontal velocities
of inlet air ranged from 1 to 5 m/s. The energy balance between air
side and tube side was within 2%. The water side resistance (evaluated as 1/hiAi) was less than 10% of the overall resistance in all cases.
The test n-and-tube heat exchangers are tension wrapped having
an L type n collar. Thermal contact conductance provided by the
manufacturers ranged from 11,000 to 16,000 W/m2 K.
3. Data reduction
The -NTU method is applied to determine the UA product in the
analysis heat transfer and pressure loss characteristics of the test
coil from the experimental data. The detailed derivation of the heat
transfer coefcient can be referred to Wang et al. [21] and will not
repeat here. The obtained air sider heat transfer coefcient is then
in terms of the Colburn j factor:
As tabulated in Table 1, a total of eight sample coils which includes plain and semi-dimple VG. The detailed dimension and the
photo of the semi-dimple VG is schematically shown in Fig. 1.
Notice that the n thickness (df), collar diameter (dc), transverse
pitch (Pt), and longitudinal pitch (Pl) for all the test samples are
0.11 mm, 7.5 mm, 21 mm, and 18.2 mm, respectively. The corresponding n pitch (Fp) ranges from 1.6 to 2.0 mm and the number of
tube row (N) spans from 1 to 2 as shown in Table 1. Detailed construction of the circuitry arrangement is identical to Wang et al.
[21]. The experiments are conducted in an open wind tunnel as
shown in Fig. 2. The ambient air ow was forced across the test
section by means of a 5.6 kW centrifugal fan with an inverter. To
avoid and minimize the effect of ow maldistribution in the experiments, an air straightener-equalizer and a mixer were provided. The inlet and the exit temperatures across the sample coil
were measured by two T-type thermocouple meshes. The inlet
measuring mesh consists of twelve thermocouples while the outlet
mesh contains 36 thermocouples. The sensor locations inside the
rectangular duct were established following ASHRAE recommendation [22]. These data signals were individually recorded and then
where Ao and Ac stand for the total surface area and the ow crosssectional area, respectively. Uncertainties in the reported experimental values were estimated by the method suggested by Moffat
[25]. The derived uncertainties of Colburn j factors range from 2.4 %
to 7.3 % and is 3.6% to 11.2 % of the friction factors.
Table 1
Detailed geometric parameters of the test samples.
No.
Fp (mm)
N, row
Geometry
1
2
3
4
5
6
7
8
1.6
1.6
2.0
2.0
1.6
1.6
2.0
2.0
1
1
1
1
2
2
2
2
Plain
VG
Plain
VG
Plain
VG
Plain
VG
ho
Pr2=3
rVmax Cpa
(1)
"
#
r
Ac rm 2DPr1
1
2
1
s
1
Ao r 1
r2
G2c
(2)
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
Fig. 1. Detailed geometry and photo of the semi-dimple VG and relevant operation (unit: mm).
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
P H.X
Air Flow
3-phase, 220V
P SAT
P NOZZLE
T
Hot Water
Thermostat
Reservoir
PID
GPIB
Hybrid
Recorder
SCR
PC
Computer
1 Air inlet
2 Straightener
3 Developing section
4 Pressure tap(inlet)
5 T/C inlet temperature measuring station
6 Test unit(Heat Exchanger)
7 T/C outlet temperature measuring station
8 Pressure tap(outlet)
9 Mixer
10 Settling Devices (Flow Straightener)
15 Centrifugal fan
16 Air discharge
17 Water pump
18 Water flow meter
19 RTD inlet temperature of water side
20 RTD outlet temperature of water side
21 Temperature sensor
22 Inverter
Fp =
Fp =
Fp =
Fp =
Fp =
Fp =
Fp =
Fp =
1.6 mm (Plate)
1.6 mm (VG)
2.0 mm (Plate)
2.0 mm (VG)
1.6 mm (Plate)
1.6 mm (VG)
2.0 mm (Plate)
2.0 mm (VG)
0.1
0.1
j and f
j and f
j
j
N=2
0.01
0.01
N=1
100
1000
Redc
Fig. 3. Test results for N 1.
10000
100
1000
10000
Redc
Fig. 4. Test results for N 2.
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
j 0:29Re0:58
dc
2:2Re0:38
dc
0:8
Fp
N0:2
dc
Fp
2
dc
0:5
1:5 !
Fp
1:4 log10 Redc
dc
(3)
(4)
0.1
f
j and f
0.01
100
N=2
1000
10000
Redc
Fig. 5. Comparison of the present semi-dimple VG subject to reversing inlet ow
condition.
The foregoing equations can predict 90% of the measured semidimple VG data within 10%.
5. Conclusions
In this study, an experimental study is carried out to examine
the air side performance of the n-and-tube heat exchangers
having plain or semi-dimple vortex generator. A total of eight
samples are made and tested in a well controlled wind tunnel. The
corresponding n pitch of the test samples are 1.6 mm and 2.0 mm
respectively and the number of tube row are 1 and 2, respectively.
The operational Reynolds number is from 400 to 4000. The inlet air
ow direction into the semi-dimple VG is also examined in this
study. Based on the foregoing discussions, some major conclusions
of this study are summarized as follows:
(1) For the air side performance for N 1 with a smaller n pitch
of 1.6 mm, the heat transfer performance for the semidimple VG is slightly higher than that of plain n geometry. For a larger n pitch of 2.0 mm, the heat transfer performance for the semi-dimple VG is approximately 10%
higher than that plain n geometry but accompanies a
30e40% increase of friction factor.
(2) For the air side performance of N 2, the effect of n pitch
cast a negligible inuence on the heat transfer performance
for both n geometries. However, the heat transfer performance of the semi-dimple VG relative to plain n geometry
is also increasing due to the contribution of mixing. A heat
transfer augmentation of 17% for semi-dimple VG can be
achieved but the corresponding friction factor penalty is
about 30%. The difference in heat transfer performance is
increased with the rising Reynolds number and the results
prevail for both n pitches. However, the difference in heat
transfer performance becomes more pronounced at a larger
n pitch due to comparatively effectively swirled motion.
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054
(3) With regard to the effect of inlet air ow into the semidimple VG heat exchangers, test results indicate that the
heat transfer performance is barely the same while the
friction factor for the opposite operation is notably lower
than those of normal operation. The difference is especially
pronounced when the Reynolds number is lower than 1500.
In fact, the difference can be as high as 30e40% when the
Reynolds number is less than 1000. The identical heat
transfer performance implies that the contribution of swirled
ow and mixing mechanism are actually comparable.
(4) A correlation is proposed to describe the data of semi-dimple
VG n-and-tube heat exchanger, the proposed correlation
can describe 90% of the test data within 10%.
Acknowledgements
The authors appreciate the nancial support from the Ministry
of Science and Technology, Taiwan under contract 103-3113-E-009002.
Nomenclature
A
Ac
Ao
cp
dc
do
f
Fp
Gc
ho
j
k
N
NTU
DP
Pl
Pr
Pt
Redc
T
df
U
Vfr
Vmax
m
r
s
area
minimum ow area, rAfr
total surface area
specic heat at constant pressure
n collar outside diameter, do 2df
tube outside diameter
friction factor
n pitch
mass ux of the air based on the minimum ow
area, rVmax
heat transfer coefcient
Nu/RePr1/3, the Colburn factor
thermal conductivity
number of tube row
number of transfer unit
pressure drop
longitudinal tube pitch
Prandtl number
transverse tube pitch
rVdc/m, Reynolds number
temperature
n thickness
overall heat transfer coefcient
frontal velocity
maximum velocity inside the heat exchanger, Vmax Vfr/s
Q_ ave =Q_ max , heat exchanger effectiveness
dynamic viscosity of uid
density
contraction ratio of cross-sectional area
Subscripts
1
air side inlet
2
air side outlet
air
air side
f
n surface
m
mean value
References
[1] C.C. Wang, Technology review e a survey of recent patents of n-and-tube
heat exchangers, J. Enhanc. Heat Transfer 7 (5) (2000) 333e345.
[2] C.C. Wang, A survey of recent patents of n-and-tube heat exchangers from
2001e2009, Int. J. Air-Cond. Refrig. 18 (1) (2010) 1e13.
[3] G. Biswas, H. Chattopadhyay, A. Sinh, Augmentation of heat transfer by creation of streamwise longitudinal vortices using vortex generators, Heat
Transfer Eng. 33 (4e5) (2012) 406e424.
[4] F.J. Edwards, G.J.R. Alker, The improvement of forced convection surface heat
transfer using surfaces protrusions in the form of (A) cubes and (B) vortex
generators, in: Proc. 5th Int. Heat Transfer Conf., vol. 2, 1974, pp. 244e248.
[5] M. Fiebig, P. Kallweit, N.K. Mitra, Wing-type vortex generators for heat
transfer enhancement, in: Proc. Eighth Int. Heat Transfer Conference, vol. 6,
1986, pp. 2909e2913.
[6] S. Tiggelbeck, N.K. Mitra, M. Fiebig, Comparison of wing-type vortex generators for heat transfer enhancement in channel ows, J. Heat Transfer 166
(1994) 880e885.
[7] S. Tiggelbeck, N.K. Mitra, M. Fiebig, Experimental investigation of heat transfer
enhancement and ow losses in a channel with double rows of longitudinal
vortex generators, Int. J. Heat Mass Transfer 36 (1993) 2327e2337.
[8] G. Biswas, N.K. Mitra, M. Fiebig, Heat transfer enhancement in n-tube heat
exchangers by winglet type vortex generators, Int. J. Heat Mass Transfer 37
(1994) 283e291.
[9] M. Fiebig, Vortices generators and heat transfer, Trans. IChemE 76 (1998)
108e123.
[10] M. Fiebig, A. Valencia, N.K. Mitra, Wing-type vortex generators for n-andtube heat exchangers, Exp. Therm. Fluid Sci. 7 (1993) 287e295.
[11] C.C. Wang, J. Lo, Y.T. Lin, M.S. Liu, Flow visualization of wavy-Type vortex
generator having inline n-tube arrangement, Int. J. Heat Mass Transfer 45
(2001) 1933e1944.
[12] H. Huisseune, C. T'Joen, P.D. Jaeger, B. Ameel, S.D. Schampheleire, M.D. Paepe,
Performance enhancement of a louvered n heat exchanger by using delta
winglet vortex generators, Int. J. Heat Mass Transfer 56 (2013) 475e487.
[13] H. Huisseune, C. T'Joen, P.D. Jaeger, B. Ameel, J. Demuynck, M.D. Paepe,
Numerical study of ow deection and horseshoe vortices in a louvered
n round tube heat exchanger, J. Heat Transfer 134 (2012) 0918011e091801-11.
[14] Y.L. He, H. Han, W.Q. Tao, Y.W. Zhang, Numerical study of heat-transfer
enhancement by punched winglet-type vortex generator arrays in n-andtube heat exchangers, Int. J. Heat Mass Transfer 55 (2012) 5449e5458.
[15] J.F. Fan, Y.L. He, W.Q. Tao, Application of combined enhanced techniques for
design of highly efcient air heat transfer surface, Heat Transfer Eng. 33 (1)
(2012) 52e62.
[16] J.M. Wu, W.Q. Tao, Impact of delta winglet vortex generators on the performance of a novel n-tube surfaces with two rows of tubes in different diameters, Energy Convers. Manag. 52 (2011) 2895e2901.
[17] J. Li, S. Wang, J. Chen, Y.G. Lei, Numerical study on a slit n-and-tube heat
exchanger with longitudinal vortex generators, Int. J. Heat Mass Transfer 54
(2011) 1743e1751.
[18] P. Chu, Y.L. He, W.Q. Tao, Three-dimensional numerical study of ow and heat
transfer enhancement using vortex generators in n-and-tube heat exchangers, J. Heat Transfer 131 (2009) 091903-1e091903-9.
[19] J. He, L. Liu, A.M. Jacobi, Air-side heat-transfer enhancement by a new winglettype vortex generator array in a plain-n round tube heat exchanger, J. Heat
Transfer 132 (2010) 071801-1e071801-9.
[20] C.C. Wang, Y.J. Chang, C.S. Wei, B.C. Yang, A comparative study of the airside
performance of winglet vortex generator and wavy n-and-tube heat exchangers, ASHRAE Trans. 110 (2004) 53e57.
[21] C.C. Wang, R.L. Webb, K.U. Chi, Data reduction of air-side performance of nand-tube heat exchangers, Exp. Therm. Fluid Sci. 21 (2000) 228e236.
[22] ASHRAE Handbook Fundamental, SI ed., American Society of Heating,
Refrigerating and air-conditioning Engineers, Inc., Atlanta, 1993, pp. 14e15
(Chap. 13).
[23] ASHRAE Standard 41.2-1987, Standard Methods for Laboratory Air-ow
Measurement, American Society of Heating, Refrigerating and AirConditioning Engineers, Inc., Atlanta, 1987.
[24] W.M. Kays, A.L. London, Compact Heat Exchangers, third ed., McGraw-Hill,
New York, 1984.
[25] R.J. Moffat, Describing the uncertainties in experimental results, Exp. Therm.
Fluid Sci. 1 (1988) 3e17.
[26] E.M. Saboya, E.M. Sparrow, Transfer characteristics of two-row plate n and
tube heat exchanger congurations, Int. J. Heat Mass Transfer 19 (1976)
41e49.
[27] K. Torikoshi, G. Xi, Y. Nakazawa, H. Asano, Flow and heat transfer performance
of a plate-n and tube heat exchanger (1st report: effect of n pitch), in: 10th
Int. Heat Transfer Conf, 1994, pp. 411e416 paper 9-HE-16.
[28] L.Z. Zhang, W.C. Zhong, J.M. Chen, J.R. Zhou, Fluid ow and heat transfer in
plate n-and-tube heat exchangers in a transitional ow regime, Numer. Heat
Transfer Part A 60 (2011) 766e784.
[29] K. Torikoshi, G. Xi, A numerical study of ow and thermal elds in nned tube
heat exchangers (effect of the tube diameter), in: ASME HTD, vol. 317-1, 1995,
pp. 453e458.
[30] C.C. Wang, C.J. Lee, C.T. Chang, Y.J. Chang, Some aspects of n-and-tube heat
exchangers: with and without louver ns, J. Enhanc. Heat Transfer 6 (1999)
357e368.
[31] C.C. Wang, K.U. Chi, Heat transfer and friction characteristics of plain n-andtube heat exchangers: part 1: new experimental data, Int. J. Heat Mass
Transfer 43 (2000) 2681e2691.
Please cite this article in press as: C.-C. Wang, et al., Investigation of the semi-dimple vortex generator applicable to n-and-tube heat
exchangers, Applied Thermal Engineering (2014), http://dx.doi.org/10.1016/j.applthermaleng.2014.09.054