1/2003 GB
Description
Construction
All the components are brought together
in a single unit. The burner motors axis is
at right angles to the direction of the air
flow and drives the fan wheels axle. All the
fuel and air regulating components are
clearly arranged and easily accessible.
The burners can be hinged open to the
left or right which facilitates work on the
combustion head, diffuser and ignition
electrodes.
Fuels
The gas burners have been tested for the
following gases in accordance with
EN 437 / DVGW Worksheet G 260/l:
Natural Gas E (formerly designated
Natural Gas H) and LL (formerly
designated Natural Gas L).
Application
The burners can be used with heat
exchangers such as hot water boilers,
steam boilers and air heaters, and for
certain process applications. As the
2
Regulation
Dependent on fuel, burner size and
requirements, the regulation of air and
fuel is by:
Flame monitoring
The burner controller, which is either built
into the control panel or onto the burner,
takes care of the automatic sequence of
operations. With its flame sensor it
monitors the flame by means of the
ionisation principle.
Valve trains
To comply with EN 676 burners must be
equipped with two solenoid valves.
Weishaupt gas and dual fuel burners are
equipped with two Class A solenoid
valves (DMV) as standard. Furthermore,
Weishaupt recommends the use of valve
proving. The use of valve proving is
compulsory for ratings above 1200 kW.
This, as well as other gas side accessories
such as gas filters and gas pressure
regulators, can be found in the List of
Accessories.
Installation sites
In standard execution (materials, construction, protection), the burners are
suitable for use indoors at temperatures
between -10C and +40C.
G1/LN
55300
G3/LN
80550
G5/LN
200900
G7/LN
2501,550
500
1,000
1,500
[mg/kWh]
110
100
90
80
70
60
50
40
30
20
10
NOx
CO
mbar
mbar
Burner type
Combustion head type
Rating kW
G1/1-E, version LN
G1/3a-105 x 36
55 300
10
Rating with
combust. head
Open
Closed
8
6
8
6
4
-2
-2
0
mbar
50
100
Burner type
Combustion head type
Rating kW
150
200
250
G3/1-E, version LN
G3/3a-120 x 41
80 550
kW
mbar
10
10
-2
mbar
100
200
Burner type
Combustion head type
Rating kW
300
400
500
kW
mbar
10
-2
-2
0
mbar
200
400
Burner type
Combustion head type
Rating kW
600
800
1000
G7/1-D, version LN
G7/3a-190 x 60
250 1550
kW
10
-2
-2
0
400
800
1200
1600
2000
kW
100
200
Burner type
Combustion head type
Rating kW
mbar
10
kW
100
Burner type
Combustion head type
Rating kW
10
kW
50
150
200
250
-2
0
kW
10
kW
Burner type
Combustion head type
Rating kW
200
400
Burner type
Combustion head type
Rating kW
400
800
300
400
500
600
800
1000
1200
1600
2000
5
Burner selection
Valve train
R
DN
Version with
DMV valves
Order No.
Size 1
Type G1/1-E, version ZE-LN
3/4
251 103 01
1
251 113 01
1 1/2
251 113 02
2
251 113 03
40
251 123 01
50
251 133 01
65
251 143 01
80
251 153 01
Type G1/1-E, version ZD-LN
3/4
251 104 01
1
251 114 01
1 1/2
251 114 02
2
251 114 03
40
251 124 01
50
251 134 01
65
251 144 01
80
251 154 01
Type G1/1-E, version ZME-LN
3/4
251 106 01
1
251 116 01
1 1/2
251 116 04
2
251 116 05
40
251 126 01
50
251 136 01
65
251 146 01
80
251 156 01
Type G1/1-E, version ZMD-LN
3/4
251 107 01
1
251 117 01
1 1/2
251 117 04
2
251 117 05
40
251 127 01
50
251 137 01
65
251 147 01
80
251 157 01
Type G1/1-E, version ZMAE-LN
1
251 116 03
1 1/2
251 116 06
2
251 116 07
40
251 126 03
50
251 136 03
Type G1/1-E, version ZMAD-LN
1
251 117 03
1 1/2
251 117 06
2
251 117 07
40
251 127 03
50
251 137 03
Size 3
Type G3/1-E, version ZE-LN
3/4
251 303 01
1
251 313 01
1 1/2
251 313 02
2
251 313 03
40
251 323 01
50
251 333 01
65
251 343 01
80
251 353 01
Valve train
R
DN
Version with
DMV valves
Order No.
Size 5
Type G5/1-D, version ZD-LN
3/4
151 504 01
1
151 514 01
1 1/2
151 514 02
2
151 514 03
40
151 524 01
50
151 534 01
65
151 544 01
80
151 554 01
100
151 564 01
Type G5/1-D, version ZMD-LN
3/4
151 507 01
1
151 517 01
1 1/2
151 517 04
2
151 517 05
40
151 527 01
50
151 537 01
65
151 547 01
80
151 557 01
100
151 567 01
Armaturen
R
DN
Version with
DMV valves
Order No.
Size 7
Type G7/1-D, version ZD-LN
1
151 714 01
1 1/2
151 714 02
2
151 714 03
40
151 724 01
50
151 734 01
65
151 744 01
80
151 754 01
100
151 764 01
Type G7/1-D, version ZMD-LN
3/4
151 707 01
1
151 717 01
1 1/2
151 717 02
2
151 717 03
40
151 727 01
50
151 737 01
65
151 747 01
80
151 757 01
100
151 767 01
Type G7/1-D, version ZMAD-LN
1
151 717 04
1 1/2
151 717 05
2
151 717 06
40
151 727 03
50
151 737 03
65
151 747 03
80
151 757 03
100
151 767 03
Note
If sliding two stage (ZM) burners are to be
used as modulating burners, this must be
advised when ordering. The two versions
have differing servomotor runtimes for the
compound regulation.
10
6
200
26 14 12 11 11 10
16
9
220
30 16 13 12 11 11
18 10
250
36 19 14 13 13 12
22 12
280
44 22 16 15 14 14
26 13
300
49 24 17 16 15 14
30 14
47.84 kWh/mn3
6
5
8
8
9
9
10 10
12 12
13 12
Burner
rating
[kW]
9
8
200
14 12 11 11 10
13 11
220
16 13 12 11 11
15 12
250
19 14 13 13 12
17 14
280
22 16 15 14 14
19 16
300
24 17 16 15 14
21 17
47.84 kWh/mn3
8
11
12
13
15
15
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
150
21 12
9
9
9
8
12
7
6
6
200
33 17 13 12 11 11
20 10
9
9
220
39 20 14 13 13 12
24 12 10 10
250
48 23 17 15 14 14
29 14 12 12
280
59 27 19 17 16 15
35 16 14 13
300
66 30 20 18 17 16
39 17 15 15
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
150
12
9
9
9
8
11
9
9
200
17 13 12 11 11
15 13 12
220
20 14 13 13 12
17 14 13
250
23 17 15 14 14
20 16 15
280
27 19 17 16 15
23 18 17
300
30 20 18 17 16
26 20 18
Burner
rating
[kW]
47.84 kWh/mn3
8
8
11 11
12 12
13 13
14 14
16 15
Burner
rating
[kW]
47.84 kWh/mn3
11 10
14 13
15 14
17 15
18 16
19 16
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
300
62 26 16 13 12 12
35 13 10 10
350
83 33 19 16 14 14
47 17 13 12
400
105 41 22 18 16 15
60 20 15 14
450
130 48 25 20 17 16
73 24 16 16
500
158 57 28 22 19 17
88 27 18 17
550
188 66 31 24 20 18
104 30 19 18
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
300
21 16 13 12 12
17 15 13 12
350
26 19 16 14 14
21 18 16 14
400
32 22 18 16 15
25 21 18 16
450
37 25 20 17 16
28 24 20 17
500
43 28 22 19 17
32 27 21 18
550
49 31 24 20 18
36 30 23 19
Burner
rating
[kW]
38
900
109 46 31 23 20 19
45
Burner
rating
[kW]
47.84 kWh/mn3
9
9
8
11 10
9
13 12 11
15 14 12
18 17 14
22 20 16
25 23 18
7
9
10
11
13
15
16
47.84 kWh/mn3
12 10 10
14 12 11
16 13 13
18 15 14
22 17 16
25 19 18
29 22 19
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
450
125 43 20 15 12 11 10
68 19 11 10
9
500
154 52 24 17 14 12 12
84 22 13 12 10
550
185 62 28 20 16 14 13
101 27 16 14 12
600
219 73 32 23 17 16 15
119 31 18 16 14
700
295 96 41 27 20 18 17
40 22 20 16
800
123 50 33 24 20 19
50 27 24 19
900
152 61 39 27 23 21
61 32 28 21
8
9
11
12
14
17
19
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
450
30 16 15 12 11
21 15 14 12 11
500
39 19 17 14 12
24 17 17 13 12
550
42 22 20 16 14
29 20 19 15 14
600
49 25 23 17 16
33 22 22 17 15
700
63 30 27 20 18
41 27 26 20 17
800
80 36 33 24 20
51 32 31 22 20
900
98 43 39 27 23
62 38 37 26 22
47.84 kWh/mn3
7
6
6
11
9
9
14 12 12
18 16 15
25 22 21
29 24 23
31 26 24
Burner
rating
[kW]
47.84 kWh/mn3
10
9
8
14 12 11
18 15 15
22 19 18
30 26 24
34 28 26
37 30 27
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
700
90 38 24 17 14 13
33 19 17 13 11 10
800
116 48 31 21 18 17
43 25 22 16 14 14
900
146 60 38 26 22 20
55 31 27 20 18 17
1000
179 73 46 31 26 23
67 38 33 25 21 20
1200
255 102 63 41 34 30
94 52 45 33 28 27
1400
131 77 48 37 33
120 64 55 38 31 29
1550
154 89 53 40 35
73 62 41 33 31
Natural gas LL, Hi = 31.79 MJ/mn3 (8.83 kWh/mn3), d = 0.641, WI = 39.67 kWh/mn3
700
57 24 21 17 14 13
35 21 20 16 14 13
800
74 30 27 21 18 17
45 27 25 20 17 16
900
92 37 33 26 22 20
56 33 31 25 21 20
1000
113 45 39 31 26 23
68 39 37 29 25 23
1200
159 61 53 41 34 30
94 53 50 38 32 30
1400
208 75 64 48 37 33
120 64 59 44 36 32
1550
249 87 73 53 40 35
72 67 48 38 34
* The figures given for size DN40 also apply to 1 1/2 and those for
DN50 to 2 valve trains.
Special equipment
Sizes 1 to 3
No. Description
G1-LN
Order No.
G3-LN
Order No.
standard
standard
210 000 67
210 000 67
250 002 83
250 002 84
250 002 85
250 002 86
250 002 87
250 002 88
Integral switchgear
G, version ZE
G, version ZD
250 000 02
250 000 04
250 000 06
250 000 08
G, version ZME
G, version ZMD
250 001 31
250 001 32
250 001 29
250 001 30
250 002 95
250 002 95
110 002 86
110 003 03
110 002 86
110 003 03
Burner controller
250 000 81
250 000 81
250 000 54
250 000 54
No. Description
G5-LN
Order No.
G7-LN
Order No.
standard
standard
110 001 05
110 001 06
150 012 53
150 012 54
150 012 55
150 012 78
150 012 79
150 012 80
Integral switchgear
G, version ZE
G, version ZD
150 006 54
150 006 56
G, version ZME
G, version ZMD
150 010 22
150 010 93
Sizes 5 to 7
150 012 63
150 012 63
110 002 86
110 003 03
110 002 86
110 003 03
Burner controller
250 000 81
250 000 81
150 010 07
150 010 07
Technical data
Product Ident. Nos.
Description
for burner
G1 . . LN
G3 . . LN
G5 . . LN
G7 . . LN
Type
kW
A
A
1/min
F
ECK07-2
0.25
2.3
10
2850
16
ECK08/90-2
0.76
6
16
2850
25
Type
kW
A
A
1/min
DK07-2
0.76
3.6/2.1
16
2820
DK07/2
0.76
3.6/2.1
16
2820
DK08/90-2
1.4
6.3/3.5
16
2820
D112/110-2/1
3.0
6.0
16
2900
Fan wheel
Ignition unit
Type
galvanised
W-ZG 02/1
galvanised
W-ZG 02/1
galvanised
W-ZG 02/1
galvanised
W-ZG 02/1
Type
LFL 1.322
LFL 1.322
LFL 1.322
LFL 1.322
Type
Type
Type
-w- 1055/80
-w- 1055/80
-w- 1055/80
-w- 1055/80
SQM 10.15562 SQM 10.15562 SQM 10.15562 SQM 10.15562
SQM 10.16562 SQM 10.16562 SQM 10.16562 SQM 10.16562
Servomotor
single and sliding two stage Z
sliding two stage ZM
modulating burners
(run time 8 s)
(run time 20 s)
(run time 42 s)
Weight
Gas burner (without valve train)
kg (approx.)
39
43
55
76
Standard burner motor version: Isolation Class Btrop., type of protection IP44
Burner type
10
G1/1-E
G3/1-E
CE-0085AP 0519
CE-0085AP 0522
G5/1-D
G7/1-D
CE-0085AP 0525
CE-0085AP 0387
The burner types shown are approved for use with Natural Gas E
(formerly Natural Gas H) and Natural Gas LL (formerly Natural
Gas L).
Included in delivery
Valve train layout
Burner type
Number of solenoid valves
G1 to 3
version LN
2
G5 to 7
version LN
2
Legend
1 Isolating cock *
2 Gas filter *
3 Governor (LP) or (HP) *
3a Governor (HP only) *
3b Governor (LP) *
4 Gas pressure switch, min.
4a Gas pressure switch, max. (TRD) *
5 Double solenoid valve
6 Gas butterfly valve
7 Gas pressure gauge and cock *
8 VPS Valve proving *
9 Gas burner
* not included in burner price
11
Dimensions
Sizes 1 and 3
Sizes 5 and 7
Drilling
dimensions of the
burner plate
Size
Dimensions in mm
l1
l2
l3
l4
l5
l6
l7
l8
Drilling
dimensions of the
burner plate
l9
l9
l10
l10
b1
b1
b2
b3
685
168
144
168
35
88
312
342
110
120
543
653
501
275
805
188
147
188
28
98
392
382
110
120
570
680
529
295
868
200
197
208
42
108
238
451
421
110
120
275
390
275
305
965
225
277
228
52
118
251
514
484
110
120
305
415
326
330
d7
h1
h2
h3
h4
h5
d1
d2
d3
d4
d5
d6
r1
r2
388
290
150
175
130
195
129
DN25
127
M8
160-170 135
550
590
280
430
325
170
175
140
220
154
DN40
160
M10
186
165
650
670
312
200
494
373
220
195
162
260
195
DN50
200
M10
235
210
680
725
355
229
560
415
245
195
182
330
235
DN65
250
M12
298
270
720
800
b4
1
248
3
5
7
b5