Installation manual
Doc. TR240709
Ed. 0.3 English 20 June 2008

MMPV Installation manual

IMPORTANT

CMZ Sistemi Elettronici reserves the right to make changes to the products described in this
manual at any time without notice.

The use of this manual is limited to CMZ Sistemi Elettronici customers. CMZ Sistemi Elettronici
guarantees the updating of technical information at the date of issue.

This manual is to be used under your own responsibility. Pay attention in the implementation of
certain functions explained in this manual in order to avoid damage to people and machinery.

CMZ Sistemi Elettronici gives no guarantee as far as imperfections, incompleteness and


operating difficulties are concerned.

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV035 - MMPV037 - MMPV057 - MMPV058


MMPV080 - MMPV084 - MMPV104 - MMPV121
MMPL035 - MMPL037 - MMPL057
Installation manual

A part from the basic functions other HMIs may have, it supports most PLC, inverter and
temperature controller drivers on the market. The ultimate patent front panel design inspired
customers to make their own HMI membrane styles. In addition to completely communication
interfaces, flexible hardware design enables Ethernet TCP/IP operation. The modernistic
outward, high brightness LCD with considerable memory let MMPV wins good reputations from
users applying HMI in factory automation, wise buildings and special tool machines.

MMPV series Touch Panel, such as MMPV080-VNT/ MMPV084-TNT/ MMPV104-VNT/


MMPV121-TNT, are expert HMIs with high functions and reasonable price answer to the needs
for most of the automation equipments and systems. High coordination screen with plentiful
colors relieve high speed and high quality. The industrial standard design let MMPV products
even meets harsh environment can still work for long and steady.

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV035 Specifications
Items
Display Type

MMPV035-TST

MMPV035-TNT

Color mode TFT LCD,


256 colors

Color mode TFT LCD,


256 colors

Display Size

3.5" (diagonal)

Number of Pixels
Display Adjustment

320X240
Contrast adjustable with VR from the rear side

Back Light
Touch Screen
Switch Key

LED; Life time is 100,000 hours


Yes

Yes

Input Power

24VDC10%; Isolation; Under 5W

CPU

RISC ARM 32Bit CPU

Flash Memory

4M Bytes

4M Bytes

System working Memory

1M Bytes

2M Bytes

Battery Backed Memory

128K Bytes(Standard) ~1M Bytes

Communication Ports

COM1/9pin Female: RS232/RS422/RS485;


COM2; 4pin Plug Connector RS422/RS485

Ethernet Port

Yes

Extension Bus Port

Front Panel Seal

IP65 / NEMA 4

Operating Temperature

0~50C

Storage Temperature

-20~60C

Ambient Humidity
Vibration Endurance
Shock Endurance

20-90% RH (non-condensing)
0.5mm displacement, 10-55Hz, 30Min. per X, Y, and Z-axis directions
10G, 11ms three times in each direction of X, Y, and Z axes

RFI testing

FCC Part15 Class A

Radiated Disturbance Test

EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test


EMC Test Report
Net Weight
Cooling

EN61000-4-5/1995
EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115
0.3Kg

0.3Kg
Natural cooling

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV037 Specifications
Items

MMPV037-LSK

MMPV037-LST

MMPV037-LNT

Display Type

Monochrome blue mode STN LCD, 16 gray levels

Display Size

3.7" (diagonal)

Number of Pixels

160x80

Display Adjustment

Contrast adjustable with VR from the rear side

Back Light
Touch Screen
Switch Key

LED; Life time is 50,000 hours


X

Yes

Yes

Number of switches are 22


keys

Input Power

24VDC10%; Isolation; Under 5W

CPU

RISC ARM 32Bit CPU

Flash Memory

1M Bytes

2M Bytes

System working Memory

256K Bytes

512K Bytes

Battery Backed Memory

Optional (from 128K Bytes~1M Bytes)

128K Bytes (Standard)


~1M Bytes
COM1/9pin Female: RS232/RS422/RS485;
COM2; 4pin Plug Connector RS422/RS485

Communication Ports
Ethernet Port
Extension Bus Port

X
Profibus (Options)

Front Panel Seal

0~50C

Storage Temperature

-20~60C

Ambient Humidity
Shock Endurance

Yes

IP65 / NEMA 4

Operating Temperature

Vibration Endurance

20-90% RH (non-condensing)
0.5mm displacement, 10-55Hz, 30Min. per X, Y, and Z-axis directions
10G, 11ms three times in each direction of X, Y, and Z axes

RFI testing

FCC Part15 Class A

Radiated Disturbance Test

EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test

EN61000-4-5/1995

EMC Test Report

EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115

Net Weight

0.30 Kg

Cooling

Doc TR240709 Ed.0.3 20 June 2008

0.32

0.32

Natural cooling

MMPV Installation manual

MMPV057 Specifications
Items

MMPV057-LST

MMPV057-BST

MMPV057-TST

Display Type

Monochrome blue mode STN LCD,


16 gray levels

Color mode TFT LCD,


256 colors

Display Size

5.7" (diagonal)

5.6" (diagonal)

320x240

320x234

Number of Pixels
Display Adjustment
Back Light

Touch Screen

Input Power
CPU

Contrast adjustable from touch screen


LED; Life time is
50,000 hours

CCFT; Life time is 20,000 hours under 25C and 85%RH


humidity

Analog resistive type; Max. Number of switches are 40x30


Chemically strengthened glass backing panel;
Over 1 million point activations;
Hard coat is resistant to most solvents and chemicals
24VDC10%; Isolation; Under 10W
RISC ARM 32Bit CPU

Flash Memory

4M Bytes

System working Memory

1M Bytes

Battery Backed Memory

128K(Standard)~1M Bytes

Communication Ports
ProfiBus Port
Front Panel Seal
Operating Temperature
Storage Temperature
Ambient Humidity
Vibration Endurance
Shock Endurance
RFI testing
Radiated Disturbance Test

COM1/9pin: RS232/RS422/RS485
COM2/9pin: RS232 .
COM2/Terminal 4Pin : RS422/RS485 .
Optional with extension card
IP65 / NEMA 4
0~50C
-20~60C
20-90% RH (non-condensing)
0.5mm displacement, 10-55Hz, 2hours per X, Y, and Z-axis directions
10G, 11ms three times in each direction of X, Y, and Z axes
FCC Part15 Class A
EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test


EMC Test Report
Net Weight
Cooling

EN61000-4-5/1995
EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115
0.85 Kg
Natural cooling

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV058 Specifications
Items

MMPV058-TST

MMPV058-TNT

Display Type

Color mode TFT LCD,


256 colors

Display Size

5.7" (diagonal)

Number of Pixels
Display Adjustment

320x240
Contrast adjustable from touch screen

Back Light

Touch Screen

Input Power
CPU

LED; Life time is 50,000 hours


Analog resistive type; Max. Number of switches are 40x30
Chemically strengthened glass backing panel;
Over 1 million point activations;
Hard coat is resistant to most solvents and chemicals
24VDC10%; Isolation; Under 10W
RISC ARM 32Bit CPU

Flash Memory
System working Memory
Battery Backed Memory
Communication Ports
ProfiBus Port
Front Panel Seal
Operating Temperature
Storage Temperature
Ambient Humidity
Vibration Endurance
Shock Endurance
RFI testing
Radiated Disturbance Test

4M Bytes
1M Bytes

2M Bytes
128K(Standard)~1M Bytes

COM1/9pin: RS232/RS422/RS485 .
COM2/9pin: RS232
.
COM2/Terminal 4Pin : RS422/RS485
Optional with extension card
IP65 / NEMA 4
0~50C
-20~60C
20-90% RH (non-condensing)
0.5mm displacement, 10-55Hz, 2hours per X, Y, and Z-axis directions
10G, 11ms three times in each direction of X, Y, and Z axes
FCC Part15 Class A
EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test


EMC Test Report
Net Weight
Cooling

Doc TR240709 Ed.0.3 20 June 2008

EN61000-4-5/1995
EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115
0.85 Kg
Natural cooling

MMPV Installation manual

MMPL035 - MMPL037 - MMPL057 Specifications


Items

MMPL035-TST MMPL037-LST MMPL057-LST MMPL057-TST


Monochrome blue mode STN LCD,
16 gray levels

Color mode TFT LCD,


256 colors

Display Type

Color mode TFT LCD,


256 colors

Display Size

3.5" (diagonal)

3.7" (diagonal)

5.7" (diagonal)

320x240

160x80

320x240

Number of Pixels
Display Adjustment

Contrast adjustable with VR from the rear side

Back Light
Touch Screen

LED; Life time is 50,000 hours


Yes

Yes

Yes

3.5" Touch Panel

3.7" Touch Panel

5.7" Touch Panel

Input Power

24VDC10%; Isolation; Under 5W

CPU
Flash Memory
System working Memory

RISC ARM 32Bit CPU


2M Bytes

1M Bytes

2M Bytes

512K Bytes

256K Bytes

512K Bytes

Battery Backed Memory

x
COM1/9pin Female : RS232;
COM2; 4pin Terminal : RS422/RS485

Communication Ports
Real Time Clock
Extension Bus Port

X(Optional)

X(Optional)

Front Panel Seal

0~50C

Storage Temperature

-20~60C

Ambient Humidity

20-90% RH (non-condensing)
0.5mm displacement, 10-55Hz, 30Min. per X, Y, and Z-axis directions

Shock Endurance

10G, 11ms three times in each direction of X, Y, and Z axes

RFI testing

FCC Part15 Class A

Radiated Disturbance Test

EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test

EN61000-4-5/1995

EMC Test Report


Net Weight
Cooling

X(Optional)

IP65 / NEMA 4

Operating Temperature

Vibration Endurance

X(Optional)

EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115
0.30 Kg

0.32

0.55
Natural cooling

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV080 MMPV084 - MMPV104 - MMPV121 Specifications


Items

MMPV080-VNT MMPV084-TNT MMPV104-VNT MMPV121-TNT


Color mode TFT LCD,
65536 colors

Display Type
Display Size

8.0" (diagonal)

8.4" (diagonal)

10.4" (diagonal)

12.1" (diagonal)

640X480

800X600

640X480

800X600

Number of Pixels
Display Adjustment

Contrast adjustable from touch screen

Back Light Life

CCFT; Life time is 20,000 hours under 25C and 85%RH humidity

Touch Screen

Analog resistive type; Max. Number of switches are 40x30


Chemically strengthened glass backing panel;
Over 1 million point activations;
Hard coat is resistant to most solvents and chemicals

Input Power

24VDC10%; Isolation; Under 30W


RISC ARM9 32 Bit CPU

CPU
Flash Memory

16M Bytes(up to 64M Bytes)

System working Memory

64M Bytes

Battery Backed Memory

128K(Up to 1024K Bytes)


COM1/9pin: RS232/RS422/RS485
COM2/9pin: RS232 .
COM2/Terminal 4Pin : RS422/RS485 .
COM3 RS232
Standard

Communication Ports

Ethernet Port
USB

Host VER:1.1 X2

ProfiBus Port

Optional with extension card

Front Panel Seal

IP65 / NEMA 4

Operating Temperature

0~50C

Storage Temperature

-20~60C
20-90% RH (non-condensing)

Ambient Humidity
Vibration Endurance

0.5mm displacement, 10-55Hz, 2hours per X, Y, and Z-axis directions

Shock Endurance

10G, 11ms three times in each direction of X, Y, and Z axes

RFI testing

FCC Part15 Class A

Radiated Disturbance Test

EN 55022/1998+A1:2000

Electrostatic Discharge Test

EN61000-4-2/1995+A1:1998

RF Electromagnetic Field Test

EN61000-4-3/1996+A1:1998

Surge Immunity Test

EN61000-4-5/1995

EMC Test Report


Net Weight
Cooling

Doc TR240709 Ed.0.3 20 June 2008

EN55022/EN55024/EN61000-3-2,3/EN61000-4-2,3,4,5,6,8,115
0.9Kg

0.9Kg

1.4Kg

2.2Kg

Nature Cooling

MMPV Installation manual

Outlet and Cut out dimensions

The outlet and cut out dimensions of MMPV037- LSK are shown as following.

The outlet and cut out dimensions of MMPL035-TST, MMPL037LST, MMPV037-LST/LNT &
MMPV035-TST/TNT are shown as following.

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

The outlet and cut out dimensions of MMPV057-LST/BST/TST & MMPV058-TST/TNT are
shown as following.

The outlet and cut out dimensions of MMPL057-LST & MMPL057-TST are shown as following.

cut out

Doc TR240709 Ed.0.3 20 June 2008

10

MMPV Installation manual

The outlet and cut out dimensions of MMPV080-VNT - MMPV084-TNT are shown as following.

The outlet and cut out dimensions of MMPV104-VNT is shown as following.

11

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

The outlet and cut out dimensions of MMPV121-TNT is shown as following

Doc TR240709 Ed.0.3 20 June 2008

12

MMPV Installation manual

Installation

Before setup HMI, please cut a hole according to the cutout dimension.
Please see below pictures for your installation reference.

MMPL035-TST
118.5mmx92.5mm
MMPL037-LST
118.5mmx92.5mm

MMPV037-LSK
159.5mmx88.5mm
MMPV037V-LSK
88.5mmx159.5mm

MMPL057-LST
MMPL057-TST
MMPV057-LST
MMPV057-BST
MMPV057-TST
MMPV058-TST/TNT
174.5mmx132.5mm

13

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV080-VNT
221.5mmx164.0mm
MMPV084-TNT
221.5mmx164.0mm

MMPV104-VNT
285.5mmx210.5mm

MMPV121-TNT
301.5mmx228.0mm

Doc TR240709 Ed.0.3 20 June 2008

14

MMPV Installation manual

How to install the HMI?

Put the HMI to the cut hole and sew the lock screws at the four assembling holes on the HMI
with average strength form the rear side. Please do not sew too tight and without equational
strength or it will damage the touch panel.

15

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

The operation of the Key Panel and Touch Panel


MMPV037-LSK, a kind of key panel equipped with a 3.7 160(H) x80(V) resolution LCD display,
a 22 keys membrane, allows users to design various applications. If the touch panel is not fixed
in a right position, set the DIP-SW1, SW2 and SW3 to off to execute the touch panel adjustment.
Please adjust it while needed and do not do the unnecessary adjustment.

The Key panel MMPV037-LSK, is equipped with 22 keys on the membrane. Those keys are
some for numeric entry and some for programmable function keys. There are four function keys,
which can be assigned with various functions in any screen from the software. The other 0-9 ten
keys on the membrane provide numerical entering function. They can also be locked temporarily.
Press ESC and ENT at the same time to lock the ten keys. To unlock, press ESC and ENT
again. For double-keys application, users can operate to press together ESC and F1~F4 to act
as a programmable function keys. The Panel will automatically judge the data format or up/down
settings to complete the data input.
MMPL035-TST - MMPL037-LST - MMPV035-TST - MMPV037-LST, a kind of touch panel
equipped with a 3.5 320(H) x240(V) or 3.7 160(H) x80(V)resolution LCD display, an analog
input touch panel, allows users to design various applications. If the touch panel is not fixed in a
right position, press the touch panel glass while power on and entry BIOS screen. You can select
Touch Panel option to execute the touch panel adjustment function. Please adjust it while
needed and do not do the unnecessary adjustment.
MMPL057-LST - MMPL057-TST - MMPV057 - MMPV058 is a kind of touch panel equipped with
a 5.7, 320(H)x240(V) size LCD display and an analog input touch panel. It accepts to have
maximum 40x30 touch buttons in a screen. The shapes of touch keys should be rectangles with
sizes from minimum 8(H) x8(V) pixels to maximum 320(H) x240(V) pixels.
MMPV080/104 are kinds of touch panel equipped with a VGA, 640(H) x 480(V) size LCD display
and an analog input touch panel. It accepts to have maximum number of switches are 40 x 30
chemically strengthened glass backing pane in a screen. The shapes of touch keys should be
rectangles with sizes from minimum 8(H) x 8(V) pixels to maximum 640(H) x 480(V) pixels.
MMPV084/121 are kinds of touch panel equipped with a Super VGA, 800(H) x 600(V) size LCD
display and an analog input touch panel. It accepts to have maximum number of switches are 40
x 30 chemically strengthened glass backing pane in a screen. The shapes of touch keys should
be rectangles with sizes from minimum 8(H) x 8(V) pixels to maximum 800(H) x 600(V) pixels.
Doc TR240709 Ed.0.3 20 June 2008

16

MMPV Installation manual

FEATURES
1. Portrait 90 display & normal horizontal display supported.
2. 100% quality test and industrial standard coating cases.
3. Adopts 32 bits high function; high reliability and fan-less ARM CPU.
4. Equipped with genuine 65535 true colors, high brightness TFT modules.
5. Provides 3 RS232/422/485 communication ports available in standard models.
6. The standard 128KB backup memory, which can expend up to 1MB, allows storing Alarm,
Recipe and historical data.
7. Supports multi-languages, Windows build-in Fonts, BMP and JPG graphics and GIF
animations.
8. Provides transparent communication for designers to save their program adjustment time.
9. The ultimate patent front panel design inspired customers to make their own HMI membrane
styles.
10. The expansion bus expends various customize devices, such as motion control, temperature
control, communication module and I/O moduleetc.
11. High speed Ethernet port supports upload and download remote communication.
12. Provides accommodative Software, PanelMaster.

Advantage functions
MMPV Series is a compact HMI with BIOS password protected function. This special function
can be used to prevent the inside application data from being stolen or destroyed. The BIOS
password is not set as a default situation.
With BIOS upgrade function, wherever in the world, whenever the HMI needs to be updated new
functions, this function supports upgrading without sending back to the factory.
With serial number in the BIOS as an ID number of the HMI. Supports checking the serial
number from the HMI to assure a complete after service.
The unique two BIOS system patent design. In our past experiences, the HMI will not be able to
run normally or even not be turned on the system due to the unstable electricity during operating.
With the two BIOS system, customers need not send the damaged HMI back to the factory.
Automatically data download and communication port COM1 or COM2 detection. No need to
setup.
With BIOS recovery system while missing password to prevent system blocking due to missing
password.
17

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

DIP Switches setting


MMPV037-LSK - MMPV057 - MMPV058 DIP Switches setting
SW1

System Menu

ON

Not display system menu, go to ON-LINE communication after turns on.

OFF

Display system menu when turns on. Not go to ON-LINE communication.

SW2
ON
OFF

Emergency recovery the HMI BIOS to default value.


Set to default OS version or customized OS version.
Set to default BIOS version B.

SW3

SW4

HMI operation mode (Supports special functions for customized BIOS version)

OFF
ON

OFF
OFF

Reserved
To execute HMI Communication testing program (SW1,2 must set to Off)

OFF

ON

To execute Key adjustment program or Touch adjustment program (SW1,2 must set to Off)

ON

ON

To execute HMI application program

SW5
ON
OFF
SW6
ON
OFF

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

MMPV080 - MMPV084 - MMPV104 - MMPV121 DIP Switches setting


SW1

System Menu

ON

Not dis play s ys tem m enu, go to ON-LINE c omm unic ation after turns on.

OFF

Dis play s ys tem m enu when turns on. Not go to ON-LINE c om m unication.

SW2
ON

Em ergenc y rec overy the H MI BIOS to default value.


Set to default OS vers ion or c us tom ized OS vers ion.

OFF

Set to default BIOS vers ion B.

SW3

SW4

HMI operation mode (Supports special functions for customized BIOS version)

OFF

OFF

Res erved

ON

OFF

To e xec ute H MI Com m unic ation tes ting program (SW 1,2 m us t s et to Off)

OFF

ON

ON

ON

To e xec ute Key adjus tm ent program or Touc h adjus tm ent program (SW 1,2
m us t s et to Off)
To e xec ute H MI applic ation program

SW5
ON
OFF
SW6
ON
OFF

Doc TR240709 Ed.0.3 20 June 2008

Res erved
Res erved
Res erved
E xtens ion Module & Com3 port Selec tion
E xtens ion Module Enable
On Board Com 3 Port enable

18

MMPV Installation manual

***The MMPV037 - MMPV057 - MMPV080 - MMPV084 - MMPV104 - MMPV121 has a BIOS


password recovery system to prevent damage when missing password. When you forget the
password, which has been set to the HMI, this HMI can execute RUN AP/Calibrate operation but
cannot execute BIOS/Download AP/Clear SRAM operations. When the users want to download
new AP without password, please set all DIP switches to off (SW1-6=Off), When turns on HMI
again, the HMI will display the clean all AP and old password screen. After proceeding this
procedure, the HMI can be operated normally again.

For some models of the MMPL037-LSK - MMPL037-LST - MMPV037-LNT - MMPL035-TST MMPV035-TST - MMPV035-TNT there are no dip switch.

19

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

Startup Test

When turns on HMI, it will display self-testing screen. After completed, HMI will show the system
menu.
HMI BIOS B1
CMZ
S/N 037LK2E0601234
Checking ..
BIOS Checksum Error
Parameter Error
RTC Function Error
DIP SW(6.1)=111100
Figure

A.1 - When there are checksum errors, that could be RTC data missing, battery failed or

AP not being well downloaded.

HMI BIOS B1.1


CMZ
S/N 037LK2E0601234
Checking ..
DIP SW(6.1)=111100

Figure

A.2

- The HMI startup self-testing _power on

When

turns on HMI, system will automatically execute hardware testing first to make sure
hardware are normal or not. The result will show on the screen (Figure A-1/A-2). If there are
problems, the HMI will not communicate with P.L.C. normally.
When losing electricity during downloading or the PC breaks off downloading, after restarting the
HMI, it will show Firmware Memory Checksum and Application Memory Checksum error. It
means there is an abnormal downloading. To get a correct self-testing result, please execute a
correct download AP procedure again.

If losing

electricity during downloading or the PC breaks off downloading when upgrading OS, it

will surely cause download failure. If you restart the HMI, it will not display normal screens or
even cannot be turned on. In that case, please set the DIP SW2 to OFF, restart the HMI to get a
default BIOS version B then execute the upgrading OS program to get a correct OS version. Set
the DIP SW2 to ON then the HMI can be turned on normally.

Doc TR240709 Ed.0.3 20 June 2008

20

MMPV Installation manual

Startup Menu

If the DIP SW1 set to off, after self-testing the MMPV037 - MMPV057 will show startup menu as
following figures.
The Startup menu of MMPV037-LSK is shown as below.
Situation 1: When SW2=OFF, it will show the default BIOS Ver. B.

Situation 2: When SW2=ON, it will show the Panel Setup screen or customized Version screen.

The Startup menu of MMPV057 is as below.


Situation 1: When SW2=OFF, it will show the default BIOS Ver. B.

21

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

Situation 2: When SW2=ON, it will show the Panel Setup screen or customized version screen.

The Startup menu of MMPV037-LST MMPLNT.


MMPL037-LST is shown as below.
Situation 1: When power on, the user press touch screen till the screen show BIOS Ver.B

Panel Setup Mode

Run AP Mode

Situation 2: If there is application data in the HMI flash memory, the HMI will show Panel Setup
Mode or Run AP directly while power on.

Doc TR240709 Ed.0.3 20 June 2008

22

MMPV Installation manual

The Startup menu of MMPV035-TST/TNT - MMPL035-TST is shown below.


Situation 1: When power on, the user press touch screen till the screen show below BIOS Ver. B

Panel Setup Mode

Run AP Mode

Situation 2: If there is application data in the HMI flash memory, the HMI will show Panel Setup
Mode or Run AP directly while power on.

System menu

Descriptions

Password

Update OS

To receive new AP OS Ver. from COM Port.

Yes*1

Copy AP

To Copy AP to another HMI from COM1/2.

Yes*1

Clear SRAM

Clear battery backup data memory.

Yes*1

Run AP

Press Run AP or ENT to communicate with P.L.C..

Setting

HMI keys and hardware functions testing.

None

LCD Test

Check HMI LCD Display

None

Exit

Press ESC to return HMI hardware self testing

None

None*2

*1.If sets a BIOS protection password to HMI, then the HMI will request the users to enter BIOS
password.
*2. If sets a login user password in AP, when selects Run AP, it will request the user to enter
BIOS password.
23

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

If the DIP SW1 set to off, after self-testing the MMPV080/084/104/121 will show startup menu as
following figures.
Situation 1: When SW2=OFF, it shows the default startup BIOS.

FigureA-3 Startup BIOS_Default


Situation 2: When SW2=ON, it shows the Panel Setup screen.

FigureA-4 Panel Setup_ Remove the USB Sticker (Horizontal & Vertical)

Doc TR240709 Ed.0.3 20 June 2008

24

MMPV Installation manual

Situation 3 : When SW2=ON and there is an USB sticker insert to rear USB port, it will show the
Panel Setup screen.

FigureA-5 Panel Setup_ Insert the USB Sticker (Horizontal & Vertical)

System menu

Descriptions

Password

Download OS

To receive new OS0 Ver. from COM Port.

Yes*1

Copy to HMI

To Copy AP to another HMI from COM1/2.

Yes*1

Run AP

Press Run AP or ENT to communicate with P.L.C..

Setting

HMI keys and hardware functions testing.

None

LCD Test

Check HMI LCD Display

None

Clock Setting

HMI Time & Date Setting

None

Ethernet Setting

Ethernet IP Address Setting

None

None*2

Memory Checking Check HMI memory size

None

Exit

None

Press ESC to return HMI hardware self testing

*1.If sets a BIOS protection password to HMI, then the HMI will request the users to enter BIOS
password.
*2. If sets a login user password in AP, when selects Run AP, it will request the user to enter
BIOS password.

25

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

Download AP
To download AP to HMI, please make sure the download cable is connected properly. During the
operating or in startup menu the HMI is ready to receive AP data sent by PC automatically. When
download AP the SW2=ON.

FigureA-6 The HMI downloading data from PC screens

FigureA-7 The HMI downloading data from PC screens


1. Connect the PC COM1 or Com2 and HMI with a PC download cable.
HMI Connector PC RS232C
HMI Connector PC Connector
9-pin Female --------- 9-pin Female
9-pin Male ---------- 9-pin Female

RXD 2
TXD 3
SG 5
RTS 7
CTS 8

2
3
5
7
8

RXD
TXD
SG
RTS
CTS

HMI COM2 ------- PC COM

RTX 2
TXD 3
SG 5
RTS 7
CTS 8

2
3
5
7
8

RXD
TDX
SG
RTS
CTS

HMI COM1 --------- PC COM

Serious

Caution: Be sure turn off the power before connecting or it will damage the HMI
communication components.

Doc TR240709 Ed.0.3 20 June 2008

26

MMPV Installation manual

2. The HMI will judge the data correctness during downloading AP.

When the PC sends AP data to HMI, the HMI will show download AP screen and display related
information automatically to receive data. The HMI will show Incorrect Model ! when the Model
No. is not set correctly in the AP data. Please select a correct Model No. from the software then
download it again. If the HMI shows Incorrect User ID Code !!, then the hardware and software
might not fit each other. Please check the brand name of the HMI to make sure you purchased a
right hardware.

COM Ports Define

The communication port COM1 of MMPV037 - MMPV057 - MMPV058 can use as RS232,
RS422 and RS485 while COM2 as RS422 and RS485.
The COM2 of MMPV057 and MMPV058 can use as RS232, RS422 and RS485. Please make
the right connecting cable according to the specifications. About the cable connecting figures of
the HMI to other PLC, please refer to the PLC manuals.

Communication port COM1 in HMI is a DB-9P Female.


COM1 pin definitions
Pin
1
2

Function
RS-422 TX+ and RS-485 +
RS-232 RXD

Pin
6
7

Function
RS-422 TX- and RS-485 RS-232 RTS

RS-232 TXD

RS-232 CTS

RS-422 RX+

RS-422 RX-

DDASSD

RD

COM2 4-pin definitions.


RS422 and RS485

COM2 pin definitions (Only MMPV057 - MMPV058 series support is a DB-9P male)

Pin

Function

Pin

Function

RS-485 +

RS-485 -

RS-232 RXD

RS-232 RTS

RS-232 TXD

RS-232 CTS

Optional 5V output

275

Signal ground

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

COM2 pin definitions


Pin
1
2
3
4
5
6
7
8*
9
10
11
12
13

Function
Chassis ground
RS-232 TXD
RS-232 RXD
RS-232 RTS
RS-232 CTS
(no function)
Signal ground
(no function)
(no function)
(no function)
(no function)
RS-422 CTS+
RS-422 CTS-

Extension Bus Port

Pin
14
15
16
17
18
19
20
21
22
23
24
25*

Function
RS-422 TXD+ and RS-485 +
RS-422 TXD- and RS-485 RS-422 RXD+
RS-422 RXD(no function)
(no function)
(no function)

RS-422 RTS+
RS-422 RTS(no function)

(Its an Optional device) This port can link with other extension modules for

advanced functions.

COM ports define

The communication port COM1 of MMPV080 - MMPV084 - MMPV104 - MMPV121 can use as
RS232, RS422 and RS485. The COM2 of MMPV080 - MMPV084 - MMPV104 - MMPV121 can
use as RS232, RS422 and RS485. Please make the right connecting cable according to the
specifications. About the cable connecting figures of the HMI to other PLC, please refer to the
PLC. manuals.
Communication port COM1 in HMI is a DB-9P female.
COM1 pin definitions
Pin
1

Function
RS-422 TX+ and RS-485 +

Pin
6

Function
RS-422 TX- and RS-485 -

RS-232 RXD

RS-232 RTS

RS-232 TXD

RS-232 CTS

4
5

RS-422 RX+
Signal ground

RS-422 RX-

Doc TR240709 Ed.0.3 20 June 2008

28

MMPV Installation manual

Communication port COM2 in HMI is a DB-9P male.


COM2 pin definitions
Pin

Function

Pin

Function

RS-485 +

RS-485 -

RS-232 RXD

RS-232 RTS

RS-232 TXD

RS-232 CTS

Optional 5V output

4
5

Signal ground

COM2 4-pin definitions.


RS422 and RS485

Communication port COM3 in HMI is a Round-6P female for RS232 use only.

Ethernet TCP/IP RJ45 connection:


(standard EIA568B)

HUB

PV

Connector 1
Pin

29

Connectore 1

Connector 2

White/orange

White/orange

orange

orange

White /green

White / green

Blue

Blue

White /Blue

White /Blue

green

green

White /Brown

White / Brown

Brown

Brown

Connector 2

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

(crossover)

PC

Connector 1

Pin

PV

Connector 2

Connector 1

Connector 2

White/ green

White/ orange

green

orange

White / orange

White / green

Blue

Blue

White /Blue

White /Blue

orange

green

White / Brown

White / Brown

Brown

Brown

Doc TR240709 Ed.0.3 20 June 2008

30

MMPV Installation manual

LCD adjustment and IP address setting


MMPV037-LST - MMPV035-TS(N)T - MMPV057-LST - MMPV058-TS(N)T

To adjust the LCD contrast, adjust the LCD adjusting knob from the MMPV037 rear side. The
MMPV037 is equipped with high luminance LED backlight, so adjusting the LCD brightness is not
necessary.
MMPV057-BST - MMPV057-TST (CCFL B.L.)

To adjust the MMPV057 LCD brightness, (Blue mode STN/Color STN LCD, TFT model can not
be adjusted the brightness), press [General] from MMPV057 Panel Setup screen or press [LCD
Testing] from [Settings] in BIOS B. From [LCD Brightness], press [Increase Brightness] to
increase the brightness, press [Decrease Brightness] to decrease brightness, press [Save
Brightness] to save. Press [OK] to return to system screen.

Figure A-4 MMPV057 Panel Setup screen_ LCD brightness adjustment

31

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

MMPV080 - MMPV084 - MMPV104 - MMPV121

To adjust the LCD brightness, (TFT model can not be adjusted the brightness), press [General]
from MMPV Panel Setup screen or press [LCD Testing] from [Settings] in BIOS B. From [LCD
Brightness], press [Increase Brightness] to increase the brightness, press [Decrease Brightness]
to decrease brightness, press [Save Brightness] to save. Press [OK] to return to system screen.

When you wish to use the Ethernet, please press [General] from MMPV Panel Setup screen and
then you can set the IP Address. You can press the IP Address number and use [+] & [-] button
to increase or decrease the IP Address number.

Figure A-6 Panel Setup screen_ LCD brightness adjustment & IP Address Setting

Doc TR240709 Ed.0.3 20 June 2008

32

MMPV Installation manual

Power and Grounding Specifications

Use

DC24V as MMPV037 power input. The power consumptions are as following table. To

ensure

the

MMPV037

MMPV057

hardware

working

properly,

to

avoid

outside

electromagnetism noise, please ground the power source properly.


Items / Models

MMPV037-LSK

Power consumption
Fuse Rating

Use

MMPV037-LST

MMPV057-BST

MMPV057-TST

24VDC10%; 6W

24VDC10%; 10W

0.5A

0.8A

DC24V as MMPV080 - MMPV084 - MMPV104 - MMPV121 power input. The power

consumptions are as following table. To ensure the MMPVPV037 - MMPV057 hardware working
properly, to avoid outside electromagnetism noise, please ground the power source properly.
Items / Models

MMPV080-VNT

MMPV084-TNT

Power consumption
Fuse Rating

MMPV104-VNT

MMPV121-TNT

24VDC10%; 20W
0.8A

Power grounding caution: The products are all equipped with power terminals and lock
assembling sets. The operating procedure is:

Screw off the power terminal.


Peel the 24V wiring(1.25mm) for 1 cm then plug in the power terminal.
Use line screw driver to screw the power terminal tight.

33

Doc TR240709 Ed.0.3 20 June 2008

MMPV Installation manual

Cautions
If this product is used in a house, radio-wave interference might occur to other devices. In the case that it does
occur, the user is requested to try a variety of remedies to solve the problem.

Power source
 MMPV series product is equipped with DC24V input power. If the supply power is other than DC24V, whatever
less or excess, it will severely damage the HMI. Therefore, check the switching power supply supporting the DC
power regularly.
 To avoid electronic shock, be sure the Power Cable is unplugged from the power outlet when connecting the
cable to the HMI.

Grounding
 From the FG terminal at the rear side of HMI, please make sure the grounding is made exclusively.
 When the FG terminal is connect, be sure the wire is grounded. Without grounding, the operation of HMI may be
severely affected by excess external noise levels and vibrations.
 Use a cable at 2 m (AWG 14) to ground the equipment. Ground resistance must be less than
100(class3).Note that the ground cable must not be connected to the same ground point as the power circuit.

Installation
Mount the HMI from the front of a suitable preserved hole.
 Attached the brackets behind.
 Fasten the screw of the brackets with proper force. Tightening too much may cause damage to the structure of
the unit.
 Input and Output signal lines must be separated from the power cables for operational circuits. Use shielded
cables or it may cause unpredictable problems.
 Do not allow cut wires, filling, or shavings to fall inside a unit or block when drilling holes or connecting
cables/lines.

Environment
 Do not install in areas subject to excessive dust, oily mist, conductive dust, corrosive gas, or flammable gas.
 Do not mount in areas subject to shock or vibration.
 Do not mount in areas subject to high temperature, moisture, or rain.
Indicated loss of life, severe personal injury, or substantial property damage will result if proper
precautions are not taken.

Doc TR240709 Ed.0.3 20 June 2008