ATEX

Instruction Manual

Type 7700E
Electropneumatic positioner
I/P 4000 Converter

Instruction
No. 185977
06/2004

Masoneilan

CONTENTS

Warning ................................................................................................................................................ 3
Instrument operation ............................................................................................................................ 3
1. Numbering system ........................................................................................................................... 4
2. Technical data ................................................................................................................................. 4
2.1. Performances .......................................................................................................................... 4
2.2. Schematic ................................................................................................................................ 4
3. ATEX marking and electrical safety parameters of the intrinsically safe
model I/P 4000 converter ............................................................................................................... 5
4. ATEX marking of the explosionproof model I/P 4000 converter ...................................................... 5
5. Electrical characteristics .................................................................................................................. 5
6. Assembly of a 7700 E positioner on a valve .................................................................................... 6
7. Pneumatic connection of positioner 7700 E .................................................................................... 6
8. Electrical connection, installation and start up of converter I/P 4000 .............................................. 6
8.1. Cable entry and electrical connection ..................................................................................... 7
8.2. Installation and start up ............................................................................................................7
9. Calibration of the 7700 E positioner ................................................................................................ 7
10. Maintenance of the positioner ........................................................................................................8
EC declaration of conformity .................................................................................................................9

2-9

WARNING
BEFORE installing, using or carrying out any maintenance tasks associated with this instrument, READ THE
INSTRUCTIONS CAREFULLY.
These instruments comply with the essential safety requirements of the European Directive ATEX 94/9/CE.
They also comply with the essential safety requirements of the European Directive EMC 89/336/CE (as
amended), for use within an industrial environment.
Products certified as explosionproof equipment or for use in intrinsically safe installations MUST BE:
a) Installed, put into service, used and maintained in compliance with national and local regulations and in
accordance with the recommendations contained in the relevant standards concerning potentially explosive
atmospheres.
b) Used only in situations that comply with the certification conditions shown in this document and after
verification of their compatibility with the zone of intended use and the permitted maximum ambient
temperature.
c) Installed, put into service and maintained by qualified and competent professionals who have undergone
suitable training for instrumentation used in areas with potentially explosive atmospheres.
Under certain operating conditions, the use of damaged instruments could cause a degradation of the
performances of the system which may lead to personal injury or death.
Use only genuine replacement parts, which are provided by the manufacturer, to guarantee that the products
comply with the essential safety requirements of the European Directives mentioned above.

INSTRUMENT OPERATION
The 7700 positioner operation principle is a force-balance mechanism:
) An entry force exerted by the double diaphragm under the effect of a pneumatic signal
pressure.

) An opposite force developed by a feed back spring. The tension of this spring
varies with the displacement of the actuator lever to which it is connected.
The 7700 E electropneumatic positioner is made with a manifold block which is equipped with a converter I/P
(Intensity/Pressure) which generates the pneumatic signal operating on the double diaphragm.

3-9

1. NUMBERING SYSTEM
- Positioner numbering system : 7700 E (I/P 4000 module).
2. TECHNICAL DATA
2.1. Performances

Performances (% of the signal range)

7700E

Started point (close valve)

2.0 %

Hysteresis (mid-stroke)

0.9 %

Input impedance

170 ohms

Maximum service temperature range: (refer to the marking on the apparatus).


Standard Instrument: - 40 C to + 85 C.
Storage temperature: - 55C to + 90C
The components of the I/P Module are protected by a metallic housing.
Housing electrical protection index: IP 66.

2.2. Schematic

REP.

Designation

115

Spring clamp

116

Take up screw

117

Locknut

REP.
C

Designation

REP.

Designation

Cover

Supply

O ring

Safety screw

Output

3. ATEX MARKING OF THE INTRISICALLY SAFE MODEL I/P 4000 CONVERTER


Marking
Masoneilan Dresser Inc
85 Bodwell Street Avon Massachusetts USA.
I/P 4000
SIRA 02 ATEX 2277 X
(Serial number)
The two first digits of the serial number indicate the year of manufacture: 02 = 2002,
03 = 2003, etc ...
Ui = 30 V, Ii = 110 mA, Li = 0, Ci = 0.
IP66

II 1G, 1D (T90C)
EEx ia IIC T6
Pi : 0.33 W
EEx ia IIC T4
Pi : 1.10 W

Ta : - 40 C to + 55 C.
Ta : - 40 C to + 80 C.
4-9

4. ATEX MARKING OF THE EXPLOSIONPROOF MODEL I/P 4000 CONVERTER


Masoneilan Dresser Inc
85 Bodwell Street Avon Massachusetts USA.
I/P 4000
SIRA 02 ATEX 1274
(Serial number)
The two first digits of the serial number indicate the year of manufacture: 02 = 2002,
03 = 2003, etc ...
Pi = 0.8 W
IP66

II 2G, 2D (T90C)
EEx d IIC T6 Ta : - 40C to + 55C
EEx d IIC T5 Ta : - 40C to + 70C
EEx d IIC T4 Ta : - 40C to + 85C

The following:
Do not open when energised.
Do not open when an explosive gas atmosphere is present.
Use cables rated to 5C above ambient.
5. ELECTRICAL CHARACTERISTICS
Input signal: 4-20 mA,
Input impedance: 170 ohms.

6. ASSEMBLY OF A 7700E POSITIONER ON A VALVE

)
)
)

Comply with current national and local regulations for electrical installation work.
Comply with national and local explosive atmosphere regulations.
Before carrying out any work on the device, power off the instrument or make sure that
the local conditions in the potentially explosive atmosphere permit the safe opening of
the cover.
Before switching on or after doing any work on the device, always tighten the cover (C)
with a seal (J) in good condition and put back the safety screw (V).

Note: Before installation, check that the device is undamaged. In the event of damage, inform the
manufacturer whose address is shown on the serial plate;
If the positioner is supplied mounted on a valve, Masoneilan install it, make the pneumatic
connection and configure and calibrate it.
When the positioner is shipped alone, the user is responsible for its installation, electrical and
pneumatic connections and its calibration.
Please refer to instruction manual EH 45004 E for more detail.

5-9

7. PNEUMATIC CONNECTION OF POSITIONER 7700 E

Make sure that the air supply pressure is suitable for the installation and for the instrument.
When using a positioner make sure that the air supply pressure matches the one specified
on the serial plate without exceeding 275 kPa (40 psi).
Minimum diameter of tubing:
- 7700 E : 4 x 6 mm
8. ELECTRICAL CONNECTION, INSTALLATION AND START UP OF CONVERTER I/P 4000.
)
)
)

Comply with current national and local regulations for electrical installation work.
Comply with national and local explosive atmosphere regulations.
Before carrying out any work on the device, power off the instrument or make sure that
the local conditions in the potentially explosive atmosphere permit the safe opening of
the cover.
Before switching on or after doing any work on the device, always tighten the cover (C)
with a seal (J) in good condition and put back the safety screw (V).

Note: Before installation, check that the device is undamaged. In the event of damage, inform
the manufacturer whose address is shown on the serial plate.
8.1. Cable entry and electrical connection
The electrical cable enters the housing of the I/P 4000 via a 1/2 NPT thread fitted a certified
cable gland (type II 2 G/D, EEx d IIB for an explosionproof instrument) and suitable to the
equipment operating zone (IP 6X for zones 20 and 21).
Connect the electrical wires to the terminal strip in accordance with the polarities + and -.
Ground the device using the grounding connections provided inside the housing and on the
outside of the device.

8.2. Installation and start up


Installation
Explosionproof instrument can be installed in flammable gas explosive atmosphere groups
IIA, IIB, IIC for the zones 1 and 2 or in flammable dust explosive atmosphere zones 21 and
22.
Intrisically safe instrument can be installed in flammable gas explosive atmospheres groups IIA,
IIB, IIC for the zones 0, 1 and 2 or in flammable dust explosive atmosphere zones 20, 21 and 22.
Note: Since the apparatus has a multiple certification: ia, d or nL, it is recommended that the type
of installation EEx ia, EEx d EEx nL is identified on or next to the apparatus.

Start up

NOTE: Before start up, proceed, if required, with instrument calibration as per paragraph 9 and/or
ensure that all the safety instructions in the preceding paragraphs have been strictly followed.
) Before switching on or after doing any work on the device, always tighten the cover
(C) with a seal (J) in good condition and put back the safety screw (V).
) Check that the cable gland is certified for the intended use and that the electrical data
are suitable for the operating zone.

6-9

9. CALIBRATION OF THE 7700 E POSITIONER


) Comply with current national and local regulations for electrical installation work.
) Comply with national and local explosive atmosphere regulations.
) Before carrying out any work on the device, power off the instrument or make sure that
the local conditions in the potentially explosive atmosphere permit the safe opening of
the cover.
) Before switching on or after doing any work on the device, always tighten the cover (C)
with a seal (J) in good condition and put back the safety screw (V).
The positioner assembled on valve is factory-calibrated, but if it is necessary to remake the
calibration on the site, it will be carried out by the customer according to the following
general principles
Make the pneumatic and electrical connections, see chapters 7 and 8.
The adjustment of the starting pressure is made by screw (116). Calibrate the electrical
signal corresponding to the closing of the valve (4 or 20 mA). Turn the take-up screw
(116) until the piston rod just begins to move (the plug leaves the contact with the seat
ring).
Tighten the locknut (117).
Note: the I/P 4000 module does not require any adjustment.

10. MAINTENANCE OF THE POSITIONER


) Comply with current national and local regulations for electrical installation work.
) Comply with national and local explosive atmosphere regulations.
) Before carrying out any work on the device, power off the instrument or make sure that
the local conditions in the potentially explosive atmosphere permit the safe opening of
the cover.
) Before switching on or after doing any work on the device, always tighten the cover (C)
with a seal (J) in good condition and put back the safety screw (V).

Make sure that the components of the instrument are not damaged.
In the event of damage replace the defective parts with genuine manufacturer's
replacement part.
Pay particular attention to the following:
General condition of the housing.
Check the cable gland and the electrical connections.
When replacing the I/P module, check the condition of the three 'O' rings (22, 23 24) and
replace them if necessary.
pilotepilote
28

29

30

The user shall clean the equipment regularly to avoid dust accumulating on the walls, for
instruments installed in zones 20, 21 and 22.
Avoid contact of the apparatus with aggressive substances which could damage the
metallic or plastic parts.

7-9

8-9

Usine et Service Clients (Rechanges et Aprs-Vente)


Factory and Customer Service (Spare Parts and After Sales)
DRESSER PRODUITS INDUSTRIELS
3, rue Saint Pierre
BP 87
14110 Cond sur Noireau, France
Tl. +33(0)2 31 59 59 59
Fax +33(0)2 31 59 59 60
www.masoneilan.com

Bureaux de Vente
Sales offices
BELGIUM
Masoneilan Division of Dresser Europe S.A.
281-283, Chausse de Bruxelles
1190 BRUSSELS - Belgium
Telephone : 32-2-344-0970
Fax : 32-2-344-1123
FRANCE
Dresser Produits Industriels
Division Masoneilan
4 Place de Saverne
92971 Paris La Dfense Cedex
France
Telephone : 33-1- 49 04 90 00
Fax : 33-1-49 04 90 10
GERMANY
DRESSER VALVES EUROPE
GmbH, Heiligenstrae 75,
41751 Viersen Germany,
Telephone : 49-2162-81700
Fax : 40-2162 81 70 200
ITALY
MASONEILAN
Division of DRESSER ITALIA S.r.l,
Via Cassano, 77,
80020 Casavatore, Napoli - Italy
Telephone : 39-081-7892-111
Fax : 39-081 7892 208

THE NETHERLANDS
DRESSER VALVES EUROPE

Steenhouwerstraat 11
3194 AG Hoogvliet
Telephone : 31-10-438-4122
Fax : 31-10-438-4443
Mailing adress :
P.O. Box 640
NL-3190 AN Hoogvliet RT
The Netherlands
SPAIN
Masoneilan S.A.
C/Murcia 39 C
08830 Sant Boi de LLobregat
Barcelona - Spain
Telephone : 34-93-6526430
Fax : 34-93 652 6444

UNITED KINGDOM
DI U.K. Limited
East Gillibrands Estate, Skelmersdale
Lancashire WN8 9TU - England
Telephone : 44-1695-52600
Fax : 44-1695-52662
DRESSER FLOW CONTROL, DI U.K. Ltd.
Unit 4, Suite 1.1, Nobel House
Grand Union Office Park, Packet Boat Lane, Uxbridge

Middlesex UB8 2GH - England


Telephone : 44-1895-454900
Fax : 44-1895-454919

You might also like