Professional Documents
Culture Documents
15
71303459
Products
Solutions
Services
Operating Instructions
FieldCare Project Tutorial
Connection of HART, PROFIBUS, FOUNDATION Fieldbus
and Ethernet devices with FieldCare via Modem,
Fieldgate and Remote I/O
Serial number
www.endress.com/deviceviewer
Endress+Hauser
Revision history
Revision history
Product
version
Operating Instructions
changes
Comments
2.09.xx
BA00065S/04/EN/
01.12
2.09.xx
BA00065S/04/EN/
02.13
New
Editorial
Layout
New CD
BA00065S/04/EN/
03.15
Layout
New CMS
New
BA00065S/04/EN/
04.15
New
Chapter 8: HART via RSG45
chapters and Chapter 20: Fieldgate SFG500 and Siemens ET200M/iSP
changes
Chapter 37: PROFIBUS DP via PROFIBUS Modem and
WAGO Remote I/O
Chapter 38: PROFIBUS DP via PROCENTEC ProfiCore
Chapter 39: Plant view
Appendix K: SFG500 error information
2.10.xx
2.10.xx
Endress+Hauser
Table of contents
Table of contents
1
Document information . . . . . . . . . . . . . . 8
1.1
1.2
1.3
1.4
1.5
Document function . . . . . . . . . . . . . . . . . . . . . 8
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2.1 Safety symbols . . . . . . . . . . . . . . . . . . 8
1.2.2 Symbols for certain types of
information . . . . . . . . . . . . . . . . . . . . 8
1.2.3 FieldCare symbols . . . . . . . . . . . . . . . . 9
Text emphasis . . . . . . . . . . . . . . . . . . . . . . . . 10
Acronyms used . . . . . . . . . . . . . . . . . . . . . . . 10
Registered trademarks . . . . . . . . . . . . . . . . . . 10
2.1
2.2
2.3
2.4
Introduction to FieldCare . . . . . . . . . . 13
3.1
3.2
3.3
3.4
General information . . . . . . . . . . . . . . . . . . .
Creating a project . . . . . . . . . . . . . . . . . . . . .
Saving a project . . . . . . . . . . . . . . . . . . . . . . .
Opening a project . . . . . . . . . . . . . . . . . . . . .
4.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Loop power from controller/field
device . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Loop power from a transmitter
power supply . . . . . . . . . . . . . . . . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
4.2
12
12
12
12
13
14
14
15
16
7.1
7.2
7.3
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connection procedure . . . . . . . . . . . . . . . . . . 35
Access to device data . . . . . . . . . . . . . . . . . . . 37
8.1
8.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Connection procedure . . . . . . . . . . . . . . . . . . 38
9.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1 HART multidrop . . . . . . . . . . . . . . . .
9.1.2 HART point-to-point connection . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
9.2
10.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1.1 Point-to-point connection . . . . . . . . .
10.1.2 Multidrop connection . . . . . . . . . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
17
18
11
5.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 Loop power from controller/field
device . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 Loop power from the transmitter
power supply . . . . . . . . . . . . . . . . . . .
Installing the Commubox FXA195 driver . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
21
47
47
47
48
11.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 51
11.2 Connection procedure . . . . . . . . . . . . . . . . . . 51
12
12.1
12.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connection procedure . . . . . . . . . . . . . . . . . . 54
13
21
22
24
24
42
42
42
43
10
10.2
16
5.2
5.3
6.2.2
13.1
13.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Connection procedure . . . . . . . . . . . . . . . . . . 58
6.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.1 Parallel access to HART control loop
with 4 to 20 mA . . . . . . . . . . . . . . . .
6.1.2 Direct/remote access to a HART
monitoring system . . . . . . . . . . . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
6.2.1 Connect to and configure Fieldgate . .
27
14
27
14.1
14.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connection procedure . . . . . . . . . . . . . . . . . . 60
6.2
Endress+Hauser
28
29
29
5
Table of contents
15
23
15.1
15.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Connection procedure . . . . . . . . . . . . . . . . . . 62
23.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 91
23.2 Connection procedure . . . . . . . . . . . . . . . . . . 91
23.3 Connection procedure . . . . . . . . . . . . . . . . . . 93
16
16.1
16.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . .
Commissioning the Fieldgate FXA720 . . . . . .
16.2.1 Basic configuration . . . . . . . . . . . . . .
16.2.2 Connection procedure . . . . . . . . . . . .
Connection procedure . . . . . . . . . . . . . . . . . .
16.3
17
65
66
66
67
70
17.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 73
17.2 Connection procedure . . . . . . . . . . . . . . . . . . 73
18
18.1
18.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connection procedure . . . . . . . . . . . . . . . . . . 77
19
19.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 79
19.2 Connection procedure . . . . . . . . . . . . . . . . . . 79
20
20.1
20.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Connection procedure . . . . . . . . . . . . . . . . . . 82
21
21.1
21.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Connection procedure . . . . . . . . . . . . . . . . . . 85
22
22.1
22.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Connection procedure . . . . . . . . . . . . . . . . . . 88
24
24.1
24.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Connection procedure . . . . . . . . . . . . . . . . . . 95
25
25.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . 98
25.2 Connection procedure . . . . . . . . . . . . . . . . . . 98
26
26.1 Application . . . . . . . . . . . . . . . . . . . . . . . . .
26.2 Commissioning the Field Controller SFC162
26.2.1 Setting up the IP address of the Field
Controller SFC162 . . . . . . . . . . . . . .
26.2.2 Select Visitor mode . . . . . . . . . . . . .
26.2.3 Select the NIC for FieldCare . . . . . . .
26.3 Connection procedure . . . . . . . . . . . . . . . . .
26.4 Upload the project . . . . . . . . . . . . . . . . . . . .
27
28.1
101
103
104
104
106
27.1 Application . . . . . . . . . . . . . . . . . . . . . . . . .
27.2 Commissioning the Field Controller SFC162
27.2.1 Setting up the IP address of the Field
Controller SFC162 . . . . . . . . . . . . . .
27.2.2 Select Visitor mode . . . . . . . . . . . . .
27.2.3 Select the NIC for FieldCare . . . . . . .
27.3 Connection procedure . . . . . . . . . . . . . . . . .
27.3.1 Connection with the Field Controller
SFC162 CommDTM . . . . . . . . . . . . .
27.3.2 Assigning the device tag and/or H1
address . . . . . . . . . . . . . . . . . . . . . .
27.3.3 Creating a FOUNDATION Fieldbus
network . . . . . . . . . . . . . . . . . . . . .
27.3.4 Opening the DeviceDTM . . . . . . . . .
27.4 Upload the project . . . . . . . . . . . . . . . . . . . .
28
101
101
107
108
108
109
110
111
111
112
113
113
114
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . .
28.1.1 Connection to a FOUNDATION
Fieldbus H1 segment . . . . . . . . . . . .
28.1.2 Point-to-point connection in Bench
mode . . . . . . . . . . . . . . . . . . . . . . .
28.2 Connection procedure . . . . . . . . . . . . . . . . .
115
115
115
116
Endress+Hauser
29
29.1
Use cases . . . . . . . . . . . . . . . . . . . . . . . . . . .
29.1.1 Connection to a FOUNDATION
Fieldbus H1 segment . . . . . . . . . . . .
29.1.2 Point-to-point connection in Bench
mode . . . . . . . . . . . . . . . . . . . . . . .
29.2 Connection procedure . . . . . . . . . . . . . . . . .
30
Table of contents
118
118
118
119
31
32
32.1
32.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . 126
Connection procedure . . . . . . . . . . . . . . . . . 126
33
34
38
38.1
38.2
38.3
Application . . . . . . . . . . . . . . . . . . . . . . . . . 142
Installing the FXA291 or TXU10 modem
driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Connection procedure . . . . . . . . . . . . . . . . . 143
39
39.1
40
Appendix . . . . . . . . . . . . . . . . . . . . . . . . 146
40.1
40.2
40.3
40.4
40.5
40.6
40.7
40.8
40.9
40.10
40.11
146
146
147
147
148
149
149
150
151
151
151
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
35
36
36.1
36.2
Application . . . . . . . . . . . . . . . . . . . . . . . . . 136
Connection procedure . . . . . . . . . . . . . . . . . 136
37
Endress+Hauser
Document information
Document information
1.1
Document function
1.2
Symbols used
1.2.1
Safety symbols
Symbol
Meaning
DANGER
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION
NOTICE
1.2.2
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol
Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
Preferred
Indicates procedures, processes or actions that are preferred.
Forbidden
Indicates procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Refers to the corresponding device documentation.
Reference to page
Refers to the corresponding page number.
Reference to graphic
Refers to the corresponding graphic number and page number.
Series of steps
Result of a sequence of actions
Help in the event of a problem
Endress+Hauser
Document information
1.2.3
FieldCare symbols
Previous symbol
Current symbol
Meaning
Start new project.
Open existing project.
Save open project.
Print open project.
Open clipboard.
Show DTM catalog.
Open documentation for selected device or detailed device
information.
Open inventory.
Activate protocol.
Add new device to the network.
Remove device from the network.
Create new network topology using CommDTM and DeviceDTMs.
Compares the network topology in the field with the actual
physical network, and devices are added to the existing network.
Scans the preconfigured topology and shows the report with the
scanned device information.
Indicates whether there is a connection with the device.
Transfer information from the device to FieldCare.
Transfer information from FieldCare to the device.
Device-specific functions for the selected device.
Add plant level.
Add item.
Remove item.
Endress+Hauser
Document information
1.3
Text emphasis
Emphasis
Meaning
Example
Bold
1.4
<DVD-ROM drive>
Acronyms used
Acronyms
Meaning
CDI
COM
Communication Equipment
CommDTM
DTM
DP
Decentralized Peripheral
FDT
FIFO
HART
I/O
Input/Output
IP
Internet Protocol
ISS
LAN
LAS
MUX
Muliplexer
NIC
PA
Process Automation
PC
Personal Computer
PCD
PCI
PCIe
DCS
PROFIBUS
SPL
PLC
TCP
UDP
USB
1.5
Registered trademarks
10
Endress+Hauser
Document information
Endress+Hauser
11
2.1
Physical and electronic access to field devices, networks, computers and systems must be
restricted to an authorized group of individuals. Use a role-based access system. Establish
detailed guidelines and processes to only allow authorized persons access to the PC or
other equipment.
2.2
Designated use
FieldCare is a FDT-based (Field Device Tool) Plant Asset Management tool which,
depending on the version, can be used for device parametrization, instrument
management and condition monitoring. By use of the appropriate Device Type Managers
(DTMs), it is able to operate field devices and system components independent of
communication protocol.
Use a properly configured firewall that blocks all data that do not meet the security
specifications. Deactivate ports that are not in use and use a demilitarized zone or an
intrusion detection system to improve security. Introduce an organized, real-time patch
management process for all products, such as operating systems, Internet browsers,
programs, apps, databases and drivers and run an anti-virus software on the PC. Only use
hardware, software, firmware and other electronic content from trusted sources.
Use a secure password for electronic access to the programs, e.g. for the PC, FieldCare, SQL
server and field devices.
A secure password should:
Be at least 8 characters long
Never contain the user name, personal names or company name
Never contain a whole word
Differ significantly from earlier passwords
Comprise upper-case letters, lower-case letters, a number and a symbol
Be changed regularly
2.3
This tutorial assumes that FieldCare has been correctly installed according to the
instructions in the Getting Started manual, (BA00027S/04/A2), and that the
appropriate DTM catalog has been installed and updated. The manual describes a number
of use cases with various system architectures. It is assumed that all devices and system
components have been installed and connected according to the instructions in the
associated Operating Instructions.
Where equipment is to be configured in explosion hazardous areas, it must be ensured all
components, including computer, have the appropriate certification.
2.4
Technical improvements
Endress+Hauser reserves the right to make technical improvements to the hardware and
software at any time and without prior notification. If such improvements have no effect
on the operation of the equipment, they are not documented. If the improvements affect
operation, a new version of the Operating Instructions is created and issued.
12
Endress+Hauser
Introduction to FieldCare
Introduction to FieldCare
3.1
General information
This manual describes how FieldCare can be used to establish a connection to Modbus,
HART, PROFIBUS, FOUNDATION Fieldbus and EtherNet/IP devices using modems,
gateways and remote I/Os. Each chapter describes a particular use case together with the
associated connection procedure. These Operating Instructions assume that FieldCare and
the appropriate DTM library are installed on your computer.
A number of FieldCare functions are determined by the preferences set within FieldCare in
the dialog Extras Options. In the descriptions which follow, FieldCare has been set up to
prompt for projects on the Project tab.
Under the Scanning tab it is possible to show or hide the Scan Result after the network
has been created. For the procedures described in these Operating Instructions, the option
has been selected which hides the Scan Result if only one device is found.
In general, if only one device is found, FieldCare will automatically make the connection
with the DTM and put it on-line. Where more than one device is found, each DTM must be
connected separately. Depending upon the DTM, a double-click on an unconnected device
will also prompt the connection. If this is not the case, the Connect option must be used.
Endress+Hauser
13
Introduction to FieldCare
3.2
Creating a project
In all cases the first steps in creating a project are identical. The FieldCare window appears
by default, but can be suppressed in the FieldCare window under Extras Options
Project. The FieldCare window is no longer displayed if the None check box is checked.
Creating a project
1.
2.
3.
Click Open.
FieldCare opens a new project with a host PC.
3.3
Saving a project
FieldCare projects are stored in a database but are not accessible as files on the hard
disk. It is possible to access these files by using FieldCare in file mode.
14
Endress+Hauser
Introduction to FieldCare
2.
3.4
Opening a project
2.
Endress+Hauser
15
4.1
Use cases
4.1.1
1
1
2
3
4
5
16
Operation of Commubox FXA191 in a control loop (I/O card active/device passive or vice versa) Via a
resistor 250 (recommended 270 to 330 ) in the control loop
I/O card PLC/DCS passive or active
Commubox FXA191
RS-232C
FieldCare
Field device passive or active
Endress+Hauser
2
1
2
3
4
5
Operation of Commubox FXA191 in a control loop (I/O card active/device passive or vice versa). In the
control loop (loop-resistance 250 )
I/O card PLC/DCS passive or active
Commubox FXA191
RS-232C
FieldCare
Field device passive or active
4.1.2
Endress+Hauser
Operation of Commubox FXA191 in a control loop powered by a transmitter power supply. From the
control room via the communication sockets of the transmitter power supply.
1
2
3
4
5
6
1
2
3
4
5
6
Operation of Commubox FXA191 in a control loop powered by a transmitter power supply. Via the resistor
250 (recommended 270 to 330 ) in the control loop (communication resistor of Commubox FXA191
off)
Active power supply (RNS221, RN221N-A, RN221N-B (Ex), RMA422, RMA42)
Commubox FXA191
RS-232C
FieldCare
I/O card PLC/DCS passive
Field device (passive)
17
5
1
2
3
4
5
6
Operation of Commubox FXA191 in a control loop powered by a transmitter power supply. In the control
loop (loop-resistance 250 )
Active power supply (RNS221, RN221N-A, RN221N-B (Ex), RMA422, RMA42)
Commubox FXA191
RS-232C
FieldCare
I/O card PLC/DCS passive
Field device (passive)
4.2
Connection procedure
Normally, the Commubox FXA191 connects to the COM1 port when it is plugged
into the computer.
It is recommended that only a native serial port be used. The use of USB/Serial
converters is not recommended.
Deactivate the FIFO buffer in the serial port settings.
When working with a modem that is connected to the COM1 port of the computer, you
can also select the HART (Point-to-Point) item in the FieldCare dialog. This
automatically sets up the project and the program scans for a device with the HART
address 0 (standard for non-multidrop mode).
Establishing a connection
18
1.
2.
3.
Endress+Hauser
Endress+Hauser
4.
In the Add New Device dialog, select the HART Communication item and click OK.
The HART CommDTM is added to the network.
5.
6.
Select Configuration.
The HART Communication (Configuration) dialog appears.
7.
8.
Click OK.
FieldCare returns to the Network dialog.
9.
19
The DeviceDTM is added to the network tree and the DTM opens.
11. The DTMs are opened as follows if the Commubox FXA191 is connected to a HART
multidrop network and several devices are found:
In the Network dialog, right-click the device and select Connect or Online
Parameterize.
12. Save the project as described in Chapter 3.3. 14
The project is saved.
If FieldCare cannot find the correct DTM, it will offer alternative versions, graded
according to their suitability in the Scan Result dialog. The user has the choice of
accepting a DTM of less quality, or canceling the scan.
DeviceDTMs for new devices that are not included in the FieldCare HART DTM
library can be downloaded from the device manufacturers website. After
installation, the FieldCare device catalog must be updated. Refer to the FieldCare
on-line help for more information. The scan can then be repeated.
If no new DTM is available, the user can still integrate the device by using the HART
iDTM.
20
Endress+Hauser
5.1
Use cases
5.1.1
6
1
2
3
4
5
Endress+Hauser
Operation of Commubox FXA195 in a control circuit (I/O card active/device passive or vice versa). In the
control circuit (communication resistor of FXA195 on)
I/O card PLC/DCS passive or active
Commubox FXA195
USB
FieldCare
Field device passive or active
21
1
2
3
4
5
22
Operation of Commubox FXA195 in a control circuit (I/O card active/device passive or vice versa). In the
control circuit (loop-resistance 250 )
5.1.2
1
2
3
4
5
6
Operation of Commubox FXA195 in a control circuit (I/O card active/device passive or vice versa). Via a
resistor 250 (recommended 270 to 330 ) in the control circuit (communication resistor of FXA195
off)
1
2
3
4
5
Operation of Commubox FXA195 in a control loop powered by a transmitter power supply. From the
control room via the communication sockets of the transmitter power supply.
Active power supply (RNS221, RN221N-A, RN221N-B (Ex), RMA422, RMA42)
Commubox FXA195
USB
FieldCare
I/O card PLC/DCS passive
Field device (passive)
Endress+Hauser
10
1
2
3
4
5
6
Operation of Commubox FXA195 in a control loop powered by a transmitter power supply. In the control
loop (communication resistor of FXA195 on)
11
1
2
3
4
5
6
Operation of Commubox FXA195 in a control loop powered by a transmitter power supply. Via a resistor
250 (recommended 270 to 330 ) in the control loop (communication resistor of FXA195 off)
12
1
2
3
4
5
6
Endress+Hauser
Operation of Commubox FXA195 in a control loop powered by a transmitter power supply. In the control
loop (loop-resistance 250 )
23
5.2
2.
3.
5.3
Connection procedure
Establishing a connection
24
1.
2.
3.
4.
In the Add New Device dialog, select the HART Communication item and click OK.
The HART CommDTM is added to the network.
Endress+Hauser
Endress+Hauser
5.
6.
Select Configuration.
The HART Communication (Configuration) dialog appears.
7.
8.
Click OK.
FieldCare returns to the Network dialog.
9.
25
The DeviceDTM is added to the network tree and the DTM opens.
11. The DTMs are opened as follows if the Commubox FXA195 is connected to a HART
multidrop network and several devices are found:
In the Network dialog, right-click the device and select Connect or Online
Parameterize.
Save the project as described in Chapter 3.3. 14
If FieldCare cannot find the correct DTM, it will offer alternative versions, graded
according to their suitability in the Scan Result dialog. The user has the choice of
accepting a DTM of less quality, or canceling the scan.
DeviceDTMs for new devices that are not included in the FieldCare HART DTM
library can be downloaded from the device manufacturers website. After
installation, the FieldCare device catalog must be updated. Refer to the FieldCare
on-line help for more information. The scan can then be repeated.
If no new DTM is available, the user can still integrate the device by using the HART
iDTM.
26
Endress+Hauser
6.1
Use cases
To connect to the HART devices in the use cases detailed below, FieldCare requires:
Fieldgate FXA520 CommDTM
HART Multiplexer Master KFD2-HMM-16 (FDT) CommDTM
HART DeviceDTMs
Fieldgate FXA520 must be commissioned and assigned a network IP address before
a connection can be established. See the Operating Instructions BA00051S/04/en
for this purpose.
The computer must also be assigned to a network address in the same domain as
that of Fieldgate FXA520 before it can connect with its CommDTM, see Appendix
A. 146
6.1.1
In this use case, the HART devices are connected to an analog I/O card (4 to 20 mA) of a
programmable logic controller. Normally, the devices will be powered by the card, but in
the case of 4-wire devices an external power supply will be required. Two-wire devices can
also be used in active mode, in which case external power sources will also be required.
The HART signal is accessed via a multiplexer and Fieldgate FXA520.
Endress+Hauser
27
3
7
Fieldgate
FXA520
5
13
1
2
3
4
5
6
7
FieldCare
Ethernet
Fieldgate FXA520
Pepperl+Fuchs HART Multiplexer
Pepperl+Fuchs HART Termination Board
RS-485
Controller with I/O cards
6.1.2
This use case is a typical Fieldgate FXA520 inventory monitoring application where the
process values are acquired via a HART multiplexer. The same architecture can be used to
give FieldCare access to the devices for parameterization.
28
Endress+Hauser
3
Fieldgate
FXA520
ENDRESS+HAUSER
RNS221
ENDRESS+HAUSER
RNS221
ON
ON
1 2
CH2
CH1
6
14
1
2
3
4
5
6
7
1 2
CH2
CH1
FieldCare
Ethernet
Fieldgate FXA520
Pepperl+Fuchs HART Multiplexer
Pepperl+Fuchs HART Termination Board
Power supply e.g. RN211N-B or RNS211
RS-485
In this case, the devices must be powered, e.g. by a RNS221 or RN211N-B power unit
for non-hazardous and hazardous areas respectively. Each power supply can power
two devices. A maximum of 30 devices can be connected to one Fieldgate FXA520.
6.2
Connection procedure
The following example shows how the Fieldgate FXA520 can be commissioned with
FieldCare. It is assumed that the FXA520 DTM is already installed.
6.2.1
Establishing a connection
Endress+Hauser
1.
2.
29
30
3.
4.
In the Add New Device dialog, select the FXA520 item and click OK.
The FXA520 is added to the network.
5.
Endress+Hauser
6.
Select Configuration.
The FXA520 (Configuration) dialog appears.
7.
Enter the following parameters in the FXA520 (Configuration) dialog and press
Enter to confirm each entry.
If the user name and password of the FXA520 (default: super/super) have been
changed, the values must be entered in the appropriate fields.
Access Mode: Fieldgate direct
Connection Type: LAN Fieldgate
Communication Mode: Direct (pass-through-HART)
Remote IP Address: IP address of the Fieldgate (default: 192.168.252.1)
8.
Close the FXA520 (Configuration) dialog by clicking X in the top right-hand corner.
9.
Endress+Hauser
31
6.2.2
When the multiplexer is added to the network, the Configuration dialog of the
multiplexer opens automatically. If this is not the case or if two multiplexers are
connected to Fieldgate FXA520, you must invoke the Configuration dialog manually.
Commissioning the multiplexer
32
1.
2.
Enter all the necessary information, e.g. the tag and description.
3.
4.
5.
Endress+Hauser
6.
In the Add New Device dialog, select the KFD2-HMM-16 (FDT) item and click OK.
2.
Click OK.
The slave is added to the Network dialog.
If a second master or additional slave is present, repeat Steps 1 and 2 to add it to the
Network View.
Fieldgate FXA520 can handle maximum of 30 devices with its Web server. For
FieldCare the number is higher, but the FXA520 cannot be used to display the
measured values.
Creating a network
1.
Endress+Hauser
33
34
2.
3.
Click OK.
All the connected devices are scanned.
The project looks something like this:
4.
5.
6.
Endress+Hauser
7.1
Application
2
3
4
5
6
15
1
2
3
4
5
6
FieldCare
Ethernet
ControlLogix HART I/O
Flex I/O
Point I/O
Compact I/O
7.2
Connection procedure
The FieldCare catalog must be updated before you can start connecting, see
Appendix E. 148
The following example shows how to establish a connection with ControlLogix.
Establishing a connection
Endress+Hauser
1.
2.
35
3.
4.
5.
6.
7.
Open the AB-ETHIP-1, Ethernet item. (This name can be selected individually)
8.
9.
10. In the Network dialog, right-click the RSLinx 1756 Backplane item.
A drop-down list opens.
36
Endress+Hauser
7.3
Device access
1.
2.
Select Connect.
The DeviceDTM is connected and all the arrows appear green.
3.
In the Network dialog, double-click the connected device in the Device Type (DTM)
column.
The device data are displayed.
4.
5.
Click Observe.
The measured values are displayed.
FieldCare offers additional functions, such as:
Switching device mode to connected or not connected
Reading data from the device
Writing data to the device
Device-specific functions
Endress+Hauser
37
8.1
Application
1
16
1
2
3
4
FieldCare
Ethernet
Memograph M RSG45
Slot
8.2
Connection procedure
Establishing a connection
38
1.
2.
3.
4.
In the Add New Device dialog, select the RSG45 HART Communication item and
click OK.
RSG45 HART Communication is added to the network.
Endress+Hauser
Endress+Hauser
5.
6.
Select Configuration.
The RSG45 HART Communication (Configuration) dialog appears.
7.
On the Configuration tab, enter the RSG45 IP address, the RSG45 port and the
address range for scanning the Memograph M RSG45, and then click Apply.
8.
39
9.
40
Endress+Hauser
Endress+Hauser
41
9.1
Use cases
To connect to the HART devices in the use cases detailed below, FieldCare requires:
HART CommDTM
HART DeviceDTMs
Fieldgate FXA520 must be commissioned and assigned a network IP address before
a connection can be established. See the Operating Instructions BA00051S/04/en.
The computer must be assigned to a network address in same domain as that of
Fieldgate FXA520 before it can connect with its CommDTM, see Appendix A.
146
9.1.1
HART multidrop
This use case is a typical Fieldgate FXA520 inventory monitoring application where the
process values are acquired via a HART multidrop bus. The same architecture can be used
to give FieldCare access to the devices for parameterization.
1
ENDRESS+HAUSER
RNS221
6
Fieldgate
FXA520
ON 1
CH2
CH1
17
1
2
3
4
5
6
FieldCare
Ethernet
Fieldgate FXA520 multidrop power supply
Channel 0 with max. 8 devices
Channel 1 with max. 8 devices
Fieldgate FXA520
9.1.2
The two HART channels (4 to 20 mA) of the Fieldgate FXA520 can also be used to make
point-to-point connections to individual HART devices.
42
Endress+Hauser
ENDRESS+HAUSER
RNS221
Fieldgate
FXA520
ON 1
CH2
CH1
18
1
2
3
4
5
6
FieldCare
Ethernet
HART power supply
Channel 0
Channel 1
Fieldgate FXA520
9.2
Connection procedure
The following example shows how the Fieldgate FXA520 can be commissioned with
FieldCare. It is assumed that the FXA520 DTM is already installed.
Establishing a connection
Endress+Hauser
1.
2.
3.
4.
In the Add New Device dialog, select the FXA520 item and click OK.
The FXA520 is added to the network.
43
44
5.
6.
Select Configuration.
The FXA520 (Configuration) dialog appears.
7.
Enter the following parameters in the FXA520 (Configuration) dialog and press
Enter to confirm each entry.
If the FieldCare user name and password have been changed, the values must be
entered in the appropriate fields.
Access Mode: Fieldgate direct
Connection Type: LAN Fieldgate
Communication Mode: Direct (pass-through-HART)
Remote IP Address: IP address of the Fieldgate (default: 192.168.252.1)
8.
Close the FXA520 (Configuration) dialog by clicking X in the top right-hand corner.
9.
Endress+Hauser
11. Select the HARTCH0 and/or HARTCH1 option (select both in this case) and click OK.
The scan is started. The devices found are assigned to their DTMs and added to
the project.
Endress+Hauser
45
46
Endress+Hauser
10
10.1
Use cases
10.1.1
Point-to-point connection
1
2
3
4
5
19
Operation of a MACTek modem in a control loop (I/O card active/device passive or vice versa)
10.1.2
Multidrop connection
Endress+Hauser
47
5
20
1
2
3
4
5
10.2
Connection procedure
Establishing a connection
48
1.
2.
3.
4.
Endress+Hauser
Endress+Hauser
5.
6.
In the Add New Device dialog, select the HART Communication item and click OK.
HART Communication is added to the network.
7.
8.
Select Configuration.
The COM40 (Configuration) dialog appears.
49
9.
The DeviceDTM is added to the network tree and the DTM opens.
13. The DTMs are opened as follows if the Commubox FXA195 is connected to a HART
multidrop network and several devices are found:
In the Network dialog, right-click the device and select Connect or Online
Parameterize.
Save the project as described in Chapter 3.3. 14
If FieldCare cannot find the correct DTM, it will offer alternative versions, graded
according to their suitability in the Scan Result dialog. The user has the choice of
accepting a DTM of less quality, or canceling the scan.
DeviceDTMs for new devices that are not included in the FieldCare HART DTM
library can be downloaded from the device manufacturers website. After
installation, the FieldCare device catalog must be updated. Refer to the FieldCare
on-line help for more information. The scan can then be repeated.
If no new DTM is available, the user can still integrate the device by using the HART
iDTM.
50
Endress+Hauser
11
11.1
Application
With regard to operation with FieldCare, the WirelessHART Adapter SWA70 acts like all
other HART devices. The connection can be established with a standard HART modem,
such as Commubox FXA191, Commubox FXA195 or MACTek.
1
21
1
2
3
4
5
6
FieldCare
Bluetooth
MACTek modem
WirelessHART Adapter terminals 7 and 8
HART Modem
USB or RS-232
The HART modem can be connected either to terminals 5 and 6 or to terminals 7 and 8
of the WirelessHART Adapter.
A 250 communication resistor must be used for communication via the MACTek
modem, see Chapter 4.1 and 10.1. 16 47
A 250 communication resistor must be used or switched on for communication via
Commubox FXA195.
If the WirelessHART Adapter is operated in a control loop with a communication resistor
no additional resistor is needed.
The COM port number is assigned when installing the Commubox FXA195 or MACTek
modem. This number is required later on.
To establish the connection via FieldCare, the COM port must be configured for the
selected HART modem. The HART CommDTM and the SWA70 DTM are needed for
the SWA70.
11.2
Connection procedure
Check whether the WirelessHART Adapter is connected to a power supply unit and is
in the communication mode, see BA00061S/04/en.
Establishing a connection
1.
Endress+Hauser
51
52
2.
3.
4.
In the Add New Device dialog, select the HART Communication item and click OK.
HART Communication is added to the network.
5.
Endress+Hauser
6.
Select Configuration.
The HART Communication (Configuration) dialog appears.
7.
8.
Click OK.
9.
53
12
12.1
Application
22
1
2
3
Fieldgate SWG70 is supplied with the default address of 192.168.1.1. This matches the
default address of the HART IP CommDTM.
The computer and the SWG70 must be in the same address domain (IP address, subnet
mask). This must be taken into consideration if the address of the computer or SWG70 is
changed.
To connect to the Fieldgate SWG70, FieldCare requires:
HART IP CommDTM
SWG70 DTM
The HARTIPCommDTM and the SWG70-DTM are needed to connect via FieldCare.
12.2
Connection procedure
Connecting
54
1.
2.
Endress+Hauser
Endress+Hauser
3.
4.
In the Add New Device dialog, select the HART IP Communication item and click
OK.
HART IP Communication is added to the network.
5.
6.
7.
55
8.
9.
10. Enter the new IP address and/or Ethernet UDP port number.
11. Click Update Changed Data.
12. Close the HART IP Communication (Set DTM Addresses) dialog.
13. In the Network dialog, right-click the WirelessHART Fieldgate item.
A drop-down list opens.
56
Endress+Hauser
17. In the WirelessHART Fieldgate dialog, expand all the submenus of the directory tree
to reveal the parameter blocks.
Start the configuration as described in Operating Instructions BA00064S/04/en.
The WirelessHART Fieldgate DTM can also be used to scan for WirelessHART
Adapters and devices in the network. A full description is provided in Operating
Instructions BA00064S/04/en.
Endress+Hauser
57
13
13.1
Application
1
23
1
2
3
FieldCare
RS485 Modbus
Field device
13.2
Connection procedure
Connecting
58
1.
2.
3.
4.
In the Add New Device dialog, select the Modbus Serial Communication DTM item
and click OK.
The Modbus Serial Communication DTM is added to the network.
Endress+Hauser
5.
6.
Select Configuration.
The Modbus Serial Communication DTM (Configuration) dialog opens.
7.
8.
On the Scan tab, select Multipoint, enter the address 247 and click Apply.
The changes are accepted and saved.
9.
Endress+Hauser
59
14
14.1
Application
1
24
1
2
3
FieldCare
Ethernet
Field device
14.2
Connection procedure
Connecting
60
1.
2.
3.
4.
In the Add New Device dialog, select the EtherNet/IP Comm Adapter item and click
OK.
EtherNet/IP Comm Adapter is added to the network.
Endress+Hauser
5.
6.
Select Configuration.
The EtherNet/IP Comm Adapter (Configuration) dialog opens.
7.
On the Configuration tab, enter the IP address of the PC under host address.
8.
On the Scan tab, select Single, enter the IP address start address and click Apply.
The changes are accepted and saved.
9.
Endress+Hauser
61
15
15.1
Application
The PlantPAx architecture provides a manufacturer and user technology such that the
input data and the output condition can be used by all ControlLogix controllers in the
system.
2
3
4
5
25
1
2
3
4
5
FieldCare
Ethernet
ControlLogix
1788HP-EN2PAR
PROFIBUS PA
15.2
Connection procedure
The FieldCare catalog must be updated before you can start connecting, see Appendix
E. 148
Establishing a connection
62
1.
2.
Endress+Hauser
Endress+Hauser
3.
4.
5.
6.
7.
8.
9.
Enter the Module IP Address and the Max Scan Address and press Enter to
confirm.
63
64
Endress+Hauser
16
16.1
Application
This use case is typical for the use of Fieldgate FXA720 to provide parallel access to a
PROFIBUS control system, e.g. for device set-up, device diagnosis or condition monitoring.
Fieldgate FXA720 operates as a Master Class 2 and uses non-cyclic communication.
A similar architecture, but not necessarily with a controller, could be used for the
monitoring of tank inventory in connection with SupplyCare software. In this case
FieldCare is used for set-up and diagnosis only.
To connect to the PROFIBUS DP/PA devices, FieldCare requires:
PROFIdtm DPV1 CommDTM
PROFIBUS CommDTM
PROFIBUS DeviceDTMs
A transparent coupler is one that does not require a CommDTM to connect to the
PROFIBUS PA devices beneath it. Pepperl+Fuchs DP/PA couplers are examples. If a
Siemens coupler or link is used, a CommDTM is required for it. The procedure for
connecting is analogous to that described in this chapter, the link being found during the
creation of the network after the Fieldgate FXA720 CommDTM has been added to the
FieldCare host.
1
ON
FAIL
ETH
RUN
DP
+24VDC
L+
ETHERNET
Fieldgate FXA720
PROFIBUS DP
COM
6
5
26
1
2
3
4
5
6
7
Endress+Hauser
FieldCare
Ethernet
Fieldgate FXA720
PROFIBUS DP
PROFIBUS PA
Transparent DP/PA coupler
Controller with I/O cards
65
16.2
16.2.1
Basic configuration
Fieldgate FXA720 must be assigned an IP address and, when used with FieldCare, the
PROFIBUS scan function must be disabled. This is done in the Fieldgate FXA720 Web
server.
Before this procedure can be started, the IP address that Fieldgate will be allocated
within the control network must be known.
If the Web browser does not find the Web server, it is essential to check whether a
proxy is in use and to switch it off if necessary.
Commissioning the Fieldgate FXA720
Set the IP address of the computer to the same domain as the Fieldgate FXA720's default
address 192.168.253.1. See Appendix A or consult your system administrator if this is
unclear. 146
66
1.
2.
Enter the Fieldgate FXA720's default address 192.168.253.1 into the address field
of the browser and press Enter to confirm.
The browser makes a connection with the Fieldgate FXA720 and the Login
dialog opens.
3.
4.
5.
Enter admin as the user name and super as the password and click Login.
6.
Endress+Hauser
7.
8.
9.
Click Send.
Changes are downloaded to Fieldgate FXA720.
16.2.2
Connection procedure
Fieldgate FXA720 must be commissioned before it can be used. This is done by either
running the set-up program supplied on accompanying the CD or calling the
PROFIBUS Control Panel Applet from the PROFIBUS DPV1 CommDTM.
The Fieldgate FXA720 set-up routine is described in Operating Instructions
BA00030S/04/en.
Starting the PROFIBUS Control Panel
1.
Endress+Hauser
67
2.
3.
For this to happen, the PROFIBUS DVP1 CommDTM must have been added to the
HOST PC beforehand.
PROFIBUS set-up
1.
68
In the PROFIBUS Control Panel dialog, select the FG series/PROFIgate item and
click Add.
The Select Node Name dialog opens.
Endress+Hauser
Endress+Hauser
2.
Enter a symbolic node name for the PROFIBUS DP channel (default value: Node 0)
and click Next.
The Select Addresses for FG series / PROFIgate dialog opens.
3.
Enter the IP address of the Fieldgate, select Bus Connector and click Next.
The Select Timeouts for FG series / PROFIgate dialog opens and the user can
make the standard timeout setting.
4.
Enter the Timeout for Connect. These settings should be made by PROFIBUS
specialists only. Click Finish.
The standard timeout settings are accepted and the configuration is completed.
The PROFIBUS Control Panel dialog returns and the symbolic name of the
Fieldgate is assigned to the FG series/PROFIgate item.
69
5.
Click Apply.
The configuration is saved. The Fieldgate FXA720 is ready if a green tick appears
next to the symbolic name. If a red tick appears, check whether the PROFIBUS
scan is switched off.
6.
16.3
Connection procedure
Establishing a connection
1.
2.
3.
4.
In the Add New Device dialog, select the PROFIdtm DPV1 item and click OK.
The PROFIdtm DPV1 is added to the network.
If the Fieldgate FXA720 is not already set up it can be set up now, see Chapter
16.2.1. 66
70
Endress+Hauser
5.
6.
Select Configuration.
The PROFIdtm DPV1 (Configuration) dialog appears.
7.
Check that the PROFIBUS bus parameters are exactly the same as those used in any
Master Class 1 in the network. The default parameters are the ones recommended
for use with a particular baud rate. They can be adjusted by deactivating the
automatic defaults.
Select Board-Name from the drop-down menu.
8.
9.
10. Enter the Start and End Address for the scan range and click OK.
The changes are saved and FieldCare returns to the Network dialog.
11. In the Network dialog, right-click the PROFIdtm DPV1 item.
A drop-down list opens.
Endress+Hauser
71
72
Endress+Hauser
17
17.1
Application
When operating with a single segment with a Pepperl+Fuchs coupler, the component
architecture is as shown in Fig. 27, for example.
Fieldgate SFG500 is connected to the Ethernet backbone via the LAN 1 Ethernet socket
and to the PROFIBUS DP segment. The segment itself is connected to a PLC or DCS, which
acts as Class 1 master. PROFIBUS PA devices are connected to the network via the coupler.
To see all the devices on the PROFIBUS DP/PA segment, FieldCare requires:
SFGNetwork DTM
PROFIBUS DeviceDTMs
1
Power
PB DP
Run
PB Err
Failure
RS485
LAN 1
LAN 2
AB001CF2897L
Reset
LAN 2
LAN 1
SFG500
6
5
27
1
2
3
4
5
6
7
FieldCare
Ethernet
Fieldgate SFG500
PROFIBUS DP
PROFIBUS PA
Transparent DP/PA coupler
Controller with I/O cards
17.2
Connection procedure
Establishing a connection
Endress+Hauser
1.
2.
73
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
74
Endress+Hauser
7.
If no DTM has been found, it is possible that the UDP ports are blocked. These ports
can be unblocked as described in Appendix B 146. Alternatively, the
CommDTM can be added manually.
In the Network dialog, right-click the SFG500 Network item.
A drop-down list opens.
8.
9.
If several Fieldgate SFG500s and connected devices are found, these are
automatically added to the network.
If any of the devices has a DTM whose quality is less than 1, the Scanning Result
dialog opens. Click OK before the devices are added to the network.
Endress+Hauser
75
76
Endress+Hauser
18
18.1
Application
When operating with multiple segments and Pepperl+Fuchs couplers the component
architecture can be as shown in Fig. 28, for example.
For simplicity the devices connected to segments 2 5 are not shown. All Fieldgate
SFG500s are connected to the Ethernet backbone via the LAN 1 Ethernet socket and share
a common Ethernet IP address domain. One Fieldgate SFG500 is connected to each
PROFIBUS DP segment. The PROFIBUS DP segments do not necessarily have to be
connected to a single PLC. PROFIBUS PA devices are connected to the PROFIBUS DP
segments via couplers.
To see all the devices on the PROFIBUS DP/PA segment, FieldCare requires:
SFGNetwork DTM
PROFIBUS DeviceDTMs
1
8
3
Power
Run
Failure
PB DP
PB Err
RS485
Power
Run
LAN 1
LAN 2
PB DP
PB Err
Failure
RS485
LAN 1
Power
Run
LAN 2
PB DP
PB Err
Failure
RS485
LAN 1
LAN 2
Power
PB DP
RS485
Power
Run
PB Err
LAN 1
Run
Failure
Failure
PB DP
PB Err
RS485
LAN 1
LAN 2
LAN 2
Reset
AB001CF2897L
AB001CF2897L
SFG500
SFG500
LAN 1
LAN 2
LAN 1
LAN 1
LAN 2
LAN 2
LAN 1
SFG500
LAN 2
LAN 2
Reset
AB001CF2897L
Reset
SFG500
LAN 1
SFG500
AB001CF2897L
Reset
AB001CF2897L
Reset
5
6
28
1
2
3
4
5
6
7
8
FieldCare
Ethernet
Fieldgate SFG500
PROFIBUS DP with segment 1-5
DP/PA coupler
PROFIBUS PA
PLC/DCS
Control network
18.2
Connection procedure
The dialogs for this procedure are identical to those in Chapter 11.2. 51
Establishing a connection
1.
Endress+Hauser
2.
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Connect.
7.
8.
9.
10. If more than one device is found, the Connect After Scanning message appears.
Click OK.
FieldCare adds the Fieldgate SFG500s found and the connected devices to the
network.
If no DTM has been found, it is possible that the UDP ports are blocked. These
ports can be unblocked as described in Appendix B. 146 Alternatively, the
CommDTM can be added manually.
11. If any of the devices has a DTM whose quality is less than 1, the Scanning Result
dialog opens.
Click OK before the devices are added to the network.
The Network dialog opens.
78
Endress+Hauser
19
19.1
Application
When operating with a Siemens DP/PA coupler or link, the component architecture can be
as shown in Fig. 29, for example.
The Fieldgate SFG500 is connected to the Ethernet backbone via the LAN 1 Ethernet
socket. PROFIBUS PA devices are connected to the network via the Siemens coupler/link.
The same architecture can be used for Fieldgate FXA720 in combination with Siemens
DP/PA link.
To see all the devices on the PROFIBUS DP/PA segment, FieldCare requires:
SFGNetwork DTM
PROFIBUS CommDTM
PROFIBUS DeviceDTMs
1
Power
Run
Failure
PB DP
RS485
PB Err
LAN 1
LAN 2
AB001CF2897L
Reset
LAN 2
LAN 1
SFG500
29
1
2
3
4
5
6
7
8
FieldCare
Ethernet
Fieldgate SFG500
PROFIBUS DP
PROFIBUS PA
Siemens link/ DP/PA coupler
PLC/DCS
Control network
19.2
Connection procedure
The dialogs for this procedure are identical to those in Chapter 11.2. 51
Establishing a connection
Endress+Hauser
1.
2.
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Connect.
7.
8.
9.
80
Endress+Hauser
Endress+Hauser
81
20
20.1
Application
This chapter describes how FieldCare should be configured for a plant that uses a Siemens
ET200M/iSP-type Remote I/O. The PC with FieldCare installed is connected to an SFG500
via Ethernet. The SFG500 is connected via Profibus DP to an ET200M/iSP, which is
connected to the field devices via HART. A cyclic master is required for the operation of the
plant.
1
30
1
2
3
4
5
6
FieldCare
Ethernet/IP
Fieldgate SFG500
PROFIBUS DP
Master
Siemens ET200 Remote I/O
20.2
Connection procedure
The dialogs for this procedure are identical to those in Chapter 11.2. 51
Establishing a connection
82
1.
2.
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Connect.
The connection to the device is established and is indicated by a green arrow.
7.
Endress+Hauser
8.
9.
Endress+Hauser
83
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Turck Remote I/O
21
21.1
Application
When operating with a Turck EXCOM Remote I/O the component architecture can be as
shown in Fig. 31, for example. The Fieldgate SFG500 is connected to the Ethernet
backbone via the LAN 1 Ethernet socket. PROFIBUS PA devices are connected to the
network via e.g. a transparent coupler. The HART devices (4 to 20 mA) are connected
point-to-point to the Turck Remote I/O which in turn is connected to the PROFIBUS-DP
segment.
The same architecture can be used for Fieldgate FXA720 and a Turck Remote I/O. The
connection procedure for the Turck Remote I/O is analogous to that in Chapter 17.2.
73
To see all the devices on the PROFIBUS DP/PA segment, FieldCare requires:
SFGNetwork DTM
Licensed Turck CommDTM EXCOM
PROFIBUS DeviceDTMs
HART DeviceDTMs
1
Power
PB DP
Run
PB Err
Failure
RS485
LAN 1
LAN 2
LAN 2
LAN 1
SFG500
AB001CF2897L
Reset
10
31
1
2
3
4
5
6
7
8
9
10
84
Control network
PLC/DCS
FieldCare
Fieldgate SFG500 Access Point
Ethernet
PROFIBUS DP
Turck EXCOM Remote I/O
HART 4 to 20 mA
DP/PA coupler
PROFIBUS PA
Endress+Hauser
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Turck Remote I/O
21.2
Connection procedure
The dialogs for this procedure are identical to those in Chapter 11.2. 51
Establishing a connection
1.
2.
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Connect.
The connection to the device is established and is indicated by a green arrow.
7.
8.
13. If more than one device is found, the Connect After Scanning message appears.
Click OK.
The CommDTM is added to the network.
Endress+Hauser
85
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Turck Remote I/O
14. If the Connect After Scanning option is selected under Extras the Connect After
Scanning dialog opens.
Click OK.
86
1.
2.
Endress+Hauser
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Stahl Remote I/O
22
22.1
Application
When operating with a Stahl CPM 9440 Remote I/O the component architecture can be as
shown in Fig. 32, for example. The Fieldgate SFG500 is connected to the Ethernet
backbone via the LAN 1 Ethernet socket. PROFIBUS PA devices are connected to the
network via e.g. a transparent coupler. The HART devices (4 to 20 mA) are connected
point-to-point to the Stahl Remote I/O which in turn is connected to the PROFIBUS-DP
segment.
The same architecture can be used for Fieldgate FXA720 and a Stahl Remote I/O. The
connection procedure for the Stahl Remote I/O is analogous to that in Chapter 17.2.
73
To see all the devices on the PROFIBUS DP/PA segment, FieldCare requires:
SFGNetwork DTM
PROFIBUS CommDTM
PROFIBUS DeviceDTMs
HART DeviceDTMs
1
Power
PB DP
Run
PB Err
Failure
RS485
LAN 1
LAN 2
LAN 2
LAN 1
SFG500
AB001CF2897L
Reset
10
32
1
2
3
4
5
6
7
8
9
10
Endress+Hauser
Control network
PLC/DCS
FieldCare
Fieldgate SFG500 Access Point
Ethernet
PROFIBUS DP
Stahl CPM 9440 Remote I/O
HART 4 to 20 mA
DP/PA coupler
PROFIBUS PA
87
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Stahl Remote I/O
22.2
Connection procedure
The dialogs for this procedure are identical to those in Chapter 11.2. 51
Establishing a connection
1.
2.
3.
4.
In the Add New Device dialog, select the SFGNetwork item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Connect.
The connection to the device is established and is indicated by a green arrow.
7.
8.
88
Endress+Hauser
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Stahl Remote I/O
14. If more than one device is found, the Connect After Scanning message appears.
Click OK.
15. In the Network dialog, right-click the DP/PA Link item.
A drop-down list opens.
16. Select Create Network.
The segment to which the DP/PA link is connected is scanned for devices.
The Create Network - Scanning Result dialog opens.
18. If the Connect After Scanning option is selected under Extras the Connect After
Scanning dialog opens.
Click OK.
19. In the Network dialog, right-click to select the CPM 9440 item.
A drop-down list opens.
20. Select Connect.
The connection to the device is established and is indicated by a green arrow.
21. In the Network dialog, right-click to select the CPM 9440 item.
A drop-down list opens.
Endress+Hauser
89
PROFIBUS DP/PA and HART via Fieldgate SFG500 and Stahl Remote I/O
24. If the Connect After Scanning option is selected under Extras the Connect After
Scanning dialog opens.
Click OK.
90
1.
2.
Endress+Hauser
23
23.1
Application
33
1
2
3
4
5
FieldCare
USB
PROFIusb modem
DP/PA coupler
PROFIBUS PA
23.2
Connection procedure
PROFIusb must be commissioned before it can be used. For this, the user calls the
PROFIBUS Control Panel Applet from the PROFIBUS DPV1 CommDTM.
Starting the PROFIBUS Control Panel
1.
Endress+Hauser
91
2.
3.
For this to happen, the PROFIBUS DVP1 CommDTM must have been added to the
HOST PC beforehand.
PROFIBUS set-up
92
1.
In the PROFIBUS Control Panel dialog, select the PROFIusb item and click Add.
The Select Node Name dialog opens.
2.
Enter a symbolic node name for the PROFIBUS DP channel (default value: Node 0)
and click Next.
Endress+Hauser
3.
Do not change the default settings (auto) for the serial number of the device.
Click Finish.
The PROFIBUS Control Panel dialog returns and the symbolic name of the
PROFIusb modem is assigned to the PROFIusb item.
4.
Click Apply.
The configuration is saved. The device is ready if a green tick appears next to the
symbolic name. If a red tick appears, check whether the PROFIBUS scan is
switched off.
5.
23.3
Connection procedure
Establishing a connection
Endress+Hauser
1.
2.
93
3.
4.
In the Add New Device dialog, select the PROFIdtm DPV1 item and click OK.
The PROFIdtm DPV1 is added to the network.
5.
The Node Name (default: Node0) entered previously in the PROFIBUS Control
Panel must be selected in the Board Name field. The other parameters must be
checked and modified as they can vary depending on the plant.
6.
7.
94
Endress+Hauser
24
24.1
Application
This chapter describes how FieldCare should be configured for a plant that uses a WAGO
Remote I/O. The PC with FieldCare installed is connected to a PROFIBUS modem via
Ethernet. A Softing ProfiUSB, for example, can be used for this. The modem is connected
to the WAGO Remote I/O via PROFIBUS DP. The WAGO Remote I/O is connected to HART
field devices by HART via one or more WAGO modules. A cyclic master is essential for the
operation of the plant. A PROCENTEC ProfiCore, for example, can be used for this.
1
34
1
2
3
4
5
6
FieldCare
Ethernet/IP
PROCENTEC ProfiCore
Softing modem
PROFIBUS DP
WAGO Remote I/O
The plant described in this chapter uses a Softing profiUSB with commDTM PROFIdtm
DPV1 as the PROFIBUS modem and a PROCENTEC ProfiCore as the cyclic master.
Alternatively, other suitable PROFIBUS devices can also be used.
24.2
Connection procedure
Endress+Hauser
1.
2.
95
3.
4.
In the Add New Device dialog, select the DTM modem and click OK. If a Softing
modem is used, PROFIdtm DP-V1 is the correct DTM.
The modem is added to the network.
5.
6.
Select Configuration.
The Configuration dialog appears.
7.
96
1.
2.
3.
Endress+Hauser
4.
5.
Select the Module Configuration tab in the Configuration dialog. The first slot (1) is
occupied by the WAGO head module and cannot be edited. Set all the modules on the
head module.
6.
7.
Recursive scanning cannot be performed with the Wago Remote I/O. Therefore, all
the devices connected to the Remote I/O and displayed in the device list must be
added manually.
Endress+Hauser
1.
2.
Select Device.
The Assign Device to Channel dialog appears.
3.
97
25
25.1
Application
This chapter describes how FieldCare should be configured for a plant that uses a
PROCENTEC ProfiCore. The PC with FieldCare installed is connected to a PROCENTEC
ProfiCore via Ethernet. The ProfiCore is connected via PROFIBUS DP to a PROFIBUS DP/PA
coupler which is connected to the field devices via PROFIBUS PA.
The following software packages must be installed and configured on the PC:
PCD setup
CommDTM PROCENTEC DP-V1 master
ProfiTrace
These can be downloaded from the PROCENTEC site at www.procentec.com
1
35
1
2
3
4
5
FieldCare
Ethernet
PROCENTEC ProfiCore
PROFIBUS DP
DP/PA coupler
25.2
Connection procedure
Establishing a connection
98
1.
2.
Endress+Hauser
3.
The Profitrace and PCD icons are displayed in the start bar on the bottom right.
Endress+Hauser
4.
5.
6.
In the Interface Settings dialog, enter values for the fields Interface name (userdefinable) , Driver = Profitrace/, serial number of the Procentec Device and
confirm.
The interface is created and can be assigned.
7.
99
8.
Select Configuration.
The Configuration dialog appears.
9.
10. In the Bord Name field, select the Interface Name entered and click Start.
The bus parameters are read and saved.
11. In the Network dialog, right-click PROFIdtm.
A drop-down list opens.
12. Select Create Network.
The network is scanned and all the field devices connected to the PROCENTEC ProfiCore
are displayed and can be used.
100
Endress+Hauser
26
26.1
Application
When operating as a visitor, the Field Controller SFC162 provides a parallel path to
devices in an existing system and is used to commission devices, to change their settings or
to monitor their condition. This assumes that the system is operating, i.e. a project has
been downloaded to the Field Controller and devices.
The Field Controller SFC162 is normally used to configure the transducer blocks only.
For some devices, the Field Controller SFC162 can also be used to configure the input
and output blocks, but normally not the logic and control blocks.
A full description of the use of the Field Controller SFC162 in bypass mode can be found
in BA00069S/04/en.
To see all the devices on the FOUNDATION Fieldbus H1 segment, FieldCare requires:
FOUNDATION Fieldbus CommDTM
FOUNDATION Fieldbus DeviceDTMs
For devices without native DTMs, the iDTM for FOUNDATION Fieldbus
1
RS-232
ETH
ON
RS-232 TX
ETH LNK
FF H1 - 1
FF H1 - 2
FF H1 - 3
FF H1 - 4
STDBY
!
See Manual
ControlCare SFC162
ETH TX
5
36
1
2
3
4
5
FieldCare
Field Controller SFC162
Ethernet
FOUNDATION Fieldbus H1
DCS
26.2
26.2.1
For this procedure, the IP address of the Fieldgate within the control network must
be known.
Do not restart the Field Controller SFC162 with the new address before Visitor
mode has been selected.
Endress+Hauser
101
Set the IP address of the computer to the same domain as the Field Controller
SFC162's default address 192.168.164.100. See Appendix A or consult your system
administrator for information on this procedure. 146
2.
If you have Application Designer installed on your computer, call HSE Network
Setup:
Programs Endress+Hauser ControlCare Tools HSE Network Setup.
Otherwise call up the Web server and enter the address 192.168.164.100 . Then
proceed with Step 5.
HSE Network Setup is launched and searches for devices in the Ethernet
network.
All devices in the network appear, irrespective of their IP domain. If this is not
the case:
Check that the proxy server of the Web browser is switched off.
Check that the Windows firewall is not blocking the program (switch off the
firewall).
Check all cables and switches.
If two or more Field Controllers with the same IP address are found, disconnect
all but one from the network.
3.
If the computer has more than one NIC, it is necessary to select the card you want to
use for communication with the Field Controllers.
Tick Active NIC and click Save.
4.
5.
The Web server will only open if the host computer and the Field Controller have
IP addresses in the same IP domain.
If the Web server still does not open, check that the proxy server on the browser
has been disabled.
6.
102
Endress+Hauser
7.
8.
9.
10. If required, enter a default gateway (usually xxx.xxx.xxx.1, selected domain) and
click Update.
11. Confirm the message stating that the Field Controller SFC162 must be restarted.
The IP address is set up.
26.2.2
There can be up to four Field Controller SFC162s in any one network. However, each
controller must be assigned a different H1 address by running the option under Step
2 above.
Selecting the Visitor mode
Endress+Hauser
1.
2.
Select the Factory Init in Visitor Mode (H1 Address 0xFC) option and click Restart.
3.
Enter pcps as the user name and pcps as the password to confirm the Field
Controller SFC162 restart.
The Field Controller SFC162 changes its mode from Controller (default setting)
to Visitor.
The Field Controller restarts as a visitor with the IP address entered as described
in Chapter 24.2.1 and the H1 address selected from the drop-down menu.
4.
Set the address of the host computer to the same domain as that of the Field
Controller SFC162 Visitor (e.g. 10.125.35.200).
103
26.2.3
If the host computer has more than one NIC, the one used for the Ethernet connection
to the controller and visitor must be specified, otherwise the applications running on
Ethernet select the first they find by default. For Application Designer, ticking and
storing the active NIC in HSE Network Setup causes the associated .ini files to be
updated.
For FieldCare these changes have to be made by hand.
Selecting the network card for FieldCare
1.
2.
3.
4.
5.
Remove the ; from the line NIC = and add the NIC address (e.g. NIC =
10.125.35.200).
6.
26.3
Connection procedure
Establishing a connection
104
1.
2.
3.
4.
In the Add New Device dialog, select the SFC162 CommDTM item and click OK.
The SFGNetwork is added to the network.
Endress+Hauser
5.
6.
Select Configuration.
FieldCare scans the network for all the Ethernet devices and displays them in the
list of HSE devices.
7.
To connect the Field Controller SFC162 Visitor, click the appropriate line (e.g.
10.125.35.190).
A tick appears next to the Field Controller SFC162 Visitor and the entry appears
green.
8.
9.
10. Select the channels to be scanned. Deselect all other channels and click OK.
The scan is started.
FieldCare scans the selected channels and adds the devices found to the network.
Endress+Hauser
105
26.4
After the devices have been configured, their settings must be uploaded to the Field
Controller SFC162 and engineering tool. Depending upon the tool and the task
(commissioning or replacement) this can be normally done for the entire fieldbus or for
individual devices.
The Field Controller manual contains instructions on how the device parameters should be
uploaded.
106
Endress+Hauser
27
27.1
Application
2
3
RS-232
FRC HLD
ETH
RUN FAIL
ON
RS-232 TX
ETH LNK
FF H1 - 1
FF H1 - 2
FF H1 - 3
FF H1 - 4
STDBY
!
See Manual
ControlCare SFC162
ETH TX
37
1
2
3
4
FieldCare
Ethernet
Field Controller SFC162
FOUNDATION Fieldbus H1
This chapter describes the point-to-point scenario. It shows how a device tag and device
address can be assigned to a device. For information about the configuration of the
devices, please refer to the appropriate manual.
The DeviceDTMs differ from device to device in the functions which can be configured:
All DTMs allow the configuration of the resource and transducer blocks.
Some DTMs allow the configuration of the device input/output blocks.
To date, no DTM allows the configuration of the tag and address. This can only be done
with the Field Controller SFC162 CommDTM.
The upload to the control system may also differ depending upon the manufacturer, type
and condition of the device. Endress+Hauser devices delivered fresh from the factory will
usually upload all the function blocks they support including logic and control blocks,
although the latter cannot be configured via DTMs.
Should a device have been subject to a download from a control system, then any block not
instantiated by the engineering tool will not be part of the upload. For a TMT162
temperature transmitter, for example, if only one analog input block has been instantiated
Endress+Hauser
107
for a project, only this block will be uploaded, although three blocks are offered in the
DTM. Configuring the two other blocks in FieldCare will not cause them to be uploaded.
27.2
27.2.1
For this procedure, the IP address of the Fieldgate within the control network must
be known.
Do not restart the Field Controller SFC162 with the new address before Visitor
mode has been selected.
Setting up the IP address of the Field Controller SFC162
1.
Set the IP address of the computer to the same domain as the Field Controller
SFC162's default address 192.168.164.100. See Appendix A or consult your system
administrator for information on this procedure. 146
2.
If you have Application Designer installed on your computer, call HSE Network
Setup:
Programs Endress+Hauser ControlCare Tools HSE Network Setup.
Otherwise call up the Web server and enter the address 192.168.164.100 . Then
proceed with Step 5.
HSE Network Setup is launched and searches for devices in the Ethernet
network.
All devices in the network appear, irrespective of their IP domain. If this is not
the case:
Check that the proxy server of the Web browser is switched off.
Check that the Windows firewall is not blocking the program (switch off the
firewall).
Check all cables and switches.
If two or more Field Controllers with the same IP address are found, disconnect
all but one from the network.
108
3.
If the computer has more than one NIC, it is necessary to select the card you want to
use for communication with the Field Controllers.
Tick Active NIC and click Save.
4.
Endress+Hauser
5.
The Web server will only open if the host computer and the Field Controller have
IP addresses in the same IP domain.
If the Web server still does not open, check that the proxy server on the browser
has been disabled.
6.
7.
8.
9.
10. If required, enter a default gateway (usually xxx.xxx.xxx.1, selected domain) and
click Update.
11. Confirm the message stating that the Field Controller SFC162 must be restarted.
The IP address is changed.
27.2.2
There can be up to four Field Controller SFC162s in any one network. However, each
controller must be assigned a different H1 address by running the option under Step
2 above.
Endress+Hauser
109
2.
Select the Factory Init in Visitor Mode (H1 Address 0xFC) option and click Restart.
3.
Enter pcps as the user name and pcps as the password to confirm the Field
Controller SFC162 restart.
The Field Controller SFC162 changes its mode from Controller (default setting)
to Visitor.
The Field Controller restarts as a visitor with the IP address entered as described
in Chapter 26.2.1 and the H1 address selected from the drop-down menu.
101
4.
Set the address of the host computer to the same domain as that of the Field
Controller SFC162 Visitor (e.g. 10.125.35.200).
27.2.3
If the host computer has more than one NIC, the one used for the Ethernet connection
to the controller and visitor must be specified, otherwise the applications running on
Ethernet select the first they find by default. For Application Designer, ticking and
storing the active NIC in HSE Network Setup causes the associated .ini files to be
updated.
For FieldCare these changes have to be made by hand.
Selecting the network card for FieldCare
1.
2.
3.
4.
5.
Remove the ; from the line NIC = and add the NIC address (e.g. NIC =
10.125.35.200).
6.
110
Endress+Hauser
27.3
Connection procedure
27.3.1
Establishing a connection
Endress+Hauser
1.
2.
3.
4.
In the Add New Device dialog, select the SFC162 CommDTM item and click OK.
The SFGNetwork is added to the network.
5.
6.
Select Configuration.
FieldCare scans the network for all the Ethernet devices and displays them in the
list of HSE devices.
7.
To connect the Field Controller SFC162 Visitor, click the appropriate line (e.g.
10.125.35.190).
A tick appears next to the Field Controller SFC162 Visitor and the entry appears
green.
111
27.3.2
112
1.
2.
Select Connect.
The arrows next to the device appear green.
3.
4.
5.
6.
7.
8.
Click Apply.
Changes are saved and downloaded to the device.
Endress+Hauser
The icon at the start of the line appears in full color if the changes have been accepted.
If there are more devices in the network, the tags and addresses of all participants
can be changed before Apply is pressed.
When all devices return to the network, the H1 list can be closed.
27.3.3
2.
3.
Select the channels to be scanned. Deselect all other channels and click OK.
The scan is started.
FieldCare scans the selected channels and adds the devices found to the network.
27.3.4
Endress+Hauser
1.
2.
Select Connect.
The arrows next to the device appear green.
113
3.
4.
27.4
After the devices have been configured, their settings must be uploaded to the Field
Controller SFC162 and engineering tool. Depending upon the tool and the task
(commissioning or replacement) this can be normally done for the entire fieldbus or for
individual devices.
The Field Controller manual contains instructions on how the device parameters should be
uploaded.
114
Endress+Hauser
28
28.1
Use cases
The National Instruments PCPC-FBUS card allows a computer or laptop with a PC interface
to connect to a FOUNDATION Fieldbus H1 segment.
The National Instruments software delivered with the card must be installed on the
computer, configured and ready for use.
If the PC-FBUS card is connected to an active FOUNDATION Fieldbus H1 segment, it
is important to read the manufacturer's instructions with regard to uploading
modified device settings to the controller.
To see all the devices on the FOUNDATION Fieldbus H1 segment, FieldCare requires:
FOUNDATION Fieldbus CommDTM
FOUNDATION Fieldbus DeviceDTMs
For devices without native DTMs, the iDTM for FOUNDATION Fieldbus
28.1.1
To connect the PC-FBUS card to a FOUNDATION Fieldbus H1 segment, the positive and
negative signal cables from the NI adapter piece must be connected to the bus line, e.g. via
a bus distributor.
1
38
1
2
3
4
5
6
DCS
Adapter
Adapter cable
NI-PC-FBUS card
FieldCare
FOUNDATION Fieldbus H1
28.1.2
In Bench mode, the devices are connected to the NI-PC-NBS card one by one in order to
configure the device address and device parameters. This requires a bus distributor with a
fieldbus power supply.
Endress+Hauser
115
39
1
2
3
4
5
6
FOUNDATION Fieldbus H1
Power conditioner/bus distributor
Adapter
Adapter cable
NI-PC-NBS card
FieldCare
28.2
Connection procedure
Establishing a connection
116
1.
2.
3.
4.
5.
In the Add New Device dialog, select the FF H1 CommDTM item and click OK.
The FF H1 CommDTM is added to the network.
6.
Endress+Hauser
7.
Select Configuration.
The FF H1 CommDTM dialog opens and FieldCare asks for the link to the
FOUNDATION Fieldbus network.
8.
Select the NI Card Link from the drop-down menu and click OK.
9.
The DTMs are opened as follows if the NI FBUS card is connected to a FOUNDATION
Fieldbus H1 segment and several devices have been found:
In the Network dialog, right-click Device Node.
A drop-down list opens.
2.
Select Connect.
3.
4.
Endress+Hauser
117
29
29.1
Use cases
29.1.1
To connect the FFusb modem to a FOUNDATION Fieldbus H1 segment, the positive and
negative signal cables must be connected to the bus line, e.g. via a bus distributor.
1
40
1
2
3
4
5
DCS
FFusb modem
USB
FieldCare
FOUNDATION Fieldbus H1
29.1.2
In Bench mode, the devices are connected to the FFusb modem one by one in order to
configure the device address and device parameters. This requires a bus distributor with a
fieldbus power supply.
118
Endress+Hauser
41
1
2
3
4
5
FOUNDATION Fieldbus H1
Power conditioner/bus distributor
FFusb modem
USB
FieldCare
29.2
Connection procedure
Establishing a connection
Endress+Hauser
1.
2.
3.
4.
5.
6.
7.
Select Configuration.
The standard parameters for a FOUNDATION Fieldbus Visitor are displayed.
8.
9.
120
Endress+Hauser
1.
The DTMs are opened as follows if the NI FBUS card is connected to a FOUNDATION
Fieldbus H1 segment and several devices have been found:
In the Network dialog, right-click Device Node.
A drop-down list opens.
2.
Select Connect.
3.
4.
Endress+Hauser
121
30
30.1
Application
42
1
2
3
4
5
6
TX
RX
5V
FieldCare
RS-232
FXA193 modem
Cable and adapter
Proline flowmeter electronic compartment or connection compartment
Power supply
The FXA193 modem must be used with the so-called Proline cable, which comprises two
components: a cable and an adapter.
The FXA193 modem is a serial modem with a Sub-D9 connector. It is recommended that
only a native serial port be used. The use of USB/Serial converters is not recommended. If
the desktop computer has no RS-232 serial port, it is recommended that either a PCI or a
PCIe card be used. For laptop computers either a PC or Express Card can be used.
To connect to flow devices via the protocol (ISS), FieldCare requires:
ISS CommDTM
ISS DeviceDTM library
30.2
Connection procedure
Establishing a connection
122
1.
2.
Endress+Hauser
Endress+Hauser
3.
4.
5.
6.
Select Configuration.
The Flow Communication FXA193/291 (Configuration) dialog appears.
7.
Set the COM port to which the FXA193 modem is to be connected and then press
Enter.
8.
123
9.
124
Endress+Hauser
31
31.1
Application
Some older flowmeters do not use the service connector shown in Fig. 42.
In this case the FXA291 modem must be used to connect to FieldCare. The connection
socket for communication can either be found inside the electronic housing or the
connection housing. Please consult the appropriate Operating Instructions for further
details. Fig. 43 shows the necessary connections.
43
1
2
3
4
5
6
FieldCare
USB
FXA291 modem
Cable and adapter
Proline flowmeter electronic compartment or connection compartment
Power supply
31.2
Normally the computer automatically recognizes the FXA291 modem. If this is not the
case, the driver must be installed, see Appendix C. 147
Installing the modem driver
1.
2.
3.
31.3
Connection procedure
Endress+Hauser
125
32
32.1
Application
For communication with level and pressure devices via the IPC protocol, connectivity is
provided with the FXA193 modem in combination with the so called ToF cable.
The connection socket for communication is the same as the one used to connect the
device display. Please consult the appropriate Operating Instructions for further details.
Fig. 44 shows the necessary connections.
1
44
1
2
3
4
5
6
FieldCare
RS-232
FXA193 modem
Cable and adapter
Level or pressure device display connection compartment
Power supply
The FXA193 modem is a serial modem with a Sub-D9 connector. For this application it can
be connected to either a native serial port or a USB/serial converter. To connect to devices
via the IPC protocol, FieldCare requires:
IPC CommDTM
IPC DTM library
32.2
Connection procedure
Establishing a connection
126
1.
2.
Endress+Hauser
Endress+Hauser
3.
4.
5.
6.
Select Configuration.
The IPC FXA193/291 (Configuration) dialog appears.
7.
8.
127
9.
128
Endress+Hauser
33
33.1
Application
For communication with level and pressure devices via the IPC protocol, connectivity can
be provided with the FXA291 modem in combination with the so called ToF cable.
The connection socket for communication is the same as the one used to connect the
device display. Please consult the appropriate Operating Instructions for further details.
Fig. 45 shows the necessary connections.
1
45
1
2
3
4
5
6
FieldCare
USB
FXA291 modem
Cable and adapter
Level or pressure device display connection compartment
Power supply
33.2
Normally the computer automatically recognizes the FXA291 modem. If this is not the
case, the driver must be installed, see Appendix D. 147
Installing the modem driver
1.
2.
3.
33.3
Connection procedure
129
34
34.1
Application
All new and projected Endress+Hauser field devices use CDI communication as standard
for the protocol. The FXA291 modem provides connectivity to all Endress+Hauser devices
using the so called CDI plug. Fig. 46 shows the necessary connections.
1
46
1
2
3
4
5
6
FieldCare
USB
FXA291 modem
Cable and adapter
Proline flowmeter electronic compartment or connection compartment
Power supply
34.2
Normally the computer automatically recognizes the FXA291 modem. If this is not the
case, the driver must be installed, see Appendix D. 147
Installing the modem driver
1.
2.
3.
34.3
Connection procedure
Establishing a connection
1.
130
Endress+Hauser
Endress+Hauser
2.
3.
4.
5.
6.
Select Configuration.
The CDI Communication FXA291 (Configuration) dialog appears.
7.
Set the COM port to which the FXA291 modem is to be connected and then press
Enter.
131
8.
Do not change the baud rate unless this is explicitly required in the device operating
manual.
9.
132
Endress+Hauser
35
35.1
Application
The TXU10 modem is a USB/CDI modem that may be used with FieldCare for configuring
the following devices:
RIA45/46, RMA42, RIA14/16, all new and projected devices
Together with M12 adapter: TMR3x
Devices without digital communication such as TMT180/181/121, TTR3x, PTP3x, PTC31,
DTT3x, RIA452, RIA141, TMT111 and TMR31x (with M12 adapter) cannot be configured
by FieldCare but require the Readwin2000 software, which can be optionally purchased
with the modem. See the Readwin2000 BA137R/09/en manual for more information.
The FXA291 modem provides connectivity to all Endress+Hauser devices using the so
called CDI plug. Fig. 47 shows the necessary connections.
1
47
1
2
3
4
5
6
FieldCare
USB
TXU10 modem
Cable
Indicators, process transmitter or TMT3x (with M12 adapter)
Power supply
35.2
Normally the computer automatically recognizes the FXA291 modem. If this is not the
case, the driver must be installed, see Appendix D. 147
Installing the modem driver
1.
2.
3.
Endress+Hauser
133
35.3
Connection procedure
Establishing a connection
134
1.
2.
3.
4.
5.
Endress+Hauser
6.
Select Configuration.
The CDI Communication FXA291 (Configuration) dialog appears.
7.
Set the COM port to which the FXA291 modem is to be connected and then press
Enter.
8.
Do not change the baud rate unless this is explicitly required in the device operating
manual.
9.
Endress+Hauser
135
36
36.1
Application
A number of CDI capable field devices can be connected directly to a computer via an
standard USB (A-B) cable. Currently these are:
EngyCal
RA33
1
48
1
2
3
4
5
FieldCare
USB
Cable
EngyCal, RA33
Power supply
36.2
Connection procedure
Establishing a connection
136
1.
2.
Endress+Hauser
3.
4.
5.
6.
7.
8.
Endress+Hauser
137
37
37.1
Application
A number of CDI capable field devices can be connected directly to a computer via a
standard Ethernet cross-cable with RJ45 connector. Examples include:
Promass 100
Promag 100
Promag 400
Fig. 49 shows the necessary connections. If the connection is made via a switch a straightthrough cable can be used. For the location of the Ethernet interface, please see the
Operating Instructions of the device concerned.
1
49
1
2
3
4
5
FieldCare
Ethernet
Category 5 cross-cable
Device e.g. Promass 100, Promag 400
Power supply
37.2
When using the Ethernet TCP/IP connection it is important to note that the computer and
device must have IP addresses within the same domain.
Computer setup
Change the computer's IP address to the same IP address range and subnet mask as
the default address of the device. The procedure for Windows 7 is described in
Appendix A.
37.3
Connection procedure
Establishing a connection
1.
138
Endress+Hauser
Endress+Hauser
2.
3.
4.
5.
6.
139
7.
8.
9.
10. Click X.
The CDI Communication TCP/IP (Configuration) dialog closes and the
Network dialog appears.
11. Connect the device to the computer via the Ethernet cable.
12. In the Network dialog, right-click CDI Communication TCP/IP.
A drop-down list opens.
140
Endress+Hauser
Endress+Hauser
141
38
38.1
Application
The TXU10 or FXA291 modem may also be used with FieldCare for configuring the
following devices:
Thermophant
Ceraphant
Flowphant
RIA1x
1
50
1
2
3
4
5
6
FieldCare
USB
TXU10 modem
Cable
Device
Power supply
51
1
2
3
4
5
6
FieldCare
USB
FXA291 modem
Cable and adapter
Device
Power supply
38.2
Normally the computer automatically recognizes the FXA291 or TXU10 modem. If this is
not the case, the driver must be installed, see Appendix C. 147
142
Endress+Hauser
2.
3.
38.3
Connection procedure
Establishing a connection
Endress+Hauser
1.
2.
3.
4.
143
5.
6.
Select Configuration.
The PCP TXU10/FXA291 dialog appears.
7.
Set the COM port to which the TXU10/FXA291 modem is to be connected and then
press Enter.
8.
Set the number of retries to 3, for example, and then press Enter.
9.
10. Change the baud rate if this is explicitly required in the device operating manual.
11. Click X in the top right.
The PCP TXU10/FXA291 dialog closes and the Network dialog appears.
12. In the Network dialog, right-click PCP TXU10/FXA291.
A drop-down list opens.
144
Endress+Hauser
Plant view
39
Plant view
The network view must first be created before the plant view can be created. The plant
view corresponds to the actual plant topology. The technology view is a hierarchical
representation of the layout process. Any user with the role of plant engineer or higher
can create new plant views or modify existing ones.
The items can be shifted in the plant view. The elements in the plant view can be renamed,
added or deleted.
39.1
CSV files can be exported to FieldCare. Similarly, CSV files containing information can be
imported into a plant.
Importing a plant view
1.
2.
3.
4.
2.
3.
4.
Endress+Hauser
145
Appendix
40
Appendix
40.1
Click Start Control Panel Network and Internet Network and Sharing
Center.
Network Connections opens.
2.
3.
4.
If required:
Enter the Administrator password or confirmation.
5.
6.
Under This connection uses the following items click Internet Protocol Version 4
(TCP/IPv4).
7.
Click Properties.
8.
Note the original values of the IP address and subnet mask of the computer to restore
them if necessary at end of the operation. A computer used in a company network
will normally obtain its address automatically.
Click Use the following IP addresses.
9.
Enter the IP address, subnet mask and default gateway for TCP/IPv4.
The settings for the IP address are accepted.
40.2
If firewalls are in use on the computers on which the servers and clients reside, they must
be programmed to allow mutual access. As firewall configuration is often a matter of
company IT security policy, your system administrator should be consulted before
proceeding. In addition, administration rights are required to perform this task.
The ports available for Fieldgate SFG500 are listed in the table below:
Port number
ID
TCP 60010
TCP_PCPS2_SFG500_PORT
UDP 60015
UDP_IDENTIFY_PORT
UDP 60020
UDP_ANNUNC_PORT
Appendix
2.
In the left pane, click Allow a program or feature through Windows Firewall.
3.
If required:
Enter the Administrator password or confirmation.
4.
Tick the check box beside the program that should be allowed through the firewall
and click OK.
5.
6.
If required:
Enter the Administrator password or confirmation.
7.
In the Windows Firewall with Advanced Security dialog, click Inbound Rules.
8.
9.
40.3
Before the modem can be used, the USB modem driver must be installed on the computer.
Installing the modem driver
1.
With the computer running, plug the connector of the modem into the appropriate
port.
The computer detects the modem as a new piece of hardware.
The Found New Hardware message is displayed.
2.
Select the No, Not This Time option and click Next.
3.
Click Next.
4.
Insert the DVD delivered with the modem into the DVD drive and click Next.
Follow the instructions of the wizard to install the modem as external hardware.
5.
6.
7.
8.
9.
To display the COM port, open the Ports (COM and LPT) node.
40.4
The FieldCare DTM library is regularly updated with all the recently released DTMs. It can
be supplied on DVD as an update service. Alternatively the latest DTMs can be downloaded
from the website of the manufacturer or FDT group. A DTM can also be supplied on a DVD
Endress+Hauser
147
Appendix
with a new device. The DTM must be installed and the DTM catalog updated before
FieldCare can work with a new DTM.
Installing the DTM or CommDTM
1.
Either insert the DVD into the CD drive of the computer or download the DTM from
the manufacturer's website.
Click the Setup.exe.
The installation is started. If AUTORUN is enabled the DVD will start
automatically.
The DTM Setup Wizard starts.
2.
3.
4.
If the installation was successful, a dialog appears with a message to this effect.
Click Finish.
40.5
The FieldCare DTM catalog must be updated if a new DTM is installed. You require
administrator rights to update the FieldCare DTM catalog.
Updating the DTM catalog
1.
2.
In the startup screen click Continue and in the FieldCare dialog click Open.
3.
4.
Click Update.
The search for DTMs is started. This can take a few minutes.
When the search is finished, the new DTM catalog appears.
5.
148
Endress+Hauser
Appendix
40.6
iDTM allows the integration of devices that have no appropriate DTM available. It has,
however, less functionality than a DTM.
If appropriate DTMs become available, the devices that were integrated into the FieldCare
project with the iDTM can be operated with this DTM. For this purpose, the iDTM must be
replaced with the DeviceDTM.
After replacement, the saved information of the iDTM must be entered again
manually in the new DTM.
Replacing an iDTM with a DeviceDTM
1.
2.
3.
4.
6.
7.
Click Yes.
The Device Type (DTM) Information dialog opens.
8.
Click OK.
The changes are accepted.
40.7
Different user roles are available to ensure that only authorized persons have access to the
technology and functions. Every user can log in with a specific role he/she has been
assigned. The user receives authorization for certain functions. Furthermore, the rights
can be defined for a set period.
Endress+Hauser
149
Appendix
40.8
The network topology in FieldCare can be compared against the actual physical network.
This is particularly useful if a device is added to an existing network. A project can be
prepared offline and then uploaded via FieldCare. In this way it is possible to verify the
current topology in the network and the physical topology to make any necessary changes.
Before verifying the network please note that only verified networks are verified for
communication devices that have at least one DTM. Otherwise the Verify Network
menu item is disabled.
Verifying the network
1.
2.
3.
4.
Changes can be made in the context menu for the individual device, e.g. reading or
writing device data or replacing the device type.
Click OK once the necessary changes have been made.
150
Endress+Hauser
Appendix
40.9
If no native DeviceDTMs are available for devices up to PA Profile 3.0, it is possible to use a
PROFIBUS PA Profile. The following profiles are available for the devices:
Actuator Profile DTM
Discrete Input Profile DTM
Discrete Output Profile DTM
Flow Profile DTM
Level Profile DTM
Pressure Profile DTM
52
53
Endress+Hauser
151
Appendix
1.
In the Network dialog, right-click to select the SFG500 item. The SFG500 must be
online for this (green background)
A drop-down list opens.
2.
The SFG500 Web application not only displays the PROFIBUS devices in a livelist but also
the HART devices behind Remote I/Os (ET200M/iSP, Stahl IS1, Turck excom, ABB S900)
and also PROFIBUS PA devices behind Siemens Link.
If HART/PA devices are not recognized when scanning or connecting, the user can check
here whether the devices are even on the bus or whether the Remote I/Os have been
configured.
Multiple remote I/O devices cannot be operated on the bus with two acyclic masters.
152
Endress+Hauser
Index
Index
09
1788-EN2PAR DTM . . . . . . . . . . . . . . . . . . . . . . . . . 62
Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Ethernet TCP/IP interface . . . . . . . . . . . . . . . . . . . . 138
EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Explosion protection . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installing the DTM . . . . . . . . . . . . . . . . . . . . . . . . . 147
Installing the USB modem driver . . . . . . . . . . . . . . . 147
IP address . . . . . . . . . . . . . . . 66, 68, 92, 101, 108, 146
IPC interface . . . . . . . . . . . . . . . . . . . . . . . . . . 126, 129
ISS interface . . . . . . . . . . . . . . . . . . . . . . . . . . 122, 125
NIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
153
Index
154
Endress+Hauser
www.addresses.endress.com