UNIVERSIDAD FIDLITAS
Facultad de Ingenieras
Escuela de Ingeniera Civil
iv
DEDICATORIA
AGRADECIMIENTOS
Agradezco de corazn:
NDICE GENERAL
Introduccin .................................................................................................... 2
1.1 Antecedentes ........................................................................................................... 2
1.2 Justificacin .............................................................................................................. 3
1.3 Objetivos ................................................................................................................... 4
1.3.1 Objetivo general .......................................................................................... 4
1.3.2 Objetivos especficos ................................................................................. 4
1.4 Alcances y limitaciones........................................................................................... 5
1.4.1 Alcances ....................................................................................................... 5
1.4.2 Limitaciones ................................................................................................. 5
1.5 Producto esperado .................................................................................................. 5
CAPTULO II......................................................................................................... 7
2
xi
xii
xiii
xiv
xv
NDICE DE FIGURAS
xvi
xvii
NDICE DE TABLAS
Tabla 1 Zonas ssmicas de Costa Rica tomado de CSCR (2010) ..................... 19
Tabla 2 Factores de direccionalidad tomado de (Acua, 2014) ......................... 24
Tabla 3 Factores topogrficos tomado de (Acua, 2014) .................................. 25
Tabla 4 Constantes de exposicin de terreno tomado de (Acua, 2014) .......... 26
Tabla 5 Coeficientes de presin de velocidad tomado de (Acua, 2014) .......... 27
Tabla 6 Coeficientes de presin Neta tomado de (Acua, 2014) ...................... 28
Tabla 7 Factores de longitud efectiva tomado de (Acua, 2014) ....................... 32
Tabla 8 Factores de reduccin de capacidad de AASHTO LRFD .................... 55
Tabla 9 Factores de reduccin de carga lateral del Manual de ingeniera de
Canad ...................................................................................................................... 55
Tabla 10 Dimensiones para varias inclinaciones ............................................... 69
Tabla 11 Clculo de la presin neta de diseo .................................................. 71
Tabla 12 Clculo de presiones mximas sotavento barlovento ......................... 71
Tabla 13 Presin y carga de diseo de viento ................................................... 72
Tabla 14 Cantidad de materiales y peso total .................................................... 72
Tabla 15 Peso total de la estructura .................................................................. 72
Tabla 16 Clculo de la fuerza de sismo ............................................................. 73
Tabla 17 Cargas y combinaciones de carga ...................................................... 74
Tabla 18 Reacciones en los soportes de la estructura ...................................... 76
Tabla 19 Fuerzas cortantes mximas en los apoyos ......................................... 76
Tabla 20 Clculo de placa base para columna .................................................. 78
Tabla 21 Resistencias reducidas de los pernos de anclaje ............................... 80
Tabla 22 Datos de entrada para diseo de pilar de concreto ............................ 81
Tabla 23 Longitud elstica del pilar de concreto ................................................ 82
Tabla 24 Capacidad ltima del pilar................................................................... 83
Tabla 25 Capacidad del pilar de concreto ......................................................... 83
Tabla 26 Capacidad de soporte lateral del pilar de concreto ............................. 85
Tabla 27 Capacidad de soporte del suelo al utilizar un pilote helicoide ............. 87
xviii
xix
PALABRAS CLAVE
Diseo, Estructuras, Paneles, Solares
LISTA DE TRMINOS
Asentamiento: desplazamiento vertical de la estructura debido al cambio de
volumen del suelo donde se encuentra, puede ser debido a tres causas: propiedades
plsticas del suelo, consolidacin primaria del suelo o consolidacin secundaria del
suelo.
Asentamiento elstico: Desplazamiento vertical asimtrico de una estructura que
provoca una diferencia de nivel entre los puntos donde se cimenta la estructura.
Capacidad de carga del suelo: Es la resistencia del suelo de cimentacin ante la
solicitacin de carga de la estructura. La capacidad de carga del suelo es menor a la
capacidad ltima del suelo
Diseo LRFD: Load and Resistance factor design, mtodo de diseo de estructuras
de acero en el cual las cargas de servicio se multiplican por factores de carga y
determinan la solicitacin ltima de la estructura. En este diseo la solicitacin
mxima de la estructuras se compara con la capacidad nominal de la estructura
reducida por un factor de reduccin.
Diseo por esfuerzo permisible: mtodo de diseo de estructuras de acero donde
la estructura al ser sometida a las combinaciones de cargas nominales estas no
superen al valor admisible permitido, la relacin entre solicitacin y capacidad
admisible se denomina factor de seguridad
Diagrama de interaccin: representacin grfica del lugar geomtrico de las
combinaciones de carga axial y un momento flector que soporta una columna
Distorsin angular: cociente entre el asentamiento diferencial entre dos puntos
vecinos y la distancia que los separa, define un ngulo que se produce por un
asentamiento no homogneo.
Estructura tipo marco: estructura de ingeniera compuesta por columnas y vigas de
concreto o acero utilizada como parte de un sistema sismo resistente.
xx
Suelo cohesivo: suelo compuesto mayormente por arcillas y limos, cuya resistencia
se debe a los enlaces qumicos de sus granos que le dan su caracterstica de
cohesin, conforme
Pierden agua su volumen varia provocando el asentamiento de las estructuras que
se soportan en ellos.
Suelo no cohesivo (granular): suelo compuesto mayormente por grava, arena y
arcilla en menor proporcin, cuya resistencia se debe al rozamiento interno entre sus
granos y soporta cargas en funcin de su compactacin.
Panel fotovoltaico: elemento plano construido de materiales semiconductores que
desprenden electrones al recibir luz solar. Se organizan en celdas que se conectan
en arreglo Matricial para formar un panel.
Perno de anclaje: Elemento de acero, longitudinal que fija una estructura a su
cimentacin sirviendo de ancla, pueden ser instalados antes de la colada del
concreto o ser instalados despus de fraguado el concreto.
Pilote: Elemento de cimentacin esbelto, hecho de acero, madera o concreto,
transmiten carga por friccin de su cuerpo con el suelo, la punta o una combinacin
de ambas
Pedestal: elemento de concreto reforzado que sirve de elemento base para soportar
una columna, el pedestal sirve de conexin entre una columna y una zapata.
Pilote helicoide: Elemento de cimentacin esbelto hecho de acero con una o varias
hlices o helicoides que le permiten soportar carga
Pilar: elemento de cimentacin cilndrico de concreto reforzado o no que transmiten
carga por friccin de su cuerpo con el suelo, la punta o una combinacin de ambas
Zapata: elemento de cimentacin hecho de concreto reforzado o no, de geometra
rectangular o cuadrada que trabaja a compresin
Zapata combinada: elemento de cimentacin hecho de dos zapatas.
xxi
RESUMEN EJECUTIVO
CAPTULO I
INTRODUCCIN
1 Introduccin
El presente documento presenta una gua de diseo estructuras de soporte
para paneles solares en parques de generacin acordes con las condiciones
climticas y ssmicas de Costa Rica.
El documento toma en cuenta
los
1.1
Antecedentes
En Costa Rica, tradicionalmente se ha generado electricidad haciendo uso de
fuentes de energa, hidrulica, fsil y elica (desde los aos 80). Sin embargo, la
generacin de energa elctrica, a travs de la energa del sol ha sido un campo que
poco se ha desarrollado, aun cuando tcnicamente existen las herramientas para su
aprovechamiento.
La problemtica de la variabilidad de los precios de los combustibles y las
restricciones al desarrollo de grandes proyectos hidroelctricos ha obligado a que la
matriz de energa para Costa Rica empiece a tomar en consideracin otras fuentes,
la solar por ejemplo.
Costa Rica en su ley 7200 permite al ICE suscribir contratos para la compra de
energa, incluyendo energa solar. Sin embargo, la generacin en parques solares es
un tema que solamente hasta el momento el instituto Costarricense de electricidad
(ICE) ha desarrollado, el (ICE) construy el primer parque de generacin mediante
paneles solares esto en el ao 2014 en la zona de Guanacaste con una capacidad
de 1MW.
A nivel de normativa, en Costa Rica existen normas que de manera general
determinan los parmetros de diseo que las estructuras deben soportar; sin
embargo, en el campo especfico de las estructuras para soporte de paneles solares
no hay una norma tcnica que indique los parmetros de diseo de estas
estructuras.
1.2
Justificacin
Costa Rica es un pas que se orienta a generar su energa utilizando como
que podr ser utilizado tanto para fines acadmicos como profesionales y permitir
desarrollar soluciones estructurales de forma clara y sencilla.
Como parte de la Gua se realizar un ejemplo de aplicacin utilizando los
paneles solares de la marca Panasonic de la serie HIT.
1.3
Objetivos
1.4
Alcances y limitaciones
1.4.1 Alcances
1. Se realizar un procedimiento para el diseo, segn el cdigo ASCE y cdigo
ssmico de Costa Rica en su Versin final del 2010.
2. La gua se realizar para la zona comprendida por el territorio de Costa Rica,
especficamente en las zonas de alto potencial de produccin de energa solar:
Guanacaste y Puntarenas.
3. Se utilizan elementos de cimentacin, realizados con concreto armado:
Zapatas combinadas, pilares de concreto y pilotes helicoides.
4. Los paneles por utilizar son los fabricados por Panasonic de la serie HIT.
5. Se utiliza como norma de diseo en acero la norma AISC.
6. Se realizar un clculo de los costos de las estructuras propuestas.
1.4.2 Limitaciones
1. Este documento solamente toma en consideracin los parques de generacin
solar para venta de energa y no es aplicable a situaciones de uso residencial.
2. No se toman en consideracin las zonas anegadas o en la superficie marina.
3. No se estudian las estructuras para fijar paneles en estructuras de techo.
4. No se analizan cimentaciones con pilotes hincados.
5. No se analizan estructuras mviles para seguimiento del sol.
6. Solamente se utiliza, como material para la estructura, aceros considerados en
la norma AISC.
1.5
Producto esperado
Se elaborar una gua de diseo de estructuras de soporte de paneles solares
CAPTULO II
MARCO TERICO
2 Marco terico
2.1
La energa Solar
generacin fotovoltaico.
2.2
Paneles solares.
Estructura de soporte.
A continuacin se da una explicacin de los elementos.
siguientes
convierten la corriente elctrica directa generada por los paneles solares a corriente
alterna. Estos equipos son de gran importancia en parques de generacin o
generacin de auto consumo.
En ciertas ocasiones, se utilizan bateras para almacenar la energa producida
por los paneles solares. Las bateras se instalan en parques de generacin as como
en aplicaciones de autoconsumo; su instalacin y seleccin sale del alcance de este
documento.
2.2.2 Sistema de conexin
Los sistemas de generacin fotovoltaicos requieren de un sistema que conecte
los paneles y lleve la energa al punto de conexin para su consumo o venta.
Este sistema de conexin est constituido por un conjunto de conductores
aislados que recorren la estructura de soporte de los paneles hasta un punto de
acondicionamiento e interconexin.
2.2.3
Paneles solares
Los paneles solares segn lo planteado en Sachs (2009) y Sick (1996) son
10
11
12
el mejor soporte. Es la
13
14
2.5
3kW.
El campo de aplicacin del presente documento lo constituyen los parques de
generacin como la planta Solar Miravalles la cual se caracteriza a continuacin.
2.6
15
2.7
2.8
16
17
nula
estructura.
En el caso de estructuras para soportar paneles solares, la carga temporal est
compuesta por el personal de mantenimiento y construccin.
Se asume que para montaje y mantenimiento se necesitar
un operario
18
Sitio tipo S1: Un perfil de roca o suelo rgido o denso con propiedades
semejantes a la roca.
19
T = 0,08N, para edificios tipo dual con sistemas duales de marcos y muros
estructurales, muros arriostrados o muros de mampostera.
20
para el tipo de instalacin, se hace uso de la aceleracin mxima del espectro, segn
lo indicado en el CSCR 2010.
9. Factor de sobre-resistencia (SR): La sobre-resistencia es igual a 2 para
estructuras tipo marco, dual y muro.
10. Factor espectral dinmico (FED): factor que modifica la aceleracin de un
sistema de un grado de libertad con respecto a la aceleracin pico efectivo de
diseo. Depende de la zona ssmica, del sitio de cimentacin, de la ductilidad
global asignada al sistema estructural, de su periodo de vibracin y de su
amortiguamiento.
11. Coeficiente ssmico (C): Este coeficiente se obtiene mediante la siguiente
ecuacin:
C=
Ecuacin 1
Dnde:
= aceleracin pico efectivo de diseo en la base de la estructura.
= Factor de importancia de la edificacin
= Factor espectral dinmico
= Factor de sobre-resistencia
12. Cortante en la base (V): Fuerza ssmica horizontal en cada direccin ortogonal
cuyo valor se calcula mediante la siguiente frmula:
V= Ecuacin 2
Dnde:
V = Cortante en la base o sumatoria de todas las fuerzas ssmicas horizontales
en cada direccin ortogonal.
C = Coeficiente ssmico.
W =peso total de la edificacin para efectos ssmicos
21
Ecuacin 3
Donde = SRei :
=Desplazamiento inelstico absoluto horizontal del nivel i
=Deriva inelstica o desplazamiento inelstico horizontal entre el nivel i y el
nivel adyacente
=Factor de desplazamiento inelstico, para edificios de un piso igual a 1
=Ductilidad global asignada
= Factor de sobre-resistencia
, =Desplazamiento elstico absoluto de nivel i y deriva elstica entre el
nivel i y el nivel adyacente inferior respectivamente
14. Reclculo del periodo del primer modo de vibracin: Una vez obtenidos los
desplazamientos calculados se debe recalcular el periodo con base en la
siguiente ecuacin:
= 2 =1
=1
Ecuacin 4
Donde:
=Desplazamiento elstico absoluto de nivel i debido a las fuerzas ssmicas
horizontales
= Aceleracin de la gravedad
De ser necesario se debe ajustar la aceleracin espectral dinmica y los dems
trminos para analizar la estructura con el primer modo obtenido.
22
23
Utilizar las definiciones del ASCE 7-10 y tratar la estructura como un edificio
abierto.
Con pendiente nica y utilizar la pendiente de montaje de los paneles solares
como el pendiente del techo indicada en la norma.
internas de estructuras
indican que es posible realizar pruebas con tnel de viento para reducir las cargas.
Las pruebas con tnel de viento escapan al alcance del presente trabajo.
A continuacin se describe el mtodo direccional del ASCE -7.
24
25
agua. En esta categora se incluye pisos de barro liso, salinas suaves y superficie de
hielo lisas.
9. Categoras de exposicin de la instalacin en el terreno.
10. Coeficiente de topografa (Kzt): Este factor puede ser determinado por medio de
la tabla 3.
26
1+1.7
1+1.7
Ecuacin 6
33
= ( )1/6 Ecuacin 7
Dnde:
=Intensidad de la turbulencia a la altura z
=Es el equivalente a la altura del edificio definida como 0.6h, pero no puede
ser menor a zmin
, =Factores tomados como 3,4
1
=
+ 0.63
1+0.63(
)
Ecuacin 8
= (33) Ecuacin 9
Los factores l y aparecen en la siguiente tabla
27
15
Ecuacin 12
Dnde:
= Presin de velocidad
G = Factor de rfaga
= Coeficiente de presin neta, obtenido de las tabla 6
28
29
30
Caso zona 1
< Lp :
Dnde:
300
Ecuacin 16
=
Caso zona 2
Ecuacin 17
< Lb <
1 + 1 + 2 ( )2
1 =
2 =
Ecuacin 18
Ecuacin 19
4 2
( )
Ecuacin 20
( )
= [ ( ) ( )] Ecuacin 21
= ( ) Ecuacin 22
Y para secciones tipo cajn
=
=
3750
5700
Ecuacin 23
Ecuacin 24
( )
= [ ( ) ( )]
Ecuacin 25
31
Caso zona 3
=
< Lb
2 1 1 + 2 1 2 /2( / )2
Ecuacin 26
5700
/
Ecuacin 27
Ecuacin 28.
32
Ecuacin 30.
=Parmetro de esbeltez.
= Lmte de fluencia del acero.
=Mdulo de elasticidad del Acero.
=Longitud no arriostrada.
=Factor de largo efectivo.
=radio de giro.
2
= ((0.658) ) , 1.50
= (
0.877
2
) , > 1.50
Ecuacin 31
Ecuacin 32
0.2 utilizar:
33
Si
+ 9 (
) 1.0 Ecuacin 33
+ 9 (
) 1.0 Ecuacin 34
34
al
suelo
de
cimentacin,
estos
elementos
son
los
denominados
cimentaciones.
Tipos de cimentaciones
Villaz (2004), plantea la existencia de dos tipos de cimentaciones: directas e
indirectas, que a continuacin se describen.
Las cimentaciones directas son elementos donde las partes verticales de la
superestructura se extienden al terreno de cimentacin y descansan en l
directamente; se utiliza un ensanchamiento de su seccin trasversal, entre ellas
tenemos: zapatas aisladas, combinadas o corridas, pilares de concreto etc.
Las cimentaciones indirectas son aquellas cimentaciones donde se alcanza el
suelo de cimentacin, al usar elementos intermedios como: pilotes o pilas de
cimentacin etc.
En el caso de las estructuras de soporte para paneles solares en Billups (2011),
Miller (2009), y Lutenenegger
cimentaciones:
Cimentaciones de balasto.
Pilotes hincados.
Pilares de concreto.
35
Zapatas combinadas.
Pilotes helicoides.
Pilares de concreto.
En la siguiente seccin se presenta una caracterizacin de los tipos de
Ecuacin 35
36
2 2 1 2
1 +2
Ecuacin 36
( )
Ecuacin 37
Ecuacin 38
Ecuacin 39
Dnde:
=Longitud de la placa
=Capacidad permisible del suelo portante
=Carga de servicio mxima
=Carga de peso propio de la cimentacin supuesta como 10% de
=rea mnima de diseo
Se debe definir el valor ancho de placa luego
=
= <
Ecuacin 40
Ecuacin 41
Donde:
B=Ancho de cimentacin de diseo
A=rea de diseo
=Carga por unidad de rea impuesta sobre el suelo portante
=Capacidad ltima del suelo de cimentacin
=Factor de reduccin de capacidad portante segn cuadro 3.1 del cdigo de
cimentaciones
37
= 0.85
Ecuacin 42
= ( )
2
Ecuacin 43
Ecuacin 44
= 0.003
Ecuacin 45
Donde:
> 0.002 , deformacin para garantizar fluencia del acero.
1=0.85 factor de ajuste del bloque de compresin para concreto de 21 MPa.
=factor de reduccin a flexin.
Se debe respetar una cuanta mnima de acero la cual est dada por la
siguiente expresin:
=
1.4
Ecuacin 46
Al hacer uso de las ecuaciones 42 a 45, se deduce una expresin que permite
encontrar el rea de acero a flexin, dicha expresin se presenta a continuacin:
0.59
2
=0
Ecuacin 47
38
Ecuacin 48
Dnde:
= Cortante ltimo proveniente de las cargas externas de los dos modos de
falla.
= Capacidad de cortante del elemento.
= Factor de reduccin para cortante = 0,75.
Para el clculo del valor de cortante se deben utilizar las siguientes
expresiones:
Cortante total en dos direcciones:
Ecuacin 49
2 = ( + )( + )
Ecuacin 50
39
Ecuacin 51
= 0.17(1 + )
= 0.083( + 2)
Ecuacin 52
Ecuacin 53
Donde:
= relacin del lado largo al lado corto del dado de concreto
= factor de ajuste por la posicin de la columna en la zapata igual a 40
= permetro alrededor del rea que penetra la columna en caso de falla
Para el clculo del valor de cortante en una direccin se deben utilizar las
siguientes expresiones:
Cortante total en una direccin:
= 2 ( + /2)
Ecuacin 54
1 =
Ecuacin 55
40
donde:
=Lado largo de la zapata combinada.
=altura de empotre.
=lado de la columna perpendicular a la zapata.
=lado de la columna paralelo a la zapata.
La capacidad de cortane en una direccion debe cumplir con la siguiente
relacin:
= 0.17
= Factor de reduccin para cortante = 0,75.
Ecuacin 56
41
cimentacin:
1. Definicin de dimensiones preliminares del pilar de cimentacin.
2. Clculo de la capacidad soportante usando la capacidad de punta y fuste
mediante el mtodo esttico segn ACG (2009).
42
= =0 0
Ecuacin 57
0
=Esfuerzo vertical efectivo promedio en el tramo
=Permetro
=Lngitud del tramo actualizado
= coeficiente friccin entre suelo no cohesivo y pilotes de concreto colado en
sitio de 1.0
Capacidad por la base
=
Ecuacin 58
43
Dnde:
=Esfuerzo vertical efectivo a nivel de la base del pilote
= Factor de capacidad de carga para una fundacin profunda
=rea seccional del pilote en la base
Y est dado por = 50
Ecuacin 59
Ecuacin 60
Ecuacin 61
Dnde
1 =0.65 para forma redonda
2 3 = 1 0.75/ , con =longitud del pilar
= 1, factor de excavacin mtodo seco.
44
Para los pilotes cortos, la resistencia ltima lateral del pilote o pila est
gobernada por la presin pasiva del terreno circundante.
Para los pilotes largos, la resistencia ltima lateral del pilote o pila est
gobernada por la resistencia ltima o la resistencia de fluencia del pilote o pila.
y la falla ocurre cuando el suelo circundante al pilote o pila llega a tener aplicada
una carga lateral igual a su resistencia ltima.
Para los pilotes largos, el mecanismo de falla ocurre cuando una rtula plstica
se forma en el punto de mximo momento; la falla ocurre cuando el momento flector
es igual al momento resistente de la seccin del pilote My.
El mtodo de Broms brinda un conjunto de ecuaciones y grficos que permiten
determinar la deflexin en el nivel de suelo y el momento que es capaz de resistir
debido a carga lateral.
45
46
Pilotes cortos
Pilotes
largos
Curvas para suelos no-cohesivos segn mtodo de Broms 1964
Pilotes cortos
Pilotes largos
Los criterios para determinar si el pilote es corto o largo aparecen en [7] y las
expersiones se presentan a continuacin.
=Longitud elstica de suelo pilote
47
= 0.75
Ecuacin 62
= 0.75
Ecuacin 63
2.0
1.5
(2014),
cimentar las estructuras de soporte de los paneles solares sin necesidad de realizar
un movimiento de excavacin de gran escala.
A continuacin se presentan las caractersticas de los pilotes helicoidales y el
procedimiento para obtener su capacidad portante.
Pilote helicoidal
Un pilote helicoidal, segn lo define el cdigo internacional de construccin
(IBC) , es un elemento que se utiliza en fundaciones profundas y que consiste en un
cuerpo central formado por un tubo de acero al cual se le agregan una o ms placas
de acero con un ngulo de ataque definido para formar un
helicoide
llamadas
48
El IBC define
pilotes
49
= ( + + 0.5 )
Ecuacin 64.
Donde:
= Capacidad ltima vertical.
= rea proyectada de la placa helicoide.
c =Cohesin del suelo .
= factor de capacidad de soporte cohesin del suelo.
= Presin de sobrecarga efectiva.
=factor de capacidad por sobrecarga.
= Peso unitario efectivo del suelo de estudio.
B = ancho de la cimentacin.
= factor de capacidad de carga.
=Carga ltima de la placa helicoide.
Segn lo planteado por A.B.Chance (2010), el factor que incluye B se
desprecia, pues realiza un aporte despreciable mientras B no sobre pase los 4
metros.
Segn lo anterior, la capacidad ltima est dada por las siguientes expresiones:
Suelo caso general
= ( + ) Ecuacin 65
Suelo cohesivo
=
Ecuacin 66
Donde:
= factor de capacidad de soporte cohesin del suelo igual a 9.
= rea proyectada de la placa helicoide.
c =Cohesin del suelo.
Suelo no cohesivo
=
Ecuacin 67
50
Donde:
= Capacidad ltima vertical.
= rea proyectada de la placa helicoide.
=factor de capacidad por sobrecarga.
El factor se lee del siguiente grfico tomado de A.B.Chance (2010).
Ecuacin 68
Donde:
Pu= capacidad ltima.
C=cohesin del suelo portante.
Nc=factor de capacidad de soporte debido a la cohesin.
q=sobre carga en la posicin de la placa.
Nq=factor de capacidad de soporte debido a suelos granulares..
51
K constante de correlacin.
T torque de instalacin.
llamadas p-y.
De acuerdo con el IBC la capacidad de carga permisible ser no ms del 50%
de la carga que produce un movimiento lateral bruto de 25 mm en la seccin ms
baja de la parte superior de la fundacin y la superficie del suelo.
Segn el manual de diseo del fabricante Magnum Piering Inc, (2010) y basado
en Puri, Stephenson, Dziedzic, y Goen (1984), la expresin que permite determinar
la relacin de carga horizontal y desplazamiento horizontal, se presenta a
continuacin:
52
= [ ( ) + (
)]
Ecuacin 69
= [ ( ) + (
)]
Ecuacin 70
Dnde:
=Mdulo de Young del material del pilote,
=Momento de Inercia del pilote,
=Mdulo elstico de la sub-rasante,
=Carga lateral aplicada,
=Momento aplicado,
y estn dadas por:
= / 1/5
Ecuacin 71
= / 1/5
Ecuacin 72
53
A continuacin se presentan las tablas con las constantes para cada caso.
54
de pilares
55
56
Ecuacin 73
Ecuacin 74
= , , , , ,
Ecuacin 75
57
2
3
valores
1 , 1.5 0.7 + 0.3
,
,
1.5
Ecuacin 76
Ecuacin 77
58
Dnde
=rea de apoyo de la cabeza del perno
=capacidad del concreto
=distancia de la superficie interna del fuste en forma en L o J hasta la parte
externa de la punta del perno en forma de L o J.
=dimetro exterior de un anclaje
, =factor de ajuste por fisuras, para concreto fisurado para cargas de servicio
, = 1.4 , en caso contrario utilizar , = 1.
Resistencia al desprendimiento lateral del concreto
Para el clculo de la capacidad del desprendimiento lateral de anclajes con
cabeza se utilizan las siguientes expresiones.
Si > 2.5 1 , siendo 1 la distancia al borde en direccin a la aplicacin de
cortante, entonces
= 131
Ecuacin 78
cortante. En caso de que 2 < 31 , el valor debe ajustarse con el factor (1+2 ),
1
dnde,
1.0 2 3.0).
1
Ecuacin 79
59
Ecuacin 80
= , , , , ,
Ecuacin 81
Dnde:
=rea proyectada por un nico anclaje en una profundidad con una
distancia a los ejes de 1.51
60
1
2
1+
31
1 , dnde es la
2
1 ,2 1.51 0.7 + 0.3 1.5
Ecuacin 82
Ecuacin 83
61
+
1.2
Ecuacin 84
Ecuacin 85
2 = 0.85 1 2 2 2 Ecuacin 86
1
Dnde
1 = rea de la placa de acero
2 = rea del concreto
=factor de reduccin de capacidad igual a 0.6
La carga ultima del concreto por aplastamiento est dada por
62
= 1.7 1
Ecuacin 87
(0.950.8 )
2
Ecuacin 90
= + 1 Ecuacin 91
=
Ecuacin 92
0.95
2
0.8
2
Ecuacin 93
Ecuacin 94
Ecuacin 95
Ecuacin 96
63
Ecuacin 97
Si ( + )2 4 0 , entonces = 0.25( + (( + ) 4)
=factor de reduccin de capacidad igual a 0.95
64
CAPTULO III
GUA DE DISEO Y
RESULTADOS
65
66
3.2
aplicacin.
Datos geotcnicos del sitio supuesto para el diseo
A continuacin se presentan las propiedades geotcnicas y el perfil
estratigrfico del Tipo de suelo de caso de estudio:
Suelo limo arenoso suave con Cu= 22KN/m2, E=16MN/m2, Gama=17.5
KN/M3, Espesor de 2.25m .
Suelo limo arenoso medio
67
68
69
15
20
25
30
35
10
45
Ancho del
Altura
Marco,[m mxima,[m]
B
2
3,1
1,118
3,0
1,381
2,9
1,635
2,7
1,880
2,6
2,113
3,1
0,849
2,2
2,534
70
Estructura prototipo
Como primera aproximacin de la estructura se utilizaron dos marcos conectados por
piezas horizontales para el montaje del panel.
Para maximizar el uso de los materiales se acomodan 14 Paneles en una pieza de
6m.
Se puede ver en la siguiente figura el prototipo de estructura de soporte dibujado con
la aplicacin Robot Structural Analisys .
71
Fuerza de Viento
Kz ,coeficiente de exposicin
0,85
Kzt ,coeficiente de topografa
1
Kd,Factor de direccionalidad
0,85
G,Factor de rfaga
0,85
Velocidad de Viento
68,35
ngulo de la estructura
45
Altura media de la estructura H [m]
2,117
Longitud paralela al viento ,L
2,235
Relacin 0.25<H/L<1
0,95
qz
7,34
psf
S cumple
Presin de Velocidad
Roof Angle
45o
Caso A (=0)
P,winward
P,Leeward
Caso B (=0)
P,winward
P,Leeward
A
B
psf
-11,75
-13,22
psf
-16,89
-5,14
Caso A (=180)
P,winward
P,Leeward
Caso B (=180)
P,winward
P,Leeward
psf
16,16
18,36
psf
19,10
10,28
72
19,10
0,91
Ancho tributario
0,78884
0,78955
0,78992
0,78925
psf
KN/m2
Carga lineal
0,720
0,721
0,721
0,720
KN/m
KN/m
KN/m
KN/m
KN/m
kg
u
kg
kg
kg
kg
73
Combinaciones de carga
Las combinaciones de carga utilizadas en el diseo de la estructura son las
combinaciones establecidas por el ASCE. Estas combinaciones toman en
consideracin una cantidad superior de casos donde interviene la carga de viento a
diferencia de las combinaciones presentadas por el Cdigo Ssmico de Costa Rica. A
continuacin se muestra el reporte de las combinaciones de carga utilizadas.
Case
1
2
3
4
5
6
7
8
9
10
11
12
13
Etiqueta
DL1
DL2
WIND1
SEIS1
LL2
Tipo de anlisis
Static - Linear
Static - Linear
Static - Linear
Static - Linear
Linear Combination
Linear Combination
Static - Linear
Linear Combination
Linear Combination
Linear Combination
Linear Combination
Linear Combination
Linear Combination
74
Case
1
2
3
4
7
Etiqueta
DL1
DL2
WIND1
SEIS1
LL2
Tipo de anlisis
Static - Linear
Static - Linear
Static - Linear
Static - Linear
Static - Linear
Caso
1:DL1
2:DL2
3:WIND1
4:SEIS1
7:LL2
Tipo de carga
self-weight
uniform load
uniform load
nodal force
uniform load
Aplicada a
1to9 11to16 18to23
8 11to16 18
8 11to16 18
4to6
8 11to16 18
75
76
12,68
-2,4
10,47
-8,17
kN
kN-m
Fx,[kN]
0,43
1,67
Fy,[kN]
2,74
8,42
77
DL
1
1
1
1
1
1
1
0,6
0,6
LL2
0
1
0,75
0
0
0,75
0,75
0
0
WIND1
0
0
0
1
0
0,75
0
1
0
SEIS1
0
0
0
0
0,75
0
0,7
0
0,7
DL,[kN]
0,92
1,14
LL,[kN]
3,37
5,01
WIND,[kN]
5,13
1,3
SEIS,[kN]
0,5
0,5
Valor
mximo
,[kN]
1
2
3
4
5
6
7
8
9
2,1
10,4
8,3
8,5
2,8
13,2
9,0
7,7
1,9
78
3.6
fy
f'c
c
A1
A2
PumaxC
Pu1
Pu2
bf
d
N
B
m
n
n*
L
tp
tp
tp
5/16"
79
3.7
Ncbg
Capacidad Nominal de traccin Ncbg
150
21
400
35
12,5
45
50
4
123
mm
Mpa
Mpa
mm
mm
mm
mm
-mm2
0,75
147
KN
40000
11025
366606,0556
0,14893617
0,985714286
1
1
195268,5316
0,75
146
mm2
mm2
N
----N
KN
80
1
123
20616,7
20616,7
82,5
62
mm2
N
N
KN
KN
32997,266
49
37
N
KN
KN
0,65
rea Avco
Avco
180000
rea Avc proyectada lateral
Avc
225000
Altura del elemento que soporta cortante
ha
300
Distancia ajustada al borde mas de un borde
ca'
200
Resistencia de Cortante del concreto
Vcbg
38005
Resistencia reducida del Cortante del concreto
Vcbg
25
7. Anlisis al desprendimiento del concreto por cabeceo debido a cortante
Factor de ajuste kcp
kcp
2,00
Capacidad Mxima a traccin
Ncbg
195268,53
Resistencia de cortante "Pryout" Vcpg
Vcpg
390537,0631
Resistencia reducida de cortante "Pryout" Vcpg
Vcpg
254
N
N
fisurado
mm2
mm2
mm
mm
N
KN
--N
N
KN
147
146
62
37
25
254
KN
KN
KN
KN
KN
KN
81
3.8
KN
KNm
m
m
Momento ltimo
8.17
elasticidad del
MPa
21.500
pilar (concreto)
Momento de
Inercia de la
0,00201 4
seccin del pilar
Mdulo de
deformacin en la
16
MPa
punta del pilar
Tabla 25 Datos de entrada para diseo de pilar de concreto
82
/3
0,3
Ancho del pilote
a
M
0,3
Base del pilote
b
M
Tabla 26 Longitud elstica del pilar de concreto
Una vez verificado como pilote corto es posible aplicar el mtodo de Broms para
calcular la capacidad lateral del pilar. Seguidamente se procede a determinar la
capacidad ltima del suelo portante la cual determina la capacidad ltima del suelo.
Los resultados se presentan a continuacin:
Capacidad de punta
Ab
rea de la base
Factor de capacidad de carga para
N*
pilotes en arcilla
Resistencia al corte no drenada
CuxN*xAb
Capacidad de fuste
Valor de adherencia para pilote pre
excavado
0,71
----
22
/2
14
7150
KN
0,3
/2
m
2
1.41
10.11
KN
24.1
KN
1.5
83
70686 2
rea de concreto
21
Capacidad del concreto
MPa
Capacidad de la columna de
1009
concreto
KN
Se selecciona como
capacidad ltima la menor
24.1 KN
14.5
KN
84
b
1
2
E
I
85
0,00895
21
1,5
Cs
187,9
/
/
5
8.47
del Pilote
Mdulo de seccin
m3
perpendicular al
plano de carga
Mdulo de fluencia
MPa
de concreto
Profundidad de
m
empotre
-Factor de forma
Momento resistente
KN-m
del pilar
--relacin D/b
--relacin ec/b
6.25
Ledo de la curva
Capacidad lateral
ltima
Capacidad
12.4
KN
reducida = 1
Tabla 29 Capacidad de soporte lateral del pilar de concreto
12.4
KN
Se puede notar que haciendo uso del factor de reduccin de capacidad lateral
del AASHTO se verifica que el pilar es capaz de soportar de manera segura la
carga lateral mxima debida al mximo momento flector.
En la siguiente pgina se presenta la curva de clculo de la capacidad lateral
tomada de (Hannigan, 1998).
86
87
88
siguiente seccin se realiza la eleccin del pilote helicoide adecuado para soportar
las cargas axiales como laterales.
89
Dimensiones del pedestal del concreto: 145mm x 160 mm, altura del
pedestal: 300 mm (determinadas del diseo de la placa y los pernos de
anclaje.).
90
Valor Unidades
Carga de servicio
Momento ltimo 1
Momento ltimo 2
Carga ltima 1
Carga ltima 2
Longitud
Dimensin ""
Dimensin ""
Dimensin /2
13,1675
-2,4
-8,17
12,68
10,47
1,47
0,25
0,95
1,72
KN
KN-m
KN-m
KN
KN
m
m
m
m
Dimensin
3,43
91
Dato
Valor
Unidades
Altura de pedestal
0.145
m
Ancho de Pedestal
0,160
m
Espesor del pedestal
0,3
m
0,45
Ancho de la zapata B
m
3,43
Largo de la zapata L
m
Peralte de la zapata H
0,25
m
Peso Volumtrico del
0,440
concreto
3
Peso volumtrico del
24
concreto
/3
9.6
Peso propio de la zapata
KN
Tabla 32 Peso propio de la zapata combinada
12.68 + 10.47
= 14.99 /2
1.54
92
Tramo
Longitud ,[m]
0.25
2.23
0.95
1.687
10.995
6.413
2.61
6.26
3.0459
0.63
0.31
Momento ltimo
flector [KN-m]
Momento ltimo
flector,[Ton-m]
0.26
Tramo c
93
Tramo
a
Tramo b Tramo c
0,26
0,63
0,31
,
2
Asreq 1,
0,41
0,98
0,47
2,15
2,15
2,15
As mn, 2
2,025
2,025
2,025
As temp, 2
2
0,55
1,31
0,63
4/3 x Asreq,
Cantidad de varillas
3
3
3
# de varilla
3
3
3
2
0,71
0,71
0,71
rea ,
2,13
2,13
2,13
As instalado, 2
0,037
0,037
0,037
Deformacin ,t
1,52
1,52
1,52
Mn,
1,36
1,36
1,36
Mn,
13,6
13,6
13,6
Mn,
10,00
10,00
10,00
Separacin S,
Tabla 34 Acero de refuerzo en la placa combinada
Se puede notar que t mayor a 0,005, lo cual significa que el acero est en
fluencia, adems que <
94
Dimensiones de la zapata
combinada
Ancho
del
145
mm
pedestal
Largo
del
160
mm
pedestal
Ancho de la
450
mm
placa
Largo de la
3430
mm
placa
Peralte "d" de
175
mm
la placa
Tabla 35 Dimensiones del pedestal de concreto
En la siguiente tabla se presentan los resultados de calcular la capacidad
reducida.
Capacidad Vn de Cortante en dos
direcciones
1
66
KN
96
KN
2
383
KN
3
Tabla 36 Capacidad reducida a cortante en dos direcciones
De la tabla anterior la capacidad reducida de la seccin ser el menor de los 3
valores. Luego se determina la capacidad a cortante en una direccin para la
columna con mayor carga axial. En la siguiente tabla se presentan los resultados.
Capacidad Vn de Cortante en una
direccin
46
KN
1
Posteriormente se calculan las fuerzas cortantes ltimas que actan en dos
direcciones y una direccin para luego realizar la comparacin. A continuacin se
presentan los resultados en la siguiente tabla.
95
10,47
KN
320
mm
15
KN/m2
2
8.93
KN
Cortante en dos direcciones columna
izquierda
12,68
KN
320
mm
15
KN/m2
2
11.14
KN
Cortante en una direccin
KN
12,68
Cortante a un "d" de
la columna
9.27
KN
1
96
97
Compresin pura
f=
P n (max) =
0,65
533,8 kN
427,0 kN
fP n (max) =
278,0 kN
Po =
= 0.8(0.85 + = 0.85 + )
= 0.65
Se asumen que se incluyen aros.
Luego se determinan los valores de carga axial y momento flector para varios
niveles de deformacin del acero y se obtiene el siguiente diagrama de interaccin:
Pn
Mn
n
n
KN
KN-m
KN
KN
427
0
277
0
360
8
234
5
246
15
160
10
143
16
118
14
21
15
19
14
-25
14
-22
13
Tabla 41 Valores para graficar curva de interaccin
98
Se puede notar que el punto de cargas de diseo est dentro del rea de
operacin segura del pedestal, con lo cual queda demostrado que la seleccin de
dimensiones y materiales del pedestal es adecuado.
Por ltimo se revisa la necesidad o no de los estribos, donde, de acuerdo con
el ACI, la seccin 11.4.6.1 plantea que si se cumple la expresin
< /2
el elemento no requiere estribos; segn lo anterior:
= 46
/2 = 23
= 8.42
Luego 8.42 <23
Sin embargo, para ayudar a la capacidad de resistencia de cortante de los
pernos de anclaje se agregan aros en varilla #3 a cada 10 cm.
A continuacin se presenta la zapata combinada con sus respectivas
dimensiones y dosificacin del acero.
99
3.9
Relacin
Altura
Carga
de
Gamma, de
al
Asentamiento
Poisson [KN/m3] Estrato, estrato elstico S,[m]
()
[m]
KN
Estrato 1
16000
0,3
17,5
13,2
0,00212713
Estrato 2
38000
0,3
18
0,75
14,15 0,00096009
Estrato 3
63000
0,3
18,5
3,35
17,58
0,00071948
S total
[mm]
3,80669269
Tabla 42 Asentamiento inmediato para el pilar de concreto
100
16000
0,3
17,5
Estrato 2
38000
0,3
18
2,6
13,20
Estrato 3
63000
0,3
18,5
3,35
16,51
S,[m]
0,00000000
0,00088153
0,00066505
S total
[mm]
Tabla 43 Asentamiento inmediato para el pilote helicoide
1,546573441
Relaci
n de
Poiss
on ()
Estrato 1
16000
0,3
0,99
0,00004950
Estrato 2
38000
0,3
0,49
3,35
0,00001728
Estrato 3
63000
0,3
0,19
3,15
Carga de
servicio
de 13,2KN
Esfuerz
o en el
estrato
,kPa
Espesor
analizad
o ,H ,[m]
Asentamiento
elstico S,[m]
0,00000980
S total
[mm]
0,076578947
Tabla 44Asentamiento inmediato en el centro de la zapata combinada
A continuacin en la siguiente tabla se presenta el resumen de los
asentamientos elsticos y la correspondiente distorsin angular que se calcula
tomando como distancia de clculo el espaciamiento de los cimientos de 2.58 m.
Asentamiento Asentamiento
Asentamiento
del pilote
de placa
del pilar
helicoide
combinada
Asentamiento, S
[mm]
Distancia L,[mm]
Distorsin angular
S/L
Distorsin angular
1 en
Distorsin angular
3,81
2800
1,55
2800
0,077
2800
0,001359533
0,000552348
0,0000273496
736
1/ 736
1810
1/ 1810
36564
1/ 36564
101
Bajo las hiptesis anteriores se presentan los precios de la estructura y los tres
tipos de cimentacin.
Pilotes
helicoides
Precio
411.061
321.441
total
1.552.848
2.915.535,60
Tabla 46 Precio de la estructura y cada tipo de cimentacin
Estructura
Zapata
Combinada
Pilares de
concreto
102
103
CAPTULO IV
ANLISIS DE
RESULTADOS
104
Anlisis de resultados
Respecto al clculo de la carga de viento, el cdigo de construccin de Costa
Rica indica en sus artculos XX.7, XX.8, XX.9 y XX.10 un mtodo de clculo de
cargas de viento basado en la presin bsica. A continuacin se presenta las
velocidades de diseo que presenta el cdigo de construcciones.
desde
estaciones
meteorolgicas
mientras
que
el
cdigo
construcciones iguala las condiciones de las zonas abiertas con zonas costeras.
de
105
Por otro lado, los valores de viento del cdigo de construcciones estn
desactualizados pues son del ao 1983, mientras que los de Patio son del ao
2005.
En cuanto a las combinaciones de carga del ASCE
resistidas por la estructura, se toma como ejemplo el efecto sobre las cargas axiales
para el diseo de las cimentaciones.
En la siguiente tabla se pueden ver las combinaciones de carga obtenidas
segn el cdigo de ssmico de Costa Rica.
Cargas en los nodos 9 y 10 (apoyos ms cargados).
Nodo
9
10
6-1
6-2
6-3.1
6-3.2
6-4.1
6-4.2
DL
0,92
1,14
CASO
1
2
3
4
5
6
LL2
3,37
5,01
DL
1,4
1,2
1,05
1,05
0,95
0,95
LL2
0
1,6
1
1
0
0
WIND1
0
0
1
-1
1
-1
WIND1
5,13
1,3
SEIS1
0
0
0
0
0
0
SEIS1
0,5
0,5
Nodo 9
1,288
6,496
9,466
-0,794
6,004
-4,256
Nodo 10
1,596
9,384
7,507
4,907
2,383
-0,217
CASO
1
2
3
4
5
6
DL
1,4
1,2
1,2
1,2
1,2
0,9
LL2
0
1,6
1,6
1
0
0
WIND1
0
0
0,8
1,6
0
1,6
SEIS1
0
0
0
0
1
0
Nodo 9
1,288
6,496
10,6
12,682
1,604
9,036
Nodo 10
1,596
9,384
10,424
8,458
1,868
3,106
Se puede notar que las combinaciones de carga del cdigo ssmico de Costa
Rica resultan en valores de
carga ltima
menores que si se
aplican las
106
El valor mximo en el nodo 9 del caso 4 del ASCE presenta una carga axial
superior en 33% al valor que se supondra utilizando solamente las combinaciones
del caso 3 del cdigo ssmico de Costa Rica.
Lo anterior se debe a que el ASCE presenta una combinacin de carga que
incrementa en 60% la participacin de la carga de viento y el cdigo ssmico de
Costa Rica no.
Lo anterior resulta en que la resistencia que deben desarrollar los elementos
diseados bajo las combinaciones de carga del ASCE es mayor que el disear, al
utilizar las combinaciones de carga del cdigo ssmico de Costa Rica.
Respecto de la estructura de acero, segn
5.1 ,5.2 y 5.3 la estructura requiere de secciones de 100 mm para no fallar por
pandeo.
Lo anterior se debe a la longitud de los miembros columna, los cuales se
eligieron de esa manera para lograr los 45 de inclinacin requeridos en el caso de
aplicacin.
La eleccin de secciones circulares permite mantener igual inercia en ambos
ejes; esta prctica es usual en varios fabricantes de estructuras de soporte.
El desplazamiento horizontal mximo se puede ver en la tabla 44 mostrada a
continuacin.
Mximo
desplazamiento
Nodo
Caso
UX (cm)
UY
(cm)
UZ (cm)
U (cm)
0,1
-1,7
-1,6
2,3
21
10 (C)
la relacin de altura
107
UY (cm)
UZ (cm)
U (cm)
Mxima
deflexin
0
0.1
1,1
1,1
Barra
7
Caso
10 (C)
Tabla 48 Deflexin mxima de la estructura
Este valor es menor al valor propuesto por Vinakota, de L/360 donde L para
3160 cm, la deflexin mxima es 8.8 cm.
Sobre pernos y la placa base, los valores obtenidos de capacidad reducida son
superiores a las solicitaciones de carga como se puede ver en las tablas 21 y 22 .
Como estos valores se obtuvieron para la estructura inclinada a 45, estos pernos
pueden utilizarse con seguridad para estructuras de menor inclinacin, pues esta
inclinacin les impondra solicitaciones de carga menores a las presentes en el caso
de estudio.
En cuanto a las cimentaciones se puede notar que los tres tipos de
cimentaciones son capaces de soportar con seguridad la estructura y estar dentro del
valor de capacidad soportante.
En cuanto a la capacidad de soporte lateral en este documento se realiza un
diseo basado en la teora LRFD, se puede ver que las capacidades reducidas de los
pilares de concreto y pilotes helicoides se obtuvieron usando los valores del
AASHTO (=1) y del manual de cimentaciones de Canad, debido al Cdigo de
cimentaciones (=05), pues no presenta valores de reduccin de capacidad lateral.
108
correspondiente asentamiento.
Pilar de
concreto
Asentamiento, S
[mm]
Distancia L,[mm]
Distorsin
angular
Precio
Asentamiento Asentamiento
de placa
del pilote
combinada
helicoide
3,81
2800
0,077
2800
1,55
2800
1/ 736
321.441
1/ 36564
411.061
1/ 1810
2.915.535,60
Se puede notar que el desempeo por asentamiento para los tres tipos es
superior al requerido por Das.B (2006) de 1/300; sin embargo, el precio mayor lo
tiene el sistema de cimentacin por pilares helicoides.
109
La razn del alto precio de los pilares helicoides es su pas de fabricacin, pues
son elementos fabricados en Estados Unidos de Amrica y no se fabrican en otro
sitio ms cercano.
Por otra parte, los pilares y zapata combinada resultan soluciones atractivas a
nivel econmico; sin embargo, al ser elementos de concreto requieren al menos 8
das para poder cargarlos mientras que los pilotes helicoides pueden utilizarse una
vez instalados.
110
CAPTULO V
CONCLUSIONES Y
RECOMENDACIONES
111
5 Conclusiones y recomendaciones
5.1
Conclusiones
1. Los valores de velocidad del viento, del cdigo de construcciones, no son una
aproximacin adecuada a las condiciones de diseo de estructuras de soporte
de paneles solares, pues son valores desactualizados.
2. Las combinaciones de carga del cdigo ssmico de Costa Rica, resultan en
valores de carga ltima, menores que si se aplican las combinaciones de carga
del ASCE.
3. La resistencia que deben desarrollar los elementos diseados bajo las
combinaciones de carga del ASCE, es mayor que al disear utilizando las
combinaciones de carga del cdigo ssmico de Costa Rica.
4. En estructuras de soporte de paneles fotovoltaicos con inclinacin de 45 se
requieren seccin circulares de al menos 100 mm de dimetro.
5. La eleccin de secciones circulares permite mantener igual inercia en ambos
ejes y mantener la rigidez igual en ambas direcciones de la estructura.
6. La
de las
pueden utilizarse con seguridad para estructuras de menor inclinacin, pues esta
inclinacin les impondra solicitaciones de carga menores a las presentes en el
caso de estudio.
9. Los tres tipos de cimentacin: zapata combinada, pilares de concreto y pilotes
helicoides son capaces de soportar con seguridad la estructura y estar dentro del
valor de capacidad soportante.
112
lateral para cimentaciones profundas, por lo que deben adoptarse los valores del
AASHTO y del manual de cimentaciones de Canad.
11. El diseo de las cimentaciones para estructuras de soporte de paneles solares,
debe
ser
de
acuerdo
con
el
diseo
LRFD
para
no
castigar
Zapata combinada
b.
Pilar de concreto
c.
Pilote helicoide
13. El desempeo por asentamiento para los tres tipos, es superior al requerido,
pues las tres cimentaciones no producen una distorsin angular de 1/300.
14. El sistema de cimentacin por pilares helicoides posee un alto precio que lo
demerita ante las cimentaciones de concreto armado y pilares de concreto.
15. Los pilares y zapata combinada resultan soluciones atractivas a nivel econmico.
5.2
Recomendaciones
Se recomiendan las siguientes acciones:
113
diseo.
8. Realizar una prueba de carga al pilote helicoide seleccionado para corroborar
las capacidades axiales y laterales obtenidas.
9. Realizar una comprobacin de capacidad de carga lateral para las
cimentaciones tipo pilar de concreto y pilote helicoide usando la aplicacin Lpile
u otro software reconocido.
10. Utilizar la aplicacin Robot structural Analisys para el estudio de estructuras
11. Utilizar perfiles tipo cajn para el diseo de estructuras de soporte para
paneles solares.
12. Se recomienda utilizar pilotes helicoides cuando el tiempo de puesta en
marcha sea tal que amerite la inversin en este tipo de cimentacin.
13. Contactar otros fabricantes de pilares helicoides para buscar un mejor precio
en el pilote helicoide.
114
Bibliografa
1. A.B. Chance Co, 2010. Catlogo de anclajes helicoides. A.B. Chance Co.
Centralia, Estados Unidos de Norteamrica.
2. Acua Bermdez, N. F. (2014). Procedimiento de anlisis y diseo estructural de
invernaderos en acero laminado en fro para Costa Rica. (Tesis de Licenciatura).
Universidad de Costa Rica. San Jos, Costa Rica.
3. American Concrete Institute . Diseo y construccin de pilares taladrados ( ACI
336.3R-93 Reapproved 1998). Reported by ACI Committee 336. Estados Unidos
de Amrica: Autor.
4. American Concrete Institute (2008). Requisitos para concreto estructural (ACI318S-08) y comentario. Estados Unidos de Amrica: Autor.
5. American Society of Civil Engineers (2010) . Minimum Design Loads for Buildings
and Other Structures ASCE/SEI 7-10. Estados Unidos de Amrica: Autor.
6. Asociacin Americana de Oficiales de Carreteras Estatales y Transportes.
AASHTO 5-E1 2010.Especificacion para diseo de Puentes
AASHTO ,5ta
T.
(2011).
Ground
MountoSolaroArrayoFoundations.
115
Editores, S.A.
11. Brenes Espinoza L. (2005) Gua de diseo para estructuras de acero laminados
en caliente. . (Tesis de Licenciatura). Universidad de Costa Rica. San Jos,
Costa Rica.
12. Brown G. Edmund Jr .California Solar Permitting Guidebook (2015).[en
Lnea].Solar Permitting Task Force Governors Office of Planning and Research
Office
of
Governor.Disponibleoen:https://energycenter.org/sites/default/files/docs/nav/polic
y/research-and-reports/California_Solar_Permitting_Guidebook_2015.pdf
13. Colegio Federado de Ingenieros y Arquitectos, comisin permanente de estudio y
revisin del Cdigo Ssmico de Costa Rica (2010). Cdigo Ssmico de Costa Rica
2010). 4 edicin. Cartago: Editorial Tecnolgica de Costa Rica.
14. Hannigan,PJ.1998.USA
Department
of
trasnportation
Federal
higway
116
de
Norteamrica,
Recuperado
el
Long
Island,
05de
EmPower
Enero
CES,32
de
Diapositivas.
2016
en
https://www.ieee.li/pdf/viewgraphs/solar_pv_basics.pdf.
29. Sick F., ErgeT .Photovoltaics in Buildings: A Design Handbook for Architects and
Engineers. International Energy Agency. Solar Heating and Cooling Programme
James & James (Science Publishers) Ltd., 1996 - 287 pages
30. Structural
engineers
association
of
California
(2012).Structural
seismic
117
Febrero 2012
31. Sociedad Canadiense de Geotecnia. Manual de Ingeniera de Fundaciones .4ta
Edicin. Canad: Autor.
32. Solar GIS (2016).Mapa de Irradiacin Global de Costa Rica. Recuperado el 05 de
Enero de 2016 en Http://solargis.info/doc/_pics/freemaps/1000px/ghi/SolarGISSolar-map-Costa-Rica-es.png
33. SmartoGridoCostaoRica.(2012).Arrancaoparqueosolaromiravallesoyoproyectoos
olaroiceosabana.Recuperadooelo12odeoFebreroodeo2016oenohttp://www.smart
gridcostarica.com/2012/11/21/arranca-parque-solar-miravalles-y-proyecto-solarice-sabana/
34. Tomlinson,M.,Woodward.J.2007 Pile design and construction prectice .5ta edicin
.Taylor& Francis, USA.
35. Villaz C.(2004).Mecnica de suelos y cimentaciones. Limusa Quinta edicin ,
Mxico.
36. Vinnakota, S. (2006). Estructuras de acero: comportamiento y LRFD. Mxico:
McGraw-Hill.
37. Vindas, I. (2006).Diseo ,anlisis y costos para marcos ordinarios en acero de
uso industrial ,segn las especificaciones del cdigo ssmico de Costa Rica 2002
y las provisiones ssmicas del AISC-2005. (Tesis de Licenciatura). Universidad de
Costa Rica. San Jos, Costa Rica.
38. Worden A. (2014). Foundation Selection For Ground Mounted PV Solar Systems.
Recuperadooelo27odeoEneroodeo2015oenohttp://www.solarpowerworldonline.co
m/2014/07/July18,
white-paper-foundation-selection-ground-mounted-pv-solar-
118
Anexos
Anexo 1 :Velocidades y zonificacin de velocidades para Costa
Rica tomado de Patio 2006
119
120
121
122
123
124
125
Nodo/Caso MX (kNm)
7/4
-0,01>>
7/10 (C)
-1,05<<
7/4
-0,01
7/10 (C)
-1,05
7/4
-0,01
7/10 (C)
-1,05
7/4
-0,01
7/10 (C)
-1,05
7/10 (C)
-1,05
7/4
-0,01
7/10 (C)
-1,05
7/2
-0,04
8/1
-0,06>>
8/10 (C)
-3,05<<
8/3
-1,5
8/6 (C)
-2,16
8/4
-0,14
8/10 (C)
-3,05
8/4
-0,14
8/6 (C)
-2,16
8/12 (C)
-2,51
8/8 (C)
-0,65
8/6 (C)
-2,16
8/4
-0,14
9/4
-0,01>>
9/10 (C)
-2,40<<
9/10 (C)
-2,4
9/4
-0,01
9/2
-0,09
9/10 (C)
-2,4
9/10 (C)
-2,4
9/4
-0,01
9/10 (C)
-2,4
Momentos
MY (kNm)
0
-0,39
0,00>>
-0,39<<
0
-0,39
0
-0,39
-0,39
0
-0,39
-0,01
-0,01
-0,1
0,03>>
-0,20<<
0
-0,1
0
-0,2
0,03
-0,15
-0,2
0
0
0
0,00>>
-0,00<<
0
0
0
0
0
MZ (kNm)
0
-0,2
0
-0,2
0,00>>
-0,20<<
0
-0,2
-0,2
0
-0,2
0
-0,01
-0,71
-0,29
-0,6
0,00>>
-0,71<<
0
-0,6
-0,49
-0,25
-0,6
0
0
0
0
0
0,00>>
-0,00<<
0
0
0
FX (kN)
0
-0,43
0
-0,43
0
-0,43
0,00>>
-0,43<<
-0,43
0
-0,43
-0,02
-0,05
-1,56
-0,41
-1,67
0
-1,56
0,00>>
-1,67<<
-0,79
-0,9
-1,67
0
0
0
0
0
0
0
0,00>>
-0,00<<
0
Fuerzas
FY (kN)
0,01
1,19
0,01
1,19
0,01
1,19
0,01
1,19
1,19>>
0,01<<
1,19
0,04
-0,05
2,49
1,99
0,58
0,49
2,49
0,49
0,58
3,07>>
-0,69<<
0,58
0,49
0
2,74
2,74
0
0,1
2,74
2,74
0
2,74>>
FZ (kN)
0,5
4,96
0,5
4,96
0,5
4,96
0,5
4,96
4,96
0,5
4,96>>
0,17<<
0,28
3,95
0,54
4,94
-0,5
3,95
-0,5
4,94
1,4
3,09
4,94>>
-0,50<<
0,5
12,68
12,68
0,5
0,45
12,68
12,68
0,5
12,68
126
Momentos
MY (kNm)
0
0
0
0
0
-0,00>>
-0,00<<
0
0
0
0
0
0
0
0
0,01
0,1
0,20>>
-0,03<<
0,1
0
0,2
0
-0,03
0,15
0,2
0
0
0,39
0,39>>
-0,00<<
0,39
0
0,39
0
0,39
0
0,39
0,01
MZ (kNm)
0
0
0
0
0
0
0
0,00>>
0,00<<
0
0
0
0
0
0
0,01
0,71
0,6
0,29
0,71>>
-0,00<<
0,6
0
0,49
0,25
0,6
0
0
0,2
0,2
0
0,20>>
-0,00<<
0,2
0
0,2
0
0,2
0
FX (kN)
0
0
0
0
0
0
0
0
0
0,00>>
-0,00<<
0
0
0
0
0,05
1,56
1,67
0,41
1,56
0
1,67>>
-0,00<<
0,79
0,9
1,67
0
0
0,43
0,43
0
0,43
0
0,43>>
-0,00<<
0,43
0
0,43
0,02
Fuerzas
FY (kN)
0,00<<
2,74
0,1
-0,03
8,1
0,5
8,1
8,1
0,5
-0,3
8,42
8,42>>
-0,39<<
3,67
0,5
-0,05
2,49
0,58
1,99
2,49
0,49
0,58
0,49
3,07>>
-0,69<<
0,58
0,49
0,01
1,19
1,19
0,01
1,19
0,01
1,19
0,01
1,19>>
0,01<<
1,19
0,04
FZ (kN)
0,5
12,68>>
0,45<<
0,47
8,45
-0,5
8,45
8,45
-0,5
5,01
3,1
3,1
6,37
10,42>>
-0,50<<
0,28
3,95
4,94
0,54
3,95
-0,5
4,94
-0,5
1,4
3,09
4,94>>
-0,50<<
0,5
4,96
4,96
0,5
4,96
0,5
4,96
0,5
4,96
0,5
4,96>>
0,17<<
127
STEEL DESIGN
------------------------------------------------------------------------------------------------------ ----------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------- ---------------CODE GROUP:
MEMBER: 1 Column_1 POINT: 3
COORDINATE: x = 1.00 L = 2.53 m
----------------------------------------------------------------------------------------------------------------------------- ---------LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
----------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION PARAMETERS: HSRO 4x0.125
d=10.2 cm
Ay=4.58 cm2
Az=4.58 cm2
Ax=9.16 cm2
Iy=111.13 cm4
Iz=111.13 cm4
J=222.27 cm4
tw=0.3 cm
Sy=21.88 cm3
Sz=21.88 cm3
Zy=28.68 cm3
Zz=28.68 cm3
----------------------------------------------------------------------------------------------------------------------------- ---------MEMBER PARAMETERS:
Ly = 2.53 m
Lz = 2.53 m
Ky = 1.00
Kz = 1.00
Lb = 2.53 m
KLy/ry = 72.77
KLz/rz = 72.77
Cb = 1.00
----------------------------------------------------------------------------------------- ---------------------------------------------INTERNAL FORCES:
Tr = -0.18 KN*m
DESIGN STRENGTHS
FiT*Tn = 6.04 KN*m
Pr = 4.64 KN
Fic*Pn = 154.87 KN
Mry = 0.61 KN*m Vry = 1.13 KN
Fib*Mny = 6.41 KN*m
Fiv*Vny = 61.40 KN
Mrz = -1.87 KN*m Vrz = 0.34 KN
Fib*Mnz = 6.41 KN*m
Fiv*Vnz = 61.40 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
128
Section OK !!!
STEEL DESIGN
--------------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
--------------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 2 Column_2 POINT: 1
COORDINATE: x = 0.00 L = 0.00 m
--------------------------------------------------------------------------------------------------------------------------------------LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
-------------------------------------------------------------------------------------------- ------------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION PARAMETERS: HSRO 4x0.125
d=10.2 cm
Ay=4.58 cm2
Az=4.58 cm2
Ax=9.16 cm2
Iy=111.13 cm4
Iz=111.13 cm4
J=222.27 cm4
tw=0.3 cm
Sy=21.88 cm3
Sz=21.88 cm3
Zy=28.68 cm3
Zz=28.68 cm3
--------------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
Ly = 0.30 m
Lz = 0.30 m
Ky = 1.00
Kz = 1.00
Lb = 0.30 m
KLy/ry = 8.61
KLz/rz = 8.61
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = -0.66 KN*m
DESIGN STRENGTHS
FiT*Tn = 6.04 KN*m
129
Pr = 3.85 KN
Fic*Pn = 203.86 KN
Mry = -0.13 KN*m Vry = 2.43 KN
Fib*Mny = 6.41 KN*m
Fiv*Vny = 61.40 KN
Mrz = 2.92 KN*m Vrz = 1.53 KN
Fib*Mnz = 6.41 KN*m
Fiv*Vnz = 61.40 KN
------------------------------------------------------------------------------------------------------------------------- ---------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- -----SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.49 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.04 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.02 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 8.61 < (K*L/r),max = 200.00
Kz*Lz/rz = 8.61 < (K*L/r),max = 200.00 STABLE
-----------------------------------------------------------------------------------------------------------------------------------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- ---------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 3 Column_3 POINT: 3
COORDINATE: x = 1.00 L = 2.53 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
----------------------------------------------------------------------------------------------------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRO 4x0.125
d=10.2 cm
Ay=4.58 cm2
Az=4.58 cm2
Ax=9.16 cm2
Iy=111.13 cm4
Iz=111.13 cm4
J=222.27 cm4
tw=0.3 cm
Sy=21.88 cm3
Sz=21.88 cm3
Zy=28.68 cm3
Zz=28.68 cm3
----------------------------------------------------------------------------------------------------------------------------- ------
130
MEMBER PARAMETERS:
Ly = 2.53 m
Lz = 2.53 m
Ky = 1.00
Kz = 1.00
Lb = 2.53 m
KLy/ry = 72.77
KLz/rz = 72.77
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = 0.01 KN*m
DESIGN STRENGTHS
FiT*Tn = 6.04 KN*m
Pr = 12.71 KN
Fic*Pn = 154.87 KN
Mry = -0.04 KN*m Vry = 2.54 KN
Fib*Mny = 6.41 KN*m
Fiv*Vny = 61.40 KN
Mrz = -4.20 KN*m Vrz = -0.06 KN
Fib*Mnz = 6.41 KN*m
Fiv*Vnz = 61.40 KN
--------------------------------------------------------------------------------------------------------------------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
---------------------------------------------------------------------------------------------------------- ------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- -----VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.70 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.04 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.00 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 72.77 < (K*L/r),max = 200.00
Kz*Lz/rz = 72.77 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ----------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
-------------------------------------------------------------------------------------------- --------------------------------------CODE GROUP:
MEMBER: 4 Column_4 POINT: 1
COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------- ---------LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
131
----------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION PARAMETERS: HSRO 4x0.188
d=10.2 cm
Ay=6.74 cm2
Az=6.74 cm2
Ax=13.48 cm2
Iy=159.42 cm4
Iz=159.42 cm4
J=319.25 cm4
tw=0.4 cm
Sy=31.38 cm3
Sz=31.38 cm3
Zy=41.77 cm3
Zz=41.77 cm3
----------------------------------------------------------------------------------------------------------------------------- ---------MEMBER PARAMETERS:
Ly = 0.30 m
Lz = 0.30 m
Ky = 1.00
Kz = 1.00
Lb = 0.30 m
KLy/ry = 8.72
KLz/rz = 8.72
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------------INTERNAL FORCES:
Tr = -0.01 KN*m
DESIGN STRENGTHS
FiT*Tn = 8.79 KN*m
Pr = 8.49 KN
Fic*Pn = 300.01 KN
Mry = -0.03 KN*m Vry = 8.44 KN
Fib*Mny = 9.33 KN*m
Fiv*Vny = 90.36 KN
Mrz = 8.33 KN*m Vrz = 0.04 KN
Fib*Mnz = 9.33 KN*m
Fiv*Vnz = 90.36 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
--------------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.91 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.09 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.00 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 8.72 < (K*L/r),max = 200.00
Kz*Lz/rz = 8.72 < (K*L/r),max = 200.00 STABLE
----------------------------------------------------------------------------------------------------------------------------- ------
Section OK !!!
STEEL DESIGN
132
----------------------------------------------------------------------------------------------------------------------------- ---------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- ---------CODE GROUP:
MEMBER: 5 Column_5 POINT: 1
COORDINATE: x = 0.00 L = 0.00 m
--------------------------------------------------------------------------------------------------------------------------------------LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
--------------------------------------------------------------------------------------------------------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
------------------------------------------------------------------------------------------------------------ --------------------------SECTION PARAMETERS: HSRO 4x0.125
d=10.2 cm
Ay=4.58 cm2
Az=4.58 cm2
Ax=9.16 cm2
Iy=111.13 cm4
Iz=111.13 cm4
J=222.27 cm4
tw=0.3 cm
Sy=21.88 cm3
Sz=21.88 cm3
Zy=28.68 cm3
Zz=28.68 cm3
--------------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
Ly = 0.30 m
Lz = 0.30 m
Ky = 1.00
Kz = 1.00
Lb = 0.30 m
KLy/ry = 8.61
KLz/rz = 8.61
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = 0.63 KN*m
DESIGN STRENGTHS
FiT*Tn = 6.04 KN*m
Pr = 3.73 KN
Fic*Pn = 203.86 KN
Mry = 0.09 KN*m Vry = 2.53 KN
Fib*Mny = 6.41 KN*m
Fiv*Vny = 61.40 KN
Mrz = 2.94 KN*m Vrz = -1.43 KN
Fib*Mnz = 6.41 KN*m
Fiv*Vnz = 61.40 KN
----------------------------------------------------------------------------------------------------- ------------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- -----SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- -----VERIFICATION FORMULAS:
133
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- ---------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 6 Column_6 POINT: 3
COORDINATE: x = 1.00 L = 2.53 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
----------------------------------------------------------------------------------------------------------------------------- -----MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRO 4x0.125
d=10.2 cm
Ay=4.58 cm2
Az=4.58 cm2
Ax=9.16 cm2
Iy=111.13 cm4
Iz=111.13 cm4
J=222.27 cm4
tw=0.3 cm
Sy=21.88 cm3
Sz=21.88 cm3
Zy=28.68 cm3
Zz=28.68 cm3
----------------------------------------------------------------------------------------------------------------------------- ---------MEMBER PARAMETERS:
Ly = 2.53 m
Lz = 2.53 m
Ky = 1.00
Kz = 1.00
Lb = 2.53 m
KLy/ry = 72.77
KLz/rz = 72.77
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- ---------INTERNAL FORCES:
Tr = 0.17 KN*m
DESIGN STRENGTHS
FiT*Tn = 6.04 KN*m
Pr = 4.67 KN
Mry = -0.63 KN*m Vry = 1.13 KN
Mrz = -1.86 KN*m Vrz = -0.42 KN
Fic*Pn = 154.87 KN
Fib*Mny = 6.41 KN*m
Fib*Mnz = 6.41 KN*m
Fiv*Vny = 61.40 KN
Fiv*Vnz = 61.40 KN
134
----------------------------------------------------------------------------------------------------------------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
--------------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- ---------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.40 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.02 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.01 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 72.77 < (K*L/r),max = 200.00
Kz*Lz/rz = 72.77 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ----------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 7 Beam_7 POINT: 3
COORDINATE: x = 1.00 L = 3.16 m
-------------------------------------------------------------------------------------------------------------- --------------------LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
----------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION PARAMETERS: HSRE 3x2x0.125
d=7.6 cm
Ay=2.47 cm2
Az=3.97 cm2
Ax=6.90 cm2
bf=5.1 cm
Iy=54.11 cm4
Iz=28.80 cm4
J=61.19 cm4
tw=0.3 cm
Sy=14.20 cm3
Sz=11.34 cm3
tf=0.3 cm
Zy=17.37 cm3
Zz=13.16 cm3
--------------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
135
Ly = 3.16 m
Lz = 3.16 m
Ky = 1.00
Kz = 1.00
Lb = 3.16 m
KLy/ry = 112.87 KLz/rz = 154.70
Cb = 1.00
--------------------------------------------------------------------------------------------------------------------------------------INTERNAL FORCES:
Tr = -0.70 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.76 KN*m
Pr = 0.99 KN
Fic*Pn = 44.93 KN
Mry = -2.19 KN*m Vry = -1.53 KN
Fib*Mny = 3.88 KN*m
Fiv*Vny = 33.14 KN
Mrz = 0.23 KN*m Vrz = -4.42 KN
Fib*Mnz = 2.94 KN*m
Fiv*Vnz = 53.20 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- -----SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.66 < 1.00 LRFD (H1-1b) Verified
Pr/(Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) + (Vry/(Fiv*Vny) + Vrz/(Fiv*Vnz) + Tr/(FiT*Tn))^2 =
0.81 < 1.00 LRFD (H3-6) Verified
Vry/(Fiv*Vny) = 0.05 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.08 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 112.87 < (K*L/r),max = 200.00
Kz*Lz/rz = 154.70 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 8 Beam_8 POINT: 3
COORDINATE: x = 1.00 L = 2.79 m
------------------------------------------------------------------------------------------------------ ----------------------------LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
----------------------------------------------------------------------------------------------------------------------------- -----MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
136
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------------INTERNAL FORCES:
Tr = -0.03 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 0.18 KN
Fic*Pn = 29.50 KN
Mry = -1.11 KN*m Vry = 1.29 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.60 KN*m Vrz = -2.37 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
----------------------------------------------------------------------------------------------------------------------------- ---------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION ELEMENTS:
Flange = Compact Web = Compact
--------------------------------------------------------------------------------------------------------------------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.64 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.04 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 200.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 200.00
STABLE
---------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- ---------CODE:
137
Ly = 3.16 m
Lz = 3.16 m
Ky = 1.00
Kz = 1.00
Lb = 3.16 m
KLy/ry = 112.87 KLz/rz = 154.70
Cb = 1.00
------------------------------------------------------------------------------------------------------------------------ ----------INTERNAL FORCES:
Tr = 0.68 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.76 KN*m
Pr = 0.84 KN
Fic*Pn = 44.93 KN
Mry = -2.18 KN*m Vry = 1.43 KN
Fib*Mny = 3.88 KN*m
Fiv*Vny = 33.14 KN
Mrz = 0.21 KN*m Vrz = 4.41 KN
Fib*Mnz = 2.94 KN*m
Fiv*Vnz = 53.20 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- -----VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.64 < 1.00 LRFD (H1-1b) Verified
138
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 11 Beam_11
POINT: 1 COORDINATE: x = 0.00 L =
0.00 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
----------------------------------------------------------------------------------------------------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
Ax=6.17 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
J=36.88 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
----------------------------------------------------------------------------------------------------------------------------- ---------MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- ---------INTERNAL FORCES:
Tr = 0.03 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 0.01 KN
Fic*Pn = 29.50 KN
139
Section OK !!!
STEEL DESIGN
CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 12 Beam_12
POINT: 3 COORDINATE: x = 1.00 L =
2.79 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
----------------------------------------------------------------------------------------------------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
Ax=6.17 cm2
J=36.88 cm4
140
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = -0.05 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 0.98 KN
Fic*Pn = 29.50 KN
Mry = -1.18 KN*m Vry = 1.29 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.61 KN*m Vrz = -2.34 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
--------------------------------------------------------------------------------------------------------------------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
--------------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- ---------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.68 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.04 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 200.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ----------
Section OK !!!
STEEL DESIGN
--------------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
--------------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 13 Beam_13
POINT: 3 COORDINATE: x = 1.00 L =
2.79 m
---------------------------------------------------------------------------------------------------------------------------------------
141
LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
--------------------------------------------------------------------------------------------------------------------- -----------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
Ax=6.17 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
J=36.88 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
--------------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = 0.06 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 0.86 KN
Fic*Pn = 29.50 KN
Mry = -1.14 KN*m Vry = 1.29 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.60 KN*m Vrz = -2.33 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
------------------------------------------------------------------------------------------------------ ----------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- -----SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- -----VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.66 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.04 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 200.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 200.00
STABLE
-----------------------------------------------------------------------------------------------------------------------------------
Section OK !!!
142
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 14 Beam_14
POINT: 3 COORDINATE: x = 1.00 L =
2.79 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
----------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
--------------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
Ax=6.17 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
J=36.88 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
----------------------------------------------------------------------------------------------------------------------------- ---------MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
--------------------------------------------------------------------------------------------- -----------------------------------------INTERNAL FORCES:
DESIGN STRENGTHS
Pr = -0.10 KN
Fity*Pnty = 137.78 KN
Mry = -1.21 KN*m Vry = 1.58 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.86 KN*m Vrz = -2.51 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
----------------------------------------------------------------------------------------------------------------------------- ---------SAFETY FACTORS
Fib = 0.90
Fity = 0.90
Fiv = 0.90
--------------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- ----------
143
VERIFICATION FORMULAS:
Pr/(2*Fity*Pnty) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.79 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.07 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.05 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 300.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 300.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 15 Beam_15
POINT: 1 COORDINATE: x = 0.00 L =
0.00 m
----------------------------------------------------------------------------------------------------------------------------------LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- -----SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
Ax=6.17 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
J=36.88 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
----------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = -0.02 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
144
Pr = -0.02 KN
Fity*Pnty = 137.78 KN
Mry = -1.16 KN*m Vry = -1.33 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.67 KN*m Vrz = 2.43 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
--------------------------------------------------------------------------------------------------------- -------------------------SAFETY FACTORS
Fib = 0.90
Fity = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- ---------VERIFICATION FORMULAS:
Pr/(2*Fity*Pnty) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.69 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.05 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 300.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 300.00
STABLE
---------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- -----CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 16 Beam_16
POINT: 1 COORDINATE: x = 0.00 L =
0.00 m
----------------------------------------------------------------------------------------------------------------------------- ---------LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
----------------------------------------------------------------------------------------------------------------------------- ---------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------------SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
Ax=6.17 cm2
J=36.88 cm4
145
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
----------------------------------------------------------------------------------------------------------------------------- -----MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
---------------------------------------------------------------------------------------- ------------------------------------------INTERNAL FORCES:
Tr = 0.05 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 1.03 KN
Fic*Pn = 29.50 KN
Mry = -1.18 KN*m Vry = -1.28 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.60 KN*m Vrz = 2.35 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
---------------------------------------------------------------------------------------------------------- ----------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.67 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.04 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 200.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ----------
Section OK !!!
STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------- ---------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------CODE GROUP:
MEMBER: 18 Beam_18
0.00 m
POINT: 1 COORDINATE:
x = 0.00 L =
146
----------------------------------------------------------------------------------------------------------------------------------LOADS:
Governing Load Case: 6 COMB2 1.2D+1.6L+0.8W (1+2)*1.20+3*0.80+7*1.60
------------------------------------------------------------------------------------------- ---------------------------------------MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- -----SECTION PARAMETERS: HSRE 3x1.5x0.125
d=7.6 cm
Ay=1.72 cm2
Az=3.97 cm2
Ax=6.17 cm2
bf=3.8 cm
Iy=44.12 cm4
Iz=14.78 cm4
J=36.88 cm4
tw=0.3 cm
Sy=11.58 cm3
Sz=7.76 cm3
tf=0.3 cm
Zy=14.67 cm3
Zz=9.01 cm3
----------------------------------------------------------------------------------------------------------------------------------MEMBER PARAMETERS:
Ly = 2.79 m
Lz = 2.79 m
Ky = 1.00
Kz = 1.00
Lb = 2.79 m
KLy/ry = 104.43 KLz/rz = 180.45
Cb = 1.00
----------------------------------------------------------------------------------------------------------------------------- -----INTERNAL FORCES:
Tr = -0.06 KN*m
DESIGN STRENGTHS
FiT*Tn = 2.02 KN*m
Pr = 0.90 KN
Fic*Pn = 29.50 KN
Mry = -1.21 KN*m Vry = -1.33 KN
Fib*Mny = 3.28 KN*m
Fiv*Vny = 23.11 KN
Mrz = -0.65 KN*m Vrz = 2.39 KN
Fib*Mnz = 2.01 KN*m
Fiv*Vnz = 53.20 KN
--------------------------------------------------------------------------------------- -------------------------------------------SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
----------------------------------------------------------------------------------------------------------------------------- ---------SECTION ELEMENTS:
Flange = Compact Web = Compact
----------------------------------------------------------------------------------------------------------------------------- ---------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.71 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.06 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.04 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 104.43 < (K*L/r),max = 200.00
Kz*Lz/rz = 180.45 < (K*L/r),max = 200.00
STABLE
---------------------------------------------------------------------------------------------------------------------------------------
147
Section OK !!!
STEEL DESIGN
---------------------------------------------------------------------------------------------------------------------- ----------------CODE: ANSI/AISC 360-10 An American National Standard, June 22, 2010
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------- -----CODE GROUP:
MEMBER: 19 Beam_19
POINT: 3 COORDINATE: x = 1.00 L =
3.16 m
----------------------------------------------------------------------------------------------------------------------------- -----LOADS:
Governing Load Case: 10 COMB5 :1.2D+1.6W+1L (1+2)*1.20+3*1.60+7*1.00
----------------------------------------------------------------------------------------------------------------------------- -----MATERIAL:
STEEL
Fy = 248.21 MPa
Fu = 399.90 MPa
E = 199948.02 MPa
----------------------------------------------------------------------------------------------------------------------------- -----SECTION PARAMETERS: HSRE 3x2x0.25
d=7.6 cm
Ay=3.91 cm2
Az=6.92 cm2
Ax=12.71 cm2
bf=5.1 cm
Iy=88.66 cm4
Iz=46.20 cm4
J=104.89 cm4
tw=0.6 cm
Sy=23.27 cm3
Sz=18.19 cm3
tf=0.6 cm
Zy=29.99 cm3
Zz=22.61 cm3
----------------------------------------------------------------------------------------------------------------------------- -----MEMBER PARAMETERS:
Ly = 3.16 m
Lz = 3.16 m
Ky = 1.00
Kz = 1.00
Lb = 3.16 m
KLy/ry = 119.65 KLz/rz = 165.74
Cb = 1.00
--------------------------------------------------------------------------------------------------------------------------------------INTERNAL FORCES:
Tr = 0.00 KN*m
DESIGN STRENGTHS
FiT*Tn = 4.90 KN*m
Pr = 0.02 KN
Fic*Pn = 72.07 KN
Mry = -5.80 KN*m Vry = -0.04 KN
Fib*Mny = 6.70 KN*m
Fiv*Vny = 52.43 KN
Mrz = 0.02 KN*m Vrz = -11.95 KN
Fib*Mnz = 5.05 KN*m
Fiv*Vnz = 92.72 KN
----------------------------------------------------------------------------------------------------------------------------- -----SAFETY FACTORS
Fib = 0.90
Fic = 0.90
Fiv = 0.90
148
--------------------------------------------------------------------------------------------------------------------------------------SECTION ELEMENTS:
Flange = Compact Web = Compact
--------------------------------------------------------------------------------------- -----------------------------------------------VERIFICATION FORMULAS:
Pr/(2*Fic*Pn) + Mry/(Fib*Mny) + Mrz/(Fib*Mnz) = 0.87 < 1.00 LRFD (H1-1b) Verified
Vry/(Fiv*Vny) = 0.00 < 1.00 LRFD (G2-1) Verified
Vrz/(Fiv*Vnz) = 0.13 < 1.00 LRFD (G2-1) Verified
Ky*Ly/ry = 119.65 < (K*L/r),max = 200.00
Kz*Lz/rz = 165.74 < (K*L/r),max = 200.00
STABLE
----------------------------------------------------------------------------------------------------------------------------- ----------
Section OK !!!
149
150
151
152
153
154
155
Mximo
desplazamiento
Nodo
Caso
UX (cm)
UY (cm)
UZ (cm)
U (cm)
0,1
-1,7
-1,6
2,3
21
10 (C)
156
157
158
159
160
161
162
Mxima deflexin
Barra
Caso
UX
(cm)
0
7
10 (C)
UY (cm)
UZ (cm)
U (cm)
0.1
1,1
1,1
163
164
0,3
---
Carga en la base
Wb
13,2
kN
rea de la base
Ab
0,070685835
m2
Eb
16000
KN/m2
0,3
Factor de forma
f-Ip
0,85
---
Asentamiento
0,00212713
Estrato 2
Asentamiento del pilar
Razn de Poisson
0,3
---
Carga en la base
Wb
14,15
kN
rea de la base
Ab
0,070685835
m2
Eb
38000
KN/m2
0,3
Factor de forma
f-Ip
0,85
---
Asentamiento
0,00096009
Estrato 3
Asentamiento del pilar
Razn de Poisson
0,3
---
Carga en la base
Wb
17,58
kN
rea de la base
Ab
0,070685835
m2
Eb
63000
KN/m2
0,3
Factor de forma
f-Ip
0,85
---
Asentamiento
0,000719478
165
Pilote helicoide
Estrato 2
Asentamiento del pilote helicoide
Razn de Poisson
Carga en la base
rea de la base
Mdulo de elasticidad del suelo
Dimetro del pilote (base helice)
v
Wb
Ab
Eb
B
0,3
13,2
0,073
38000
0,3048
--kN
m2
KN/m2
m
Factor de forma
f-Ip
0,85
---
Asentamiento 0,000881527
Estrato 2
Asentamiento del pilote helicoide
Razn de Poisson
Carga en la base
rea de la base
Mdulo de elasticidad del suelo
Dimetro del pilote (base helice)
v
Wb
Ab
Eb
B
Factor de forma
f-Ip
0,3 --16,51 kN
0,073 m2
63000 KN/m2
0,3048 m
0,85 ---
Asentamiento 0,000665046
166
Placa embebida
Estrato 1
Asentamiento de placa combinada
ngulo de friccin
0,3
---
Eb
16000
kPa
0,99
kPa
Ka
---
Ko
---
Asentamiento
0,00004950
Estrato 2
Asentamiento de placa combinada
ngulo de friccin
0,3
---
3,35
Eb
38000
kPa
0,49
kPa
Ka
---
Ko
---
Asentamiento
0,00001728
Estrato 3
Asentamiento de placa combinada
ngulo de friccin
0,3
---
3,15
Eb
63000
kPa
0,49
kPa
Ka
---
Ko
---
Asentamiento
0,000009800
167
Estructura
Materiales
689.154
Mano de Obra
206.746
Subcontratos
145.895
Cargas Sociales
103.373
1.145.168
Costos directos
Zapata
Combinada
Pilares de
concreto
153.984
84.795
2.016.300,00
99.439
69.504
25.200,00
48.000
96.000,00
34.752
12.600,00
49.720
Pilotes helicoides
303.143
237.051
2.150.100,00
Costos
indirectos
Costos
directos+Costos
indirecto
Imprevistos 3%
229.034
60.629
47.410
430.020,00
1.374.202
363.771
284.461
2.580.120,00
41.226
10.913
8.534
77.403,60
Utilidad 10%
137.420
1.552.848
36.377
28.446
258.012,00
411.061
321.441
2.915.535,60
Precio
CONCRETO
Dosificacin
Cemento
Piedra
Quebrada
Arena
Volumen de
concreto (m3)
Cemento (sacos
de 50 kg)
Resistencia a la
Piedra (m3) compresin a los 28 das
Arena (m3)
(kg/cm2)
(Lb/in2)
4,37
0,486
0,972
105
1500
2,5
5,1
0,472
0,944
140
2000
6,12
0,456
0,912
175
2500
1,5
7,65
0,427
0,854
210
3000
10,2
0,378
0,756
245
3500
Acero de refuerzo
Varilla #2(+15%)
Varilla #3(+15%)
Varilla #4(+15%)
Varilla #5(+15%)
Varilla #6(+15%)
Varilla #7(+15%)
Varilla #8(+15%)
Alambre
Varilla #9(+15%)
Descripcion
1,560 / Varilla grafilada #2 (5.25mm)
6 metros W
1,560 / UND Varilla deformada
grado 60 #3 3/8" 6 metros W
2,765 / UND Varilla deformada
grado 60 #4 1/2" 6 metros W
4,320 / UND Varilla deformada
grado 60 #5 5/8" 6 metros W
9,340 / UND Varilla deformada
grado 60 #6 3/4" 9 metros W
8,450 / UND Varilla deformada
grado 60 #7 7/8" 6 metros W
11 mil / UND Varilla deformada
grado 60 #8 1" 6 metros W
650 / KG Alambre negro #16
21,128.61 / UND Varilla deformada
grado 60 #9 1-1/8" 6 metros W
Precio UN
560
1.560
2.765
4.320
9.340
8.450
11.000
650
21.129
Unidad [m] o kg
Peso kg/m
0,384
0,56
0,996
1,56
2,25
3,042
6
1
3,975
Precio/kg
243
464
463
462
461
463
461
650
880
168
Introduccin
Este documento presenta un procedimiento para el diseo de una estructura de soporte
de paneles solares a utilizar en parques de generacin fotovoltaica.
La gua de diseo plantea un procedimiento para disear los siguientes elementos:
Pgina 2 de 49
Contenido
A. Datos de entrada ................................................................................................................. 3
B. Procedimiento de diseo geomtrico de la estructura ........................................................ 4
C. Procedimiento de cmputo de las cargas de diseo ........................................................... 8
D. Procedimiento de modelado, diseo y comprobacin de elementos de la estructura ...... 15
E. Procedimiento de diseo de la cimentacin ..................................................................... 24
Diseo de pilares de concreto ............................................................................................ 24
Diseo de la cimentacin con pilote helicoidal .................................................................. 28
Diseo de placa combinada ............................................................................................... 31
F. Anexos 39
Anexo 1 Tabla de velocidades de Viento para Costa Rica ................................................... 39
Anexo 2 Tabla de Factores CNW y CNL ASCE-7 ............................................................. 43
Anexo 3 Frmulas de diseo LRFD para la estructura ........................................................ 44
Anexo 4 Grficos del mtodo del mtodo de Broms ............................................................ 45
Anexo 5 Hojas de datos de los pilotes helicoides ................................................................. 47
Anexo 6 Hojas tcnicas de capacidad ltima y lateral de los pilotes helicoides .................. 48
Pgina 3 de 49
A. Datos de entrada
Los siguientes datos de entrada corresponden a informacin ya establecida en un
proceso de estudio de factibilidad e ingeniera bsica.
______
Distrito: ______
Angulo de inclinacin de los paneles en grados :
Velocidad de Viento [ km/h] : __________ (segn Anexo 1)
Pgina 4 de 49
Trabajar con
intermedios de requerirse.
Pgina 5 de 49
Ecuacin 1
Dnde:
, es la cantidad de paneles que se pueden montar sobre una pieza de longitud dada
, es la longitud de la pieza de acero Pieza de apoyo donde se apoyan los paneles
, es el ancho de cada panel.
b. En la siguiente figura se muestra de manera esquemtica como se disponen los
paneles uno seguido del otro en dos hileras.
Una vez determinada la cantidad de paneles que se pueden montar en una pieza de
dimensin , se procede a determinar las dimensiones de los marcos de soporte.
Pgina 6 de 49
Pgina 7 de 49
ngulo
[]
Separacin
entre
columnas,
[m]
B
15
3,1
20
3,0
25
2,9
30
2,7
35
2,6
40
2,4
45
2,2
Altura menor de la
estructura , [m]
1,1
1,4
1,6
1,9
2,1
2,3
2,5
2
1,4
1,7
1,9
2,2
2,4
2,6
2,8
1,5
1,8
2,0
2,3
2,5
2,7
2,9
0,3
0,6
0,7
Ecuacin 2
= 2
Ecuacin 3
2 = 1 + 2
Ecuacin 4
Dnde:
: Longitud del panel fotovoltaico
: ngulo de inclinacin de los paneles fotovoltaicos
: Longitud de la viga
: Separacin entre columnas
2 : Altura de la columna ms alta (altura mxima de la estructura)
1 : Altura la columna ms corta (distancia libre al suelo)
*Recomendaciones
Se recomienda que 1 , no sea menor a los 0.3 m, para evitar el contacto de los
paneles al suelo.
Pgina 8 de 49
Peso de la estructura
Para efecto de diseo la carga de paneles fotovoltaicos se convierte a una carga por
unidad de rea, esta carga se aplica con direccin de la gravedad, segn se muestra en la
siguiente figura.
Dnde:
: Longitud del panel fotovoltaico, [m]
: Ancho del panel fotovoltaico, [m]
1 : Peso de un panel, [kN]
Ecuacin 5
Pgina 9 de 49
W= 1.1 Ecuacin 6
*Este peso se calcula cada vez que se cambien los perfiles de la estructura.
La estructura con los paneles es una estructura abierta de una sola pendiente.
b. Datos de entrada
Velocidad de Viento 1: ___ [km]. (Segn Isotacas de Viento Costa Rica segn Patio).
Este valor debe convertirse en millas por hora.
Velocidad de viento en milla por hora = 0.6213711 [mph]
Dimensiones de los paneles: Largo ___ [m], Ancho: ___ [m]
Numero de paneles en la estructura: N: ___
: ngulo de inclinacin de los paneles fotovoltaicos
Pgina 10 de 49
Factor de efecto de rfaga (G): Para edificios rgidos u otras estructuras este factor
puede se toma como 0,85, de manera conservadora, Seccin 26.9.1 ASCE 7-10.
Pgina 11 de 49
Ecuacin 7
Ecuacin 8
psf
psf
Pgina 12 de 49
Pgina 13 de 49
Tipo de sitio
S1
S2
S3
S4
Tipo C (CSCR-pgina
C=
Dnde:
Ecuacin 10
Pgina 14 de 49
V= Ecuacin 11
Dnde:
V = Cortante en la base
C = Coeficiente ssmico.
W =peso total de la estructura
l. Fuerza ssmica de diseo: la Fuerza ssmica horizontal de diseo se toma como el
valor de la cortante en la base aplicado como carga puntual y distribuido como se
muestra en la siguiente figura
Ecuacin 12
Pgina 15 de 49
Combinaciones de
Carga de servicio
Caso 1: 1.4D
Caso 1: D
Caso 2:D + L
Caso 4:D + W
Caso 5:1.2D + E + L
Caso 5:1.2D + E + L
Caso 7:0.9D + E
Dnde:
D: Carga muerta, peso de la estructura y los paneles fotovoltaicos
L: Carga viva, se recomienda incluir el peso de un operador en la estructura con un valor
de 90 kg
E: Carga de sismo
W: Carga de viento
Las combinaciones para diseo LRFD brindan las cargas mayoradas de diseo de la
estructura y cimentaciones.
Las combinaciones de servicio se utilizan para la verificacin del desempeo de la
estructura y cimentaciones, la mayor combinacin ser utilizada como carga de servicio
Pgina 16 de 49
b. Simular la estructura apoyado sobre apoyos tipo empotre suponiendo que no hay
rotacin en la base.
c. Crear los casos de carga del paso anterior.
d. Preliminarmente asumir unos tipos de perfiles de acero A36 , que sean normados
por el AISC, a continuacin se listan unas dimensiones recomendadas para
realizar el anlisis preliminar:
o Columnas: Elementos tubulares circulares o cuadrados 2 (dos) pulgadas
de dimetro o peralte segn corresponda
o Vigas: Elementos rectangulares 2 (dos ) dos pulgadas de peralte .
o Soportes de paneles: Elementos en forma de C de dos pulgadas de
peralte.
e. Someter la estructura a una corrida de simulacin para todos los casos de carga
de diseo LFRD
f. Obtener las cargas en los elementos y los apoyos.
g. Verificar que las piezas seleccionadas no fallen por pandeo general, pandeo local
y cumplan con las capacidades requeridas en compresin, tensin, flexo
compresin y cortante segn correspondan.
h. Si dada la seleccin preliminar alguno o algunos elementos fallan se deben variar
espesores o la seccin de los elementos y volver a correr un anlisis hasta que
ningn elemento falle.
i. Las siguientes fuerzas deben obtenerse para realizar los diseos de la placa base ,
pernos de anclaje y cimentacin :
o Cargas axiales mximas en los apoyos
o Momentos mximos en los apoyos
o Cargas cortantes mximas en los apoyos
Pgina 17 de 49
Nota :El proceso de seleccionar el perfil adecuado para las solicitaciones de carga es
un proceso iterativo, el proceso se detiene cuando se encuentra el elemento ms liviano
de acero que cumpla con los requerimientos.
2 = 0.85 1 2 2 2 Ecuacin 14
1
Dnde:
1 = rea de la placa de acero
2 = rea del concreto
=factor de reduccin de capacidad igual a 0.6
e. La carga ultima del concreto por aplastamiento est dada por
= 1.7 1
Ecuacin 15
Pgina 18 de 49
(0.950.8 )
2
Ecuacin 18
= + 1 Ecuacin 19
1
Ecuacin 20
0.95
2
0.8
2
Ecuacin 21
Ecuacin 22
Ecuacin 23
Ecuacin 24
Ecuacin 25
Pgina 19 de 49
Si ( + )2 4 0 , entonces = 0.25( + (( + ) 4)
=factor de reduccin de capacidad igual a 0.95
a. Datos de entrada
Dimetro del perno ,[mm] (Se recomienda iniciar el clculo con media pulgada)
Excentricidad de aplicacin de las fuerzas = 0, [mm]
Separacin perno a perno S,[mm]
Distancia de los extremos al borde C , [mm]
Nmero de los pernos n=4
rea efectiva del perno ,[mm2]
Longitud de empotre recomendada = 12d
Profundidad de empotre corregida = Tan(35)
Dnde:
Ecuacin 26
Pgina 20 de 49
a,mn
1 si C 1.5hef 0.7 + 0.3 1.5h
Ecuacin 27
ef
c,N =Factor de modificacin por concreto agrietado igual a 1, (para una zona ssmica
se recomienda tomar en al concreto como agrietado)
cp,N =Factor de modificacin para anclajes post instalados, (tomar como 1)
ANco = 9h2ef , rea de falla proyectada de un nico perno (distancia al borde igual o
superior a 1.5hef )
ANc =rea de falla proyectada de un grupo de pernos, es el rea del pilar donde se
instalan.
Se presenta en la siguiente figura la seccin de la estructura con las dimensiones
indicadas.
Ecuacin 28
Dnde:
=4 pernos
Abrg =rea de apoyo de la cabeza del perno tomada como el rea del perno
(conservadoramente)
Pgina 21 de 49
Ecuacin 29
Dnde:
ca1 la distancia al borde perpendicular a la direccin a la aplicacin de cortante.
=rea de apoyo de la cabeza del perno tomada como el rea del perno
(conservadoramente)
=Factor de reduccin por traccin 0,75
= 1 (pernos embebidos)
e. Clculo de capacidad en cortante del acero del anclaje
La resistencia al cortante de los pernos de anclaje Vsa est dada por:
Vsa = nAse,V futa0.6 Ecuacin 30
Dnde:
=4 pernos
, =rea del perno
=resistencia del acero
f. Resistencia al arrancamiento del concreto para anclajes a cortante
Calcular la resistencia bsica al arrancamiento por cortante de un anclaje en concreto
fisurado, est dado por:
Dnde:
e =hef longitud de empotre
da =dimetro del anclaje
= 1 (pernos embebidos)
1 = distancia al borde en direccin a la cortante
Ecuacin 31
Pgina 22 de 49
/1.5
un tercio del espaciamiento mximo entre los anclajes dentro del grupo.
Ecuacin 32
Dnde:
AVco =rea proyectada por un nico anclaje dado por 4.5ca1 2
AVc =rea proyectada de una superficie de falla en el lado del concreto segn la figura.
ec,V=factor de modificacin por excentricidad igual a 1 (se supone carga centrada)
ed,V =factor de modificacin para el efecto de borde donde est dado por
c
a1
Ecuacin 33
c,V=factor por fisuracin igual a 1.0 para anclajes con concreto fisurado con o sin
refuerzo de borde menor que una barra #4
Pgina 23 de 49
1.5ca1
h,V =
ha
Ecuacin 34
Las capacidades de la tabla deben ser superiores o iguales a los valores mximos de
cortante en los apoyos obtenidos en el diseo de la estructura.
Pgina 24 de 49
Pilar de concreto
Pilote helicoide
Placa combinada
asentamientos despreciables
Suelos cohesivos y no cohesivos ,no aptos en Roca
Suelos Rocosos , Suelos
= =0 0
Ecuacin 35
0
=Esfuerzo vertical efectivo promedio en el tramo
=Permetro
=Longitud del tramo actualizado
Pgina 25 de 49
Ecuacin 37
Ecuacin 38
Ecuacin 39
Dnde
1 =0.65 para forma redonda
2 3 = 1 0.75/ , con =longitud del pilar
= 1, factor de excavacin mtodo seco
Pgina 26 de 49
= 0.6
kN
KN
KN
= 0.75
Ecuacin 40
= 0.75
Ecuacin 41
2.0
1.5
Usando las dimensiones del pilar de concreto ya determinadas y las cargas de se procede
a determinar la capacidad lateral .La siguiente tabla contiene los datos de entrada que se
utilizan el mtodo de Broms , se recomienda su uso para mayor orden.
Pgina 27 de 49
Datos de entrada
Carga Axial ltima
Momento ltimo
Longitud del pilar
Dimetro del pilar
Mdulo de elasticidad
del pilar (concreto)
Momento de Inercia de
la seccin del pilar
= 0.25( )4
2
Mdulo de deformacin
en la punta del pilar
kN-m
kN
21.500
MPa
16
MPa
Valor
1
2
1 2 80
=
3
=
32
Unidades
Descripcin
Brazo de palanca
KPa
m
KPa
Coeficiente de reaccin
horizontal
m3
Mdulo de seccion
perpendicular al plano de carga
MPa
KN-m
Profundidad de empotre
Momento resistente del pilar
---
---
/
/
Compresin inconfinada
promedio
kN
kN
Capacidad reducida, = 1
Segn recomendacin AASHTO
D/b y ec /b son los valores con los que se entra en las curvas para leer el factor
Qu
Kp b 3
Qu
c u b2
Pgina 28 de 49
Ecuacin 42
Dnde:
= factor de capacidad de soporte cohesin del suelo igual a 9
= rea proyectada de la placa helicoide
c =Cohesin del suelo
Suelo no cohesivo
= Ecuacin 43
Dnde:
= Capacidad ltima vertical
= rea proyectada de la placa helicoide
=factor de capacidad por sobrecarga
= Presin de sobrecarga efectiva
El factor se lee del siguiente grfico .
Pgina 29 de 49
Ecuacin 44
Ecuacin 45
= [ ( ) + (
)]
Ecuacin 46
= [ ( ) + (
)]
Ecuacin 47
Ecuacin 48
= / 1/5
Ecuacin 49
Dnde:
=Mdulo de Young del material del pilote
=Momento de Inercia del pilote
=Mdulo elstico de la sub-rasante
Pgina 30 de 49
Pgina 31 de 49
Se recomienda que la capacidad de carga permisible sea no ms del 50% de la carga que
produce un movimiento lateral bruto de 25 mm en la seccin ms baja de la parte
superior de la fundacin y la superficie del suelo.
Las cargas aplicadas al pilote helicoide se muestran en la siguiente figura
rea Cargada
Nc
--
/2
kN
0,50
----
Capacidad reducida Qu
Carga axial ltima
aplicada
kN
kN
Valor
Unidades
/2
Pgina 32 de 49
Carga de servicio
Momento ltimo 1
kN-m
Momento ltimo 2
kN-m
Carga ltima 1
kN
Carga ltima 2
kN
La siguiente figura presenta el modelo con las fuerzas que actan en la placa combinada
a disear
2 2 1 2
1 +2
Ecuacin 50
Ecuacin 51
( )
Ecuacin 52
Ecuacin 53
Ecuacin 54
Haciendo uso de las dimensiones del pedestal determinado por el diseo de la placa y de
los pernos de anclaje, las dimensiones iniciales B (ancho de la placa combinada) y H
(peralte de la placa) se obtiene un peso aproximado de cimentacin.
Se recomienda utilizar la siguiente tabla para tabular los datos.
Pgina 33 de 49
Dato
Altura de pedestal
Ancho de Pedestal
Espesor del pedestal
Ancho de la zapata B
Largo de la zapata Lf
Peralte de la zapata H
Volumen del concreto ,
Peso volumtrico del
concreto, P
Peso propio de la zapata
=
Valor
Unidades
m
m
m
m
m
m
3
24
/3
kN
Ecuacin 55
Dnde:
=Carga de servicio mxima
=Carga de peso propio de la cimentacin supuesta
=Capacidad permisible del suelo portante
=rea mnima de diseo
Se calcula la carga la cual debe ser menor a la capacidad reducida del suelo,
mediante la siguiente expresin
Wu =
N1 +N2
A
< Qu
Pgina 34 de 49
=0
Ecuacin 56
Dnde:
= Momento mximo de la seccin de diseo
= rea de acero a flexin.
= fluencia del acero igual a 420 MPa.
= Capacidad del concreto igual a 21 MPa.
=factor de reduccin a flexin igual a 0.9
d=peralte de la placa
Se debe respetar una cuanta mnima de acero la cual est dada por la siguiente
expresin
=
1.4
Ecuacin 57
Pgina 35 de 49
= 0.33
Ecuacin 58
= 0.17(1 + )
Ecuacin 59
= 0.083( + 2) Ecuacin 60
Dnde:
= relacin del lado largo al lado corto del dado de concreto
= factor de ajuste por la posicin de la columna en la zapata igual a 40
= permetro alrededor del rea que penetra la columna en caso de falla
1 +2
Ecuacin 61
2 = ( + )( + )
Ecuacin 62
Pgina 36 de 49
Ecuacin 63
Dnde:
= Carga puntal actuando.
= Ancho de la seccin de estudio
= Largo de la seccin de estudio
= Cortante ltimo proveniente de las cargas externas de los dos modos de falla.
= Capacidad de cortante del elemento
= Factor de reduccin para cortante = 0,75.
= 2 ( + /2)
1 =
Ecuacin 64
Ecuacin 65
Dnde:
=Lado largo de la zapata combinada
=altura de empotre
=lado de la columna perpendicular a la zapata
=lado de la columna paralelo a la zapata
Pgina 37 de 49
Ecuacin 66
e. Verificacin de Asentamientos
Se requieren los siguientes datos de entrada:
Relacin de Poisson
Pgina 38 de 49
v
Wb
Ab
Eb
B
0,3
--kN
m2
KN/m2
m
Factor de forma
f-Ip
0,85
---
Asentamiento
Razn de Poisson
Carga en la base
rea de la base
Mdulo de elasticidad del suelo
Dimetro del pilote (base helice)
Factor de forma
v
Wb
Ab
Eb
B
0,3
--kN
m2
KN/m2
m
f-Ip
0,85
---
Asentamiento
v
Wb
Ab
Eb
B
0,3
--kN
m2
KN/m2
m
Factor de forma
f-Ip
0,85
---
Asentamiento
Pgina 39 de 49
F. Anexos
Anexo 1 Tabla de velocidades de Viento para Costa Rica
Pgina 40 de 49
Pgina 41 de 49
Pgina 42 de 49
Pgina 43 de 49
ngulo de
Inclinacin
7.5
15
22.5
30
37.5
45
Direccin Gama =0
Caso
CNW
CNL
CNW
CNL
1,2
0,3
1,2
0,3
-1,1
-0,1
-1,1
-0,1
-0,6
-1
0,9
1,5
-1,4
1,6
0,3
-0,9
-1,3
1,3
1,6
-1,9
1,8
0,6
-1,5
-1,6
1,7
1,8
-2,4
-0,3
2,2
0,7
-1,8
-1,8
2,1
2,1
-2,5
-0,5
2,6
-1,8
-1,8
2,1
2,2
-2,4
-0,6
2,7
1,1
-1,6
-1,8
2,2
2,5
-2,3
-0,7
2,6
1,4
Pgina 44 de 49
Ecuaciones de diseo a
compresin
=
flexin-compresin
Zona 1 < Lp :
= ((0.658) ) , 1.50
= (
0.877
2
reduccin
compresin
=Parmetro de esbeltez
= Lmte de fluencia del acero
=Mdulo de elasticidad del Acero
=Longitud no arriostrada
=Factor de largo efectivo
=radio de giro
3750
, =
de
Si
5700
( )
( )
Zona 3 < Lb
5700
0.2 utilizar:
8
+ (
+
) 1.0
9
= [ ( )
, =
= , = ( )
) , > 1.50
300
Si
+ (
) 1.0
Pgina 45 de 49
Pgina 46 de 49
Pgina 47 de 49
Pgina 48 de 49
Pgina 49 de 49