Professional Documents
Culture Documents
Outline
Power Factor:
Definition & Examples
Cost Savings
Power Factor Correction Equipment
Harmonics:
Introduction
Harmonics and Power Factor Correction Capacitors
IEEE 519 Standard
Traditional Harmonic Mitigation Methods
Active Filter Technology & Applications
Power Factor =
Reactive
Power
(kVAR)
=
=
Reactive
Power
kW
Active
Power
Power Factor =
Beer (kW)
Mug Capacity (kVA)
Current that is drawn from the voltage source is then only used to do
real work (kW) and not to create a magnetic field (kVAR). The source
current is then minimized
The customer only pays for the capacitor
Since the utility doesnt supply the kVAR, the customer doesnt
pay for it
In short, capacitors save money
Schneider Electric Global PQ June 2013
A2
kW
100
kVAR
100
kVA = 141
PF = 70%
Schneider Electric Global PQ June 2013
kW
100
kVAR
75
kVA = 125
PF = 80%
kW
10
0
kVA = 100
PF = 100%
8
Billing
Demand
kW
900.0
800.0
850.0
875.0
910.0
780.0
890.0
870.0
760.0
750.0
690.0
870.0
Power
Factor
0.8000
0.7950
0.7625
0.7511
0.7574
0.7722
0.7950
0.7950
0.7625
0.7511
0.7574
0.7722
Actual
Actual
Demand Demand
kVA
kW
1,000.0
800.0
888.9
706.7
944.4
720.1
972.2
730.2
1,011.1
765.8
866.7
669.2
988.9
786.2
966.7
768.5
844.4
643.9
833.3
625.9
766.7
580.7
966.7
746.5
0.0
0.0
Savings
2012
Possible
Cost
Savings
$550.00
$513.33
$714.24
$796.20
$793.01
$609.18
$571.08
$558.25
$638.61
$682.46
$601.30
$679.47
Required
Required
% Reduction
Capacitor kVAR Capacitor kVAR of Transformer
for 0.92 pf
for 1.0 pf
kVA Load
259
600
20%
238
539
21%
304
611
24%
331
642
25%
334
660
24%
266
551
23%
265
600
21%
259
586
21%
272
546
24%
284
550
25%
253
501
24%
296
614
23%
$7,707.13
Approximate cost of standard power factor correction equipment $12 to $15K === Payback about 2 years.
Approximate cost of filtered power factor correction equipment $18 to $21K === Payback about 3 years.
Active Filters
LV and MV Hybrid VAR Compensation Products
10
11
Outline
Power Factor:
Definition & Examples
Cost Savings
Power Factor Correction Equipment
Harmonics:
Introduction
Harmonics and Power Factor Correction Capacitors
IEEE 519 Standard
Traditional Harmonic Mitigation Methods
Active Filter Technology & Applications
13
Harmonic Basics
Waveform seen
with oscilloscope
Fundamental
rd
3 Harmonic
th
7 Harmonic
t1h
5 Harmonic
Harmonic Frequency
Sequence
1
2
3
4
5
6
7
:
19
60Hz
120Hz
180Hz
240Hz
300Hz
360Hz
420Hz
:
1140Hz
+
0
+
0
+
+
Hc = np 1
HC = characteristic harmonics
to be expected
n = an integer from 1,2,3,4,5,
etc.
p = number of pulses or
rectifiers in circuit
14
Harmonic Filtering
15
Multi-pulse Converters
Harmonic Orders Present
Hn = np +/- 1
Hn = characteristic
harmonic order
present
n = an integer
p = number of pulses
Elimination of lower orders
removes largest amplitude
harmonics
Schneider Electric Global PQ June 2013
Hn
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
AccuSine SWP
AccuSine PCS
3 phase
18-pulse
x
x
x
x
16
Harmonic Basics
Nonlinear loads draw harmonic current from source
Does no work
Voltage: flat
topping of
waveform
Inverter
Converter
DC bus
A
B
C
17
Harmonic Basics
Why the concern?
Current distortion
Added heating = reduced capacity
Equipment failures
Transformers
Conductors and cables
Nuisance tripping of electronic
circuit breakers (thermal
overloads)
Ih
Loads
Vh = Ih Zh
18
Harmonic Basics
Voltage distortion
Created as current harmonics flow
through the system
Interference with other electronic loads
Ih
Malfunctions to failure
Loads
Vh = Ih Zh
19
Magnification of harmonics by
resonance
Utility
VFD
20
Capacitor Resonance
21
Detuned Capacitors
22
L2
L3
Electromechanical
switching
elements
(contactors) are
used to connect a
capacitor group.
23
IEEE 519-1992
Defines current distortion as TDD (Total Demand Distortion)
THDv =
2
V
h
Vf
TDD =
2
I
h
If ( FLA )
THDi =
2
I
h
If
24
IEEE 519-1992
Issues addressed:
THD(V) delivered by utility to user (Chapter 11)
THD(V) must be < 5% [< 69 KV systems]
Defines the amount of TDD a user can cause (Chapter 10)
Based upon size of user in relation to power source
Table 10.3 for systems < 69 kV
Defines limits for voltage notches caused by SCR rectifiers
Table 10.2
Defines PCC (point of common coupling)
25
IEEE 519-1992
TDD and THD(I) are not the same except at 100% load
As load decreases, TDD decreases while THD(I) increases.
Example:
Total I,
rms
Full load
936.68
836.70
767.68
592.63
424.53
246.58
111.80
Measured
Fund I, Harm I,
rms
rms
936.00
836.00
767.00
592.00
424.00
246.00
111.00
35.57
34.28
32.21
27.23
21.20
16.97
13.32
THD(I)
3.8%
4.1%
4.2%
4.6%
5.0%
6.9%
12.0%
TDD
3.8%
3.7%
3.4%
2.9%
2.3%
1.8%
1.4%
26
<11
4.0%
7.0%
10.0%
12.0%
15.0%
h>=35
0.3%
0.5%
0.7%
1.0%
1.4%
TDD
5.0%
8.0%
12.0%
15.0%
20.0%
27
Harmonic Standards
Designed
to protect utility
Most harmonic problems are not at PCC with utility
Occur
28
Advantage
Disadvantage
TDD
Multiplier*
Dependent
upon SCR***
Increase short
circuit capacity
Reduces THD(V)
Increases TDD
Not likely to occur**
C-Less
Technology
Lower TDD
Simplified design
Less cost
Compliance is limited
Application limited
Size limited
30 - 50% TDD
0.90 - 0.95
Impedance (3%
LR or 3% DC
choke)
Compliance difficult
30 - 40% TDD
1.05 - 1.15
5th Harmonic
filter
18 - 22% TDD
1.20 - 1.45
Broadband filter
8 - 15% TDD
1.25 - 1.50
12-pulse rectifiers
Reduces TDD
Reliable
Large footprint/heavy
Good for >100 HP
8 - 15 % TDD
1.65 - 1.85
18-pulse rectifiers
Reduces TDD
Reliable
Large footprint/heavy
Good for >100 HP
5 - 8% TDD
1.65 - 1.85
Large footprint/heavy
Very high cost per unit
High heat losses
< 5% TDD
2.0 - 2.5
XFMR
SOURCE
Sense
LOAD
Sense
Is
Il
Ia
Parallel connected
Is + Ia = Il
Optional CT
location
Ia
Is
<5% TDD
30
31
32
AccuSine PCS
50-300 Amps
208-480 VAC/600 VAC/690 VAC
AccuSine PFV
50-300 Amps
208-480 VAC/600 VAC/690 VAC
No harmonics
33
AccuSine SWP
The Schneider Electric solution for harmonic filtering in buildings.
34
AccuSine PCS
The Schneider Electric solution for active harmonic filtering in
industrial installations.
35
AccuSine PCS/PFV
Power Diagram
IGBT Module
Pre-charge
Contactor
S1
S3
S5
DC Bus
Capacitors
Fuse
AC
Lines
Fuse
Line
Inductor
+
C
Fuse
Inductor
Filter
Board
S2
S4
S6
36
AccuSine PCS
Performance Summary - Harmonics
Discrete Spectrum Logic (DSL)
TDD <= 5%, if loads have =>3% Z installed
2nd to 50th orders, discrete
<2 cycle response
Resonance avoidance logic
Adjustable trip limits per harmonic order
On-board commissioning program
Phase rotation (clockwise required)
Automatic CT orientation (phase rotation/polarity/calibration)
Run lockout if not possible to re-orient
Oscilloscope feature built into HMI
Load/source bar graphs
Load balancing
Can parallel up to 99 units of each size and mix sizes
37
System Solution
AccuSine PCS Sizing Example
A 125 HP variable torque 6-pulse VFD with 3% LR
Required AHF filtering capability = 47.5 amperes
38
AccuSine PCS/PFV
Product Package
Standard (UL/CSA, ABS)
Three current ratings
Enclosed NEMA 1/IP20
50 amp 52(1321mm) x 21(533mm) x
19(483mm)
Weight 250#(114 K\kg)
100 amp 69(1753mm) x 21(533mm) x
19(483mm)
Weight 350#(159 kg)
300 amp 75(1905mm) x 32(813mm) x
20(508mm)
Weight 775#(352 kg)
39
AccuSine PCS/PFV
Product Package
Other enclosures (380 - 480VAC)
NEMA 12, IP30, IP54
50 amp 75(1905mm) x
31.5(800mm) x 23.62(600mm)
Weight 661Ib(300 kg)
100 amp 75(1905mm) x
31.5(800mm) x 23.62(600mm)
Weight 771Ib(350 kg)
300 amp 75(1905mm) x
39.37(1000mm) x 31.5(800mm)
Weight 1012Ib(460 kg)
Free standing with door interlocked
disconnect
CE Certified, C-Tick, ABS, UL, CUL
Schneider Electric Global PQ June 2013
40
Height
300A
1000 mm
800 mm
Height
1900 mm
Depth
800 mm
50/100A
800 mm
600 mm
1972 mm 600 mm
41
AccuSine Performance
At VFD Terminals
AccuSine injection
Source
current
Order
Fund
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
TDD
AS off
AS on
% I fund % I fund
100.000%100.000%
0.038% 0.478%
31.660% 0.674%
11.480% 0.679%
0.435% 0.297%
7.068% 0.710%
4.267% 0.521%
0.367% 0.052%
3.438% 0.464%
2.904% 0.639%
0.284% 0.263%
2.042% 0.409%
2.177% 0.489%
0.293% 0.170%
1.238% 0.397%
1.740% 0.243%
0.261% 0.325%
0.800% 0.279%
1.420% 0.815%
0.282% 0.240%
0.588% 0.120%
1.281% 0.337%
0.259% 0.347%
0.427% 0.769%
1.348% 0.590%
35.28% 2.67%
42
43
44
45
AccuSine PCS
Dual Mode Operation
Assignment of capacity
Assign priority to Harmonic or PF/LB
(fundamental) modes
Use % of harmonic mode to set split
100% means capacity utilized for
harmonic correction, then left
over can be used for PF/LB
0% assigns fundamental (PF
correction/LB) current as primary
mode, left over used for harmonic
correction
Can split to limit harmonic mode
capacity, left over to PF
correction/LB
I as = I h + I f
2
Examples
Ih
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
95.0
If
99.5
98.0
95.4
91.7
86.6
80.0
71.4
60.0
43.6
31.2
46
AccuSine PFV
Power Factor & VAR Compensation
HVC (AccuSine PFV + PF caps)
Larger systems approach
HVC is Hybrid VAR Control
47
Thank You
Questions?
48