Professional Documents
Culture Documents
Content
1.0
Introduction
1.1 Objectives
1.2 Project Description
1.3 Floor Plans
2.0
Lighting
2.1 Daylighting Factor Analysis
2.1.1
2.1.2
E-Library
3.0
Office
Acoustics
3.1 External Noise Calculation
3.1.1
Discussion Room
E-Library
4.0
Reference
Reading Terrace
1.0 Introduction
1.1 Objectives
This project aims to integrate the understanding of the principles of lighting and acoustics in
the context of the final design project of Studio 5. This project involves forward-thinking of
daylighting systems and the integration of artificial lighting, strategies for noise management
and room acoustics.
2.0 Lighting
2.1 Daylighting Factor Analysis
Daylight factor (DF) is defined as the ration of interior illuminance(Ei) to available outdoor
illuminance:
Where Eh is the unobstructed horizontal exterior illuminance. The daylight factor concept is
applicable only where the sky luminance distribution is known or can resonably be estimated.
In this case, the average daylight level in Malaysia (EH) is assumed to be 20000 lux.
The CIBSE Lighting Guide 10(LG10-1999) broadly bands average daylight factors into the
following categories:
2-5 Adequately lit but artificial lighting may be in use for part of the time
>5 Well lit artificial lighting generally not required except at dawn and dusk but
glare and solar gain may cause problems
Daylight is used in several spaces in order to decrease mechanical energy usage of the library. The
chosen spaces are the Outdoor Childrens area and Ground Floor Caf.
2.1.1
60.11m2
Perimeter: 16m
Height: 4.2m
Area: 67.2m2
Daylight Factor
67.2
100%
60.11
= 111.8 % 0.1
=11.18 %
= 100 %
11.18 =
100%
32000
= 3500
The selected childrens outdoor area has a daylight factor of 11.18%, and natural illumination of 3500 lux.
Based on the requirements of MS1525, the childrens outdoor area has more than 6% casuing a very
large with thermal glare problems.
Therefore, based on recommended illuminance categories, childrens outdoor area need to reduce by
2300 lux. Double Skin Faade will be added to the opening of the childrens outdoor area to avoid the
thermal glare problems.
2.1.2
Caf Area
The selected area is the caf. It is located at the ground floor. The reason being
chosen is to study the area which exposed to daylight. The caf is designed to
have more opening to allow interaction between outside and inside.
76.44m2
Perimeter: 7.8m
Height: 7.6m
Area: 59.28m2
Daylight Factor
59.28
100%
76.44
= 77.5 % 0.1
= 7.75 %
= 100 %
7.75 =
100%
32000
= 2500
The selected Caf area has a daylight factor of 7.75%, and natural illumination of 2500 lux. Based on the
requirements of MS1525, the caf area has more than 1% casuing a very large with thermal glare
problems.
Therefore, based on recommended illuminance categories, Caf area need to reduce by 1300 lux. As
the opening is a glass faade, curtain blinds or louvers blinds will be added to avoid too much glare
problems especially during the afternoon sun.
10
E-Library
The E-Library located at the first floor of the library. It is an enclosed space
where minimal daylighting get through this space. Sufficient and even
distribution of lighting is needed for the users to carry out their research at the
E-library.
11
Material Properties
Material
Concrete
Glass Panel
Fabric
Timber
Function
Colour
Area (m2)
Surface Type
Wall
Floor
Ceiling
Wall
Chair
Table
Grey
Grey
Grey
Transparent
Dark Brown
Beige
43.19
77.29
77.29
43.19
15.05
2.1
Reflective
Reflective
Reflective
Reflective
Absorptive
Reflective
Reflectance
Value
70
25
70
6-10
25-35
30
Fixture Properties
Types of Fixture Parabolic T8 Fluorescent Lighting
Specification
Waltage: 32 W
Colour Temperature: 5000k
Bulb Finish: Warm White
Luminious Flux
(lm)
Utilization Factor
Maintanance Factor
No. of Luminaires
350 77.3
=
(1300 3) 0.6 0.8
= 14 ()
=
12
1
77.3
2.4
14
= 0.98
=
= 0.98
2.4
= 2.35 ()
Fittings required along wall
No. of fittings/row = 4
= 3.5 () 4 ()
6.55
13
From the calculation, the E-Library required a total of 14 units of lighting fixtures with 1.64m spacing
arranged in 4 row configuration to achieve even light distribution.
14
Office
The Office located at the second floor of the library. It is an enclosed space
where minimal daylighting get through this space. Sufficient and even
distribution of lighting is needed for the workers to do work.
15
Material Properties
Material
Function
Colour
Area (m2)
Concrete
Timber
Concrete
Glass Panel
Timber
Wall
Floor
Ceiling
Window
Furniture
Grey
Light Brown
Grey
Transparent
Light Brown
Surface Type
Reflective
Reflective
Reflective
Reflective
Reflective
Reflectance
Value
70
60
70
6-10
30
Fixture Properties
Types of Fixture LED Downlight
Specification
Luminious Flux
(lm)
Waltage: 8 W
Colour Temperature: 3000k
Bulb Finish: Warm Light
8000 lux per lamp
Utilization Factor
Maintanance Factor
16
No. of Luminaires
200 38
=
800 0.4 0.8
= 30 ()
=
1
38
3.042
30
= 0.37
=
= 0.37
3.042
= 1.125 ()
Fittings required along wall
30
6
5.2
17
There are 30 lights fitting at the office. The light fittings are controlled by 5 switches, SW4 and SW5 can
be turned off during the day due to sufficient daylighting from the side glass panels where there is a void
beside the office. SW1, SW2 and SW3 have to be turn on during the day to achieve 200 lux requirement
of MS1525 and also uniform lighting of the space.
18
3.0 Acoustic
3.1 External Noise Calculation
3.1.1
19
The sound level assumption is made during non-peak hour (10am) and during peak hour (6pm). Noise
sources are categorized as external traffic noise as well as internal noise. They are marked by human
activities along the busy street, along Jalan Haji Salleh.
Peak Hour
Highest Reading: 86dB
Lowest Reading: 67dB
Using the formula where,
= 1010 (
1
)
10
Highest Reading
1
)
1 1012
= (108.6 )(1 1012 )
= 3.98 104
86 = 1010 (
Lowest Reading
1
)
1 1012
6.7
12
= (10 )(1 10 )
= 5.01 106
67 = 1010 (
Total Intensities
Combined Sound Pressure Level
= 1010 [
= 86.05
20
4.03104
11012
],
1
)
10
Highest Reading
1
)
1 1012
= (106.7 )(1 1012 )
= 5.01 106
67 = 1010 (
Lowest Reading
1
)
1 1012
= (105.2 )(1 1012 )
= 1.58 107
52 = 1010 (
Total Intensities
Combined Sound Pressure Level
= 1010 [
5.17106
11012
],
= 67.13
According to Australian Acoustic Association, recommended internal noise levels for library general area
is 40dB.
21
Surface Area(m2)
11.20
55
11.20
11.20
49
47
17.57
54
= 10
= 10
1
47
= 10
1
= 105.5
1
105.5
= 10
= 49
= 54
1
54
= 10
1
= 104.9
=
1
104.7
= 10
= 2.00 105
55
= 104.7
= 3.16 106
= 10
= 47
= 55
55
SRI (dB)
1
104.9
= 105.4
=
1
105.4
= 3.98 106
= 1.26 105
22
= (
55
Surface area
(m2)(S)
11.20
Transmission
Coefficient (T)
3.16 106
49
47
54
11.20
11.20
17.57
1.26 105
2.00 105
3.98 106
Material
SRI (dB)
Lightweight
concrete
UHPC panels
Rockwool Flexi
Softwood timber
ST (Area x TC)
3.54 105
1.41 104
2.24 104
6.97 106
= 7.96 106
= 10log(
= 10log(
1
)
7.96 106
= 51
86 51 = 34
The overall transmission loss from Jalan Haji Salleh to the library area is 34dB. The sound pressure level
at Jalan Haji Salleh during highest is 86dB, the sound that transmitted through the wall into the library is
34dB. According to the noise criteria environment perception, 34dB is a meeting room environment. It is
lower than the standard SPL of the library general area which is 40dB
23
The sound pressure for reading terrace is 40dB. The combine SPL reading of 86.05dB of Jalan Haji
Salleh is too high for a reading terrace. The design solution proposed to address to this issue is to create
a buffering zone which is the operable shutters are inserted into the opening facing the main road. The
shutters also acts as the faade which absorb the sound from the traffic during the peak hour, users can
close the shutters to prevent sound from entering the reading terrace.
Figure 3.2 Transmission loss from Jalan Haji Salleh into library area
24
25
1
)
1 1012
= (1 104 ) + (1 106 )
= 1.01 104
2
] , = 1 1012
2
= 1010 [
1.01 104
]
1 1012
= 80.04
The sound pressure for library area is 35dB according to Australian Acoustic Association standard. The
combine SPL reading of 80.04dB is too high for a reading area.
The design solution is to arrange the spaces according to zoning during the design planning stage. The
childrens reading area is located on the other side of the car service center. There is also plants placed
around the area to absorb the noise.
26
3.2.1
27
Furniture
Opening
People(peak)
Brickwork, 10mm
flush pointing
4mm glass
Parquet fixed in
asphalt, on
concrete
Plasterboard
10mm thick
backed with
25mm thick
bitumen
Clothupholstered
seats
Timber
Wall
20.5
Absorption
Sound
Coefficient at Absorption
2000Hz (s)
(Sa)
0.22
4.51
Glass panel
Floor Finish
14.09
23.27
0.05
0.06
0.7
1.4
Ceiling finish
23.27
0.05
1.16
Arm Chair
10
0.87
8.7
Table
3.27
0.3
1.16
Single seals
glass
-
Door
1.26
0.54
4.59
0.46
3.68
Material
Function
Area, m2
(A)
= 0.16
= 0.16
85.165
25.9
= 0.52
28
Component
Wall
Floor
Ceiling
Furniture
Opening
People(peak)
Brickwork, 10mm
flush pointing
4mm glass
Parquet fixed in
asphalt, on
concrete
Plasterboard
10mm thick
backed with
25mm thick
bitumen
Clothupholstered
seats
Timber
Wall
20.5
Absorption
Sound
Coefficient at Absorption
500Hz (s)
(Sa)
0.12
2.46
Glass panel
Floor Finish
14.09
23.27
0.05
0.07
0.7
1.63
Ceiling finish
23.27
0.15
3.49
Arm Chair
10
0.49
4.9
Table
3.27
0.05
0.16
Single seals
glass
-
Door
1.26
0.44
0.55
0.46
3.68
Material
Function
Area, m2
(A)
= 0.16
= 0.16
85.165
17.57
= 0.78
The reverberation time for discussion room in 2000Hz of absorption coefficient is 0.52s while in 500Hz
of absorption coefficient is 0.78s. According to the standard reverberation time, the standard comfort of
general use of discussion room is within the range of 0.6 to 1s. Hence, the reverberation time of
discussion room is within the range of comfort reverberation time.
29
E-Library
30
Component
Wall
Absorption
Coefficient at
2000Hz (s)
0.22
Sound
Absorption
(Sa)
9.5
0.02
0.3
0.05
0.86
23.19
3.86
Arm Chair
10
0.87
8.7
Material
Function
Area, m2
(A)
Brickwork, 10mm
flush pointing
6mm glass
Carpet, on concrete
Plasterboard 10mm
thick backed with
25mm thick bitumen
Cloth-upholstered
seats
Timber
Wall
Table
3.27
0.3
1.16
Opening
Door
2.73
0.54
1.47
People(peak)
12
0.46
5.52
Floor
Ceiling
Furniture
43.18
= 0.16
= 0.16
282.88
54.26
= 0.83
31
Wall
43.18
Absorption
Sound
Coefficient at Absorption
500Hz (s)
(Sa)
0.12
5.18
Glass panel
Floor Finish
43.18
77.29
0.05
0.25
2.16
19.32
Ceiling finish
77.29
0.15
11.6
Arm Chair
10
0.49
4.9
Table
3.27
0.56
1.83
Opening
2.73
0.44
1.20
People(peak)
12
0.46
5.52
Component
Wall
Floor
Ceiling
Furniture
Material
Brickwork, 10mm
flush pointing
6mm glass
Carpet, on
concrete
Plasterboard
10mm thick
backed with 25mm
thick bitumen
Cloth-upholstered
seats
Timber
Function
Area, m2
(A)
= 0.16
= 0.16
282.88
51.71
= 0.87
The reverberation time for e-library in 2000Hz of absorption coefficient is 0.83s while in 500Hz of
absorption coefficient is 0.87s. According to the standard reverberation time, the standard comfort of
general use of e-library is within the range of 0.4 to 0.8s. Hence, the reverberation time of discussion
room is slightly higher between the ranges of comfort reverberation time.
32
3.3.1
33
Material
4x8x18 3-cell
lightweight concrete
masonry units,
common brick,
mortared together
Timber, wood veneer
finishes
Pivoting Door
Surface Area
2.664x3.66=9.75
SRI (dB)
51
3x1.2=3.6
33
Wall
= 10
= 51
51
1
= 10
= 105.1
=
1
105.1
= 7.943 106
Pivoting Door
= 10
= 33
33
1
= 10
= 103.3
=
1
103.3
= 5.012 104
34
Material
SRI (dB)
Lightweight
concrete with
common brick
Timber, wood
veneer finishes
51
Surface area
(m2)(s)
9.75
33
3.6
= (
Transmission
Coefficient (T)
7.943 106
5.012 104
ST(Area x TC)
7.74 105
1.804 103
= 1.41 104
= 10log(
= 10log(
1
)
1.41 104
= 38.5
65 38.5 = 26.5
The overall transmission loss from the reading terrace to the library study area is 38.5dB. The sound
pressure level at the reading terrace is 65dB, the sound that transmitted through the wall into the library
reading area is 26.5dB. This reading is lower than the standard SPL of the library study area which is
35dB. Hence, it is an ideal value for the library study area as the noise from reading terrace does not
penetrate to the study zone and disrupt the concentration of studying.
35
4.0 Reference
Association of Australian Acoustical Consultants Guideline ... (n.d.). Retrieved June 21, 2016, from
http://www.daydesign.com.au/downloads/AAAC guideline.pdf
Illuminance - Recommended Light Levels. (n.d.). Retrieved June 23, 2016, from
http://www.engineeringtoolbox.com/light-level-rooms-d_708.html
Steffy, G. (2008). Architectural Lighting Design. New York: Wiley and Sons
36