Operate under positive pressure to


minimize the ingress of dirty air
Internal finish should be non-shedding
Provide access to all sections
Unit must be cleanable
Attenuators should be non-shedding
and located upstream of HEPAs

Humidifiers present a risk of microbiological


growth use clean steam
Drain pans must not allow standing water
Provision for HEPA filter testing with aerosol
injection ports and downstream access

Make-Up air is required for:


Exhaust air
Space pressurization
Leakage (refer to ASHRAE Fundamentals)

Must remove external contamination sources


Dehumidification to control dew point

Outside Air Load


Direct Drive Fan with VFD
Dual Fans
Humidifier

Pre-filter

& Final Filter


TEAO Motor
Direct Digital Controls
Flexibility & Redundancy
6

Understand peak load coil


conditions
Sensible
Latent (dehumidification)

Velocity and air pressure drop


Chilled water operating
temperatures

Reduce the airs capacity to hold


moisture
Increase pressure or cool it

Attract water vapor with a desiccant


Liquid
Solid

Moves air in & out of cleanroom


Recirculating air handlers with
ducted terminal HEPA filters are
most common

Sensible Only Cooling


Direct Drive Fan with VFD
Humidifier
Pre-filter

TEAO

Motor
Minimize Pressure Drop
Direct Digital Controls
Control Valves

HVAC systems for cleanrooms are expensive


and consume high amount of energy
Optimize air change rates and differential
pressures
Maximize life of HEPA filters
Design for good maintenance and testing

ASHRAE HVAC Applications - Clean Spaces


IEST Recommended Practices
ISPE Pharma Engineering Guides
US FDA Center for Drug Evaluation and
Research http://www.fda.gov/cder/