You are on page 1of 113

Clculos Elctricos

FM

Version 3.7

Lista de Cargas del Sistema


N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

TAG

Datos generales
Descripcin
CAMARA (FUENTE)
MICROONDAS (FUENTE)
INFRAROJOS (fuente)
EQUIPOS DE INTERFASE

Ubicacin

Alimentacin
Cant. Tipo Voltios
Sist.
13
AC
240
1 Fase
16
AC
240
1 Fase
26
AC
240
1 Fase
18
AC
240
1 Fase
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110

Consumo unitario
Valor Unidad
120
VA
0.2
A
0.2
A
333
VA

Proyecto:
Instalacin:

TOMOPORO
CERCA PERIMETAL

POTENCIA TOTAL
Consumo unitario
T. Uso Factor
FP Eff % Horas Oper.
0.95 98
8
1.00
0.95 98
8
1.00
0.95 98
8
1.00
0.95 98
8
1.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

VA
1560.00
768.00
1248.00
5994.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

W
1482.00
729.60
1185.60
5694.30
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

VAR
487.11
239.81
389.69
1871.63
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Sub Total

9091.50

TOTAL [VA] 9570.00


kVA 9.57

2988.23

Clculos Elctricos Para Motor


Nombre del Proyecto:
Cdigo:
Nombre del motor:

Nombre
Codigo
Motor XXX

Fecha
7/22/2016

Datos del Motor


Tipo de Motor: MOTOR DE INDUCCION
Tipo de alimentacin:
Trifasico
Clase NEMA:
B De propsito general
Tipo de aislamiento NEMA:
F 155C MAX (operacin)
Codigo letra rotor bloqueado NEMA:
G 5,6 - 6,29 kVA/HP
Potencia:
15 HP
Potencia Activa salida:
11.19 kW (Rotor)
Potencia Activa entrada:
12.29 kW (Alimentacin)
Potencia Reactiva entrada:
14.29 kVA
Voltaje nominal:
220 V
Frecuencia de alimentacin:
60 Hz
Corriente nominal:
37.51 A
Corriente de arranque:
234.02 A (6.23 In)
FP:
0.86
Eff.:
91 %
Factor de Servicio:
1.15
N de Polos:
4
Cerramiento:
TEFC
Velocidad de sincronismo:
1800 RPM
Deslizamiento aprox:
2.54 %
Totalmente Cerrado con
ventilacin externa
Velocidad de operacin aprox:
1754 RPM
Frame NEMA:
254T

Corriente a plena carga en base a un motor de: 15 HP con un voltaje de operacin de: 208 V la
corriente a plena carga es: 46.2 A, segn CEN 2004

Datos de Alimentador
Factor mult. de corriente:
Corriente de diseo:
Tabla aplicada:
Material:
Voltaje de Operacin:
Temp. Op.:
Fact. Temp:
Calibre:
Capacidad del cable:
Conductores por fase:

125 % (CEN 2004 430.22)


46.2A X 125% = 57.75A
310-16 CEN 2004
COBRE
0 - 2000 V
0
60C
26-30 C
100% de la capacidad nominal del cable
4 AWG/MCM
70 A
1
6/113

Cap. Total por fase:


% carga en el cable:
% Reserva:
Material del ducto:
Resistencia:
Reactancia:
Longitud del cable:
Cada de tensin:
Mxima cada permitida:
Cada durante el arranque:
Max cada al arranque:

70 A
82.50% @57.75A
17.50%
PVC
1.020 Ohm/kM
0.157 Ohm/kM
100.0 M
2.83 %
5%
6.31 %
15 %

CEN 2004 Tabla 9

0.00102 Ohm/M

CEN 2004 Tabla 9

0.000157 Ohm/M

a corriente nominal
6 X In (FP=0,2 IEEE Std 399-1997)

7/113

Datos de Canalizacin
Calibre de conductores:
4 AWG / MCM
Aislante:
THW
rea del cable:
62.92 mm2
CEN 2004 Tabla 5
Cantidad de cables:
3
rea Total:
188.77 mm2
Tamao tubera:
4"
Tipo : Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD
rea Total:
8110.96 mm2
CEN 2004 Tabla 4
% de Ocupacin:
2%

Proteccin y Arranque
Proteccin contra cortocircuitos
Tipo: Interruptor automatico de disparo instantaneo
Caracterstica de motor: Polifasico todo proteccion
Ajuste mximo del dispositivo:
800 % la corriente de diseo (CEN 2004 430-152)
Cap. de corriente del dispositivo:
250 A
Amperios Frame
Mxima corriente de ajuste:
369.60 A
Amperios de disparo
Marca: Cualquiera
Polos:
3
Voltaje Max:
600 V
Contactor Arrancador / Proteccin contra sobrecarga
Tipo de Arranque: Arranque directo.
Tipo de contactor: No Reversible
Caracterstica: Motores con un factor de servicio no menor a 1,15
Ajuste de corriente segn CEN: Articulo 430-32
Factor para ajuste de proteccin:
125 % In
Mxima corriente de ajuste:
57.75 A
Tipo de Contactor
Tamao del contactor:
5 NEMA
AC-3
Voltaje de operacin:
460/575 V
Contactos
Cap. Del contactor hasta:
200 HP

NA
Contactos
Amper-Frame:
270 A

Articulo

Cant.
auxiliares
auxiliares

NC

Sistema de puesta a tierra


Tipo de conductor:
Cantidad de conexiones:
Calibre mnimo:

Desnudo
2 Puntos
2/0 AWG

CEN

430-32
(po
defecto)
430-34

2
2

CEN 2004 tabla 250-122

8/113

Gabinete de control / potencia


rea de instalacin
Clase: No Clasificada
Divisin:
N/A
Gabinete o Tablero
Ubicacin:
Exterior
Cerramiento:
4x NEMA
Tipo de proteccin: Sellado contra agua y resistente a la corrosin. Los
gabinetes tipo 4X tienen las mismas caractersticas
que los tipo 4, adems de ser resistentes a la
corrosin.

Capacidad de las barras:


300 A
Instalacin: Auto soportado
Otras caracteristicas

Bot n

de START

Bot n

de STOP

Selector

de operaci n

Comunicaci n

con PLC

TX

Comunicaci n

con RTU

Fusibles
control

Calentador

Volt metro

Bot n

paro de emergencia

Luz

indicadora 1

Verde

Pantalla

Luz

indicadora 2

Roja

Luz

indicadora 3

Ambar

Ventilaci n

interna

para sist.

interno

Amper metro
digital

auxiliar para control

Notas

V3.7

fm

9/113

220 V

Barra

3(1 X 4 AWG/MCM)

Interruptor

250A (AF) / 369.6A (AT)

220 V
NEMA 5
AC-3

Arrancador

120 V

57.75A (AT)

Circuito de Control

M
15 HP

Clculos Elctricos Para Transformador


Nombre del Proyecto:
Cdigo:
Nombre del transformador:

Datos Elctricos
Potencia:
Tipo de alimentacin:
Impedancia base:
Frecuencia:
Relacin de Trans.:

75 kVA
Trifasico
3.07 m
60 Hz
1:1

Clase del transformador :


Transformadores Monofsicos de Distribuc
Enfriamiento:
TIPO OA Sumergido en aceite, con enfriam
natural.

Primario

Secundario
Tipo de conexin:
Delta
Hilos:
2
Voltaje de lnea:
0.48 kV L-L
Voltaje de fase:
0.48 kV
Corriente de lnea:
90.21 A
Corriente de Fase:
52.08 A
Conexin del neutro: No tiene

Alimentadores
Primario

Secundario

Factor mult. de corriente


125 %
Corriente de diseo:
112.76 A
Material:
COBRE
Voltaje de Operacin Cable: 5001-35000 V
Tabla aplicada: Tabla 310.73 CEN 2004
Calibre
2 AWG / MCM
Temp. Op.
90C
0
Fact. Temp
36-40 C
Corriente nominal cable
150 A
Conductores por fase
1
Cap. Total por fase
150 A
% carga en el cable
75.18%
% Reserva
24.82%
Calibre del neutro:
4 AWG / MCM
Conductores por neutro:
1

Factor mult. de corriente

Voltaje de Operacin Cable:

Corriente nominal cable

Conductores del neutro:

Datos de canalizacin
Primario

Secundario
Calibre de conductores
Aislante

2 AWG / MCM
THW
Tabla 5 CEN 2004

Calibre de conductores

11/113

rea del cable


86.14 mm2
Cantidad de cables
3 (Fases + Neutro igual calibre)
rea Total
258.42 mm2
Tamao tubera
4"
Tipo : Tubo de PVC, Tipo A
Tabla 4 CEN 2004
rea Total
8946.53 mm2
% de Ocupacin
2.89%

12/113

Protecciones
Primario

Secundario

Limitaciones sobre el lugar: Cualquiera


% Impedancia del TX: Mas de 6% pero menos de 10%
Tipo de proteccin: Fusible
Tabla 450.3(B) CEN 2004
Ajuste max. del dispositivo:
250 % I de diseo
Cap. de corriente del dispositivo:
15 A
AF
Max corriente de ajuste:
281.91 A
AD
Sistema de puesta a tierra
Tipo de conductor:
Cantidad de conexiones:
Calibre mnimo:

Ajuste max. del dispositivo:


Cap. de corriente del dispositivo:
Max corriente de ajuste:

Desnudo
2 CEN 2004 tabla 250-122
2/0
0

Otras caractersticas
Indicador

de temperatura

Indicador

de presi n

Indicador

de nivel de liquido

Interior

Indicador

de sobrecarga

Exterior

Color de pintura:

Descargador

Instalado

de sobre voltajes

en

Gris

V3.7

13/113

nsformador
Fecha
7/22/2016

transformador :
adores Monofsicos de Distribucin Tipo Intemperie/Pos
(IEEE C57.93)
Sumergido en aceite, con enfriamiento

Tipo de conexin:
Estrella
Hilos:
3
Voltaje de lnea:
0.48 kV L-L
Voltaje(s) de fase: 0.277128129 kV
0 kV L-N
Corriente de lnea:
90.21 A
Corriente de Fase:
90.21 A
Conexin del neutro: solidamente a tierra

(480 V)
(0 V)

Factor mult. de corriente


125 %
Corriente de diseo:
112.76 A
Material:
COBRE
Voltaje de Operacin Cable:
0 - 2000 V
Tabla aplicada: Tabla 310.16 CEN 2004
Calibre
1/0 AWG / MCM
Temp. Op.
90C
Fact. Temp
36-40 C
Corriente nominal cable
154.7 A
Conductores por fase
1
Cap. Total por fase
154.7 A
% carga en el cable
72.89%
% Reserva
27.11%
Calibre del neutro:
4/0 AWG / MCM 0
Conductores del neutro:
2
0

Calibre de conductores
Aislante

1/0 AWG / MCM


THW
Tabla 5 CEN 2004
14/113

rea del cable


143.70 mm2
Cantidad de cables
8 (Fases + Neutro igual calibre)
rea Total
1149.58 mm2
Tamao tubera
4"
Tipo : Tubo de PVC Rigido, Sch. 40 y tubo de PE
Tabla 4 CEN 2004
rea Total
8110.96 mm2
% de Ocupacin
14.17%

15/113

Tipo de proteccin: Interruptor automtico


Tabla 450.3(B) CEN 2004
Ajuste max. del dispositivo:
125 % I de diseo
de corriente del dispositivo:
200 A
AF
Max corriente de ajuste:
140.95 A
AD

AF: AMPERIOS FRAME


AD: AMPERIOS DE DISPARO

fm

16/113

Proyecto:
0

TX:

Cargas del Transformador


N
1
2
3
4
5
6
7
8
9
10

100%

Descripcin

Carga

Unidad

VA
VA
HP
HP
HP
HP

FP

Ef.

VA

0
0
0
0
0
0
0
0
0
0

Sub Total

0.00

0.00

90

Total

S P2 Q2

Nota: todas las cargas se consideran trifsicas para fines del calculo, a menos que se
exprese directamente en VA

Uso

Reserva

Capacidad del Transformador

75 kVA

VAR
0
0
0
0
0
0
0
0
0
0

0.707

Voltaje del sistema 480 V

W
0
0
0
0
0
0
0
0
0
0

0.00% Uso
100.00% Reserva
75 kVA Reserva

0 VA

Clculos Elctricos Banco de Baterias


Segn norma IEEE 1115-2000
Nombre del Proyecto:
Cdigo:
Identificador :

Tension terminal de celda:

1.1 V

Cap. Inicial del Banco:

A-H

Temp. electrolito:
Margen de diseo:
Factor de envejecimiento

C
1.10 FD
1.25 FE

Tabla de carga
Tiempo Inicio
(min)

Tiempo Fin
(min)

Duracion
(min)

L1
L2
L3
L4
L5
L6

0
0
0
0
0
0

30
0
0
0
0
0

30.00
0.00
0.00
0.00
0.00
0.00

37.18
0
0
0
0
0

18.59
0.00
0.00
0.00
0.00
0.00

Aleatoria LA

0.00

0.00

Carga
1
2
3
4
5
6

Descripcion

Corriente
(A)

TOTAL

Capacidad
(A-H)

18.59 A-H
Capacidad Preliminar

Curva de carga
Corriente (A)
40
35
30
25
20
15
10
5
0
0

10

15

20

25

30 Tiempo (min)
35
18/113

Corriente (A)
40
35
30
25
20
15
10
5
0
0

10

15

20

25

30 Tiempo (min)
35

Tabla de comportamiento general de carga


SEC

Desde (min)

Hasta (min)

Duracion(min)

Total A

1
2
3
4
5
6
7
8
9
10

0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

30
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

30.00
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

37.18
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

Capacidad
(A-H)
18.59
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

19/113

Demanda Maxima:
Demanda Minima:
Demanda Promedio:

n
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

T (MIN)
30.000
-

37.18 A
37.18 A
37.18 A
Calculo del factor de capacidad
T2
A para T1
A para T2
266
-

T1
30
-

Factor K1
1.387
-

Factor K2
-

Curva del factor de correccin por temperatura de electrolito


3
2.5
2

1s - 10 min
30 min

Factor Tt
1.5

60 min
3H
5-8H

1
0.5
0
-29

-20

-10

10

20

25

20/113

Hoja de seleccin de capacidad


Periodo

Carga

Cambio de carga
(A)

(A)

Duracion
(min)

Tiempo final de
seccion (min)

Factor de
Factor de
capacidad (Kt) temperatura (Tt)

Valor positivo
(AH)

37

37

30.000

30.000

1.387

1.000
Sub total
Total

52
51.58
51.58

1
2

37.18
0.00

37
-37

30.000
0.000

30.000
0.000

1.387

1.000

51.58
0.00
0.00
0.00

Sub total
Total
1
2
3

37
0
0

37
-37
0

30.000
0.000
0.000

30.000
0.000
0.000

1.387

1.000

Sub total
Total
1
2
3
4

37
0
0
0

37
-37
0
0

30.000
0.000
0.000
0.000

30.000
0.000
0.000
0.000

1.387

1.000

Sub total
Total
1
2
3
4
5

37
0
0
0
0

37
-37
0
0
0

30.000
0.000
0.000
0.000
0.000

30.000
0.000
0.000
0.000
0.000

1.387

1.000

Sub total
Total
1
2
3
4
5
6

37
0
0
0
0
0

37
-37
0
0
0
0

30.000
0.000
0.000
0.000
0.000
0.000

30.000
0.000
0.000
0.000
0.000
0.000

1.387
#N/A
#N/A
#N/A
#N/A
#N/A

1.000

Sub total
Total
1
2
3
4
5
6
7

37
0
0
0
0
0
0

37
-37
0
0
0
0
0

30.000
0.000
0.000
0.000
0.000
0.000
0.000

30.000
0.000
0.000
0.000
0.000
0.000
0.000

1.387
#N/A
#N/A
#N/A
#N/A
#N/A
#N/A

1.000

Sub total
Total

52
0
0
0.00
0.00
52
0
0
0
0.00
0.00
52
0
0
0
0
0.00
0.00
52
0
0
0
0
0
0.00
0.00
52
0
0
0
0
0
0
0.00
0.00

21/113

Aleatoria

0.000

0.000

#N/A

#N/A
Total

Tamao de la seccin mayor 51.57 AH + Seccin aleatoria 0AH = Tamao sin correccin:

Capacidad final :TSC X FD X FE =

70.91

0.000
0.00
51.57 AH

AH

V3.7

22/113

ctricos Banco de Baterias

n norma IEEE 1115-2000


Fecha
7/22/2016

Curva de carga

15

20

25

30 Tiempo (min)
35
23/113

15

20

25

30 Tiempo (min)
35

24/113

lo del factor de capacidad


Factor Kt
1.387
-

25/113

de seleccin de capacidad
Valor negativo

(AH)

0
0.00

0.00
0.00

0
0
0.00

0
0
0
0.00

0
0
0
0
0.00

0
#VALUE!
0
0
0
0
0.00

0
#VALUE!
0
0
0
0
0
0.00

26/113

0.000

fm

27/113

Cada de tensin sistemas Trifasico (Conductor de Cobre)


Carga:
Longitud del circuito:
Tensin del sistema
FP:
Calibre del Cable:
Material de la tubera:
R:
X:

100000 VA
200 m
220 V
0.84

100 kVA

500

Cond. por fase

0.0445 OHM/kM
0.064 OHM/kM

Cada de tensin:
Voltaje Final:

(r cos x sen
5 kV 2

V (%) (kVA m)

V(%) = 2.97
213.44 V

de Cobre)
k

(r cos x sen )
2
10 5 kV

k=0.0001

V (%) (kVA m) k

Regulaci n

Max.

Cada de tensin sistemas Monofasicos (Conductor


Carga:
Longitud del circuito:
Tensin del sistema
FP:

3%

5%

Calibre del Cable:


Material de la tubera:
R:
X:

7210 VA
40 m
240 V
1

7,21 kVA

1
0.62 OHM/kM
0.148 OHM/kM

Cada de tensin:
Voltaje Final:
V3.7

V(%) = 0.62
238.5 V

ofasicos (Conductor de cobre)


k

(r cos x sen )
5 kV 2

Distancia
0
0
0
0.00215278

Cond. por fase


k=0.0021

V (%) (kVA m) k

0.62086111
1

%) = 0.62

3
1000

22

10

220

Caida de tension en sistemas DC


Resistividad del cobre:

mm 2
m

0.018

Distancia del tramo:

200

48

VDC

Dimetro del cable:

1.63

mm

Resistencia del cable

4.42

Resistencia de carga

1152

Voltaje en terminales

47.82

VDC

Regulacin:

0.38

Tipo

de carga

Vatios
Amperio

Voltaje del sistema:


Calibre del cable:

Calculo de corriente de corto circuito


Tension del sistema:
0.48 kV
Lugar: Barra 480

Impedancias del sistema


Equipo
Red
Cable

Rt =
Xt =
Zt =
Icc =
R/X =
Factor K =
Icc asimetrica =

R
0.194
0.013

X
0.788
0.004

Total
0.2072
0.7920
0.8186
0.34 kA sim
0.26

1.44
0.69 kA asim

IEC60909

Calculo de corriente de corto circuito


Motor Trifsico
An lisis

Potencia:
15 HP
Voltaje nominal:
0.22 kV en el lado de la falla
Eficiencia:
91 %
FP:
0.86
Tipo: Motor de alta velocidad

Motor de alta velocidad


Motor de Baja velocidad
Compensador

Xd"
15
35
25

Xd
25
50
40

Sub
Transitorio

Transitorio

Xd
80
100
160

T1. Reactancias en % de motores y compensadores

Se tiene que:

Sn
Sn =

Luego:

Xm

P
FP
14.29

kW

X
V2

100 S n

X=
Xm =

25
846.59

mOhm

0.8465948763

Rm 0,2 X m
Rm =

Rm

Xm

169.32

0.20

Zt R X
2
t

I cc , sim
Por lo tanto:

Icc, sim =

mOhm

2
t

Zt=

Vn2
3 Zt
147.12

A simtricos

0.8633607589
863.36 mOhm

Luego tenemos que:

K=

1.54

, para

Rt
0.20
Xt

( IEC 60909 )

I cc 2 K I cc , sim

Finalmente:
Basado en la norma UTE C 15-105 y IEC 60 909.

Icc =

320.61

A asimtricos
1.540952

Calculo de corriente de corto circuito


Transformador trifsico
Potencia:
75 kVA
Voltaje en lado de falla (V2):
0.48 kV
Voltaje de corto circuito %:
4
Tabla T1
Ra: 0.207232196 Ohm
Xa: 0.791974384 Ohm

V1:

13.8 kV

Rr 0.000250716 Ohm reflejada


Xr 0.000958154 Ohm reflejada

T1. Tensin de cortocircuito Vcc normalizada para los transformadores MT/BT de distribucin pblica.

kVA
Vcc (%)

630
4

800
4.5

Se tiene que:

Por lo tanto:

Se tiene que:

Por lo tanto:

Se tiene que:

Por lo tanto:

Luego:

1000
5

Z t Vcc
Zt =

Vn2
Sn

1250
5.5

122.88 m

X t Zt

Por lo tanto:

Luego tenemos que:

0.12288

X del transformador

Xt =

122.88 m

Rt 0,20 X t
Rt =

Xr =0.958m

R del transformador

24.576 m

Rtotal
X total

I cc , sim

2000
7

Z del transformador

Rr =0.25m

0.20

0.1263022338

Z to tal ( Rt Rr ) 2 ( X t X r ) 2
Se tiene que:

1600
6

Zt =

126.30

Vn2
3 Zt

Icc, sim =

K = 1.54

2.19

kA simetricos

, para

I cc 2 K I cc , sim

Rt
0.20
Xt

( IEC 60909 )

Finalmente:
Basado en la norma UTE C 15-105 y IEC 60 909.

Icc =

4.78

kA asimetricos
1.5401381277

Calculo de corriente de corto circuito


Aporte de corriente de la red electrica

Tension Nominal:
Icc:
Scc:
Icc Asimetrica:

13.8 kV
17 kA sim
234.6 MVA
35.27 kA asim

Ra/Za:
Za:
Xa:
Ra:
Ra/Xa:
Factor K:

0.239
0.812
0.788
0.194
0.246
1.467

Red electrica

13,8kV 17kA sim

(IEC 60909)

N
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

PDVSA 90619.1.089
Cada de tensin mtodo amperios pie
Potencia de lmparas:
430 W
Voltaje de operacin:
220 V
Distancia entre lmparas:
30 M
Tramo inicial:
20.00 M
Cantidad de Luminarias:
12
Distancia entre lmpara:
98.424 FT
Distancia
Amperios Distancia (FT)
A-pie
(M)
65.6
20.00
-1.95
65.6
20.00
128.2
1.95
131.2
40.00
256.4
1.95
196.8
60.00
384.7
1.95
262.4
80.00
512.9
1.95
328.0
100.00
641.1
1.95
393.6
120.00
769.3
1.95
459.2
140.00
897.5
1.95
524.8
160.00
1025.7
1.95
590.4
180.00
1154.0
1.95
656.0
200.00
1282.2
1.95
721.6
220.00
1410.4
1.95
787.2
240.00
1538.6
1.95
852.8
260.00
0.0
1.95
918.4
280.00
0.0
1.95
984.0
300.00
0.0
1.95
1049.6
320.00
0.0
1.95
1115.2
340.00
0.0
1.95
1180.8
360.00
0.0
1.95
1246.4
380.00
0.0
1.95
1312.0
400.00
0.0
1.95
1377.6
420.00
0.0
Total

10001.0 A-P

Calibre del conductor:


Factor K:
Area:

Caida de tension:
% de Caida de tension:

14

21.4

66360 Mil Circular


3.23 V
1.47%

Calculo de cada de tensin para circuitos monofsicos de iluminacin

Tensin del sistema

0.12 kV

Calibre del cable:

Factor de potencia
Cantidad de Postes
P. Poste
D0
DEP

0.95
29
100 VA
114 m
5m

Canalizacion:
Resistencia:
Reactancia:

N
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

Potencia

[VA]
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
0

Paso de
Distancia [m]
Distancia [m]
114
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5

114
119
124
129
134
139
144
149
154
159
164
169
174
179
184
189
194
199
204
209
214
219
224
229
234
239
244
249
254
0

Total

kVA x m
11.4
11.9
12.4
12.9
13.4
13.9
14.4
14.9
15.4
15.9
16.4
16.9
17.4
17.9
18.4
18.9
19.4
19.9
20.4
20.9
21.4
21.9
22.4
22.9
23.4
23.9
24.4
24.9
25.4
0

(r cos x sen )
5 kV 2

k = 0.005

V (%) ( kVA m) k
V(%) = 3.07

Voltaje Final:

533.6 kVA x m

ofsicos de iluminacin

10

0.39 /km
0.144 /km

(r cos x sen )
5 kV 2

V (%) (kVA m) k

116.31 V

3.07904976
0.005770333
0.317560429
0.3122499

Calculo de Alimentador
Datos de la Carga
Carga nominal:
9000 W
Tension del sistema:
220 V
Fp:
1
Eff:
100 %
Factor de diseo:
125 %
Corriente:
23.62 A
Datos del Conductor
Calibre:
10 AWG/MCM
Capacidad nominal:
30 A
Factor correcion Temp:
1
Conductores por fase:
2
Capacidad Total:
60.00 A

3(1#16 AWG)
3(2#500 MCM)
3(2#16 AWG)
1(1#16 AWG)+1T#16 AWG
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)
(#)

13800
13800
220
480
480

15000
15000
600
600
600

Hasta

XLPE-PVC
XLPE-PVC
XLPE-PVC
XLPE-PVC
THHN

250
300
260
100
100

TEST
TEST
TEST
TEST
TEST

TEST
TEST
TEST
TEST
TEST

4/0 AWG
16 AWG
500 MCM
16 AWG
16 AWG

Calibre Neutro

Desdes

Tipo Aislante

Cant. Act.X
Fase

3(1#4/0 AWG)

Tension
Max (V)

Fases

P-001

Tension
Oper (V)

COVENIN 398

Calibre

TAG

Distancia (M)

Lista de Cables Monopolares

(#)

Proyecto:

Nomenclatura COVENIN

X ( n Y ) mN # Y ' pT # Y ' '

Indicacin de X fases de n conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre
Links
Aralven (Cables)

16 AWG

1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Cantidad
Cond. Tierra
(M)

Cantidad
Cond.
Neutro (M)

Cantidad
Cond. Activo
(M)

Cond Act.

Cant. Tierra
X GF

Cant. Neutro
X GF

Calibre
Tierra

750
900
1560
600
100
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
100
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Observaciones

e Y, mas m conductores de neutro (N) calibre Y, mas p conductores de tierra (T) calibre Y.

AISLANTES DE CONDUCTORES
Tipo
DESNUDO
FXT TFF TWF

RHHN

Descripcion

Sin recubrimiento
Los conductores flexibles de cobre tipo FXT, TFF y TW-F son utilizados para alambrado de aparatos, c
tableros elctricos de control, bateras de vehculos, instalaciones generales industriales y comerciales
requiera de gran flexibilidad debido a las dificultades de trabajo y en general como cables sometidos a
movimiento, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser us
secos y hmedos, su temperatura mxima de operacin es 60 C y su tensin de servicio para todas la
es 600 V.
AISLANTE DE MATERIAL TERMOPLASTICO, XLPE 600 V. - 90 C, ANTILLAMA.

THHN

Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en
industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por du
usarse en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias qum
como pinturas, solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de condu
utilizado como THHN puede ser usado en lugares secos con temperatura mxima de operacin de 90
utilizado como THWN-2 puede ser usado en lugares secos y hmedos con temperatura mxima de op
as mismo cuando estn expuestos a aceites, grasas, pinturas, solventes qumicos, etc., su temperatur
operacin es 75 C. En cuanto a su tensin de servicio, para todas las aplicaciones, es de 600 V.

THW

Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificacione
comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el Nation
Code. Este tipo de conductor puede ser usado en lugares secos y hmedos, su temperatura mxima d
de 75 C y su tensin de servicio para todas las aplicaciones es 600 V.

TTU

Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edifi
industriales y comerciales, son especialmente aptos para instalaciones a la intemperie o directamente
como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares
hmedos, su temperatura mxima de operacin es 75 C y su tensin de servicio para todas las aplica

TW

Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones
comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conduc
usado en lugares secos y hmedos, su temperatura mxima de operacin es 60 C y su tensin de ser
las aplicaciones es 600 V

XHHW

Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificacio
comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el N
Electrical Code. Este tipo de conductor puede ser utilizados en lugares secos y hmedos, su temperatu
operacin es 90 C y su tensin de servicio para todas las aplicaciones es 600 V.

ORES

o
dos para alambrado de aparatos, cableado de
enerales industriales y comerciales donde se
general como cables sometidos a continuo
ste tipo de conductor puede ser usado en lugares
su tensin de servicio para todas las aplicaciones

, ANTILLAMA.

circuitos de fuerza y alumbrado en edificaciones


para instalaciones especiales por ductos difciles y
solinas, etc. y otras sustancias qumicas corrosivas
Electrical Code. Este tipo de conductor cuando es
ratura mxima de operacin de 90 C, pero si es
dos con temperatura mxima de operacin de 90 C,
entes qumicos, etc., su temperatura mxima de
as aplicaciones, es de 600 V.

fuerza y alumbrado en edificaciones industriales,


tal como se especifica en el National Electrical
medos, su temperatura mxima de operacin es
V.

itos de fuerza y alumbrado en edificaciones


nes a la intemperie o directamente enterrados, tal
ductor puede ser usado en lugares secos y
n de servicio para todas las aplicaciones es 600 V.

uerza y alumbrado en edificaciones industriales,


lectrical Code. Este tipo de conductor puede ser
racin es 60 C y su tensin de servicio para todas

e fuerza y alumbrado en edificaciones industriales y


perie, tal como se especifica en el National
res secos y hmedos, su temperatura mxima de
nes es 600 V.

18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
3 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
600 MCM
700 MCM
750 MCM
800 MCM
900 MCM
1000 MCM
1250 MCM
1500 MCM
1750 MCM
2000 MCM

Calibr
e

Metros de cable por nivel de tension (TOTAL)

600

5000

15000

3500

0
800
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1560
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
900
0
0
0
0
0
0
0
0
0
0
0
0
750
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Ocupacion de ductos
Cable Monopolar
N

Calibre

Aislante

Cantidad

Diametro*
mm

Area por cable


mm2

14.53

165.81

4.60

16.62

4.60

16.62

4.60

16.62

4.60

16.62
Area Total

Tipo de Ducto:

Diametro:
Pulgadas
Diametro**
Area Total

Dimetro mnimo recomendado


2 1/2 "

Max. Ocupacion
*Fabricante del cable: Aralven
** Segn tabla del CEN 2004

40.00%

Ocupacin

Total Grupo
mm2
994.88
0.00
0.00
0.00
0.00
994.88

mm2

101.5 mm
8091.37 mm2

12.30%

Potencia

Factor de Potencia

Aparente

Activa

Reactiva

[VA]

Potencia:
FP (%):
Cos():
Sen():

18600
60
0.6
0.80

[W]

[VAR]

S
P
Q

31000.00 VA
18600.00 W
24800.00 VAR

S
VA
W
VAR

x
p
Q
S

eje

P
18600
31000
23250

y
0
18600.00
18600.00
18600.00
0
18600.00

0
0
0
24800.00
0
24800.00

0
24800.00

18600.00
0

Q
11160
18600
13950

14880
24800
18600

Triangulo de potencia
30000
25000
20000
(VAR)

15000
10000
5000
0
0

5000

10000

15000
(W )

20000

25000

30000

TABLERO ELECTRIC
Tipo de Tablero:

Instalacion:
NLAB

C. Interrupcin [kA]:
22
Color:
GRIS INDUSTRIAL
Interruptor principal 3P [A]:
400

Auto soportado
Cerramiento NEMA:
3R
Corriente de Barras [A]:
100

Polos:
18
Voltaje del Tablero [V]:
240

Fases:
Proyecto:
3
Alimentador Principal:
Calibre
Aislante
250 MCM
A

Tuberia
Carga Conectada

VA

Material

Conductor

Diametro
[pul]

Cond. por
fase

Aislante

Interruptor
Calibre

Tipo

In [A]
3P

1500

Carga N 1

CARGA 4

RESERVA

1500

N
1

PVC

THHN

6 AWG

QC

20

1500

500

500

PVC

THHN

14 AWG

QC

20

500

11

1000

13

1000

15

1000

17

THHN
B

19

21
23
25

27
29
31

33
35

V3.7

VA

% POT.

6250

15.04

0.33

6250

15.04

0.33

6250

15.04

0.33

TOTAL

18750

RO ELECTRICO
Proyecto:

entador Principal:
Aislante
THHN

ejemplo
Instalacion:
Cnd X fase
1

Conduit
4

Entrada

ejemplo

Superior

Nombre del Tablero:


ejemplo

Interruptor
N

In [A]
3P

Tipo

Conductor
Calibre

Aislante

Tuberia
Cond. por
fase

Diametro
[pul]

Material

2
4

VA

Carga Conectada
1000

30

THQC

250 MCM

TTU

PVC

1000

1000

1250

10

90

THQC

14 AWG

TTU

PVC

1250

12

1250

14

1000

16

1000

18

1000

Carga N 2

CARGA 3

RESERVA

20
22
24
26
28
30
32
34
36

RESERVA
6000.00
32.00%

VA

BARRA

DE TIERRA

BARRA

DE NEUTRO

TABLERO ELECTRICO
Tipo de Tablero:

Instalacion:
NLAB

C. Interrupcin [kA]:
22
Color:
GRIS INDUSTRIAL
Interruptor principal 3P [A]:
400

Auto soportado
Cerramiento NEMA:
3R
Corriente de Barras [A]:
100

Polos:
36
Voltaje del Tablero [V]:
240

Fases:
Proyecto:
3
Alimentador Principal:
Calibre
Aislante
1/0 AWG
A

Tuberia
Carga Conectada

VA

Material

Conductor

Diametro
[pul]

Interruptor

Cond. por
fase

Aislante

Calibre

Tipo

In [A]
3P

carga 1

1500

PVC

THW

12 AWG

QC

20

carga 4

1500

PVC

THW

12 AWG

QC

20

11

13

15

17

THHN
B

19

21

23

25

27

29

31

33

35

V3.7

VA

% POT.

3000

7.22

50.00

3000

7.22

50.00

TOTAL

6000

LERO ELECTRICO
Proyecto:
Alimentador Principal:
Aislante Cnd X fase
THHN

ejemplo
Instalacion:
Conduit

Entrada

Superior

Interruptor
N

In [A]
3P

Tipo

ejemplo
Nombre del Tablero:
ejemplo

Conductor

Tuberia

Calibre

Aislante

Cond. por
fase

Diametro
[pul]

Material

VA

Carga Conectada

PVC

THW

12 AWG

QC

20

1500

carga 2

PVC

THW

12 AWG

QC

20

1500

reserva

6
8
10
12
14
16
18

20
22
24
26
28
30
32
34
36

RESERVA
1500.00
25.00%

VA

BARRA

DE TIERRA

BARRA

DE NEUTRO

SEPARACIN MINIMA RECOMENDADA ENTRE DUCTOS Y BANDEJAS


NIVELES
1.- APLICACIONES ALTAMENTE SUSCEPTIBLES A RUIDOS.
SEALES DE INSTRUMENTOS DE 4-20 mA 24Vdc, OTRAS SEALES ANLOGAS < 50Vdc Y TRASMISORES DIGITALES
SEALES DISCRETAS DE 24 Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS ANALGICOS +- 50Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS DIGITALES +- 24Vdc
CIRCUITOS DE TERMOCUPLA Y RTD
CIRCUITOS TELEFNICOS

2.- APLICACIONES MEDIANAMENTE SUSCEPTIBLES A RUIDOS


ILUMINACION E INTERRUPTORES DE 24Vdc O MENOS
SEALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO

3.- APLICACIONES BAJAMENTE SUSCEPTIBLES A RUIDOS


ALIMENTADORES EN 120/240 Vac DE MENOS DE 20 A
ILUMINACION E INTERRUPTORES DE 24Vdc O MAS
SEALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO

4.- APLICACIONES DE POTENCIA INTERMEDIA


PRIMARIOS Y SECUNDARIOS DE TRANSFORMADORES < 5kVA
BARRAS AC O DC 0-800 V CON CORRIENTES MAYORES A 20 A

5.- APLICACIONES DE ALTA POTENCIA


BARRAS AC O DC> 1kW Y/O CORRIENTES MAYORES A 800 A

CASO DE ESTUDIO
CASO:

NIVEL A:
1

SEPARACIN MINIMA RECOMENDADA:

26 IN

66.04 CM

NOTAS
1 Esta hoja no aplica para ductos no metlicos
2 La distancia definida aqu, indica el espacio mnimo entre el tope y el fondo de las bandejas o el espacio lateral entre ellas.
3 Estas distancias tambin aplican como el espacio entre bandejas y equipos de potencia menores a 100kVA
4 Las distancia mnimas de los ductos se indican en referencia al exterior de los mismos
5 Cuando seales de distintos niveles deban cruzarse, deben hacer en un ngulo de 90. Cuando no sea posible mantener las distancias de
separacin se debe interponer una barrera metlica aterrada.
6 Los niveles 3 y 4 pueden ser canalizados en la misma bandeja siempre que se coloque una barrea entre ellos

7 Cuando sea impractico separarlos, los niveles 1 y 2 pueden ser usados en la misma bandeja, siempre que tenga una barrera metlica aterrada entre
ellos.
8 Las bandejas de todos los niveles deben ser metlicas solidamente aterradas.
9 Bandejas y ductos de los niveles 1 y 2 no podrn ser llevadas en paralelo con equipos de alta potencia cerrados mayores a 100kVA a 150 cm de las
bandejas y 80 cm de los ductos.
10 Cunado no se posible mantener el espacio indicado arriba, se debe minimizar el recorrido en paralelo de las rutas, en tal caso, el recorrido no podr
superar los 150 cm de longitud.
Fuentes:
PIP PCCEL001
IEEE 518

BANDEJAS

NIVEL B:

ellas.

ner las distancias de

barrera metlica aterrada entre

ores a 100kVA a 150 cm de las


tal caso, el recorrido no podr

BANDEJAS PORTACABLES
Caso

de Estudio

Lista de Cables
Tipo de Bandeja:

CABLES MONOPOLARES

Material:
Carga de Trabajo:
Espacio entre soportes:

Lbs/ft.
ft.

Cables

1000kCMIL o mayores

Cables

250kCMIL a 1000kCMIL

Cables

Mayores a 1000kCMIL con menores a 1000 kCMIL

Con

Clase NEMA: 8C
Calculado:

22.30 cm

Ancho Seleccionado:

22.5 cm

Bandeja de ancho menor a la requerida

algun cable instalado entre 1/0 y 4/0

CABLES MULTICONDUCTORES
Calibres

4/0 o Mayores

Calibres

menores a 4/0

Cables

4/0 o mayores con cables menores a 4/0

Cables

control / alumbrado / se alizacion

2
Tipo de bandeja
Escalera
Perforado ranurado

ancho de bandejas
15
22.5
30
45
60
75
90

3
1
Carga de TrabajoDistancia entre soportes
50
8
75
12
100
16
20

2
Material
Altura
Aluminio
Acero Inoxidab
Acero Galvani
Fibra de Vidrio

Seleccin
2
3
4
5
6

Bandejas
###
22.30
33.75
11.09
68.60
24.15
49.81
9.70

Lista de Cables

Seleccin

Bandejas

CABLE MONOPOLAR
Bandejas de fondo escalera o ventilado

Cables 1000 kCMIL o mayores


Diam. (mm)

Area (mm2)

Area Total
(mm2)

25.40

506.71

2533.54

10

28.40

633.47

6334.71

10

31.11

760.13

7601.34

36

33.60

886.68

31920.59

36

35.92

1013.36

36480.86

Cantidad

Tipo de Conductor

Calibre

Ancho de conductores

392-10(a) (1) NEC 2008

20%

Fuente: lugsdirect.com

Reserva:

Ancho total de Bandeja (cm)

Cables 250kCMIL a 1000kCMIL


Diam. (mm)

Area (mm2)

Area Total
(mm2)

13.51

143.35

716.75

13.51

143.35

1146.81

19.42

296.20

1481.01

14.66

168.79

337.59

19.42

296.20

1481.01

Cantidad

392-10(a) (2) NEC 2008


Fuente: Aralven

Tipo de Conductor

Calibre

Ancho Minimo (cm)


20%

Reserva:

Ancho total de Bandeja (cm)

Cables mayores a 1000kCMIL con menores a 1000kCMIL


Cables Mayores o iguales a 1000kCMIL
Diam. (mm)

Area (mm2)

Area Total
(mm2)

25.40

506.71

3040.24

31.11

760.13

760.13

Diam. (mm)

Area (mm2)

Area Total
(mm2)

25.52

511.51

2557.53

4.47

15.69

31.39

8.93

62.63

125.26

Cantidad

Tipo de Conductor

Calibre

Cables menores a 1000kCMIL


Cantidad

Tipo de Conductor

Calibre

5
2

Ancho Minimo (cm)

392-10(a) (3) NEC 2008

20%

Fuente: Aralven

Reserva:

Ancho total de Bandeja (cm)

Con algun cable instalado entre 1/0 y 4/0


Diam. (mm)

Area (mm2)

Area Total
(mm2)

18.48

268.22

1341.11

13.51

143.35

0.00

17.46

239.43

0.00

17.46

239.43

0.00

17.46

239.43

0.00

Cantidad

392-10(a) (4) NEC 2008


Fuente: Aralven

Tipo de Conductor

Calibre

Ancho de conductores
20%

Reserva:

Ancho total de Bandeja (cm)

Ancho
Requerido (cm)

12.7
28.4
31.11
120.96
129.312
322.48
64.50

386.98

Ancho
Requerido (cm)

2.58
4.13
5.33
1.22
5.33
18.59
3.72

22.30

CMIL
Ancho
Requerido (cm)

15.24
3.11

Ancho
Requerido (cm)

9.21
0.11
0.45
28.12
5.62

33.75

Ancho
Requerido (cm)

9.24
0
0
0
0
9.24
1.85

11.09

CABLE MULTICONDUCTOR
Bandejas de fondo escalera o ventilado

CALIBRES 4/0 O MAYORES


Cantidad

Tipo de Conductor

Calibre

Diam. (mm)

34.88

25.52

54.86

55.90

76.90

NEC 2008 392.9 (a) (1)


Los cables deben ser instalados en una sola capa

Ancho total de Band

Fuente: Manual de gedisa

CABLES MENORES A 4/0


Cantidad

10

Tipo de Conductor

Calibre

Diam. (mm)

13.51

10

15.96

18.90

10

36.30

10

36.30

NEC 2008 392.9 (a) (2)


Fuente: Manual de gedisa

Ancho total de Band

CABLES 4/0 O MAYORES CON CABLES MENORES


Cables Mayores a 4/0
Cantidad

Tipo de Conductor

Calibre

Diam. (mm)

34.88

76.90
Cables menores a 4/0

13.51

13.51

30.40

30.40

NEC 2008 392.9 (a) (3)


Todos los cables mayores a 4/0 se deben instalar en una sola capa

Ancho total de Band

Fuente: Manual de gedisa

CABLES CONTROL / ALUMBRADO / SEALIZACION


N Conductores
3

Tipo de Aislante

Calibre

Diam.

(mm)

11.10
23.20

16.30

16.30

14.40

NEC 2008 392.9 (b)


Se considera la altura de la bandeja como 10cm
Fuente: Manual de gedisa

Ancho total de Band

UCTOR

do

ES
Area (mm2)

Area Total (mm2)

Ancho
Requerido (cm)

955.53

1911.05

6.98

511.51

2557.53

12.76

2364.09

7092.28

16.46

2454.22

2454.22

5.59

4644.54

9289.08

15.38

Ancho de conductores
20%

57.17

Reserva:

11.43

Ancho total de Bandeja (cm)

68.60

0
Area (mm2)

Area Total (mm2)

Ancho
Requerido (cm)

143.35

1433.51

4.73

200.06

1000.29

3.30

280.55

561.10

1.85

1034.91

3104.73

10.25

1034.91

0.00

0.00

Ancho Minimo (cm)


20%

Reserva:

Ancho total de Bandeja (cm)

20.13
4.03

24.15

ES MENORES
Area (mm2)

Area Total (mm2)

Ancho
Requerido (cm)

955.53

5733.16

20.93

4644.54

4644.54

7.69

143.35

286.70

0.95

143.35

716.75

2.37

725.83

1451.67

4.79

725.83

1451.67

4.79

Ancho Minimo (cm)


20%

Reserva:

Ancho total de Bandeja (cm)

41.51
8.30

49.81

EALIZACION
Area
(mm2)

Area Total
(mm2)

Ancho
Requerido (cm)

96.77

2419.22

6.05

422.73

0.00

0.00

208.67

0.00

0.00

208.67

0.00

0.00

162.86

814.30

2.04

Ancho de conductores
20%

8.08

Reserva:

1.62

Ancho total de Bandeja (cm)

9.70

Canalizacion
Tamao

4"
Tuberia No Metalica Electrica
0 mm

Diametro
Area total

0.00 mm2

Area 31%
Area 40%
Area 53%

0.00 mm2
0.00 mm2
0.00 mm2

Tamao

Tuberia Metalica
Electrica

Tuberia No
Metalica Electrica

Tubo Metalico
Flexible

Tubo Metalico
Intermedio IMC

3/8
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6

0
15.8
20.9
26.6
35
40.9
52.5
69.4
85.2
97.4
110
0
0

0
14.2
19.3
25.4
34
39.8
51.3
0
0
0
0
0
0

9.7
16.1
20.9
25.9
32.4
39
51.8
63.5
76.2
88.9
101.6
0
0

0
16.8
21.9
28.1
36.8
42.7
54.6
64.9
80.7
93.2
105.8
0
0

Tubo No Flexible
hermetico a los
liquidos (Tipo
FNMC-B)

Tubo No Flexible
hermetico a los
liquidos (Tipo
FNMCA-A*)

Tubo No Flexible
hermetico a los
liquidos

Tubo Metalico
Rigido

Tubo de PVC
Rigido, Sch. 80

12.5
16
21.1
26.8
35.4
40.3
51.6
0
0
0
0
0
0

12.6
16
21
26.5
35.1
40.7
52.4
0
0
0
0
0
0

12.5
16
21.1
26.8
35.4
40.3
51.6
63.3
78.3
89.4
102.1
0
0

0
16
21.2
27
35.4
41.2
52.9
63.2
78.5
90.7
102.9
128.8
154.8

0
13.4
18.3
23.8
31.9
37.5
48.6
58.2
72.7
84.5
96.2
121.1
145

Tubo de PVC
Tubo de PVC, Tipo Tubo de PVC, Tipo
Rigido, Sch. 40 y
A
EB
tubo de PE-AD
0
15.2
20.4
26.1
34.5
40.4
52
62.1
77.3
89.4
101.5
127.4
153.2

0
17.8
23.1
29.8
38.1
43.7
54.7
66.9
82
93.7
106.6
0
0

0
0
0
0
0
0
56.4
0
84.8
96.6
108.9
135
160.9

CALIBRE
14

THW
Calibre
18
16
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

AISLANTE Cant Cables


THW
1

Diametro
Area

4.14 mm
13.49 mm2

Area Total

13.49 mm2

CEN 1999 Tabla 5


TW
THHN
Diametro Seccion mm2 Diametro Seccion mm2 Diametro
0
0.00
0
0.00
13.49
3.38
8.99
2.82
4.14
16.80
3.86
11.73
3.3
4.62
21.53
4.47
15.73
5.23
4.16
35.98
5.99
28.25
6.76
5.48
46.92
7.72
6.45
62.92
8.94
8.23
73.32
9.65
8.94
86.14
10.46
9.75
123.02
12.5
11.33
143.70
13.51
12.34
169.67
14.68
13.51
201.55
16
14.83
240.28
17.47
16.3
297.23
19.43
18.06
341.60
20.83
19.45
385.22
22.12
20.75
427.78
23.31
21.94
510.74
25.47
24.1
629.20
28.27
26.69
711.88
30.07
28.5
753.18
30.93
29.36
793.65
31.75
30.17
876.70
33.37
31.8
956.19
34.85
33.27
1203.02
39.09
1402.72
42.21
1602.09
45.11
1798.85
47.8

Resistencia y reactancia de conductores


Calibre:
Mat. de la tuberia:
Distancia:

Resistencia
Reactancia

Conductore por fase

Acero
20 M

0.660 Ohm/kM
0.187 Ohm/kM

R: 0.013
X: 0.004

CALIBRE
8
Cap. Nominal
Factor Correc.

TEMP.
75C

MATERIAL
COBRE

COR. Temp.
36-40

50 A
0.88

Capacidad

44 A

Tabla 310.16 CEN 1999


Ampacidades admisibles de los conductores aislados para tensiones nominales de 0 a 2000 V
y 60c a 90c con no mas de tres conductores portadores de corriente en una canalizacin,
cable o directamente enterrados, basadas en una temperatura ambiente de 30c
Calibre

COBRE
75C

60C

AWG/kcmil

18
16
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

TW*, UF*

0
0
20
25
30
40
55
70
85
95
110
125
145
165
195
215
240
260
280
320
355
385
400
410
435
455
495
520
545
560

90C

TBS, SA,
SIS, FEP*,
FEPB*, MI,
RHH*,
FEPW*,
RHW-2,
RH*, RHW*,
THHN*,
THHW*,
THHW*,
THW*,
THW-2*,
THWN*,
THWN-2*,
XHHW*,
USE-2,
USE*, ZW*
XHH,
XHHW*,
XHHW-2,
ZW-2
0
0
20
25
35
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
420
460
475
490
520
545
590
625
650
665

ALUMINIO
75C

60C

14
18
25
30
40
55
75
95
110
130
150
170
195
225
260
290
320
350
380
430
475
520
535
555
585
615
665
705
735
750

90C

TBS, SA,
SIS, THHN*,
THHW*,
RH*, RHW*, THW-2,
THHW*,
THWN-2,
THW*,
RHH*,
THWN*,
RHW-2,
XHHW*,
USE-2,
USE*
XHH,
XHHW,
XHHW-2,
ZW-2

TW*, UF*

0
0
0
0
25
30
40
55
65
75
85
100
115
130
150
170
190
210
225
260
285
310
320
330
355
375
405
435
455
470

0
0
0
20
30
40
50
65
75
90
100
120
135
155
180
205
230
250
270
310
340
375
385
395
425
445
485
520
545
560

0
0
0
25
35
45
60
75
85
100
115
135
150
175
205
230
255
280
305
350
385
420
435
450
480
500
545
585
615
630

TEMP AMB.
21-25
26-30
31-35
36-40
41-45
46-50
51-55
56-60
61-70
71-80

1.08
1
0.91
0.82
0.71
0.58
0.41

1.05
1
0.94
0.88
0.82
0.75
0.67
0.58
0.33

1.04
1
0.96
0.91
0.87
0.82
0.76
0.71
0.58
0.41

1.08
1
0.91
0.82
0.71
0.58
0.41

1.05
1
0.94
0.88
0.82
0.75
0.67
0.58
0.33

1.04
1
0.96
0.91
0.87
0.82
0.76
0.71
0.58
0.41

CALIBRE
2
Cap. Nominal

TEMP.
90C

Tension
2001-5000 V

130 A

Capacidad

130 A

Tabla 310.73 CEN 1999


Ampacidades de cables triples aislados o de tres conductores de
cobre sencillos, en un conducto fsicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90C en una temperatura
ambiente de 40C
Calibre
AWG/kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

2001-5000 V
90C
105C
55
61
75
84
97
110
130
145
155
175
180
200
205
225
240
270
280
305
315
355
385
430
475
530
600
665
690
770

5001-35000 V
90C
105C
83
110
150
170
195
225
260
295
330
395
480
585
675

93
120
165
190
215
255
290
330
365
440
535
655
755

CALIBRE
4/0
Cap. Nominal

TEMP.
90C

Tension
5001-35000 V

230 A

Capacidad

230 A

Tabla 310.74 CEN 1999


Ampacidades de cables triples aislados o de tres conductores de
aluminio sencillos, en un conducto fsicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90C en una temperatura
ambiente de 40C
Calibre
AWG/kcmil
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

2001-5000 V
90C
105C
43
48
58
65
76
85
100
115
120
135
140
155
160
175
190
210
215
240
250
280
305
340
380
425
490
545
580
645

5001-35000 V
90C
105C
65
84
115
130
150
175
200
230
255
310
385
485
565

72
94
130
150
170
200
225
260
290
350
430
540
640

A
AAC
AACS
AC
ACSR
ACSR-AG AL
ACSR-AW
AF
Al
Alta frecuencia
AM
Amplitud
Ancho de banda
Apertura
numrica
Armadura

Atenuacin
ATM
AW
AWG
AWM
Baja Frecuencia
Bel
BIL
Bit
Blindaje
C
c.a.

c.c.
c.d.
Capacitador

Capacitancia

Capacitancia
mutua
Capacitor
CATV
CCS
CCTV
Circuito en serie
Circuito paralelo
CL2
CL3
CM
Conductividad
Constante
dielctrica
CP
CPE
CSA
Cu
CuSn
CV
CW
CXC
DCS
DGN
Diafona
Dielctrico
Dispersin

Dispersin
cromtica
Dispersin
modal
DIT
DRS

DS
Efecto piel
EIA/TIA
Electromagntic
o
EP(R)
EPDM
f
FA
Fan-out
Fase
FCC
FDDI
FEP
FM
FOA
FOW
FTP
G
G-GC

Glosario de trminos relacionados con conductores elctricos y cables para telecomunicacione


H
HDPE
Higroscpico
Hilo dren
HMWP
HP
HPN
HPOF
Hz
I
I2R
IACS

ICEA
IEC
IEEE
Iexc
Impedancia
Indice de
refraccin
Inductancia
ISO
ITU
Jumper
kCM
kV
l
LAN
LDPE
Lnea
balanceada
Lnea de
transmisin
Longitud de
onda de Malla
lpi Longitudinal
lpof
m.s.n.m
Malla
Mc
Mi
MIC
mp
mp-gc
MTW
Multimodo
Multiplexar
MV

mw
NEC
Neopreno
NFPA
NM
NM-B o NMC-B
NMC
NMX
NOM
Non break out
NZ
OA
Ohm
OTDR
OW
Pantalla
PCC
PCG
PCM
PE
Prdidas por
doblez
PFA
PFAH
PG
Pig-tail
PILC
Plstico
Plastificante
Plenum
PMD
Polietileno
celular

Polilam

Polmero
POT
psi
PVC
PVDF
RDI
REA (RUS)
Reactancia
Resistencia a la
abrasin
RG/U
RH/RW
RHH
RHW
RHW-2
SA
SBR
SDH
SE
SF
SFF
SH
SHD
SHD-GC SHD.
SIC

SIS
SJ
SJO

SJT SJ
SMT
SNM

SO
SONET
SPT
ST
STP
SU
SV
SVT
SVTO
TA
TAGA
TAGT
TC

TEFLON*
TF
TFE
TFF
TFFN
TFN
THHN
THHW
THW1
THW-21
THWN
TP

TPT TP
TTU

TW
UD
UF
UHF
UL
Unimodo
URD
USE
USG
UTP
V
VA
Velocidad de la
luz
Velocidad de
propagacin
VHF
Volt
VW-1
W
WDM
XHHW
XHHW-2
XLP
XT

Ampere: Unidad utilizada para denominar la intensidad de corriente elctrica.


All Aluminum Conductor: conductor o cable de hilos de aluminio.
Aluminum Alloy Standed Conductor: cable de aleacin de aluminio.
Armored Cable: cables provistos de una armadura metlica flexible.
Aluminum Conductor Steel Reinforced: conductor de aluminio con centro de acero galvanizado.
ACSR con aleacin de aluminio para alta temperatura (150C) y acero de alta resistencia. Smbolo de
ACSR con centro de acero recubierto con aluminio (Alumo-Weld). Tambin conocido como ACSR-AS.
Audio Frecuencia: Rango de frecuencias que caen dentro del rango perceptible del odo humano: apro
a 20, 000 Hz
Smbolo del aluminio.
La banda de 3 MHz a 1 GHz.
Amplitud Modulada.
El valor mximo de variacin de una onda.
Es la diferencia entre los valores superior e inferior de una banda de frecuencias dada. Se expresa en
Es la medida de aceptacin angular de una fibra ptica, que es aproximadamente el seno de la mitad
cono de aceptacin de la fibra.
Cinta corrugada de acero que tiene la funcin de proteger el cable contra maltrato mecnico y ataque
aplicaciones especiales se llegan a usar armaduras de cinta engargolada o de alambres de acero.

Es el decremento en magnitud de una onda mientras esta viaja en medio transmisor, sea un cable o u
atenuacin se mide como una razn o como logartimo de la razn (decibel).
Siglas en ingls para la tcnica de codificacin y conmutacin en bloques llamada Asynchronous Tran
permite multiplexar seales de velocidades distintas en un mismo canal digital.
American Wire Gauge: escala de calibres americanos para alambres y cables, tambin conocida com
and Sharpe) Wire Gauge.
American Wire Gauge: Escala de calibres americanos para alambres y cables, tambin conocida com
and Sharpe) Wire Gauge.
Appliance Wiring Material: Conductores destinados al alambrado interno de aparatos electrodomstico
La banda de 30-300 KHz.

Es una unidad que representa el logaritmo de la razn de dos niveles.


Basic Impulse Insulation Level: nivel bsico de aislamiento al impulso.
Es un dgito binario.
Capa conductiva en un cable que tiene la funcin de reducir la interferencia electomagntica. Puede s
alambres, una cinta metlica o una cinta plstica metalizada.
Smbolo de capacitancia y grados centgrados.
Corriente alterna: Es una corriente que perodicamente revierte la direccin del flujo de electrones. La
un ciclo completo ocurre por unidad de tiempo (normalmente un segundo) se le denomina frecuencia

Corriente continua (ver c.d.)


Corriente directa: Es la corriente elctrica donde los electrones fluyen en una sola direccin.
Dos superficies conductoras separadas por un material dielctrico. La capacitacin es determinada po
superficies, tipo de dielctrico y el espaciamiento entre los conductores.

Es la propiedad que tiene un material dielctrico situado en medio de dos conductores de almacenar e
cuando existe una diferencia de potencial entre los conductores. La unidad de medida es el Farad, qu
capacitancia que almacenar una carga de un Cuolomb cuando exista una diferencia de potencial de
conductores.

Es la capacitancia que existe entre dos concluctores cuando los dems conductores estn conectados

Dos superficies conductoras separadas por un material dielctrico. La capacitancia es determinada po


superficies, tipo de dielctrico y el espaciamiento entre los conductores.
Community Antena TeleVision: trmino empleado para los cables coaxiales destinados a los sistemas
comunitaria.
Siglas en lngls para conductores de acero cubierto cle cobre (Copper Cladded Steel).
Circuito Cerrado cle TeleVisin.
Es un circuito cuyos componentes distribuidos a lo largo de camino comn.

Es un circuito en el cual un mismo voltaje se presenta en todos los componentes, con corriente dividid
acuerdo a su resistencia o impedancias.
Cables para circuitos Clase 2, segn NEC-725, bajo voltaje y potencia.
Idem a CL2, para 300 volts mximo, bajo potencia.
Circular Mil: rea de un circuito con un dimetro de 1/1000 de pulgada.
La capacidad de un material para permitir el flujo de electrones, medido por la corriente por unidad de
Es el recproco de la resistividad.
Tambin se llama permitividad. Es aquella propiedad del dielctrico que determina la cantidad de ener
que puede almacenarse cuando es aplicado un voltaje.
Caballos de Potencia: tambin conocido como HP.
Chlorinated PolyEthylene: polietileno clorado.
Canadian Standard Association: Institucin canadiense para la certificacin de equipo elctrico y elect
las normas que ellos mismos publican.
Smbolo del cobre.
Smbolo que denota cobre estaado.
Continuous Vulcanization: proceso de vulcanizacin en lnea con la extrusin.
CopperWeld: varilla de acero, con recubrimiento de cobre.
Designacin de cable coaxial por CSA (Canadian Standars Association).
Cables para Distribucin Comercial Subterrnea.
Direccin General de Normas de la Secretara de Comercio y Fomento Industrial.
Transferencia no deseada de seal entre distintos canales de un equipo a cable.
Es un medio aislante (no-conductivo).
Fenmeno por el cual componentes de la luz transmitida por la fibra sufren retrasos distintos. Es la su
efectos, principalmente dispersin modal y dispersin cromtica. Puede limitar la velocidad de transm

Es el retraso diferente que sufren las distintas longitudes de onda que componen a luz portadora, por
velocidades distintas en la fibra. En fibras con diseo estndar la dispersin cromtica tiene un valor m
la ventana de 1310 nm.
Es el retraso diferente que presentan los modos de propagacin en una fibra multimodo por viajar en
no existe en las fibras unimodo en las que se transmite un modo de propagacin.
Dispositivo de Interconexin Terminal: es el lmite entre la red pblica y la que es responsabilidad del u
Cables para Distribucin Residencial Subterrnea (tipo URD).

Siglas en ingls para dispersin corrida, son las fibras unimodo con dispersin mnima enla ventana d

Es la tendencia que tiene la corriente alterna de viajar en el permetro del conductor con el incremento

Asociacin de las industrias electrnica y de comunicaciones en EUA.


Se reflere a la combinacin de campos elctricos y magnticos originado por el movimiento de los ele
conductor.
Fluorinated Ethylene Propylene: aislamiento de etileno-propileno fluorado.Ethylene Propylene (Rubber
base de etileno-propileno.
Ethylene Propylene Dionomer: etileno-propileno dieno monmero.
Frecuencia: El nmero de veces que una accin peridica ocurre en un lapso de tiempo: Es el nmero
que una corriente elctrica completa 1 seg.
Forced Air: enfriamiento con aire forzado.
Cable ptlco para conectorizar, que permite separar las fibras individuales sin necesidad de darles pro
adicional.
Es la relacin angular entre ondas.
Flexible Control Cable: cable control, flexible.
Fiber Distribution Digital Interface: especificacin para la red de datos 100% ptica a 100 Mb/s.
Nombre abreviado para tetrafluoruroetileno-exafluoruropropileno, material aislante con excelentes pro
elctricas y qumicas que se usan en cables categora plenum.
Frecuencia modulada.
Forced Oil and Air: enfriamiento con aceite forzado y aire.
Forced Oil and Water: enfriamiento con aceite forzado y agua.
Foiled Twisted Pair: cables multipares para datos blindados por medio de una cinta plstica aluminizad

Ground: cable flexible para minas con conductores para conexin a tierra, 600 2000 volts.
Ground-Ground Check: cable flexible para minas, con conductores para conexin a tierra y un conduc
verificar la continuidad de los conductores de tierra, 600 2000 volts.
rio de trminos relacionados con conductores elctricos y cables para telecomunicaciones
Henry: Es la unidad prctica de inductancia que producir un incremento de voltaje de 1 Volt cuando la
cambie a razn de un ampere/seg.
High Density PolyEthylene (PE): polietileno de alto densidad.
Propiedad de algunos materiales de absorber agua del ambiente. Las cintas e hilos usados en cables
hacerlo.
Es un alambre desnudo que est en contacto con el blindaje del cable a lo largo de toda su longitud.
High Molecular Weight Polyethylene: polietileno de alto peso molecualr.
Horse Power: caballo de potencia.
Heater Cord Parallel Neoprene: cordn paralelo de dos conductores flexibles con aislamiento elastom
aparatos electrodomsticos resistentes al calor, 90 C, 600 volts.
High Pressure Oil Filled: cables tipo Pipe (tubo) de alta tensin con aislamiento de papel impregnado i
de un tubo de acero con aceite a alta presin.
Hertz: Es la unidad de medida de frecuencia: 1 ciclo por segundo.
Smbolo utilizado para designar corriente.
Frmula de potencia en Watts, donde I=corriente en amperes, R=resistencia en Ohms.
International Annealed Copper Standard: patrn internacional para la conductividad del cobre (igual al
cobre electroltico recocido).

Insulated Cable Engineers Association: nombre actual de IPCEA (Power), asociacin norteamericana
normalizacin de conductores elctricos.
International Electrotechnical Commission: organizacin internacional encargada de la normalizacin
elctricos.
Institute of Electrical and Electronic Engineers: principal asociacin a nivel mundial de ingenieros en e
electrnica y materias afines.
Corriente de excitacin.
Es la oposicin total de un circuito, cable, o algn componente al paso de la corriente alterna. Esta inc
resistencia y a la reactancia. La unidad de medida es el Ohm y su smbolo es la Z.
Es un promedio del ndice de refraccin para las longitudes de onda en la ventana de transmisin; es
necesario que se debe conocer para medir la distancia de un enlace en un OTDR.
Es la propiedad de un conductor o un circuito que se resiste al cambio de corriente. Su unidad de med
su smbolo es L.
International Standards Organization: organizacin internacional de normalizacin.
International Telecomunication Union: organizacin para normalizacin internacional en
Cable para conexiones en un distribuidor, puede ser un par de cobre o una fibra Monotel con conector
kiloCircularMil:unidad de rea del sistema norteamericano de calibres de conductores elctricos, igual
mils (CM). Anteriormente conocida como MCM.
kiloVolt: unidad de medida de tensin elctrica igual a 1000 volts.
Smbolo utilizado para designar corriente.
Local Area Network: red de datos de corta longitud en un edificio o conjunto de edificios.
Low Density PolyEthylene (PE): polietileno de bajo densidad,
Es un cable que tiene 2 conductores idnticos con las mismas caractersticas electromagnticas en re
dems conductores y tierra.
Es el arreglo de dos o ms conductores o una gua de onda que se utiliza para transferir seales de u
Es la distancia entre picos o nodos sucesivos de una onda.

Paper Insulated: proceso para la fabricacin de cables telefnicos con aislamiento de papel aplicado
longitudinalmente.
Low Pressure Oil Filled: cables con aislamiento de papel impregnado tipo Autocontenidos para alta ten
. Metros sobre el nivel del mar.
Es un grupo de filamentos metlicos entretejidos para formar una esfructura tubular la
Metal Clad: cable armado con una cubierta metlica del tipo interlock o tubo corrugado.
Mineral Insulated: cable con aislamiento mineral de xido de magnesio y cubierta de tubo de cobre o a
temperatura y resistencia al fuego, 90 a 250 C.
Tcnica de modulacin en que la amplitud de una seal analgica en cierto momento se expresa con
binario de 8 cifras.
Mine Power Feeder Cable: cable alimentador para minas con tres conductores de fase y tres conducto
conexin a tierra.
MP-Ground Check: MP con un conductor aislado para verificar la continuidad de los conductores de ti
Machine Tool Wire: conductor con aislamiento termoplstico para alambrado de mquinas herramient
Fibras que tienen un ncleo relativamente grande (50 micras o ms), que permiten transmitir varios ha
llamados modos de propagacin.
Combinacin de varias seales para enviarlas por un solo canal de transmisin.
Medium Voltage Cable: cables cona aislamiento slido para tensiones de 2001 a 35,000 volts.

Micro m Wave: microonda.


Natinal Electrical Code: Norma general sobre productos e instalaciones
Policloropreno, hule sinttico empleado como aislamiento y cubierta de cables flexibles.
National Fire Protection Association: asociacin americana para la proteccin contra incendios respon
publicacin del NEC.
Non-Metallic Sheathed Cable: conductores aislados y con cubierta no metlica resistente a la humeda
la flama; sugerido para ambientes secos.
NM o NMC con aislamiento de THHN.

NM con cubierta elastomrica resistente a la corrosin; para ambientes secos o hmedos.


Norma Mexicana; documentos publicados por organismos privados autorizados. Son de uso voluntario
Norma Oficial Mexicana: documentos publicados por la DGN para la normalizacin y especificacin de

Cable ptico para distribucin en edificios en el que las fibras no tienen proteccin individual para sep

Fibras pticas de baja dispersin cromtica, pero nunca igual a una de 1530 a 1560 mm, permite tran
portadores (ver WDM).
Oil and Air: enfriamiento natural aire-aceite.
Es la unidad elctrica de resistencia. Es el valor de resistencia a travs del cual una diferencia de pote
mantendr una corriente de un ampere.
Reflectmetro ptico en dominio de tiempo, es un equipo que inyecta un pulso de luz a la fibra y detec
reflexiones, permite medir atenuacin y longitud de un enlace.
Oil and Water: enfriamiento con aceite-agua.
Vea blindaje.
Designacin de CSA para los cables de uso interior (Premises Comunication Cable).
Portable Cable Control and Ground conductors: cable flexible para minas con conductores de control y
tierra, 600 2000 volts.
Siglas en ingls para la tcnica de modulacin llamada en espaol MIC (Modulacin por Impulsos Cod
Polietileno, puede ser de los tipos HMWP,HDPE y LDPE.
Es la forma que toma la curva de atenuacin que es causada por: a)Una fibra ptica curveada alreded
curvatura cerrado, o b) Microdobleces causados por esfuerzo mecnico de la fibra.
PerFluoro-Alkoxy: cables para alta temperatura; ambiente seco, con aislamiento de Perfluoro-Alkoxy, h

PerFluoro-Alkoxy Heat: PFA con temperaturas mayores de hasta 250 C.


Portable Cable Ground Conductor: cable flexible para minas con conductores de fase y para conexin
2000 volts.
Fibra ptica Monotel con conector en una punta.
Papel Insulated Lead Cover: cable para media tensin aislado con papel impregnado y con cubierta d
Sustancia polimricas que incluyen tanto materiales naturales como sintticos.
Es un qumico que se agrega al plstico pare hacerlo ms suave y flexible.
Cables que cumplen con las normas de seguridad parta poder instalarse sin tubo conduit sobre el fals
Siglas en ingls para el fenmeno de dispersin por polarizacin de modos, en el que existe una difer
velocidad entre los componentes de campo elctrico y magntico de un mismo modo de propagacin.
Tcnica de introducir burbujas en el plstico del aislamiento pare bajar la capacitancia del cable.

Cinta de aluminio de acero con espesor entre 0. 15 y 0.2 mm que tiene un recubrimiento plstico en
caras, lo que permite que se adhiera a la cubierta de polietileno de un cable formando una barrera con

Es una substancia hecha de muchas unidades qumicas moleculares. El trmino polmero es regularm
vez de plstico, hule o elastmero.
Cordn paralelo con aislamiento termoplstico para 300 volts, 60 C.
pounds per square inch: libras por pulgada cuadrada.
PolyVinyl Chloride: cloruro cle poli-vinilo, compuesto ampliamente usado como aislamiento y cubierta.
PolyVinyliDene Fluoride: compuesto termoplstico a base de fluor usado generalmente como cubierta
construccin.
Red Digital Integrada; servicio de alta velocidad para grandes usuarios a travs de la red pblica.
Rural Electrification Administracion: oficina norteamericana del Departamento de Agricultura encargad
normalizacin de equipos ofrecidos por las compaas telefnicas independientes.
Es una medida de los efectos combinados de capacitancia e inductancia en corriente alterna. Es la va
oposicin tiene con la frecuencia de la corriente. Su smbolo es X.
Capacidad de resistir desgaste superficial.

Radio Frecuency Guide, Universal: designacin para cables coaxiales para radiofrecuencias.
Rubber Heat, Rubber Moisture (Water): cables con aislamiento y cubierta de hules sintticos para 75
seco y 60 C en hmedo, 600 volts.
Rubber High Heat: cables con aislamiento y cubierta de hule sinttico, para 90 C, 600 V.
Rubber Heat Moisture (Water): cables con aislamiento y cubierta de hules sintticos para75 C en amb
hmedo.
Igual a RHW pero con aislamiento de 90 C en ambiente seco y hmedo.
Silicone Asbestos: cables aislados con hule silicn y malla de asbesto o fibra de vidrio.
Styrene Butadiene Rubber: elastmero sinttico a base de Estireno y Butadieno, empleado para aislam
de cordones flexibles, se conoca como GRS (Government Rubber Standard).
Siglas en ingls pare el sistema de transmisin ptica sincrono (Synchronous Digital Hierarchy).
Service Entrance: uno o ms conductores con o sin cubierta exterior usados para alimentacin de ser
Silicone Rubber Fiber Glass: alambre o cable de 7 hilos aislados con hule silicn y malla de fibra de vi
Silicone Rubber Fiber Glass Flexible: SF con conductor ms flexible, 150 C.
Shielded Mining Cable Single Conductor: cable monopolar flexible para minas con pantalla y cubierta

Shielded mining Cable with Ground Conductors: cable trifsico flexible para minas con pantalla. "D" si
conductor de fase lleva pantalla y que el cable tres conductores para conexin a tierra.
Ground Check: SHD con un conductor aislado para el circuito de comprobacin de continuidad de con
dos conductores de tierra.
Specific Inductive Capacity: inductancia capacitiva especfica, constante dielctrica de un material que
que existe entre un condensador con el material como dielctrico y el mismo condensador con aire co
Synthetic Insulated Switchboard Cable: cable para tableros con aislamiento elastomrico sinttico, 90

Hard Service Cord Junior: cordn uso rudo para servicio ligero con aislamiento elastomrico, 300 volts
SJ Oil Resistant: SJ con aislamiento resistente al aceite.

Thermoplastic: SJ con aislamiento y cubierta termoplstica, 60 C, 300 volts (90 y105 C con aislamie

Construccin igual al SPT pero con conductores clase M.


Shielded Non-Metallic-Sheathed Cable: dos o ms conductores aislados con un ncleo de material res
humedad y retardante de la llama; sobre el conjunto lleva una pantalla a base de hilos y cintas; cubier
material no metlico resis
Service Cord Oil Resistant: cordn uso rudo para servicio pesado; aislamiento y cubierta elastomrica
resistente al aceite, hasta 90 C, 600 volts.
Siglas en ingls para el sistema de transmisin ptica sincrono de EUA (Synchronous Optical NETwor
Service Parallel Thermoplastic: cordn paralelo con aislamiento de PVC para servicio ligero, 60 C, 30
C con aislamiento de PVC).
Hard Service Cord Thermoplastic: cable o cordn uso rudo para servicio pesado con aislamiento y cub
termoplstica, 60 a 105 C, 600 volts.
Shielded Twisted Pair: cables multipares para datos, blindados con una cinta plstica aluminizada y un
de cobre estaado.
Trmino empleado para denominar la tubera de PVC Subterrnea.
Service Cord Vacuum Cleaner: cordn tipo uso rudo flexible para conexin de aspiradoras con aislam
elastomrica, 60 C, 300 volts.SV con cubierta de neopreno.
SV con aislamiento y cubierta Termoplstica, 60 a 90 C, 300 volts.
SVT Oil Resistant: SVT con cubierta resistente al aceite, 60 C.
Thermoplastic Asbestos: cable para alambrado de tableros con aislamiento termoplstico; carda de as
de algodn retardante a la llama, 90 C, 600 volts (En desuso).
Tefln*-Asbestos-G lass-Asbestos: conductor con aislamiento de Tefln trenza de asbesto, trenza de f
malla de eabesto para circuitos de fuerza y control, 250 C, 600 volts.
TAGA sustituyendo la cubierta final de asbesto por una cinta de Tefln*.
Power and Control Tray Cable: dos o ms conductores aislados con o sin conductor de tierra y con un
exterior de material no metlico, y aprobado para usarse en instalaciones en charolas, canalizaciones
un hilo mensajero.
Marca registrada de DuPont para el poli-tetraflouretileno, tambin denominado PTFE.
Thermoplastic Fixture: alambre o cable de 7 hilos para alambrado de aparatos elctricos , aislamiento
600 volts.
Cable para alta temperatura aislado con Tefln*, 250 C.
TF Flexible: TF pero con conductor flexible.
Thermoplastic Fixture Flexible Nylon: TFN con conductor flexible.
TF Nylon: TF con aislamiento de PVC y cubierta de nylon, 90 C, 600 volts.
Thermoplastic High Heat Nylon: alambre o cable con aislamiento de PVC y cubierta de nylon, 90 C en
600 volts.
Thermoplastic High Heat Moisture (Water) Resistant: cable aislado con PVC para 90 C en ambientes
en hmedos, 600 volts.
Thermoplastic Heat and Moisture (Water) Resistant: alambre o cable con aislamiento de PVC par a75
secos o hmedos, 600 volts.
THW para 90 C en ambientes secos y hmedos
THW con cubierta de nylon, resistente a la humedad, aceites e hidrocarburos, 75 C en ambientes hm
Tinsel Cord Parallel: dos conductores paralelos extraflexibles con aislamiento y cubierta elastomrica
en dispositivos de hasta 50 watts.

Thermoplastic: TP pero con aislamiento y cubierta termoplsticos, 125 volts.


Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground
Thermoplastic Building Wire Moisture (Water) Resistant: alambre o cable aislado con PVC resistente a
C, 600 volts.
Underground Distribution: cables para distribucin subterrnea, tambin conocidos como cables DS.
Underground Feeder: cable de uno o varios conductores con aislamiento y cubierta termoplstica para
subterrneas en baja tensin.
Ultra High Frequency: ultra alto frecuencia. Es la banda de 300 a 3000 MHz.
Underwrites Laboratories, Inc.: institucin (privada) dedicada al reconocimiento y aprobacin de produ
electrnicos, acorde a sus propias normas.
Fibras que tienen un ncleo pequeo que permite transmitir un solo haz luminoso llamado modo de pr

Underground Residential Distribution: cables de distribucin residencial subterrnea, tambin conocid

Underground Service Entrance: cable para acometidas subterrneas en baja tensin, aislamiento y cu
elastomricas.
United States Standard Gauge: escala para calibres de lmina de acero.
Unshielded Twisted Pair: cables multipares para datos, sin blindaje.
Volt: unidad utilizada para denominar tensin elctrica.
Volt Ampere: unidad de potencia aparente para transformadores.
2.998x108 m/seg.

La velocidad de transmisin de la energa elctrica en una longitud de cable comparado con la velocid
el aire. Se estima generalmente en porcentaje.
Very High Frecuency: extra alta frecuencia, 30 a 300 MHz.
Es la unidad de tensin elctrica: 1 Volt ser la tensin elctrica que causar que 1 ampere de corrien
de una resistencia de 1 Ohm.
Vertical Wire Flame Test: prueba de resistencia a la flama colocando el especimen en posicin vertica
Cables flexibles para minas: redondos o planos de uno o varios conductores con aislamiento y cubiert
para servicio extrapesado.
Siglas en ingls para la multiplexacin por divisin de longitud de onda. En estos sistemas se transmit
simultnea varias longitudes de onda independientes.
Cross (X)-Linked Polyethylene High Heat and Moisture (Water) Resistant: cable con aislamiento de po
cadena cruzada, 90 C ambiente seco y 75 C en ambiente hmedo, 600 volts.
XHHW para 90 C en ambientes secos y hmedos.
Cross (X)-Linked Polyethylene: polietileno de cadena cruzada, tambin conocida como polietileno vulc

Xmas Tree Cord: cordn paralelo, dos conductores aislados con PVC para series de rboles de navid

CLCULOS ELCTRICOS
Ing. FIDEL MORENO
fidelsmc@gmail.com
Maracaibo - Venezuela
2008
Version 3.7
Dedicado a Jessica