Air Conditioner        Edition:2006/1/10

CAUTION
READ THIS MANUAL CAREFULLY TO
DIAGNOSE TROUBLE CORRECTLY
BEFORE OFFERING SERVICE .

SERVICE MANUAL
Air Conditioners

THIS MANUAL IS USED BY


QUALIFIED APPLIANCE
TECHNICIANS ONLY. HAIER
DOES NOT ASSUME ANY
RESPONSIBILITY FOR PROPERTY
DAMAGE OR PERSONAL INJURY
FOR IMPROPER SERVICE
PROCEDURES DONE BY ONE
UNQUALIFIED PERSON.

MODEL: HSU-07HV03/R2
HSUHSU-09HV03/R2
HSU-12HV03/R2
HSU-18HV03/R2
HSU-22HV03/R2

REVISION 0

Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION

MODEL: HSU-07HV03/R2

Features
Comfortable: wide-angle airflow
health air purifying
quiet operation
super energy efficient

Main Specification
Cooling Capacity 2300W
Rated Power/Current(cooling) 680W/3.0A
EER: 3.38
Heating Capacity 2500W
Rated Power/Current(heating): 690W/3.1A
COP: 3.62
Air Volume(Indoor): 400m3/h
Power: 1PH 220-230V~ 50 Hz

Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION

MODEL: HSU-09HV03/R2

Features
Comfortable: wide-angle airflow
health air purifying
quiet operation
super energy efficient

Main Specification
Cooling Capacity 3000W
Rated Power/Current(cooling) 860W/3.5A
EER: 3.49
Heating Capacity 3000W
Rated Power/Current(heating): 830W/3.5A
COP: 3.61
Air Volume(Indoor): 420m3/h
Power: 1PH 220-230V~ 50 Hz

Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION

MODEL: HSU-12HV03/R2

Features
Comfortable: wide-angle airflow
health air purifying
quiet operation
super energy efficient

Main Specification
Cooling Capacity 4000W
Rated Power/Current(cooling) 1200W/5.0A
EER: 3.33
Heating Capacity 4200W
Rated Power/Current(heating): 1160W/5.8A
COP: 3.62
Air Volume(Indoor): 450m3/h
Power: 1PH 220-230V~ 50 Hz

Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION

MODEL: HSU-18HV03/R2

Features
Comfortable: wide-angle airflow
health air purifying
quiet operation
super energy efficient

Main Specification
Cooling Capacity 5000W
Rated Power/Current(cooling) 1555W/6.9A
EER: 3.22
Heating Capacity 5500W
Rated Power/Current(heating): 1525W/6.8A
COP: 3.61
Air Volume(Indoor): 750m3/h
Power: 1PH 220-230V~ 50 Hz

Air Conditioner        Edition:2006/1/10

IMPORTANT INFORMATION

MODEL: HSU-22HV03/R2

Features
Comfortable: wide-angle airflow
health air purifying
quiet operation
super energy efficient

Main Specification
Cooling Capacity 6000W
Rated Power/Current(cooling) 1990W/8.9A
EER: 3.02
Heating Capacity 6500W
Rated Power/Current(heating): 2020W/9.0A
COP: 3.22
Air Volume(Indoor): 750m3/h
Power: 1PH 220-230V~ 50 Hz

Air Conditioner        Edition:2006/1/10

Safety Information
General Information
This Service Manual describes the operation,disassembly,troubleshooting,and repair of Haier Room Air
Conditioners,etc. It is intended for use by authorized servicers who troubleshoot and repair these units.
NOTE:It is assumed that users of this manual are familiar with the use of tools and equipment used to
troubleshoot and repair electrical,mechanical,and refrigeration systems;and understand the terminology
used to describe and discuss them.
Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure
to comply with safety information may result in severe personal injury or death.

Related Publications
This is a base service manual,covering a range of similar models.It is intended to be used in
conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.

General Precautions and Warnings

WARNING
To avoid risk of personal injury or death due to electrical shock,disconnect electrical power to unit
before attempting to service the unit.

WARNING
To avoid risk of personal injury or death due to electrical shock,DO NOT,under any circumstances,alter
the grounding plug .Air conditioner must be grounded at all times.Do not remove warning tag from power
cord.If a two-prong (non-grounding) wall receptacle is encountered,contact a qualified electrician and
have the receptacle replaced with a properly grounder wall receptacle in accordance with the National
Electrical Code.

WARNING
To avoid risk of personal injury or death due to electrical shock,grounding wires and wires colored like
grounding wires are NOT to be used as current carrying conductors.The standard accepted color coding
for ground wires is green or green with a yellow stripe.Electrical components such as the compressor
and fan motor are grounded through an individual wire attached to the electrical component and to
another part of the air conditioner.Grounding wires should not to be removed from individual components
while servicing,unless the component is to be removed and replaced.It is extremely important to replace
all removed grounding wires before completing service.

WARNING
To avoid risk of heat exposure,which may cause death or severe illness,air conditioner must be
monitored when malfunctions or shuts down.

Air Conditioner        Edition:2006/1/10

CONTENTS

1. SPECIFICATION....................................1
2. ....................................
3. ..............................
4. ...........................
.................................
6. .......................

Air Conditioner       

SPECIFICATION

Edition:2006/1/10

Air Conditioner        Edition:2006/1/10

Model HSU-07HV03/R2
Cooling Capacity
Rated Power/Current
Cooling
Max Power/Current
EER
Heating Capacity

Heating

Rated Power/Current

HAIER

Brand Mark
2300W
680W/3.0A

1PH

Power

1050W/4.0A

COP

220-230V~ 50 Hz
--------

ModelSectional Area

3.38

Power Cord

2500W

Refer. No.
Compressor

690W/3.1A
1300W/5.3A

Compressor

3.62

--------

RECHI/39A173AD&94K

manufacturer/Type
Max Power/Current

50Hz

Frequency Range

----(poe)

Oil charge

Power/Current of
-----

R410A 650g

Type/Net Charge

Electric Heating

Operating temp. range

Additional Charge for

-7OC-43OC

Refrigerant

1200

0g

exhausting air.
Charge if over Standrad

r/min

20g/m

Pipe Lenth
Indoor
1000

Velocity M
L

950

H
H

850
----

Velocity H

----

Outdoor

LenthInternal/External

r/min
Capilary
r/min

1.4*550+1.4*1350

Diametre
Refer No.----

r/min
Height of rising
r/min
radiator slice
r/min

Indoor Weight

Air

-------

Indoor
Outdoor

mm
mm

Net

8.6kg

Gross

10.6kg

Net

28kg

Gross

30kg

Outdoor Weight
Volume Indoor
(High) Outdoor
Capacitor of Fan Motor:
Class of electric Shock Protection
Class of Water Proof
Moisture Removal
Remote

Model:

Controller

Refer. No.

400
-----

m /h

778*197*250mm

m /h Indoor Dimension(LWH)

2.5indoor Packaging Dimension(LWH)

IP 24

865*272*330mm

Outdoor Dimension (LWH)

780*245*540 mm

Outdoor Packaging dimension(LWH)

908*342*619mm

1.210-3m 3/h

6.35/9.52

liquid /Gas pipe Diametre


Refrigerant

YR-H65
0010401540

5m

standard Lenth

Pipe

Max Lenth

15

Remote Controller Bracket

-----

Lenth/Diametre of Drain Hose

----

Appearance

-----

Max. pressure at warm side

4.15

Climate Type

T1

Max.pressure at cool side

4.15MPa

Installation Bracket Type

-----

Plug Type(spec.)

---

Ammeter spec.

---

Area available for clooling/heating

15-23

Dry/Wet ball(indoor) 32/ 2 3


Max.running
temperature(cooling):

mm

MPa
MPa

Dry/Wet ball(indoor)/
--
Max.running

Dry/Wet ball(outdoor)43 / 26

Dry/Wet ball(outdoor):
temperature(heating):

Air Conditioner        Edition:2006/1/10

Model HSU-09HV03/R2
Cooling Capacity
Rated Power/Current
Cooling
Max Power/Current
EER
Heating Capacity

Heating

Rated Power/Current

HAIER

Brand Mark
3000W
860W/3.5A

1PH

Power

1150W/5.0A

COP

220-230V~ 50 Hz
--------

ModelSectional Area

3.49

Power Cord

3000W

Refer. No.
Compressor

830W/3.5A
1500W/6.3A

Compressor

3.61

--------

RECHI/44A233AJ-JEK

manufacturer/Type
Max Power/Current

50Hz

Frequency Range

---(poe)

Oil charge

Power/Current of
-----

R410A 950g

Type/Net Charge

Electric Heating

Operating temp. range

Additional Charge for

-7OC-43OC

Refrigerant

1250

0g

exhausting air.
Charge if over Standrad

r/min

20g/m

Pipe Lenth
Indoor
1050

Velocity M

950

L
H
,

850
----

Velocity L

----

Outdoor

LenthInternal/External

r/min
Capilary
r/min

1.4*750+1.4*800

Diametre
Refer No.----

r/min
Height of rising
r/min
radiator slice
r/min

Indoor Weight

Air

-------

Indoor
Outdoor

mm
mm

Net:

8.6kg

Gross

10.6kg

Net

31kg

Gross

32kg

Outdoor Weight
Volume Indoor
(High) Outdoor
Capacitor of Fan Motor:
Class of electric Shock Protection
Class of Water Proof
Moisture Removal
Remote

Model:

Controller

Refer. No.

420
-----

m /h

778*197*250mm

m /h Indoor Dimension(LWH)

2.5indoor Packaging Dimension(LWH)

IP 24

865*272*330 mm

Outdoor Dimension (LWH)

780*245*540mm

Outdoor Packaging dimension(LWH)

908*342*619 mm

1.210-3m 3/h

6.35/9.52

liquid /Gas pipe Diametre


Refrigerant

YR-H65
0010401540

5m

standard Lenth

Pipe

Max Lenth

15

Remote Controller Bracket

-----

Lenth/Diametre of Drain Hose

----

Appearance

-----

Max. pressure at warm side

4.15

Climate Type

T1

Max.pressure at cool side

4.15MPa

Installation Bracket Type

-----

Plug Type(spec.)

---

Ammeter spec.

---

Area available for clooling/heating

15-23

Dry/Wet ball(indoor) 32/ 2 3


Max.running
temperature(cooling):

mm

MPa
MPa

Dry/Wet ball(indoor)/
--
Max.running

Dry/Wet ball(outdoor)43 / 26

Dry/Wet ball(outdoor):
temperature(heating):

Air Conditioner        Edition:2006/1/10

Model HSU-12HV03/R2
Cooling Capacity
Rated Power/Current
Cooling
Max Power/Current
EER
Heating Capacity

Heating

Rated Power/Current

HAIER

Brand Mark
4000W
1200W/5.0A

1PH

Power

1500W/6.0A

COP

220-230V~ 50 Hz
--------

ModelSectional Area

3.33

Power Cord

4200W

Refer. No.
Compressor

1160W/5.8A
1500W/6.3A

Compressor

3.62

--------

MEIZHI/PA150X2C-4EN

manufacturer/Type
Max Power/Current

50Hz

Frequency Range

500(poe)

Oil charge

Power/Current of
-----

R410A 950g

Type/Net Charge

Electric Heating

Operating temp. range

Additional Charge for

-7OC-43OC

Refrigerant

1350

0g

exhausting air.
Charge if over Standrad

r/min

20g/m

Pipe Lenth
Indoor
1200

Velocity M

H
M

850
----

Velocity L

----

Outdoor

Capilary

1150

LenthInternal/External

r/min
r/min

Diametre
Refer No.

r/min
Height of rising
r/min
radiator slice
r/min

-----

Indoor Weight

Air

-------------

Indoor
Outdoor

mm
mm

Net

8.8kg

Gross

10.6kg

Net

31kg

Gross

32kg

Outdoor Weight
Volume Indoor
(High) Outdoor
Capacitor of Fan Motor:
Class of electric Shock Protection
Class of Water Proof
Moisture Removal
Remote

Model:

Controller

Refer. No.

450
-----

m /h

795*182*265 mm

m /h Indoor Dimension(LWH)

2.5F

IP 24
1.610-3m 3/h

indoor Packaging Dimension(LWH)

865*272*330 mm

Outdoor Dimension (LWH)

780*245*540mm

Outdoor Packaging dimension(LWH)

908*342*619 mm
6.35/9.52 mm

liquid /Gas pipe Diametre


Refrigerant

YR-H65
0010401540

5m

standard Lenth

Pipe

Max Lenth

15

Remote Controller Bracket

-----

Lenth/Diametre of Drain Hose

----

Appearance

-----

Max. pressure at warm side

4.15

Climate Type

T1

Max.pressure at cool side

4.15MPa

Installation Bracket Type

-----

Plug Type(spec.)

---

Ammeter spec.

---

Area available for clooling/heating

15-23

Dry/Wet ball(indoor) 32/ 2 3


Max.running
temperature(cooling):

MPa
MPa

Dry/Wet ball(indoor)/
--
Max.running

Dry/Wet ball(outdoor)43 / 26

Dry/Wet ball(outdoor):
temperature(heating):

Air Conditioner        Edition:2006/1/10

Model HSU-18HV03/R2
Cooling Capacity
Rated Power/Current
Cooling
Max Power/Current
EER
Heating Capacity

Heating

Rated Power/Current

HAIER

Brand Mark
5000W
1555W/6.9A

1PH

Power

2000W/9.2A

COP

220-230V~ 50 Hz
--------

ModelSectional Area

3.22

Power Cord

5500W

Refer. No.
Compressor

1525W/6.8A
2000W/9.2A

Compressor

3.61

--------

HITACHI/ASH201

manufacturer/Type
Max Power/Current

50Hz

Frequency Range

500(poe)

Oil charge

Power/Current of
-----

R410A 1230g

Type/Net Charge

Electric Heating

Operating temp. range

Additional Charge for

-7OC-43OC

Refrigerant

1350

0g

exhausting air.
Charge if over Standrad

r/min

20g/m

Pipe Lenth
Indoor
1250

Velocity M

Outdoor

Capilary

1100

L
H

880
----

LenthInternal/External

r/min
r/min
r/min
r/min

-----

Diametre
Refer No.

Height of rising

----1.30
1.55

Indoor
Outdoor

mm
mm

radiator slice

Velocity L

----

r/min

Indoor Weight

Air

Net

12kg

Gross

15kg

Net

39kg

Gross

44kg

Outdoor Weight
Volume Indoor
(High) Outdoor
Capacitor of Fan Motor
Class of electric Shock Protection
Class of Water Proof
Moisture Removal
Remote

Model:

Controller

Refer. No.

750
-----

m /h

850305230 mm

m /h Indoor Dimension(LWH)

IP 24
2.010-3m 3/h

Indoor Packaging Dimension(LWH)

960x310x370 mm

Outdoor Dimension (LWH)

820290650 mm

Outdoor Packaging dimension(LWH)

890340710 mm
6.35/12.7 mm

liquid /Gas pipe Diametre


Refrigerant

YR-H10
0010401627

5m

standard Lenth

Pipe

Max Lenth

15

Remote Controller Bracket

-----

Lenth/Diametre of Drain Hose

----

Appearance

-----

Max. pressure at warm side

4.15

Climate Type

T1

Max.pressure at cool side

4.15MPa

Installation Bracket Type

-----

Plug Type(spec.)

---

Ammeter spec.

---

Area available for clooling/heating

15-23

Dry/Wet ball(indoor) 32/ 2 3


Max.running
temperature(cooling):

MPa
MPa

Dry/Wet ball(indoor)/
--
Max.running

Dry/Wet ball(outdoor)43 / 26

Dry/Wet ball(outdoor):
temperature(heating):

Air Conditioner        Edition:2006/1/10

Model HSU-22HV03/R2
Cooling Capacity
Rated Power/Current
Cooling
Max Power/Current
EER
Heating Capacity

Heating

Rated Power/Current

HAIER

Brand Mark
6000W
1990W/8.9A

1PH

Power

2650W/14.0A

COP

220-230V~ 50 Hz
--------

ModelSectional Area

3.02

Power Cord

6500W

Refer. No.
Compressor

2020W/9.0A
2650W/14.0/

Compressor

3.22

Oil charge

--------

HITACHI/PA240X2CS-4KT1

manufacturer/Type
Max Power/Current

50Hz

Frequency Range

500(poe)

Power/Current of
-----

R410A 1530g

Type/Net Charge

Electric Heating

Operating temp. range

Additional Charge for

-7OC-43OC

Refrigerant

1350

0g

exhausting air.
Charge if over Standrad

r/min

20g/m

Pipe Lenth
Indoor
1250

Velocity M

H
M

880
----

Velocity L

----

Outdoor

Capilary

1150

LenthInternal/External

r/min

Diametre

r/min

Refer No.

r/min
Height of rising
r/min
radiator slice
r/min

-----

Indoor Weight

Air

-----

Indoor
Outdoor

1.30
1.55

Net

12kg

Gross

15kg

Net

45kg

Gross

53kg

Outdoor Weight
Volume Indoor
(High) Outdoor
Capacitor of Fan Motor
Class of electric Shock Protection
Class of Water Proof
Moisture Removal
Remote

Model:

Controller

Refer. No.

750
-----

m /h

865228304 mm

m /h Indoor Dimension(LWH)

IP 24
2.510-3m 3/h

Indoor Packaging Dimension(LWH)

923x294x347 mm

Outdoor Dimension (LWH)

810288680 mm

Outdoor Packaging dimension(LWH)

915325699 mm
6.35/12.7 mm

liquid /Gas pipe Diametre


Refrigerant

YR-H10

5m

standard Lenth

Pipe

0010401627

mm
mm

Max Lenth

15

Remote Controller Bracket

-----

Lenth/Diametre of Drain Hose

----

Appearance

-----

Max. pressure at warm side

4.15

Climate Type

T1

Max.pressure at cool side

4.15MPa

Installation Bracket Type

-----

Plug Type(spec.)

---

Ammeter spec.

---

Area available for clooling/heating

15-23

Dry/Wet ball(indoor) 32/ 2 3


Max.running
temperature(cooling):

MPa

Dry/Wet ball(indoor)/
--
Max.running

Dry/Wet ball(outdoor)43 / 26

Dry/Wet ball(outdoor):
temperature(heating):

Air Conditioner      

OPERATION

Edition:2006/1/10

Air Conditioner        

Edition:2006/1/10

Cautions
Safety Instructions and Warnings

Disposal of the old air conditioner


Before disposing an old air conditioner that
goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner
in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system
contains refrigerants, which require specialized waste disposal. The valuable materials
contained in an air conditioner can be recycled
.Contact your local waste disposal center for
proper disposal of an old air conditioner and
contact your local authority or your dealer if
you have any question. Please ensure that
the pipework of your air conditioner does not
get damagedprior to being picked up by the
relevant waste disposal center, and contribute
to environmental awareness by insisting on an
appropriate, anti-pollution method of disposal.

Before starting the air conditioner, read the


information given in the User's Guide carefully. The User's Guide contains very important observations relating to the assembly,
operation and maintenance of the air
conditioner.
The manufacturer does not accept responsibility for any damages that may arise due
to non-observation of the following
instruction.
Damaged air conditioners are not to be
put into operation. In case of doubt, consult
your supplier.
Use of the air conditioner is to be carried
out in strict compliance with the relative
instructions set forth in the User's Guide.
Installation shall be done by professional
people, don't install unit by yourself.

Disposal of the packaging of your


new air conditioner

All the packaging materials employed in the


package of your new air conditioner may be
disposed without any danger to the
environment.
The cardboard box may be broken or cut into
smaller pieces and given to a waste paper
disposal service. The wrapping bag made of
polyethylene and the polyethylene foam pads
contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to
a waste collecting center and used again after
adequate recycling.
Consult your local authorities for the name
and address of the waste materials collecting
centers and waste paper disposal services
nearest to your house.

For the purpose of the safety,the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air
conditioner before openning inlet grill. Never
unplug your air conditioner by pulling on
the power cord. Always grip plug firmly and
pull straight out from the outlet.
All electrical repairs must be carried out
by qualified electricians. Inadequate repairs
may result in a major source of danger for
the user of the air conditioner.
Do not damage any parts of the air
conditioner that carry refrigerant by piercing
or performating the air conditioner's tubes
with sharp or pointed items, crushing or
twisting any tubes, or scraping the coatings
off the surfaces. If the refrigerant spurts
out and gets into eyes, it may result in
serious eye injuries.

Air Conditioner        

Edition:2006/1/10

Cautions
Do not obstruct or cover the ventilation
grille of the air conditoner.Do not put fingers
or any other things into the inlet/outlet and
swing louver.
Do not allow children to play with the air
conditioner.In no case should children be
allowed to sit on the outdoor unit.

Specifications
The refrigerating circuit is leak-proof.

The machine is adaptive in following


situation
1.Applicable ambient temperature range:
Indoor
Cooling

o
o
Maximum:D.B/W.B 32 C/23 C
o
Minimum:D.B/W.B 18 C/14oC
o
o
Maximum:D.B/W.B 43 C/26 C
o
18 C

Outdoor Minimum:D.B

27oC
15oC

Indoor

Maximum:D.B
Minimum:D.B

Outdoor

o
o
Maximum:D.B/W.B 24 C/18 C
o
o
Minimum:D.B/W.B -7 C/-8 C

Heating

2. If the power supply cord is damaged, it


must be replaced by the manufacturer
or its service agent or a similar qualified
person.
3. If the fuse of indoor unit on PC board is
broken,please change it with the type of
T. 3.15A/ 250V.
4. The wiring method should be in line with
the local wiring standard.
5. After installation, the power plug should
be easily reached.
6. The waste battery should be disposed
properly.

7. The appliance is not intended for use


by young children or infirm persons
without supervision.
8. Young children should be supervised
to ensure that they do not play with
the applience.
9.Please employ the proper power plug,
which fit into the power supply cord.
10 .The power plug and connecting cable
must have acquired the local attestation.

Air Conditioner        

Edition:2006/1/10

Cautions
Safety Instruction
Please read the following Safety Instructions carefully prior to use.
The instructions are classified into two levels, WARNING and CAUTION according to
the seriousness of possible risks and damages as follows. Compliance to the
instructions are strictly required for safety use.

Installation
WARNING
Please call Sales/Service Shop for the Installation.
Do not attempt to install the air conditioner by yourself because improper works
may cause electric shock, fire, water leakage.

lnstallation in a inadequate place may cause accidents. Do not install in the following place.

CAUTION
Connect the earth
cable.

Do not install in the Do not get the unit


place where there is exposed to vapor
any possibility of
or oil steam.
inflammable gas
leakage around the
unit.

Check proper
installation of the
drainage securely

earthing

PROHIBITION

10

PROHIBITION

STRICT
ENFORCEMENT

Air Conditioner        

Edition:2006/1/10

Cautions
WARNING
When abnormality such as burnt-small found,
immediately stop the operation button and
contact sales shop.

Use an exclusive power source with a


circuit breaker

STRICT
ENFORCEMENT

OFF
Connect power supply cord
to the outlet completely

STRICT
ENFORCEMENT
Do not use power supply cord
in a bundle.

PROHIBITION
Do not start or stop the
operation by disconnecting
the power supply cord and so on.

PROHIBITION

Use the proper voltage

STRICT
ENFORCEMENT
Take care not to damage
the power supply cord.

Do not use power supply cord


extended or connected in halfway

PROHIBITION
Do not insert objects into the air
inlet or outlet.

PROHIBITION

PROHIBITION
Do not channel the air flow directly
at people, especially at infants or
the aged.

Do not try to repair or reconstruct


by yourself.

PROHIBITION

CAUTION
Do not use for the purpose of storage of Take fresh air occasionally especially Do not operate the switch with
food, art work, precise equipment,
when gas appliance is running at the wet hand.
breeding, or cultivation.
same time.

PROHIBITION
Do not install the unit near a fireplace
or other heating apparatus.

PROHIBITION
Do not place animals or plants in
the direct path of the air flow

PROHIBITION

STRICT
ENFORCEMENT
Check good condition of the
installation stand

PROHIBITION
Do not pour water onto the unit
for cleaning

PROHIBITION

PROHIBITION
Do not place any objects on or
climb on the unit.

PROHIBITION

11

Do not place flower vase or water


containers on the top of the unit.

PROHIBITION

Air Conditioner        

Edition:2006/1/10

Parts and Functions


Indoor unit
Outlet
Air filter(inside)

Display board
Inlet
Air Purifying Filter
(inside)
Inlet grille

Anion generator
(inside)

Vertical flap
(adjust up and down air flow.
Don't adjust it manually)
Horizontal louver
(adjust left and right air flow)

Power plug

For multi-split type, the power plug is on the outdoor unit.

Outdoor unit

HSU-07HV03/R2
HSU-09HV03/R2

HSU-12HV03/R2
HSU-18HV03/R2

H2SM-18HV03/R2
H2SM-(9+12)HV03/R2

HSU-22HV03/R2

OUTLET

3 CONNECTING PIPING AND ELECTRICAL WIRING

INLET

DRAIN HOSE

12

Edition:2006/1/10

Air Conditioner        

Parts and Functions


16

19

29

10

14

20

15

10. TIMER ON display


11. FAN SPEED display
LOW

HI

MED

AUTO

12. LOCK display


13. SWING UP/DOWN display
14. SLEEP display
15. HEALTH display
16. Operation mode display
Operation mode

AUTO COOL

DRY

HEAT FAN

Remote controller
28

Display board

17.Singal sending display


18. Left/right air flow display
19. TEMP display
Remote controller: to display the TEMP. setting.

1.RESET
When the remote controller appears abnormal,
use a sharp pointed article to press this button
to reset the remote controller normal.

2.LIGHT button
3. TIMER button
Used to select TIMER ON, TIMER OFF,
TIMER ON-OFF.

24. HEALTH AIRFLOW button


Used to set the health airflow mode.

25. SWING UP/DOWN button


Used to select up or down air sending direction.

26. SWING LEFT/RIGHT button

4. CLOCK button
Used to set correct time.

Used to select left/right air flow.

5. SLEEP button
Used to select sleep mode.

6. MODE button
COOL

Used to select your desired temperature.

23. FAN button


Used to select fan speed: LOW,MED, HI, AUTO.

Control the lightening and extinguishing of


the indoor LCD display board.

AUTO

20. TIMER OFF display


21. TIMER display
22. TEMP button

27. SET button


Used to confirm timer and clock settings.

28. LOCK
DRY

FAN

HEAT

7. HOUR button
Used to set clock and timer setting.

8. HEALTH button
Used to set healthy operation.

9. ON/OFF button
Used for unit start and stop.

Used to lock buttons and LCD display. If pressed, the


other buttons will be disabled and the lock condition
display appears. Press it once again, lock will be
canceled and lock condition display disappears.

29. Ambient temp.display


When receiving the remote control signal, display the set
temperature and in the rest time the room temperature is
displayed and this room temperature is only for reference.

NOTE: Cooling only unit do not have functions and displays related with heating.

13

Air Conditioner        

Edition:2006/1/10

Parts and Functions


Clock Set
When unit is started for the first time and after replacing batteries in
remote controller, clock should be adjusted as follows:
1. Press CLOCK button,"AM" or "PM" flashes.
2. Press or
to set correct time. Each press will increase or decrease
1 min. If the button is kept depressed, time will change quickly.
3. After time setting is confirmed, press SET, "AM" or "PM" stop flashing,
while clock starts working.
Remote controller's operation
When in use, put the signal transmission head directly to the receiver hole on the indoor unit.
The distance between the signal transmission head and the receiver hole should be within
7m without any obstacle as well.
Don't throw or knock the remoter controller.
When electronic-started type fluorescent lamp or change-over type fluorescent lamp or
wireless telephone is installed in the room, the receiver is apt to be disturbed in receiving
the signals, so the distance to the indoor unit should be shorter.

Loading of the battery


Load the batteries as illustrated right
2 R-03 (7#) batteries
Remove the battery cover:
Slightly press" "area and push down the cover
as illustrated.
Load the battery:
Be sure that the loading is in line with the "+" / "-".
request as illustrated on the bottom of the case.
Put on the cover again.
Confirmation indicator:
After pressing power ON/OFF, if no display, reload the batteries.
Note:
Full display or unclear display during operation indicates the batteries have been used up.
Please change batteries.
Used two new same-typed batteries when loading.
If the remote controller can't run normally during operation, please remove the batteries and
reload several minutes later.
Hint:
Remove the batteries in case unit won't be in usage for a long period. If there are any display
after taking-out, just need to press reset key.

14

Air Conditioner        

Edition:2006/1/10

Operation
HEALTH operation

Remote controller
1.Unit start
Press ON/OFF on the remote controller, unit starts.

2.Health anion function


Press HEALTH button. For each press,
is displayed.
Air conditioner starts health anion function operation.
For twice press,
disappears,the operation stops.

When indoor fan motor is running, it has healthy


process function. (It's available under any mode)
When the fan in the indoor unit does not work, the health lamp
lights up, but the anion generator does not release anion.

BRIEF INTRODUCTION TO HEALTH ANION FUCTION


The anion generator in the air conditioner can generate a lot of
anion effectively balance the quantity of position and anion in the
air and also to kill bacteria and speed up the dust sediment in
the room and finally clean the air in the room.

15

Air Conditioner        

Edition:2006/1/10

Operation
Auto Operation

Remote controller

1. Unit start
Press ON/OFF on the remote controller, unit starts.

2.Select operation mode


Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO

Then

COOL

DRY

FAN

HEAT

Select Auto operation

On the displaying board,colorful displaying bar will be white.

3.Select temp.setting
Press TEMP. button
Every time the button is pressed, temp.setting
increase 1oC,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease 1oC,if kept depressed, it will decrease
rapidly
Select a desired temperature.

4.Fan speed selection


Press FAN button. For each press, fan speed changes as
follows:
Remote controller:
LOW

MED

HI

AUTO

Air conditioner is running under displayed fan speed.


When FAN is set to AUTO, the air conditioner
automatically adjusts the fan speed according to room
temperature.

5.Unit stop
Press ON/OFF button, the unit stops.
About Auto Operation
Under the mode of auto operation, air conditioner will
automatically select Cool or Heat operation according
to room temperature.

16

Air Conditioner        

Edition:2006/1/10

Operation
Cool Operation

Remote controller
1. Unit start
Press ON/OFF on the remote controller, unit starts.

2.Select operation mode


Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO

COOL

DRY

FAN

HEAT

Then Select COOL operation


On the displaying board,colorful displaying bar will be blue.

3.Select temp.setting
Press TEMP. button
Every time the button is pressed, temp.setting
increase 1oC,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease 1oC,if kept depressed, it will decrease
rapidly
Select a desired temperature.

4.Fan speed selection


Press FAN button. For each press, fan speed changes as
follows:
Remote controller:
LOW

MED

HI

AUTO

Air conditioner is running under displayed fan speed.


When FAN is set to AUTO, the air conditioner
automatically adjusts the fan speed according to room
temperature.

5.Unit stop
Press ON/OFF button, the unit stops.

17

Air Conditioner        

Edition:2006/1/10

Operation
Dry Operation

Remote controller
1. Unit start
Press ON/OFF on the remote controller, unit starts.

2.Select operation mode


Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO

COOL

DRY

FAN

HEAT

Then Select DRY operation


On the displaying board,colorful displaying bar will be
light blue

3.Select temp.setting
Press TEMP. button
Every time the button is pressed, temp.setting
increase 1oC,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease 1oC,if kept depressed, it will decrease
rapidly
Select a desired temperature.

4.Fan speed selection


Press FAN button. For each press, fan speed changes as
follows:
Remote controller:
LOW

MED

HI

AUTO

Air conditioner is running under displayed fan speed.


In DRY mode, when room temperature becomes
lower than temp.setting+2oC,unit will run intermittently
at LOW speed regardless of FAN setting.

5.Unit stop
Press ON/OFF button, the unit stops.

18

Air Conditioner        

Edition:2006/1/10

Operation
Fan Operation

Remote controller

1. Unit start
Press ON/OFF on the remote controller, unit starts.

2.Select operation mode


Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO

COOL

DRY

FAN

HEAT

Then Select FAN operation


On the displaying board,colorful displaying bar will be pink.

3.Fan speed selection


Press FAN button. For each press, fan speed changes as
follows:
Remote controller:
LOW

MED

HI

4.Unit stop
Press ON/OFF button, the unit stops.

About FAN operation


In FAN operation mode, the unit will not operate in
COOL or HEAT mode but only in FAN mode ,AUTO is
not available in FAN mode.And temp.setting is disabled.
In FAN mode,SLEEP operation is not available.

19

Air Conditioner        

Edition:2006/1/10

Operation
Heat Operation

Remote controller

1. Unit start
Press ON/OFF on the remote controller, unit starts.

2.Select operation mode


Press MODE button. For each press, operation mode
changes as follows:
Remote controller:
AUTO

COOL

DRY

FAN

HEAT

Then Select HEAT operation


On the displaying board,colorful displaying bar will be red

3.Select temp.setting
Press TEMP. button
Every time the button is pressed, temp.setting
increase 1oC,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease 1oC,if kept depressed, it will decrease
rapidly
Select a desired temperature.

4.Fan speed selection


Press FAN button. For each press, fan speed changes as
follows:
Remote controller:
LOW

MED

HI

AUTO

Air conditioner is running under displayed fan speed


IN HEAT mode, warm air will blow out after a short period
of the time due to cold-draft prevention function.
When FAN is set to AUTO, the air conditioner
automatically adjusts the fan speed according to room
temperature.

5.Unit stop
Press ON/OFF button, the unit stops.

20

Air Conditioner        

Edition:2006/1/10

Operation
Air Flow Direction Adjustment
1.Status display of air sending
Vertical flap

Horizontal louvers

Pos.1
Pos.1
Pos.2

Pos.2

Pos.3

Pos.3

Pos.4

Pos.4

Pos.5

Pos.5

Pos.6

Pos.6

(Auto swing)

Pos.7
Pos.8

2.Up and down air flow direction


For each press of
button, air flow direction on remote controller displays
as follows according to different operation modes:
COOL/DRY/FAN
Pos.1
Pos.2
Pos.3
Pos.4
Pos.6
remote
controller:
:
HEAT:
remote controller:

Pos.5

Pos.4

Pos.3

Pos.2

Pos.1

Pos.6

AUTO:
remote controller:

Pos.1

Pos.2

Pos.3

Pos.4

Pos.5

Pos.6

The vertical flap will swing according to the above positions

3.Left and right air flow direction


For each press of
remote controller:
Pos.1

Pos.2

button, remote controller displays as follows :


Pos.3

Pos.4

Pos.5

Pos.6

Pos.7

Pos.8

The horizontal louvers will swing according to the above positions.


Note:When restart after remote turning off, the remote controller will automatically
memorize the previous set swing position.

21

Edition:2006/1/10

Air Conditioner        

Operation
Sleep Operation

SLEEP operation starts

SLEEP operation stops


Approx.6hrs

Before going to bed, you can simply press the


SLEEP button and unit will operate in SLEEP
mode and bring you a sound sleep.

1 hr

Rises 1OC

1 hr

Use of SLEEP function


After the unit starts, set the operation status,
then press SLEEP button before which the
clock must be adjusted and time being set.

Rises 1OC

Unit stop

Temp.setting

In COOL, DRY mode

2. In HEAT mode

Operation Mode
1. In COOL,DRY mode
1 hours after SLEEP mode starts, temp. will
O
become 1 C higher than temp. setting. After
O
another 1 hours, temp. rises by 1 C further.
The unit will run for further 6 hours then stops.
Temp. is higher than temp. setting so that room
temperature won't be too Iow for your sleep.

1 hours after SLEEP mode starts, temp


O
will become 2 C lower than temp.
setting. After another 1 hours, temp
decrease by 2 OC further. After more
O
another 3 hours, temp. rises by 1 C
further. The unit will run for further 3
hours then stops. Temp. is lower than
temp. setting so that room temperature
won't be too high for your sleep.
Temp.setting

Remote Controller

1 hr

Unit stop

Decreases 2OC
1 hr

Decreases 2OC
3 hrs
3 hrs

Rises 1OC

SLEEP
operation stops

SLEEP
operation starts

In HEAT mode

3. In AUTO mode
The unit operates in corresponding sleep
mode adapted to the automatically selected
operation mode.
4. In FAN mode
It has no SLEEP function.
5.Set the wind speed change when sleeping
If the wind speed is high or middle before
setting for the sleep, set for lowing the wind
speed after sleeping.
If it is low wind, no change.
6.Note to the compensation for the power out:
press the sleep button ten times in five seconds
and enter this function after hearing four sounds.
And press the sleep button ten times within five
seconds and leave this function after hearing
two sounds.
NOTE: With the power-out compensation, when setting
the TIMER ON, TIMER OFF and TIMER ON/OFF,
its memorized as shutdown status when resuming
after power out.

22

Air Conditioner        

Edition:2006/1/10

Operation
Timer On/Off Operation

Remote Controller

Set clock correctly before starting TIMER operation.


1. After unit starts, select your desired operation mode
Operation mode will be displayed on LCD.
2. Timer mode selection
Press TIMER button to change TIMER mode. Every
time the button is pressed, display changes as follows:
Remote controller:
BLANK
TIMER ON

TIMER OFF

TIMER ON-OFF

Then select your desired TIMER mode (TIMER ON or


TIMER OFF). "
"or "
"will flash.

3.Time setting
Press HOUR
button.
Every time the button is pressed, time setting
increases 1 min, if kept depressed, it will increase
rapidly.
Every time the button is pressed, time setting
decreases 1 min, if kept depressed, it will decrease
rapidly.
It can be adjusted within 24 hours.

4.Confirming your setting


After setting correct time, press SET button to confirm
"
"or"
"on the remote controller stops flashing.
Time displayed: Unit starts or stops at x hour x min.
(TIMER ON or TIMER OFF).

5.Cancel TIMER mode


Just press TIMER button several times until TIMER
mode disappears.
Hints:
After replacing batteries or a power failure happens, time setting should be reset.
Remote controller possesses memory function, when use TIMER mode next time,
just press SET button after mode selecting if time setting is the same as previous one.

23

Air Conditioner        

Edition:2006/1/10

Operation
Timer On-Off Operation

Remote Controller

Set clock correctly before starting TIMER operation.


1. After unit starts, select your desired operation mode
Operation mode will be displayed on LCD.
2. Timer mode selection
Press TIMER button to change TIMER mode. Every time
the button is pressed, display changes as follows:
Remote controller:
BLANK
TIMER ON

TIMER OFF

TIMER ON-OFF

Then select your desired TIMER mode (TIMER ON - OFF).


"
"will flash.
3.Time setting
Press HOUR
button.
Every time the button is pressed, time setting increases
1 min, if kept depressed, it will increase rapidly.
Every time the button is pressed, time setting decreases
1 min, if kept depressed, it will decrease rapidly.
It can be adjusted within 24 hours.

4.Timer confirming for TIMER ON


After setting correct time, press TIMER button to confirm
"
" on the remote controller stops flashing.
"
" starts flashing.
Time displayed: Unit starts or stops at x hour x min.
5.Time setting for TIMER OFF
Just press HOUR button ,follow the same procedure in
"Time setting for TIMER ON"
6.Time confirming for TIMER OFF
After time setting,press SET button to confirm.
"
" on the remote controller stops blinking.
Time displayed:Unit stops at x hour x min.
To cancel TIMER mode
Just press TIMER button several times until TIMER
de disappears.
According to the Time setting sequence of TIMER ON
or TIMER OFF, either Start-Stop or Stop-Start can be
achieved.

24

Air Conditioner        

Edition:2006/1/10

Operation
Health airflow Operation

Remote controller

1.Press ON/OFF to starting


The liquid crystal will display the working state of last time
(Except timer, sleeping, power/soft and health airflow).
Setting the comfort work conditions.

2.The setting of health airflow function


1).Press the button of health airflow,
appears on the
display. The nether inlet and outlet grills of the air conditioner are closed and the airflow is blown horizontally from
the above inlet and outlet grills. Avoid the strong airflow
blows direct to the body.
2).Press the button of health airflow again,
appears on
the display. The above inlet and outlet grills of the air conditioner are closed and the airflow is blown vertically from the
nether inlet and outlet grills. Avoid the strong airflow blows
direct to the body.

3.The cancel of the health airflow function


Press the button of health airflow again, both the inlet and
outlet grills of the air conditioner are opened, and the unit
goes on working under the condition before the setting of
health airflow function.
After stopping, the outlet grille will close automatically.
Notice: Cannot pull direct the outlet grille by hand. Otherwise,
the grille will run incorrectly. If the grille is not run correctly,
stop for a minute and then start, adjusting by remote controller.
Note:
1 .After setting the health airflow function, the position of inlet
and outlet grills is fixed.
2.In heating, it is better to select the
mode.
3.In cooling, it is better to select the
mode.
4.In cooling and dry, using the air conditioner for a long time
under the high air humidity, a phenomenon falling drips of
water occurs at the outlet grille .
5.Select the appropriate fan direction according to the actual
conditions.

25

Air Conditioner        

Edition:2006/1/10

Operation
Emergency and Test Operation
Emergency operation:
Use this operation only when the remote controller
is defective or lost.
When the emergency operation switch is
pressed,the" Pi "sound is heard once, which means
the start of this operation.
In this operation, the system automatically selects
the operation modes, cooling or heating, according
to the room temperature.
Temperature Operation Designated
mode
temperature

Timer
mode

Air flow

ABOVE 21OC COOLING

24OC

NO

AUTOMATIC

BELOW 21 C HEATING

24OC

NO

AUTOMATIC

It is not possible to operate in dry mode.

Test operation:
Test operation switch is the same as emergency switch.
Use this switch in the test operation when the room
O
temperature is below 16 C, do not use it in the normal
operation.
Continue to press the test operation switch for more
than 5 seconds. After you hear the "Pi" sound twice,
release your finger from the switch: the cooling operation
starts with the air flow speed "Hi".
After 30 minutes, test operation ends automatically.

Removal of the restriction of emergency or test operation


Press the emergency operation switch once more, or manipulate through the
remote controller; the "Pi" sound, the emergency or test operation is terminated.
When the remote controller is manipulated, it gets the system back to the
normal operation mode.

26

Air Conditioner        

Edition:2006/1/10

Maintenance
For Smart Use of The Air Conditioner
Setting of proper room

Do not block the air inlet

temperature

or outlet

Proper
temperature

Close doors and windows

Use the timer effectively

during operation

During cooling operation


prevent the penetration of
direct sunlight with
curtain or blind

If the unit is not to be used


for a long time, turn off the
power supply main switch.

Use the louvers effectively

OFF

27

Air Conditioner        

Edition:2006/1/10

Maintenance
For Smart Use of The Air Conditioner
WARNING
Before maintenance,be sure to turn off the system and the circuit breaker.

Remote Controller

Do not use water, wipe the controller with a


dry cloth.Do not use glass cleaner or chemical
cloth.

Indoor Body

Wipe the air conditioner by using a soft and


dry cloth.For serious stains,use a neutral
detergent diluted with water.Wring the water
out of the cloth before wiping.then wipe off
the detergent completely.

Do not use the following for cleaning

Gasoline,benzine, thinner or cleanser may


damage the coating of the unit.

Hot water over 40 C(104 F) may cause


discoloring or deformation.

Air Filter cleaning


Open the inlet grille by pulling it upward.
Remove the filter.
Push up the filter's center tab slightly until it is released
from the stopper, and remove the filter downward.

Clean the filter.


Use a vacuum cleaner to remove dust, or wash the filter with
water.After washing, dry the filter completely in the shade.

Attach the filter.


Attach the filter correctly so that the "FRONT" indication is
facing to the front.Make sure that the filter is completely
fixed behind the stopper.If the right and left filters are not
attached correctly, that may cause defects.

Close the inlet grille.

28

Once every
two weeks

Air Conditioner        

Edition:2006/1/10

Maintenance
Replancement of Air Purifying Filter
1.Open the lnlet Grille
Open the inlet grille by pushing each ends of
the inlet grille upward.(use thumbs to push
up)

2.Detach the standard air filter


Slide the knob slightly upward to release the
filter, then withdraw it.

3.Attach old Air Purifying Filter


Put air purifying filter appliances into the
right and left filter frames.

4.Attach the standard air filter


(Necessary installation)

5.Close the Inlet Grille

Detach old Air Purifying Filter

Note: the bacteria-killing mediums placed on the


left side. the multi-lights touching intermediary is
placed on the right side.

Close the Grille surely

NOTE:
The photocatalyst air purifying filter and the bacteria-killing medium air purifying filter
will be used based on real situation.
The photocatalyst air purifying filter will be solarized in fixed time. In normal family,
it will be solarized every 6 months. The solarization time will last no less than 8 hours
under the state of abundant sun.
The bacteria-killing medium air purifying filter is available for a long time and neednt to
be changed. But it must be noticed to use the vacuum cleaner frequently to adsorb the
dusts covering the purifying filter lest the covering dusts effect the function of the
bacteria-killing medium air purifying filter. (It is strictly prohibited for the bacteria-killing
medium air purifying filter to be washed)
The green aspect of the bacteria-killing medium air purifying filter will face outside,
the white aspect will face to the machine.

29

Air Conditioner        

Edition:2006/1/10

Maintenance
To Keep Your Air conditioner in Good Condition
after Season.

Operate in cooling mode for 2-3 hours.


To prevent breeding mold or bad smell, be sure to
operate at the designated temperature or 30OC,cooling
mode and High speed fan mode for 2-3 hours.

Put off the power supply cord.

Cleaning the body.

Take out the batteries from the


wireless remote controller.

30

Air Conditioner        

Edition:2006/1/10

Maintenance
Before Setting in High season
Cleaning the standard air filter.
Operation without filter may cause troubles.Be sure
to attach both right and left filters prior to the operation.
Each of them are of different shapes.

Connecting the earthing cable.


Caution
Incomplete earthing may cause an electric shock.

EARTHING

Do not block the air inlet or outlet.

Plug-in
Caution
After brush away dust at the plug, insert the
plug of the power supply cord into the outlet
completely.In case of suing exclusive circuit
breaker,switch on the circuit breaker.

31

NO WET HAND

Air Conditioner        

Edition:2006/1/10

Trouble shooting
Before asking for service, check the following first.
Phenomenon

Cause or check points

The system does not restart


immediately.

When unit is stopped, it won't restart


immediately until 3 minutes have elapsed
to protect the system.
When the electric plug is pulled out and
reinserted, the protection circuit will work
for 3 minutes to protect the air conditioner.

Noise is heard:

Normal
Performance
inspection

Smells are generated.


Mist or steam are blown out.

Multiple
check

Does not work at all.

Poor cooling

During unit operation or at stop, a swishing


or gurgling noise may be heard. At first 2-3
minutes after unit start, this noise is more
noticeable. (This noise is generated by
refrigerant flowing in the system.)
During unit operation, a cracking noise may
be heard. This noise is generated by the
casing expanding or shrinking because of
temperature changes.
Should there be a big noise from air flow in
unit operation, air filter may be too dirty.
This is because the system circulates smells
from the interior air such as the smell of
furniture, cigarettes.
During COOL or DRY operation, indoor unit
may blow out mist. This is due to the sudden
cooling of indoor air.

Is power plug inserted?


Is there a power failure?
Is fuse blown out?
Is the air filter dirty? Normally it should be
cleaned every 15 days.
Are there any obstacles before inlet and outlet?
Is temperature set correctly?
Are there some doors or windows left open?
Is there any direct sunlight through the
window during the cooling operation?(Use
curtain)
Are there too much heat sources or too many
people in the room during cooling operation?

32

Air Conditioner        Edition:2005/11/18

ELECTRICAL CONTROLL

33

Air Conditioner        

Edition:2006/1/10

2. Run mode:(Tr: inlet air temperature,Tsthe set temperature)


2.1 automatic run mode
The background lighting of the LCD is white
1) cooling only type automatic run mode:
When the system runs under "automatic" mode for the first time, it will determine the operating mode
according to the follows,
TrTs+3 Choose Cooling mode
Tr<Ts-3
Choolse Blowing Mode
The system will shift its operating mode between the above mentioned two to changes of the indoor
temperature. If the system is currently under cooling mode, it will switch to blowing mode when
Tr<Ts-3; if the system is currently under blowing mode, it will in turn switch to cooling mode
when Tr > Ts+3. The switching mode as below,
2) cold/warm type run mode:
When the system runs under "automatic" mode for the first time, it will determine the operating mode
according to the follows,
TrTs-3
Choose Cooling Mode
TrTs-3
Choose Heating Mode
The system will shift its operating mode between the above mentioned two to changes of the indoor
temperature. If the system is currently under cooling mode, the compressor will stop functioning if the
temperature lowers to such a degree that requires so; then it will recheck the temperature 15 minutes
later: it will switch to the heating mode if the temperature is TrTs-3,or it will still stay in cooling
mode(including blowing mode). if the system is currently under heating mode, the compressor will
stop running if the temperatur lowers to such a degree that requires so, then it will recheck teh
temperatur 15 minutes later: it will switch to the cooling mode if the temperature is TrTs+3.
2.2 Cooling run mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is blue
Temperature control range : 1630
Temperature control precision: 1
Compressor cant be controlled by temperature sensor within 2 minutes after it starts.
Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan motor run at
fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr > Ts, outdoor fan motor
and compressor are working again.
If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressors state will not change.
wind speed control: (the temperature difference is 1)
auto:
when Tr>=Ts+3, the wind speed is high;
when Ts+1Tr<Ts+3, the wind speed is medium.
When Tr<Ts+1, the wind speed is low.
When temperature sensor is off, the fan motor runs at low speed.
when the wind speed changes from low to higher, there is no delay, and when it
changes from high to lower, there is a 3-minutes delay before conversion.
Manual operation: When unit is on the wind speed can be set to high, medium, low or automatic as
required (execute instruction 2 seconds later after receiving remote signal)

Air Conditioner        

Edition:2006/1/10

compressor controlThe compressor cant be controlled by temperature sensor within 2 minutes after
startup and can be only restarted at least 3 minutes later after shutdown. There is no 3-minute
protection with power on for the first time (over 3 minutes with power off). The compressor
must
stands by for 3 minutes before it is restarted after shutdown.
There is no 2-minute limit when changing the temperature setting or shutting down the machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the compressor startup.
Controlling the position of air door: set the position of air door as required.
Protection of expiration of current peak value is available: Current cross detection is available in order
to avoid burning out the compressor when the current is too big. The action character as
follows:
The compressor cant be detected in 60 seconds after startup. when current is above CT 1.6 V
and lasts 3 seconds, the system enter protection mode and shut off compressor with outdoor air
blower and indoor fan motor controlled as the temperature sensor is off. After 3 minutes the
machine can be started again.
Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut
off when the temperature of the indoor coil pipe is or below 0 and the compressor runs
for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7, the
compressor is restarted (must meet a 3-minutes delay)
Timer on, Timer off and sleep control are available.
2.3 Dehumidifying mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is aquamarine blue
Temperature control range : 1630
Temperature control precision: 1
control character:
When Tr (indoor temperature) > Ts (temperature setting) +2, compressor and outdoor fan

motor run continuosly with indoor fan motor runnig in accordance with the wind speed setting.
When Tr ranges from Ts to Ts +2, outdoor fan motor and compressor are on for 10 minutes
and off for 6 minutes, the indoor fan motor is off in 3 minutes after shutdown of compressor
and gives breeze in other time.
When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor fan motor
enter breeze mode 3 minutes later after shut down of compressor.
When all the ranges alternate, there is 1 difference.

Wind speed control:


Automation: When Tr >= Ts + 5, the wind speed is high.
When Ts+3 Tr <Ts+5, the wind speed is medium.
When Ts+2 Tr <Ts+3, the wind speed is low.
When Ts Tr <Ts+2, the machine gives breeze intermittently.
When Tr < Ts, the indoor fan motor is shut off. in 3 minutes
When Tr < Ts, the machine gives breeze after 3 minutes
Manual operation: When the temperation sensor is off or the Indoor fan motor runs intermittently,
the indoor fan motor can not be operated by hand (compelling automatic operation), along with

Air Conditioner        

Edition:2006/1/10

the indoor fan motor can be operated in cooling mode. While controlling fan motor by hand in
cooling mode, the cooling ranges include wind speed setting and refriferation range, others are the
same as fan motor in automation mode.
compressor controlThe compressor cant be controlled by temperature sensor in 2 minutes after
startup and also cant be started again at least 3 minutes later after shutdown. There are
3-minutes protection with power on for the first time (over 3 minutes with power off). The
compressor must be started again 3 minutes later after shutdown.
There is no 2-minutes limit when changing the temperature setting or shutting off the machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor startup.
Controlling the position of air door: set the position of air door as required.
Protection of expiration of current peak value is available: Current cross detection is available in order
to avoid burning out the compressor when the current is too big. The action character as
follows:
The compressor cant be detected in 60 seconds after startup. when current is above CT 1.6 V
and lasts 3 seconds, the system enter protection mode and shut off compressor with outdoor air
blower and indoor fan motor controlled as the temperature sensor is off. After 3 minutes the
machine can be started again.
Protection of frost is available (disable in test run or heating mode): In order to prevent the indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor will be shut
off when the temperature of the indoor coil pipe is or below 0 and the compressor runs
for over 5 minutes. When the temperature of the indoor coil pipe ascends to over 7, the
compressor is restarted (must meet a 3-minutes delay)
Timer on, Timer off and sleep control are available.
2.4 Heating mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is red
Temperature control range : 1630
Temperature control precision: 1
Control Character:
When Tr Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan motor runs as
in cold blast avoidance mode, and 4of compensation is added after compressor is started.
When Tr>Ts+5, compressor is off, and the indoor fan motor runs as in cold blast avoidance
mode.
When Tr<Ts+5, compressor, four-ways valve and outdoor fan motor is on, and the indoor fan
motor runs as in the mode of avoiding cold blast.
Control of indoor fan motor:
Manual operation: The wind speed can be set to high, medium, low or automatic as required.
Automatic operation: When Tr < Ts, the wind speed is high;
When Ts=<Tr<Ts+2, the wind speed is medium.
When Tr>= Ts+2, the wind speed is low.
Control of air door: setting the position of air door as required.
compressor controlThe compressor cant be controlled by temperature sensor in 2 minutes after
startup and also cant be started again at least 3 minutes later after shutdown. There are 3-minute
protection with power on for the first time (over 3 minutes with power off). The compressor must

Air Conditioner        

Edition:2006/1/10

be started again 3 minutes later after shutdown.


There is no 2-minutes limit when changing the temperature setting or shutting off the machine through
the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outlet air is available 2 seconds later after startup.
Timer on, Timer off and sleep control are available.
Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts runnig 10
seconds earlier than compressor does. After compressor stops runnig, the 4-way valve continues
running for 2 minutes and 30 seconds then stops. If changing the unit from heating to cooling, the
4-way valve is shut off 2 minutes later and compressor is started 3 minutes later.
Cold blast avoidance mode:
(1)Compressor is interrupted during the defrosting operation and continues to run after defrosting is
completed. When the indoor exchanging temperature is below 23, the indoor fan motor is off.
When the indoor exchanging temperature is above 23, the indoor fan motor is running at
weak speed.
(2)If the temperature of coil pipe cant be above 38 4 minutes later after startup, fan motor is
running at the preset wind speed.
(3) If the temperature of coil pipe is above 38 in 4 minutes after start up, fan motor is running at
the preset wind speed immediately.
(4)If coil pipe descends to the temp. lower than 38 from 38. fan motor still running at the
preset wind speed.
(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil pipe is
above 23, fan motor enter breeze mode; and if the temperature of coil pipe is below 20,
fan motor stops running.
(6)Shut down the unit and indoor fan motor stops running.
High temperature protection and high temperature expiration protection:
z High temperature prevention: When the temp. of coil pipe is above 64, the outdoor fan motor
stops.When the temp descends to 60, the outdoor fan motor is restarted and fan speed
invertage frequence is more than 45 seconds. High temperature expiration prevention: When
the temp. of coil pipe is above 73,compressor and outdoor fan motor stop running 2 seconds
later, and inlet air runs as the temp. sensor is off. When compressor stands by for 3 minute and
the temp. of coil pipe is below 64, the unit can be started again.
Current protection and current expiration protection: (Not detecting within 60 seconds after startup)
z Current
protection:
If
current
detected
is
above
(HSU-12HV03/R2:5.8A;HSU-09HV03/R2:4.5A;HSU-07HV03/R2:4.2A)
and
lasts
10
senconds
continuously,
outlet
air
stops.
If
current
detected
is
below
(HSU-12HV03/R2:5.2A;HSU-09HV03/R2:4.2A;HSU-07HV03/R2:3.8A) , outlet air is
regained Current peak expiration protection: If current detected is above
(HSU-12HV03/R2:9.5A;HSU-09HV03/R2:8.5A;HSU-07HV03/R2:8.5A) , 3 seconds later the
system enter current cross protection, compressor and air outlet stop and start again 3 minuts
later, and air inlet runs as the temperature sensor is off.(different mode has the different CT
value)
Overcooling protection:
One and a half minute later after compressor starts, if the temperature of coil pipe is below -4,
compressor and air outlet stop, and air inlet runs according to the temp. setting. Compressor can be

Air Conditioner        

Edition:2006/1/10

restarted 3 minutes later.


Defrosting:
1.Entry conditions of defrosting:
A. Indoor unit enter overload protection and air outlet stops when air outlet has been restarted
and runs over 10 minutes, and compressor runs over 45 minutes in total and over 20 minutes
continuously, and the temp. of indoor coil pipe is below 38.
B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe decreases 1
per 6 minutes and this operation repeats 3 times, and the temp. of coil pipe is below 38,
then 5 minutes later . the system enters defrosting mode.
C. When compressor runs over 3 hours in total and over 20 minutes continuously and after the
temp. of indoor coil pipe is below 38, the system enters defrosting mode.
D. The difference between the temp. of indoor coil pipe and the indoot temp. is below 16 and
lasts 5 minutes, compressor runs over 45 minutes in total and over 20 minutes continuously,
the temp. of indoor coil pipe is below 38, the system enters defrosting mode.
2.Exit conditions of defrosting:
Defrosting time is higher than 12 minutes (compressor is on), or CT current is above (8.5A).
z During the defrosting, if current peak value is cut off, the unit quit the defrosting mode. But the
protection of expiration of current peak value is unavailable with 60 senconds after compressor
is started.
z During the defrosting and 2 minutes after the defrosting, abnormality of temp. sensor isnt
detected.
z After quiting the defrosting mode, the fan motor enter cooling prevention mode.
3.Defrosting oscillogram:

Automatic temperature compensation of heating:


1. Conditions: Halt time of compressor is below 5 minutes.
2. Operation rules: 1) Ts=Tr + 5 + (Tr Td (temperature detected)[the moment of startup])
2)Tr Td[the moment of startup] 2
Note: the two items above is disable when starting for the first time.

Air Conditioner        

Edition:2006/1/10

3)Press - button in the remote controller, and then restore Ts = Tr + 5.


Press + button in the remote controller, and then operate according to automatic
compensation setting
4)If Tr Td [before compressor starts] 0, and then operate according to
Ts = Tr + 5.
3. If air door in health airflow mode and blow up, the temp. setting of heating is added by 2 in
the base of beginnig.
4.Control function:
4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum time unit is 1
minute. After setting, a pattern of clock displaied on the LCD, and it is off when timer setting is
completed. There are several timer mode as follows.
z Timer on: The pattern of clock displaied on the LCD,the background light is off, and unit
behaves with halt status. Timer on is completed, and then unit starts running with the pattern
of clock disappeared,and the background light is on. The unit starts with the last setting
receiving timer signals, and sleep setting is not allowed.
z Timer off: Unit working, the pattern of clock displaied on the LCD; When reaching time
setting, unit enters shutdown mode, and sleep function can be set. If timer off and sleep are
set synchronously, the one which time is short run first. Executing shutdown instruction clear
timer and sleep function.
z Timer on and timer off can be set synchronously. when they are completed,
4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD
z In cooling/defrosting mode, the temp. setting increases 1 one hour later after startup. After
another hour the temp. setting increase by more 1 and then run continuously for another 6
z

hours and then close.


In heating mode, the temp. setting decrease 2 one hour after startup. After another hour
the temp. setting decrease by more 2. After 3 hours the temp. setting rise by 1and then

run continuously for another 3 hours and then close.


z If the wind speed is set to high or medium before going to bed, the wind speed shifts to
medium or low. If the wind speed is set to low before going to bed, the wind speed keep
unchanged.
4.3 Protection of malfunction of temperature sensitive resistance.
z The temperature sensitive resistor is short circuit or open circuit, the machine doesnt work.
z During defrosting, dont detect if the temperature sensor short circuit or open circuit.
z Detect the temperature of coil pipe is below -40, then think the temperation circuit of coil
z

pipe is open.
Detect the temperature of coil pipe is above 95, then think the temperation circuit of coil pipe

is short .
Detect the temperature of inlet air is below -20, then think the temperation circuit of inlet air

is open.
Detect the temperature of inlet air is above 90,

then think the temperation circuit of inlet air

is short.
4.4 Emergency switch imput:
z Press the switch of emergency operation, then buzzer rings once and unit enters the automatic
operation mode. (emergency operation)

Air Conditioner        

Edition:2006/1/10

If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter enter test run
mode.
z Press the switch again, and then closes.
z The unit can receive remote control.
z Enter emergency operation from timer mode, then timer is cancelled.
z Test run:
1) The temperature sensor of inlet air doesnt work, and compressor starts (but subject to the
limit of -minute delay excluding the first time), and high wind, cooling, and air door is
open.The indoor fan motor runs, running indicator lights up, compressor relay and the one
of outdoor fan motor is closed
2) During test run:
z The prevention of freezing of evaporator doesnt work.
z Over current control doesnt work.
z The control of current peak expiration doesnt work.
z Temperature control doesnt work.
z Temperature expiration control doesnt work.
z The test run is over after 30 minutes,then the unit turn off
4.5 Executive function after 2 seconds by remoter control:
After receiving remote control signal, the mainboard doesnt enter the corresponding
instruction task until 2 seconds elapse.
zF The memory function of power down is available, and the auto recovery function of power on is
optional. (In auto, heating, cooling, or defrosting status, press the sleeping button 10 times within 5
seconds, and the auto recovery function of power on can be set on/off. If the buzzer rings 4 times, the
the auto recovery function of power on is available; If the buzzer rings 2 times, the the auto recovery
function of power on is unavailable.)
4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and the impulse
from fan motor is not detected, then stop outputting voltage to indoor fan motor, send alarm signals.
4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30, and press the sleeping
button for 6 times within 5 seconds, and after the buzzer rings 3 times, the air conditioner
enter manual defrosting mode, which is the same as heating defrosting.

Air Conditioner        

Edition:2006/1/10

2. Run mode:(Tr: inlet air temperature,Tsthe set temperature)


2.1 automatic run mode
The background lighting of the LCD is white
1) cooling only type automatic run mode:
When the system runs under "automatic" mode for the first time, it will determine the
operating mode according to the follows,
TrTs+3 Choose Cooling mode
Tr<Ts-3 Choose Blowing Mode
The system will shift its operating mode between the above mentioned two to changes of
the indoor temperature. If the system is currently under cooling mode, it will switch to
blowing mode when Tr<Ts-3; if the system is currently under blowing mode, it will in
turn switch to cooling mode when Tr > Ts+3. The switching mode as below,
2) cold/warm type run mode:
When the system runs under "automatic" mode for the first time, it will determine the
operating mode according to the follows,
TrTs-3
Choose Cooling Mode
TrTs-3
Choose Heating Mode
The system will shift its operating mode between the above mentioned two to changes of
the indoor temperature. If the system is currently under cooling mode, the compressor
will stop functioning if the temperature lowers to such a degree that requires so; then it
will recheck the temperature 15 minutes later: it will switch to the heating mode if the
temperature is TrTs-3,or it will still stay in cooling mode(including blowing mode).
if the system is currently under heating mode, the compressor will stop running if the
temperatur lowers to such a degree that requires so, then it will recheck teh temperatur

Air Conditioner        

15 minutes later:

Edition:2006/1/10

it will switch to the cooling mode if the temperature is TrTs+3.

2.2 Cooling run mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is blue
Temperature control range : 1630
Temperature control precision: 1
Compressor cant be controlled by temperature sensor within 2 minutes after it starts.
Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan
motor run at fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr
> Ts, outdoor fan motor and compressor are working again.
If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressors state will not
change.
wind speed control: (the temperature difference is 1)
auto:
when Tr>=Ts+3, the wind speed is high;
when Ts+1Tr<Ts+3, the wind speed is medium.
When Tr<Ts+1, the wind speed is low.
When temperature sensor is off, the fan motor runs at low speed.
when the wind speed changes from low to higher, there is no delay, and
when it changes from high to lower, there is a 3-minutes delay before
conversion.
Manual operation: When unit is on the wind speed can be set to high, medium, low or
automatic as required (execute instruction 2 seconds later after receiving remote
signal)
compressor controlThe compressor cant be controlled by temperature sensor within 2
minutes after
startup and can be only restarted at least 3 minutes later after shutdown. There is no
3-minute
protection with power on for the first time (over 3 minutes with power off). The
compressor must
stands by for 3 minutes before it is restarted after shutdown.
There is no 2-minute limit when changing the temperature setting or shutting down the
machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the
compressor startup.
Controlling the position of air door: set the position of air door as required.
Protection of expiration of current peak value is available: Current cross detection is
available in order
to avoid burning out the compressor when the current is too big. The action
character as follows:
The compressor cant be detected in 60 seconds after startup. when current is above
CT 1.6 V
and lasts 3 seconds, the system enter protection mode and shut off compressor with
outdoor air

Air Conditioner        

Edition:2006/1/10

blower and indoor fan motor controlled as the temperature sensor is off. After 3
minutes the
machine can be started again.
Protection of frost is available (disable in test run or heating mode): In order to prevent the
indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor
will be shut off when the temperature of the indoor coil pipe is or below 0 and
the compressor runs for over 5 minutes. When the temperature of the indoor
coil pipe ascends to over 7, the compressor is restarted (must meet a 3-minutes
delay)
Timer on, Timer off and sleep control are available.
2.3 Dehumidifying mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is aquamarine blue
Temperature control range : 1630
Temperature control precision: 1
control character:
When Tr (indoor temperature) > Ts (temperature setting) +2, compressor and

outdoor fan motor run continuosly with indoor fan motor runnig in accordance with
the wind speed setting.
When Tr ranges from Ts to Ts +2, outdoor fan motor and compressor are on for
10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after
shutdown of compressor and gives breeze in other time.
When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor
fan motor enter breeze mode 3 minutes later after shut down of compressor.
When all the ranges alternate, there is 1 difference.

Wind speed control:


Automation: When Tr >= Ts + 5, the wind speed is high.
When Ts+3 Tr <Ts+5, the wind speed is medium.
When Ts+2 Tr <Ts+3, the wind speed is low.
When Ts Tr <Ts+2, the machine gives breeze intermittently.
When Tr < Ts, the indoor fan motor is shut off. in 3 minutes
When Tr < Ts, the machine gives breeze after 3 minutes
Manual operation: When the temperation sensor is off or the Indoor fan motor runs
intermittently, the indoor fan motor can not be operated by hand (compelling
automatic operation), along with the indoor fan motor can be operated in cooling
mode. While controlling fan motor by hand in cooling mode, the cooling ranges
include wind speed setting and refriferation range, others are the same as fan motor in
automation mode.
compressor controlThe compressor cant be controlled by temperature sensor in 2
minutes after
startup and also cant be started again at least 3 minutes later after shutdown. There
are 3-minutes protection with power on for the first time (over 3 minutes with
power off). The compressor must be started again 3 minutes later after shutdown.
There is no 2-minutes limit when changing the temperature setting or shutting off the

Air Conditioner        

Edition:2006/1/10

machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor
startup.
Controlling the position of air door: set the position of air door as required.
Protection of expiration of current peak value is available: Current cross detection is
available in order
to avoid burning out the compressor when the current is too big. The action
character as follows:
The compressor cant be detected in 60 seconds after startup. when current is above
CT 1.6 V
and lasts 3 seconds, the system enter protection mode and shut off compressor with
outdoor air
blower and indoor fan motor controlled as the temperature sensor is off. After 3
minutes the
machine can be started again.
Protection of frost is available (disable in test run or heating mode): In order to prevent the
indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor
will be shut off when the temperature of the indoor coil pipe is or below 0 and
the compressor runs for over 5 minutes. When the temperature of the indoor
coil pipe ascends to over 7, the compressor is restarted (must meet a 3-minutes
delay)
Timer on, Timer off and sleep control are available.
2.4 Heating mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is red
Temperature control range : 1630
Temperature control precision: 1
Control Character:
When Tr Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan
motor runs as in cold blast avoidance mode, and 4of compensation is added after
compressor is started.
When Tr>Ts+5, compressor is off, and the indoor fan motor runs as in cold blast
avoidance mode.
When Tr<Ts+5, compressor, four-ways valve and outdoor fan motor is on, and the
indoor fan motor runs as in the mode of avoiding cold blast.
Control of indoor fan motor:
Manual operation: The wind speed can be set to high, medium, low or automatic as
required.
Automatic operation: When Tr < Ts, the wind speed is high;
When Ts=<Tr<Ts+2, the wind speed is medium.
When Tr>= Ts+2, the wind speed is low.
Control of air door: setting the position of air door as required.
compressor controlThe compressor cant be controlled by temperature sensor in 2

Air Conditioner        

Edition:2006/1/10

minutes after startup and also cant be started again at least 3 minutes later after
shutdown. There are 3-minute protection with power on for the first time (over 3
minutes with power off). The compressor must be started again 3 minutes later after
shutdown.
There is no 2-minutes limit when changing the temperature setting or shutting off the
machine through the remote controller, and the machine can be shut down
immediately.
Avoiding electrical shock: outlet air is available 2 seconds later after startup.
Timer on, Timer off and sleep control are available.
Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts
runnig 10 seconds earlier than compressor does. After compressor stops runnig, the
4-way valve continues running for 2 minutes and 30 seconds then stops. If changing
the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and
compressor is started 3 minutes later.
Cold blast avoidance mode:
(1)Compressor is interrupted during the defrosting operation and continues to run after
defrosting is completed. When the indoor exchanging temperature is below 23,
the indoor fan motor is off. When the indoor exchanging temperature is above 23,
the indoor fan motor is running at weak speed.
(2)If the temperature of coil pipe cant be above 38 4 minutes later after startup, fan
motor is running at the preset wind speed.
(3) If the temperature of coil pipe is above 38 in 4 minutes after start up, fan motor
is running at the preset wind speed immediately.
(4)If coil pipe descends to the temp. lower than 38 from 38. fan motor still
running at the preset wind speed.
(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil
pipe is above 23, fan motor enter breeze mode; and if the temperature of coil
pipe is below 20, fan motor stops running.
(6)Shut down the unit and indoor fan motor stops running.
High temperature protection and high temperature expiration protection:
z High temperature prevention: When the temp. of coil pipe is above 65, the
outdoor fan motor stops.When the temp descends to 60, the outdoor fan motor is
restarted and fan speed invertage frequence is more than 45 seconds. High
temperature expiration prevention: When the temp. of coil pipe is above 72
,compressor and outdoor fan motor stop running 2 seconds later, and inlet air
runs as the temp. sensor is off. When compressor stands by for 3 minute and the
temp. of coil pipe is below 64, the unit can be started again.
Current protection and current expiration protection: (Not detecting within 60 seconds
after startup)
z Current protection: If current detected is above (CT1) and lasts 10 senconds
continuously, outlet air stops. If current detected is below (CT2) , outlet air is
regainedCurrent peak expiration protection: If current detected is above (CT3) , 3
seconds later the system enter current cross protection, compressor and air outlet
stop and start again 3 minuts later, and air inlet runs as the temperature sensor is

Air Conditioner        

Edition:2006/1/10

off.(different mode has the different CT value)


Overcooling protection:
One and a half minute later after compressor starts, if the temperature of coil pipe is
below -4, compressor and air outlet stop, and air inlet runs according to the temp.
setting. Compressor can be restarted 3 minutes later.
Defrosting:
1.Entry conditions of defrosting:
A. Indoor unit enter overload protection and air outlet stops when air outlet has been
restarted and runs over 10 minutes, and compressor runs over 45 minutes in total
and over 20 minutes continuously, and the temp. of indoor coil pipe is below 38
.
B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe
decreases 1 per 6 minutes and this operation repeats 3 times, and the temp. of
coil pipe is below 38, then 5 minutes later . the system enters defrosting mode.
C.

When compressor runs over 3 hours in total and over 20 minutes continuously
and after the temp. of indoor coil pipe is below 38, the system enters defrosting

mode.
D. The difference between the temp. of indoor coil pipe and the indoot temp. is
below 18 and lasts 5 minutes, compressor runs over 45 minutes in total and
over 20 minutes continuously, the temp. of indoor coil pipe is below 38, the
system enters defrosting mode.
2.Exit conditions of defrosting:
Defrosting time is higher than 12 minutes (compressor is on), or CT current is above
(CT1).
z

During the defrosting, if current peak value is cut off, the unit quit the defrosting
mode. But the protection of expiration of current peak value is unavailable with 60
senconds after compressor is started.
z During the defrosting and 2 minutes after the defrosting, abnormality of temp.
sensor isnt detected.
z After quiting the defrosting mode, the fan motor enter cooling prevention mode.
3.Defrosting oscillogram:

Air Conditioner        

Edition:2006/1/10

Automatic temperature compensation of heating:


1. Conditions: Halt time of compressor is below 5 minutes.
2. Operation rules: 1) Ts=Tr + 5 + (Tr Td (temperature detected)[the moment of
startup])
2)Tr Td[the moment of startup] 2
Note: the two items above is disable when starting for the first time.
3)Press - button in the remote controller, and then restore Ts = Tr + 5
.
Press + button in the remote controller, and then operate according
to automatic compensation setting
4)If Tr Td [before compressor starts] 0 , and then operate
according to
Ts = Tr + 5.

4.Control function:
4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum
time unit is 1 minute. After setting, a pattern of clock displaied on the LCD, and it is
off when timer setting is completed. There are several timer mode as follows.
z Timer on: The pattern of clock displaied on the LCD,the background light is off,
and unit behaves with halt status. Timer on is completed, and then unit starts
running with the pattern of clock disappeared,and the background light is on.
The unit starts with the last setting receiving timer signals, and sleep setting is
not allowed.
z Timer off: Unit working, the pattern of clock displaied on the LCD; When
reaching time setting, unit enters shutdown mode, and sleep function can be set.

Air Conditioner        

Edition:2006/1/10

If timer off and sleep are set synchronously, the one which time is short run first.
Executing shutdown instruction clear timer and sleep function.
z Timer on and timer off can be set synchronously. when they are completed,
4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD
z In cooling/defrosting mode, the temp. setting increases 1 one hour later after
startup. After another hour the temp. setting increase by more 1 and then run
z

continuously for another 6 hours and then close.


In heating mode, the temp. setting decrease 2 one hour after startup. After
another hour the temp. setting decrease by more 2. After 3 hours the temp.
setting rise by 1and then run continuously for another 3 hours and then close.

If the wind speed is set to high or medium before going to bed, the wind speed
shifts to medium or low. If the wind speed is set to low before going to bed, the
wind speed keep unchanged.
4.3 Protection of malfunction of temperature sensitive resistance.
z The temperature sensitive resistor is short circuit or open circuit, the machine
doesnt work.
z During defrosting, dont detect if the temperature sensor short circuit or open
circuit.
z Detect the temperature of coil pipe is below -40, then think the temperation
z

circuit of coil pipe is open.


Detect the temperature of coil pipe is above 95, then think the temperation

circuit of coil pipe is short .


Detect the temperature of inlet air is below -20, then think the temperation

circuit of inlet air is open.


Detect the temperature of inlet air is above 90,

then think the temperation

circuit of inlet air is short.


4.4 Emergency switch imput:
z Press the switch of emergency operation, then buzzer rings once and unit enters the
automatic operation mode. (emergency operation)
z If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter
enter test run mode.
z Press the switch again, and then closes.
z The unit can receive remote control.
z Enter emergency operation from timer mode, then timer is cancelled.
z

Test run:
1) The temperature sensor of inlet air doesnt work, and compressor starts (but
subject to the limit of -minute delay excluding the first time), and high wind,
cooling, and air door is open.The indoor fan motor runs, compressor relay and
the one of outdoor fan motor is closed
2) During test run:
z The prevention of freezing of evaporator doesnt work.
z Over current control doesnt work.
z The control of current peak expiration doesnt work.

Air Conditioner        

Edition:2006/1/10

z Temperature control doesnt work.


z Temperature expiration control doesnt work.
z The test run is over after 30 minutes,then the unit turn off
4.5 Executive function after 2 seconds by remoter control:
After receiving remote control signal, the mainboard doesnt enter the
corresponding instruction task until 2 seconds elapse.
zF The memory function of power down is available, and the auto recovery function of
power on is optional. (In auto, heating, cooling, or defrosting status, press the sleeping
button 10 times within 5 seconds, and the auto recovery function of power on can be set
on/off. If the buzzer rings 4 times, the the auto recovery function of power on is available;
If the buzzer rings 2 times, the auto recovery function of power on is unavailable.)
4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and
the impulse from fan motor is not detected, then stop outputting voltage to indoor fan motor, send
alarm signals.
4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30, and press the
sleeping button for 6 times within 5 seconds, and after the buzzer rings 3 times,
the air conditioner enter manual defrosting mode, which is the same as heating
defrosting.

Air Conditioner        

Edition:2006/1/10

2. Run mode:(Tr: inlet air temperature,Tsthe set temperature)


2.1 automatic run mode
The background lighting of the LCD is white
1) cooling only type automatic run mode:
When the system runs under "automatic" mode for the first time, it will determine the
operating mode according to the follows,
TrTs+3 Choose Cooling mode
Tr<Ts-3 Choose Blowing Mode
The system will shift its operating mode between the above mentioned two to changes of
the indoor temperature. If the system is currently under cooling mode, it will switch to
blowing mode when Tr<Ts-3; if the system is currently under blowing mode, it will in
turn switch to cooling mode when Tr > Ts+3. The switching mode as below,
2) cold/warm type run mode:
When the system runs under "automatic" mode for the first time, it will determine the
operating mode according to the follows,
TrTs-3
Choose Cooling Mode
TrTs-3
Choose Heating Mode
The system will shift its operating mode between the above mentioned two to changes of
the indoor temperature. If the system is currently under cooling mode, the compressor
will stop functioning if the temperature lowers to such a degree that requires so; then it
will recheck the temperature 15 minutes later: it will switch to the heating mode if the
temperature is TrTs-3,or it will still stay in cooling mode(including blowing mode).
if the system is currently under heating mode, the compressor will stop running if the
temperatur lowers to such a degree that requires so, then it will recheck teh temperatur

Air Conditioner        

15 minutes later:

Edition:2006/1/10

it will switch to the cooling mode if the temperature is TrTs+3.

2.2 Cooling run mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is blue
Temperature control range : 1630
Temperature control precision: 1
Compressor cant be controlled by temperature sensor within 2 minutes after it starts.
Control character: when Tr> Ts, outdoor fan motor and compressor on, and indoor fan
motor run at fixed wind speed. When Tr < Ts, outdoor fan motor and compressor off, and when Tr
> Ts, outdoor fan motor and compressor are working again.
If Tr=Ts, the indoor fan motor,outdoor fan motor and the compressors state will not
change.
wind speed control: (the temperature difference is 1)
auto:
when Tr>=Ts+3, the wind speed is high;
when Ts+1Tr<Ts+3, the wind speed is medium.
When Tr<Ts+1, the wind speed is low.
When temperature sensor is off, the fan motor runs at low speed.
when the wind speed changes from low to higher, there is no delay, and
when it changes from high to lower, there is a 3-minutes delay before
conversion.
Manual operation: When unit is on the wind speed can be set to high, medium, low or
automatic as required (execute instruction 2 seconds later after receiving remote
signal)
compressor controlThe compressor cant be controlled by temperature sensor within 2
minutes after
startup and can be only restarted at least 3 minutes later after shutdown. There is no
3-minute
protection with power on for the first time (over 3 minutes with power off). The
compressor must
stands by for 3 minutes before it is restarted after shutdown.
There is no 2-minute limit when changing the temperature setting or shutting down the
machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after the
compressor startup.
Controlling the position of air door: set the position of air door as required.
Protection of frost is available (disable in test run or heating mode): In order to prevent the
indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor
will be shut off when the temperature of the indoor coil pipe is or below 0 and
the compressor runs for over 5 minutes. When the temperature of the indoor
coil pipe ascends to over 7, the compressor is restarted (must meet a 3-minutes
delay)

Air Conditioner        

Edition:2006/1/10

Timer on, Timer off and sleep control are available.


2.3 Dehumidifying mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is aquamarine blue
Temperature control range : 1630
Temperature control precision: 1
control character:
When Tr (indoor temperature) > Ts (temperature setting) +2, compressor and

outdoor fan motor run continuosly with indoor fan motor runnig in accordance with
the wind speed setting.
When Tr ranges from Ts to Ts +2, outdoor fan motor and compressor are on for
10 minutes and off for 6 minutes, the indoor fan motor is off in 3 minutes after
shutdown of compressor and gives breeze in other time.
When Tr < Ts, outdoor fan motor and compressor are unavailable, and the indoor
fan motor enter breeze mode 3 minutes later after shut down of compressor.
When all the ranges alternate, there is 1 difference.

Wind speed control:


Automation: When Tr >= Ts + 5, the wind speed is high.
When Ts+3 Tr <Ts+5, the wind speed is medium.
When Ts+2 Tr <Ts+3, the wind speed is low.
When Ts Tr <Ts+2, the machine gives breeze intermittently.
When Tr < Ts, the indoor fan motor is shut off. in 3 minutes
When Tr < Ts, the machine gives breeze after 3 minutes
Manual operation: When the temperation sensor is off or the Indoor fan motor runs
intermittently, the indoor fan motor can not be operated by hand (compelling
automatic operation), along with the indoor fan motor can be operated in cooling
mode. While controlling fan motor by hand in cooling mode, the cooling ranges
include wind speed setting and refriferation range, others are the same as fan motor in
automation mode.
compressor controlThe compressor cant be controlled by temperature sensor in 2
minutes after
startup and also cant be started again at least 3 minutes later after shutdown. There
are 3-minutes protection with power on for the first time (over 3 minutes with
power off). The compressor must be started again 3 minutes later after shutdown.
There is no 2-minutes limit when changing the temperature setting or shutting off the
machine
through the remote controller, and the machine can be shut down immediately.
Avoiding electrical shock: outdoor fan motor is available 2 seconds later after compressor
startup.
Controlling the position of air door: set the position of air door as required.
Protection of frost is available (disable in test run or heating mode): In order to prevent the
indoor heat
exchanger from freezing (in refrigation or dehumidifying mode), the compressor
will be shut off when the temperature of the indoor coil pipe is or below 0 and
the compressor runs for

over 5 minutes. When the temperature of the indoor

Air Conditioner        

Edition:2006/1/10

coil pipe ascends to over 7, the compressor is restarted (must meet a 3-minutes
delay)
Timer on, Timer off and sleep control are available.
2.4 Heating mode: (Tr: inlet air temperature,Tsthe set temperature)
The background lighting of the LCD is red
Temperature control range : 1630
Temperature control precision: 1
Control Character:
When Tr Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan
motor runs as in cold blast avoidance mode, and 4of compensation is added after
compressor is started.
When Tr>Ts+5, compressor is off, and the indoor fan motor runs as in cold blast
avoidance mode.
When Tr<Ts+5, compressor, four-ways valve and outdoor fan motor is on, and the
indoor fan motor runs as in the mode of avoiding cold blast.
Control of indoor fan motor:
Manual operation: The wind speed can be set to high, medium, low or automatic as
required.
Automatic operation: When Tr < Ts, the wind speed is high;
When Ts=<Tr<Ts+2, the wind speed is medium.
When Tr>= Ts+2, the wind speed is low.
Control of air door: setting the position of air door as required.
compressor controlThe compressor cant be controlled by temperature sensor in 2
minutes after startup and also cant be started again at least 3 minutes later after
shutdown. There are 3-minute protection with power on for the first time (over 3
minutes with power off). The compressor must be started again 3 minutes later after
shutdown.
There is no 2-minutes limit when changing the temperature setting or shutting off the
machine through the remote controller, and the machine can be shut down
immediately.
Avoiding electrical shock: outlet air is available 2 seconds later after startup.
Timer on, Timer off and sleep control are available.
Control of 4-way valve: When the unit is started for the first time, the 4-way valve starts
runnig 10 seconds earlier than compressor does. After compressor stops runnig, the
4-way valve continues running for 2 minutes and 30 seconds then stops. If changing
the unit from heating to cooling, the 4-way valve is shut off 2 minutes later and
compressor is started 3 minutes later.
Cold blast avoidance mode:
(1)Compressor is interrupted during the defrosting operation and continues to run after
defrosting is completed. When the indoor exchanging temperature is below 23,
the indoor fan motor is off. When the indoor exchanging temperature is above 23,
the indoor fan motor is running at weak speed.
(2)If the temperature of coil pipe cant be above 38 4 minutes later after startup, fan
motor is running at the preset wind speed.

Air Conditioner        

Edition:2006/1/10

(3) If the temperature of coil pipe is above 38 in 4 minutes after start up, fan motor
is running at the preset wind speed immediately.
(4)If coil pipe descends to the temp. lower than 38 from 38. fan motor still
running at the preset wind speed.
(5)If the temperature sensor is off. Compressor stops runnig. If the temperature of coil
pipe is above 23, fan motor enter breeze mode; and if the temperature of coil
pipe is below 20, fan motor stops running.
(6)Shut down the unit and indoor fan motor stops running.
High temperature protection and high temperature expiration protection:
z High temperature prevention: When the temp. of coil pipe is above 58, the
outdoor fan motor stops.When the temp descends to 55, the outdoor fan motor is
restarted and fan speed invertage frequence is more than 45 seconds. High
temperature expiration prevention: When the temp. of coil pipe is above 68
,compressor and outdoor fan motor stop running 2 seconds later, and inlet air
runs as the temp. sensor is off. When compressor stands by for 3 minute and the
temp. of coil pipe is below 46, the unit can be started again.
Overcooling protection:
One and a half minute later after compressor starts, if the temperature of coil pipe is
below -4, compressor and air outlet stop, and air inlet runs according to the temp.
setting. Compressor can be restarted 3 minutes later.
Defrosting:
1.Entry conditions of defrosting:
A. Indoor unit enter overload protection and air outlet stops when air outlet has been
restarted and runs over 10 minutes, and compressor runs over 45 minutes in total
and over 20 minutes continuously, and the temp. of indoor coil pipe is below 38
.
B. Compressor runs 20 minutes continuously, and the temp. of indoor coil pipe
decreases 1 per 6 minutes and this operation repeats 3 times, and the temp. of
coil pipe is below 38, then 5 minutes later . the system enters defrosting mode.
C.

When compressor runs over 3 hours in total and over 20 minutes continuously
and after the temp. of indoor coil pipe is below 38, the system enters defrosting

mode.
D. The difference between the temp. of indoor coil pipe and the indoot temp. is
below 18 and lasts 5 minutes, compressor runs over 45 minutes in total and
over 20 minutes continuously, the temp. of indoor coil pipe is below 38, the
system enters defrosting mode.
2.Exit conditions of defrosting:
Defrosting time is higher than 12 minutes (compressor is on)
z During the defrosting, if current peak value is cut off, the unit quit the defrosting
mode. But the protection of expiration of current peak value is unavailable with 60
senconds after compressor is started.
z During the defrosting and 2 minutes after the defrosting, abnormality of temp.

Air Conditioner        

Edition:2006/1/10

sensor isnt detected.


z After quiting the defrosting mode, the fan motor enter cooling prevention mode.
3.Defrosting oscillogram:

Automatic temperature compensation of heating:


1. Conditions: Halt time of compressor is below 5 minutes.
2. Operation rules: 1) Ts=Tr + 5 + (Tr Td (temperature detected)[the moment of
startup])
2)Tr Td[the moment of startup] 2
Note: the two items above is disable when starting for the first time.
3)Press - button in the remote controller, and then restore Ts = Tr + 5
.
Press + button in the remote controller, and then operate according
to automatic compensation setting
4)If Tr Td [before compressor starts] 0 , and then operate
according to
Ts = Tr + 5.

4.Control function:
4.1Timer function: You can set 24-hour timer on or timer off as required, and the minum
time unit is 1 minute. After setting, a pattern of clock displaied on the LCD, and it is
off when timer setting is completed. There are several timer mode as follows.
z Timer on: The pattern of clock displaied on the LCD,the background light is off,
and unit behaves with halt status. Timer on is completed, and then unit starts
running with the pattern of clock disappeared,and the background light is on.
The unit starts with the last setting receiving timer signals, and sleep setting is

Air Conditioner        

Edition:2006/1/10

not allowed.
z Timer off: Unit working, the pattern of clock displaied on the LCD; When
reaching time setting, unit enters shutdown mode, and sleep function can be set.
If timer off and sleep are set synchronously, the one which time is short run first.
Executing shutdown instruction clear timer and sleep function.
z Timer on and timer off can be set synchronously. when they are completed,
4.2 Sleep function (saving function at night):. The pattern of clock displaied on the LCD
z In cooling/defrosting mode, the temp. setting increases 1 one hour later after
startup. After another hour the temp. setting increase by more 1 and then run
z

continuously for another 6 hours and then close.


In heating mode, the temp. setting decrease 2 one hour after startup. After
another hour the temp. setting decrease by more 2. After 3 hours the temp.
setting rise by 1and then run continuously for another 3 hours and then close.

If the wind speed is set to high or medium before going to bed, the wind speed
shifts to medium or low. If the wind speed is set to low before going to bed, the
wind speed keep unchanged.
4.3 Protection of malfunction of temperature sensitive resistance.
z The temperature sensitive resistor is short circuit or open circuit, the machine
doesnt work.
z During defrosting, dont detect if the temperature sensor short circuit or open
circuit.
z Detect the temperature of coil pipe is below -40, then think the temperation
z

circuit of coil pipe is open.


Detect the temperature of coil pipe is above 95, then think the temperation

circuit of coil pipe is short .


Detect the temperature of inlet air is below -20, then think the temperation

circuit of inlet air is open.


Detect the temperature of inlet air is above 90,

then think the temperation

circuit of inlet air is short.


4.4 Emergency switch imput:
z Press the switch of emergency operation, then buzzer rings once and unit enters the
automatic operation mode. (emergency operation)
z If the switch is kept pressed for 5 seconds, buzzer ring two times and unit enter test
run mode.
z Press the switch again, and then closes.
z The unit can receive remote control.
z Enter emergency operation from timer mode, then timer is cancelled.
z

Test run:
1) The temperature sensor of inlet air doesnt work, and compressor starts (but
subject to the limit of -minute delay excluding the first time), and high wind,
cooling, and air door is open.The indoor fan motor runs, compressor relay and
the one of outdoor fan motor is closed
2) During test run:

Air Conditioner        

Edition:2006/1/10

z The prevention of freezing of evaporator doesnt work.


z Over current control doesnt work.
z The control of current peak expiration doesnt work.
z Temperature control doesnt work.
z Temperature expiration control doesnt work.
z The test run is over after 30 minutes,then the unit turn off
4.5 Executive function after 2 seconds by remoter control:
After receiving remote control signal, the mainboard doesnt enter the
corresponding instruction task until 2 seconds elapse.
zF The memory function of power down is available, and the auto recovery function of
power on is optional. (In auto, heating, cooling, or defrosting status, press the sleeping
button 10 times within 5 seconds, and the auto recovery function of power on can be set
on/off. If the buzzer rings 4 times, the auto recovery function of power on is available; If
the buzzer rings 2 times, the auto recovery function of power on is unavailable.)
4.6 Alarm from indoor fan motor: 120 seconds later after the indoor fan motor is charged, and
the impulse from fan motor is not detected, then stop outputting voltage to indoor fan motor, send
alarm signals.
4. 7 Manual defrosting: when the wire controller is on, choose high wind, 30, and press the
sleeping button for 6 times within 5 seconds, and after the buzzer rings 3 times,
the air conditioner enter manual defrosting mode, which is the same as heating
defrosting.
5.express mode of malfunction:

Air Conditioner        

Edition:2006/1/10

Error Codes and Description


Code indication

Description

indoor

Indoor Malfunction

E1

Room temperature sensor failure

E2

Heat-exchange sensor failure

E4

Indoor EEPROM error/Humidity sensor malfunction

E14

Indoor fan motor malfunction

Reference
Page

Trouble Shooting
E1: Room temperature sensor failure
E2: Heat-exchange sensor failure

whether terminal CN8 on

CN8
CN8

NO

indoor PCB contact wellt?

Pull out the terminals on the indoor mainboard and


reinsert them

YES
Pull the sensor out of the mainboard
1)

Measure the value of resistance Between its tw o


jumpers

2)

Measure the temperature at the room temperature


sensing head.

Check the value of the

NO

sensor to see whether the


sensor is damaged or not?

YES
The indoor PCB is broken, replace with new indoor PCB

E4: Indoor EEPROM error: Replace the PCB of indoor unit

Sensor is broken,replace it with new sensor

Air Conditioner        

Edition:2006/1/10

E14 :Indoor fan motor malfunction

whether terminal CN7

YES

Pull out and reinsert the terminals

and CON12 on indoor PCB


well inserted or not?

NO
Electrify the machine again and turn it on in the cooling operation,

Measure voltage between the

positions 1 ( red wire) and 5( black

wire) of Terminal CON12 on the indoor PCB

NO

. the voltage is about

the indoor pcb is damaged and need replace

90-200vac
Yes

NO

check whether motor

the indoor motor is damaged and need

can run when

replace

turn on the unit

Yes

When motor is running Measure


whether

there

pulse(0-5VDC)

is

NO

voltage

between

the

the indoor motor is damaged and need

positions 2 (middle wire) and


3(

replace

black wire) of Terminal

CN7on the indoor PCB

the indoor pcb is damaged and need replace

       

Air Conditioner      

TROUBLE

SHOOTING

60

Edition:2006/1/10

Air Conditioner        Edition:2006/1/10

Air Conditioner         Edition:2006/1/10

INSTALLATION

62

Air Conditioner        Edition:2006/1/10

Installation Manual of Room Air Conditioner


Read this manual before installation
Explain sufficiently the operating means to the user
according to this manual.

Necessary Tools for Installation


1.Driver
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)

5.Torque wrench(17mm,22mm,26mm)
6.Pipe cutter
7.Flaring tool
8.Knife

9.Nipper
10.Gas leakage detector or
soap-and-water solution
11.Measuring tape

12.Reamer

Drawing for the installation of indoor and outdoor units


The models adopt HFC free refrigerant R410A

No.
1
2

Accessory parts
Remote controller

R-03 dry battery

Number
of
articles

mo

re th

an

10c

Indoor unit A
Indoor unit B

more than 5cm

Accessory parts

Mounting plate

6
7

4X25
Screw

Plastic cap

Drain-elbow

Cushion

mo

re th

Mark

Drain hose

Optional parts for piping

an

Parts name

Non-adhesive tape

Adhesive tape

Saddle(L.S) with screws

D
E

Connecting electric cable


for indoor and outdoor
Drain hose

Heating insulating material

10c

Attention must be paid to


the rising up of drain hose

Piping hole cover


m

an

Arrangement of piping directions

re th

re

tha

n1

Rear left

10c

mo

mo

0c

Rear
right

Left

Right
Below

an

60c

re th

mo

The marks from A to G in the figure are the parts numbers.


The distance between the indoor unit and the floor should be
more than 2m.

63

more

than

15c

256

319.5

Air Conditioner        Edition:2006/1/10

140

500

140

113.5

Floor fixing dimensions


of the outdoor unit
(Unit:mm)

HSU-07HV03/R2
HSU-09HV03/R2

HSU-12HV03/R2
HSU-18HV03/R2

Fixing of outdoor unit

583

113.5

Floor fixing dimensions


of the outdoor unit
(Unit:mm)

Floor fixing dimensions


of the outdoor unit
(Unit:mm)

HSU-22HV03/R2

Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.
When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails
or wires in consideration of earthquake and strong wind.
If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Indoor Unit

Selection of Installation Place

Place, robust not causing vibration, where the body can be supported
sufficiently.
Place, not affected by heat or steam generated in the vicinity, where
inlet and outlet of the unit are not disturbed.
Place, possible to drain easily, where piping can be connected with the
outdoor unit.
Place, where cold air can be spread in a room entirely.
Place, nearby a power receptacle, with enough space around. (Refer
to drawings).
Place where the distance of more than lm from televisions, radios,
wireless apparatuses and fluorescent lamps can be left.
In the case of fixing the remote controller on a wall, place where the
indoor unit can receive signals when the fluorescent lamps in the room
are lightened.

Outdoor Unit

Place, which is less affected by rain or direct sunlight and is


sufficiently ventilated.
Place, possible to bear the unit, where vibration and noise are
not increased.
Place, where discharged wind and noise do not cause a
nuisance to the neighbors.
Place, where a distance marked
is available as illustrated
in the above figure.

Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.
Install an exclusive branch circuit of the power.
A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

Selection of pipe
To this unit, both liquid and gas pipes shall be insulated
as they become Iow temperature in operation.
Use optional parts for piping set or pipes covered with
equivalent insulation material.
The thickness of the pipe must be 0.8 mm at least.

For 07,09,12
Liquid pipe(
Gas pipe(

64

)
)

For 18,22

6.35mm(1/4")

6.35mm(1/4")

9.52mm(3/8")

12.7mm(1/2")

Air Conditioner        Edition:2006/1/10

Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed

A=80mm

35

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be
fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from
the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape

Fit the level line

When the mounting plate is fixed side bar and lintel


Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten
the plate to the fixed mounting bar.
Refer to the previous article, "
position of wall hole.

When the mounting plate is first fixed ", for the

2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation

Indoor side
Wall hole
70mm

Outdoor side
Thickness
of wall

(Section of wall hole) G Piping hole pipe

3.Installation of the Indoor Unit


Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left

Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear
piping which is marked on heat insulation materials.

65

Air Conditioner        Edition:2006/1/10

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then
connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

Heat insulation
material
Lid for right piping

Pipe supporting plate

Lid for left piping


Drain hose

Lid for under piping

Piping

Indoor/outdoor
electric cable

Fix with adhesive tape

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

[Other direction piping]


Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation
of connecting part specially.

Fixing the indoor unit body


Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing.
In order to fix the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.

4.Connecting the indoor/outdoor Electric Cable


Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then
take off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit


1. Insert from outside the room cable into left side of the wall hole, in which
the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.

66

Air Conditioner        Edition:2006/1/10

When connecting the cable before installing the indoor unit


Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring
is not correct, proper operation can not be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
qualified person. The type of connecting wire is H05RN-F or H07RN-F.
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

WHT
BR
RED
YEL/GRN

BLK WHT

BLK
RED

BR
YEL/GRN

Indoor unit

Outdoor unit

HSU-07HV03/R2
HSU-09HV03/R2
HSU-12HV03/R2
WHT

YEL/GRN

RED

BLK WHT

BLK

1(L) 2(N)

Indoor unit

BR
RED

BR
YEL/GRN

HSU-18HV03/R2
HSU-22HV03/R2

Outdoor unit

claw of the clip

5.Easily-demount cleaning of indoor unit


1.Top inlet can be taken down
Open the inlet grille, press the claw of the clip on the unit,then
take down the top inlet.(according to figure 1)

Figure 1
Figure 2

2.Vertical flap can be taken down


Overturn the vertical flap, press the claw of the clip ,then take
down vertical flap.(according to figure 2)
3.Horizontal louvers can be taken down
After taking down vertical flap.Horizontal louvers are appeared,draw
the middle louver,and take down the horizontal louvers .
(according to figure 3)

Figure 2
Daff

Figure 3

67

Air Conditioner        Edition:2006/1/10

Outdoor unit
1.Installation of Outdoor Unit
Install according to

Drawing for the installation of indoor and outdoor units

2.Connection of pipes
To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Flare nut

Half union

Forced fastening without careful centering


may damage the threads and cause a
leakage of gas.
Pipe Diameter (

Spanner

Fastening torque

Liquid side 6.35mm(1/4")

18N.m

Gas side 9.52mm(3/8")

40N.m

Gas side 12.7mm(1/2")

55N.m

Torque wrench

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.

3.Connection
HSU-12HV03/R2
Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into
terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor unit.
If wiring is not correct, proper operation can not be carried out and controller may be damaged.
Fix the cable with a clamp.

4.Attaching Drain-Elbow
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)

68

Air Conditioner        Edition:2006/1/10

2-way valve
Liquid Side

6.Purging Method:To use vacuum pump

3-way valve
Gas Side

1
Detach the service port's cap of 3-way valve, the

Gaugemanifold(for R410A)

valve rod's cap for 2-way valve and 3-way's, connect

Anti countercurrent joint

the service port into the projection of charge hose


(Iow) for gaugemanifold. Then connect the projection
of charge hose (center) for gaugemanifold into
Tube(for R410A)

vacuum pump.

Vacuum pump(for R410A)

2
Open the handle at Iow in gaugemanifold, operate

Open

vacuum pump. If the scale-moves of gause (Iow)


reach vacuum condition in a moment, check 1 again.

3
Vacuumize for over 15min. And check the level gauge
which should read -0.1 MPa (-76 cm Hg) at Iow
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the

Close

operation of the vacuum pump.


Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of 3 .

2-way valve

4
Open the valve rod for the 2-way valve to an angle of
anticlockwise 90 degrees.

3-way valve

Open
O

90

After 6 seconds, close the 2-way valve and make


the inspection of gas leakage.

2-way valve
5
No gas leakage?

In case of gas leakage, tighten


parts of pipe connection. If
leakage stops, then proceed

If it does not stop gas leakage, discharge


whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder.

steps.

3-way valve

2-way valve

6
Detach the charge hose from the service port, open

3-way valve

2-way valve and 3-way. Turn the valve rod anticlockwise

HSU-07HV03/R2
HSU-09HV03/R2
HSU-22HV03/R2

until hitting lightly.


6

7
To prevent the gas leakage, turn the service port's

2-way valve

2-way valve

3-way valve

cap, the valve rod's cap for 2-way valve and 3-way's
3-way valve

a little more than the point where the torque increases


suddenly.

7 Valve rod cap

8
After attaching the each caps, check the gas leakage
around the caps.

HSU-12HV03/R2
HSU-18HV03/R2

7 Valve rod cap


7 Service port cap

CAUTION:
1.If the refrigerant of the air conditioner leaks, it is necessary to

2.Please do not let other cooling medium, except specified one (R410A),

discharge all the refrigerant. Vacuumize first, then charge the liquid

or air enter into the cooling circulation system. Otherwise, there will be

refrigerant into air conditioner according to the amount marked on

abnormal high pressure in the system to make it crack and lead to

the name plate.

personal injuries.

69

Air Conditioner        Edition:2006/1/10

1.Power Source Installation


The power source must be exclusively used for air conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place, please install an
earth leakage breaker.
For installation in other places, use a circuit breaker as far as possible.

2.Cutting and Flaring Work of Piping


Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.
A

Flare tool for R410A

Flare tooling die


1.Cut pipe

2.Remove burs

Clutch-type

Conventional flare tool


clutch-type(Rigid-type) Wing-nut type (Imperial-type)

0~0.5mm

1.0~1.5mm

1.5~2.0mm

3.Insert the flare nut

Incorrect

Correct
4.Flare pipe

Lean Damage of flare Crack

Partial

Too outside

3.On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.

Less than 5cm

It becomes high
midway.

The end is immersed


in water.

It waves.

The gap with the ground


is too small

There is the bad smell


from a ditch

Please pour water in the drain pan of the indoor unit, and confirm that drainage is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation
to it without fail.

Check for Installation and Test Run


Please kindly explain to our customers how to operate through the instruction manual.

Check Items for Test Run


Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of
indoor and outdoor firmly inserted
to the terminal block?
Is the connecting wiring of indoor
and outdoor firmly fixed?

Put check mark

in boxes

Is drainage securely carried out?


Is the earth line securely
connected?
Is the indoor unit securely fixed?
Is power source voltage abided
by the code?
Is there any noise?

70

Is the lamp normally lighting?


Are cooling and heating (when
in heat pump) performed normally?
Is the operation of room temperature
regulator normal?

Air Conditioner        Edition:2005/1/10

CIRCUIT AND WIRING DIAGRAM

71

Air Conditioner        Edition:2006/1/10

CIRCUIT DIAGRAM FOR INDOOR


UNIT

BUZ1

+5

R54

CON21

FUSE1

07
11
12

48
+5V

+5

R 4 2 10K
R29 10K

D2 RLS4148

R3 1K
C1
102

PTF4/TBCH0

56
60
10
C2 104
57

Q3
2SC2412

220V-N

2UF 450V

IC3

R57

2003

680

+12V
R64

C11
104

+12

E12
100u/25v

R73
R 2 6 4.7K
4.7K
5v
SW2

10K

COMP

IC4

R56

HXF

2003

PTE0/TXD NET OUT


PTE1/RXD NET IN
PTE2/TACH0 PG BACK
PTG2/KBD2 STF

16
17
18
19
20

PTE3/TACH1 PG OUT
PTE4/SS
COMP OUT
PTE5/MISO HXF/JY
PTE6/MOSI FLZ
PTE7/SPSCK W F J

01

PTC4

26
27

R2522K C
D
R4822K A

28
29

PA2 (LARGE/ SMALL


UP C
PA3
UP D

30
31
32
33
38

PA4
PA5
PA6
PA7
PTB4

DOWN A
DOWN B
DOWN C
DOWN D
LEFT D

50

PTD4

DOOR

B
C
D
D

PA0 (COOL/HEAT) UP A
PA1

UP B

58
55
VREFH
54
VDDA
C4
104
PTG0/KBD0 23
PTG1/KBD1
24
EE SCL PTF2/TBCH2 06
EE DATAPTF1/TACH3 05
VDDAREF
RIGHT APTD3
RIGHT BPTD2
RIGHT CPTD1
RIGHT DPTD0
LEFT A PTB7/ATD7
LEFT B PTD6/ATD6
LEFT C PTB5/ATD5

16
15
14
13
12
11
10
9

R32 1 K

1
2
3
4
5
6
7
8
9
10

72

C22
102/50V

1
2
3
4
5
6
7
8
9
10

C23

63

103/50V

C24

62

103/50V

C25

53

102/50V

C26

52

102/50V

CON5-1
TO DISP

C27

51

102/50V

4
3
2
1

6
Vcc

+5
A
B
C
D
A
B
C

C6

R46

R24

1K

10K

C15
102

C8
102

DJR
CON16(BLUE)

+12

C7

1
D15

+5

RL2
OEG-SS-112DM

CON20
COMP

DJR

IC5

CON21
220VL

C20
104

RL1

+12

D5

ZJ1

G4A-1A-P
CON14(RED)
1

+5

FLZ

IN4148
CN3

R39

R38

1K

390

LEFT STEP

RIGHT STEP

VR1

CN10

DOOR

UP STEP DOWN STEP

5
6 SDA
7 SCL
8 24C01A

C14
104

2003

1
2

FLZ

102/50V
64

IC2

R8 10K

XT1
8M

ZJ/SHORT

+5v
R33 10K

C21
102
CN2

R1
1M

MC68HC908AB32

+12
WFJ

R7 10K

44
47
46
43
42
41
40
39

ZJ/SHORTPTB1/ATD1 35
34
CT
PTB0/ATD0

CON18 CON19

C3
103

R43 1K
C19
104
+12

1K
Q8 2SB1182

+5

1
2
3
4
5
6
7
8

TLP3526

L2 125UH

HXF

+5V

OSC2

1
2
3
4
5
6
7
8

1W-120O

E13
100u/16v
+5V

C38

61

WHITE

R53 1 K
R85 330
R69 100
R68 100
R67 100
R70 330
R71 330
R72 330

103/50V

NC

A
R22 22K

4.7UF/50V

C47

CGMXFC

R40 4.7K

R20 22K

16
15
14
13
12
11
10
9

+12V

IC10

Q9

2SC2412
+5
R19 4.7K R21 4.7K

220V-L

C39
R83

DJR

4.7UF/50V

E6

220V-L

15

E7

REC

103/50V

13
14

STF

1
2
3

PTF7

3.3K 1%

1
2
3
4
5
6
7
8

C16
102

4
3
2
1

R23 4.7K

CON12

YJKG

R 3 6 1K

25

PTC0

GND

20K 1%

R35

1
ROOM 2
PIPE 3
4

16
15
14
13
12
11
10
9

CN6
C43
103

VSSA

04
61
64
63
62
53
52
51
59

R34

R14 1K

FANBACK

AVSS/VRE GND

PTF0/TACH2
PTC1
PTC5
PTC3
PTC2/MCLK
PTD7
PTD6/TACLK
PTD5
OSC1

C41
102

1
2
3

09

REC
TIM
RED
BLUE
GREEN
POW
RUN
HEALTH

R44 1K
C9
102

+5V
R50 5 1 K

+5
CN7

+5V
R 3 7 10K

C10
102

GND

CN8

+5
R45 1K

ROOM PTB2/ATD2 36
PIPE
PTB3/ATD3 37

RST
VSS

E5
100u/16v

2
1

R10 10K

PTH1/KBD3 FAR IN
PTH1/KBD4 FAR OUT

45

C18
104/50V

Ultraviolet_A
Ultraviolet_C

08

21

C13
104

PTF3/TBCH3 BUZZ
PTF5
PTF6

49

03
E1
1UF/16V

2W

C33 222/300VAC

4.7K

RLS4148

C5 102

Q2
2SC2412

R55
560

10V/0.5V

R60
1.3

R62
39K

22

D7

104/50V

R9

STD2NBP60

10K
R76

5
4
3
2
1

R 2 8 1K

VDD

C34
104
R61
E14
4.7K 100U/16V

Q817C

S
E9
22U/25V

220VL
+5

IRQ

220V-L
02

T3.15A

C 2 8 E4
104 220U/16V

D IC13
C

NCP1200P60

R41 1K

R2 10K

15
R75

GND

IC6

CS

S14K350

+5

C36
104

IC8

DRV

C40

IC7
7805

C48
104/50V

ZE1

104/275V

20UHE11
470U/25V

C35
104

C30102 R58 27

D6

220V-N

10K

SW1

L1
E10 12V

1000U/25V

R18 C17
4.7k 103/50v

R59
4.7K

R31

UF302

UF4007

NC

Q4

C12
102

10K

D8

Q5
2SC2412

2SC2412

R30

+12V

E8
22U/450V

Q1
2SC2412

R 6 6 27

JZKZ

TLP521

D12

HV

1K
R27 1 0 K

2
1

3
D9

5
4
3
2
1

CN9

R49
100

103/50V

R13

1
R65
C37 4.7k
104

C31 TRAN1-3

R51
47K/2W

R121 K
+5

R17
10k

10K

C44

D111N4007 R52 3 .6/ 3W


D14

FB

104/50V

D13

R11

103/50V

C42

LX1

R16
10k

IC9

C45

CN12

472/1KV T1

2W/78K

C29
R15
104/50v 10k

+12v

ADJ

Q6
S9013

Q7
S9013

A 1
12V 2
C 3

CT1
E3

CN4

CON15
1

D10
RLS4148
STF

RL4
G5N-1A

RL5

WFJ

FLZ
220N

STF

2
WFJ 3

W04
BD2

470U/16V

RL3
G5N-1A

220V-N

+5

BEEP-PKM13EPY-4002

Ultraviolet_Control

+12v

HSU-07/09/12HV03/R2

CON13
B3P5-VH-3/( BLUE
JAQ-1 12V MOL-35979-0314

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR INDOOR


UNIT

HSU-07HV03/R2

Fan Motor

8
FUSE
LCD Board

UV Light

CT

7
Heater

B
R
BR
BL
W

BLACK
RED
BROWN
BLUE
WHITE

Y/G YELLOW/GREEN

POWER SUPPLY

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR OUTDOOR


UNIT

HSU-07HV03/R2

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR INDOOR


UNIT

HSU-09HV03/R2

Fan Motor

8
FUSE
LCD Board

UV Light

CT

7
Heater

B
R
BR
BL
W

BLACK
RED
BROWN
BLUE
WHITE

Y/G YELLOW/GREEN

POWER SUPPLY

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR OUTDOOR


UNIT

HSU-09HV03/R2

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR INDOOR


UNIT

HSU-12HV03/R2

Fan Motor

8
FUSE
LCD Board

UV Light

CT

7
Heater

B
R
BR
BL
W

BLACK
RED
BROWN
BLUE
WHITE

Y/G YELLOW/GREEN

POWER SUPPLY

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR OUTDOOR


UNIT

HSU-12HV03/R2

Air Conditioner        Edition:2006/1/10

CIRCUIT DIAGRAM

HSU-18HV03/R2

+5
R15

+12v

C29
104/50v

electrical source

10k

R47
10k

BUZ1

T1
TRAN1-3

LB2271

D13

4007
D9

D14

R30

103/50v

ZE1

C40

2SC2412

E4

C28
104

S14K350

104/275V

220U/16V

CON21

FUSE1

10K

+12V

Q4

100U/25V

+5

220V-N

C17

R18
3k

Q1
2SC2412

R66 27

E14

D12

2SC2412

Q5
2SC2412

R27 10K

D11

Q4

104
E11
470U/25V C36

C34
104

104
C35

1000U/35V
E10

10k

10K
R49
100

centralize control

+5V

7805

R17

R11

+5

IC7

12V

T3.15A

220V-L

R59
4.7K

R31

220VL

C12 102

10K

+5

R41 1K

02

R9

07

4.7K

11
12

R2 10K

+5

+5V

R42 10K
R29 10K

C1
102

03
21

C13
104

E1
1UF/16V

45
56
60

C2 104

room temp.
pipe temp.

centralize control OUT

R45 1K

36
37

C10
102

C9
102

GND

remote REC
red lamp
blue lamp
green lamp
DAL
WRL
LCS
CX1

AVSS/VRE GND
VSSA

GND

manual switch

3-min delay

remote REC

100
100
100
330
330
330

57

C47

CGMXFC

R1
1M

none

Q3
2SC2412

220V-N

right A
right B
right C
left D
left A
left B
left C

AO42-20uH

TLP3526

R22 22K

IC3

R57

2003

680

PG-OUT

4.7K

C11
104

+12

R26
4.7K

R73
4.7K

R2522K
R4822K

E12
100u/25v

5v

compressor

SW2

26

function select up A

27

display select 1 up B

short time/self test

C
D

28
29

model select up C
display select 2 up D

curient test

A
B
C
D
D

30
31
32
33
38
50

IC4

CN2

35
34

R46

R24

1K

10K

C15
102

C8
102

C7
103/50V

+12

none 23

short time/self test

CON21

C20
104
+12

up louver motor down louver motor

R38
390

1
2

anion

BD2

CT1

RL3
G5N-1A

CN4

CON15(W)
1

left louver motor right louver motor


VR1

E3

D10
RLS4148
4-way valve

W04
470U/16V

CON14(R)

+5

CN10

door switch

G4A-1A-P

FLZ

CN3
1K

220VL

RL1
compressor

ZJ1

IN4148

R39

CON20
compressor
1

IC5

none 24

+5v
R33 10K
R32 1K

4
3
2
1

+5

2003

D5

C21
102

102/50V

101/50V
C6
104/50V

MC68HC908AB32

+12

C27

IC2

door switch

ANION

C26

51

C46

R43 1K

OUT FAN

52

+5

A
B
C
D
A
B
C

47
46
43
42
41
40
39

none 61

down A
down B
down C
down D
left D

C19
104
+12

2003

O2

16
15
14
13
12
11
10
9

L1

R21

102/50V

102/50V

5
SDA
6
SCL
7
8 24C01A

C14
104

06
EE clock
05
EE date
44

PG-OUT
compressor
fresh air
anion
outdoor fan

1
2
3
4
5
6
7
8
9
10

0.01U*120/300V

+5

1
2
3
4
5
6
7
8

IC10

1
2
3
4
5
6
7
8

RC1

R19 4.7K
R20 22K

C25

53

101/50V

ST OUT

01

+12V

16
15
14
13
12
11
10
9

FAN

2UF 450V

103/50V
103/50V

R7 10K

R8 10K

C32

C3
103

C24

+5V

PG-FB

R40 10K
220V-L

C39

+5
C4
104

C23

62

220V-L

16
17
18
19
20

58
55
54

CN5-1

63

1
2
3
4
5
6
7
8

R23 4.7K

4-way valve

CX2
VREFH
VDDA

network OUT
network IN

15

E13
100u/16v

1
2
3
4
5
6
7
8
9

16
15
14
13
12
11
10
9

13
14

4
3
2
1

network (R)

25

1
2
3

+5V

5
4
3
2
1

CN6

C16
102

R14 1K
C43
103

2
1

1
2
3

PG-FB

CON12

103/50V

XT1
8M

R36 1K

+5
CN7

09

5
4
3
2
1

+5V
R37 10K

+5V
R50 51K

103/50V

E6 4.7UF/50V

R53 1K
R69
R68
R67
R70
R71
R72

C22

64

R35 3.3K 1%

C41
102

04
64
63
62
53
52
51
59

1
2
3
4

(W)

R34 20K 1%

reset
VSS

CN8

room temp.
pipe temp.
E7 4.7UF/50V

R44 1K

buzzer 2
none

10

R10 10K

+5

centralize control IN

08
61

E5
100u/16v

C18
104/50V

UV light class A
UV light class C

49

D2 RLS4148

R3 1K

manual switch

22

buzzer

48
SW1

VDD

cross zero

220V-N

C5 102

R28 1K
Q2
2SC2412

RL4
G5N-1A

JAQ-1 12V

1
2

WFJ

RL5
out fan

FLZ
220N
STF

CON13

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR INDOOR UNIT

Y/G

Fan Motor

HSU-18HV03/R2

SW1
CON12

CN8

CN9

CN7

CON13
CN3

CON21
W

CN4

FUSE1
T3.15A
250VAC

C0N15
R
C0N14

CN2
LCD Board

C0N20
4

CN5-1

BR
R
Y/G
BR

BL

Y/G

W B

R BR
3 4

POWER SUPPLY
TO THE OUTDOOR UNIT

B
R
BR
BL
W

BLACK
RED
BROWN
BLUE
WHITE

Y/G YELLOW/GREEN

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR OUTDOOR UNIT

HSU-18HV03/R2

Air Conditioner        Edition:2006/1/10

CIRCUIT DIAGRAM

HSU-22HV03/R2

+5
R15

+12v

C29
104/50v

electrical source

10k

R47
10k

BUZ1

T1
TRAN1-3

LB2271

D13

4007
D9

D14

+5

C17

R18
3k

Q4

100U/25V

+5

220V-N

ZE1

103/50v

C40

2SC2412

Q1
2SC2412

R30

E14

D12

2SC2412

Q5
2SC2412

R27 10K

D11

Q4

104
E11
470U/25V C36

C34
104

104
C35

1000U/35V
E10

10k

10K

R66 27

+5V

7805

R49
100

centralize control

IC7

12V

R17

R11

E4

C28
104

S14K350

104/275V

FUSE1

CON21

T3.15A

220VL

220U/16V

10K
+12V

220V-L

R59
4.7K

R31

C12 102

10K

+5
02

4.7K

07
11
12

48
SW1

R2 10K

+5

+5V

R42 10K

08

D2 RLS4148

R3 1K

manual switch

49

R29 10K

61

C1
102

03
21

C13
104

E1
1UF/16V

45
56
60
10

R10 10K

C2 104

VDD

cross zero

22

E5
100u/16v

C18
104/50V

buzzer
UV light class A
UV light class C

+5

centralize control IN
room temp.
pipe temp.

centralize control OUT

R45 1K

36
37

R44 1K

buzzer 2

C10
102

none

C9
102

GND

remote REC
red lamp
blue lamp
green lamp
DAL
WRL
LCS
CX1

AVSS/VRE GND
VSSA

GND

manual switch

3-min delay

R69
R68
R67
R70
R71
R72

100
100
100
330
330
330

C47

16
17
18
19
20

Q3
2SC2412

220V-N

PG-FB

+5

R21

right A
right B
right C
left D
left A
left B
left C

4.7K

R22 22K

1
2
3
4
5
6
7
8

RC1

R19 4.7K
R20 22K

R25 22K

R57

2003

104

680

PG-OUT

C11

+12

R26
4.7K

R73
4.7K

R48 22K

5v

E12
100u/25v

SW2

27

display select 1 up B

short time/self test

C
D

28
29

model select up C
display select 2 up D

curient test

A
B
C
D
D

30
31
32
33
38
50

IC4

compressor

function select up A

1
2
3
4
5
6
7
8

AO42-20uH

TLP3526

26

35
34

R46

R24

1K

10K

C15
102

C8
102

4
3
2
1

none 23

short time/self test

+12

CON21

C20
104
+12

ZJ1

220VL

RL1
compressor

R32 1K

door switch

up louver motor down louver motor

R38

1K

390

FLZ
anion

BD2

CT1

RL3
G5N-1A

CN4

CON15(W)
1

left louver motor right louver motor


VR1

E3

D10
RLS4148
4-way valve

W04

470U/16V

CON14(R)

+5

CN10
1
2

C21
102

R39

G4A-1A-P
1

IN4148

CN3

+5v
R33 10K

CON20
compressor
1

IC5

none 24

C7
103/50V

+5

2003

D5

ANION
CN2

102/50V
102/50V

101/50V
C6
104/50V

MC68HC908AB32

+12

C27

C46

R43 1K

OUT FAN

C26

51

IC2

door switch

C19
104
+12

2003
O2

102/50V
52

+5

A
B
C
D
A
B
C

47
46
43
42
41
40
39

none 61

down A
down B
down C
down D
left D

16
15
14
13
12
11
10
9

L1

IC3

1
2
3
4
5
6
7
8
9
10

0.01U*120/300V

103/50V

+5V

5
6 SDA
SCL
7
8 24C01A

C14
104

06
EE clock
05
EE date
44

PG-OUT
compressor
fresh air
anion
outdoor fan

01

+12V

IC10

16
15
14
13
12
11
10
9

FAN

2UF 450V

C25

101/50V

ST OUT

R40 10K
220V-L

C39

C24

53

R7 10K

R8 10K

C32

C3
103

103/50V
62

220V-L

R23 4.7K

4-way valve

+5
C4
104

CN5-1

C23

63

1
2
3
4
5
6
7
8

15

58
55
54

E13
100u/16v

1
2
3
4
5
6
7
8
9

16
15
14
13
12
11
10
9

network (R)

CX2
VREFH
VDDA

network OUT
network IN

13
14

4
3
2
1

5
4
3
2
1

CN6

C16
102

2
1

R14 1K
C43
103

25

1
2
3

+5V

R36 1K

1
2
3

PG-FB

CON12

103/50V

XT1
8M

5
4
3
2
1

+5

CN7

R1
1M

none

103/50V
remote REC

CGMXFC
09

C22

64

E6 4.7UF/50V

R53 1K

57

+5V
R37 10K

+5V
R50 51K

(W)

R35 3.3K 1%

C41
102

04
64
63
62
53
52
51
59

1
2
3
4

R34 20K 1%

reset
VSS

CN8

room temp.
pipe temp.
E7 4.7UF/50V

220V-N

R9

C5 102

R41 1K
R28 1K
Q2
2SC2412

RL4
G5N-1A

JAQ-1 12V

1
2

WFJ

RL5
out fan

FLZ
220N
STF

CON13

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR INDOOR UNIT

Y/G

Fan Motor

HSU-22HV03/R2

3
Central control

SW1(CN11) CN8
CON21

CON13

CON12 CN7
CN3

C0N15
(C0N25)

CN9

CN4

FUSE1
T3.15A
250VAC

C0N14

CN2
RECEIVER
DISPLAY
CN5-1
5

C0N20

Y/G BL

BR

4 5

TERMINAL BLOCK

TO THE OUTDOOR UNIT

BLACK

R
BR
BL
W

RED
BROWN
BLUE
WHITE

Y/G YELLOW/GREEN

Air Conditioner        Edition:2006/1/10

WIRING DIAGRAM FOR OUTDOOR UNIT

WIRING DIAGRAM OF OUTDOOR UNIT

HSU-22HV03/R2

Sincere Forever

Haier Group
Haier Industrial Park, No.1, Haier Road
266101, Qingdao, China
http://www.haier.com