SEL-735 Settings Sheets


General Settings
General settings are available from the front panel and communications ports.

Identifier and Scaling Settings


Meter Identifier Labels
Meter Identifier (20 characters)
MID

:=

TID

:=

CTR

:=

PTR

:=

Terminal Identifier (20 characters)

Current and Potential Transformer Ratios


Phase Current Transformer Ratio CTR:1 (1.00006000)

Potential Transformer Ratio PTR:1 (1.000010000)

Analog Quantity Scaling Settings


Voltage Scaling (UNITY, KILO, MEGA)
VOLT_SCA :=
Power and Demand Scaling (UNITY, KILO, MEGA)
POWR_SCA :=
Energy Scaling (UNITY, KILO, MEGA)
ENRG_SCA :=
Present Analog Quantities in Primary (Y, N)
PRI_SCA

Date Code 20160628

Instruction Manual

:=

SEL-735 Meter

SET.2 of 32

Instrument Transformer Compensation


For the following settings, replace x with the Phase A, B, or C, and replace n with the calibration point
number. Form 5 meters do not have Phase B CT compensation. Form 5 and Form 36 meters do not
have Phase B PT compensation.

Enable ITC for Current (N, 16)


EITCI

:=

ICAL_n

:=

IRCFx_n

:=

IPAMx_n

:=

EITCV

:=

VCAL_n

:=

VRCFx_n

:=

VPAMx_n

:=

WGAIN

:=

VARGAIN

:=

Secondary Amps for Calibration Point n (0.0120.00 A)

CT Ratio Correction Factor (0.98001.0200)

CT Phase Angle Minutes (300.0 to 300.0)

Enable ITC for Voltage (N, 16)

Secondary Volts for Calibration Point n (5.00300.00 V)

PT Ratio Correction Factor (0.98001.0200)

PT Phase Angle Minutes (300.0 to 300.0)

Global Settings
Gain Adjustment Settings
Watt Gain % (10.00 to 10.00)

VAR Gain % (10.00 to 10.00)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.3 of 32

Advanced Global Settings


Watt/VAR angle cutoff (OFF, 110 degrees)
ANGCUT

:=

IST

:=

IST_TYPE

:=

PHROT

:=

DATE_F

:=

TSTYPE

:=

Starting Current Threshold (x10 mA)


(x is 1.0 mA for CL2/10/20 meters and 5.0 mA for
CL10/20 meters)

Starting Current Type (ALL, RMS_ONLY)

Phase rotation (ABC, ACB)

Date format (MDY, YMD, DMY)

IRIG Time Source Type (IRIG, IEEE*)


(Hidden and forced to IEEE if EPMIP > 0)

*(When TSTYPE := IEEE, the device requires IEEE C37.118 control bits to be sent from the IRIG clock.
If TSTYPE is set to IEEE, but control bits are not included in the IRIG signal, then the device word bit
TIRIG will continually toggle.)

Offset from UTC (24.00 to +24.00 hours)


UTC_OFF

:=

Time Change Flag Threshold (159 s)


TIME_CHG :=

Flicker Meter Setting


Flicker Reference Voltage (VBASE, 120, 230)
FLICKREF :=

Synchrophasors

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.4 of 32

Messages per Second


(1, 2, 5, 10, 25, or 50 when frequency := 50 Hz)
(1, 2, 4, 5, 10, 12, 15, 20, 30, or 60 when frequency := 60 Hz)
MRATE

:=

PMSTN

:=

PMID

:=

PHDATAV

:=

VCOMP

:=

PHDATAI

:=

ICOMP

:=

NUMANA

:=

PMUAQ1

:=

PMUAQ2

:=

PMUAQ3

:=

PMUAQ4

:=

Station Name (16 characters)

PMU Hardware ID (165534)

Phasor Data Set, Voltages (V1, PH, ALL, NA)

Phase Voltage Angle Compensation (179.99 to +180.00 deg)

Phasor Data Set, Currents (I1, PH, ALL, NA)

Phase Angle Current Compensation (179.99 to +180.00 deg)

Number of PMU Analog Values (04)

PMU Analog Quantity 1

PMU Analog Quantity 2

PMU Analog Quantity 3

PMU Analog Quantity 4

Number of 16-bit Digital Status Words (0, 1)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.5 of 32

NUMDSW

:=

TREA1

:=

TREA2

:=

TREA3

:=

TREA4

:=

PMTRIG

:=

FP_TO

:=

FP_CONT

:=

SCROLD

:=

DPn

:=

DPn_1

:=

Trigger Reason Bit 1 (SELOGIC)

Trigger Reason Bit 2 (SELOGIC)

Trigger Reason Bit 3 (SELOGIC)

Trigger Reason Bit 4 (SELOGIC)

PMU Trigger (SELOGIC)

Front Panel
Front-Panel Display Settings
Front-Panel Time-out (OFF, 1120 min)

Front-Panel Contrast (18)

Display Update Rate in seconds (160)

Front-Panel Display Point Settings


Replace n with the display point value 0150.

Logic String

Alternate Display when Logic = 1 (64 characters, NA to null)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.6 of 32

Normal Display when Logic = 0 (64 characters, NA to null)


DPn_0

:=

Front-Panel LED Logic Settings


Replace n with the LED value 0114. T07_LEDT14_LED are available only if the corresponding
PB0nFCN (where n = 14) button is set to NA. Refer to on page for more details.

First Pushbutton Function (TEST, ALT, WAVCAP,


RSTPQALRM, RESETPE, RESETPD, LAMPTEST, NA)
PB01FCN

:=

PB02FCN

:=

PB03FCN

:=

PB04FCN

:=

Tn_LED

:=

Second Pushbutton Function (TEST, ALT, WAVCAP,


RSTPQALRM, RESETPE, RESETPD, LAMPTEST, NA)

Third Pushbutton Function (TEST, ALT, WAVCAP,


RSTPQALRM, RESETPE, RESETPD, LAMPTEST, NA)

Fourth Pushbutton Function (TEST, ALT, WAVCAP,


RSTPQALRM, RESETPE, RESETPD, LAMPTEST, NA)

Front-Panel LEDn Logic

RESET Pushbutton Function (RESETPE, RESETPD,


LAMPTEST)
RESETFCN :=
Reset Peak Demand Inhibit Time (OFF, 0.012250.00 hours)
RPDEMINH :=

Metering Settings
Demand
EDEM Enable Demand Metering Method
Demand Metering (THM = Thermal, ROL = Rolling,
BLOK = Block)
EDEM
SEL-735 Meter

Instruction Manual

:=
Date Code 20160628

SET.7 of 32

EDEM Enable Demand Metering Method


Time constant (1, 5, 10, 15, 30, 60 minutes)
DMTC

:=

DMSI

:=

Sub-interval time constant (see Table 0.1)


(Hidden if EDEM set to THM or BLOK)

Table 0.1 DMSI Range


DMTC
Value

DMSI Range

1 min

5, 1 min

10

10, 5, 2, 1 min

15

15, 5, 3, 1 min

30

30, 15, 10, 6, 5, 3, 1 min

60

60, 30, 20, 15, 12, 10, 6, 5, 3, 1 min

Demand Block Time (OFF, 1300 minutes)


DBLOCK

:=

FLTBLK

:=

EOIPT

:=

PRED

:=

PREDAL

:=

Fault Bit Block (SELOGIC control equation)

End of Interval Pulse Timer (OFF, 15 s)

Predicted Peak Demand Quantity (any present interval Demand


Analog Quantity) (Hidden if EDEM = THRM)

Peak Demand Alarm Level (Primary units; kilo scaling for


power quantities, unity scaling for current quantities units
0.001,000,000.00) (Hidden if EDEM =THRM)

Loss Compensation Settings


The following settings are available when ETLLC = Y.
Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.8 of 32

ETLLC Enable Transformer/Line Losses Compensation


Enable Transformer/Line Losses Compensation (Y, N)
ETLLC

:=

BPOS

:=

MPOS

:=

ELCU

:=

ELFE

:=

LWCU

:=

LWFE

:=

MVA

:=

KVLL

:=

%Z

:=

Meter Position Settings


System Billing Point (14)

System Metering Point (14)

Transformer Losses Settings


Transformer Copper Losses Compensation (Y, N)
(Hidden if ETLLC = N)

Transformer Iron Losses Compensation (Y, N)


(Hidden if ETLLC = N)

Transformer Copper Watt Losses (0.0000110000.00000 kW)

Transformer Iron Watt Losses (0.0000110000.00000 kW)

Transformer 3-Phase MVA Rating (0.0000110000.00000


MVA)

Primary Line-to-Line Metered Voltage (0.0000110000.00000


kV)

Transformer Percentage Impedance (0.001%19.999%)

Transformer Percentage Exciting Current (0.001%19.999%)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.9 of 32

%IMAG

:=

SLR

:=

SLX

:=

LLR

:=

LLX

:=

XFTR

:=

Supply and Load Line Losses Settings


Supply Line Resistance (0.0000999.9999 Ohms, primary)

Supply Line Reactance (0.0000999.9999 Ohms, primary)

Load Line Resistance (0.0000999.9999 Ohms, primary)

Load Line Reactance (0.0000999.9999 Ohms, primary)

Power Transformer Turns Ratio (VSupply/VLoad)

Energy Preload Settings


Replace n with the phase number of A, B, or C, or 3 for three-phase. Single-phase settings are only
available with Form 9 and Form 36 meters.

Meter Energy Preload Settings (Compensated)


Phase n KWh Delivered (0999999999999.999 kWh)

KWHn_DEL

:=

Phase n KWh Received (0999999999999.999 kWh)

KWHn_REC

:=

Phase n KVAh Delivered (0999999999999.999 kVAh)

KUHn_DEL

:=

Phase n KVAh Received (0999999999999.999 kVAh)

KUHn_REC

:=

Phase n KVARh Delivered Lag


(0999999999999.999 kVARh)

KQHn_DEL_LG :=

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.10 of 32

Phase n KVARh Delivered Lead


(0999999999999.999 kVARh)

KQHn_DEL_LG :=

Phase n KVARh Received Lag


(0999999999999.999 kVARh)

KQHn_REC_LG :=

Phase n KVARh Received Lead


(0999999999999.999 kVARh)

KQHn_REC_LG :=

Meter Energy Preload Settings (Uncompensated)


Phase n KWh Delivered (0999999999999.999 kWh) KWHn_DEL_UC

:=

Phase n KWh Received (0999999999999.999 kWh)

KWHn_REC_UC

:=

Phase n KVARh Delivered Lag


(0999999999999.999 kVARh)

KQHn_DEL_LG_UC :=

Phase n KVARh Delivered Lead


(0999999999999.999 kVARh)

KQHn_DEL_LD_UC :=

Phase n KVARh Received Lag


(0999999999999.999 kVARh)

KQHn_REC_LG_UC :=

Phase n KVARh Received Lead


(0999999999999.999 kVARh)

KQHn_REC_LD_UC :=

Configurable Registers
The Configurable Registers settings cannot be preconfigured when ordering an SEL-735.

Configurable Register (11000)

CONFIGREG

:=

Analog Quantity (Analog Quantity)

NAME

:=

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.11 of 32

Alias String (39 chars max)

ALIAS

:=

Units String (15 chars max)

UNITS

:=

Decimal Places (06)

DECIMALS

:=

Leading Zeros (Y, N)

LEADINGZEROS

:=

Large Font (Y, N)

LARGEFONT

:=

User Scale (Y, N)

SCALEUSER

:=

Scale (1 x 1010 to 1 x 1010)

SCALEVALUE

:=

Offset (1 x 1010 to 1 x1010)

OFFSET

:=

Scale Type (PRIMARY, SECONDARY)

SCALETYPE

:=

Units Type (UNITY, KILO, MEGA)

UNITSTYPE

:=

Rollover Type (DIALS, VALUE)

ROLLOVERTYPE :=

Rollover Dials (512)

ROLLOVERDIALS :=

Rollover Value (0 to 1 x 1015)

ROLLOVERVALUE:=

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.12 of 32

Inputs/Outputs
KYZ Pulse Outputs
KYZ Pulse n Settings
Replace n with the KYZ channel number 14.

KEn Scale (PRI, SEC)


KEn_SCALE :=
Watthour Constant n (0.00019,999.0000)
KEn

:=

KEn_UNIT

:=

KYZDn

:=

MYZPWn

:=

KEn_OUT

:=

KET

:=

OUT1n

:=

KEn Units (UNITY, KILO, MEGA)

Demand Type to Output n

KYZ Minimum Pulse Width n (25, 50, 75, 100 ms)

KYZ Output Contact

(Available only with solid-state output contacts)

KYZ Pulse Test Mode Setting


Watthour Constant (0.00019999)

Output Contacts
Output Contact Equations
Replace n with the output contact number 0103.

Output Contact 1n

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.13 of 32

Output Contact Equations (Extra I/O Board)


Replace n with the output contact number 0104.

Output Contact 4n
OUT4n

Optoisolated Input Timers 101102


Replace n with the optoisolated input number 0102.

Input IN1n debounce time (08 ms, AC)


IN1nD

:=

IN4nD

:=

AOnAQ

:=

AOnAQL

:=

AOnAQH

:=

AOnL

:=

AOnH

:=

Optoisolated Input Timers 401404


Replace n with the optoisolated input number 0104.

Input IN4n debounce time (08 ms, AC)

Analog Output Settings


Replace n with a value 0104.

AOn Analog Quantity

AOn Analog Quantity Low


(2147483647.000 to +2147483647)

AOn Analog Quantity High


(2147483647.000 to +2147483647)

AOn Low Analog Output Value (1.200 or 24.000)

AOn High Analog Output Value (1.200 or 24.000)

Events and Logging


Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.14 of 32

Load Profile Settings


Billing Recorder
Load profile settings consist of 112 recorders, each containing as many as 16 elements from analog
quantities.

Recorder Function (EOI, AVG, COI, MAX, MIN)


LDFUNC1

:=

LDLIST1

:=

LDAR1

:=

LMDUR1

:=

Load Profile List (16 elements max., NA to null)

Load Profile Acquisition Rate


(359 s; 1, 2, 3, 5, 10, 15, 30, 60, 120 minutes)

Load Profile Maximum Duration (0.055000.00 days)

(359 s requires Advanced or Intermediate PQ and Recording)

Recorder n
For additional recorders, replace n with a value of 212. Additional recorders require Advanced or
Intermediate PQ and Recording.

Recorder Function (EOI, AVG, COI, MAX, MIN)


LDFUNCn

:=

LDLISTn

:=

LDARn

:=

LMDURn

:=

Load Profile List (16 elements max, NA to null)

Load Profile Acquisition Rate


(359 s; 1, 2, 3, 5, 10, 15, 30, 60, 120 minutes)

Load Profile Maximum Duration (0.055000.00 days)

(359 s requires Advanced or Intermediate PQ and Recording)

Voltage Sag/Swell/Interruption Settings


Voltage Base (20.00300.00 VL-N for Form 9 and
36 meters. 20.00480.00 VL-L for Form 5 meters.)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.15 of 32

VBASE

:=

AVG_TIME (OFF, 110 min)


AVG_TIME :=
The following Voltage/Sag/Swell/Interruption Settings are in percent of VBASE.

L-N Voltage Interrupt (OFF, 5.0099.00)


VINT

:=

VINTHYS

:=

VSAG

:=

VSAGHYS

:=

VSWELL

:=

Voltage Interruption Hysteresis (0.0010.00)

L-N Voltage Sag (OFF, 10.0099.00)

Voltage Sag Hysteresis (0.0010.00)

L-N Voltage Swell (OFF, 101.00180.00)

Voltage Swell Hysteresis (0.0010.00)


VSWELHYS :=

Harmonics Settings
Harmonic Triggers
Replace n with the harmonic component 0215.
The following Harmonic Alarm settings are in percent of VBASE.

Harmonic Trigger Quantities (ALL, VOLTAGE, CURRENT)


HARMTRIG :=
nth Harmonic Threshold (OFF, 3100%)
HARMn

:=

INCIHQ

:=

Interharmonic Quantities
Include Interharmonic Quantities (Y, N)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.16 of 32

(Requires Advanced PQ and Recording)

Sequential Events Recorder Settings


Replace n with the Sequential Events Recorder number 13.

Auto-Removal Enable (Y, N)


ESERDEL

:=

SRDLCNT

:=

SRDLTIM

:=

SERn

:=

Number of Counts (220)

Removal Time (0.590.0 s)

(For more details, refer to on page )

Sequential Events Recorder n (24 elements max, NA to null)

Event Report
Replace n with the Event Report Trigger List number 13. Includes optional features.

ER Trigger List n
ERn

:=

SRATE

:=

LER

:=

PRE

:=

Waveform Capture Sample Rate (16, 128, 512 samples


per cycle)

Event Length (15, 30, 60, 120, 300, 600 cycles)

(15 cycles only available with Basic PQ and Recording)


(600 cycles not available when SRATE = 512)

Prefault Length (1595 cycles)

(The Prefault Length must be at least 5 cycles less than the Event Length)

SELOGIC Control Equations


SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.17 of 32

Latch Bits
Latch Bit Settings
Replace n with the Latch Bit number 0116.

Set Latch Bit LTn


SETn

:=

RSTn

:=

LReset Latch Bit LTn

Control Equations
Replace n with the SELOGIC control equation number 0116.

SELOGIC Control Equation Variable SVn


SVn

:=

SVnPU

:=

SVnDO

:=

MVn

:=

SCnCV

:=

SCnPV

:=

SVn Timer Pickup (0.0001000000.000 s)

SVn Timer Dropout (0.0001000000.000 s)

Math Variables
Math Variable Equations
Replace n with the Math Variable number 0116.

SELOGIC Math Equation Variable MVn

Counter Equations
Counter Equation Settings
Replace n with the Counter number 0116.

Current Value (0999999)

(SCnCV must be less than or equal to SCnPV)

Counter Preset Value (1999999)

Reset (SELOGIC Equation)


Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.18 of 32

SCnR

:=

SCnLD

:=

SCnCU

:=

SCnCD

:=

TMBnA

:=

TMBnB

:=

RSTDEM

:=

RSTPKDM

:=

Load (SELOGIC Equation)

Count Up (SELOGIC Equation)

Count Down (SELOGIC Equation)

MIRRORED BITS Communications Equations


Replace n with the Transmit MIRRORED BIT number 18.

MIRRORED BITS Channel A


Channel A, transmit bit n

MIRRORED BITS Channel B


Channel B, transmit bit n

Reset Trigger Equations


Reset Trigger SELOGIC Equations
Demand Reset (SELOGIC Equation)

Peak Demand Reset (SELOGIC Equation)

Reset Peak Demand Counters (SELOGIC Equation)


RPKDMCT :=
Reset Energy (SELOGIC Equation)
RSTENRG

:=

Reset Power Quality Alarm (SELOGIC Equation)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.19 of 32

RPQALRM :=

Communication
Ports
Port Security Settings
Enable Port (Y, N)
EPORT

:=

ETELNET

:=

Enable Telnet (Y, N)

Enable Modbus (Y, N)


EMODBUS :=
Maximum Access Level (1, E, 2)
MAXACC

:=

(If the password jumper is installed, MAXACC does not limit the ports access level and all ports
enable regardless of the EPORT setting)

Enable TCP Keep-Alive (Y, N)


ETCPKA

:=

Enable FTP (Y, N)


EFTPSERV :=
Enable IEC 61850 Protocol (06)
E61850

:=

EGSE

:=

ESNTP

:=

Enable IEC 61850 GSE (Y, N)

(EGSE is only available if E61850 > 0)

Enable SNTP (OFF, UNICAST, MANYCAST, BROADCAST)

Enable DNP3 LAN/WAN Sessions (05)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.20 of 32

EDNP

:=

EPMIP

:=

Enable PMU Sessions (02)

(ETELNET, EMODBUS, E61850, EGSE, ESNTP, EFTPSERV, ETCPKA, EDNP, and EPMIP only
apply to Ethernet ports [Port 1])

Communications Settings
Port 1 (Ethernet) Settings
Telnet Port One (23, 102565534)
TPORT

:=

TIDLE

:=

IPADDR

:=

SUBNETM

:=

DEFRTR

:=

Telnet Port One Idle Time (OFF, 130 min)

IP Address

Subnet Mask

Default Router

Table 0.2 defines the valid IP Address settings. The most significant byte (MSB) of the IP Address
determines the valid range of the setting. For example, if the IP Address MSB is 192, then valid IP
Addresses range from 192.0.1.1 to 192.255.254.254.
Table 0.2 Valid IP Addresses
Valid IP Address Range
IP Address MSB
From

To

1126

1.0.0.1

126.255.255.254

128191

128.1.0.1

191.255.255.254

192223

192.0.1.1

223.255.254.254

Keep-Alive Settings
The following settings are used if ETCPKA = Y.

TCP Keep-Alive Idle Range (120 s)


KAIDLE
SEL-735 Meter

Instruction Manual

:=
Date Code 20160628

SET.21 of 32

TCP Keep-Alive Interval Range (120 s)


KAINTV

:=

KACNT

:=

FTPUSER

:=

FTPCBAN

:=

FTPIDLE

:=

SNTPPSIP

:=

SNTPBSIP

:=

TCP Keep-Alive Count Range (120 messages)

FTP Settings
The following settings are used if EFTPSERV = Y.

FTP User Name

FTP Connect Banner

FTP Idle Timeout (5255 min)

SNTP Settings
The following settings are only used if ESNTP OFF.

Primary Server IP Address

Backup Server IP Address

(SNTPBSIP only available if ESNTP = UNICAST)

SNTP IP (Local) Port Number (165534)


SNTPPORT :=
SNTP Update Rate (153600 s)
SNTPRATE :=
SNTP Timeout (520 s)
SNTPTO

:=

(SNTPTO only available if ESNTP = UNICAST or MANYCAST)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.22 of 32

DNP Ethernet Session Settings


The following settings are only available on Port 1 and when EDNP > 0.

DNP TCP and UDP Port (165534)


DNPNUM

:=

DNPADR

:=

PMOTS1

:=

PMOIPA1

:=

PMOTCP1

:=

PMOUDP1

:=

PMOTS2

:=

PMOIPA2

:=

PMOTCP2

:=

PMOUDP2

:=

(DNPNUM applies to all Ethernet DNP sessions)

DNP Address (065519)

(DNPADR applies to all Ethernet DNP sessions)

PMU Session Settings


PMU Output 1 Transport Scheme (OFF, TCP, UDP_S, UDP_T,
UDP_U)

PMU Output 1 Client IP (Remote) Address (www.xxx.yyy.zzz)

PMU Output 1TCP/IP (Local) Port Number (165534)

PMU Output 1 UDP/IP Data (Remote) Port Number (165534)

PMU Output 2 Transport Scheme (OFF, TCP, UDP_S, UDP_T,


UDP_U)

PMU Output 2 Client IP (Remote) Address (www.xxx.yyy.zzz)

PMU Output 2 TCP/IP (Local) Port Number (165534)

PMU Output 2 UDP/IP Data(Remote) Port Number (165534)

Port F, Port 2, Port 3, Port 4 Settings


Communications Interface (232, 485, Modem)
SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.23 of 32

COMMINF :=
(COMMINF is only available on Port 4)

Protocol (SEL, MOD, DNP, LMD*, MBA*, MB8A*, MBB*,


MB8B*)
PROTO

:=

*Not available on Port F.


Protocol Settings:
Set PROTO = SEL for standard SEL ASCII protocol and MV-90 protocol.
Set PROTO = MOD for Modbus RTU Protocol. Refer to for details on Modbus protocol.
Set PROTO = DNP for Distributed Network Protocol (DNP). Refer to for details on DNP protocol.
Set PROTO = LMD for SEL Distributed Port Switch Protocol.
Set PROTO = MBA, MBB, MB8A, or MB8B for MIRRORED BITS protocol. Refer to for details.
SPEEDs 57600 and 115200 are not available on Port F.

Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400,


57600, 115200)
SPEED

:=

BITS

:=

PARITY

:=

STOP

:=

RTSCTS

:=

Data Bits (6, 7, 8)

Parity (O, E, N) {Odd, Even, None}

Stop Bits (1, 2)

Enable Hardware Handshaking (Y, N, MBT)

(RTSCTS not available on Port 1 (Ethernet), Port 4A (EIA-485), EIA-485 Port 3, or a port configured
for SEL Distributed Port Switch Protocol (LMD). With RTSCTS = Y, the meter will not send characters
until the CTS input is asserted. If the meter is unable to receive characters, it deasserts the RTS line.
RTSCTS = MBT is only available when SPEED = 9600. In this mode, the meter deasserts the RTS
line and does not monitor the CTS line. This selection is normally used with MIRRORED BITS
communications, PROTO = MBA or MBB. See for more detail.
Set RTSCTS = Y to enable hardware handshaking.)

Minutes to Port Time-out (030)


T_OUT

:=

(Set T_OUT = 0 for no port time out)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.24 of 32

Enable Port Power (Y, N)


EPP

:=

(Enable or disable Pin 1 +5 V power on EIA-232 Port 2 or Port 3. Port power is disabled by default.)

Send Auto Messages to Port (Y, N)


AUTO

:=

(AUTO only available if PROTO = SEL or LMD. Set AUTO = Y to allow automatic messages at the
serial port.)

Fast Operate Enable (Y, N)


FASTOP

:=

(FASTOP only available if PROTO = SEL or LMD.


Set FASTOP = Y to enable binary Fast Operate messages at the serial port. Set FASTOP = N to
block binary Fast Operate messages. Refer to for the description of the SEL-735 Fast Operate
commands.)

Sync. Phasor Transmission Data Set (V1, V, A)


PMDATA

:=

PMADDR

:=

PREFIX

:=

ADDR

:=

SETTLE

:=

(PMDATA only available if PROTO = SEL or LMD)

Address of Sync. Phasor Measurement Data (0xFFFFFFFFh)

(PMADDR only available if PROTO = SEL or LMD)

LMD Protocol Settings


The following settings are used if PROTO = LMD.

LMD Prefix (@, #, $, %, &)

LMD Address (199)

LMD Settling Time (0.0030.00 s)

Modem Settings
Modem Initialization AT String
ATSTRING :=
(ATSTRING is only available if COMMINF = MODEM)
SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.25 of 32

DNP Serial Settings


The following settings are only available on Port F, Port 2, Port 3, and Port 4.

DNP Address (065519)


DNPADR

:=

REPADR

:=

DNPMAP

:=

ECLASSB

:=

ECLASSC

:=

ECLASSA

:=

DECPLA

:=

DECPLV

:=

DECPLM

:=

DECPLE

:=

DNP Address to Report to (165519)

DNP Session Map (1, 2)

Event Data by Class


Class for Binary Event Data (03)

Class for Counter Event Data (03)

Class for Analog Event Data (03)

Scaling Decimal Places


Amps Scaling Decimal Places (06)

Voltages Scaling Decimal Places (06)

Misc Data Scaling Decimal Places (06)

Energy Counter Scaling Decimal Places (06)

Reporting Dead-band Counts


Amps Reporting Dead-band Counts (032767)

Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.26 of 32

ANADBA

:=

ANADBV

:=

ANADBM

:=

TIMERQ

:=

STIMEO

:=

ETIMEO

:=

DRETRY

:=

DTIMEO

:=

CZPCT

:=

UNSOL

:=

Volts Reporting Dead-band Counts (032767)

Misc Data Reporting Dead-band Counts (032767)

Timeouts
Minutes for Request Interval (I, M, 132767)

Seconds to Select/Operate Time-Out (0.030.0)

Event Message Confirm Timeout (150 s)

Data Link
Retries (015)

Seconds to Time-Out (05)

(DTIMEO only available if DRETRY > 0)

Class 0 Reporting
Class 0 Response Counter Object (20, 21, Both)

Unsolicited Messages
Enable Unsolicited Reporting (Y, N)

The following Unsolicited Message settings are only available if UNSOL = Y.

Enable Unsolicited Reporting at Power-Up (Y, N)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.27 of 32

PUNSOL

:=

NUMEVE

:=

AGEEVE

:=

URETRY

:=

UTIMEO

:=

MINDLY

:=

MAXDLY

:=

PREDLY

:=

PSTDLY

:=

Number of Events to Transmit On (1200)

Oldest Event to Transmit On (099999 s)

Unsolicited Message Max Retry Attempts (210)

Unsolicited Message Offline Timeout (15000 s)

Serial Control Lines


Minimum Seconds from DCD to TX (0.001.00)

Maximum Seconds from DCD to TX (0.001.00)

Settle Time from RTS On to TX (OFF, 0.0030.00 s)

Settle Time from TX to RTS OFF (0.0030.00 s)

DNP Ethernet Session n


Replace n with the DNP session number 25. If n is omitted, then the setting applies to DNP
Session 1.

DNP IP Network
DNP Session Map (1, 2)
DNPMAP[n] :=
Transport Protocol (UDP, TCP)
DNPTR[n]

:=

Master IP Address (zzz.yyy.xxx.www)


Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.28 of 32

DNPIP[n]

:=

UDP Response Port (REQ, 165534)


DNPUDP[n] :=
DNP Address to Report To (165519)
REPADR[n] :=

Event Data by Class


Class for Binary Event Data (03)
ECLASSB[n] :=
Class for Counter Event Data (03)
ECLASSC[n] :=
Class for Analog Event Data (03)
ECLASSA[n] :=

Scaling Decimal Places


Amps Scaling Decimal Places (06)
DECPLA[n] :=
Voltages Scaling Decimal Places (06)
DECPLV[n] :=
Misc Data Scaling Decimal Places (06)
DECPLM[n] :=
Energy Counter Scaling Decimal Places (06)
DECPLE[n] :=

Reporting Dead-band Counts


Amps Reporting Dead-band Counts (032767)
ANADBA[n] :=
Volts Reporting Dead-band Counts (032767)

SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.29 of 32

ANADBV[n] :=
Misc Data Reporting Dead-band Counts (032767)
ANADBM[n] :=

Timeouts
Minutes for Request Interval (I, M, 132767)
TIMERQ[n] :=
Seconds to Select/Operate Time-Out (0.030)
STIMEO[n] :=
Event Message Confirm Timeout (150 s)
ETIMEO[n] :=

Data Link
Seconds to Send Data Link Heartbeat (07200)
DNPINA[n] :=

Class 0 Reporting
Class 0 Response Counter Object (20, 21, Both)
CZPCT[n]

:=

UNSOL[n]

:=

Unsolicited Messages
Enable Unsolicited Reporting (Y, N)

The following Unsolicited Message settings are only available if UNSOL = Y.

Enable Unsolicited Reporting at Power-Up (Y, N)


PUNSOL[n] :=
Number of Events to Transmit On (1200)
NUMEVE[n] :=
Oldest Event to Transmit On (099999 s)
AGEEVE[n] :=
Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.30 of 32

Unsolicited Message Max Retry Attempts (210)


URETRY[n] :=
Unsolicited Message Offline Timeout (15000 s)
UTIMEO[n] :=

DNP Map Settings


DNP Map n
Replace n with the DNP map number 1 or 2.

Binary Input n
BI_MAPn

:=

BO_MAPn

:=

AI_MAPn

:=

AO_MAPn

:=

CO_MAPn

:=

FMR1

:=

FMR2

:=

FMR3

:=

FMR4

:=

Binary Output n

Analog Input n

Analog Output n

Counter Input n

Fast Messages
Enable Energy Message (Y, N)

Enable 4Quadrant Demand Message (Y, N)

Enable 4Quadrant Peak Demand Message (Y, N)

Enable 4Quadrant Meter Message (Y, N)

Uncompensated Quantities in Fast Message (Y, N)


SEL-735 Meter

Instruction Manual

Date Code 20160628

SET.31 of 32

FMQ_UC

:=

Modem Settings
The following settings are only available when COMMINF = MODEM.

Dial Out When a New Event Is Recorded (Y, N)


DIALOUT

:=

(DIALOUT only available on Modem ports and PROTO = SEL)

Event Notification String (30 chars max.)


EVE_STR

:=

ID_CMD

:=

CONN_ID

:=

(EVESTR only available on Modem port and DIALOUT = Y)

ID Command String (20 chars max.)

(ID_CMD only available on Modem port and DIALOUT = Y)

Connection ID String (20 chars max.)

(CONN_ID only available on Modem ports and DIALOUT = Y)

Modem Connected to Port (Y, N)


MODEM

:=

(MODEM only available when PROTO = DNP and


COMMINF = 232 or the physical port is an EIA-232 port)

Modem Initialization at String (30 chars max.)


ATSTRING :=
(ATSTRING only available on Modem port)

Modem Startup String (30 chars max.)


MSTR

:=

PH_NUM

:=

MDTIME

:=

Phone Number for Dial-Out (30 chars max.)

Time to Attempt Dial (5300 s)

Time Between Dial-Out Attempts (53600 s)


Date Code 20160628

Instruction Manual

SEL-735 Meter

SET.32 of 32

MDRET

:=

(MSTR, PH_NUM, MDTIME, and MDRET are only available on EIA-232 serial ports and MODEM = Y
with PROTO = DNP; or PROTO = SEL with DIALOUT = Y. Additionally, MSTR is not available on Port
4.)

Modbus Protocol Settings


Modbus Slave ID (1247)
SLAVEID

:=

(SLAVEID is only available when PROTO = MOD)


: SEL Communications Processors
Appendix C
: MIRRORED BITS Communications
Appendix F
: MIRRORED BITS Communications
Appendix F
: Distributed Network Protocol
Appendix D
: Modbus Communications Protocol
Appendix E
6.5
Sequential Events Recorder (SER) Report
3.5
Four User-Configurable Pushbuttons and LEDs

SEL-735 Meter

Instruction Manual