(SINGLE DWELLING)
A. LIGHTING LOAD
1- 15 mm Rigid PVC
Conduit
1- 15 AT, 2-P, 230V, ITCB
Total loads
220 Volts
1100 VA
220 Volts
B. SMALL APPLIANCE
LOAD AND
CONVENIENCE OUTLET
BRANCH CIRCUIT NO. 3
= 5 Amperes
Use:
2- 2.0 mm2 THWN Cu
wire, 75C, 20A (5A/20A)
1- 15 mm Rigid PVC
Conduit
1- 15 AT, 2-P, 230V, ITCB
BRANCH CIRCUIT NO. 2
No. of outlet/receptacle = 12
Rated @ 100 VA, 220 Volts
Total loads = No. of outlet x100
VA
= 12 x 100 VA
= 1200 VA
IBC =
Total loads
220 Volts
1200VA
220 Volts
No. of outlet/receptacle = 9
Rated @ 200 VA, 220 Volts
Total loads = No. of outlet x200
VA
= 9 x 200 VA
= 1800 VA
IBC =
Total loads
220 Volts
1800VA
220 Volts
= 8.18 Amperes
Use:
2- 3.5 mm2 THWN Cu
wire, 75C, 20 A
(8.18A/25A)
1- 20 mm Rigid PVC
Conduit
1- 20 AT, 2-P, 230V, ITCB
BRANCH CIRCUIT NO. 4
= 5.45 Amperes
Use:
2- 2.0 mm2 THWN Cu
wire, 75C, 20A
(5.45A/20A)
No. of outlet/receptacle = 9
Rated @ 200 VA, 220 Volts
Total loads = No. of outlet x200
VA
= 7 x 200 VA
= 1400 VA
IBC =
Total loads
220 Volts
75C (Neutral)
30 AT, 2-P, 230V, ITCB
1800VA
220 Volts
Air-conditioning unit
Circuit
= 8.18 Amperes
Use:
2- 3.5 mm2 THWN Cu
wire, 75C, 20 A
(8.18A/25A)
1- 20 mm Rigid PVC
Conduit
1- 20 AT, 2-P, 230V, ITCB
FL
= 1.25 x 10 A
= 12.5 A
Over Protective Device
IOPD = 250% (IFL)
= 2.5 (10A)
= 25 A
Use:
2- 3.5 mm2 THWN Cu
wire, 75C, 25 A
(12.5A/25A)
1- 2.0 mm2 THWN Cu
wire,
FL
= 1.25 x 8 A
= 10 A
Over Protective Device
IOPD = 250% (IFL)
= 2.5 (8A)
= 20 A
Use:
Total loads
220 Volts
IBC =
1.25 x I
FL
= 1.25 x 10 A
= 12.5 A
Over Protective Device
IOPD = 250% (IFL)
= 2.5 (10A)
= 25 A
Use:
2- 3.5 mm2 THWN Cu
wire, 75C, 25 A
(12.5A/25A)
4- 2.0 mm2 THWN Cu
wire,
75C (Neutral)
30 AT, 2-P, 230V, ITCB
12000 VA
230 Volts
= 52.2 A
Use demand factor of
80%
= 0.8 x 52.2
=41.76 A
Use:
2- 8.0 mm2 THWN Cu
wire, 75C, 35 A
(41.76/50A)
1- 2.0 mm2 THWN Cu
wire,
75C (Neutral)
50 AT, 2-P, 230V, ITCB
BRANCH CIRCUIT NO. 10
BRANCH CIRCUIT NO. 9
WATER HEATER
No. of outlet = 1
Rated @ 5000 VA, 230 Volts
Total loads = 1 x 5000 VA
= 5000 VA
IBC =
Total loads
220 Volts
5000VA
220 Volts
= 22.7 Amperes
Use:
2- 3.5 mm2 THWN Cu
wire, 75C, 20 A
(22.7A/25A)
1- 20 mm Rigid PVC
Conduit
1- 20 AT, 2-P, 230V, ITCB
SAMPLE COMPUTATION
SERVICE ENTRANCE COMPUTATION
AND MAIN DISCONNECTING MEANS:
A. Lighting Load................3300 Watts
B. Small Appliance Load...................3600 Watts
C. Other Loads(Laundry and Range)..........14605
Watts
Total Load except Motor Loads such as ACU.....21,505
Watts
First 3000 VA at 100% Demand Factor...........3000
Watts
21,505 W 3,000 W = 18,505 Watts at 35%
D.F..6476.75 Watts
1 ACU at 12 A x 230 V = 2,760 W x 100% D.F.2760
Watts
Total Connected Load.
12236.75 Watts
12236.75+25 (2,760)
=56.2 Amperes
230
1. All electrical works herein shall be done in accordance w/ the standards and
provisions of the Philippine Electrical Code (PEC).
2. All electrical works herein shall be in direct supervision of a duty licensed
electrical engineer or registered master electrician.
3. The minimum size of wire for lighting loads shall be 2.0mm2 THW Copper
Wire and 3.5mm2 THWN Copper Wire for small appliance loads.
4. All circuit homerun shall be used herein shall be PVC conduit pipes and RMC
for service entrance.
5. All motor loads shall be in separate branch circuit.
6. All lighting fixtures shall be in a semi-indirect lighting system except pin
lights.
7. All pin lights to be used shall be of LED-Type Bulb, 5W, 220V, FIREFLY.
8. All pin lights shall use a smoke glass cover as a diffuser.
9. The wiring method will be conduit wiring in PVC for all circuit homeruns and
conduit wiring in RMC for the service entrance.
10. The minimum size of wire for the main feeder and neutral conductor shall be
22.0mm2 THWN Copper Wire and 14.0mm2 THWN Copper Wire,
respectively.
THE SITE