You are on page 1of 52

LS Air-Conditioning System

The air-conditioning system of LS will be responsible for pleasant


air-conditioning for four seasons, cooler in summer and warmer in winter.
With various air-conditioning systems, from centrifugal chiller for district
cooling plants to individual air-conditiong and heating system.
LS is leading the industry and comercial business of air-conditioning system.

YOUR NO.1 CREATIVE PARTNER!


LS proclaimed a new vision for the company to be
"Your No. 1 Creative Partner" and started facing a new
challenge on Sept. 1st, 2004.
Being 'Your No.1 Creative Partner' means that LS will meet customer needs by customers with the best services in an original
method that no one can imitate. It will allow customers to fulfill their
dreams and ideals in creating a partnership with them.
The new vision of LS represents its resolution to achieve the challenging and future-oriented goal of becoming a first class company
for its customers by adapting to the current business environment.
To fulfill this vision, LS Cable deemed 'Integrity','Openness', 'Logical
Stretching', 'Consistent Innovation' and 'Fairness' as its most basic
and important values and has selected these to be the core value of
LS. Based on these core value, LS will ensure Market Intelligence,
Technology, and Creative Implementation, which are its main capabilities

Head office

Factory

LS Absorption Chiller

With over 50% domestic market share, LS cable has provided heating, ventilating and air conditioning total
solution to industrial and commercial fields over 30 years. Now the company, specialized in absorption,
centrifugal & GHP, now wants to share its leading technology with the global friends.
The LS Absorption Chillers have always been nations No.1 energy saving chillers, since the company has
considered R&D as frontier mover of all.
Features of LS Absorption Chillers
where cooling/heating demands are all year around by using diversified energy sources as Gas, Steam and
Beneficial
Hot water.
operation cost in where electrical costs are high.
Reduces
Utilizing
environmental
safe, non chlorine mixture based refrigerant.
Reduces green house effect
by less using hydrocarbon fuels as well as electricity.

Model Naming

D F

- S

0 3 2

LS Absorption Chiller

Fuel Sources (DF type only)

Model TYPE

G : GAS(LNG)
K : Kerosene
D : Dual

DF : Direct Fired
SH, SM, SL : Steam Fired
(High, Medium, Low Pressure Range; 1~8kgf/cm2)
WM : Hot Water Fired

Nominal Cooling Capacity


Indicated by 10usRT units
Ex) 150usRT=015

Rank-Up (Heating)
S : Standard
1 Stage Rank-up : A
2 Stage Rank-up : B

Type Series
R : R-TYPE

Double-Effect
Direct-Fired Absorption Chiller

LS Absorption Chiller

W : W-TYPE

Double-Effect
Steam-Fired Absorption Chiller

Single-Effect
Hot-Water Fired Absorption Chiller

Absorption Cycle
Single Effect Cycle

Condenser

Generator

Evaoorator

Absorber

Cooling water flows through the Absorber to the


Condenser. The cooling water in the Condenser cools
down the refrigerant vapor from the the Generator back
into refrigerant. The cooling water in the Absorber absorbs
the heat when the refrigerant vapor is absorbed by the
absorbent.
The Generator
heat the diluted solution by driving heat
source. The diluted solution releases the refrigerant vapor
and becomes the concentrated solution.
At the Condenser, the refrigerant vapor which came from
the Generator condensed by cooling water.
The condensed refrigerant drops on the heat transfer
tubes of evaporator
drops of the refrigerant evaporate
on the tubes. The water through the heat transfer tubes of
evaporator is cooled by the latent heat of vaporized refrigerant.
The refrigerant vapor is absorbed on the heat transfer
tubes
by absorbent from the Generator. The absorbent
diluted by refrigerant vapor goes to the Generator.

Double Effect Cycle

Condenser

Generator

Absorber
Evaoorator

In case of the Single Effect Type Absorption Machine, all


condensation heat when the refrigerant vapor coming from
Generator is cooled and condensed at the Condenser, is
released in the cooling water.
The Double Effect Type Absorption Machine is used the
condensation heat efficiency. The Generator section is
divided into a High Temperature Generator and a Low
Temperature Generator. The refrigerant vapor produced by
the High Temperature generator is used to heat the LiBr
solution in the Low Temperature Generator in which the
pressure(hence the boiling point) is lower.
As mentioned in the Single Effect Type Machine, the refrigerant vapor produced by the Low Temperature Generator is
sent to the Condenser to become liquid refrigerant. On the
other hand, the refrigerant vapor produced by the High
Temperature Generator turns to water as it released heat to
the intermediate LiBr solution. This occurs inside the heat
transfer tubes in the Low Temperature Generator. The
refrigerant vapor produced by both Low and High temperature Generator turn to liquid refrigerant and mixed in the
Condenser before returning to the Evaporator.
In this step, the diluted solution is heated by driving heat
source and by the latent heat in the refrigerant vapor which
otherwise would be released into the cooling water. This
combination means a lower energy consumption of driving
heat source. Moreover, less heat being discarded into the
cooling water translates into a small cooling water. As
shown above.

45

Features of LS Absorption Chiller

Reinforced User Interface Design is enabled through our


Over 30 years experience with successful 10000 unit delivery, LS Absorption chiller has born with focusing on user
interface and reliable convenient operations that to considered as a first step of total HVAC solution.

1. High Efficiency & High Energy Saving


Operation
Inverter Controlled Solution pump enabled
High Part-Load Efficiency with Fast
Full-Loaded Operation

Cooling Capacity(%)

Main Features of LS Absorption Chiller


LSs New PID Control
100

Conventional Control

flow rate of solution is decided upon cooling


Optimized
demand and that to enable highly efficient energy saving

50

operation at all operation range.

time

Reinforced Safety Operation Function

abnormal operation. The machine can stop automatically by reinforced safety function even when the chiller
operation reached at abnormal state.

ON-OFF Control

LNG GAS Consumption (N m3/h.RT)

unique microprocessor keeps monitoring every part


LS's
of chiller so to prevent any damage could happen at

0.30
0.25

P Control
0.20

0.15

LSs New PID Control

0.10

20

40

60

80

100

Cooling Load

Optimized Dilution Operation shortened


Stoppage Time
newly designed Microprocessor decides when to
LS's
equalize concentration of solution in every part of chiller
by self diagnostic calculations. Also this led to saving
dilution operation as well as energy saving at auxiliary
equipments, such as water pumps by reducing idle time
from 15 min to 5 min.

Combustion

Refrigerant
Pump
Cooling
Water Pump
Absorbent
Pump No.1
Absorbent
Pump No.2
1min

1min
4min

Stop Signal
Combustion

LS Absorption Chiller

T2
Completed
when the Temp. of
High Temp. Generator
reaches 120C

Shut Down

2. High Reliability & Practical Design


High Corrosion Resistance Designed HTG
to new HTG design with smoke type tube and
Due
enlarged heat transfer surface, corrosion on partial high
temperature zone at HTG is relieved and the increased
heat flux fabricated additional efficiency factor which led
to energy saving. Also compact design allowed minimized number of connection joint which made machine
with higher durability and reliability.

High Performance of Purging System


designed injector typed, purging either at upper
Newly
shell and lower shell, a new LS purging system, enabled
less purging time and better purging performance.

Marine Hatch Type Water Box


need to cut or dissemble for tube cleaning or mainte No
nance purposes, marine hatch typed water box allows
an operator to clean tubes in less time.

Refrigerant Re-Cycling Circuit


non evaporized refrigerant that is accumulated at the
Abottom,
is once again pumped to upper shell for a storage in case of sudden cooling demand which can cause
dry out in evaporator. Thanks to recycling refrigerant, a
cooling water can be lowered as 19C.
this circuit can supply refrigerant from refrigerant
Also
tank to evaporator when refrigerant is lacked in evaporator at part load and let the chiller run at low cooling water
temperature condition.

67

Outstanding Performance Features

3. High Performance Controller


Delicate Designed with PID Control Logic, a new Micro Processor enables LS Chiller be always at
optimum operation state

User Set Menu

Graph Display

Language Selection

Service Menu

A new Quick Response PID Control Logic


quick response, new LS designed PID algorithm
Aenabled
high sensitive combustion control rate that to
meet minimized reaching time of demand temperature.
It also reduced the fluctuating temperature difference
so that to enable constant temperature control logic.

temp.(C)
9
8
Set Value 7
6
5

Load

LSs New
PID Control

Conventional Control
(P Control)

Load Variation

60%

90%
time

LS Absorption Chiller

Self Diagonistic Safety Operation


) Anti-Crystallization Safety Operation
concentration is monitored at micro processor
Ain solution
all operational condition and keeps concentration level
in optimum state by controlling a combustion rate.

) Self Diagnostics / Mal function Alarm feature


factor predicted while normal opera Iftion,anyadisturbing
chiller tests itself and determines whether it has
to turn into safe mode operation or to stop.

<Maintenance purpose>

) A Safety Operation Feature against Cooling


Water temperature
stable operation, entering cooling water can be
For
reset based on remote temperature range of 19~34C
as well as responding its temperature at the micro
processor by controlling combustion rate.

) Operation Data Storage/Maintenance Feature

Chamber Cleaning: by monitoring exhaust gas


temperature, operators can predict right time of cleaning
a combustion channel of HTG.

<Malfunction alarm feature>


Monitoring all sensors, of their conditions like
temperatures and pressure state so that if any abnormal
sign occurs it shows abnormal reason on the display for
easy operation.

20 years normal operation history data record


301 abnormal message history data record
10.6 day temperature sensing data record
Based on all stored data, more accurate operational
maintenance is capable.

89

Outstanding
Features
OutstandingPerformance
Performance

Enhanced user interface designed Micro processor


) Operation State Display

) Annex System Control

Operation state is displayed either in text or as graph


so to enable better understanding

) Printer(Option)

Pumps and cooling fan are in control with micro


processor for automated operation

) Schedule Operation

Stored operation normal/abnormal/ alarm history data


can be printed out from mounted printer

Schedule operation can be done in days or at the


desired any time

) Flow Rate Indication(Option)


A flow rate of chilled/ cooling water flow rate can be
indicated on the display. For this operation an
additional transducer should be applied on
chilled/cooling water pipe line.

VOLTAGE
COOLING
RUN
HEATING
STOP
INLET TEMP.
CHW/HW
OUTLET TEMP.
CHW/HW
INLET TEMP.
CW
TEMP.
H.GEN
L.GEN TEMP.

READING
CONDENSING TEMP.
VALUE
(LCD DISPLAY) REMOTE SET TEMP.
V/V OPEN(%)
CONTROL
CONCENTRATION
LIBR
INVERTER(HZ)
PID VALUE
STATUS
DISPLAY
(LED DISPLAY)

OPERATION
TIME
(LCD DISPLAY)

NO. OF
RUN/STOP
(LCD DISPLAY)

SETTING
VALUE

TIME
RUNNING
TIME
COMBUSTION
PUMP RUN TIME
REF.
PUMP #1 RUN TIME
ABS
ABS PUMP #2 RUN TIME
RUN/STOP
CHILLER
COMBUSTION
RUN/STOP
ABS PUMP #1 RUN/STOP
ABS PUMP #2 RUN/STOP

READING
VALUE
(LCD DISPLAY)

INLET TEMP.
CHW/HW
OUTLET TEMP.
CHW/HW
TEMP.
CW
VALUE
PI VALUE
D CALUE

SIGNAL
COMBUSTION
CHAMBER PRESSURE
PURGE
LEVEL LOW
H.RUNGENMODE
CONTROL V/V MODE
ABS PUMP #1 TH. RELAY
ABS PUMP #2 TH. RELAY
CHW/HW PUMP INTERLOCK
CW PUMP INTERLOCK
H. GEN PRESSURE
CHW FLOW RATE
CW FLOW RATE
ABS PUMP #1 M. CONTACTOR
ABS PUMP #2 M. CONTACTOR
PURGE PUMP M. CONTACTOR

Group Unit System Control for Intelligent Buildings and huge Factories
LS Remote Monitoring & Control System allow operators to check and control LS Chiller family remotely via Internet or
direct connection

) Communication protocol for Building Automation and Remote monitoring control


accessible to user's interface
Easily
RS232c/RS485
processor installed
BACnet, MODbus,communication
TCP/IP
Modem,
Modem are available as an option
Operational data acquisition
Graphical display of monitoring & control status
Data editing and Report generation with MS EXCEL
Real-time graphical display of trend data
Various graphic display for analog data
Password protected

LS Absorption Chiller

SYSTEM CONFIGURATION

) Optimized Operation

Integrated System Management

Integrated control of Chillers and


Peripheral Equipment which are connected to
LS controller

TCP/IP

Preventative Maintenance

Log data management


: Daily report generation of operation data,
abnormal data and etc.

Serial to LAN
Converter

Operational Cost Saving


Auxiliary Function

RS-485 Multi-Drop

Cost saving through centralized monitoring

Control of peripheral equipment, load control

Protocol
Converter
RS-485 Multi-Drop

RS485 to RS232c
Converter
RS-485 Multi-Drop

Main Control Screen

System P&ID

Chiller P&ID

10 11

Double-Effect Direct-Fired Absorption Chiller

Standard Specifications
MODEL
Nominal Cooling Capacity
Nominal Heating Capacity
Temperature
Chilled(Hot)
Water Flow Rate
Water
Pressure Drop
Data
Connection Size
Temperature
Cooling
Water Flow Rate
Water
Pressure Drop
Data
Connection Size
Source

UNIT

Total Electric Current


Gas Wire Size
Electric Consumption
Total Electric Current
Oil Wire Size
Electric Consumption
Electrical
Absorbent Pump No.1
Data
Absorbent Pump No.2
Refrigerant Pump
Purge Pump
Burner Blower(Gas)
Burner Blower(Oil)
Oil Pump(Oil)
Length(L)
Dimension Width(W)
Height(H)
Operating
Weight Rigging
Shipment
B(inch)
Nozzle Size
Fuel
Gas
11,000kcal/Nm3(Cooling/Heating) Nm3/h
B(inch)
Nozzle size
Oil
Diesel(Cooling/Heating) kg/h
mm
Flue Connection Size
mm
Clearance for Tube Removal
Note

LDF-S010S LDF-S012S LDF-S015S LDF-S018S LDF-S021S LDF-S024S LDF-S028S LDF-S032S LDF-S036S LDF-S040S

USRT
100
120
M cal/h
253
304
C
60.5
72.6
m3/h
mAq
6.5
6.6
B(inch)
4
C
m3/h
100
120
mAq
3.9
4.4
B(inch)
5
,V,Hz
A
11.83
mm3
kVA
7.3
A
12.63
mm3
kVA
7.7
kW(A)
kW(A)
kW(A)
kW(A)
kW(A) 0.75(2.2)
kW(A) 0.75(2.2)
kW(A) 0.24(0.8)
mm
2,700
mm
1,990
mm
ton
4.8
5.1
ton
4.0
4.2

150
380

180
210
240
280
320
360
400
455
531
607
708
810
911
1,012
Cooling12 7C (Heating 55.8 60C)
90.7
108.9
127.0
145.2
169.3
193.5
217.7
241.9
8.0
8.3
7.5
7.9
5.1
5.5
5.8
6.1
5
6
32 37.5C
150
180
210
240
280
320
360
400
6.5
7.7
5.6
6.2
10.9
12.1
8.7
9.4
6
8
3, 220/380/440V, 50~60Hz
15.63
14.23
19.72
27.32
5.5
3.5
7.7
8.6
11.9
13.9
17.43
29.12
16.03
21.52
3.5
8.0
5.5
9.7
15.1
17.2
2.4(6.4)
3.4(10.2)
n/a
0.4(1.42)
0.2(1.13)
0.4(1.6)
1.5(4.6)
2.2(6.0)
5.5(13.6)
2.2(6.0)
1.5(4.6)
5.5(13.6)
0.55(1.8)
3,720
3,740
3,780
3,890
2,010
2,190
2,210
2,310
2,350
2,170
2,540
2,030
6.1
6.7
7.9
8.2
9.2
9.8
12.3
12.7
5.1
5.6
6.4
7.6
8.1
8.7
10.8
11.1
One-Section
1 1/2
2
27.3
32.8
41.0
49.1
57.3
65.5
76.4
87.4
98.3
109.2
15
27.4
32.9
41.1
49.3
57.5
65.8
76.7
87.7
98.6
109.6
280x210
310x310
360x310
2,400
3,400
4,500

1. 1 usRT =3.52kW(3,024kcal/h) 2. Standard Tube and Water Side Pressure(Chilled & Cooled Water Circuit ): 8kgf/cm2 (785kPa) 3. Standard gas pressure : 4,000mmAq
4. Currents & Electricity Consumptions are based on 3Ph/380V/50Hz 5. Power supply wire size is based on the due of metal conduit and 40C of ambient temperature.
6. The specifications are subject to change without prior notice.

LS Absorption Chiller

LDF-S Series [100~1,500USRT]

Low Temp
Generator

Condenser

Refrigerant
Vapur
Exhaust Gas

Cooling Water
Outlet

Fusible Plug

Intermediate
Solution

Cooling Water

Concentrated
Solution
High Temp
Generator

Chilled
Water
Outlet

Cycle of
Double-Effect
Direct-Fired
Chiller

Chilled
Water

Evaporator

Abosorber

Diluted
Solution

Purge
Unit

H 2O
LI BR+H2O

Purge valve

Burner

Chilled
Water
Inlet

Damper
Fuel
Control
Valve

PB

Blower

Vacuum Pump

Controller
Refrigerant

Refrigerant
Pump

Absorbent
Pump

Low Temp.
Heat Exchanger

High Temp.
Heat Exchanger

Cooling Water
Inlet

LDF-S045S LDF-S050S LDF-S056S LDF-S063S LDF-S070S LDF-S080S LDF-S090S LDF-S100S LDF-S110S LDF-S120S LDF-S130S LDF-S140S LDF-S150S
450
1,139

500
1,265

560
1,417

630
1,594

700
1,771

800
900
1,000
1,100
1,200
1,300
2,024
2,277
2,530
2,783
3,036
3,289
Cooling12 7C (Heating 55.8 60C)
272.2
302.4
339.0
381.0
423.0
484.0
544.0
605.0
665.0
726.0
786.0
5.2
5.5
4.6
6.2
8.1
4.7
6.4
8.4
6.2
7.9
9.8
8
10
12
32 37.5C
450
500
560
630
700
800
900
1,000
1,100
1,200
1,300
10.3
11.2
7.1
9.4
12.1
8.4
11.1
14.3
8.8
10.9
13.4
10
14
16
3, 220/380/440V, 50~60Hz
27.32
41.82
40.62
49.62
40.42
57.32
69.4
5.5
22.0
38.0
14.0
33.4
13.9
24.4
27.2
49.4
29.12
46.42
42.22
45.22
54.22
61.92
74
8.0
14.0
22.0
38.0
25.5
36.0
17.2
17.2
27.6
30.1
52.0
3.4(10.2)
6.6(16.2)
7.5(25.0)
n/a
2.0(6.8)
2.2(5.8)
5.5(14.5)
0.4(1.42)
1.5(4.0)
0.4(1.6)
0.75(2.4)
7.5(15.0)
11(22.7)
11.0(22.7)
5.5(13.6)
11(22.7)
11.0(22.7)
7.5(15.0)
5.5(13.6)
1.1(4.6)
0.55(1.8)
4,870
5,060
6,100
5,740
6,240
6,760
6,170
6,690
7,190
2,570
3,080
3,400
4,180
2,765
3,600
3,255
15.2
15.6
21.8
23.5
25.3
33.5
36.1
38.9
44.3
47.6
50.6
13.3
13.4
19.1
20.6
22.1
29.4
31.8
34.3
39.8
42.8
45.5
One-Section
Multi-Sectional-Shipment
2
2 1/2
122.9
136.5
153
172
191
218
245
273
300
327
355
15
25
20
123.3
137
154
173
192
219
246
273
301
328
356
410x310
500x350
620x400
900x400
4,500
4,600
5,200
5,700
5,200
5,700
6,200
5,700
6,200
6,700

1,400
3,542

1,500
3,795

847.0
8.0

907.0
9.8
14

1,400
12.3

1,500
14.6

6,850

7,350
4,590
3,800

55.5
50.0

58.5
52.6

382

409

383

411
6,200

12 13

Double-Effect Direct-Fired Absorption Chiller


Dimension
Outline (LDF- 010S~S100S)

NOTE
1. ALL WATER PIPING CONNECTIONS ARE WELDED ANSI 150
PSIG RF FLANGES.
2. INSTALLATION AND SERVICE CLEARANCE AS FOLLOWS :
LONGITUDINAL DISTANCE - 1000mm
TOP - 200mm
OTHERS - 500mm

30
R6

(W)

(L)

(H)

MICOM

B
A

D*

C*

B*

A*

Length(L)

Dimension(mm)
Depth(W)

Height(H)

Connection Size(inch)
C

G(mm)

LDF-S010S

2700

1990

2030

5*

5*

2400

LDF-S012S

2700

1990

2030

5*

5*

2400

LDF-S015S

3720

1990

2030

4*

5*

3400

LDF-S018S

3720

2010

2030

4*

5*

3400

LDF-S021S

3740

2190

2300

5*

6*

3400

LDF-S024S

3740

2210

2300

5*

6*

3400

LDF-S028S

4780

2170

2300

8*

4500

LDF-S032S

4780

2170

2300

8*

4500

LDF-S036S

4890

2310

2540

8*

4500

LDF-S040S

4890

2350

2540

8*

4500

LDF-S045S

4870

2570

2765

10

10*

4500

LDF-S050S

4870

2570

2765

10

10*

4500

LDF-S056S

5060

3080

3255

12*

12

4600

LDF-S063S

5600

3080

3255

12*

12

5200

LDF-S070S

6100

3080

3255

12*

12

5700

LDF-S080S

5740

3400

3600

14*

10

10

14

5200

LDF-S090S

6240

3400

3600

14*

10

10

14

5700

LDF-S100S

6760

3400

3600

14*

10

10

14

6200

Model

A : Cooling water inlet

LS Absorption Chiller

B : Chilled water inlet

C : Chilled water outlet

D : Cooling water outlet

G : Space for tube removal

LDF-S Series [100~1,500USRT]

Outline (LDF-S110S~S150S)
R630

NOTE
1. ALL WATER PIPING CONNECTIONS ARE WELDED ANSI 150
PSIG RF FLANGES.
2. INSTALLATION AND SERVICE CLEARANCE AS FOLLOWS:
LONGITUDINAL DISTANCE - 1000mm TOP - 200mm
CONTROL PANEL SIDE - 1200mm OTHERS - 500mm

(W)

(L)

D*

C*

B*

A*

(H)

(G)

Length(L)

Dimension(mm)
Depth(W)

Height(H)

Connection Size(inch)
C

G(mm)

LDF-S110S

6170

4180

3600

16

12

12

16

5700

LDF-S120S

6690

4180

3600

16

12

12

16

6200

LDF-S130S

7190

4180

3600

16

12

12

16

6700

LDF-S140S

6850

4590

3800

16

14

14

16

6200

7350

4590

3800

14

14

16

6200

Model

LDF-S150S
A : Cooling water inlet

B : Chilled water inlet

C : Chilled water outlet

16
D : Cooling water outlet

G : Space for tube removal

14 15

Double-Effect Direct-Fired Absorption Chiller


Foundation
NOTE

C
D

1.

V (ton)

U (ton)

100(50)

HEIGHT
200~250

HEIGHT
200~250

100(50)

100(50)

100(50)

INDICATES THE POSITON OF ANCHOR BOLTS.

2. THE FOUNDATION AND THE FLOOR MUST BE SUFFICIENTLY


STRONG TO SUPPORT THE UNIT WEIGHT.
3. PROVIDE A FLOOR DRAIN NEAR CHILLER FOUNDATION.
4. ONLY IF FOUNDATION ANCHORING IS REQUIRED, ANCHOR BOLTS,
NUTS AND WASHERS, SHALL BE SUPPLIED TOGETHER WITH CHILLER.
ANCHOR BOLTS MUST BE FIXED ON THE FOUNDATION PRIOR TO
CHILLER INSTALLATION
5. UNIT MUST BE LEVELED BEFORE STARTUP.
(HORIZONTAL LEVEL MUST BE BELOW THAN 2mm/1000mm)
6. DIMENSIONS IN ( ) FOR LDF-S080S~LDF-S150S.

SECTION B-B

SECTION A-A

NUT
WELD

WASHER
BASE PLATE

W (ton)

X (ton)

BASE CONTACT

Model
LDF-S010S
LDF-S012S
LDF-S015S
LDF-S018S
LDF-S021S
LDF-S024S
LDF-S028S
LDF-S032S
LDF-S036S
LDF-S040S
LDF-S045S
LDF-S050S
LDF-S056S
LDF-S063S
LDF-S070S
LDF-S080S
LDF-S090S
LDF-S100S
LDF-S110S
LDF-S120S
LDF-S130S
LDF-S140S
LDF-S150S
Model
LDF-S010S
LDF-S012S
LDF-S015S
LDF-S018S
LDF-S021S
LDF-S024S
LDF-S028S
LDF-S032S
LDF-S036S
LDF-S040S
LDF-S045S
LDF-S050S
LDF-S056S
LDF-S063S
LDF-S070S
LDF-S080S
LDF-S090S
LDF-S100S
LDF-S110S
LDF-S120S
LDF-S130S
LDF-S140S
LDF-S150S
Note.

A
170
170
170
170
185
185
185
185
210
210
210
210
235
235
235
210
210
210
210
210
210
210
210

B
175
175
175
175
185
185
185
185
210
210
210
210
235
235
235
210
210
210
210
210
210
210
210

C
1926
1926
2946
2946
2916
2916
3936
3936
3886
3886
3886
3886
3836
4378
4876
4328
4826
5350
4426
4950
5450
4950
5450

D
175
175
175
175
185
185
185
185
210
210
210
210
235
235
235
210
210
210
210
210
210
210
210

M
170
170
170
170
185
185
185
185
210
210
210
210
200
200
200
200
200
200
200
200
200
200
200

N
160
160
160
160
185
185
185
185
210
210
210
210
200
200
200
200
200
200
200
200
200
200
200

O
170
170
170
170
185
185
185
185
210
210
210
210
200
200
200
200
200
200
200
200
200
200
200

Dimension(mm)
P
Q
425
880
425
1080
657
1130
657
1330
668
1350
669
1550
1102
1850
1102
2050
1115
1750
718
1950
830
2050
830
2250
1165
2000
1165
2250
1165
2450
1328
2400
1328
2700
1328
3000
0.0
3100
0.0
3400
0.0
3700
0.0
3700
0.0
3900

U, V, W, X(ton) : Indicates the chillers weight that one base contact bears.

LS Absorption Chiller

E
170
170
170
170
185
185
185
185
210
210
210
210
235
235
235
210
210
210
210
210
210
210
210

Dimension(mm)
F
G
200
880
200
880
200
880
200
880
170
940
170
940
170
940
170
940
170
980
170
980
170
1080
170
1080
180
1280
180
1280
180
1280
130
1380
130
1380
130
1380
130
1500
130
1500
130
1500
130
1720
130
1720

H
200
200
200
200
170
170
170
170
170
170
170
170
180
180
180
130
130
130
130
130
130
130
130

I
480
480
480
480
600
600
600
600
640
640
740
740
920
920
920
1120
1120
1120
1240
1240
1240
1460
1460

J
520
520
573
589
563
585
548
535
497
537
557
557
480
480
480
460
460
460
750
750
750
800
800

R
170
170
225
225
200
200
200
200
185
185
185
185
180
180
180
130
130
130
130
130
130
130
130

T
170
170
225
225
200
200
200
200
185
185
185
185
180
180
180
130
130
130
130
130
130
130
130

U
1.6
1.7
2.1
2.3
2.7
2.8
3.3
3.5
4.4
4.5
5.4
5.5
8.0
8.6
9.2
12.4
13.2
14.1
15.6
16.7
17.6
19.3
20.4

Load(ton)
V
W
1.6
0.7
1.7
0.8
2.1
0.9
2.3
1.0
2.7
1.1
2.8
1.2
3.3
1.2
3.5
1.3
4.4
1.7
4.5
1.8
5.4
2.1
5.5
2.2
8.0
2.7
8.6
3.0
9.2
3.3
12.4
4.1
13.2
4.6
14.1
5.2
15.6
6.4
16.7
6.9
17.6
7.5
19.3
8.3
20.4
8.7

S
640
640
750
750
750
750
750
750
820
820
920
920
1320
1320
1320
1420
1420
1420
1520
1520
1520
1600
1600

K
300
300
300
300
350
350
350
350
450
450
550
550
960
960
960
1160
1160
1160
1260
1260
1260
1340
1340

L
160
160
160
160
185
185
185
185
210
210
210
210
200
200
200
200
200
200
200
200
200
200
200
X
0.9
0.9
1.0
1.1
1.4
1.4
1.4
1.5
1.8
1.9
2.3
2.4
3.1
3.3
3.6
4.6
5.1
5.5
6.7
7.3
7.9
8.6
9.0

LDF-S Series [100~1,500USRT ]


Thermal Insulation

Evaporator Water
bax cover

Refrigerant Pump
Dont insulate the motor of refrigerant pump

Dont insulate fusible plug.

Combustion
chamber
cover

Removal structure

100mm FOR WARM SURFACE


50mm FOR WARM SURFACE
25mm FOR WARM SURFACE
20mm FOR COLD SURFACE

Size(mm)
Model
LDF-S010S
LDF-S012S
LDF-S015S
LDF-S018S
LDF-S021S
LDF-S024S
LDF-S028S
LDF-S032S
LDF-S036S
LDF-S040S
LDF-S045S
LDF-S050S

100mm
6.3
6.9
8.1
8.7
10.1
10.9
11.9
12.6
14.5
15.3
17.5
18.4

Warm(m2)
50mm
1.6
1.6
2.2
2.2
2.4
2.4
3.2
3.2
3.7
3.7
4.0
4.0

25mm
3.4
3.7
3.9
4.3
4.7
4.8
5.6
5.8
6.2
6.3
6.5
6.7

Material: Glass wool, Non-flammable rubber sponge


Galvanized steel plate
Insulation area includes pipings

Cold(m2)
20mm
4.4
4.4
5.9
5.9
6.8
6.8
8.4
8.4
9.9
9.9
11.2
11.2

100mm

Warm(m2)
50mm

LDF-S056S

20.0

4.8

7.0

13.9

LDF-S063S

21.3

5.2

7.4

15.0

LDF-S070S

22.4

5.6

7.7

16.1

LDF-S080S

27.2

6.2

8.5

17.3

LDF-S090S

29.0

6.6

8.9

19.5

LDF-S100S

30.8

7.0

9.3

19.9

LDF-S110S

36.7

7.6

10.8

12.7

LDF-S120S

38.7

8.0

11.1

13.3

LDF-S130S

40.7

8.4

11.4

13.8

LDF-S140S

45.5

8.6

12.1

14.6

LDF-S150S

47.0

9.1

12.4

15.1

Size(mm)
Model

25mm

Cold(m2)
20mm

Insulation area includes pipings

16 17

Double-Effect Direct-Fired Absorption Chiller


Control Sequence Diagram
Normal Operation
NORMAL OPERATION

RUN
NO

51A
51R
51B

Motor
ABNORMAL

Cooling

Cooling/Heating
Mode Change S/W

REMOTE

RUN
BUTTON

Chilled Water Pump


ON

NORMAL OPERATION

YES

Motor
ABNORMAL

Heating

RUN
Remote Signal
Hot Water Pump
ON

Heating

Cooling Water Pump


ON
Cooling

NO

L-CUT OFF

YES

YES

Cooling/Heating
Mode Change S/W

NO

H-CUT OFF

Combustion OFF
Chilled Water Pump
LOW

YES

Hot Water Temp.


HIGH

YES
After 20 Sec
88B

NO

NO

PERIPHERAL EQUIPMENT ABNORMAL

Burner Blower OFF


Chilled Water Pump
INTERLOCK

NO
Cooling Water Pump
Interlock OFF
52CO
NO

YES

Equipment
Abnormal

YES

Combustion OFF
Hot Water Pump
INTERLOCK

NO
Chilled Water Pump
INTERLOCK
52CO

NO

YES
Chilled Water Pump
Interlock OFF
52CH

52CH

NO

YES

YES

SVM1.2
Burner Blower OFF
88B
Heating

Cooling/Heating
Mode Change S/W
Chilled(Hot) Water
Cut-off S/W
ON

Cooling

NO

Refrigerant Pump
OFF

69CH

YES

Absorbent Pump
RUN

88R
Absorbent Pump
OFF

Burner Blower
ON
YES
NO

88A
88B

6~15 min

Flame Detector
NORMAL
FD-PR
YES
Air Pressure
NORMAL

Complete STOP

Gas Pressure
NORMAL

Gas Control V/V


OPEN

Gas Control V/V


OPEN

RUN
RUN S/W
STOP

PGSL
PGSH

Control Valve
CLOSE Signal

Cooling/Heating
Mode Change S/W

YES
Combustion System
ABNORMAL

RUN
BUTTON

Remote Signal
OFF

PAS

YES
NO

5 min

STOP
Remote

NO

Absorbent Pump
OFF

PR
CMG
1~5 min

5 min

1 min

Refrigerant Pump
OFF

Absorbent Pump
OFF

Combustion
OFF

Cooling Water Pump


OFF

Complete
STOP

After
20 sec.

1 min

Complete
STOP

Burner Blower
OFF

NO
33H

YES
30 sec

Gas Control V/V


OPEN

PR-CMG

NO

Gas Control V/V


CLOSE
33L
YES

Gas Cut-Off V/V


OPEN
NO
After 4 Sec
OFF

Ignition Trans
ON

Chilled Water Pump


OFF
YES

33LO

TIG

1~9 min

Absorbent pump
OFF

Gas Cut-Off V/V


FD-PR
OPEN
Complete
STOP

NO
IGNITION
YES
Combustion System
ABNORMAL
Refrigerant Pump
ON
NORMAL
OPERATION

LS Absorption Chiller

Abnormal & Emergency Operation


GENERATOR SYSTEM ABNORMAL
Generator Input
HIGH

YES

COMBUSTION SYSTEM ABNORMAL

Generator
ABNORMAL

Ignition FAILURE
ABNORMAL

63GH

NO
Exhaust Gas Temp.
HIGH

NO

Combustion
OFF
SVM1.2

YES

88B
Generator Temp.
HIGH
26GE
NO

YES
Cooling/Heating
Mode Change S/W

YES

Air Pressure
LOW

Heating

YES

6~15 min

Burner Blower
OFF
88B
Heating

Cooling/Heating
Mode Change S/W

Refrigerant Pump
OFF
88R

NO

Combustion
ABNORMAL

PAS

NO

Cooling
Generator Level
LOW

Combustion
OFF
SVM1.2
15 sec.

YES
Gas Pressure
ABNORMAL
PGSL
NO
PGSH

Burner Blower
OFF

NO

YES
FD-PR

Cooling
Refrigerant Pump
OFF
88R

5 min

Absorbent Pump
OFF

6~15 min

88A

5 min

Absorbent Pump
OFF

Complete
STOP

88A
Complete
STOP

MOTORS ABNORMAL

RE-START AFTER ABNORMAL CONDITION


RUN BUTTON

Motor ABNORMAL
YES
Absorbent Pump
OVER-CURRENT
51A
NO

Burner Blower
OFF

YES
Rerfrigerant Pump
OVER-CURRENT
51R
NO
Burner Blower
OVER-CURRENT
51B
NO

Abnormal Causes Check and Removal

Combustion
OFF
SVM1.2

Motors ABNORMAL

Combustion System ABNORMAL

Motor Over-Load Relay RE-SET

Protector RE-SET

88B
Cooling/Heating
Mode Change S/W
43T
Cooling

YES

Heating

51A, R, B

Refrigerant Pump
OFF
88R
Absorbent Pump
OFF
88A
Complete
STOP

RE-START
Absorbent Pump
OFF
88A

CHILLED(HOT) WATER SYSTEM ABNORMAL


Chilled Water Temp.
LOW(Cooling)
63GH
NO

Motor ABNORMAL
Combustion
OFF
SVM1.2

Hot Water Temp.


HIGH(Heating)

Burner Blower
OFF

YES

YES

NO

Chilled(Hot) Water System


ABNORMAL
Combustion
OFF
SVM1.2
Burner Blower
OFF

88B

88B
Heating

Cooling/Heating
Mode Change S/W
Cooling

YES
Chilled(Hot) Water
Cut-off S/W
OFF
69CH
NO

Refrigerant Pump
OFF

Cooling/Heating
Mode Change S/W
Cooling
Refrigerant Pump
OFF

88R
6~15 min

Heating

Absorbent Pump
OFF

88R
5 min

Absorbent Pump
OFF

Absorbent Pump
OFF
88A
6~15 min

5 min

88A
Complete
STOP

Complete
STOP

18 19

Fuel Piping
Combustion
Combustion Sequence Diagram

GAS
GAS PRESSURE : 200mmAq

GAS PRESSURE : 900~4,000mmAq

OIL

* The information is typical

Flue and Stack Connection


1. Local regulations regarding exhaust of direct-fired burners
must be adhered to. These instructions shown are typical
and are not meant to supersede local codes in any way.
2. The steel stack should be lined on the interior surface to
protect the stack from corrosion due to moisture in the
exhaust gas.
3. The flue and stack must be heat insulated and provided
with a condensate drain.
4. Do not connect the flue to an incinerator stack.
5. Place the top of the stack within a sufficient distance from
the cooling towers to prevent contamination.
6. Provide a barometric draft regulator or damper if fluctuations or downdraft in static pressure are expected inside
the flue. Some means of controlling the flue draft may be
necessary to insure that proper combustion efficiency is
maintained at all times.
7. If a common stack is to be used, exhaust must be prevented from floeing into the unit(s) that are not in operation.
8. The draft pressure at the flue flange should be designed
for a maximum negative pressure of-5mmH2O.

LS Absorption Chiller

INTER LINING

DRAFT
REGULATOR

FLUE(INSULATED)

STACK

DAMPER
CONDENSATE
DRAIN
FIRE PROOF
MORTAR

CONDENSATE
DRAIN

Piping Diagram

Flue Flange

NOTE : 1. Field supply


2. Steel material

Model
LDF-S010S
LDF-S012S
LDF-S015S
LDF-S018S
LDF-S021S
LDF-S024S
LDF-S028S
LDF-S032S
LDF-S036S
LDF-S040S
LDF-S045S
LDF-S050S
LDF-S056S
LDF-S063S
LDF-S070S
LDF-S080S
LDF-S090S
LDF-S100S
LDF-S110S
LDF-S120S
LDF-S130S
LDF-S140S
LDF-S150S

A
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

B
C
D
110
110
110
110
110
110
110
110
120
120
120
120
120
120
120
120
103
103
103
103
103
103
115
115
115
115
115
115
139.5 139.5 139.5
139.5 139.5 139.5
139.5 139.5 139.5
113
113
113
113
113
113
113
113
113
119
120
120
119
120
120
119
120
120
119
120
120
119
120
120

E
113
113
113
120
120
120
120
120

F
113
113
113
120
120
120
120
120

G
120
120
120
120
120

Dimension(mm)
H
K
L
330
360
330
360
330
360
330
360
360
390
360
390
360
390
360
390
412
442
412
442
460
490
460
490
558
588
558
588
558
588
678
708
678
708
678
708
120
958
988
120
958
988
120
958
988
120
958
988
120
958
988

M
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38
38

N
130
130
130
130
120
120
120
120
120
120
120
120
137
137
137
114.5
114.5
114.5
112.5
112.5
112.5
112.5
112.5

P
Q
120
120
120
120
120
120
120
120
137
137
137
114.5 114.5
114.5 114.5
114.5 114.5
112
112
112
112
112
112
112
112
112
112

R
260
260
260
260
360
360
360
360
360
360
360
360
411
411
411
458
458
458
449
449
449
449
449

S
290
290
290
290
390
390
390
390
390
390
390
390
441
441
441
488
488
488
479
479
479
479
479

T
10
10
10
10
12
12
12
12
14
14
14
14
14
14
14
20
20
20
24
24
24
24
24

20 21

Piping Diagram
Water Circuit
Piping Diagram

Keep running a chilled water pump no.1,no.2 and an air conditioner continuously
in order to protect freezing trouble during the dilution opreration.(about 15min.)
p
g
p p
y
in order to protect freezing trouble during the dilution opreration.(about 15min.)

EXPANSION

TANK

COOLING
TOWER

AIR
CONDITIONER
C
HC
FLUE

CHILLED
WATER
PUMP NO.2

CHILLED
WATER
PUMP NO.1

WATER SUPPLY

THERMOSTAT

BY-PASS V/V

SYM.

GAS

T
P

ABSORPTION CHILLER/HEATER

SUPPLY HEADER

RETURN HEADER

NAME
TEMPERATURE
GAUGE
PRESSURE
GAUGE
FLOWMETER
PUMP

TO DRAIN DITCH

SYM.

NAME
STRAINER

DRAIN V/V
CHEMICAL
CLEANSING V/V

VALVE

TO DRAIN DITCH

Water Circuit Connection Procedure


GENERAL REMARK ON PIPE-LAYING WORK
1. The range of equipment to be supplied by LS is enclosed by
the two-dot chain line.(__ _ _ __)
2. For pipe diameter, pipe connections, etc., refer to the mechanical layout diagram [OUTLINE].
3. The maximum operating pressure in the chilled and cooling
water is 8 kgf/cm2
4. Concerning the temperature control of cooling water, refer to
another diagram.
[CONTROL OF COOLING WATER TEMPERATURE] (__ _ __)
5. Provide a bleeder in the cooling water line for control of cooling water quality.
6. Provide a bleeder in the cooling water line for control of cooling water quality.
7. Install a strainer having a mesh of 10 or so.
8. At the point of connection for smoke pipe or smoke stack.
1) Provide heat insulation to the smoke pipe, which should be
equipped with a condensation drain.
2) Don't connect the smoke pipe to the smoke stack of an incinerator.

LS Absorption Chiller

3) When one smoke pipe on used for two of more units, a


device has to be provided to prevent the flow of exhaust
into the one which is out of operation.
4) If the static pressure inside the smoke pipe is subject to
fluctuations, provide a draft regulator.
9. To maintain a chilled water and cooling water, install a stop
valve near a inlet and outlet of each drain pipe, also observe
following an essential subjects.
1) Provide a thermometer and pressure gauge at the outline
and inlet of cooling water and chilled water.
2) Provide an air vent each of the chilled and cooling water
lines at a higher point than the headers for chilled water and
cooling water.
3) Install a drain in each of the chilled and cooling water lines
at a higher point between chiller and stop value on chilled
water and cooling water drain pipe and drain to the drain
ditch.
4) Install a chemical cleaning value on drain pipe between a
chiller and inlet and outlet stop value.

PUW-Series (50~80RT)

NOTE
1. 1usRT=3,024kcal/h
2. Standard Tube & Water side pressure : 5kgf/cm2
3. Standard gas pressure : 200mmAg
4. Specifications subject to change without prior notice.
5. Currents & Electricity Consumptions are based on 3Ph/380V/50Hz

Standard Specifications
MODEL
Nominal Cooling Capacity
Nominal Heating Capacity
Inlet/outlet Temp
Chilled Flow Rate
Water
Pressure Drop
Data
Connection Size
Inlet/outlet Temp
Hot
Flow Rate
Water
Pressure Drop
Data
Connection Size
Inlet/outlet Temp
Cooling Flow Rate
Water
Pressure Drop
Data
Connection Size
Source

Absorbent Pump
Refrigerant Pump
Purge Pump
Electrical
Burner Blower
Data
Control Circuit
Total Current
Wire Size
Power
Length(L)
Dimension Width(W)
Height(H)
Operating
Weight
Rigging
Shipment
11,000kcal/Nm3(Cooling)
Gas
11,000kcal/Nm3(Heating)
Fuel
10,960kcal/Nm3(Cooling)
Diesel
10,960kcal/Nm3(Heating)
Flue Connection Size
Clearance For Tube Removal

UNIT

PUW-50AU

PUW-60AU

PUW-70AU

PUW-80AU

USRT
103/kcal/h

50
182

60
218

70
254

80
291

m3/h
mAq
A

30.3
3.0

36.3
3.3

42.4
2.4

48.4
2.5

42.4
2.1

48.4
2.2

70
3.9

80
4.2

12

3
54

m3/h
mAq
A

30.3
2.6

3
32

m3/h
mAq
A

50
4.4

37.6

60
5.2

4
3, 220/380/440V, 50~60Hz
1.2(4.1/3.0A)
0.2(1.1/ 1.13A)
0.4(1.3A)

,V,Hz
kW
kW
kW
kW
kVA
A
mm2
kVA
mm
mm
mm
TON
TON

60

36.3
2.9

0.37(1.0A)

0.74(2.3A)
0.3(0.9A)
9
3.5
5.6

2,079

2.476
1,699

1,490
1,852
3.2
2.9

3.4
3.1

14.5
20.0
14.0
19.3

17.4
23.9
16.9
23.3

3.8
3.5

4.0
3.7

20.3
27.9
19.7
27.0

23.2
31.9
22.4
30.9

ONE-SECTION
Nm3/h
Nm3/h
kg/h
kg/h
mm
mm

190 x 110
1,700

270 x 150
2,200

22 23

Double-Effect Steam-Fired Absorption Chiller

Standard Specifications
MODEL
Nominal Cooling Capacity
Temperature
Chilled
Water
Data

LSH-S010 LSH-S012 LSH-S015 LSH-S018 LSH-S021 LSH-S024 LSH-S028 LSH-S032 LSH-S036 LSH-S040
100

120

150

180

210

240

280

320

360

400

kW

352

422

528

633

739

844

985

1,125

1,266

1,407

12 7

Water Flow Rate

m /h

60.5

72.6

90.7

108.9

127.0

145.2

169.3

193.5

217.7

241.9

Pressure Drop

mAq

6.5

6.6

8.0

8.3

7.5

7.9

5.1

5.5

5.8

6.1

Connection Size
Temperature
Cooling
Water
Data

UNIT
USRT

B(inch)

32 37.5

Water Flow Rate

m3/h

100

120

150

180

210

240

280

320

360

400

Pressure Drop

mAq

3.9

4.4

6.5

7.7

5.6

6.2

10.9

12.1

8.7

9.4

Connection Size

B(inch)

Source

,V,Hz

Total Current

Wire Size

mm2

Electrical Power
Data
Absorbent Pump No.1

kVA

Absorbent Pump No.2

kW

Refrigerant Pump

kW

Purge Pump

kW

3, 220/380/440V, 50~60Hz
9.6

9.6

13.7
3.5

6.3

kW

6.3
2.4(6.4)

9.0
2.4(6.4)

3.4(10.2)

*********
0.2(1.13)

0.4(1.42)
0.4(1.6)

Length(L)

mm

Dimension Width(W)

mm

1,775

1,880

Height(H)

mm

2,030

2,300

Operating

Ton

Rigging

Total.Shipping
Steam Flow Rate

Fuel

Steam Inlet Connection Size

B(inch)

Drain Outlet Connection Size

B(inch)

Steam Control Valve

B(inch)

Clearance For Tube Removal


Note

kg/h

mm

2,650

3,670

3,730

4,750

4,850
2,110
2,550

4.2

4.4

5.5

5.7

6.8

7.1

8.4

8.8

10.8

3.8

4.0

5.0

5.1

6.1

6.3

7.5

7.8

9.6

9.9

440

528

660

792

924

1,060

1,230

1,410

1,580

1,760

2 1/2

1 1/2

1 1/2
2,400

2
3,400

4,500

1. 1 usRT =3.52kW(3,024kcal/h) 2. Standard Tube and Water Side Pressure(Chilled & Cooled Water Circuit ): 8kgf/cm (785kPa)
3. Currents & Electricity Consumptions are based on 3Ph/380V/50Hz 4. Alternate cooling water temperature range available upon request.
5. Specifications is subject to change without prior notice

LS Absorption Chiller

1
1

11.2

LSH-S Type (100~1,500USRT)

Cooling Water
Outlet

Refrigerant
Vapur

Low Temp
Generator

Condenser

Intermediate
Solution

High Temp
Generator

Cooling Water

Steam
Control

M Valve
Concentrated
Solution

Cycle of
Double-Effect
Steam-Fired
Chiller

Steam
Inlet

Steam
Chilled
Water
Outlet

Evaporator

Chilled
Water
Inlet

Abosorber

Steam
Trap
Purge
Unit

H2 O

Diluted
Solution

Purge valve

Chilled
Water

LI BR+H2O

Heat
ReClaimer
Drain
Outlet

Vacuum Pump

Controller
Refrigerant

Refrigerant
Pump

Low Temp.
Heat Exchanger

Absorbent
Pump

High Temp.
Heat Exchanger

Cooling Water
Inlet

LSH-S045

LSH-S050

LSH-S056

LSH-S063

LSH-S070

LSH-S080

LSH-S090

LSH-S100

LSH-S110

LSH-S120

LSH-S130

LSH-S140

LSH-S150

450

500

560

630

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,583

1,758

1,969

2,216

2,462

2,813

3,165

3,517

3,869

4,220

4,572

4,924

5,275
907.2

12 7
272.2

302.4

338.7

381.0

423.4

483.8

544.3

604.8

665.3

725.8

786.2

846.7

5.2

5.5

4.6

6.2

8.1

4.7

6.4

8.4

6.2

7.9

9.8

8.0

10

12

9.8
14

32 37.5
450

500

560

630

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

10.3

11.2

7.1

9.4

12.1

8.4

11.1

14.3

8.8

10.9

13.4

12.3

14.6

6,830

7,330

10

12

14

16

3, 220/380/440V, 50~60Hz
13.7

26.8

25.8

3.5

34.6

9.0

17.7

3.4(10.2)

17.0

46.7

14

22

22.8

30.7

6.6(16.2)

****

7.5(25.0)

2.0(6.8)

4,850

5,060

2.2(5.8)

5.5(14.5)

0.4(1.42)

1.5(4.0)

0.4(1.6)

0.75(2.4)

5,600

6,100

5,710

6,210

6,730

6,170

6,690

2,250

2,480

2,825

3,000

2,780

3,255

3,400

3,600

7,180

3,250
3,650

13.2

13.6

18.8

20.4

21.9

28.1

30.1

32.2

35.7

38.0

40.1

44.4

11.6

11.9

16.3

17.7

19.0

24.1

25.8

27.7

31.2

33.2

35.1

38.8

41.0

1,980

2,200

2,470

2,780

3,080

3,520

3,960

4,400

4,840

5,280

5,720

6,160

6,600

6,300

6,800

1 1/2

4,500

2 1/2

2 1/2

3
4,600

5,200

5,700

5,200

46.8

4
5,700

6,200

5,800

6,300

6,800

24 25

Double-Effect Steam-Fired Absorption Chiller


Dimension
Outline (LSH-S010~S100)
E

NOTE.

NOTE.
1. INDICATES THE POSITION OF ANCHOR BOLTS.
1. INDICATES THE POSITION OF ANCHOR BOLTS.
2. ALL WATER, STEAM PIPING CONNECTOINS ARE WELDED ANSI 150 PSIG
2. ALL RF
WATER,
STEAM
PIPING
ARE
WELDED
ANSI 150
PSIG
FLANGES.
(FOR
STEAMCONNECTOINS
CONTROL VALVE,
THE
CONNECTION
IS WELDED
RF FLANGES.
(FOR STEAM CONTROL VALVE, THE CONNECTION IS WELDED
DIN-PN25 FLANGE.)
DIN-PN25
FLANGE.)AND SERVICE CLEARANCE ARE AS FOLLOWS:
3. INSTALLATION
LONGITUDINAL
1000mm
3. INSTALLATION
ANDDISTANCE
SERVICECLEARANCE
ARE AS FOLLOWS:
CONTROL PANEL
SIDE 1200mm
LONGITUDINAL
DISTANCE
1000mm
TOP

200mm
CONTROL PANEL SIDE 1200mm
500mm
TOPOTHERS
200mm
OTHERS 500mm

(L)

(W)

D
F
C

MICOM

(H)

E
B

Model
LSH-S010
LSH-S012
LSH-S015
LSH-S018
LSH-S021
LSH-S024
LSH-S028
LSH-S032
LSH-S036
LSH-S040
LSH-S045
LSH-S050
LSH-S056
LSH-S063
LSH-S070
LSH-S080
LSH-S090
LSH-S100

Length(L)
2650
2650
3670
3670
3730
3730
4750
4750
4850
4850
4850
4850
5060
5600
6100
5710
6210
6730

Dimension(mm)
Width(W)
Hight(L)
1775
2030
1775
2030
1775
2030
1775
2030
1880
2300
1880
2300
1880
2300
1880
2300
2110
2550
2110
2550
2250
2780
2250
2780
2480
3255
2480
3255
2480
3255
2825
3400
2825
3400
2825
3400

A
5*
5*
5
5
6
6
8
8
8
8
10
10
12*
12*
12*
14*
14*
14*

B
4*
4*
4
4
5
5
6*
6*
6*
6*
8*
8*
8*
8*
8*
10*
10*
10*

Nozzle Connection Size(B, inch)


C
D
E
4
5
1
4
5
1
4
5
1
4
5
1
5
6
1
5
6
1
6
8
1
6
8
1
6
8
1 1/2
6
8
1 1/2
8
10
1 1/2
8
10
1 1/2
8
12*
2
8
12*
2
8
12*
2
10
14*
2 1/2
10
14*
2 1/2
10
14*
2 1/2

A : Cooling Water Inlet B : Chilled Water Inlet C : Chilled Water Outlet D : Cooling Water Outlet E : Drain Outlet F : Steam Inlet
* The direction of inlet/outlet is opposite of the showen in the illustration above.

LS Absorption Chiller

F
2
2
2
2
2 1/2
2 1/2
2 1/2
2 1/2
3
3
3
3
4
4
4
5
5
5

G(mm)
2400
2400
3400
3400
3400
3400
4500
4500
4500
4500
4500
4500
4600
5200
5700
5200
5700
6200

LSH-S Type (100~1,500USRT)

Outline (LSH-S110~S150)
E

NOTE.
NOTE.
F

1. 1.INDICATES
THE
POSITION
INDICATES
THE
POSITIONOFOFANCHOR
ANCHORBOLTS.
BOLTS.
2. ALL
WATER,
STEAM
PIPING
CONNECTOINS
150PSIG
PSIG
2. ALL
WATER,
STEAM
PIPING
CONNECTOINSARE
AREWELDED
WELDED ANSI
ANSI 150
RF FLANGES.
(FOR
STEAM
CONTROLVALVE,
VALVE,THE
THECONNECTION
CONNECTION IS
RF FLANGES.
(FOR
STEAM
CONTROL
ISWELD
WELDED
DIN-PN25
FLANGE.)
DIN-PN25
FLANGE.)
3. INSTALLATION
AND
SERVICECLEARANCE
CLEARANCEARE
AREAS
AS FOLLOWS:
FOLLOWS:
3. INSTALLATION
AND
SERVICE
LONGITUDINAL
DISTANCE
1000mm
LONGITUDINAL
DISTANCE
1000mm
CONTROL
PANEL
SIDE

1200mm
CONTROL PANEL SIDE 1200mm
200mm
TOPTOP
200mm
OTHERS 500mm
OTHERS 500mm

(W)

(L)

(H)

MICOM

Nozzle Connection Size(B, inch)


C
D
E
12
16
3

LSH-S110

Length(L)
6170

Dimension(mm)
Width(W)
3000

Hight(L)
3600

A
16

B
12

LSH-S120

6690

3000

3600

16

12

12

16

LSH-S130

7180

3000

3600

16

12

12

16

LSH-S140

6830

3250

3650

16

14

14

LSH-S150

7330

3250

3650

16

14

14

Model

F
6

G(mm)
5800

6300

6800

16

6300

16

6800

A : Cooling Water Inlet B : Chilled Water Inlet C : Chilled Water Outlet D : Cooling Water Outlet E : Drain Outlet F : Steam Inlet

26 27

Double-Effect Steam-Fired Absorption Chiller


Foundation
LSH-S010~S032

"A"

200

100

"I" (ton)

HEIGHT
200~250

DRAIN DITCH

100

200

"J" (ton)

100
G
"H"

A
H

200

100

LSH-S036~S150

"J" (ton)

"I" (ton)

200

NOTE.

100
B
"F"

1. INDICATES THE POSITON OF ANCHOR BOLTS.


2. THE FOUNDATION AND THE FLOOR MUST BE SUFFICIENTLY
STRONG TO SUPPORT THE UNIT WEIGHT.
3. PROVIDE A FLOOR DRAIN NEAR CHILLER FOUNDATION.
4. ONLY IF FOUNDATION ANCHORING IS REQUIRED, ANCHOR BOLTS,
NUTS AND WASHERS, SHALL BE SUPPLIED TOGETHER WITH CHILLER.
ANCHOR BOLTS MUST BE FIXED ON THE FOUNDATION PRIOR TO
CHILLER INSTALLATION
5. UNIT MUST BE LEVELED BEFORE STARTUP.
(HORIZONTAL LEVEL MUST BE BELOW THAN 2mm/1000mm)

BASE CONTACT

Model
LSH-S010
LSH-S012
LSH-S015
LSH-S018
LSH-S021
LSH-S024
LSH-S028
LSH-S032
LSH-S036
LSH-S040
LSH-S045
LSH-S050
LSH-S056
LSH-S063
LSH-S070
LSH-S080
LSH-S090
LSH-S100
LSH-S110
LSH-S120
LSH-S130
LSH-S140
LSH-S150
Note.

Dimension(mm)
A
210
210
210
210
235
235
235
235
470
470
470
470
470
470
470
520
520
520
520
520
520
520
520

B
210
210
210
210
235
235
235
235
270
270
270
270
270
270
270
320
320
320
320
320
320
320
320

C
420
420
420
420
470
470
470
470
1760
1760
1860
1860
2060
2060
2060
2300
2300
2300
2500
2500
2500
2700
2700

I, J(ton) : Indicates the chillers weight that one base contact bears.

LS Absorption Chiller

D
1160
1160
1160
1160
1460
1460
1460
1460
1560
1560
1660
1660
1860
1860
1860
2100
2100
2100
2300
2300
2300
2500
2500

E
960
960
960
960
1260
1260
1260
1260
1360
1360
1460
1460
1660
1660
1660
1900
1900
1900
2100
2100
2100
2300
2300

Load(ton)
F
1360
1360
1360
1360
1660
1660
1660
1660
3716
3716
3716
3716
3706
4248
4746
4188
4686
5211
4286
4811
5311
4811
5311

G
220
220
220
220
270
270
270
270
120
120
120
120
130
130
130
140
140
140
140
140
140
140
140

H
1846
1846
2866
2866
2816
2816
3836
3836
175
175
175
175
170
170
170
190
190
190
190
190
190
190
190

I
2.1
2.2
2.8
2.9
3.4
3.6
4.2
4.4
5.4
5.6
6.6
6.8
9.4
10.2
11.0
14.1
15.1
16.1
17.9
19.0
20.1
22.2
23.4

J
2.1
2.2
2.8
2.9
3.4
3.6
4.2
4.4
5.4
5.6
6.6
6.8
9.4
10.2
11.0
14.1
15.1
16.1
17.9
19.0
20.1
22.2
23.4

LSH-S Type (100~1,500USRT)


Thermal Insulation

CHAMBER COVER
OF EVAPORATOR

REFRIGERANT PUMP
Don't insulate the motor of refrigerant pump

NOTE.
1. Use noncombustible insulation material
2. Do not insulate motor of refrigerant pump.
3. Total insulation area includes piping.
4. The chiller is coated with a anticorrosive paint at the factory.
Finish painting is typically performed in the field after insulating is complete.

75mm FOR WARM SURFACE


25mm FOR WARM SURFACE
20mm FOR COLD SURFACE

Item
Model
LSH-S010
LSH-S012
LSH-S015
LSH-S018
LSH-S021
LSH-S024
LSH-S028
LSH-S032
LSH-S036
LSH-S040
LSH-S045
LSH-S050

Hot Surface(m2)
75mm
25mm
5.3
3.0
5.3
3.4
7.5
3.7
7.5
4.2
8.4
4.7
8.4
4.8
11.2
5.8
11.2
6.0
12.7
6.5
12.7
6.7
13.4
6.9
13.4
7.2

REMOVAL PART

Cold Surface(m2)
20mm
4.4
4.4
5.9
5.9
6.8
6.8
8.4
8.4
9.9
9.9
11.2
11.2

Item
Model

Hot Surface(m2)
75mm
25mm

Cold Surface(m2)
20mm

LSH-S056

16.1

8.8

13.9

LSH-S063

18.1

9.3

15.0

LSH-S070

19.9

9.7

16.1

LSH-S080

21.2

10.7

17.3

LSH-S090

23.3

11.2

18.5

LSH-S100

25.4

11.7

19.9

LSH-S110

27.2

13.5

12.7

LSH-S120

29.6

13.9

13.3

LSH-S130

31.9

14.3

13.8

LSH-S140

31.3

15.2

14.6

LSH-S150

33.8

15.5

15.1

28 29

Piping Diagram
Water Circuit
Piping Diagram

Keep running a chilled water pump no.1,no.2 and an air conditioner continuously
in order to protect freezing trouble during the dilution opreration.(about 15min.)

REDUCING V/V

R
MAIN STEAM PIPING

COOLING
TOWER

SAFETY V/V

*
HC

WATER SUPPLY

AIR CONDITIONER

STEAM
MV CONTROL V/V
P

CHILLED
WATER
PUMP NO.1

THERMOSTAT

CHECK V/V

CHILLED
WATER
PUMP NO.2
BY-PASS V/V

SYM.

NAME

THERMOMETER
PRESSURE
GAUGE

P
F

FLOWMETER

TO BOILER

PUMP

ABSORPTION CHILLER

SYM.

NAME
STRAINER

DRAIN V/V
CHEMICAL
CLEANSING V/V
TRAP

VALVE
SUPPLY HEADER

RETURN HEADER

COOLING
WATER
PUMP
TO DRAIN DITCH

TO DRAIN DITCH

Water Circuit Connection Procedure


GENERAL REMARKS ON PIPE-LAYING WORK
1. The range of equipment to be supplied by LS is enclosed by the
two-dot chain line.(
)
2. For pipe diameter, pipe connections, etc., refer to the mechanical layout diagram.[OUTLINE]
3. The maximum operating pressure in the chilled and cooling
water is 8 kgf/cm2
4. Concerning temperature control of cooling water, refer to another diagram.
[CONTROL OF COOLING WATER TEMPERATURE](
)
5. Provide separate chilled and cooling water pumps for each
absorption machine.
Flow rate of chilled and cooling water should confirm to the
specifications.
6. Provide a bleeder in the cooling water line for control of cooling
water quality.

LS Absorption Chiller

7. Install a strainer having a mesh of 10 or so.


8. Install a steam stop v/v(*) to shut off a steam line to a chiller
when the chiller is not operate.
9. Provide the inlet and outlet piping for chilled and cooling water
with the stop valve so that the piping can be cleaned easily.
1) Install thermometers and pressure gauges at locations convenient for servicing in the inlet and outlet water lines.
2) Install air vent valves for water lines at a position above the
absorption machine.
3) Install drain valves for water lines at a position bottom the
absorption machine, and then extend them up to the ditch.
4) For chemical cleaning, install the stop valves for cleaning
between the unit and each stop valve at the inlet or outlet.

Performance Graph
How Chilled or Cooling Water Temperature can affect Cooling Capacity
Cooling Capacity & Chilled Water Outlet Temp.

Cooling Water (Inlet Temperature)


130

120

110

Cooling Capacity(%)

Cooling Capacity(%)

120
110
100
90
80

100

90

80

70

70

26

27

28

29

30

31

32

33

34

Cooling Water Inlet Temp.(C)

10

11

12

13

CHILLED WATER OUTLET TEMP.(C)

* Condition
Chilled Water Temperature : (Inlet) 12C (Outlet) 7C
Difference Between Inlet And Outlet Of Cooling Water

Temperature ( t) = 5.5C

* Condition
Difference of Chilled Water Inlet And Outlet Temp.

( t) : 5.0C
Cooling Water Temp. : 32C 37.5C

How Temperature Difference affect( t) of Chilled or Cooling Water Temperature can after
Cooling Capacity
Cooling Water

Chilled Water
120

110

100

Cooling Capacity(%)

Cooling Capacity(%)

110

90

80

70

100

90

80

70

Difference Between Inlet And Outlet


Of Cooling Water Temperature(C)
Chilled Water Temp. : (Inlet) 12C (Outlet) 7C
Cooling Water Inlet Temperature : 32C

10

Difference Between Inlet And Outlet

Of Chilled Water Temperature( t)


Chilled Water outlet Temp. : 7C
Cooling water Temp : (inlet) 32C

(outlet) 37.5C

30 31

Single-Effect Steam-Fired Absorption Chiller

Standard Specifications
MODEL
Nominal Cooling Capacity
Chilled
Water
Data

A-100A

A-120A

A-150A

A-180A

B-210A

B-240A

B-280A

C-320A

C-360A

C-400A

100

120

150

180

210

240

280

320

360

400

12 7

Inlet Outlet

Flow Rate

m3/h

60.5

72.6

mAq

2.2

2.5

Pressure Drop
Connection

Cooling
Water
Data

UNIT
usRT

B(inch)

90.7

109

127

145

169

194

218

242

2.9

3.4

3.1

3.3

4.9

4.7

4.6

4.9

5
32 39.5

Inlet Outlet

Flow Rate

m3/h

100

120

150

180

210

240

280

320

360

400

Pressure Drop

mAq

3.6

3.7

4.8

5.3

4.7

5.1

7.3

6.0

6.3

6.7

Connection
Source

Abso Pump
MOTER
POWER Refr Pump
Purge Pump
Electrical
Data
Control Circuit

B(inch)
,V,Hz

3, 220V/380V, 50Hz/60Hz

kW(A)

2.0(6.8A)

kW(A)

3.0(9.5A)

0.3(1.16A)

0.4(1.42A)

kW(A)

0.4(1.6A)

kVA(A)

0.3(0.5A)

Total Current

10.1

10.3

13.0

3.5

Wire

mm2

Power

kVA

Length(L)

mm

Dimension Width(W)
Heigth(H)

mm

1,490

1,680

mm

2,180

2,410

Operating

Ton

4.1

4.3

5.5

5.8

6.8

7.1

8.0

9.8

10.2

Rigging

Ton

3.7

3.9

5.0

5.2

6.0

6.3

7.0

8.5

8.9

9.2

Consumption

kg/h

800

960

1,200

1,440

1,680

1,920

2,240

2,560

2,880

3,200

Weight

Steam Inlet Connection

B(inch)

Drain Outlet Connection


Clearance For Tube Removal

B(inch)
mm

Steam

Note

6.6

6.8

2,630

3,650

3,730

8.6
4,340

4,440
1,910
2,750

6
11/2

2,400

3,400

1. 1 usRT =3.52kW(3,024kcal/h) 2. Standard Tube and Water Side Pressure(Chilled & Cooled Water Circuit ): 8kgf/cm2 (785kPa)
3. Currents & Electricity Consumptions are based on 3Ph/380V/50Hz 4. Alternate cooling water temperature range available upon request.
5. Specifications is subject to change without prior notice

LS Absorption Chiller

8
2
4,100

10.6

A/V Type (100~1,400USRT)

Steam
Inlet

Condenser

Cooling Water
Outlet

Steam
Control

Cooling Water

M Valve

Drain
Outlet

Concentrated
Solution

Cycle of
Single-Effect
Steam-Fired
Chiller

Chilled
Water
Outlet

Evaporator

Chilled
Water
Inlet

Abosorber
Purge valve

Chilled
Water

Purge
Unit

H 2O

Li Br+H2O
Heat
Exchanger

Diluted
Solution

Vacuum Pump

Controller
Refrigerant
Pump

Refrigerant

Absorbent
Pump

Cooling Water
Inlet

D-450A

D-500A

E-550V

E-620V

E-690V

E-770V

F-850V

F-950V

G-1050V

G-1150V

G-1300V

G-1400V

450

500

550

620

690

770

850

950

1,050

1,150

1,300

1,400

466

514

575

635

696

786

847

3.5

3.5

3.6

3.9

4.0

6.6

6.6

12 7
272

302

333

375

417

4.6

5.5

5.8

3.3

4.6
8

10

12

32 39.5

32 40.2

450

500

498

561

624

697

769

860

950

1,041

1,177

1,267

5.9

6.2

7.2

7.6

10.8

11.3

9.9

10.3

8.3

8.8

13.8

14.2

10

12

14

16

3, 220V/380V, 50Hz/60Hz
3.0(9.5A)

4.5(19.5A)

0.4(1.42A)

5.5(20A)

1.5(4.0A)

0.4(1.6A)

0.75(2.5A)
0.3(0.5A)

13.0

13.9

16.5

26.5

27.0

3.5

8.6

9.2

10.9

4,440

5,810

7,040

1,910

17.4

2.100

2,970

17.8

7,250

7,360

8,600

2,500

3,230

2,800

3,600

4,200

12.1

12.6

20.0

20.8

24.1

25.3

27.8

28.6

37.2

38.0

42.4

10.5

10.8

17.3

18.1

21.0

22.2

23.4

24.2

32.2

33.0

36.4

37.2

3,600

4,000

4,400

4,960

5,520

6,160

6,800

7,600

8,400

9,200

10,400

11,200

8
4,100

10

12

14

2 1/2

5,320

6,560

43.2

7,910

32 33

Single-Effect Steam-Fired Absorption Chiller


Dimension
Outline
NOTE
1. Indicates the position of anchor bolts.
2. All external water pipings are to be provided
with welded ANSI 150# RF flanges by the customer.
3. Indicates the position of the power supply
connection to control panel. (DIAMETER 32mm)
4. Indicates the position of the power supply
5. Indicates the position of the power supply
6. Indicates the position of the power supply
7. Indicates the position of the power supply

Model
A-100A
120A
150A
180A
B-210A
240A
280A
C-320A
360A
400A
D-450A
500A
E-550V
620V
690V
770V
F-850V
950V
G-1050V
1150V
1300V
1400V

Overall Dimension(mm)
L
W
H
2,830
1,560
2,220
2,830
1,560
2,220
3,850
1,560
2,220
3,850
1,560
2,220
3,930
1,750
2,450
3,930
1,750
2,450
4,540
1,750
2,450
4,640
1,980
2,790
4,640
1,980
2,790
4,640
1,980
2,790
4,640
1,980
3,010
4,640
1,980
3,010
6,010
2,170
3,270
6,010
2,170
3,270
7,240
2,170
3,270
7,240
2,170
3,270
7,450
2,570
3,640
7,450
2,570
3,640
7,560
2,870
2,850
7,560
2,870
2,850
8,800
2,870
2,850
8,800
2,870
2,850

A
125
125
125
125
150
150
150
200
200
200
250
250
300
300
300
300
350
350
400
400
400
400

B
100
100
10
10
125
125
125
150
150
150
200
200
250
250
250
250
250
250
300
300
300
300

Nozzle Connection(A)
C
D
E
100
125
125
100
125
125
100
125
125
100
125
125
125
150
150
125
150
150
125
150
150
150
200
200
150
200
200
150
200
200
200
250
200
200
250
200
250
300
250
250
300
250
250
300
250
250
300
250
250
350
300
250
250
300
300
400
350
300
400
350
300
300
350
300
400
350

F
40
40
40
40
40
40
40
50
50
50
65
65
65
65
65
65
80
80
100
100
100
100

A : Cooling water outlet, B : Chilled water outlet, C : Chilled water inlet, D : Cooling water inlet, E : Steam inlet, F : Drain outlet, G : Tube removal clearance
* The direction of inlet/outlet is opposite of the showen in the illustration above.

LS Absorption Chiller

G
2,400
2,400
3,400
3,400
3,400
3,400
3,400
4,100
4,100
4,100
4,100
4,100
4,720
4,720
5,960
5,960
6,200
6,200
6,200
6,200
7,530
7,530

A/V Type (100~1,400USRT)

Foundation

A-100AS ~ B-280AS

C-320AS ~ G-1400VS

Center Point for


Checking Dimension

Model
A-100A
120A
150A
180A
B-210A
240A
280A
C-320A
360A
400A
D-450A
500A
E-550V
620V
690V
770V
F-850V
950V
G-1050V
1150V
1300V
1400V
Note.

Center Point for


Checking Dimension

Dimension(mm)
A
1,845
1,845
2,865
2,865
2,815
2,815
3,425
3,305
3,305
3,305
3,305
3,305
4,472
4,472
5,706
5,706
5,506
5,506
5,306
5,306
6,556
6,556

B
1,000
1,000
1,000
1,000
1,300
1,300
1,300
1,300
1,300
1,300
1,500
1,500
1,700
1,700
1,700
1,700
2,200
2,200
2,160
2,160
2,160
2,160

C
1,300
1,300
1,300
1,300
1,600
1,600
1,600
1,600
1,600
1,600
1,800
1,800
1,900
1,900
1,900
1,900
2,440
2,440
2,400
2,400
2,400
2,400

D
320
320
320
320
370
370
370
370
370
370
370
370
420
420
420
420
500
500
640
640
640
640

E
150
150
150
150
150
150
150
150
150
150
150
150
100
100
100
100
120
120
120
120
120
120

weight
F
220
220
220
220
270
270
270
270
270
270
270
270
320
320
320
320
400
400
540
540
540
540

G
1,200
1,200
1,200
1,200
1,500
1,500
1,500
1,500
1,500
1,500
1,700
1,700
1,800
1,800
1,800
1,800
2,340
2,340
2,300
2,300
2,300
2,300

H
160
160
160
160
185
185
185
125
125
125
125
125
150
150
150
150
130
130
170
170
170
170

120
120
120
120
120
120
120
120
120
240
240
300
300
300
300

W
2.1
2.2
2.8
2.9
3.4
3.6
4.0
4.9
5.1
5.3
6.1
6.3
10.0
10.4
12.1
12.7
13.9
14.3
18.6
19.0
21.2
21.6

W(ton) : Indicates the chillers weight that one base contact bears.

34 35

Piping Diagram
Water Circuit
Piping Diagram

Water Circuit Connection Procedure


1. __ _ _ __ Work outside the area surrounded by this line shall
have to be executed at the expense of the owner.
2. Refer to the external dimensions diagram and specification
tables for pipe connections and diameter.
3. Standard supply steam press. Is 1.0~1.5 kgf/cm2
Reducing valve which blowing 1.9 kgf/cm2 Should be located
near the machine as in above diagram if the supply press. Is
higher than 1.5 kgf/cm2 Pipe should be extended from this
safety valve to release excess steam outdoors.
4. Even if a reducing valve is not required, a strain-er, pressure
gauge and drain trap should be pro-vided for each machine
near the steam inlet.
5. The back pressure in the steam drain line should be limited to
less than 2 maq.
6. Determine the locations of the chilled water pumps and the
cooling water pumps in due consid-eration of the pumps
in due consid-eration of the pumps hydrostatic head and lift.
the machine should not be subject to a pressure larger than
8 kgf/cm2 at any water header.

LS Absorption Chiller

7. Concerning the temperature control of cooling water refer to


control of cooling water tem-perature
8. Provide a thermometer and pressure gauge at the outlet and
inlet of cooling water and chilled water.
9. Provide an air vent in each of the chilled and cooling water
lines at a point higher than the headers for chilled water and
cooling water.
10. Lay pipe from the cover of the evaporator and absorber to
the drain ditch.
11. Provide a bleeder in the cooling water line for control of waer
quality.
12. There should be a sufficient clearance for access to the
absorber,evaporator and conders-er to facilitate inspection
and cleaning work.
13. All external water piping are provided with ansi #150 lb rf.
welding flanges by the customer.

Introduction of PID Logic


For optimized control, LS Double-Effect Absorption Machine adopts PID control. As a combination of Proportional,
Integral and Differential Control, PID Control allow better load tracing and faster response. PID action allows smooth
control by removing Off-Set and Hunting of chilled water outlet temp. which are demerits of Proportional action. Integral
action correct Off-Set automatically and Differential Action responses quickly against external influence. Comparing to
typical chillers which are controlled by Proportional Control, microprocessor-controlled LS Absorption machine enables.

1. Constant Temperature control by removing Off-Set of Chilled Outlet temperature.


Therefore, LS Absorption Machine provide excellent process cooling solution in semiconductor, chemical, and pharmaceutical facilities and air conditioning solution in Intelligent Building.
2. Energy Saving because of lower gas consumption which is generated by the reduction of chilled water outlet temperature Hunting.
3. Higher efficiency at partial load because the flow rate of absorbent solution is controlled by digital PID and Inverter.

C onventional
C onvent
C ontirol
onal C ontrol

Power Consumption Rate(%)

Fuel Consumption Rate(%)

Partial Load Characters (Comparing to Conventional Control)

Cooling Capacity Rate(%)

Cooling Capacity Rate(%)

Test Condition
1. Chilled water outlet temp. : 7C (Constant) 2. Cooling water inlet temp. : depends on out-air temp.
3. Load/Cooling water inlet temp. : 100% /32C, 50%/27C, 30%/25C

36 37

Single-Effect Hot-Water Fired Absorption Chiller

Standard Specifications
MODEL
Chilled Water Temp
Cooling Capacity
Chilled Flow rate
Water Pressure drop
Data
Connection size
Water in/out temp
Colling Flow rate
Water
Data Pressure drop
Connection size
Water in/out temp
Hot Flow rate
Water Pressure drop
Circuit
Connection size

UNIT LWM-W003 LWM-W004 LWM-W005 LWM-W007 LWM-W008 LWM-W010 LWM-W012 LWM-W014 LWM-W016 LWM-W019 LWM-W021 LWM-W024
C
USRT

12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
28

30

38

mAq

2.2

2.5

2.9

B(INCH)

Electrical Total current


Data Wire size
Electric consumption
Motor Abso pump No.1
Power Abso pump No.2

Dimension

Weight

Note

47

50

61

65

75

80

94

100

113 120

132 140 151

160

179 190 198 210 226

3.3

5.3

6.0

6.5

7.3

2 1/2

6.7

7.6

5.8

6.5

5.8

6.5

6.0

6.8

6.4

7.2

5.9

6.6

5.8

6.5

5.9

6.7
6

31 36.5

m3/h

37.4 39.4 49.8 52.5 62.3 65.7 81.0 85.4 99.7 105.1 124.6 131.3 149.5 157.6 174.4 183.9 199.4 210.2 236.8 249.6 261.7 275.8 299.1 315.2

mAq

2.5

2.8

3.6

B(INCH)

44.0 6.3

7.0

2.3

2.6

2.8

3.1

4.3

4.8

5.1

5.7

3.6

4.0

4.1

44.6

7.3

8.1

7.8

8.7

5.7

6.3

95 80

C
3

m /h

8.0

8.4

10.7 11.2 13.4 14.0 17.4 18.2 21.4 22.4 26.7 28.0 32.0 33.6 37.4 39.2 42.7 44.8 50.7 53.2 56.1 58.8 64.1 67.2

mAq

1.1

1.2

1.2

1.3

2.6

2.9

1 1/2

B(INCH)

0.8

0.9

0.9

1.0

2.1

2.3

2.2

2.4

2 1/2
1 1/2

2.2

2.4

2.4

2.6

4.4

4.8

4.3

2 1/2

,V,Hz

4.7

4.4

4.8

4
3

3, 220V/380V, 50Hz/60Hz
6.7

9.4

9.7

8.9

3.5

mm2
kVA

4.4

kW(A)

1.2(4.1)

6.2

6.4

5.9

2.0(6.8)

2.2(6.0)

********

kW(A)
0.2(1.13)

kW(A)

0.2(1.13)

0.4(1.42)

0.4(1.0)

Refer pump

kW(A)

Purge pump

mm

Length(L)

mm

1,344

1,346

1,305

1,476

Width(W)

mm

1,952

1,965

2,150

2,330

Height(H)

ton

2.1

Operating weight

ton

1.8

Rigging

mm

2,020

2,000

2,520

2.3

2.7

1.9

2.3

2,547

3,567

3,627

4.1

4.3

5.3

5.7

3.5

3.7

4.6

4.9

2,400

4,630

7.2

8.4

5.8

6.1

7.1

3,400

4,784
1,539

6.9

1. 1 usRT =3.52kW(3,024kcal/h) 2. Standard Tube and Water Side Pressure(Chilled & Cooled Water Circuit ): 8kgf/cm2 (785kPa)
3. Currents & Electricity Consumptions are based on 3Ph/380V/50Hz 4. Alternate cooling water temperature range available upon request.
5. Specifications is subject to change without prior notice

LS Absorption Chiller

240

Connection size of control valve B(INCH)


Source

40

m3/h 17.1 18.1 22.8 24.2 28.5 30.2 37.0 39.3 45.6 48.4 57.0 60.5 68.3 72.6 79.7 84.7 91.1 96.8 108.2 114.9 119.6 127.0 136.7 145.2

8.9

10.8

7.5

9.1

4,500

LWM-W Type (30~1,020USRT)

Condenser

Cooling Water
Outlet

Hot
Water
Inlet

Hot water

Cooling Water
Hot
Water
Outlet

Concentrated
Solution
Chilled
Water
Outlet

Chilled
Water

Evaporator

Chilled
Water
Inlet

Abosorber

Purge
Unit

H 2O

Purge valve

Cycle of
Single-Effect
Steam-Fired
Chiller

Li Br+H2O
Heat
Exchanger

Diluted
Solution

Vacuum Pump

Controller
Refrigerant

Refrigerant
Pump

Absorbent
Pump

Cooling Water
Inlet

LWM-W027 LWM-W031 LWM-W034 LWM-W038 LWM-W043 LWM-W048 LWM-W054 LWM-W060 LWM-W067 LWM-W074 LWM-W081 LWM-W088 LWM-W095 LWM-W102
12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8 12-7 13-8
254

270

292

310

320

340

358

380

405

430

452

480

509

540

565

600

631

670

697

740

763

810

829

880

895

950

961 1,020

153.8 163.3 176.6 187.5 193.7 205.6 216.4 229.8 244.9 260.1 273.4 290.3 307.6 326.6 341.7 362.9 381.6 405.2 421.5 447.6 461.4 489.9 501.2 532.2 541.1 574.6 581.0 616.9
5.7

6.4

6.6

7.4

6.4

7.2

5.8

6.5

8.1

9.1

10.8 12.2

6.0

6.8

8.0

9.0

10.6 11.9

7.9

8.9

10.1 11.4 12.5 14.1

10.2 11.5 12.7 14.3

10

12

31 36.5
336.4 354.4 386.3 407.2 423.7 446.6 473.5 499.1 535.8 564.8 598.1 630.5 672.9 709.3 747.6 788.1 834.9 880.0 922.1 972.0 1.009 1.064 1.097 1.156 1.184 1.248 1.271 1.340
6.3

7.0

7.2

8.0

7.7

8.6

5.8

6.4

7.8

10

8.7

10.2 11.3

5.9

6.6

7.7

12

8.5

10.0 11.1

6.2

6.9

7.7

8.6

9.5

14

10.6

8.8

9.8

10.4 11.6

16

95 80
72.1 75.6 82.8 86.8 90.8 95.2 101.5 106.4 114.8 120.4 128.2 134.4 144.2 151.2 160.2 168.0 178.9 187.6 197.6 207.2 216.3 226.8 235.0 246.4 253.7 266.0 272.4 285.6
4.4

4.8

4.4

4.8

4.4

4.8

2.0

2.2

2.7

3.0

3.6

4.0

2.5

2.8

3.4

3.7

4.5

4.9

1.3

1.4

1.6

1.8

2.0

2.2

1.7

1.9

2.0

2.2

3, 220V/380V, 50Hz/60Hz
8.9

20.9

19.9

3.5

5.5

5.9

13.8

13.1

2.0(6.0)

25.7

38.0

8.0

14.0

16.9

25.0

3.0(11.2)

*****

2.0(6.8)

4.5(17.0)
2.2(5.8)

5.5(14.5)

0.4(1.42)

1.5(4.0)

0.4(1.0)
4,784

4,789

1,539

1,652

2,630
11.3
9.5

4,931

0.75(2.0)
5,971

5,616

2,015

2,886
14.0

11.2

11.7

19.3

20.9

6,114

6,639

6,346

2,195

3,260

13.4

4,500

5,473

27.5

29.5

7,371

7,050

2,680

3,680
22.0

6,871

3,920
31.7

35.7

38.2

7,550
2,970
4,040

40.5

45.0

47.4

16.2

17.6

18.5

22.7

24.4

26.3

30.1

32.3

34.2

37.8

39.8

4,600

5,200

5,700

5,200

5,700

6,200

5,800

6,300

6,800

6,500

7,000

38 39

Single-Effect Hot-Water Fired Absorption Chiller


Dimension
Outline
NOTE.
1. INDICATES THE POSITION OF ANCHOR BOLTS.
2. ALL WATER PIPING CONNECTIONS ARE WELDED ANSI 150
PSIG RF FLANGES. (FOR HOT WATER CONTROL VALVE,
THE CONNECTION IS WELDED DIN-PN10 FLANGE.)
3. INSTALLATION AND SERVICE CLEARANCE ARE AS FOLLOWS:
LONGITUDINAL DISTANCE - 1000mm
CONTROL PANEL SIDE - 1200mm
TOP - 200mm OTHERS - 500mm
4. WATER PIPING DIRECTIONS ARE DIFFER FROM EACH MODEL.

(W)

F*

E*

D*

C*

(H)

MICOM

B*

A*

Model
LWM-W003
LMW-W004
LWM-W005
LWM-W007
LWM-W008
LWM-W010
LWM-W012
LWM-W014
LWM-W016
LWM-W019
LWM-W021
LWM-W024
LWM-W027
LWM-W031
LWM-W034
LWM-W038
LWM-W043
LWM-W048
LWM-W054
LWM-W060
LWM-W067
LWM-W074
LWM-W081
LWM-W088
LWM-W095
LWM-W102

Length(L)
2020
2020
2520
2547
2547
3567
3567
3627
3627
4630
4630
4784
4784
4789
4789
4930
5473
5971
5616
6114
6639
6346
6871
7371
7070
7570

Dimension(mm)
Depth(W)
Height(H)
1394
1952
1396
1965
1396
1965
1355
2150
1355
2150
1355
2150
1355
2150
1526
2330
1526
2330
1526
2330
1526
2330
1575
2630
1575
2630
1702
2886
1702
2886
2015
3190
2015
3190
2015
3190
2195
3640
2195
3640
2195
3640
2680
3840
2680
3840
2680
3840
2890
4040
2910
4040

A
3
3
3
5
5
5*
5*
6*
6*
8*
8*
8*
8*
10*
10*
12*
12*
12*
14*
14*
14*
16
16
16
16
16

B
2 1/2*
2 1/2*
2 1/2*
3
3
4
4
4
4
5*
5*
6*
6*
6*
6*
8*
8*
8*
8*
8*
8*
10
10
10
12
12

A : Cooling water inlet B : Chilled water inlet C : Chilled water outlet D : Hot water inlet
* The direction of inlet/outlet is opposite of the showen in the illustration above.

LS Absorption Chiller

Connection Size(inch)
C
D
E
2 1/2*
1 1/2*
3
2 1/2*
1 1/2*
3
2 1/2*
2 1/2*
3
3
2 1/2*
5
3
2 1/2*
5
4
3
5
4
3
5
4
3
6
4
3
6
5
4
8
5
4
8
6
4
8
6
4
8
6
5
10
6
5
10
8
6*
12
8
6*
12
8
6*
12
8
8*
14
8
8*
14
8
8*
14
10*
8*
16
10*
8*
16
10*
8*
16
12*
8*
16
12*
8*
16
E : Cooling water outlet

F : Hot water outlet

F
1 1/2*
1 1/2*
2 1/2*
2 1/2*
2 1/2*
3
3
3
3
4
4
4
4
5
5
6
6
6
8
8
8
8*
8*
8*
8*
8*

G(mm)
2000
2000
2400
2400
2400
3400
3400
3400
3400
4500
4500
4500
4500
4500
4500
4600
5200
5700
5200
5700
6200
5800
6300
6800
6300
6800

G : Space for tube removal

LWM-W Type (30~1,020USRT)


Foundation
NOTE.
1. INDICATES THE POSITON OF ANCHOR BOLTS.
2. THE FOUNDATION AND THE FLOOR MUST BE SUFFICIENTLY
STRONG TO SUPPORT THE UNIT WEIGHT.
3. PROVIDE A FLOOR DRAIN NEAR CHILLER FOUNDATION.
4. ONLY IF FOUNDATION ANCHORING IS REQUIRED, ANCHOR BOLTS,
NUTS AND WASHERS, SHALL BE SUPPLIED TOGETHER WITH CHILLER.
ANCHOR BOLTS MUST BE FIXED ON THE FOUNDATION PRIOR TO
CHILLER INSTALLATION.
5. UNIT MUST BE LEVELED BEFORE STARTUP.
(HORIZONTAL LEVEL MUST BE BELOW THAN 2mm / 1000mm)

W (ton)

W (ton)

W (ton)

W (ton)

BASE CONTACT

Model
LWM-W003
LWM-W004
LWM-W005
LWM-W007
LWM-W008
LWM-W010
LWM-W012
LWM-W014
LWM-W016
LWM-W019
LWM-W021
LWM-W024
LWM-W027
LWM-W031
LWM-W034
LWM-W038
LWM-W043
LWM-W048
LWM-W054
LWM-W060
LWM-W067
LWM-W074
LWM-W081
LWM-W088
LWM-W095
Note.

Dimension(mm)

Load(ton)

1,471
1,471
1,971
1,926
1,926
2,946
2,946
2,816
2,816
3,836
3,836
3,716
3,716
3,716
3,716
3,706
4,248
4,746
4,188
4,686
5,211
4,286
4,811
5,311
4,811

900
900
900
820
820
820
820
980
980
980
980
1,040
1,040
1,160
1,160
1,600
1,600
1,600
1,800
1,800
1,800
2,100
2,100
2,100
2,300

1,120
1,120
1,120
1,120
1,120
1,120
1,120
1,280
1,280
1,280
1,280
1,340
1,340
1,460
1,460
1,900
1,900
1,900
2,100
2,100
2,100
2,400
2,400
2,400
2,600

195
195
195
245
245
245
245
370
370
370
370
370
370
370
370
370
370
370
420
420
420
420
420
420
420

110
110
110
150
150
150
150
150
150
150
150
120
120
120
120
130
130
130
140
140
140
140
140
140
140

95
95
95
145
145
145
145
270
270
270
270
270
270
270
270
270
270
270
320
320
320
320
320
320
320

1,020
1,020
1,020
1,020
1,020
1,020
1,020
1,180
1,180
1,180
1,180
1,240
1,240
1,360
1,360
1,800
1,800
1,800
2,000
2,000
2,000
2,300
2,300
2,300
2,500

97.5
97.5
97.5
125
125
125
125
185
185
185
185
125
125
125
125
120
120
120
140
140
140
140
140
140
140

1.10
1.15
1.35
2.05
2.15
2.65
2.85
3.45
3.60
4.20
4.45
5,40
5.65
6.70
7.00
9.65
10.45
11.00
13.75
14.75
15.85
17.85
19.10
20.25
25.00

W(ton) : Indicates the chillers weight that one base contact bears.

40 41

Piping Diagram
Water Circuit
Piping Diagram

Keep running a chilled water pump no.1,no.2 and an air conditioner continuously
in order to protect freezing trouble during the dilution opreration.(about 15min.)

HOT WATER OUTLET


HOT WATER INLET

THREE WAY
VALVE

HOT WATER PUMP

AIR
CONDITIONER

HC

COOLING TOWER

WATER SUPPLY

C
CHILLED
WATER
PUMP NO.1

CHILLED
WATER
PUMP NO.2

BYPASS V/V

THERMOSTAT
HOT WATER
ABSORPTION CHILLER
SYM.
T
P
F

SUPPLY HEADER

NAME

SYM.

TEMPERATURE
GAUGE
PRESSURE
GAUGE
FLOWMETER
PUMP

RETURN HEADER
TO DRAIN DITCH

TO DRAIN DITCH

Water Circuit Connection Procedure


GENERAL REMARK ON PIPE-LAYING WORK
1. The range of equipment tobe supplied by LS is enclosed by
the two-dot chain line.(__ _ _ __)
2. For pipe diameter , pipe connections, etc. refer to the mechanical layout diagram. [OUTLINE]
3. The maximum operating pressure in the chilled, cooling and
hot water is 8 kgf/cm2.
(For LWM-W003-W005 5 kgf/cm2 is standard.)
4. Cincerning temperature control of cooling water, refer to
another diagram.
[CONTROL OF COOLING WATER TEMPERATURE] (__ _ _ __)
5. Provide separate chilled, cooling and hot water pumps for
each absorption machine.
Flow rate of chilled, cooling and hot water should confirm to
the specifications.
6. Provide a bleeder in the cooling and hot water line for control
of cooling water quality.
7. Install a strainer having a mesh of or so.

LS Absorption Chiller

8. Provide the inlet and outlet piping for chilled, cooling and hot
water with the stop walve so that the piping can be cleaned
easily.
1) install thermometers and pressure guages at locations convernient for servicing in the inlet and outlet water lines.
2) Install air vent valves for water lines at a position above the
absorption machine.
3) install drain valves for water lines at a Position bottom the
absorption machine, and then ectend them up to the ditch.
4) For chemical cleaning, install the stop valves for cleaning
between the unit and each stop walve at the inlet or outlet.

NAME
STRAINER

DRAIN V/V
CHEMICAL
CLEANSING V/V

VALVE

Control of Cooling Water


Maintenance & Installation
Quality Control of Cooling Water
The cooling water of an open-type recycling cooling
tower lowers temperature of the cooling water using
vaporized latent-heat and is reused. In this case, the
water is evaporated and dissolved salts,
Hardness materials, sulfate ion, etc. in the water will
increase. Namely, condensation phenomena of such
materials occurs in the water, and water quality will grad-

ually be degraded. As the water and air always come in


contact with each other in the cooling
tower, sulfurous acidgas, dust, sand, etc. in the atmosphere will mix into the water, further degrading the water
quality. in the cooling water system, problems with water
are caused by these factors.
Typical problems are corrosion, scales and slimes.

Standard Value of water Quality


Cooling Water
ITEMS
pH(25C)
Electrical conductivity (25C s/cm)
Alkalinity (ppm)
Total hardness (ppm)
Chlorine ion (ppm)
Sulfuric acid ion (ppm)
Total ion (ppm)
Sulfur ion (ppm)
Ammonium ion (ppm)
Silica (ppm)
Free carbonic acid (ppm)

One-pass or
Circulating
6.5~8.0
Max.800
Max.100
Max.200
Max.200
Max.200
Max.1.0
No trace
Max.1.0
Max.50
*******

Make-up
water
6.5~8.0
Max.200
Max.50
Max.50
Max.50
Max.50
Max.0.3
No trace
Max.1.0
Max.30
*****

Chilled Water

Tendency

Circulating
water

Make-up

Corrosion

Scale

6.5~8.0
Max.500
Max.100
Max.100
Max.100
Max.100
Max.1.0
No trace
Max.0.5
Max.50
Max.1.0

6.5~8.0
Max.200
Max.50
Max.50
Max.50
Max.50
Max.0.3
No trace
Max.0.2
Max.30
Max.1.0

O
O

O
O
O

O
O
O
O
O
O
O
O

Control of Cooling Water Temperature

Ensure that the cooling water temperature does not fall more than
10C below the design temperature. For example, if the cooling
water inlet temperature is 32C, ensure that the cooling water
temperature does not fall below 22C. During starting, however,
a lower temperature is permissible until the machine reaches the
rated capacity.

1. Be sure to start and stop the fan by means of the


cooling water thermostat.
2. Cooling water thermostat setting value
(When the cooling water inlet temp. is 32C)
22C and below ... off,
25C and above ... on

42 43

Interface Connection Diagram(Chiller via Utility)


Direct-Fired Chiller(LDF-S010S~S150S)

RUN & STOP FLOW DIAGRAM


OF AUXILIARY EQUIPMENT

LS Absorption Chiller

Steam-Fired & Water Chiller

RUN & STOP FLOW DIAGRAM


OF AUXILIARY EQUIPMENT

44 45

Electric Wiring Circuit of Micro Processor


Direct-Fired Chiller (LDF-S010S~S150S)
Pump
Refrigerant & Absorbent Pump

Chilled & Cooling Water Pump

Burner

LS Absorption Chiller

Main Board

I/O Board

46 47

Schematic Diagram
Steam-Fired Type (LSH-S010~S150)
Pump
Refrigerant & Absorbent Pump

Chilled &
Cooling Water Pump

LS Absorption Chiller

Main Board

I/O Board

48 49

Schematic Diagram
Hot-Water Fired Type (LWM-W030~W102)
Pump
Refrigerant & Absorbent Pump

Chilled &
Cooling Water Pump

LS Absorption Chiller

Main Board

I/O Board

50 51

Specifications subject to change without prior notice.