Professional Documents
Culture Documents
location
duration of
of building
high
internal
temperature
expected
comfort
conditions.
degree of air
movement
percentage saturation
In some buildings it may be possible to maintain acomfortable
environmentwith mechanical ventilation but the air change
rate will tend to be high (above about8air changes per hour)
which can in itself cause air distribution problems.
Since air conditioning is bothexpensiveto install and maintain,
it is best avoided if possible.
This may possibly be achieved by careful building design and by
utilising methods such as:
owindow blinds or
shading methods
oheat absorbing glass
oheat reflecting glass
oopenable windows
ohigher ceilings
osmaller windows on
south
facing facades
oalternative
lighting
schemes.
The diagram below shows some of these methods.
units.
units
Induction
Variable Air
Volume
units
Dual duct systems
Chilled ceiling,
but we will consider the more commonly used methods first.
2.Window/wall units.
Wall unitslike the one shown below are built into an external
wall and contain all the necessary items of equipment to provide
cool air in summer and some may even provide heating in
winter.
AirConditioning
Air Flow Rates
Whendeterminingairflowratesforroomsthatareairconditioned,thefollowingprocedureshouldb
adopted;
1.Calculateheatgains.
2.Completepsychometricchart.
3.Determinemassflowrateofsupplyairfromthefollowing;
m
where;
H=Sensibleheatgain(kW)
m=massflowrateofair(kg/s)
Cp=Specificheatcapacityofair(1.005kJ/kgK)
tr=roomtemperature(oC)
ts=supplyairtemperature(oC)frompsychometricchart.
4.Convertmassflowratetoavolumeflowrate:
Volume flow rate (m3/s)
(kg/m3)
5.ConvertthistoanAirChangerateforcomparison.
Volume flow rate (m3/h)
6.CheckouttherecommendedairflowratefromCIBSEGuideB2
(VentilationandAirConditioning)Section3-Requirements.
Usethehighervalueofairchangeratefordesignpurposes.
Example 1
Determinethesupply,freshairandrecirculationairflowratesfortheSportsCentre(FitnessSuiteN
shownbelow.
SeeAssignmentssectionDrawings.
Theroomistobefullyairconditioned.
DATA
Occupancy=80people
Roomvolume=3740m3.
Roomtemperature=18oCfromtable3.19CIBSEguide.
Sensibleheatgain=70kWfromcalculations(notshown)
SeeHeatGainssectionofthesenotesforfurtherdetails.
Supplyairtemp.=13oCfrompsychrometricchart(notshown)
SeePsychrometricssectionofthesenotesforfurtherdetails.
Supplyairdensity=SeeSciencesectionPropertiesofairdensityat13oCand50%=1.225
kg/m3.
SupplyAirRate
m=H/(Cpx(trts))
m=70/(1.005x(18-13))
m=70/5.025
m=13.93kg/s
Volumeflowrate(m3/s)=massflowrate(kg/s)/densityofair(kg/m3)
=13.93/1.225
=11.37m3/s
Volumeflowrate(m3/h)=Volumeflowrate(m3/s)x3600
=11.37m3/sx3600
=40,932m3/h
SupplyAirRate(AC/h)=VolumeFlowRate(m3/h)/RoomVolume(m3)
=40,932m3/h/3740
=10.9 AC/h
Table3.1SummaryofRecommendations(GuideB2)directstoTable3.19.
FromTable3.19forFitnessCentretheairflowrateis10to12 AC/h.
Usehighervalueof12 AC/hsupplyairrateasfoundfromaboveTable.
Thishighervalueisthenusedtosizeallplantandductwork.
FreshAirRate
Section3.2.1.3Bodyodour(CIBSEguideB2)givesthefollowinginformation;
Therefore in the absence of further information, it is recommended that 8 litre.s-1 per perso
should be taken as the minimum ventilation rate to control body odour levels in rooms with
sedentary occupants.
SincethelevelofactivityishigherthansedentaryintheFitnessRoom,wewilladoptafreshairrate
l/sperperson.
Freshairrate=24l/sx80people
=1920l/s
=1.92m3/s
=1.92x3600=6912m3/h
=6912m3/h/3740=1.9 AC/h
Percentagefreshair;1.9/12.0(x100%)=15.8%
RecirculationAirRate
RecirculationAirRate=Supplyairrate-Freshairrate
=12.0-1.9
=10.1 AC/h
Percentagerecirculationair;10.1/12.0(x100%)=84.2%
Theairflowratesareshownonthediagrambelow.
AslightnegativepressuremaybeprovidedintheFitnessRoom.
ThisissothatcontaminatedairdoesnotentertheadjoiningReception/Foyerarea.
TheReturnairamountmaybeincreasedto110%ofthepreviouslycalculatedvalue;thatis,13.2
AC/hor13.72m3/s.
Introduction
Heat gains from the sun can lead to increases in internal temperatures beyond t
This is usually above24oCdry bulb temperature in theUK.
A software programme such asHevacompis often used to determine the interna
for a building.
It is therefore necessary to determine the amount ofsolar radiationthat is trans
windows, walls, roof, floor and by admitting external air into the building.
Several measures can be adopted to reducesolar radiationin buildings.
These are external and internal shading and by careful building design.
Natural vegetation such as talltreescan also reduce solar heat gains.
Window areas can be reduced although natural day lighting is important in north
there is a limit to glass reduction.
Buildings can be orientated so that there is less window area facing directly sou
These are just some of the ways to reducesolar radiation.
The load on an air-conditioning system can be divided into the following section
1.Sensible Transmission through glass.
2.Solar Gain through glass.
The heat gain through the glass windows is divided intotwoparts since
totemperature differencebetween outside and inside and another gain due tos
windows.
The method adopted uses theCIBSE guide A (2006)andCIBSE Guide J (2002).
The Tables that are referred to areCIBSE guide A (2006)Solar cooling loads inTa
CIBSE Guide J (2002)Air and Sol-air temperatures inTable 5.36 (London), Table 5
5.38 (Edinburgh)
This is the Solar Gain due to differences between inside and outside tempera
this can be quite significant.
This gain only applies to materials of negligible thermal capacityi.e. glass.
The cooling loads per metre squared window area have been tabulated inCIBSE
5.24for various; locations, times, dates and orientations.
These figures are then multiplied bycorrection factorsfor; shading and air node
Heat load is found from;
The Air point control factors (F c) and Shading factors (Fs) are given in the Tab
glass, building weights and for open and closed blinds.
Type of glass
Clear 6mm
The CIBSE guide method of calculating solar gains through glazingin Guide A
slightly different formula as follows;
Qsg=S . qsg. Ag
Internal gains can account for most heat gain in buildings in theU.K.
These gains are fromoccupants, lights, equipment and machinery,as detailed b
OCCUPANTS - Sensible and latent heat gains can be obtained fromCIBSE Guide
Typical gains are shown below.
Conditions
Seated very light work
Moderate office work
Standing, light work; walking
Walking standing
Sedentary work
Light bench work
Athletics
4.1Sol-Air Temperature
In the calculation of this heat flow use is made of the concept ofsol-airtempe
the value of the outside air temperature which would, in the absence of all
same rate of heat flow into the outer surface of the wall as the actual combina
and radiation exchanges.
SOL-AIR TEMP,
teo=ta+( ).....
where
teo=sol-air temperature (oC)
ta=outside air temperature (oC)
=absorption coefficient of surface
4.2Thermal Capacity
The heat flow through a wall is complicated by the presence ofthermal capac
passing through it is stored, being released at a later time.
Thick heavy wallswith a high thermal capacity will damp temperature swings co
wallswith a small thermal capacity will have little damping effect, and flu
temperature will be apparent almost immediately.
The thermal capacity will not affect thedaily mean solar gainbut will affect
time.
The particular timeof a solar gain is normally the time of the maximum gain.
The heat gain arrives at the inside of a thick wall some time after the sun hits th
This time lag is.
The calculation is, therefore, again split into two components.
1. Mean gain through wall,
Q=f ( teo-tem).
A=area of wall (m 2)
The heat gain through a roof uses the same equation as for a wall as shown belo
Recommended infiltration rates are1/2 air change per hourfor most air-condit
per hourfor double glazing or if special measures have been taken to prevent in
Ventilation or fresh air supply loads can be added to either the roomorcentral
accounted for once.
Qtotal=Qg+Qsg+Qint.+Q +Wall+Q
Therefore, it will be this gain which determines when the total heat gain to the r
Heat gains may be calculated and displayed in table form as shown below.
Heat Gain from
1.
2.
3.
4.
5.
6.
Latent Gains
Example1
The outsideair temperature(to) may be found from CIBSE Guide J (2002) - Table
The maximum value ocurrs at 16.00 hrs. and is25.4oC.
DATA:
Occupants=100
Infiltration=0.5 air changes per hour
Building classification=lightweight,
Building response=fast.
NOTE:It should be noted that this total heat gain is used to size central
Condensers andCoolingTowers.
Cooling coils are sized usually with a pschrometric chart.
Answer
Areas:
Area of window=1.2 x 1.7 = 2.04 m 2.
Total area of glass=2.04 x 12No. windows=24.4
Area of glass facing South=12.24 m 2.
Gains:
1.Sensible transmission through glassQg=AgUg(to-tr)
Qg=24.48 x 2.8
Qg=301.6 Watts
Qsg=2,518.4 Watts
3.InternalQint.=Qint.
Qint.=Lights (30 W/m2x 308)+ 4000 W+ Peop
Qint.=9,240+4,000+10,000
Qint.=23,240.0 Watts
Qtotal=301.6+2,518.4+23,240.0+413.5+0+
Qtotal=27,377 Watts
The results are shown in the table below.
Example2
The outsideair temperature(to) may be found from CIBSE Guide J (2002) - Table
The maximum value ocurrs at 16.00 hrs. and is25.4oC.
DATA:
Occupants=80
Lighting=35Watts / m 2floor area
Infiltration=0.4air changes per hour
Building classification=lightweight with fast response.
External wall surface texture=dark.
Answer
Areas:
Area of window=1.2 x 1.7 = 2.04 m 2.
Total area of glass=2.04 x 10No. windows=
Area of glass facing South West=10.2 m 2.
Gains:
3.InternalQint.=Qint.
Qint.=Lights (35 W/m2x 288)+ 3000 W+ Peop
Qint.=10,080+3,000+8,000
Qint.=21,080.0 Watts
4.External wallQ Wall=A U [( tem-tr)
where,
Q=heat gain through wall at time(Watts)
7.Qtotal=Qg+Qsg+Qint.+Q Wall+QRoof+Qsi
Qtotal=233.4+2,892.3+21,080.0+171.9+0+5
Qtotal=24,884.5 Watts
The results are shown in the table below.
Heat Gain from
1.
2.
3.
4.
5.
6.
The heat gain in the previous example was88.8 W/m2floor area and the total w
The heat gain in this example is86.4 W/m2floor area and the total is24,884.5
The value of sensible heat gain can be used in a psychrometic chart to determin
Air Handling Unit (AHU).
Example3
Answer
Areas:
Area of window=1.4 x 2.0 = 2.8 m 2.
Total area of glass=2.8 x 10No. windows=28.0 m 2.
Area of glass facing South=14.0 m 2.
=Rafter len
300.
=Rafter leng
= 5.774 metres
Ceiling area=14x2 (5.774)=161.7 m 2.
Room volume=140m 2x3+( 14 x 5 x 2.9 )=623 m 3.
Gains:
Wall is type 8(e) and the decrement factor is 0.42,time lagis 8.8 hour
If the maximum solar heat gain is at 12.30 pm and the time lag is 8.8 h
relevant sol air temperature is;
12.50 -8.8 = 3.7 sayis at 4.00 am.
QWall=14.56[ 3.8 + - 5
since it happens so early in the morning and will be neglected.
QWall=14.56[ 3.8]
QWall=55 Watts
5.Roof
Find decrement factor (f) from CIBSE Guide A (2006) Table 3.50, use info
The decrement factor is 0.88,time lag is 3.0 hours, U value 0.23 W/m
If the maximum solar heat gain is at 12.30 pm and the time lag is 3.0 h
relevant sol air temperature is;
is at 12.30 hrs -3.0 = 9.30 hrs
7.Qtotal=Qg+Qsg+Qint.+Q Wall+QRoo
Qtotal=470+2,880+12,080+55+703+
Qtotal=17,434 Watts
Building Weight
Light
Heavy
Light
Heavy
Light
Heavy
Light
Heavy
Typical building
Offices, hotels, apartments
Offices, hotels, apartments
Department store, retail store
Bank
Restaurant
Factory
Gymnasium
Watts
Watts
301.6
2,518.4
23,240.00
413.5
0
903.5
27,377
Watts
233.4
2,892.30
21,080.00
171.9
0
506.9
24,884.50
Watts
470
2,880
12,080
55
703
1,246
17,434
on factors (Fc)
Single Glaz
Horizontal bl
0.91
0.83
ctors (Fs)
Single Glaz
Open horizontal blind
1
0.97
0.86
0.85
0.78
0.77
0.64
0.62
100%
%
1.1
9.2
84.9
1.5
0
3.3
100%
%
0.9
11.6
84.7
0.7
0
2.1
100%
%
2.7
16.5
69.3
0.3
4.0
7.2
100%
Single Glazing
Horizontal blind
0.91
0.83
Single Glazing
Closed horizontal blind
0.77
0.77
0.77
0.77
0.73
0.73
0.57
0.57
Double glazing
Horizontal blind
0.91
0.9
Double glazing
Open
Closed
horizonta horizonta
l blind
l blind
0.95
0.74
0.94
0.76
0.66
0.66
0.54
0.53
0.48
0.47
0.55
0.57
0.47
0.48
0.41
0.41
Fin and tube heat exchangers are used extensively forheating and cooling air.
one or more rows of finned tubes connected to headers and mounted within a sh
casing with flanged ends suitable for duct mounting.
Heating coilsmay be used with hot water or steam as the heat transfer media
heaters usually have electric heating elements.
Usually the flow of water and air are in opposite directions to each other, this be
ascounter-flow heat exchanger.
This configuration gives maximum heat transfer.
Latent heatis absorbed by the air stream from the refrigerant as the refrigeran
With this type of coil, as with steam, there is no distinction made between paral
flow since the surface temperature is more uniform owing to the refrigerant in th
at aconstant temperature.
Whendirect expansioncoils are used they become the evaporator of the refri
and may be termed either dry orflooded.
In thefloodedDX coil most of the coil is filled with liquid refrigerant and altho
efficient, it is not used so much in air-conditioning since the additional refrigeran
The copper tubing runs perpendicular to the aluminium fins, making U-turns bac
until the desired coil size is achieved.
The cooling effect that takes place inside the coil requires apressure dropin the
This drop can be accomplished in a number of ways: capillary tube, piston or ori
thermostatic expansion valve.
Acapillary tubeis a thin copper tube of predetermined length into which the c
liquid refrigerant is pumped.
The length of the tubing causes thepressure dropand subsequent cooling effe
refrigerant.
A piston or orifice blocks the flow of refrigerant and forces it through a tiny hole,
needed pressure drop.
It determines this demand by way of a sensing bulb attached to the outlet tube
Because it can meter the flow to meet demand, theexpansion valvecan keep
optimum cooling potential.
Because the cooling coil is an integral part of the air distribution system, itsgeo
number of rows, fin spacing, and fin profile contributes to the airside pressure
affects the sound power level of the fans. (Fan power needed to circulate air thro
system may warrant extra sound attenuation at the air handler.)
Water Removal
Moisture in air can condense in the air stream or when the air impinges upon a
solidcoolsurface.
This can happen at sharp bends where water collects in a puddle at the lower su
ductwork.
Droplet separators have been developed to remove water droplet carry-over fro
They consist of a media that can absorb thewater dropletsand transport them
the material to the drainage section.
The system shown below uses aglass-fibre-based materialand the droplet s
best with air velocities between 0 and 4 m/s.
The media is so efficient that it can arrest100 litresof water per cubic metre of
Some droplet separators are produced as cassettes to ensure easy handling. sev
can be linked together to achieve the desired surface area.
HeaterBatteryPipework
Chilled-watercoolingcoilsarefinned-tubeheatexchangersconsistingofrowsoftubes(usuallycopp
throughsheetsofformedfins(usuallyaluminium).Asairpassesthroughthecoilandcontactstheco
transfersfromtheairtothewaterflowingthroughthetubes.
Thefollowingequationquantifiestheheat-transferprocess:
Q=UALMTD
Where,
Q=amountofheattransferred,Btu/hr(W)
U=heat-transfercoefficient,Btu/hrftF(W/mK)
A=effectivesurfaceareaforheattransfer,ft(m)
LMTD=log-meantemperaturedifferenceacrossthecoilsurface,F(
Increasinganyoneofthesevariables(heat-transfercoefficient,surfacearea,orlog-meantemperatu
inmoreheattransfer.
Arguablythemosteffectivewaytoimproveheat-transferperformanceistoincreasethelog-meante
difference(LMTD).Inthecontextofachilled-watercoolingcoil,LMTDdescribesthedifferencebe
temperaturesoftheairpassingacrossthecoilfinsandthewaterflowingthroughthecoiltubes:
LMTD=(TD2TD1)/ln(TD2/TD1)
Where;
TD1=leaving-airandentering-watertemperaturedifferenceatthecoil
TD2=entering-airandleaving-watertemperaturedifferenceatthecoil
OnewaytoincreaseLMTDistosupplythecoilwithcolderwater.
Heat-transfer coefficient, Q=UALMTD
Thermal conductancedescribestherateatwhichheatflowsthroughthealuminiumfinsandcop
Systemdesignerscandolittletoaffectthermalconductance,buttheycanalterthefilmcoefficients.
of airflowreducesheat-transferresistanceontheairsideofthecoolingcoil.Likewise,increasingthe
velocityreducesthewatersideresistancetoheattransfer.
Fin geometrycan improve the overall heat-transfer coefficient, too, by lessening the airside film coeffi
Turbulent water flow, like turbulent airflow, also reduces resistance to heat transfer. And, like fin geom
Bothmethodsofimprovingtheheat-transfercoefficient(increasedvelocityandturbulence)createhi
whichcanmeanadditionalfanorpumppower.
Coil surface area, Q=UALMTD
Thethirddeterminantofheattransferisthecoilssurfacearea.Typically,fin spacingforcomforthe
rangesfrom24to50finspermetre.Spacingthefinsclosertogethermultipliesthesurfaceareabype
perlinearunit.Althoughtheairsidepressuredropmayincrease,addingfinsextendstheavailablesu
affectingtheoverallsizeofthecoil.
Addingrowsoftubesalsoincreasestheheat-transfersurfacearea.Mostcoilsareconstructedwithsa
connections,sorowsareusuallyaddedinpairs.Theweightandcostofthecoilincreaseaccordingly
pressuredropmaynot.(Widerfinspacingoftenaccompaniesthedecisiontoaddrows.)
Thebestwaytoextendthesurfaceareaforheattransferistodecreasetheface velocityofthecoil,t
relative to airflow:
facevelocity=airflow/facearea
Facevelocitycanbereducedinoneoftwoways:byincreasingthesizeofthecoilor(paradoxically)
requiredairflow.Selectingaphysicallylargercoilincreasestheinitialinvestmentinthecoilandthe
alsoenlargetheair-handlerfootprint...seldomdesirableoutcomes.So,howcanwereducetherequi
sacrificingcoilcapacity?
Loweringthesupplyairtemperaturereducestheamountofairrequiredforsensiblecoolingandsave
ourreviewoftheheat-transferequation,weknowthat:lessairflowincreasesairsidefilmresistance,
transfercoefficientU;andrequirescolderair,whichdecreasesLMTD.
Tocompensateforthenegativeeffectsoncoilperformancethataccompanylessairflow,wemustfin
increaseU(heat-transfercoefficient)and/orA(surfacearea).Inotherwords,wemustselectacoolin
than-averageheat-transfercharacteristics.
Increase U
Recallthatturbulentflowreducesthefilmresistancetoheattransfer.Choosingafinconfigurationw
pronouncedwaveformand/oraddingturbulatorsinsidethecoiltubeswillimprovetheheat-transferc
Increase A
Anyadditionalincreaseinheat-transfercapacitymustbeachievedbyphysicallyincreasingtheavail
thatis,by:
Adding rows
Adding fins
Increasing the physical size of the coil (which will increase the initial costs of the coil, air ha
accessories).
Introduction
The aim of this section of the notes is to allow students to size air conditioning plant such as;
cooling coil, heater battery and humidifier.
The notes are divided into several sections as follows:
PSYCHROMETRY FOR AIR CONDITIONING
THE PSYCHROMETRIC CHART
EXAMPLES OF PSYCHROMETRIC PROPERTIES
AIR CONDITIONING PLANT FOR SUMMER & WINTER
BASIC PROCESSES
TYPICAL AIR CONDITIONING PROCESSES
ANNOTATION AND ROOM RATIO
SUMMER AND WINTER CYCLES
EXAMPLES
The first section deals with Psychrometry for air conditioning and discusses some properties o
A simplified psychrometric chart is shown for familiarisation, and some examples of how to find
are provided.
A diagram of an air conditioning system is shown in schematic form in the section entitled AIR
PLANTFORSUMMER&WINTER.
Before sizing takes place the student should also understand the processes that take place in
systems.
There are four basic processes for summer and winter air conditioning systems.
The following basic processes are explained:
1. Mixing
2. Sensible Cooling and Heating
3. Cooling with Dehumidification
4. Humidification
The section on Typical Air Conditioning Processes shows winter and summer schematic diagra
psychrometric charts.
There are some more details that may be useful to the designer of air conditioning systems.
Further information is as follows: Annotation, Room ratio
When the processes have been superimposed onto a psychrometric chart then calculations m
These are as detailed in the following sections of the notes.
Summer and Winter Cycles
1. Summer cycle psychrometrics
2. Summer cycle calculations
3. Winter cycle psychrometrics
4. Winter cycle calculations
5. Duct and Fan gains.
The final section is seven examples of plant sizing using psychrometric charts.
Nitrogen 78.03%, Oxygen 20.99%, Argon 0.94%, Carbon Dioxide 0.03%, and Hydrogen 0.01%
The Ideal Gas Laws are used to determine psychrometric data for air so that the engineer can
calculations.
To make life easier a chart has been compiled with all the relevant psychrometric data indicate
This is called the Psychrometric Chart.
A typical chart is shown below.
This is the air temperature measured by a mercury-in-glass thermometer which has the mercu
gauze that is kept moist by a reservoir of water.
When exposed to the environment the moisture evaporates from the wetted gauze, which give
reading on the thermometer.
This gives an indication of how dry or how moist the air is, since in dry air the water will eva
from the gauze, which depresses the thermometer reading.
3. Moisture content
This is the amount of moisture in air given in kg of moisture per kg of dry air e.g. for room air a
and 15oC wet bulb, the moisture content is about 0.008 kg/kg d.a.
This is a small mass of moisture ( 0.008 kg = 8 grams) per kg of dry air or 9.5 grams per cubic
4. Percentage saturation
The Percentage saturation is another indication of the amount of moisture in air.
This is the ratio of the moisture content of moist air to the moisture content of saturated air at t
temperature.
When air is saturated it is at 100% saturation and cannot hold any more moisture.
5. Specific enthalpy
This is the amount of heat energy (kJ) in air per kg.
If heat is added to the air at a heater battery for example, then the amount to be added can be
from Specific enthalpy change.
6. Specific volume
This is the volume of moist air (dry air + water vapour) per unit mass.
The units of measurement are m3 per kg.
Also specific volume = 1 / density.
The six properties of air previously discussed can be shown on one chart called a Psychromet
One of the purposes of the Psychrometric Chart is to size heater batteries, cooling coils and hu
A simplified Psychrometric Chart is shown below.
If any two properties of air are known then the other four can be found from the psychrometric
Find the moisture content of air at 25oC dry-bulb temperature and 25oC wet-bulb temperature.
Referring to the chart below, a vertical line is drawn upwards from 25oC dry-bulb temperature u
25oC wet-bulb temperature.
This intersection point happens to be on the 100% saturation line.
The intersection point is highlighted and a horizontal line is drawn to the right to find the corres
content.
The moisture content is therefore 0.020 kg/kg dry air.
EXAMPLE 2
Find the specific volume and wet-bulb temperature of air at 20oC dry-bulb temperature and 50%
Referring to the chart below, a vertical line is drawn upwards from 20oC dry-bulb temperature u
with the 50% saturation curve.
The intersection point is sometimes referred to as the state point.
The specific volume is found to be 0.84 m3/kg and the wet-bulb temperature is 14oC
EXAMPLE 3
Find the specific volume, percentage saturation and moisture content of air at 15 oC dry-bulb te
10oC wet-bulb temperature.
Referring to the chart below, a vertical line is drawn upwards from 15oC dry-bulb temperature u
with the 10oC wet-bulb temperature line.
This intersection is the state point.
The specific volume is found to be 0.823 m3/kg, the percentage saturation 52% and the moistu
content 0.0054 kg/kg d.a.
EXAMPLE 4
Find the specific volume, wet-bulb temperature, moisture content and specific enthalpy of air a
temperature and 30% saturation.
Referring to the chart below, a vertical line is drawn upwards from 35oC dry-bulb temperature u
with the 30% saturation curve.
This intersection is the state point.
The specific volume is found to be 0.883 m3/kg, the wet-bulb temperature is 22oC, the moistur
content 0.011kg/kg d.a.and the specific enthalpy 65 kJ/kg.
In the summer time when cooling is required by the air conditioning plant it will be necessary to
the cooling coil,reheater and possibly other plant as well.
In winter time the preheater and reheater battery will probably be on to provide warm air to ove
losses.
Other plant may be switched on as well.
These plant items are shown in the diagram below.
Where two air streams are mixed the psychrometric process is shown as a straight line betwee
conditions on the psychrometric chart, thus points 1 and 2 are joined and the mix point 3 will lie
Two air streams are mixed in air conditioning when fresh air (m1) is brought in from outside and
with recirculated air(m2).
The resulting air mixture is shown below as (m3).
m1 + m 2 = m 3
m1 h1 + m2 h2 = m3 h3
When air is heated or cooled sensibly, that is, when no moisture is added or removed, this proc
represented by a horizontal line on a psychrometric chart.
where:
The most commonly used method of removing water vapour from air (dehumidification) is to co
its dew point.
The dew point of air is when it is fully saturated i.e. at 100% saturation.
When air is fully saturated it cannot hold any more moisture in the form of water vapour.
If the air is cooled to the dew point air and is still further cooled then moisture will drop out of th
of condensate.
This can be shown on a psychrometric chart as air sensibly cooled until it becomes fully satura
point is reached) and then the air is cooled latently to a lower temperature.
This is apparent on the psychrometric chart as a horizontal line for sensible cooling to the 100%
curve and then the process follows the 100% saturation curve down to another point at a lower
This lower temperature is sometimes called the Apparatus dew Point (ADP) of the cooling co
In reality the ADP of the cooling coil is close to the cooling liquid temperature inside the coil.
Chilled water or refrigerant may be the cooling liquid.
The psychrometric process from state point 1 to 2 to 3 may be shown as a straight line for sim
above with a yellow line.
In the absence of a suitable psychrometric chart the following formula may be used;
The sensible heat removed is:
where:
H
m
Some of the air going through a cooling coil does not come into contact with the tubes or fins o
and is therefore not cooled to the ADP temperature.
A mixing process therefore takes place as two air streams mix downstream of the cooling coil a
One air stream is cooled down to the ADP and the other air stream by-passes the coil surfaces
coil air temperature (mixed air stream) a little higher than the ADP.
This may be looked upon as an inefficiency of the coil and is usually given as the cooling coil c
The process is shown on the psychrometric chart below.
If is it necessary to add some moisture to the supply air then this is best done by injecting stea
stream.
Humidification can be carried out by spraying a fine mist of water droplets into the air but this is
recommended in rooms occupied by people due to the risk of bacteria carry over.
Dry steam may be injected from a steam supply pipe or generated in a local packaged unit as
photograph below. A disadvantage of using an existing steam supply is smells may be carried
The steam package unit is situated close to the air duct and is sized to meet the maximum req
usually in winter in the U.K.
A steam pipe ( sometimes hoses are used) passes from the packaged unit to the air duct and
injected into the air stream via. a sparge pipe. The un-used steam is drained from the system v
tundish and drain. It is important to layout the steam pipework so that any condensate will drain
The psychrometric process is shown below.
See Summer and Winter Cycles section for calculation of amount of moisture added at humidi
The schematic diagram below shows a typical plant system for summer air conditioning.
The schematic diagram below shows a typical plant system for winter air conditioning.
Annotation
The state points on a psychrometric chart may be given numbers or symbols to identify them.
used the following system may be adopted:
Room Ratio
This is the ratio of sensible to total heat in the room for summer or winter.
The total heat gain (summer) or loss (winter) will be determined by adding the Latent and Sens
room or rooms, i.e.
(SUMMER)
(WINTER)
Total heat
The room ratio is used on a psychrometric chart to determine the supply air state point.
A room ratio line is superimposed from the protractor on the psychrometric chart onto the main
by a line passing through the room state point R.
An example calculation is as follows:
Sensible heat gain
9.0 kW
2.25 kW
9.0 kW + 2.25 kW
Room ratio
Room ratio
9 / 11.25
11.25 kW.
0.8
The supply air state point must also be somewhere on this room ratio line to meet the room he
requirements i.e. the room ratio line always passes through points R and S.
A room is to be maintained at 22oC dry-bulb temperature, 50% saturation, when the sensibl
10.8 kW in summer.
The latent heat gain is 7.2 kW.
Determine the cooling coil and reheater outputs required by using a psychrometric chart if t
schematic is as shown below.
DATA:
Outdoor condition is 28oC, 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
The Apparatus Dew Point ADP is 8oC
Neglect the cooling coil contact factor.
Note:
The cooling coil output of 38.2 kW is a much higher value than the sensible heat gain of 10
It should be remembered that the difference is these two values is mostly from the fresh air
It takes quite a lot of energy in summer to cool fresh air coming into air handling units.
This can be minimised by bringing in minimum fresh air but not too little otherwise the build
from lack of oxygen and feel stuffy.
That is why psychrometric charts are required to calculate cooling coil output including fresh
So, dont size cooling coil and indoor cooling units on sensible heat gain only if there is fres
the plant.
Size these items of plant using a psychrometric chart.
A room has a 18.0 kW sensible heat loss in winter and a 4.5 kW latent heat gain from the o
Determine the supply air temperature and heater battery load using the following informatio
DATA:
Indoor condition: 21oC dry-bulb temperature, 50% saturation.
Outdoor condition: -2oC d.b., 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
No preheating or humidification takes place in this simplified example.
4. No Preheater condition P
5. Join points O and R
6. Find the mix point M by measuring the length of the line O-R
and multiply this by the mixing ratio.
On a full size CIBSE psychrometric chart this measures 110mm.
The ratio of recirculated air is 0.therefore;110mm x 0.8 = 88mm
Measure up theO-R line from pointO by 88mm.
This determines pointM .
If there is more recirculated air than outside air at the mix point, then point M will be closer t
point O.
7. Find the room ratio.
This is the sensible to total heat ratio.
Neglect signs ie. the total heat for the room will be Sensible loss plus Latent gain.
Total heat = 18 kW sensible + 4.5 kW latent = 22.5 kW total.
Heat ratio = 18 / 22.5 = 0.8
Plot this ratio on the protractor, top segment, on the psychrometric chart and transfer this lin
so that it passes through point R.
This is on a horizontal line from point M to the right hand side of the chart, and inters
RRL.
When the sensible heat loss and supply air temperature in winter are known then the mass
calculated from the following formula:
Hs = ma x Cp ( ts - tr )
where:
Hs
=
ma
=
Cp
tr
ts
..............th
ma = Hs / Cp ( ts - tr )
ma = 18 / 1.01 (32.5 - 21)
ma = 18 / 11.615
ma = 1.55 kg/s
Determine the cooling coil and reheater outputs required by using a psychromet
plant schematic is as shown below.
DATA:
Outdoor condition is 28oC, 80% saturation.
The outdoor air and recirculated air ratio is; 20% / 80%.
The Apparatus Dew Point ADP is 8 oC
The cooling coil contact factor is 0.8. (See explanation of contact factor in page
5.Find the mix pointMby measuring the length of the lineO-Rand multiply
mixing ratio.
On a full size CIBSE psychrometric chart this measures 85mm.
The ratio of recirculated air is 0.8...therefore;85mm x 0.8 = 68m
Measure down theO-Rlinefrom pointOby 68mm.
This determines pointM.
6.Find the room ratio.This is the sensible to total heat gain ratio.
Total heat = 8 kW sensible + 2 kW latent = 10 kW total.
Heat ratio = 8 / 10 = 0.8
Plot this ratio on the protractor, bottom segment, on the psychrometric chart an
line onto the chart so that it passes through pointR.
7.Plot the Apparatus Dew PointADPof the cooling coil.
This is on the 100% saturation curve.The ADP is 80C.
8.Join pointsMandADP.
ma=1.584 kg/s
where:
Hcooling coil=Cooling coil output (kW)
ma=mass flow rate of air (kg/s)
HeaterBatteryOutput
The heater battery or reheater output is as follows:
Hheater battery=ma( hS- hW)
where:
Hheater battery=Heater battery output (kW)
ma=mass flow rate of air (kg/s)
Example 4.
Determine the preheater and reheater outputs required and the amount of moisture to be adde
humidifier in litre/hour, by using a psychrometric chart if the plant schematic is as shown below
DATA:
Outdoor condition is -2oC, 80% saturation.
The outdoor air and recirculated air ratio is 50%/50%.
Maximum occupancy is 250 people.
The preheater off coil temperature is 5oC.
Supply air quantity is 8 air changes per hour.
Room volume is 20 x 12 x 4m high = 960 m3.
40 W/person x 250 =
10 kW
10,000 Watts
8 x 960(m3)
7680 (m3/h)
= 2.45 kg/s
The Preheater process will be a horizontal line from O to P and acts as a fro
case, heating the air to 5oC.
4.
Join points P and R.
5.
Find the mix point M by measuring the length of the line P-R
and multiply this by the mixing ratio.
The line measures 82mm long.
82 x 0.5 = 41 mm
6.
Find the room ratio.
Plot this ratio on the protractor, so that it passes through point R.
Total heat is 17 kW sensible + 10 kW latent = 27kW.
Ratio is 17/27 = 0.63.
Hs
ma x Cp ( ts - tr )
where:
Hs
=
ma
=
Cp
tr
ts
( ts - tr )
8.
Hs /
ma x Cp
( ts - tr )
17 / 2.45 x 1.01
( ts - tr )
6.87 deg.C
( ts - 21)
6.87 deg.C
ts
21 + 6.87 deg.C
ts
9.
Plot condition H on the psychrometric chart.
This is vertically down from point S, and horizontally across from point M.
This is because M-H is the reheater process and thus a horizontal line and H-S is the humi
and is close to a vertical line if steam is used.
Humidifier Output
The amount of moisture added to the air may be calculated from the following formula:
m sS
m sH
Example 5
Use CIBSE guide B2 (2001) to determine air flow rates and calculate the mass flow rate of
supply air to the room.
The lecture room may be taken as an Assembly hall.
The room is a non-smoking area.
Information from CIBSE Guide B2 (2001) Table 3.3 is as follows (see Ventilation Ventilatio
The recommended outdoor air rate is 8 l/s/person for non-smoking.
Information from CIBSE Guide B2 (2001) Table 3.1 is as follows (see Ventilation Ventilatio
Assembly halls and auditorium refers to Table 3.6 (see Ventilation Ventilation rates section
The recommended total air supply rate is 6 10 air changes per hour for high level mecha
Fresh Air Flow Rate
1600 l/s
1.6 m 3/s
The specific volume at the outside condition may be determined from a psychrometric chart
Mass flow rate = Volume flow rate / specific volume
Mass flow rate (Fresh Air) = 1.6 / 0.88
=
1.82 kg/s .
Supply Air Flow Rate
If the maximum ventilation supply air rate is taken from Table 3.6 to be 10.0 air changes pe
mass flow rate can be calculated.
=
=
=
=
2.5 m 3/s.
The specific volume at the supply condition may be approximated at this stage from a psych
is 0.834 m3/kg.
Mass flow rate (Supply Air) =
2.5 / 0.834
=
3.0 kg/s.
In this example the supply air temperature will be found by rearranging the following formula
Hs
ma x Cp ( tr - ts )
where:
Hs
=
ma
=
Cp
tr
ts
( tr - ts )
Hs / ( ma x Cp )
( tr - ts )
( tr - ts )
since tr
ts
ts
=
=
=
=
=
12 / ( 3.00 x 1.01 )
3.96 deg.C
22oC
22 - 3.96 =
18.04 oC
18 oC approx.
2. Point ADP can be indicated and lines drawn between these points as shown.
3. The room ratio line can be drawn.
4. Point S is then shown on the chart, on the room ratio line at 18 oC.
5. A horizontal line is then drawn from point S towards the line O ADP.
6. Point W can then be found where the horizontal line W - S intersects the line O - ADP.
From the psychrometric chart point W is at approximately 9 oC dry bulb.
The heat ratio is 12 kW sensible / 22 kW total = 0.545.
H cooling coil
ma (hM - hADP)
where:
H cooling coil
ma
hM
=
specific enthalpy at condition M (kJ/kg)
from psychrometric chart.
hADP =
specific enthalpy at condition ADP (kJ/k
from psychrometric chart
3.00 ( 64 - 24)
H cooling coil =
120.0 kW
H heater battery
ma ( h S - h W )
where:
H heater battery
ma
=
=
hS
=
specific enthalpy at condition S (kJ/kg)
psychrometric chart.
hW
=
specific enthalpy at condition W (kJ/kg
from psychrometric chart.
The specific enthalpies at pointsW andSare shown on the psychrometric Chart above
H heater battery =
H heater battery =
Example 7
3.00 ( 36 - 26.5)
28.5 kW
HEAT GAINS
Sensible (200 x 80) + (100 x 80) + ( 15 x 24 x 10) = 27,600 Watts = 27.6 kW + sola
kW = 32.6 kW
Latent
Total heat gain
Room ratio
When the supply air temperature has been found from the psychrometric chart then the ma
to offset heat gains can be calculated from the following formula:
ma
Hs / ( Cp ( tr - ts ) )
where:
H s = Sensible heat gain to room (kW)
m a = mass flow rate of air (kg/s)
C p = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
The supply air temperature is 14.5oC.
ma
ma
=
=
ma ( hM - hADP)
hM
hADP =
H cooling coil
105.4 kW
=
=
hS
hD
The specific enthalpies at pointsS andDare shown on the psychrometric Chart above
H heater battery =
H heater battery =
6.5 kW
Displacement Ventilation
The previously cooled air rises slowly to the ceiling when it is heated by the room
ceiling level.
The diagram below shows awall mountedoutlet but under floor outlets can also
The temperature of the stratified layer near the ceiling can be allowed to rise ab
because itisabove the occupied zone.
The cooling capacity of displacement ventilation systems is about40 W/m2.
The rate of air supply is typically around 4 air changes per hour.
The supply air is not too cold (about18oCis not unusual) thus reducing theamo
energy input at chillers.
The system is sometimes combined with active cooling systems such aschilled
cooling capacity.
Ideally, a minimum floor to ceiling height of2.7 mis required.
Appropriate diffusers must be selected.
Natural convection from internal heat sources, such as occupants and equipmen
movementin the room.
The more heat there is in the room the quicker the air will rise.
The warm, contaminated air forms a stratified region above the occupied zone,
high level.
Some advantages are as follows;
Useless energythan conventional systems.
Quiet.
Some disadvantages are as follows;
There arealternative methodsof cooling buildings other than full comfort air co
These include;
Night-time cooling
Evaporative cooling
Ice storage
Chilled beams and ceilings
Hollow floor slabs with air
Cooling air by subsoil or water
Night-time Cooling
This is particularly suited to areas where the summer temperature drops off at n
The system is improved by having building fabric exposed to the cooling effect o
time air as shown below.
Evaporative Cooling
As water is sprayed into an air stream thewater evaporates.
The heat that allows the water to evaporate (the latent heat of vaporisation) is t
the air thus causing adrop in the dry bulbtemperature.
This is demonstrated on the psychrometric chart below.
The exhaust louvre for this system must be well away from the fresh air intake l
ensure nocross contaminationof air streams.
The efficiency of the system relies on the efficiency of the heat exchanger.
The best heat exchangers at present arethermal wheels.
Many systems already incorporate a heat exchanger in the exhaust to recover h
winter.
A plentiful supply of water is required to add at the humidifier.
Ice Storage
The storage oficecan be used to provide chilled water for; cooling coils, fan coi
induction units or chilled beam/ceiling.
The advantage of using ice is that it acts as abuffer.
In ice storage systems refrigeration plant generates an ice bank duringoff-pea
which is melted to provide chilled water for use during peak periods.
The cool air descends into the room through outlet slots on the underside of the
The chilled ceiling operates by radiation heat exchange and does not involve co
fan assisted air movement.
Theslab is cooledby chilled air or night time cool air so that the concrete mass
lowered temperature.
The system has several advantages;
Dampens swingsin internal temperature due to high thermal
concrete.
Uses existing space in slabs for transporting air.
Uses the cooler slab as a means of keeping the building air cond
without the need for ductwork.
Hollow Floor Slab systems can offset heat gains up to 30 W/m 2where the under
slab is not exposed and 50 W/m2where it is exposed.
The cooled air from the above system can be used either; directly tocool a bui
pre-conditioned air to be further cooled by a refrigeration system.
The system also can be used to pre-heat air in winter when the ground tempera
above the outside air temperature.
Theefficiencyof the system depends on; air temperatures, air flow rates and t
effectiveness of the soil/pipe/air heat transfer system.
Another method of cooling air uses water sources such as; the sea, a lake, a rive
Where available this is preferred over subsoil cooling, since water has aboutfou
heat capacitycompared to air.
Water is pumped from the source and passed through a heat exchanger where w
chilled and passed to cooling coils.
Another use of cool water is as a source for a; water to water or water to air hea
2.no fresh air delivery to the room, this can be overcome with a fr
separate ducted system.
3.filters in room a.c. units are not very efficient and staining may
4.if used extensively and at full load for most of the running perio
use central plant.
5.the condensate drain may block and stain the ceiling.
Several ceiling mounted cassette units will be installed flush with the ceiling and
connected to outdoor units (air cooled condensers)
The outdoor units can be mounted at ground level or on a roof or wall of the bui
They should be protected from vandalism and pollution and leaves blocking the
Suction and delivery refrigeration pipework is routed from the outdoor units to t
mounted cassettes.
This is typical for this country and can be checked from other examples in this s
Examples of heat gain calculations give Internal gains to be 67% to 85% of the t
To include other gains from sun :22 / 0.7=31.42 kW say32 kWtotal heat
The R410A is the type of refrigerant used; this does not deplete the ozone layer
Power supply is 230-3-50, i.e. 230volt, 3 phase, 50hertz supply.
Benefits -2,3 or 4 indoor units can be connected to only 1 outdoor unit even if
capacities.
All indoor units operate within the same mode (cooling or heating) from one rem
Reverse cycle means that the unit can be switched to heat pump mode and hea
Model
RZQ71B
RZQ100B
RZQ71B
RZQ100B
RZQ71B
RZQ71B
RZQ100B
RZQ100B
RZQ71B
System Design
The drawing below shows a suitable system.
Refrigeration suction and delivery pipework omitted for clarity.
0A
Indoor
unit
kW
Class
FAQ71B
FAQ100B
7.1
10
2.36
2.79
EER
3.01 B
3.58 A
FCQ71B
FCQ100
B
7.1
10
2.17
2.63
FHQ71B
FUQ71B
7.1
7.1
2.47
2.26
kW
8
11.2
2.42
3.2
3.31
3.5
3.27 A
3.8 A
8
11.2
2.49
3.02
3.21
3.71
2.87 C
3.14 B
8
8
2.78
2.71
2.88
2.95
FHQ100B
10
3.16
3.16 B
11.2
3.6
3.11
FUQ100B
10
3.05
3.28 A
11.2
3.29
3.4
7.1
2.15
3.3 A
2.31
3.46
FBQ71B
Class
COP
C
B
C
A
D
D
D
C
B
(ii)HumidifierFever
(iii)SickBuildingSyndrome
Legionnaires Disease
Thebacteriathrivenaturallyinwarm moist conditionsfoundinswamps
Theyhaveadaptedtotheartificialclimate/environmentofairconditionedbuildings.
Anypermanentlymoist/warm situationsuchasadeadlengthsofpipeandtrapped
waterinshowerrosescouldattractthebacteria.
Cooling towersofairconditioningplantsarethemostpredominantbreedingarea.
Themostatriskareelderlyandpeoplewithrespiratorydisordersthoughrelatively
youngfitpeoplehavedied.
Thebacterialivesandmultipliesattempsbetween20-60OC(Optimum35OC).
Solution:Abolitionofcoolingtowers,replacementwithaircooledcondenserunitsorastrict
maintenanceroutine.
ThroughtheHealthandSafetyCommission(HSC),airconditionedbuildingownersmustnow
undertakeregularmaintenenceofcoolingtowers.
Treatwaterwithbiocides
Keeprecordsofmaintenanceandtreatment
Appointapersonorfacilitiesmgt.companytoberesponsibleforsupervisionof
maintenance.
Humidifier Fever
Anallergycausingtemporarydiscomfortwithsymptomssimilartoinfluenza.
Thesourcehasbeenfoundinwater reservoirsofhumidifiers.
Microorganismsoftheamoebaespeciesbreedwhiletheplantisshutdownfor
weekendsandholidays.
Thedeadhusksoftheamoebaearedrawnintotheairstreamanddryintoafinedust
whichisinhaledbybuildingoccupants.
Biocidal treatmenttothespraywaterisonesolution,replacementwithasteam
injectionhumidifierisanother.
Theseoccurancesaremoreprevalentincontemporarybuildings,whicharesealed a
haveanartificiallycontrolledenvironment.
Definedinsymptoms,notcauses,sickbuildingsyndromeissomethingofamystery
Fortunatelynotdeadlyordisablingbutisacontributortoabsenteeism.
SickBuildingSyndromehasbeenrecognisedintraditional buildings(notjustair
conditionedones)
Additionalissuesbeingconsideredascontributoryareairpollutants,poorly
maintainedormisusedventilationsystems,eliminationoffreshairfromsystemsto
economiseonfuel,cleaningequipmentandmaterials,syntheticfibres/materialsin
carpetsandsoftfurnishings,organicdustpollution,microbiologicalinfestationfrom
dustorcarpetmites.
Commissioning
CIBSE
confirm that an appropriate risk assessment has been carried out, an effective m
strategy is in place for controlling risks and that the required cleaning and dosin
adhered to rigorously.
Commissioning Procedures
Preliminary Checks
Checks
Drawings
As installeddrawings are important to the commissioning process.
A schematic drawing of the system is most valuable and should show the gener
sizes of the distribution ductwork, including the positions of the following:
1.test points
2.branch dampers
3.fire dampers
4.fans
5.louvres (intake and exhaust)
6.control sensors
7.grilles (together with details)
8.heater/cooler batteries
9.filters
10.terminal units
11.energy recovery devices.
Design flow rates and pressure drops should be recorded on the drawing, ideally
selected test points.
Avoidance of draughts
Avoidance of Noise