ALL WEIGHTS AND DIMENSIONS ARE APPROXIMATE. CERTIFIED PRINTS ARE AVAILABLE UPON REQUEST.
66"
5"
269 3/8"
197 1/16"
528 15/16"
DETAIL A
NOTES:
1. ADD EXHAUST HOOD DIMENSION OF 17 1/16" OR RETURN HOOD DIMENSION
OF 29 1/4", DEPENDING ON UNIT CONFIGURATION, TO UNIT LENGTH SHOWN
ABOVE TO DERIVE OVERALL UNIT LENGTH. (SEE HOOD DETAIL)
DETAIL A
103 3/4"
SEE NOTE 1
529 1/2"
HINGED PANEL
UNIT CONTROL
1 13/16"
139 1/2"
135 7/8"
63 1/8"
97 9/16"
139 13/16"
102 5/16"
143 1/2"
Page: 1
Qatar - CCPP
SUPPLY
TONNAGE
120 - 150
D
320 13/16"
CONTROLS
Page: 2
Qatar - CCPP
6 5/16"
127 1/8"
57 13/16"
RETURN
EXHAUST HOOD
35 3/16"
47 3/16"
29"
103 3/4"
37 1/2"
EXHAUST HOOD
1 1/2"
8 3/16"
17 1/16"
Page: 3
Qatar - CCPP
3 1/8"
1 1/2"
1 1/2"
Page: 4
Qatar - CCPP
31 11/16"
16"
60 3/4"
53 11/16"
81 1/4"
76 1/4"
71 1/4"
51 5/8"
48 1/16"
46 1/16"
44"
61 3/4"
5 5/16"
6 5/16"
OUTSIDE EDGE
OF BASE RAIL
1 1/16" DIA
EXTERNAL CUSTOMER
CONNECTION POINTS
7/8" DIA. MARINE LIGHTS CUSTOMER
SUPPLIED POWER SERVICE ENTRANCE
1 1/2"
Page: 5
Qatar - CCPP
(2)(3)(4)
Tons: Unit
Operating Voltage Range:
Unit Primary Voltage:
Unit Hertz:
Unit Phase:
EER at ARI 360 rating conditions:
150
342-418
380
50
3
9.68
HEATING - PERFORMANCE
Heat Input:
Heat Output:
Capacity Steps:
Gas Inlet Pressure (MIN/MAX):
Gas Pipe Connection Size:
Crankcase Heaters
Full Load Amps:
ELECTRIC HEATER
N/A
N/A
N/A
N/A
N/A
(5)
COMPRESSOR
300
285.6
Circuit 1/2
Number:
Ton(s):
Rated Load Amps:
Locked Rotor Amps:
4
150
49.4
320.0
Number:
Horsepower:
Full Load Amps:
1
50.0
71.5
EXHAUSTFAN MOTOR
Number:
Horsepower:
Full Load Amps:
Number:
Horsepower:
Full Load Amps:
8
1.5
20.0
FILTERS
1
30.0
47.0
FINAL FILTERS
Type
Furnished:
Recommended Size:
Type
Furnished:
Recommended Size:
N/A
N/A
N/A
Perfilter:
21 - 21"x20"x2"
5 - 12"x24"x4"
Prefilter:
N/A
REFRIGERANT
Type:
(6)
Factory Charge
Circuit 1/2
NOTES:
1. Load 1 = Current of the largest motor Load 2 = Sum of the currents of all remaining motor; Load 3 = Current of electric heaters; Load 4 = Control Power Transformer 90-130
ton units add 6 FL amps for wire sizing formula).
2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes using the larger value for sizing. (When determining Loads, the compressors do not
operate when the unit is in heating mode) (Heating Load 4 = 12 amps on 200,230 volt units and 9 amps on 460, 575 volt units).
3. If selected MOP is less than the MCA, then select the lowest standard maximum fuse size that is equal to or less than the MCA,.provided it does not exceed 800 amps.
4. If the selected Recommended Dual Element fuses size is greater then the selected Max Over current Protection value, then select the Recommended Dual Element fuse size
Value to equal the Max over current protection value.
5. Compressor kW at ARI Rating condition of 80/67/95.
6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions.
Page: 6
Qatar - CCPP
A
84 15/16"
TONNAGE
120 - 150
SUPPLY
DIMENSION
B
10 5/8"
C
54 3/4"
D
319 1/2"
Page: 7
Qatar - CCPP
(2)(3)(4)
Tons: Unit
Operating Voltage Range:
Unit Primary Voltage:
Unit Hertz:
Unit Phase:
EER at ARI 360 rating conditions:
150
342-418
380
50
3
9.68
HEATING - PERFORMANCE
Heat Input:
Heat Output:
Capacity Steps:
Gas Inlet Pressure (MIN/MAX):
Gas Pipe Connection Size:
Crankcase Heaters
Full Load Amps:
ELECTRIC HEATER
N/A
N/A
N/A
N/A
N/A
(5)
COMPRESSOR
N/A
N/A
Circuit 1/2
Number:
Ton(s):
Rated Load Amps:
Locked Rotor Amps:
4
150
49.4
320.0
Number:
Horsepower:
Full Load Amps:
1
40.0
59.0
EXHAUSTFAN MOTOR
Number:
Horsepower:
Full Load Amps:
Number:
Horsepower:
Full Load Amps:
8
1.5
20.0
FILTERS
1
30.0
47.0
FINAL FILTERS
Type
Furnished:
Recommended Size:
Type
Furnished:
Recommended Size:
N/A
N/A
N/A
Perfilter:
21 - 21"x20"x2"
5 - 12"x24"x4"
Prefilter:
N/A
REFRIGERANT
Type:
(6)
Factory Charge
Circuit 1/2
NOTES:
1. Load 1 = Current of the largest motor Load 2 = Sum of the currents of all remaining motor; Load 3 = Current of electric heaters; Load 4 = Control Power Transformer 90-130
ton units add 6 FL amps for wire sizing formula).
2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes using the larger value for sizing. (When determining Loads, the compressors do not
operate when the unit is in heating mode) (Heating Load 4 = 12 amps on 200,230 volt units and 9 amps on 460, 575 volt units).
3. If selected MOP is less than the MCA, then select the lowest standard maximum fuse size that is equal to or less than the MCA,.provided it does not exceed 800 amps.
4. If the selected Recommended Dual Element fuses size is greater then the selected Max Over current Protection value, then select the Recommended Dual Element fuse size
Value to equal the Max over current protection value.
5. Compressor kW at ARI Rating condition of 80/67/95.
6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions.
Page: 8
96"
96"
96"
SERVICE CLEARANCE
UNIT CLEARANCE
SERVICE CLEARANCE
Qatar - CCPP
72"
Page: 9
Qatar - CCPP
SPREADER BAR
A
B
Page: 10
IP2
IP4
Qatar - CCPP
IP6
IP8
IP10
IP12
IP1
IP3
IP5
IP7
IP9
IP11
X
X-Y Dimension
X1: 4.00 in
Y1: 2.88 in
X2: 97.80 in
Y2: 140.93 in
X3: 191.60 in
X4: 285.40 in
X5: 379.20 in
X6: 498.30 in
X7: N/A
X8: N/A
0,0
Page: 11
IP2
IP4
Qatar - CCPP
IP6
IP8
IP10
IP12
IP1
IP3
IP5
IP7
IP9
IP11
X
X-Y Dimension
X1: 4.00 in
Y1: 2.88 in
X2: 97.80 in
Y2: 140.93 in
X3: 191.60 in
X4: 285.40 in
X5: 379.20 in
X6: 498.30 in
X7: N/A
X8: N/A
0,0
Page: 12
14 1/16"
1 13/16"
5 15/16"
123"
Base pan
Gasket
1 13/16"
2"
1/2"
2"x4"
1 13/16"
2"x4"
Gasket
1/2"
2"
1 13/16"
SECTION B-B
2"
14 1/16"
317 7/8"
283"
248 1/8"
213 1/16"
179 3/8"
145 11/16"
103 3/8"
49 1/2"
11 15/16"
SECTION A-A
379 5/16"
49 1/2"
11 15/16"
2 9/16"
20 15/16"
104"
145 1/4"
SECTION C-C
11 13/16"
2 7/8"
NOTE:
1. ALL DIMENSIONS MEASURED
FROM TOP FLANGE OF ROOF CURB
117 1/16"
134 7/8"
Page: 13