You are on page 1of 148

Table of Contents

Hilti Firestop Systems


Guide to Specification, Installation & Inspection
07270/07840 - Firestopping

TOPIC

PAGE

Typical Firestop Applications

2-3

Product Data Sheets

4-23

Firestop Accessories

24

Firestop Selection Chart

25-27

Firestop Application Drawings & Installation Instructions

28-111

Estimating Tables

112-115

Firestopping Terms & Definitions

116

Using the UL Directory

117

Material Safety Data Sheets

118-137

UL Certificates of Compliance

138-147

1-800-879-8000

Metal pipes

Plastic/glass pipes

Cables/cable trays

Insulated metal pipes

Metal ducts

Multiple penetrations

Joints

Firestop Systems Application Review

Product

Description

FS-ONE High Performance


Intumescent Firestop

A water-based firestop
sealant, designed to expand
when exposed to heat

FS 657 FIRE BLOCK

An innovative and simple to


install firestop block designed
to expand when exposed
to heat

CP 672 Firestop Joint Spray

A flexible fire-rated mastic for


construction joints where
movement up to 50%
is expected

CP 601S Elastomeric
Firestop Sealant

A single component silicone


firestop sealant for joint
applications where movement
up to 25% is expected

CP 606 Flexible
Firestop Sealant

An acrylic based firestop


sealant for joint applications
where movement up to 10%
is expected

CP 642/CP 643
Firestop Collar

A ready-to-use firestop device


designed to collapse plastic
pipe penetrations when
exposed to fire conditions

FS 635 Firestop
Compound

Is a dry powder, when mixed


with water forms a pourable
trowelable firestop mortar

CP 617 Firestop Putty Pad

An intumescent putty sheet


designed to protect electrical
outlet boxes

CP 618 Firestop Putty Stick

An intumescent putty which


remains pliable over time

tlk

e0
9^)
&(/
R
84t
sod
c )v
fm,e
Z8Z
645
v iJdj
3
4i5k23awp fiwh
u9+ irdwiloi43i4e riuh.
02 No
12
oeo jtf-x-.v 88u WE
o
bvb 27uze
vh,
ireiv

Firestop
System

ch.

ans

tzm

chu

nds

Bra

NoW

h.
7uze
whriu 88u2 ireiv
iJdjfi e02
vh,
vbvb
m,ev p3i4
-x-.
sodf 3aw
Z8Z2rdwiloi4jtf
oo
4i5ki 12oe
u9+

CP

642

CP 636
Brandsch

utzmrtel

sodfm,ev
iJdjfiwhriuh
Z8Z23awp
. NoWE
4i5kirdwiloi 3i4e0288u
27uze
u9+12oeo4jtf-x-.vbvbvh,
ireiv
o

1-800-879-8000

Firestop Systems Application Review

tlk

e0
9^)
&(/
R
84t
sod
c )v
fm,e
Z8Z
645
v iJdj
3
4i5k23awp fiwh
u9+ irdwiloi43i4e riuh.
02 No
12
oeo jtf-x-.v 88u WE
o
bvb 27uze
vh,
ireiv

Firestop
System

ch.

ans

tzm

chu

nds

Bra

NoW

h.
7uze
whriu 88u2 ireiv
iJdjfi e02
vh,
vbvb
m,ev p3i4
-x-.
sodf 3aw
Z8Z2rdwiloi4jtf
oo
4i5ki 12oe
u9+

CP

642

Features

Benefits

UL Listings for various penetrating items


Several 1/4" depth systems
Available in foil pack (600 ml)

ONE product to specify, purchase or inspect for most applications


Low cost per penetration
Quick and simple installation procedure

Soft flexible design


Easy to cut and shape
User friendly UL designs
Innovative designs

Easy to install, reuse and re-penetrate


Just trim BLOCK to fit around penetrating items
Reduces need for extra labor, tools and parts (i.e. wire mesh)
Easiest solution for large openings with multiple penetrations

Water based formulation


Maximum flexibility
Can be used with many standard texture
spray equipment

Fast and easy clean-up


Tested to new UL 2079 Test Standard
No special modification or extra expense for
product application

Silicone based formula


1/4" depth systems
Available in foil pack (600 ml)

Allows for movement and vibration


Cost effective solutions
Fast and easy dispensing

Acrylic based formula


Can be painted
Available in foil pack (600 ml)

Fast and easy clean-up with water


Allows for excellent finished appearances
Fast and easy dispensing

Ready-to-use out of package


Adjustable mounting tabs
Low profile design

Simple and quick installation


Flexibility in positioning of collar
Allows for correct installation in tight areas

Mixes in its own container


All applications require 2-1/2" depth
Cleans up with water

No need for added pails


Economical and simple to use
Fast and easy clean-up

6" x 7" pad size


1 & 2 hour listing
Tested for wood and steel studs

Fits most common electrical boxes


Only one pad to stock and install
Can be used for commercial and residential applications

Non-curing formation
No volatile solvents
Intumescent

Reusable and easily re-penetrated


May be used in confined spaces
Approved for combustible penetrations (cables) along
with conduit, EMT and steel pipe

CP 636
Brandsch

utzmrtel

sodfm,ev
iJdjfiwhriuh
Z8Z23awp
. NoWE
4i5kirdwiloi 3i4e0288u
27uze
u9+12oeo4jtf-x-.vbvbvh,
ireiv
o

1-800-879-8000

Product Information

FS-ONE
High Performance
Intumescent Firestop Sealant
Product description
Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations for
up to 4 hours fire rating

Areas of application

Steel, copper and EMT pipes


Insulated steel and copper pipes
Jacketed cables and cable bundles
Closed or vented plastic pipes

tlk

e0
9^
)&
(/R
84
sod
tc
fm
)v
Z8Z ,ev
64
iJ
53
4i5 23aw djfiw
k

h
u9+ irdwil p3i4e riuh.
12 oi4jt 02 No
oeo f-x 88u WE
-.vb 27
o
vbv uze
h, ir
eiv

For use with

Concrete, masonry, drywall and wood floor assemblies


Wall and floor assemblies rated up to 4 hours

Internationally tested and approved


C

Sealing around plastic pipe penetrations in fire rated


construction

LA

SSIFIE

Examples

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

System/Product advantages

Hi

Protects more than 95% of all typical firestop applications


Easy to work with and fast cleanup
Quick sealing of remaining gaps
Can be repenetrated when laying new cables

FM
APPROVED

For Penetration Fire Stops.


Consult the Factory Mutual Research Corporation Approval Guide.

i r e s t o p System
lti F
s

Z - 19. 15 - 471
Ge

rma

n DIN Stand

ar

FS-ONE
Intumescent Firestop Sealant
Ordering
Description

FS-ONE, tube
FS-ONE, foil
FS-ONE, pail

Color

red
red
red

Package contents

Volume

Item No.

10.1 oz. (300 ml)


18 in
00259579
00311387
(Qty 20) 20.2 oz. (600 ml) 36 in3
5 Gallons (19 liter)
1155 in3 00259578

CB 200 Pl-300/310 ml Dispenser


600 ml Foil Dispenser

Simplicity

00055205
00024669

Confidence

Value

1-800-879-8000

Installation Instructions

FS-ONE
High Performance
Intumescent Firestop Sealant
Product description
Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations for
up to 4 hours fire rating

Product features

Smoke, gas and water resistant


Contains no halogen, solvents or asbestos
High fire rating properties
Water based, easy to clean

Technical Data
FS-ONE Intumescent Firestop
(at 73F (23C) and 50% relative humidity)
Chemical basis:
Water-based intumescent acrylic dispersion
Density:
Approx. 1.5 g/cm3
Color:
Red
Working time:
Approx. 20-30 min
Curing time:
Approx. 14-21 days
Shore A Hardness:
Approx. 35
Movement capability:
Approx. 5%
Intumescent Activation:
Approx 250F (121C)
Expansion rate (unrestricted):
Up to 3-5 times original volume
Temperature resistance (cured): -40F (-40C) to 212F (100C)
Application temperature:
35F (2C) to 100F (38C)
Surface burning characteristics: Flame Spread: 0
(ASTM E 84-96)
Smoke Development: 5

Tested in accordance with

Approvals

UL 1479
ASTM E 814
UL 2079

ICBO Evaluation Service, Inc.


California State Fire Marshal
City of New York
City of Los Angeles

Report No. 5071


Listing No. 1200:108
MEA 326-96-M
Research Report 25188

Installation instructions for FS-ONE


Firestop
System

1. Clean opening.

2. Pack mineral
wool. (If required)

3. Apply FS-ONE.

Opening
1. Clean the opening. Surfaces to which FS-ONE will be applied
should be cleaned of loose debris, dirt, oil, moisture, frost and
wax. Structures supporting penetrating items must be installed
in compliance with local building and electrical standards
Application of firestop sealant
2. Install the prescribed backfilling material type and depth to
obtain the desired rating (if required). Leave sufficient depth for
applying FS-ONE.
3. Application of firestop sealant: Apply FS-ONE to the required
depth in order to obtain the desired fire rating. Make sure
FS-ONE contacts all surfaces to provide maximum adhesion.
For application of FS-ONE use a standard caulking gun, foil pack
gun, bulk loader and bulk gun. With FS-ONE buckets, Graco type
sealant pumps may be used. (Contact pump manufacturer for
proper selection.)
4. Smoothing of firestop sealant: To complete the seal, tool immediately to give a smooth appearance. Excess sealant, prior to
curing, can be cleaned away from adjacent surfaces and tools
with water.
5. Leave completed seal undisturbed for 48 hours.
6. For maintenance reasons, a penetration seal could be permanently
marked with an identification plate. In such a case, mark the identification plate and fasten it in a visible position next to the seal.

4. Smooth FS-ONE.

5. Leave completed
seal undisturbed for
48 hours.

6. Fasten identification
plate (if required).

Notice about approvals


Check that the penetration has been sealed according to the specified
drawing in the UL Fire Resistance Directory or Hilti Firestop manual.
For further advice, please contact Hilti customer service. Refer to
Hilti product literature and UL fire resistance directory for specific
application details.
Not to be used...
For high movement expansion joints
Underwater
On building materials which bleed oil, plasticizers or solvents
(impregnated wood, oil-based seals, green or partially vulcanized rubber)
In any penetration other than those specifically described in the Hilti
Firestop Manual or the test reports
Safety precautions
Before handling, read the product and material safety data sheet for
detailed use and health information.
Keep out of reach of children
Wear suitable gloves and eye protection
Storage
Store only in the original packaging in a location protected from
moisture at temperatures between 40F (5C) and 86F (30C).
Observe expiration date on the packaging.

1-800-879-8000

Product Information

FS 657
FIRE BLOCK
Product description
Ready-to-use, intumescent flexible block based on a twocomponent polyurethane foam

Areas of application

Sealing single or multiple penetrations in small to large openings


Temporary or permanent sealing of cables and cable
tray penetrations.
Temporary or permanent sealing of insulated and noninsulated
metallic pipes and combustible pipe penetrations

For use with

Walls (UL tested up to max. opening 52" x 48")


Floors (UL tested up to max. opening 36" x 36")
Concrete, porous concrete, masonry and gypsum wall assemblies
Wall and floor assemblies rated up to 4 hours

LA

Completely dust and fiber-free rooms and places where


electrical installations are frequently used, such as computer
centers, hospitals and laboratories
New buildings in the construction phase and during renovation
Large openings containing multiple penetrations as found
in production bays, warehouses, hospitals etc.

SSIFIE

Examples

Internationally tested and approved

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

FM
APPROVED

For Penetration Fire Stops.


Consult the Factory Mutual Research Corporation Approval Guide.

System/Product advantages

Suitable for re-penetration of new penetrations


Economical in use with short installation times
Easy installation as no special tool is required
Ideal for use in floors as no forming is required
Smoke and gas resistant

FS 657 FIRE BLOCK


Description

Color

FS 657 FIRE BLOCK

red

Ordering
Designation

FS 657

Simplicity

Volume
3

80 in

Item No.

00306241

Confidence

Value

1-800-879-8000

Installation Instructions

Technical Data
FS 657 FIRE BLOCK

FS 657
FIRE BLOCK
Product description
Ready-to-use, intumescent flexible block based on a twocomponent polyurethane foam

Product features

Completely free from dust and fibers


Halogen, asbestos and solvent free
Operational immediately after installation
Can be painted with dispersion, acrylic or silicone

(at 73F (23C) and 50% relative humidity)


Density:
Dimensions:
Color:
Application temperature:
Temperature resistance:
Intumescent Activation:
Expansion ratio (unrestricted):
Surface burning characteristics:
(ASTM E 84-96)

Approx. 0.25 g/cm3


2"x5"x8"
Red
23F (-5C) to 104F (40C)
-60F (-51C) to 140F (+60C)
Approx. 300F (149C)
Up to 1: 5
Flame Spread Index: 0
Smoke Development Index: 25

Approvals

Tested in accordance with

ICBO Evaluation Service, Inc.


California State Fire Marshall
City of New York
City of Los Angeles

ASTM E 814
UL 1479

Report No. 5071


Listing No. 1200:106
MEA 325-96-M
Research Report 25188

Installation instructions for CP 657


Ausfhrungsschild

1. Clean opening

2. a) Build up blocks

2. b) Cut blocks to
size for penetrations
in place

Opening
1. Clean the opening. Penetration and penetration supporting
structures must be installed in compliance with local building
and electrical standards.
Application of FIRE BLOCKS
2a. If no penetrations are located (temporary firestop), build up
FS 657 FIRE BLOCK firmly seated, within opening.
2b. If penetrations are located (permanent firestop), build up
FS 657 FIRE BLOCK firmly seated, while cutting blocks with
a knife to suit the placed penetrations.
3. Finish building up FIRE BLOCKS until entire opening is filled.
4. Completely fill cable spaces, gaps between blocks and pipes,
and joints with FS-ONE Firestop Sealant.
5. For maintenance reasons, a penetration seal could be permanently marked with an identification plate. In such a case, mark
the identification plate and fasten it in a visible position next to
the seal.

3. Build up blocks

4. Fill gaps with


FS-ONE

5. Fasten installation
plate in place
(If required)

Notice about approvals


When making a cable seal using Hilti FS 657 Intumescent FIREBLOCK, national approvals must be observed. Please refer to the
UL Directory or the Hilti Firestop Manual for restrictions as to
opening size, type and thickness of wall or floor, maximum cable
diameter, etc.
Not to be used...
In wet rooms, outdoors or exposed to the weather or UV radiation
(can be done only after applying an additional silicone coating,
i.e. CP 601s).
Safety precautions
Keep out of the reach of children.
Read the material safety data sheet.
Storage
Store only in the original packaging in a location protected from
moisture and direct sunlight.

Re-installing cables or other penetrations

Remove or cut the block from the seal.

Install the penetrant and re-lay the block in compliance with


the approval. Fill gaps and spaces with FS-ONE.
Single cables can be run through joints between blocks or
a hole can be drilled through a block using a sharpened
piece of metal pipe or tubing.

1-800-879-8000

Product Information

CP 672
Firestop Joint Spray
Product description
A sprayable fire-rated mastic for construction joints where
maximum movement is required

Areas of application

Top-of-wall joints
Curtain wall/perimeter joints
Expansion joints

Firestop
System

For use with

Concrete, masonry and gypsum wall assemblies


Wall and floor assemblies rated up to 2 hours

Examples
LA

SSIFIE

Where a gypsum wall assembly meets the underside of a


metal or concrete deck
Where a concrete floor assembly meets up with an exterior
wall (concrete, glass, etc.)

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

System/Product advantages

Maximum flexibility, meets 500 cycle requirements


(ASTM E 1399 & UL 2079)
Quick and easy installation
Utilizes many standard off the shelf texture spray equipment

CP 672 Firestop Joint Spray


Description

Color

Package
Contents

Volume

Item No.

CP 672, pail

red

5 Gallon (19 liter)

1155 in3

00315267

EZ-Tex Sprayer for CF 672 Firestop

Simplicity

00332214

Confidence

Value

1-800-879-8000

Installation Instructions

Technical Data
CP 672 Firestop Joint Spray

CP 672
Firestop Joint Spray
Product description
A sprayable fire-rated mastic for construction joints where
maximum movement is required

Product features
Contains no halogens, solvents or asbestos
Water based, easy to clean
Sprayable or apply by brush

Tested in accordance with


UL 2079
ASTM E 1399
ASTM C 920 (In progress; call for details)

(at 73F (23C) and 50% relative humidity)


Chemical basis:
Latex-based dispersion
Consistency:
Sprayable liquid
Color:
Red
Density:
Approx 9 lb/gal
Working time:
30-45 min
Curing time:
5-7 days
Ph-value:
Approx. 6.75
Movement capability:
Approx. 50%
Temperature resistance:
35F (2C) to 120F (49C)
Application temperature:
40F (5C) to 90F (32C)
Surface burning characteristics:
Flame spread: In progress; call for details
(ASTM E 84-96)
Smoke development: In progress;
call for details

Approvals
ICBO Evaluation Service, Inc.
California State Fire Marshal
City of New York
City of Los Angeles

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

Installation instructions for CP 672

Firestop
System

1. Clean opening

2. Pack in mineral wool

3. Spray on CP 672

Opening
1. Clean the opening. Surfaces to which CP 672 will be applied
should be cleaned of loose debris, dirt, oil, moisture, frost and wax.
Application of firestop spray
2. Mineral wool packing
Install the prescribed back filling material type and depth to
obtain desired rating.
3. Application of firestop spray
Apply CP 672 to the required depth in order to obtain the
desired rating. Make sure CP 672 contacts all surfaces and
overlaps 1/2" beyond all surrounding surfaces.
Benron EZ-Tex Sprayer and Graco Texspray Compact HP
pumps have been successful in applying CP 672 Firestop Joint
Spray. Contact Hilti Technical Support for more information.
4. Curing of firestop spray
Allow 5 to 7 days (@ 73F) for CP 672 to fully cure
5. For maintenance reasons, joint seal could be permanently marked
with an identification plate. In such a case, mark the installation
plate and fasten it in a visible position next to the seal.

4. Allow CP 672 to cure

5. Fasten identification
plate (if required)

Notice about approvals


When making a seal using Hilti CP 672 Firestop Joint Spray,
please refer to the UL Directory or the Hilti Firestop Manual for
restrictions as to joint size, type and thickness of wall or floor,
movement capabilities, etc.
Not to be used...
In areas underwater
On hot surfaces (above 200F)
Safety precautions
Before handling, read the Material Safety Data Sheet for detailed
use and health information
Wear suitable gloves and eye protection.
Keep out of the reach of children.
Storage
Store only in the original packaging at temperatures
40F (5C) to 100F (37C).
Observe expiration date on package.

1-800-879-8000

Product Information

CP 601S
Elastomeric Firestop Sealant
Product description

A silicone based firestop sealant that provides maximum


movement in fire-rated joint applications

Areas of application

Sealing construction/expansion joints


Wall to wall
Curtain wall/perimeter joints
Floor to floor

For use with

Various base materials such as masonry, concrete,


metal, glass, etc.
Wall and floor assemblies rated up to 3 hours
Joint widths up to a maximum of 3-1/2"

Internationally tested and approved

Where a concrete floor assembly meets up with an


exterior wall (concrete, glass, etc.)
Joints in walls or fire compartments
Sealing floor to floor joints to impede the passage of fire,
smoke and toxic fumes

LA

SSIFIE

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN THROUGH PENETRATION
FIRESTOP SYSTEMS AND JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

Examples

System/Product advantages

Simple use and application


Good adhesion without use of a primer
Smoke, gas and water resistant
Excellent movement capability, meets 500 cycle requirements
(ASTM E 1399 & UL 2079)

CP 601S
Elastomeric Firestop Sealant
Description

Color

CP 601S, tubes
CP 601S, foil
CP 601S, pail

red
red
red

Package
Contents

10.5oz (310 ml)


(Qty 20) 20.2oz (600 ml)
5 gallons (19 liter)

CB 200 Pl-300/310 ml Dispenser


600 ml Foil Dispenser

Volume

Item No.
3

18 in
36 in3
1155 in3

00314268
00314269
00314270

00055205
00024669

10

1-800-879-8000

Installation Instructions

CP 601S
Elastomeric Firestop Sealant
Product description

A silicone based firestop sealant that provides maximum


movement in fire-rated joint applications

Product features

Halogen and solvent free


Weather and UV-resistant
Asbestos free

Technical Data
CP 601S Elastomeric Firestop Sealant
(at 73F (23C) and 50% relative air humidity)
Density:
Approx. 1.4 g/cm3
Color:
Red
Application temperature:
40F (5C) to 77F (25C)
Skin-forming time:
Approx. 15 min.
Curing rate:
Approx. 1/8" per day
Volume shrinkage:
Approx. 0 5%
Movement capability:
Approx. 25%
Temperature resistance:
-30F (-34C) to 302F (150C)
Surface burning characteristics:
Flame spread: 0
(ASTM E84-96)
Smoke development: 30

Tested in accordance with

Approvals

ICBO Evaluation Service, Inc.


California State Fire Marshal
City of New York
City of Los Angeles

UL 2079
ASTM E 1399
UL 1479
ASTM E 814
ASTM C 920

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

Installation instructions for CP 601s

1. Clean opening.

2. Insert backing material.

3. Apply CP 601S.

4. Smooth CP 601S.

Opening
1. Clean the opening. Joint sides must be sound, dry and free from
dust, oil and grease.

Application of firestop
2. Insert fill of mineral wool (or backer as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before the skin forms.
Once cured, CP 601S can only be removed mechanically.
5. For maintenance reasons (not shown), a penetration seal could
be permanently marked with an identification plate. In such a
case mark the identification plate and fasten it in a visible
position next to the seal.

Notice about approvals


When using Hilti CP 601S Elastomeric Firestop Sealant, check
that the joint application has been sealed according to the
applicable drawing in the UL Fire Resistance Directory or Hilti
Firestop Manual.

Chemical resistance
At room temperature the cured silicone sealant is resistant for a
short time to diluted (5%) acids and lyes/alkalis as well as
commercially available cleaning agents and disinfectants (except
those containing iodine).
Concentrated acids and lyes/alkalis destroy silicone rubber
over time.
Solvents and mineral oils cause cured silicone to swell.
Consequently, proper functioning of the sealant should be
checked after exposure to a solvent / mineral oil.

Please contact your local sales representative or the nearest


Hilti center if special requirements for chemical resistance have
to be met.

Not to be
Used on areas immersed in water
Painted
Safety precautions
Keep out of reach of children.
Read the material safety data sheet.
Eyes and hands must be suitably protected.
Avoid contact with eyes/skin.
Only use in well ventilated areas.
Storage
Store only in the original packaging in a location protected from
moisture at a temperature of 40F (5C) to 77F (25C).
Observe expiration date on packaging.

11

1-800-879-8000

Product Information

CP 606
Flexible Firestop Sealant
Product description

An acrylic based firestop sealant that provides movement


capability in fire rated joint applications

Areas of application

Sealing construction/expansion joints


Top-of-wall joints

For use with

Various base materials such as masonry, concrete, metal, etc.


Wall and floor assemblies rated up to 2 hours
In joint widths up to a maximum of 3-3/4"

Examples

Internationally tested and approved


LA

SSIFIE
D

Where a gypsum wall assembly meets the underside of


a metal or concrete deck
Sealing perimeter joints to impede the passage of fire,
smoke and toxic fumes

System/Product Advantages

fanstalt f.
lpr
d.
ia

Amtl. Ma
te
r

Paintable
Meets 500 cycle requirements (ASTM E 1399 & UL 2079)
Smoke, gas and water resistant
Easy clean up with water

sen
uwe
Ba

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

Br

VMPA

a u n s c h w ei

PA-III 2.2654
DIN 4102 - B1

berwacht

CP 606 Flexible Firestop Sealant


Description

CP 606, tube
CP 606, foil
CP 606, pail

Color

white
white
white

Package
Contents

Volume

Item No.
3

10.5oz (310 ml)


18 in
(Qty 20) 20.2oz (600 ml) 36 in3
5 gallons (19 liter)
1155 in3

CB 200 Pl-300/310 ml Dispenser


600 ml Foil Dispenser

Simplicity

00314271
00314272
00314273

00055205
00024669

Confidence

Value

12

1-800-879-8000

Installation Instructions

Technical Data
CP 606 Flexible Firestop Sealant

CP 606
Flexible Firestop Sealant

(at 73F (23C) and 50% relative air humidity)


Density:
Approx. 1.5 g/cm3
Color:
White
Application temperature:
40F (5C) to 77F (25C)
Skin-forming time:
Approx. 15 min.
Curing rate:
Approx. 1/16 in 3 days
Volume shrinkage:
Less than 20%
Movement capability:
Approx. 10%
Temperature resistance:
-40F (-40C) to 176F (80C)
Surface burning characteristics:
Flame spread: 0
(ASTM E84-96)
Smoke development: 5

Product description

An acrylic based firestop sealant that provides movement


capability in fire rated joint applications

Product features

Silicone free
Halogen, asbestos and solvent free
UV-resistant

Tested in accordance with

Approvals

UL 2079
ASTM E 1399
ASTM C 920

ICBO Evaluation Service, Inc.


California State Fire Marshal
City of New York
City of Los Angeles

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

Installation instructions for CP 606

1. Clean opening.

2. Insert backing material.

3. Apply CP 606.

Opening
1. Clean the opening. Joint sides must be sound, dry and free from
dust, oil and grease.
Application of firestop
2. Insert fill of mineral wool (or backer as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before the skin forms.
Once cured, CP 606 can only be removed mechanically.
5. For maintenance reasons (not shown), a penetration seal could
be permanently marked with an identification plate. In such a
case mark the identification plate and fasten it in a visible
position next to the seal.
Notice about approvals
When using Hilti CP 606 Flexible Firestop Sealant, check
that the joint application has been sealed according to the
applicable drawing in the UL Fire Resistance Directory or Hilti
Firestop Manual.

4. Smooth CP 606.

Not to be used
On areas immersed in water
Safety precautions
Keep out of reach of children.
Read the material safety data sheet.
Eyes and hands must be suitably protected.
Avoid contact with eyes/skin.
Only use in well ventilated areas.
Storage
Store only in the original packaging in a location
protected from moisture at a temperature of 40F (5C) to
77F (25C).
Observe expiration date on top of package.

13

1-800-879-8000

Product Information

CP 643
Firestop Collar
Product description

A ready-to-use firestop collar, made of a galvanized steel


housing and intumescent inserts.
For firestopping combustible pipes

Areas of applicaton

Firestopping combustible pipes up to 4" in diameter in


penetrations through fire walls and floors.
Suitable for the following pipe materials:
- PVC, CPVC, ABS, PVDF and FRPP

h.

sc

an

tzm

hu

sc

nd

E
oW
N uze
iuh.
6
whr 288u27 , ireiv
CP
djfi
v iJ 4e0 bvbvh
.v
fm,e p3i
-xsod
23aw i4jtf
Z8Z irdwilo o
4i5k 2oeo
1
u9+
Bra
42

For use with

Concrete, masonry, wood floor and gypsum wall assemblies


Wall and floor assemblies rated up to 3 hours

Internationally tested and approved

Types of installation

Wall: two collars, one on each side


Floor: one collar on underside (bottom)

LA

SSIFIE

Example

Waste water pipes


Fresh water pipes

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

System/Product advantages

Quick and easy closure without the use of a tool


Adjustable position tabs for simple fastening
Low profile for tight installations

CP 643 Firestop Collar*


Package
Contents
(pcs)

Description

Ordering
Designation

Item No.

CP 643 Firestop Collar


CP 643 Firestop Collar
CP 643 Firestop Collar
CP 643 Firestop Collar
* incl. fastening hooks

1
1
1
1

CP 643-50/1.5"
CP 643-63/2"
CP 643-90/3"
CP 643-110/4"

00307707
00307708
00307709
00307710

Fastening Hook

CP 643-hook

00307701

Simplicity

CP 643

Confidence

Value

14

1-800-879-8000

Installation Instructions

CP 643
Firestop Collar
Product description

A ready-to-use firestop collar, made of a galvanized steel


housing and intumescent inserts.
For firestopping combustible pipes

Product features

Adjustable mounting tabs


Ready-to-use collar; no construction required, therefore
fast installation time

Tested in accordance with

Dimensions
CP 643 Collar/plastic pipes
Designation/
size
CP 643-50/1.5
CP 643-63/2
CP 643-90/3
CP 643-110/4

Pipe outside Collar outside Collar height No. of


dia. (in.)
dia. (in.)
(in.)
hooks and
fasteners
1.4 2.0
2.8
0.9
2
2.0 2.5
3.4
1.3
2
2.6 3.6
4.9
1.7
3
3.6 4.5
6.0
1.9
3

Approvals
ICBO Evaluation Service, Inc.
California State Fire Marshall
City of New York
City of Los Angeles

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

UL 1479
ASTM E 814

Installation instructions for CP 643

Firestop
System

1. Clean plastic pipe

2. Close remaining gap 3. Close collar


to provide smoke and
gas tight seal

Opening
1. Clean the plastic pipes. Expansion of the intumescent material
during a fire acts to close the plastic pipe. Very dirty pipes with,
for example, remains of mortar, may lead to a delay in this
closing action. Badly soiled plastic pipes should, therefore, be
cleaned in the area where the CP 643 firestop collar is to
be installed.
Application of firestop system
2. Seal the opening. Gaps must be closed with FS-ONE. The
approved methods vary and are given in the specific UL system.
3. Close the CP 643 firestop collar. Place the CP 643 firestop collar
around the plastic pipe and lock the closure with firm pressure
until it latches.
4. Attach fastening hooks. The fastening hooks can be attached to
various points on the metal housing. This allows the fastening
points to be made to suit the space available in each case.
The hooks must be positioned as symmetrically as possible.
The required number of fastening hooks is indicated on
the packaging.
5. Fastening the CP 643 firestop collar. Only when fastened properly
can CP 643 protect against fire passing through.
- Mark the fastening points.
- Drill holes with a Hilti rotary hammer drill (i.e. TE 5) or,
depending on base material, fasten using Hilti power actuated
tool (e.g. DXA 40).

4. Attach fastening
hooks

5. Fasten collar and


installation plate
(if required)

- To secure the CP 643 firestop collar, use Hilti anchors/fasteners.


- For maintenance reasons, a penetration seal could be
permanently marked with an identification plate. In such a case
mark the identification plate and fasten it in a visible position
next to the seal.
Notice about approvals
When making a pipe seal using Hilti CP 643 Intumescent Firestop
Collar, please refer to the UL directory or Hilti Firestop Manual for
restrictions as to opening size, type and thickness of wall or floor,
maximum pipe diameter, etc.
Not to be used...
With folded and coiled sheet-metal and cast-iron pipes (not tested)
In highly corrosive surroundings
With unapproved anchors/fasteners
Safety precautions
Keep out of the reach of children.
Read the material safety data sheet.
Storage
Store only in the original packaging in a location protected
from moisture.

15

1-800-879-8000

Product Information

CP 642
Firestop Collar
Product description

Galvanized sheet steel containing sections of


intumescent material (designed to expand when exposed to fire)
For firestopping large combustible pipes

Areas of application

Sealing combustible pipes from 6" to 10" in diameter.


Suitable for:
- Vented or closed pipe
- PVC, CPVC, ABS, FRPP, PP, PVDF
- Pneumatic tube conveyors with two lines (mail)
- Plastic pipes with acoustic insulation

h.

sc

an

tzm

hu

sc

nd

E
oW
ze
h. N
6
hriu 88u27uireiv
CP
djfiw
h,
v iJ 4e02bvbv
3i
.v
m,e
sodf awp jtf-x23
i4
Z8Z irdwilo
oo
4i5k 12oe

u9+
Bra
42

For use with

Concrete, masonry, wood floor assemblies and gypsum walls


Wall and floor assemblies rated up to 3 hours

Internationally tested and approved


C

LA

SSIFIE

- Wall: two collars, one on each side


- Floor: one collar on underside (bottom)

Types of installation

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

Examples

Hil

Waste water pipes


Fresh water pipes

FM
APPROVED

For Penetration Fire Stops.


Consult the Factory Mutual Research Corporation Approval Guide.

restop Syste
ti Fi
m

Z - 19. 17 - 835
Ge

rma

n DIN Stand

ar

System/Product advantages

Snap connection for quick and easy closure without use of a tool
Adjustable position tabs for convenient fastening
Ready to use out of the package

CP 642 Firestop Collar*


Package
Contents
(pcs)

Description

Ordering
Designation

Item No.

CP 642 Firestop Collar


CP 642 Firestop Collar
CP 642 Firestop Collar
* incl. fastening hooks

1
1
1

CP 642-160/6"
CP 642-200/8"
CP 642-250/10"

00236709
00310084
00310085

Fastening hook
Spare part

10

CP 642 hook

00236711

Simplicity

CP 642

Confidence

Value

16

1-800-879-8000

Installation Instructions

Dimensions
CP 642 Collar/plastic pipes

CP 642
Firestop Collar

Designation

Pipe outside
dia. (in.)

Product description

Galvanized sheet steel containing sections of


intumescent material (designed to expand when exposed to fire)
For firestopping large combustible pipes

CP 642-160/6
CP 642-200/8
CP 642-250/10

5.3-6.3
7.9
9.8

Product features

Approvals

ICBO Evaluation Service, Inc.


California State Fire Marshal
City of New York
City of Los Angeles

Ready-to-use collar, no construction required, therefore


fast installation time
Adjustable/moveable fastening tabs

Tested in accordance with

Collar outside
Collar
No. of
dia. (in.)
Height (in.) hooks and
fasteners
8.2
4.4
6
10.0
6.9
7
12.4
9.1
9

Report No. 5071


Listing No. 1200:105
Report No. MEA 113-96-M
Research Report 25188

UL 1479
ASTM E 814

Installation instructions for CP 642

Firestop
System

1. Clean plastic pipe.

2. Close remaining gap to


provide smoke and gas
tight seal.

3. Close collar.

Opening
1. Clean the plastic pipes. Expansion of the intumescent material
during a fire acts to close the plastic pipe. Very dirty pipes with,
for example, remains of mortar, may lead to a delay in this
closing action. Badly soiled plastic pipes should, therefore, be
cleaned in the area where the CP 642 firestop collar is to
be installed.
Application of firestop system
2. Seal the opening. Gaps must be closed with FS-ONE. The
approved methods vary and are given in the specific UL system.
3. Close the CP 642 firestop collar. Place the CP 642 firestop collar
around the plastic pipe and lock the closure with firm pressure
until it latches.
4. Attach fastening hooks. The fastening hooks can be attached to
various points on the metal housing. This allows the fastening
points to be made to suit the space available in each case.
The hooks must be positioned as symmetrically as possible.
The required number of fastening hooks is indicated on
the packaging.
5. Fastening the CP 642 firestop collar. Only when fastened properly
can CP 642 protect against fire passing through.
- Mark the fastening points.
- Drill holes with a Hilti rotary hammer drill (i.e. TE 5) or,
depending on base material, fasten using Hilti power actuated
tool (e.g. DXA 40).

4. Attach fastening hooks.

5. Fasten collar and


installation plate.
(If required)

- To secure the CP 642 firestop collar, use Hilti anchors/fasteners.


For maintenance reasons, a penetration seal could be
permanently marked with an identification plate. In such a case
mark the identification plate and fasten it in a visible position
next to the seal.
Notice about approvals
When making a pipe seal using Hilti CP 642 Intumescent Firestop
Collar, please refer to the UL directory or Hilti Firestop Manual for
restrictions as to opening size, type and thickness of wall or floor,
maximum pipe diameter, etc.
Not to be used...
With folded and coiled sheet-metal and cast-iron pipes (not tested)
In highly corrosive surroundings
With unapproved anchors/fasteners
Safety precautions
Keep out of the reach of children.
Read the material safety data sheet.
Storage
Store only in the original packaging in a location protected
from moisture.

17

1-800-879-8000

Product Information

CP 618
Firestop Putty Stick
Product description
An intumescent, non-hardening, firestop putty for cable
and pipe penetrations

Areas of application

Single or bundled cables


Non-combustible pipes
Blank openings

For use with

Concrete, masonry and gypsum wall assemblies


Wall and floor assemblies rated up to 3 hours

Examples

LA

SSIFIE

Where telecommunication and data lines penetrate gypsum


wall assemblies
Where steel conduit and EMT penetrate concrete
and block wall assemblies
Where blank openings exist in concrete and
block wall assemblies

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

System/Product advantages

Reusable
Easy to add or subtract cables
Fast installation time

CP 618 Firestop Putty Stick


Description

Color

CP 618 Putty Stick

Package
Contents

Volume
3

red 12 Putty Sticks 18 in per stick

Simplicity

Item No.

00314721

Confidence

Value

18

1-800-879-8000

Installation Instructions

Technical Data
CP 618 Firestop Putty Stick

CP 618
Firestop Putty Stick
Product description
An intumescent, non-hardening, firestop putty for cable
and pipe penetrations

Product features
Contains no volatile solvents or asbestos
Water resistant
Easy to re-penetrate

Tested in accordance with

(at 73F (23C) and 50% relative humidity)


Dimensions:
18 cu. in.
Consistency:
Moldable putty
Color:
Red
Application temperature:
40F (5C) to 95F (35C)
Cure:
Non-curing
Density:
Approx. 1.48 g/cm3
Intumescent activation:
Approx. 220F (104C) to 250F (121C)
Surface burning characteristics: Flame Spread: In progress; call for details
(ASTM E-84-96)
Smoke Development: In progress;
call for details

Approvals

UL 1479
ASTM E 814

ICBO Evaluation Service, Inc.


California State Fire Marshal
City of New York
City of Los Angeles

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

Installation instructions for CP 618

1. Clean opening

2. Slice CP 618 to be
packed into opening
from stick

3. Pack in CP 618

Opening
1. Clean the opening. Surfaces to which CP 618 will be applied
should be cleaned of loose debris, dirt, oil, moisture, frost
and wax.
Application of firestop putty
2. Backing material
Install the prescribed backing material, if required.
3. Application of firestop putty
Install CP 618 Firestop Putty to the required depth, making
sure that the putty contacts all surfaces to provide the
greatest adhesion.
4. Smooth CP 618 putty.
5. Marking
For maintenance reasons, a penetration seal could be
permantently marked with an identification plate. In such a
case, mark the identification plate and fasten it in a visible
position next to the seal.
6. Re-installation (not shown)
Remove and re-install CP 618 Firestop Putty as needed.

4. Smooth CP 618

5. Fasten installation
plate (if required)

Notice about approvals


When using Hilti CP 618 Firestop Putty Stick please refer to the
UL Directory or the Hilti Firestop Manual for restrictions as to
opening size, type and thickness of wall or floor, penetration
type, etc.
Not to be used...
In areas underwater
Safety precautions
Before handling, read the Material Safety Data Sheet for detailed
use and health information.
Wear suitable gloves and eye protection.
Keep out of the reach of children.
Storage
Store only in the original packaging at temperatures
40F (5C) to 104F (40C).

19

1-800-879-8000

Product Information

CP 617
Firestop Putty Pad
Product description
An intumescent moldable firestop putty designed to help protect
electrical outlet boxes

Areas of application

Protection of:
Electrical cabinets
Mechanical cabinets
Electrical outlet boxes

For use with

Gypsum wall assemblies with wood or metal studs

Examples
Where two outlets are within a single stud/cavity or within 24"
LA

SSIFIE

System/Product advantages

Applied by hand
Fast installation

UNDERWRITERS LABORATORIES, INC.


CLASSIFIED
WALL OPENING PROTECTIVE MATERIAL
FIRE RESISTANCE CLASSIFICATION
SEE PRODUCT CATEGORY
IN UL FIRE RESISTANCE DIRECTORY
66Y7

CP 617 Firestop Putty Pad


Description

Color

CP 617 Putty Pad

red

Package
Contents

(Qty 20) 6" X 7" Pads

Simplicity

Area

Item No.
2

42 in per pad

00309760

Confidence

Value

20

1-800-879-8000

Installation Instructions

Technical Data
CP 617 Firestop Putty Pad

CP 617
Firestop Putty Pad
Product description
An intumescent moldable firestop putty designed to help protect
electrical outlet boxes

Product features
Applied by hand
Fast installation

Tested in accordance with


UL 263

(at 73F (23C) and 50% relative humidity)


Dimensions:
6" X 7" X 1/8" (15 X 18 X .3 cm)
Consistency:
Moldable putty
Color:
Red
Application temperature:
40F (5C) to 95F (35C)
Storage temperature:
40F (5C) to 104F (40C)
Cure:
Non-curing
Density:
1.48 g/cm3
Intumescent activation:
Approx. 220F (104C) to 250F (121C)
Volatile solvents:
None
Asbestos fibers:
None
Surface burning characteristics:
Flame Spread: In progress; call for details
(ASTM E-84-96)
Smoke Development: In progress;
call for details

Approvals
ICBO Evaluation Service, Inc.
California State Fire Marshall
City of New York
City of Los Angeles

In progress; call for details


In progress; call for details
In progress; call for details
In progress; call for details

Installation instructions for CP 617

1. Remove label from


one side of CP 617

2. Adhere CP 617
to application

3. Reshape CP 617 to fit


around box

Application of firestop putty


1. Remove label from one side of pad. For a 1 to 2 hour fire rating,
one CP 617 pad is required.
2. Adhere pad to side of the box, overlapping the stud and all
edges of the box.
When drywall is installed: fix pad into gap between electrical
cabinet and gypsum board slightly overlapping the inner wall
board surface.
When drywall will be installed later: overlap front edge of
electrical cabinet so that CP 617 will be compressed around
edges of box as gypsum board is installed.
3. Reshape CP 617 to fit around conduit or cables.
4. Press CP 617 to all sides of electrical box. Trim excess at
corners and apply to conduit fittings connected to the box.
5. Remove other side of label. To help prevent passage of cold
smoke, CP 617 may optionally be placed into inside of electrical
conduit fittings.

4. Press CP 617 to all


sides of application

5. Remove other side


of label

Notice about approvals


CP 617 Firestop Putty Pad is classified by Underwriters
Laboratories, Inc., (UL) as a Wall Opening Protective Material.
Therefore, specific UL listings are not required. Specific details
can be found in the Hilti Firestop Inspection and Installation
Manual and/or current UL Fire Resistance Directory, Volume I.
Not to be used...
In areas underwater
Safety precautions
Before handling, read the product Material Safety Data Sheet and
product label for detailed use and health information.
Wear suitable gloves and eye protection.
Keep out of the reach of children.
Storage
Store only in the original packaging in a location at temperatures
40F (5C) to 104F (40C).

21

1-800-879-8000

Product Information

FS 635
Trowelable Firestop Compound

CP 636
Brands

chutzm
rtel
sodfm,e
v iJdjfiwh
Z8Z23a
riuh. No
wp3i4e
0288u WE
4i5kirdw
27uze
iloi4jtf-
x-.vbvb
u9+12
vh, ireiv
oeoo

Product description
Fire-resistant, cement-based mortar suitable for firestopping
large openings.

Areas of application

Sealing medium-sized to large openings with non-combustible


pipes or cable trays.
Permanent fire seal for cables, cable trays and noncombustible pipes.

For use with

Concrete and masonry assemblies


Walls and floors rated up to 3 hours

Large openings containing multiple steel, conduit and EMT pipes


Large openings with single or multiple cable tray applications

LA

SSIFIE

Examples
R

System/Product advantages

FILL, VOID OR CAVITY MATERIALS


CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7

Fast cleanup
Paintable
Simple application by trowel

FS 635 Firestop Compound


Description

Color

Packaging
contents

Volume

Item No.

FS 635, pail

red

40 lbs

1260 in3

00220425

Simplicity

Confidence

Value

22

1-800-879-8000

Installation Instructions

FS 635
Trowelable Firestop Compound
Product description
Fire-resistant, cement-based mortar suitable for firestopping
large openings.

Product features
High yield
Adheres very well to common substrates (steel, concrete
or masonry)
Contains no asbestos, phenol or halogen constituents

Tested in accordance with


ASTM E 814
UL 1479

Technical Data
FS 635 Firestop Compound
(at 73F (23C) and 50% relative humidity)
Mix ratio:
40 lb:2 gal (mortar to water)
Application temperature:
Ideal between 40F (5C) and 110F (43C)
Color:
Red
Form removal (depending on
consistency):
Approx. 24 hours
Density (ASTM E605):
Approx. 55 pcf
Compressive strength
(after 28 days at 74F):
Approx. 360 psi
Surface burning characteristics:
Flame spread: 0
(ASTM E84-96)
Smoke development: 0
Bond strength (ASTM E726)
To concrete: approx. 4500 psf
To steel: approx. 3400 psf
Thermal conductivity (ASTM C518) 1748 BTU-in./hr ft2F

Approvals
ICBO Evaluation Service, Inc.
California State Fire Marshal
City of New York
City of Los Angeles

Report No. 5071


Listing No. 1200:102
Report No. MEA 321-93-M
Research Report 25188

Installation instructions for FS 635


Ausfhrungsschild

1. Clean opening,
moisten surfaces

2. Mix FS 635 mortar


with water

3. Put mortar into place,


using forming as
necessary

Opening
1. Clean and pre-moisten surfaces.
- Cables and cable supporting structures must be installed in
compliance with local building and electrical standards.
Application of firestop compound
2. Mix the mortar.
- Add water to mortar in a ratio of about 2 gallons to 40 lbs.
(water to mortar). Stir the mixture thoroughly with, for
example, a Hilti mixing paddle. The mix ratio of water
to FS 635 determines the desired consistency (stiffness).
- Do not use any other binders or additives/aggregates.
3. Apply the mortar.
- Use forms on one or both sides for larger penetrations, as
needed. Apply mixed mortar in the opening using a trowel or
a pump and compact it. Make sure all gaps and spaces are
completely filled and closed.
4. For maintenance reasons, a penetration seal could be
permanently marked with an identification plate. In such a
case mark the identification plate and fasten it in a visible position
next to the seal.

4. Fasten identification
plate in place
(if required)

Notice about approvals


When making a seal using Hilti FS 635 Trowelable Firestop
Compound, please refer to the UL Directory and/or Hilti Firestop
Manual for restrictions as to opening size, type and thickness of
wall or floor, maximum cable diameter, etc.
Not to be used...
As a structural material for bearing external loads.
In penetrations subject to significant movement.
Safety precautions
Keep out of the reach of children.
Before handling, read the material safety data sheet.
Storage
Store only in the original packaging in a location protected
from moisture.
Observe expiration date on pail.

23

1-800-879-8000

Firestop Accessories

Description

Item Number

Picture

Foil Pack (600 ml) Dispenser

00024669

Nozzles (Qty. 10) for Foil Pack

000220139

300/310 ml Dispenser (CB 200 PL)

00055205

Standard 300/310 ml Dispenser

00024825

Bulk Caulk Gun

98450002

Follow Plate

98450004

Force Flow Bulk Loader

98450020

Benron EZ-Tex Firestop Sprayer

00332214

Mineral Wool (18,432 in3)

00236993

Stainless Steel Mixing Paddle

00024155

Retaining Collar (25 ft. Roll)

00029410

Collar Clamps (Qty. 10-4" dia.)

00029783

Hilti Firestop System Identification Plate

00306219

1
2

6
5

Simplicity

Confidence

Value

24

1-800-879-8000

Selection Chart

Firestop Selection Chart Through Penetrations


How to use the selection chart
Hilti has simplified the process for selecting the correct UL system for your application. Simply identify the penetrating item
(metal pipe, insulated metal pipe, cable, etc.) and the base material.
C Concrete or Concrete Block

G Gypsum

W Wood Frame

Match the two items within the selection chart below to identify the Hilti UL System. Additional systems are available by contacting
your local Hilti Sales Representative or Customer Service at (800) 879-8000.

Base
Material

Fire
Rating
(F Rating)

Hilti
Product
Used

UL
System
Number

Page
Number

Blank opening (sleeved)

3-hour

FIRE BLOCK

CAJ 0055

28

Blank opening

3-hour

CP 618

CAJ 0058

29

3-hour

FS-ONE

CAJ 1155

31

Steel, copper, conduit or EMT

3-hour

FS-ONE

CAJ 1184

32

Steel, copper, conduit or EMT

3-hour

FS-ONE

CAJ 1226

33

Penetrating Item

Blank Openings

Metal Pipe

Steel, copper, conduit or EMT

(sleeved or unsleeved)

(sleeved or unsleeved)
C

Steel, conduit, or EMT

3-hour

CP 618

CAJ 1276

34

Steel, cast iron, conduit, or EMT

3-hour

CP 618

CAJ 1277

35

Steel, copper, conduit or EMT

3-hour

FS-ONE

CAJ 1278

36

Steel, copper, conduit or EMT (sleeved)

4-hour

FS-ONE

WJ 1041

64

Steel, copper, conduit or EMT

4-hour

FS-ONE

WJ 1042

65

Steel, copper, conduit or EMT

1 or 2-hour

FS-ONE

WL 1054

72

Steel or copper (sleeved)

2-hour

FS-ONE

WL 1058

73

Steel, cast iron, copper, conduit or EMT

1 or 2-hour

FS-ONE

WL 1085

74

Steel, copper, conduit or EMT (sleeved)

4-hour

FS-ONE

WL 1110

75

Steel, copper, conduit or EMT

4-hour

FS-ONE

WL 1111

76

Steel, copper, conduit or EMT

1 or 2-hour

FS-ONE

FC 1009

58

PVC, CPVC, ABS, FRPP (vented or closed)

3-hour

CP 642/643

CAJ 2109

37

PVC, CPVC, ABS, FRPP (vented or closed)

3-hour

CP 642/643

CAJ 2110

38, 39

3-hour

FS-ONE

CAJ 2118

40

PVC, CPVC (vented or closed)

3-hour

FS-ONE

CAJ 2141

41

PVDF (vented or closed)

3-hour

FS-ONE

CAJ 2217

42

PVC, CPVC, ABS, FRPP (vented or closed)

2-hour

CP 642/643

FA 2025

57

ENT (sleeved or unsleeved)

1 or 2-hour

FS-ONE

WL 2075

77

PVC, CPVC, ABS, FRPP (vented or closed)

1 or 2-hour

CP 642/643

WL 2078

78

PVC, CPVC (closed)

1 or 2-hour

FS-ONE

WL 2098

79

PVC, CPVC, ABS, FRPP (vented or closed)

1 or 2-hour

CP 643

FC 2025

59

PVC, CPVC, ABS, FRPP (vented or closed)

1-hour

CP 643

FC 2030

60

PVC, CPVC (vented or closed) main w/ PVC,

1-hour

CP 643 w/FS-ONE FC 2050

61

Plastic and Glass Pipe

(sleeved)
C

Glass pipe (vented or closed)


(sleeved or unsleeved)

CPVC (vented or closed) branch

25

1-800-879-8000

Selection Chart
Base
Material

Fire
Rating
(F Rating)

Hilti
Product
Used

UL
System
Number

Page
Number

3-hour

FS-ONE

CAJ 3095

43

Multiple cables

3-hour

CP 642/643

CAJ 3096

44

Single cable

3-hour

CP 618

CAJ 3138

45

Multiple cables

3-hour

CP 618

CAJ 3139

46

Cable trays (steel or aluminum)

3-hour

FS 635

CAJ 4017

47

Penetrating Item

Cables/Cable Trays
C

Single or multiple cables


(sleeved or unsleeved)

Cable tray (steel or aluminum)

3-hour

FIRE BLOCK

CAJ 4035

48

Single or multiple cables

2-hour

CP 618

WJ 3036

66

Spine cable trays (steel or aluminum)

2-hour

FIRE BLOCK

WJ 4016

67

Single or multiple cables

1 or 2-hour

FS-ONE

WL 3065

80

1 or 2-hour

CP 618

WL 3111

81

Single or multiple cables (sleeved)

1 or 2-hour

CP 618

WL 3112

82

Cable tray (steel or aluminum)

1 or 2-hour

FIRE BLOCK

WL 4011

83

(sleeved or unsleeved)

(sleeved or unsleeved)
G

Single or multiple cables


(sleeved or unsleeved)

Spine cable trays (steel or aluminum)

1 or 2-hour

FIRE BLOCK

WL 4019

84

Single or multiple cables

1 or 2-hour

FS-ONE

FC 3012

62

3-hour

FS-ONE

CAJ 5090

49

2-hour

FS-ONE

CAJ 5091

50

2-hour

FS-ONE

CAJ 5113

51

4-hour

FS-ONE

WJ 5028

68

1 or 2-hour

FS-ONE

WL 5025

85

1 or 2-hour

FS-ONE

WL 5028

86

1 or 2-hour

FS-ONE

WL 5029

87

4-hour

FS-ONE

WL 5073

88

1 or 2-hour

FS-ONE

FC 5004

63

Electrical busway

3-hour

FS 635

CAJ 6006

52

Electrical busway

3-hour

FS-ONE

CAJ 6017

53

Metal duct w/o damper

1-hour

FS 601

WJ 7001

69

Metal duct w/o damper

1-hour

FS 601

WL 7003

89

Metal duct w/o damper (sleeved)

1-hour

FS-ONE

WL 7017

90

Insulated Metal Pipes


C

Steel or copper w/AB/PVC insulation


(sleeved or unsleeved)

Steel or copper w/glass fiber insulation


(sleeved or unsleeved)

Steel or copper w/glass fiber insulation


(sleeved or unsleeved)

Steel, copper, conduit or EMT


w/glass fiber insulation (sleeved)

Steel, copper, conduit or EMT w/glass


fiber insulation (sleeved or unsleeved)

Steel, copper, conduit or EMT


w/AB/PVC insulation

Steel, copper, conduit or EMT


w/glass fiber insulation

Steel, copper, conduit or EMT


w/glass fiber insulation (sleeved)

Steel, copper, conduit or EMT


w/glass fiber or AB/PVC insulation
Metal Ducts and Electrical Busway

Simplicity

Confidence

Value

26

1-800-879-8000

Selection Chart
Base
Material

Fire
Rating
(F Rating)

Hilti
Product
Used

UL
System
Number

Page
Number

3-hour

FS 635

CAJ 1140

30

3-hour

FS-ONE

CAJ 8041

54

3-hour

FIRE BLOCK

CAJ 8056

55

Multiple cables, EMT, and PVC (closed)

2-hour

FS-ONE

WJ 8004

70

Multiple insulated and non-insulated steel,

4-hour

FIRE BLOCK

WJ 8007

71

Multiple cables, EMT, and PVC (closed)

2-hour

FS-ONE

WL 8004

91

Multiple insulated and non-insulated steel,

1 or 2-hour

FIRE BLOCK

WL 8013

92

4-hour

FIRE BLOCK

WL 8014

93

Floor to floor (concrete to concrete)

3-hour

CP 601S

FFD-1011*

94

Floor to floor (concrete to concrete)

2-hour

CP 606

FFD-1012*

95

Floor to floor (concrete to concrete)

2-hour

CP 672

FFD-1013*

96

Floor to wall (concrete to concrete)

3-hour

CP 601S

FWD-1011*

97

Floor to wall (concrete to concrete)

2-hour

CP 606

FWD-1012*

98

Penetrating Item

Large Openings
Multiple Penetrations
C

Multiple pipes: Steel, copper,


conduit or EMT

Multiple insulated and non-insulated steel,


copper, conduit, or EMT

Multiple insulated and non-insulated steel,


copper, EMT, cables and cable trays

copper, EMT, cables and cable trays

copper, EMT, cables, cable trays and PVC


plastic pipe

Multiple insulated and non-insulated steel,

copper, EMT, cables and cable trays


Joints

Floor to wall (concrete to concrete)

2-hour

CP 672

FWD-1013*

99

Concrete block wall to metal deck

1 or 2-hour

FS 601 or

HWD-0008

104

(top of wall)

Concrete block wall to concrete floor

FS-ONE
3-hour

CP 601S

HWD-1008*

108

2-hour

CP 606

HWD-1009*

109

3-hour

CP 601S

WWD-1011*

110

(top of wall)

Concrete block wall to concrete floor

(top of wall)

Wall to wall (concrete to concrete)

Wall to wall (concrete to concrete)

2-hour

CP 606

WWD-1012*

111

Gypsum wall to metal deck (top of wall)

1 or 2-hour

FS 601 or

HWD-0003

100

Gypsum wall to metal deck (top of wall)

1 or 2-hour

FS 601

HWD-0004

101, 102

Gypsum wall to metal deck (top of wall)

1 or 2-hour

FS 601 or

HWD-0005

103

HWD-0010

105

FS-ONE
G

FS-ONE
G

Gypsum wall to concrete floor (top of wall)

1 or 2-hour

FS 601 or
FS-ONE

Gypsum wall to metal deck

2-hour

CP 672

HWD-0042*

106

Gypsum wall to metal deck (top of wall)

1 or 2-hour

CP 606

HWD-0045*

107

* Meets new UL 2079 standard with 500 cycles.

27

1-800-879-8000

UL System Number CAJ0055

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Cut FIRE BLOCK 1/2" larger than diameter of opening. Firmly pack FIRE BLOCK into opening. Orientation of FIRE BLOCK is
noted above in the UL System Drawing.

Simplicity

Confidence

Value

28

1-800-879-8000

UL System Number CAJ0058

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack backer rod into opening as a permanent form. Backer rod should be recessed from top surface of floor
or from both surfaces of wall as required to accommodate the required thickness of fill material.
STEP 3 - FIRESTOP PUTTY: Apply the required thickness of putty material over the backing material within the annulus, flush with top surface of
floor or with both surfaces of wall.

Simplicity

Confidence

Value

29

1-800-879-8000

UL System Number CAJ1140

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING: Cut forms (i.e. plywood or foam insulation board) to fit as closely as possible around all penetrating items. To keep FS 635
from sticking to the forms, cover them with plastic or apply an appropriate release agent. Fasten forms to the surface of the substrate or friction fit
forms within opening to allow a min. 2-1/2" space for FS 635. Seal any remaining gaps with Hilti CF 128 Filler Foam and allow it to cure for at least
1 hour.
STEP 3 - FIRESTOP COMPOUND: Mix FS 635 with water according to the instructions on the container. Apply mixture in the forms to a min. depth
of 2-1/2". Using a trowel, push the material in place to completely fill the opening and smooth the surface for neat, finished appearance.
STEP 4 - REMOVE FORMS (optional): Forms may be removed after 24 hours.

30

1-800-879-8000

UL System Number CAJ1155

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

31

1-800-879-8000

UL System Number CAJ1184

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant flush with the top or bottom of the floor. Wall penetrations and Pre-cast
(Hollow-Core) Units require Firestop Sealant installed flush with both sides. Tool the sealant with a putty knife to push it in place and smooth the
surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

32

1-800-879-8000

UL System Number CAJ1226

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping material.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

33

1-800-879-8000

UL System Number CAJ1276

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP PUTTY: Apply the required depth of putty material within the annulus, flush with top surface of floor or with both surfaces
of wall.

Simplicity

Confidence

Value

34

1-800-879-8000

UL System Number CAJ1277

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack backer rod into opening as a permanent form. Backer rod should be recessed from top surface of floor
or from both surfaces of wall as required to accommodate the required thickness of fill material.
STEP 3 - FIRESTOP PUTTY: Apply the required thickness of putty material over the backing material within the annulus, flush with top surface of
floor or with both surfaces of wall.

Simplicity

Confidence

Value

35

1-800-879-8000

UL System Number CAJ1278

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant flush with the top of the floor. Wall penetrations require Firestop
Sealant installed flush with both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal
undisturbed for 48 hours.

Simplicity

Confidence

Value

36

1-800-879-8000

UL System Number CAJ2109

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: To impede cold smoke, apply Firestop Sealant within annulus, flush with bottom surface of floor or both surfaces
of wall.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to base material with recommended fasteners. Wall penetrations require the installation of a firestop device on both sides.

Simplicity

Confidence

Value

37

1-800-879-8000

UL System Number CAJ2110

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: To impede cold smoke, apply Firestop Sealant within annulus, flush with bottom surface of floor or both surfaces
of wall.
STEP 3 - COVER PLATE: Cut sheet metal cover plate out of min. 18 Ga. steel with max. inside diameter 1/4" larger than outside diameter of pipe.
The outer diameter of cover plate should be 2-1/2" larger than outside diameter of pipe. Install on underside of floor or both sides of wall between
collar and floor or wall surface.
STEP 4 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
"click". Install the required number of mounting tabs around the device and secure to base material with recommended fasteners. Wall penetrations require the installation of a firestop device on both sides.
R

38

1-800-879-8000

UL System Number CAJ2110

Simplicity

Confidence

Value

39

1-800-879-8000

UL System Number CAJ2118

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

40

1-800-879-8000

UL System Number CAJ2141

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 -FORMING MATERIAL: Install the required depth of CF 128 Filler Foam around the penetrating item as a permanent form. Forming material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

41

1-800-879-8000

UL System Number CAJ2217

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: To impede cold smoke, apply Firestop Sealant within annulus, flush with bottom surface of floor or both surfaces
of wall.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
"click". Install the required number of mounting tabs around the device and secure to base material with recommended fasteners. Wall penetrations require the installation of a firestop device on both sides.

Simplicity

Confidence

Value

42

1-800-879-8000

UL System Number CAJ3095

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

43

1-800-879-8000

UL System Number CAJ3096

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.
STEP 4 - FIRESTOP DEVICE: Place the device around the cable bundle and press together the open ends firmly until it catches (close) with an
audible click. Install the required number of mounting tabs around the device and secure to base material with recommended fasteners.
Wall penetrations require the installation of a firestop device on both sides.
R

44

1-800-879-8000

UL System Number CAJ3138

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clear, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP PUTTY: Apply the required thickness of putty material over the backing material within the annulus, flush with top surface of
floor or with both surfaces of wall.

Simplicity

Confidence

Value

45

1-800-879-8000

UL System Number CAJ3139

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of putty material.
STEP 3 - FIRESTOP PUTTY: Apply the required thickness of putty material over the packing material within the annulus, flush with top surface of
floor or with both surfaces of wall.

Simplicity

Confidence

Value

46

1-800-879-8000

UL System Number CAJ4017

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING: Cut forms (i.e, plywood or foam insulation board) to fit as closely as possible around all penetrating items. To keep FS 635
from sticking to the forms, cover them with plastic or apply an appropriate release agent. Fasten forms to the surface of the substrate or friction fit
forms within opening to allow a min. 2-1/2" space for FS 635. Seal any remaining gaps with Hilti CF 128 Filler Foam and allow it to cure for at least
1 hour.
STEP 3 - FIRESTOP COMPOUND: Mix FS 635 with water according to the instructions on the container. Apply mixture in the forms to a min. depth
of 2-1/2". Using a trowel, push the material in place to completely fill the opening and smooth the surface for neat, finished appearance.
STEP 4 - REMOVE FORMS (optional): Forms may be removed after 24 hours.

47

1-800-879-8000

UL System Number CAJ4035

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

48

1-800-879-8000

UL System Number CAJ5090

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

49

1-800-879-8000

UL System Number CAJ5091

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal
undisturbed for 48 hours.

Simplicity

Confidence

Value

50

1-800-879-8000

UL System Number CAJ5113

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal
undisturbed for 48 hours.

51

1-800-879-8000

UL System Number CAJ6006

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING: Cut forms (i.e. plywood or foam insulation board) to fit as closely as possible around penetrating item. To keep FS 635 from
sticking to the forms, cover them with plastic or apply an appropriate release agent. Fasten forms to the surface of the substrate or friction fit
forms within opening to allow a min. 2-1/2" space for FS 635. Seal any remaining gaps with Hilti CF 128 Filler Foam and allow it to cure for at least
1 hour.
STEP 3 - FIRESTOP COMPOUND: Mix FS 635 with water according to the instructions on the container. Apply mixture in the forms to a min. depth
of 2-1/2". Using a trowel, push the material in place to completely fill the opening and smooth the surface for neat, finished appearance.
STEP 4 - REMOVE FORMS (optional): Forms may be removed after 24 hours.

52

1-800-879-8000

UL System Number CAJ6017

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

53

1-800-879-8000

UL System Number CAJ8041

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus. Wall penetrations require
Firestop Sealant installed on both sides. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

54

1-800-879-8000

UL System Number CAJ8056

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of
FIRE BLOCK is noted above in the UL System Drawing.
STEP 3 FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

55

1-800-879-8000

UL System Number FA2025

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - METAL PLATE ENCLOSURE: Build metal pan enclosure to dimensions listed in drawing. Both ends of plate, perpendicular to flutes,
should be cut to permit the ends to be bent upward 90 to follow the contour of the metal deck.
STEP 3 - PACKING MATERIAL: Firmly pack mineral wool into flutes of metal deck above metal plate enclosure to completely fill cavities. Bend
metal enclosure to conform to metal decking enclosing the packing material.
STEP 4 - FIRESTOP SEALANT: Apply bead of Firestop Sealant around the perimeter of the metal plate enclosure at the interface of the enclosure and
steel deck.
STEP 5 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to base material with recommended fasteners. Wall penetrations require the installation of a firestop device on both sides.
R

56

1-800-879-8000

UL System Number FA2025

Simplicity

Confidence

Value

57

1-800-879-8000

UL System Number FC1009

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT AT SUBFLOOR: Apply the required depth of Firestop Sealant in the annular space between the pipe and subfloor. Tool
the sealant with a putty knife to push it in place and smooth the surface.
STEP 3 - FIRESTOP SEALANT AT TOP PLATE: Apply a generous bead of Firestop Sealant in the annular space between the pipe and the top plate.
Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for 48 hours.

Simplicity

Confidence

Value

58

1-800-879-8000

UL System Number FC2025

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annular space between the pipe and subfloor and between the
pipe and the top plate. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for
48 hours.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to the subfloor, with recommended fasteners.

Simplicity

Confidence

Value

59

1-800-879-8000

UL System Number FC2030

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annular space between the pipe and subfloor and between the
pipe and the top plate. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for
48 hours.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to the top plate, with recommended fasteners.

Simplicity

Confidence

Value

60

1-800-879-8000

UL System Number FC2050

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annular space between the pipe and subfloor and between the
pipe and the top plate. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for
48 hours.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to the subfloor, with recommended fasteners.
STEP 4 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annular space between the branch pipe and the subfloor. Tool the
sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for 48 hours.

61

1-800-879-8000

UL System Number FC3012

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT AT SUBFLOOR: Apply the required depth of Firestop Sealant in the annular space between the cables and the subfloor. Tool the sealant with a putty knife to push it in place and smooth the surface.
STEP 3 - FIRESTOP SEALANT AT TOP PLATE: Apply a generous bead of firestop sealant in the annular space between the cables and the top plate.
Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for 48 hours.

Simplicity

Confidence

Value

62

1-800-879-8000

UL System Number FC5004

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT AT SUBFLOOR: Apply the required depth of Firestop Sealant in the annular space between the insulated pipe and the
subfloor. Tool the sealant with a putty knife to push it in place and smooth the surface.
STEP 3 - FIRESTOP SEALANT AT TOP PLATE: Apply a generous bead of firestop sealant in the annular space between the insulated pipe and the top
plate. Tool the sealant with a putty knife to push it in place and smooth the surface. Leave both completed seals undisturbed for 48 hours.

Simplicity

Confidence

Value

63

1-800-879-8000

UL System Number WJ1041

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annulus, flush with both sides of wall. Tool the sealant with a
putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

64

1-800-879-8000

UL System Number WJ1042

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annulus, flush with both sides of wall. Tool the sealant with a
putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

65

1-800-879-8000

UL System Number WJ3036

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP PUTTY: Putty to be forced into interstices of cables to maximum extent possible. Also, apply the required depth of putty
material within the annulus, with additional crown on both sides of wall.

Simplicity

Confidence

Value

66

1-800-879-8000

UL System Number WJ4016

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

67

1-800-879-8000

UL System Number WJ5028

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annulus, flush with both sides of wall. Tool the sealant with a
putty knife to push it in place and smooth the surface. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

68

1-800-879-8000

UL System Number WJ7001

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant in the annular space between the duct and wall on both sides and tool
with a putty knife until flush with both surfaces. Leave completed seal undisturbed for 48 hours.
STEP 3 - STEEL RETAINING ANGLE: Leave seal undisturbed for 48 hours before attaching angle. Fasten recommended steel angle to all four sides
of the air duct on both sides of the wall with the appropriate fasteners and recommended spacing. Angle does not have to be attached to the wall.

Simplicity

Confidence

Value

69

1-800-879-8000

UL System Number WJ8004

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - SLEEVE (hollow block walls only): Measure the thickness of the wall and cut No. 8 steel wire mesh or sheet metal (min. 20 gauge) to a
length 1/4" less than the wall thickness. Center the sleeve in the wall and form it to fit the perimeter of the opening. Ends (seam) should overlap at
least 1".
STEP 3 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating items as a permanent form. Packing material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 4 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the annulus on both sides of wall and
tool with a putty knife until flush with both surfaces. Leave completed seal undisturbed for 48 hours.

70

1-800-879-8000

UL System Number WJ8007

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

71

1-800-879-8000

UL System Number WL1054

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

72

1-800-879-8000

UL System Number WL1058

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - SLEEVE: Cut No. 8 steel wire mesh or min. 20 gauge galvanized sheet metal to a length of 4-3/4". Form it into a cylindrical shape and
insert it into the opening. Center it in the wall and allow it to spring out and conform to the opening. Ends (seam) should overlap at least 1".
STEP 3 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating items as a permanent form. Packing material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 4 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

73

1-800-879-8000

UL System Number WL1085

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

74

1-800-879-8000

UL System Number WL1110

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

75

1-800-879-8000

UL System Number WL1111

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

76

1-800-879-8000

UL System Number WL2075

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

77

1-800-879-8000

UL System Number WL2078

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: To impede cold smoke, apply required depth of Firestop Sealant in annular space around pipe.
STEP 3 - FIRESTOP DEVICE: Place the device around the plastic pipe and press together the open ends firmly until it catches (close) with an audible
click. Install the required number of mounting tabs around the device and secure to base material with recommended fasteners.
STEP 4 - FIRESTOP SEALANT: Leave completed cold smoke seal undisturbed for at least 48 hours. Repeat steps 1-4 on the opposite side
of the wall.

Simplicity

Confidence

Value

78

1-800-879-8000

UL System Number WL2098

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

79

1-800-879-8000

UL System Number WL3065

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

80

1-800-879-8000

UL System Number WL3111

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP PUTTY: Putty to be forced into interstices of cables to maximum extent possible. Also, apply the required depth of putty
material within the annulus, with additional crown on both sides of wall.

Simplicity

Confidence

Value

81

1-800-879-8000

UL System Number WL3112

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the cables as a permanent form. Packing material should be
recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Putty.
STEP 3 - FIRESTOP PUTTY: Putty to be forced into interstices of cables to maximum extent possible. Also, apply the required depth of putty
material within the annulus.

Simplicity

Confidence

Value

82

1-800-879-8000

UL System Number WL4011

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

83

1-800-879-8000

UL System Number WL4019

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

84

1-800-879-8000

UL System Number WL5025

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall.
STEP 3 - RETAINING COLLAR: Measure and cut enough retaining collar to encircle the penetrating item and overlap the ends at least 1". Bend the
anchor tabs (long tabs with hole) outward 90, and bend every 3rd support tab (short tapered tab) inward 90. Wrap the collar around the pipe
insulation so the anchor tabs contact the wall and the support tabs rest on the pipe insulation. The ends should overlap at least 1". Place a collar
clamp (or several clamps fastened together) around the collar at mid-height and gently tighten it until collar is supported in the correct position.
Fasten every other anchor tab to the wall using Hilti Toggler Bolts.
STEP 4 - FIRESTOP SEALANT: Completely fill the retaining collar with FS-ONE. Bend the remaining support tabs inward 90. Gently tighten the
collar clamp(s) to remove any slack. Excess sealant may be removed with a putty Knife. Leave completed seal undisturbed for 48 hours. Repeat
steps 1-4 on the opposite side of the wall.
R

85

1-800-879-8000

UL System Number WL5028

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

86

1-800-879-8000

UL System Number WL5029

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

87

1-800-879-8000

UL System Number WL5073

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating item as a permanent form. Packing material
should be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

88

1-800-879-8000

UL System Number WL7003

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.
STEP 3 - STEEL RETAINING ANGLE: Leave seal undisturbed for 48 hours before attaching angle. Fasten recommended steel angle to all four sides
of the air duct on both sides of the wall with the appropriate fasteners and recommended spacing. Angle does not have to be attached to the wall.

Simplicity

Confidence

Value

89

1-800-879-8000

UL System Number WL7017

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials
STEP 2 - FORMING MATERIAL: Install CF 128 Filler Foam around the penetrating item, recessing it from both surfaces of the wall as required to
allow proper space for the firestop sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

90

1-800-879-8000

UL System Number WL8004

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - SLEEVE: Measure the thickness of the wall and cut No. 8 steel wire mesh or sheet metal (min. 20 Gauge) to a length 1/4" less than the
wall thickness. Center the sleeve in the wall and form it to fit the perimeter of the opening. Ends (seam) should overlap at least 1".
STEP 3 - PACKING MATERIAL: Firmly pack required depth of mineral wool around the penetrating items as a permanent form. Packing material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 4 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant within the annulus on both sides of wall. Tool with a putty knife until
flush with both surfaces. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

91

1-800-879-8000

UL System Number WL8013

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

92

1-800-879-8000

UL System Number WL8014

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRE BLOCK: Firmly pack FIRE BLOCK into opening. FIRE BLOCK may be cut to fit properly around penetrating items. Orientation of FIRE
BLOCK is noted above in the UL System Drawing.
STEP 3 - FIRESTOP SEALANT: Apply Firestop Sealant around penetrating items and in all voids that exist after FIRE BLOCKS are installed.

Simplicity

Confidence

Value

93

1-800-879-8000

UL System Number FF-D-1011

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with top surface of floor.
Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

94

1-800-879-8000

UL System Number FF-D-1012

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with top surface of floor.
Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

95

1-800-879-8000

UL System Number FF-D-1013

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SPRAY: Spray or trowel the required depth of Firestop Spray to completely cover forming material and to overlap a min. of 1/2
onto the top surface of the floor on both sides of joint.

Simplicity

Confidence

Value

96

1-800-879-8000

UL System Number FW-D-1011

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with top surface of floor
Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

97

1-800-879-8000

UL System Number FW-D-1012

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with top surface of floor.
Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

98

1-800-879-8000

UL System Number FW-D-1013

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from the top surface
of floor to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SPRAY: Spray or trowel the required depth of Firestop Spray to completely cover forming material and to overlap a min. of 1/2"
onto the top surface of the floor and side of wall.

Simplicity

Confidence

Value

99

1-800-879-8000

UL System Number HW-D-0003

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Firmly pack required depth of mineral wool into the fluted deck opening as a permanent form. Forming material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material within the flutes of the steel floor units and
between the top of the wallboard and the bottom of the steel floor units, flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

100

1-800-879-8000

UL System Number HW-D-0004

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - WALLBOARD, GYPSUM: For 1 hour fire rated walls, an additional layer of nom. 5/8" thick gypsum wallboard shall be installed at the top
of the wall and cut to fit the contour of the steel units to match the base layer. The additional layer shall extend a min. 6-1/2" below steel floor unit
valleys and be secured to each stud with a min. of two screws.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant between the top of the wallboard and all surfaces of the steel floor units,
flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

101

1-800-879-8000

UL System Number HW-D-0004

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant between the top of the wallboard and all surfaces of the steel floor units,
flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

102

1-800-879-8000

UL System Number HW-D-0005

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant between the top of the wallboard and the bottom of the steel floor unit,
flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

103

1-800-879-8000

UL System Number HW-D-0008

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Firmly pack required depth of mineral wool into the fluted deck opening as a permanent form. Forming material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material within the flutes of the steel floor units and
between the top of the wall and the bottom of the steel floor units, flush with each surface of wall assembly. Leave completed seal undisturbed for
48 hours.

Simplicity

Confidence

Value

104

1-800-879-8000

UL System Number HW-D-0010

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant between the top of the wallboard and the bottom of the concrete floor,
flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

105

1-800-879-8000

UL System Number HW-D-0042

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Compress mineral wool 50 percent in thickness and insert into the flutes of the steel floor units above the top of the
ceiling runner, flush with wall surface. Strips of mineral wool are then to be compressed and tightly packed into the gap between the top of the
wallboard and bottom of the steel floor units on both sides of wall.
STEP 3 - FIRESTOP SPRAY: Spray or trowel the required depth of Firestop Spray to completely cover forming material and to overlap a min. of 1/2"
onto wallboard and steel deck on both sides of wall.

Simplicity

Confidence

Value

106

1-800-879-8000

UL System Number HW-D-0045

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Firmly pack required depth of mineral wool into the fluted deck opening as a permanent form. Forming material
should be recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material within the flutes of the steel floor units and
between the top of the wallboard and the bottom of the steel floor units, flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

107

1-800-879-8000

UL System Number HW-D-1008

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Firmly pack required depth of mineral wool into the joint as a permanent form. Forming material should be
recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material between the top of the wall and the bottom of
the floor, flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

108

1-800-879-8000

UL System Number HW-D-1009

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - FORMING MATERIAL: Firmly pack required depth of mineral wool into the joint as a permanent form. Forming material should be
recessed from both surfaces of wall as required to accommodate the required thickness of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the forming material between the top of the wall and the bottom of
the floor, flush with each surface of wall assembly. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

109

1-800-879-8000

UL System Number WW-D-1011

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from each surface of
wall to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with each surface of
wall. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

110

1-800-879-8000

UL System Number WW-D-1012

Installation Instructions
STEP 1 - PREPARATION: All surfaces must be clean, sound, dry and frost free prior to application of firestopping materials.
STEP 2 - PACKING MATERIAL: Firmly pack required depth of mineral wool into the opening as a permanent form, recessing it from each surface of
wall to accommodate the required depth of Firestop Sealant.
STEP 3 - FIRESTOP SEALANT: Apply the required depth of Firestop Sealant over the packing material within the joint, flush with each surface of
wall. Leave completed seal undisturbed for 48 hours.

Simplicity

Confidence

Value

111

1-800-879-8000

Estimating Tables**
TABLE 1 PACKAGING COVERAGE CHART
Product Description

FS-ONE High Performance


Intumescent Firestop Sealant
CP 601S Elastomeric Firestop Sealant

CP 606 Flexible Firestip Sealant

Packaging

Contents (cubic inches)

10.1 fl.oz. tube

18.2

600 ml foil pack

36.4

5.0 gallon bucket

1155

10.5 fl.oz. tube

18.9

600 ml foil pack

36.4

5.0 gallon bucket

1155

10.5 fl.oz. tube

18.9

600 ml foil pack

36.4

5.0 gallon bucket

1155

FS 635 Trowelable Firestop Compound

40 lb bucket

1260

FS 657 Fire Block

single blocks

80.0

(2" X 5" X 8")


CP 617 Firestop Putty Pads

6" x 7" x 1/8"

5.25

CP 618 Firestop Putty Stick

1-1/4" x 1-1/2" x 10"

18.0

CP 672 Firestop Joint Spray

5.0 gallon bucket

1155

Retaining Collar (for use with FS-ONE)

1 roll/box

25 ft. (300 in.)

Mineral Wool

1 box

18432

4 pcs (48" x 24" x 4")

TABLE 2 CALCULATION CHART FOR PIPE AREAS


Nominal Pipe Size

Pipe O.D.

Area (sq.in.)

1/2"

0.84

0.55

1"

1.3

1.33

1-1/2"

1.9

2.83

2"

2.4

4.52

3"

3.5

9.62

4"

4.5

15.9

6"

6.6

34.19

8"

8.6

58.06

10"

10.8

91.56

12"

12.75

127.61

Pipe O.D. based on schedule 40 steel pipe

Simplicity

Confidence

Value

112

1-800-879-8000

Estimating Tables**
TABLE 3 ESTIMATION CHART: VOLUME OF FIRESTOP AT 1/2" DEPTH (in3)
A
O.D.*

0.84

1.05

1.3
N

H O L E

S I Z E

( I N . )

1/2

3/4

1.9
O

2.4
M

1-1/2

3.5
A

4.5
I

5.6

6.6

8.6

10.8

12.8

10

12

0.12

1-1/2

0.60

0.46

0.22

1.30

1.14

0.90

0.16

2-1/2

2.18

2.02

1.78

1.04

0.20

3.26

3.10

2.86

2.12

1.28

3-1/2

4.54

4.38

4.14

3.40

2.54

6.00

5.84

5.62

4.86

4.02

1.48

9.54

9.38

9.14

8.40

7.56

5.00

13.86

13.70

13.46

12.72

11.86

9.32

6.18

1.82

18.96

18.80

18.56

17.82

16.98

14.42

11.28

6.92

24.84

24.68

24.46

23.70

22.86

20.32

17.18

12.82

8.02

31.52

31.36

31.12

30.38

29.54

26.98

23.84

19.48

14.70

2.76

10

38.98

38.82

38.58

37.84

36.98

34.44

31.30

26.94

22.16

10.22

12

56.24

56.08

55.86

55.10

54.26

51.72

48.58

44.22

39.42

27.50

10.74

1.86
2.14

14

76.66

76.50

76.26

75.52

74.66

72.12

68.98

64.62

59.84

47.90

31.14

13.12

16

100.20

100.10

99.82

99.06

98.22

95.68

92.54

88.18

83.38

71.46

54.70

36.68

Coverages are based on the outside diameter of schedule 40 steel pipe.


* For insulated pipes, use the outside diameter of the insulation.
- For 1/4" depth, divide above number by 2.
- For 5/8" depth, multiply above number by 1.25.
- For 3/4" depth, multiply above number by 1.50.
- For 1" depth, multiply above number by 2.
- For 1-1/4" depth, multiply above number by 2.5.
Note: Walls require firestop on both sides; multiply above number again by 2.

TABLE 4 ESTIMATION CHART: VOLUME OF FIRESTOP USED IN RETAINING COLLAR AROUND VENTED PLASTIC PIPE
FS ONE

Approximate

Collar

Pipe

Pipe

Collar

Volume

# of 10.1 oz.

Length

# of

I.D.

O.D.

I.D.

Required

Tubes Required

Required*

Clamps

(in.)

(in.)

(in.)

(cu. in.)

To Fill One Collar

(in.)

Required

4.5

24.73

1.35

19.84

3.5

20.02

1.09

16.70

2.4

3.9

14.84

0.81

13.25

1.5

1.9

3.4

12.48

0.69

11.68

1.4

2.9

10.13

0.55

10.11

* Collar length assumes the ends overlap 1".

Simplicity

Confidence

Value

113

1-800-879-8000

Estimating Tables**
TABLE 5 ESTIMATION CHART FOR TOP-OF-WALL JOINTS
U.L. System

Size of Metal Deck Flute

Numbers

1-1/2"

3"

HWD-0003 or

0.84 lineal feet/10.5 oz. tube

0.84 lineal feet/10.5 oz. tube

0.63 lineal feet/10.5 oz. tube

HWD-0008

1.6 lineal feet/600 ml foil pack

1.6 lineal feet/600 ml foil pack

1.2 lineal feet/600 ml foil pack

10 lineal feet/gallon

10 lineal feet/gallon

7 lineal feet/gallon

HWD-0004

2"

0.91 lineal feet/10.5 oz. tube

1.03 lineal feet/10.5 oz. tube

0.95 lineal feet/10.5 oz. tube

1.8 lineal feet/600 ml foil pack

2.0 lineal feet/600 ml foil pack

1.83 lineal feet/600 ml foil pack

11 lineal feet/gallon

12 lineal feet/gallon

11 lineal feet/gallon

Estimations based upon joint width of 1/2".

TABLE 6 COVERAGE TABLE FOR JOINTS


Joint

Lineal Feet/10.5 oz. Tube

Width

Lineal Feet/600 ml Foil

Sealant Depth (in.)

(in.)

1/2

5/8

1/4

12.6

10.08

1/2

6.3

5.04

Lineal Feet/Gallon

Sealant Depth (in.)


1-1/4

1/2

5/8

5.04

24.0

19.2

2.52

12.0

9.6

Sealant Depth (in.)


1-1/4

1/8

1/2

5/8

1-1/4

9.6

610

154

123

61

4.8

305

77

61

30

3/4

4.2

3.36

1.68

8.0

6.4

3.2

204

51

41

20

3.15

2.52

1.26

6.0

4.8

2.4

153

38

30

15

1-1/4

2.52

4.8

122

30

1-1/2

2.1

4.0

102

25

1.57

3.0

76

19

2-1/2

1.26

2.4

61

15

1.05

2.0

51

12

.52

1.0

25

* Denotes non-applicable width. See UL System HWD-0003 for details on installation.

** These tables are approximate values typically required, and assume no waste.

Simplicity

Confidence

Value

114

1-800-879-8000

How to estimate amount of Firestop needed for pipe penetrations


Single pipe in circular opening:
1.

Use the Estimation Chart (Table 3) found on page 113. Find the pipe size across the top of the table and match
it with the hole diameter found along the side of the chart. The value from the table represents the volume of firestop
per penetration.

Single pipe in rectangular opening:


1.

Calculate the area of the pipe. Use the Calculation Chart For Pipe Areas (Table 2) found on page 112. Find the pipe size
that is used and note the Area located in the far right column OR calculate the total cross-sectional area of the penetration
using the following formula (note: all values should be in units of inches):
AP = (rP2 ) x 3.14
AP = total area of penetrating pipe
rP = radius of penetrating pipe = diameter
2

2.

Calculate the area of the opening:


Ao = length x width
Ao = area of opening

3.

Subtract the area of the penetrating pipe from the area of the opening and multiply by the depth of the
firestop required:
Total firestop required = (Ao - AP ) x FD
Total firestop required per penetration. For wall systems requiring
firestopping on both sides, multifly by 2.
FD = firestop depth

For multiple pipes in an opening:


1.

Use the methods stated above, but add all of the penetration areas (AP) together before subtracting from the
total area of the opening (Ao).

Sample Problem
APPLICATION:

3-hour fire rated concrete floor. Opening size is 8" dia. steel sleeve with 6" dia. steel pipe.
Use UL System CAJ 1155 (1/4" depth FS-ONE)
Ao = 8" diameter

50.24 in2

AP = 6" diameter

-34.19 in2
16.05 in2 x 1/4" @ 4.0 in3 of FS-ONE

Simplicity

Confidence

Value

115

1-800-879-8000

Product Information
Firestopping
Terms & Definitions
1.

FIRESTOP SYSTEM

A specific construction consisting of a fire-rated wall or floor assembly, a penetrating


item or items passing through an opening in the assembly, and the materials
designed to help prevent the spread of fire through the openings.

2.

FIRE RESISTANCE RATING

The period of time a building or building component maintains the ability to confine
a fire or continues to perform a structural function or both. This is usually determined
or measured by ASTM E-119 test standard.

3.

THROUGH - PENETRATION

An opening made completely through a fire-rated wall or floor to accommodate a


penetrating item(s).

4.

PENETRANT (PENETRATING ITEM)

Any item passing completely through a wall or floor, such as pipes, conduits, cables, etc.

5.

ANNULAR SPACE
(ANNULUS)

The distance between a penetrating item and the surrounding opening


Example: a pipe with an outside diameter of 4.5" centered in a 6" diameter hole has an
annular space of (6-4.5) 2 = 3/4".

6.

POINT OF CONTACT (ANNULAR SPACE)

When listed on UL system drawing, allows penetrating item to touch edge of opening.

7.

ANNULAR SPACE REQUIREMENTS


PER NFPA STANDARD #13

In section 4-5.4.3.4, it requires that sprinkler pipes in seismic areas, have a minimum
annular space of 1-inch for pipes 1" through 3-1/2" and 2-inches for pipes 4" and larger.
Exceptions to this standard do exist. Please consult NFPA Standard #13 for details.

8.

PERCENT FILL

The cross-sectional area of an opening that is occupied by a penetrating item(s).


Typically found in UL Systems containing cables. Percent fill may be calculated
with the following formulas:
Percent Fill (%f) = (Aw / Ao) X 100
2

9.

FILL, VOID OR CAVITY MATERIAL

N = number of wires

Area of Wire (Aw) = [3.14 X (rc )] X N

rc = radius of wire,

Area of Opening (Ao) = 3.14 X (ro2)

ro = radius of opening

A firestop material (e.g. sealant, putty, mastic, etc.)

10. BACKING MATERIAL


(FORMING MATERIAL,
PACKING MATERIAL)

Material used in firestop systems (e.g mineral wool, backer rod or CF 128 Foam)
to set the depth and provide support for the fill, void cavity material.

11. ASTM E-814

Standard Method of Fire Tests of Through-Penetration Firestops.

12. UL 1479

Fire Tests of Through-Penetration Firestops (equivalent to ASTM E-814).

13. UL 2079

Tests for fire resistance of building Joint systems.

14. F RATING

The time a firestop system prevents the passage of flame through an opening as determined
by ASTM E-814 and UL 1479.

15. T RATING

The time for the temperature on the unexposed surface of the firestop system or any
penetrating item to rise 325 F above its initiai temperature as determine by ASTM
E-814 and UL 1479.

16. L RATING

An optional measurement of the rate of air leakage through test samples resulting
from a specified air pressure difference applied across the surface of the test samples.

17. UL

UL is an abbreviation for Underwriters Laboratories Inc., a not for profit independent


organization testing for public safety.
UL maintains and operates laboratories for the examination and testing of firestop systems.

18. UL FIRE RESISTANCE DIRECTORY

A UL publication which contains descriptions and ratings of firestop systems.

19. CLOSED PIPING SYSTEM

Piping system which is completely enclosed, usually carrying fluids under pressure.
Examples: hot/cold water distribution, sprinkler piping, chilled water supply and return.

20. VENTED (OPEN) PIPING SYSTEM

Piping system which is atmospherically vented by design to prevent backflow or vacuum.


Examples: DWV piping (drain, waste or vent).

21. INTUMESCENT

A term describing materials which expand significantly (typically 2 to 10 times original volume)
when exposed to heat. Intumescent materials are often used as firestops, particularly around
combustible penetrants.

116

1-800-879-8000

Installation
Using the UL
Instructions
Directory
THE FIRE RESISTANCE DIRECTORY UTILIZES AN ALPHA-NUMERIC NUMBERING SYSTEM: BASIC NUMBER SYSTEM = ALPHA-ALPHA-NUMERIC
THROUGH - PENETRATIONS
THE FIRST LETTER REPRESENTS WHAT
IS BEING PENETRATED:
F = FLOORS
W = WALLS
C = FLOORS OR WALLS (COMBINED)

THE SECOND LETTER(S) PROVIDE MORE INFORMATION


ABOUT THE FLOOR OR WALL.

THE FOUR DIGIT NUMBER DESCRIBES THE


PENETRATING ITEM(S).

EXAMPLE: CAJ1150

A.
B.
C.
D.
E.
J.

0000 - 0999
1000 - 1999
2000 - 2999
3000 - 3999
4000 - 4999
5000 - 5999
6000 - 6999
7000 - 7999
8000 - 8999
9000 - 9999

C = FLOOR OR WALL PENETRATION

K.
L.
M.
N.

CONCRETE FLOORS 5 INCHES THICK OR LESS


CONCRETE FLOORS GREATER THAN 5 INCHES THICK
FRAMED FLOORS - FLOOR/CEILING ASSEMBLIES
STEEL DECK CONSTRUCTION
THRU I. NOT USED AT THE PRESENT TIME
CONCRETE OR MASONRY WALLS 8 INCHES THICK
OR LESS
CONCRETE WALLS GREATER THAN 8 INCHES THICK
FRAMED WALLS - GYPSUM WALLBOARD ASSEMBLIES
BULKHEADS
THRU Z. NOT USED AT THE PRESENT TIME

BLANK OPENINGS
METAL PIPE, CONDUIT OR TUBING
NONMETALLIC PIPE CONDUIT OR TUBING
CABLES
CABLE TRAYS
INSULATED PIPES
MISCELLANEOUS ELECTRICAL (BUSWAY)
MISCELLANEOUS MECHANICAL
MIXED PENETRATING ITEMS
RESERVED FOR FUTURE USE

A = CONCRETE FLOOR 5" OR LESS


J = CONCRETE OR MASONRY WALLS
8" OR LESS

1150 = METAL PIPE, CONDUIT OR TUBING

JOINT SYSTEMS
THE FIRST TWO LETTERS IDENTIFIES
THE TYPE OF JOINT.
F F = FLOOR-T0-FLOOR
WW = WALL-TO-WALL
FW = FLOOR-TO-WALL
HW = HEAD-TO-WALL
CG = WALL-TO WALL JOINTS
INTENDED AS CORNER GUARDS

THE THIRD LETTER SIGNIFIES THE MOVEMENT


CAPABILITIES OF THE JOINT SYSTEM.
S = NO MOVEMENT (STATIC)
D = ALLOWS MOVEMENT (DYNAMIC)

Simplicity

THE FOUR DIGIT NUMBER DESCRIBES THE


NOMINAL JOINT WIDTH.

EXAMPLE: HWD0003

0000 - 0999 LESS THAN OR EQUAL TO 2"


1000 - 1999 GREATER THAN 2" AND LESS THAN
OR EQUAL TO 6"
2000 - 2999 GREATER THAN 6" AND LESS THAN
OR EQUAL TO 12"
3000 - 3999 GREATER THAN 12" AND LESS THAN
OR EQUAL TO 24"
4000 - 4999 GREATER THAN 24"

HW = HEAD-OF-WALL

Confidence

D = ALLOWS MOVEMENT (DYNAMIC)


0003 = CONCRETE OR MASONRY WALLS

Value

117

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

FS-ONE High Performance Intumescent Firestop Sealant

DESCRIPTION:

One-part acrylic-based sealant

MSDS No.:
Revision No.:
Date:
Page:

259
002
06/25/96
PAGE 1 of 2

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Calcium carbonate
Ammonium polyphosphate
Zinc borate
Talc
Expandable graphite
Alkyd resin
Polyisobutylene
1,2-Benzenedicarboxylic acid,
diisononyl ester
Iron oxide
Ethylene glycol
Glass fiber
Ammonium hydroxide
Water

CAS NUMBER:
000471-34-1
007722-76-1
138265-88-0
014807-96-6
012689-13-3
899990-13-5
009003-27-4

PEL:
NA
NE
NE
NA
NA
NE
NE

TLV:
NA
NE
NE
NA
NA
NE
NE

STEL:
NA
NE
NE
NA
NA
NE
NE

028553-12-0
001309-37-1
000107-21-1
065997-17-3
001336-21-6
007732-18-5

NE
NA
C:50 ppm
NE
NE
NE

NE
NA
C:50 ppm
NE
NE
NE

NE
NE
NE
NE
NE
NE

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by C (Ceiling) or STEL (Short Term Exposure Limit). NA = Not Applicable. NE = None Established.
ND = Not Determined.
PHYSICAL DATA
APPEARANCE AND ODOR: Red paste. Odorless.

pH: Not Determined

BOILING POINT: Approx. 212F

MELTING POINT: Not Determined

VOC CONTENT: None

VAPOR PRESSURE: Not Determined

EVAPORATION RATE: Not Determined

VAPOR DENSITY: Not Determined

SOLUBILITY IN WATER: Slightly soluble (prior to curing)

SPECIFIC GRAVITY: 1.5

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Non-Flammable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: This product is non-combustible. Use extinguishing agent suitable for type of surrounding fire.
SPECIAL FIRE FIGHTING PROCEDURES: A self-contained breathing apparatus should be worn when fighting fires
involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None Known
REACTIVITY DATA
STABILITY: Stable.

CONDITIONS TO AVOID: None Known

INCOMPATIBILITY: Strong acids, peroxides and other oxidizing agents


HAZARDOUS DECOMPOSITION PRODUCTS: Thermal decomposition can yield carbon dioxide and/or carbon monoxide.
HAZARDOUS POLYMERIZATION: Will not occur.
HEALTH HAZARD DATA
KNOWN HAZARDS: None known. Possibly irritating upon contact with the eyes or repeated contact with and skin.

Simplicity

Confidence

Value

118

1-800-879-8000

Material Safety Data Sheet


CARCINOGENICITY: No ingredients are considered by IARC, NTP, or OSHA to be carcinogens.
PRIMARY ROUTES OF EXPOSURE: Dermal.
SIGNS AND SYMPTOMS OF EXPOSURE: None expected.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye and skin conditions.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Immediately flush with plenty of water while holding eyelids apart. Contact a physician if any effects occur.
SKIN: Wipe off material and wash with soap and water. Always launder contaminated clothing before reuse.
INHALATION: Move victim to fresh air if discomfort develops. If symptoms persist, consult a physician.
INGESTION: Give plenty of water to drink. Never give anything by mouth to an unconscious person. Do not induce vomiting
unless directed to by a physician. Call a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (natural or mechanically induced fresh air movements).
EYE PROTECTION: Safety glasses or goggles are recommended in most work environments.
SKIN PROTECTION: None required; however, gloves are recommended (cotton are sufficient).
RESPIRATORY PROTECTION: None normally required. Use a NIOSH-approved organic vapor respirator when vapor concentrations exceed recommended exposure limits. Never enter a confined space without an appropriate air-supplied respirator (e.g.
SCBA or airline with escape pack).
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Observe good hygiene practices. Do not eat, drink, or smoke while using.
Wash hands during breaks and before eating. Keep container closed when not in use. Store between 50 and 100 F.
Keep from freezing.
SPILL PROCEDURES: Allow to cure. Scrape up spilled material and place in a closed container for disposal.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING INFO: Non-regulated.
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product contains 1 - 4% ethylene glycol (CAS 107-21-1) which is subject to reporting under
Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply with
local, state, and federal health and environmental regulations.
CONTACTS:

TECHNICAL:
HEALTH/SAFETY:

Jim Taite
Steve Gerrard

(x6772)
(x6309)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 259

Page: PAGE 2 of 2

Simplicity

Confidence

Value

119

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

FS FIRE BLOCK

DESCRIPTION:

Intumescent Firestop Block

MSDS No.:
261
Revision No.:
001
Date:
07/17/96
Page: PAGE 1 of 2

INGREDIENTS AND EXPOSURE LIMITS


This product is regarded as an Article by definition under OSHA Regulation, 29CFR 1910.1200(c). FS 657 can best be
described as a polyurethane sponge-like material which expands when exposed to heat. The physical form of the product
precludes exposure to workers under normal conditions of use.
PHYSICAL DATA
APPEARANCE AND ODOR: Foam (sponge-like) block. Dark Red.

pH: Not Determined

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VOC CONTENT: None

VAPOR PRESSURE: Not Applicable

EVAPORATION RATE: Not Applicable

VAPOR DENSITY: Not Applicable

SOLUBILITY IN WATER: Insoluble

SPECIFIC GRAVITY: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not Applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Not Applicable


SPECIAL FIRE FIGHTING PROCEDURES: A self-contained breathing apparatus and protective clothing should be worn
when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None Known
REACTIVITY DATA
STABILITY: Stable
INCOMPATIBILITY: None known. See special handling and storage instructions.
HAZARDOUS DECOMPOSITION PRODUCTS: When heated to decomposition, can yield COx and NOx.

HAZARDOUS POLYMERIZATION: Will not occur.


CONDITIONS TO AVOID: See handling and storage instructions.
HEALTH HAZARD DATA
KNOWN HAZARDS: None known.
CARCINOGENICITY: No ingredients are considered by IARC, NTP, or OSHA to be carcinogens.
PRIMARY ROUTES OF EXPOSURE: None expected.
SIGNS AND SYMPTOMS OF EXPOSURE: None expected.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye and skin conditions.

Simplicity

Confidence

Value

120

1-800-879-8000

Material Safety Data Sheet


EMERGENCY AND FIRST AID PROCEDURES
EYES: No effects expected.
SKIN: No effects expected.
INHALATION: Not a route of exposure.
INGESTION: Not a likely route of exposure.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (natural or mechanically induced fresh air movements).
EYE PROTECTION: Safety glasses or goggles are recommended in most work environments.
SKIN PROTECTION: None required.
RESPIRATORY PROTECTION: None normally required. Never enter a confined space without an appropriate air-supplied
respirator (e.g. SCBA or airline with escape pack).
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Observe good hygiene practices. Do not eat, drink, or smoke while using.
Wash hands after using and before meals. Store in a dry place out of direct sunlight. For industrial use only. Keep out of
reach of children.
SPILL PROCEDURES: Not Applicable
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS is considered to be an article under the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 0, Flammability 0, Reactivity 0, PPE A
DOT SHIPPING INFO: Non-regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under
Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
CONTACTS:

TECHNICAL:
HEALTH/SAFETY:

Jim Taite
Steve Gerrard

(x6772)
(x6309)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 261

Page: PAGE 2 of 2

Simplicity

Confidence

Value

121

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 672 Firestop Joint Spray

DESCRIPTION:

Fire rated mastic for construction joints

MSDS No.:
Revision No.:
Date:
Page:

268
001
03/23/98
1 of 2

INGREDIENTS AND EXPOSURE LIMITS


No hazardous ingredients as defined by OSHA 29 CFR 1910.1200 / 1926.59
PHYSICAL DATA
APPEARANCE AND ODOR: Viscous red paste, mild odor

VOC CONTENT: None

BOILING POINT: 212 F

MELTING POINT: Not Applicable

VAPOR PRESSURE: 17 mm Hg @ 88 F

VAPOR DENSITY: Not Applicable

EVAPORATION RATE: > 1 (ethyl acetate = 1)

SOLUBILITY IN WATER: Soluble

SPECIFIC GRAVITY: 1.1

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: None

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: As appropriate for surrounding fire (e.g. Water, Carbon Dioxide, Dry Chemical, Foam)
SPECIAL FIRE FIGHTING PROCEDURES: Wear full protective clothing. A NIOSH-approved self-contained breathing
apparatus (SCBA) should be worn when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known. Thermal decomposition products such as oxides of carbon
and nitrogen can be produced under fire conditions. See below.
REACTIVITY DATA
INCOMPATIBILITY: Metal salts

STABILITY: Stable

HAZARDOUS DECOMPOSITION PRODUCTS: Thermal decomposition can yield oxides of carbon and nitrogen.
HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: Avoid temperature extremes which could shorten the shelf-life of this product; i.e. below 40
and above 100 F. (See handling and storage requirements).
HEALTH HAZARD DATA
KNOWN HAZARDS: Acute: Irritation is possible. Chronic: None known
CARCINOGENICITY: No ingredients are classified by IARC, NTP, or OSHA as known or potential carcinogens.
PRIMARY ROUTES OF EXPOSURE: Dermal.
SIGNS AND SYMPTOMS OF EXPOSURE: Eyes - Can cause irritation or watering but injury is unlikely. Skin - Irritation is
possible with some individuals. Inhalation - No effects expected. Ingestion - Not considered to be a route of exposure.
Effects of ingestion have not been determined. Considered to have a low acute oral toxicity.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE:: None known

Simplicity

Confidence

Value

122

1-800-879-8000

Material Safety Data Sheet


EMERGENCY AND FIRST AID PROCEDURES
EYES: Wash immediately with large amounts of clean water. Seek medical attention if any effects develop.
SKIN: Wash with soap and water. Seek medical attention if any effects persist.
INHALATION: No ill effects expected. Should discomfort occur, move to fresh air.
INGESTION: Do not induce vomiting unless large amounts are ingested. If conscious, give plenty of water to drink.
Never give anything by mouth to an unconscious person. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: While spraying, chemical goggles are recommended. As a minimum, wear safety glasses with side shields.
SKIN PROTECTION: Cloth may be suitable; impervious (neoprene or rubber) gloves are recommended.
RESPIRATORY PROTECTION: Not normally required.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area. Keep from freezing. Store between 40 and 100 F.
For industrial use only. Keep out of reach of children. Use with adequate ventilation. Keep container closed when not in use.
Do not get into the eyes. Avoid prolonged or repeated contact with the skin. Practice good hygiene; i.e. wash after using and
before eating or smoking.
SPILL PROCEDURES: Wipe away spilled material immediately before it hardens and place in a container for proper disposal
in accordance with all applicable local, state, or federal requirements. Not considered to be a hazardous waste according to
EPA definitions.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 0, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING NAME: Not regulated
IMDG (OCEAN) SHIPPING DESCRIPTION: Not regulated
IATA (AIR) SHIPPING DESCRIPTION: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under Section
313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee
or warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 268

Page: PAGE 2 of 2

Simplicity

Confidence

Value

123

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 601S Elastomeric Firestop Sealant

DESCRIPTION:

Mixture of siloxanes and silicones

MSDS No.:
Revision No.:
Date:
Page:

266
001
02/24/98
1 of 2

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
CAS NUMBER:
PEL:
TLV:
STEL:
Siloxanes and silicones, di-Me, terminated
068037-58-1
NE
NE
NE
Siloxanes and silicones, di-Me
063148-62-9
NE
NE
NE
Fumed silica
112945-52-5
NE
NE
NE
Methyltrimethoxysilane
001185-55-3
NE
NE
NE
Calcium carbonate
000471-34-1
NE
NE
NE
Hydrogenated castor oil
008001-78-3
NE
NE
NE
PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by "C" (Ceiling) or "STEL" (Short Term Exposure Limit). NE = None Established. NA = Not Applicable.
PHYSICAL DATA
APPEARANCE AND ODOR: Medium viscosity liquid, negligible odor

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY: Not Applicable

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Negligible

SPECIFIC GRAVITY: 1.3

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: > 200 F

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Water, CO2, Dry Chemical, Foam


SPECIAL FIRE FIGHTING PROCEDURES: Wear full protective clothing. A NIOSH-approved self-contained breathing
apparatus (SCBA) should be worn when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known. Thermal decomposition products can be produced under
fire conditions. See below.
REACTIVITY DATA
STABILITY: Stable
INCOMPATIBILITY: Strong acids, peroxides and other oxidizing agents
HAZARDOUS DECOMPOSITION PRODUCTS: Thermal decomposition can yield carbon dioxide and/or carbon monoxide.
HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: Avoid temperature extremes which could shorten the shelf-life of this product; i.e. below freezing
and above 100 F. (See handling and storage requirements).
HEALTH HAZARD DATA
KNOWN HAZARDS: Acute: Eye, skin, and respiratory irritation. Chronic: Sensitization is possible.
CARCINOGENICITY: No ingredients are classified by IARC, NTP, or OSHA as known or potential carcinogens.
PRIMARY ROUTES OF EXPOSURE: Dermal. Inhalation.

Simplicity

Confidence

Value

124

1-800-879-8000

Material Safety Data Sheet


SIGNS AND SYMPTOMS OF EXPOSURE: Eyes - Can cause irritation but injury is unlikely. Skin - Can cause irritation. An allergic skin reaction (e.g. rash, itching, reddening) can occur with some individuals. Inhalation - No effects expected. Exposure to
heated vapors can cause irritation. Ingestion - Not considered to be a route of exposure. Effects of ingestion have not been
determined. Considered to have a low acute oral toxicity.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye, skin, and respiratory conditions.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Wash immediately with large amounts of clean water. Seek medical attention if any effects develop.
SKIN: Wash with soap and water. Seek medical attention if any effects persist.
INHALATION: Move victim to fresh air. Give oxygen and/or artificial respiration if needed. Call a physician.
INGESTION: If conscious, give plenty of water to drink. Do not induce vomiting unless large amounts are ingested. Never give
anything by mouth to an unconscious person. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Not required, however, safety glasses should be worn in most industrial settings.
SKIN PROTECTION: Cloth may be suitable; impervious (neoprene or rubber) gloves are recommended.
RESPIRATORY PROTECTION: Not normally required. Where ventilation is inadequate to control vapors, use a NIOSH-approved
respirator with organic vapor cartridges. Never enter a confined space without an appropriate air supplied respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area. Keep from freezing. Store between 40 and 100 F.
Flammable. Keep away from ignition sources such as hot surfaces, sparks and flames. For industrial use only. Keep out of reach
of children. Use with adequate ventilation. Do not get into the eyes. Avoid prolonged or repeated contact with the skin. Practice
good hygiene; i.e. wash after using and before eating or smoking.
SPILL PROCEDURES: Take up with an absorbent material and place in a container for proper disposal in accordance with all
applicable local, state, or federal requirements. Not considered to be a hazardous waste according to EPA definitions.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 1, Reactivity 0, PPE B
DOT SHIPPING NAME: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under Section
313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 266

Page: PAGE 2 of 2

Simplicity

Confidence

Value

125

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 606 Flexible Firestop Sealant

DESCRIPTION:

Fire resistant sealant

MSDS No.:
Revision No.:
Date:
Page:

267
001
02/28/98
1 of 2

TLV:
10 mg/m3
NE
NE
10 mg/m3
NE
NE
NE
10 ppm

STEL:
NE
NE
NE
NE
NE
NE
NE
15 ppm

INGREDIENTS AND EXPOSURE LIMITS


Ingredient:
Calcium carbonate
Polybutylene
Propylene glycol
Titanium dioxide
Amorphous silica
Softener
Water
Vinyl acetate

CAS Number:
00471-34-1
09003-29-6
00107-21-1
13463-67-7
07631-86-9
28553-12-0
07732-18-5
00108-05-4

PEL:
5 mg/m3
NE
NE
5 mg/m3
NE
NE
NE
10 ppm

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by "C" (Ceiling) or "STEL" (Short Term Exposure Limit). NE = None Established. NA = Not Applicable.
indicates as total inhalable dust
PHYSICAL DATA
APPEARANCE AND ODOR: White paste; negligible odor

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY Not Applicable

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Miscible

SPECIFIC GRAVITY: 1.55

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not Applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: As appropriate for the surrounding fire


SPECIAL FIRE FIGHTING PROCEDURES: Wear full protective clothing. A NIOSH-approved self-contained breathing apparatus
(SCBA) should be worn when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known.
REACTIVITY DATA
INCOMPATIBILITY: Strong oxidizing agents

STABILITY: Stable

HAZARDOUS DECOMPOSITION PRODUCTS: None when used as directed.


HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: Avoid temperature extremes which could shorten the shelf-life of this product. See handling and
storage requirements.
HEALTH HAZARD DATA
KNOWN HAZARDS: Acute: Material is slightly alkaline. Minor irritation is possible. Chronic: None known.
CARCINOGENICITY: This product contains < 1% vinyl acetate which is classified by IARC as a Group 2B carcinogen
(inadequate evidence for human carcinogenicity and limited evidence for lab animals). Based upon the nature and use of this
product, it does not pose a cancer risk from exposure to vinyl acetate.
PRIMARY ROUTES OF EXPOSURE: Dermal.

Simplicity

Confidence

Value

126

1-800-879-8000

Material Safety Data Sheet


SIGNS AND SYMPTOMS OF EXPOSURE: Eyes - Can cause slight irritation but injury is unlikely. Skin - Can cause irritation with
some individuals. Inhalation - No effects expected. Ingestion - Not considered to be a route of exposure. Effects of ingestion
have not been determined. Considered to have a low acute oral toxicity.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye, skin, and respiratory conditions.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Flush with large amounts of clean water while holding eyelids apart. Seek medical attention if any effects develop.
SKIN: Wash with soap and water. Seek medical attention if any effects persist.
INHALATION: No ill effects expected. If symptoms occur, move to fresh air.
INGESTION: If conscious, give plenty of water to drink. Do not induce vomiting unless large amounts are ingested. Never give
anything by mouth to an unconscious person. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Not required, however, safety glasses should be worn in most industrial settings.
SKIN PROTECTION: Cloth gloves are recommended.
RESPIRATORY PROTECTION: Not normally required. Where ventilation is inadequate to control vapors, use a NIOSH-approved
respirator with organic vapor cartridges. Never enter a confined space without an appropriate air supplied respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area. Keep from freezing. Shelf life is one year from date of
manufacture if stored between 40 and 77 F (5 - 25 C). For industrial use only. Keep out of reach of children. Keep container
sealed when not in use to prevent curing of the product. Avoid contact with the eyes and skin. Practice good hygiene; i.e. wash
after using and before eating or smoking.
SPILL PROCEDURES: Allow to cure and place in a container for proper disposal in accordance with all applicable local, state,
or federal requirements. Not considered to be a hazardous waste according to EPA definitions.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING NAME: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product contains < 1% vinyl acetate (as excess monomer) which is subject to reporting
under Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee
or warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 266

Page: PAGE 2 of 2

Simplicity

Confidence

Value

127

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 642 Firestop Collar

DESCRIPTION:

Intumescent material in metal case

MSDS No.:
Revision No.:
Date:
Page:

236
002
03/11/95
1 of 2

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Epoxy resin based intumescent
material containing graphite

CAS NUMBER:

PEL:

TLV:

STEL:

NE

NE

NE

NE

PHYSICAL DATA
APPEARANCE AND ODOR: Dark grey to black rubbery tape enclosed in galvanized metal jacket, no odor.
BOILING POINT: Not Applicable

VOC CONTENT: Not Applicable

MELTING POINT: Not Determined

pH: 6.1 (110 g/l @ 20 C)

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY: Not Applicable

SPECIFIC GRAVITY: 1.05

SOLUBILITY IN WATER: Insoluble

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Non-flammable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Water, Water Fog, CO2, Dry Chemical, Foam


SPECIAL FIRE FIGHTING PROCEDURES: None known, however, a self-contained breathing apparatus (SCBA) and protective
clothing should be worn when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known. Expands to 10 times the original volume at temperatures
>120C/250F.
REACTIVITY DATA
STABILITY: Stable.

INCOMPATIBILITY: None known.

HAZARDOUS DECOMPOSITION PRODUCTS: None known.


HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: None known.
HEALTH HAZARD DATA
KNOWN HAZARDS: None anticipated.
CARCINOGENICITY: No ingredients are listed by IARC, NTP, or OSHA as carcinogens.
PRIMARY ROUTES OF EXPOSURE: Dermal. Inhalation.
SIGNS AND SYMPTOMS OF EXPOSURE: None expected from routine use/installation according to manufacturer's
specifications and technical guides.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known or anticipated.

Simplicity

Confidence

Value

128

1-800-879-8000

Material Safety Data Sheet


EMERGENCY AND FIRST AID PROCEDURES
EYES: Flush with water if dust, debris, etc. from work overhead gets into the eyes. Do not rub the eyes as this can cause
corneal abrasions. Call a physician if irritation continues or if redness, swelling, or similar symptoms occur.
SKIN: Practice good hygiene; i.e. wash hands during breaks, before eating or smoking, and after work.
INHALATION: No first aid should be needed. If ill effects occur, move to fresh air. If symptoms persist, seek medical attention.
INGESTION: Not a likely route of exposure.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury or exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e. natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Safety glasses recommended in most industrial settings.
SKIN PROTECTION: None required; however, (cotton) gloves recommended.
RESPIRATORY PROTECTION: No respiratory protection is needed for normal application of this product. If any dust is
generated during use or during any cutting or grinding operations, use a NIOSH-approved dust mask.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool dry place.
SPILL PROCEDURES: No special requirements.
REGULATORY INFORMATION
OSHA HAZARD COMMUNICATION: This Material Safety Data Sheet has been prepared in accordance with the federal
OSHA Hazard Communication Standard. This product is considered to be an "article" under that standard.
DOT PROPER SHIPPING NAME: Non-regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any ingredients subject to reporting under requirements of
Section 313 of the Superfund Amendments and Reauthorization Act of 1986 and 40 CFR Part 372.
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
CONTACTS:

TECHNICAL:
HEALTH/SAFETY:

Jim Taite
Steve Gerrard

(x6772)
(x6309)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 236

Page: PAGE 2 of 2

Simplicity

Confidence

Value

129

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 8000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 643 Firestop Collar

DESCRIPTION:

Intumescent material enclosed in a metal housing

MSDS No.:
262
Revision No.:
001
Date:
12/16/96
Page:
1 of 2

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Polyethylene based intumescent
enclosed in galvanized metal jacket

CAS NUMBER:
NE

PEL:
NE

TLV:
NE

STEL:
NE

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by C (Ceiling) or STEL (Short Term Exposure Limit). NE = None Established. NA = Not Applicable.
PHYSICAL DATA
APPEARANCE AND ODOR: Dark grey material in galvanized metal jacket

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY: Not Applicable

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Negligible

SPECIFIC GRAVITY: Not Applicable

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not Applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Not Applicable. Use Water, CO2, Dry Chemical, Foam as appropriate for surrounding fire.
SPECIAL FIRE FIGHTING PROCEDURES: Not Applicable, however, a NIOSH-approved self-contained breathing apparatus
(SCBA) should be worn when fighting fires involving chemicals.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known. Product serves as a fire stopping material and intumesces
(expands) when exposed to temperatures > 120 C / 250 F.
REACTIVITY DATA
INCOMPATIBILITY: None known

STABILITY: Stable

HAZARDOUS DECOMPOSITION PRODUCTS: None known


HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: None known
HEALTH HAZARD DATA
KNOWN HAZARDS: None known
CARCINOGENICITY: No ingredients are listed by IARC, NTP, or OSHA as carcinogens.
PRIMARY ROUTES OF EXPOSURE: None known
SIGNS AND SYMPTOMS OF EXPOSURE: None expected from routine use/installation according to manufacturers
specifications and technical guides.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye, skin, and respiratory conditions.

Simplicity

Confidence

Value

130

1-800-879-8000

Installation Instructions
EMERGENCY AND FIRST AID PROCEDURES
EYES: Flush with water if dust, debris, etc. from work overhead gets into the eyes. Do not rub the eyes as this can cause
corneal abrasions. Call a physician if irritation continues or if redness, swelling, or similar symptoms occur
SKIN: Practice good hygiene; i.e. wash hands during breaks, before eating or smoking, and after work.
INHALATION: No first aid should be needed. If ill effects occur, move to fresh air. If symptoms persist, seek medical attention.
INGESTION: If conscious, give plenty of water to drink. Do not induce vomiting unless large amounts are ingested.
Never give anything by mouth to an unconscious person. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Not required, however, safety glasses should be worn in most industrial settings.
SKIN PROTECTION: None required; however, (cotton) gloves recommended.
RESPIRATORY PROTECTION: No respiratory protection is needed for normal application of this product. If any dust is
generated during use or during any cutting or grinding operations, use a NIOSH-approved dust mask.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area.
SPILL PROCEDURES: No special requirements.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This product is considered to be an article as defined in the federal OSHA Hazard
Communication Standard.
DOT SHIPPING NAME: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under
Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee
or warranty of any kind expressed or implied is made with respect to the information provided.
MSDS 262, Page 2 of 2

Simplicity

Confidence

Value

131

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 618 Firestop Putty Stick

DESCRIPTION: Fire rated putty

MSDS No.:
Revision No.:
Date:
Page:

264
001
01/08/98
1 of 2

TLV:
NE
NE
NE
NE

STEL:
NE
NE
NE
NE

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Triazine triamine phosphate
Calcium borate
Polyphosphoric acid
Isodecyldiphenyl ester

CAS NUMBER:
41583-09-9
12007-56-6
68333-79-9
29761-21-5

PEL:
NE
NE
NE
NE

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by "C" (Ceiling) or "STEL" (Short Term Exposure Limit). NE = None Established. NA = Not Applicable.
PHYSICAL DATA
APPEARANCE AND ODOR: Flesh colored putty, negligible odor

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY: Not Applicable

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Slightly soluble

SPECIFIC GRAVITY: 1.48

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Water, CO2, Dry Chemical, Foam


SPECIAL FIRE FIGHTING PROCEDURES: A NIOSH-approved self-contained breathing apparatus (SCBA) should be worn
when fighting fires involving chemical products.
UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire conditions will activate product causing it to intumesce.
REACTIVITY DATA
STABILITY: Stable
INCOMPATIBILITY: Strong acids, bases and oxidizing agents
HAZARDOUS DECOMPOSITION PRODUCTS: Thermal decomposition can yield oxides of carbon and nitrogen.
HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: Avoid temperature extremes which could shorten the shelf-life of this product; i.e. below freezing and
above 100 F. (See handling and storage requirements).
HEALTH HAZARD DATA
KNOWN HAZARDS: Irritation of the eyes and skin is possible.
CARCINOGENICITY: No ingredients are classified by IARC, NTP, or OSHA as known or potential carcinogens.
PRIMARY ROUTES OF EXPOSURE: Contact.

Simplicity

Confidence

Value

132

1-800-879-8000

Material Safety Data Sheet


SIGNS AND SYMPTOMS OF EXPOSURE: Eyes - Can cause irritation and watering but injury is unlikely. Skin - Can cause
irritation. Inhalation - No effects expected. Not considered to be a route of exposure. Ingestion - Can cause nausea and
vomiting. Considered to have a low acute oral toxicity.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Wash immediately with large amounts of clean water. Seek medical attention if any effects develop.
SKIN: Wash with soap and water. Seek medical attention if any effects persist.
INHALATION: Not applicable.
INGESTION: If conscious, give plenty of water to drink. Never give anything by mouth to an unconscious person. Do not induce
vomiting unless directed to by a physician. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Not required, however, safety glasses should be worn in most industrial settings.
SKIN PROTECTION: Gloves are recommended; cotton gloves are suitable.
RESPIRATORY PROTECTION: Not required.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area. Keep from freezing. For industrial use only. Keep out
of reach of children. Avoid prolonged or repeated contact with the skin. Do not rub the eyes after contact with the hands.
Practice good hygiene; i.e. wash after using and before eating or smoking.
SPILL PROCEDURES: No special requirements.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING NAME: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under
Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply with
local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 264

Page: PAGE 2 of 2

Simplicity

Confidence

Value

133

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

CP 617 Firestop Putty Pad

DESCRIPTION:

Fire rated putty pad

MSDS No.:
Revision No.:
Date:
Page:

263
001
01/08/98
1 of 2

TLV:
NE
NE
NE
NE

STEL:
NE
NE
NE
NE

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Triazine triamine phosphate
Calcium borate
Polyphosphoric acid
Isodecyldiphenyl ester

CAS NUMBER:
41583-09-9
12007-56-6
68333-79-9
29761-21-5

PEL:
NE
NE
NE
NE

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8 hour time-weighted averages unless
otherwise indicated by "C" (Ceiling) or "STEL" (Short Term Exposure Limit). NE = None Established. NA = Not Applicable.
PHYSICAL DATA
APPEARANCE AND ODOR: Rust colored putty, negligible odor

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Applicable

VAPOR PRESSURE: Not Applicable

VAPOR DENSITY: Not Applicable

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Slightly soluble

SPECIFIC GRAVITY: 1.48

pH: Not Determined

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Water, CO2, Dry Chemical, Foam


SPECIAL FIRE FIGHTING PROCEDURES: A NIOSH-approved self-contained breathing apparatus (SCBA) should be worn
when fighting fires involving chemical products.
UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire conditions will activate product causing it to intumesce.
REACTIVITY DATA
STABILITY: Stable
INCOMPATIBILITY: Strong acids, bases and oxidizing agents
HAZARDOUS DECOMPOSITION PRODUCTS: Thermal decomposition can yield oxides of carbon and nitrogen.
HAZARDOUS POLYMERIZATION: Will not occur.
CONDITIONS TO AVOID: Avoid temperature extremes which could shorten the shelf-life of this product; i.e. below freezing and
above 100 F. (See handling and storage requirements).
HEALTH HAZARD DATA
KNOWN HAZARDS: Irritation of the eyes and skin is possible.
CARCINOGENICITY: No ingredients are classified by IARC, NTP, or OSHA as known or potential carcinogens.
PRIMARY ROUTES OF EXPOSURE: Contact.
SIGNS AND SYMPTOMS OF EXPOSURE: Eyes - Can cause irritation and watering but injury is unlikely. Skin - Can cause
irritation. Inhalation - No effects expected. Not considered to be a route of exposure. Ingestion - Can cause nausea and
vomiting. Considered to have a low acute oral toxicity.

Simplicity

Confidence

Value

134

1-800-879-8000

Material Safety Data Sheet


MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Wash immediately with large amounts of clean water. Seek medical attention if any effects develop.
SKIN: Wash with soap and water. Seek medical attention if any effects persist.
INHALATION: Not applicable.
INGESTION: If conscious, give plenty of water to drink. Never give anything by mouth to an unconscious person. Do not induce
vomiting unless directed to by a physician. Contact a physician immediately.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: General (i.e., natural or mechanically induced fresh air movements that maintain vapor concentrations below
recommended exposure limits).
EYE PROTECTION: Not required, however, safety glasses should be worn in most industrial settings.
SKIN PROTECTION: Gloves are recommended; cotton gloves are suitable.
RESPIRATORY PROTECTION: Not required.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Store in a cool, dry area. Keep from freezing. For industrial use only. Keep out
of reach of children. Avoid prolonged or repeated contact with the skin. Do not rub the eyes after contact with the hands.
Practice good hygiene; i.e. wash after using and before eating or smoking.
SPILL PROCEDURES: No special requirements.
REGULATORY INFORMATION
HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING NAME: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under Section
313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply with
local, state, and federal health and environmental regulations.
HEALTH / SAFETY CONTACTS:

Steve Gerrard
Jerry Metcalf

(x6309)
(x6704)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 263

Page: PAGE 2 of 2

Simplicity

Confidence

Value

135

1-800-879-8000

Material Safety Data Sheet


HILTI, INC.:

P.O. Box 21148, Tulsa, OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444

PRODUCT NAME:

FS 635 Trowelable Firestop Compound

DESCRIPTION:

Cementitious mixture for use as a fire barrier

MSDS No.:
Revision No.:
Date:
Page:

212
003
08/16/94
1 of 2

INGREDIENTS AND EXPOSURE LIMITS


INGREDIENTS:
Portland cement
Crystalline silica
(natural sand or gravel)
Perlite
Iron oxide
Polyvinyl acetate
Cellulosic fiber
Limits are for respirable fraction unless noted with (*)

CAS NUMBER:
65997-15-1
14808-60-7

PEL:
10mg/m3*
0.1mg/m3

TLV:
10mg/m3*
0.1mg/m3

STEL:
NE
NE

93763-70-3
01332-37-2
09003-20-7
65996-61-4
which indicates total dust

15mg/m3
10mg/m3
NE
NE

10mg/m3
5mg/m3 NE
NE
NE

NE
NE
NE

PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. These are 8-hour time-weighted averages unless
otherwise indicated by "C" (Ceiling) or "STEL" (Short Term Exposure Limit). NE = None Established.
PHYSICAL DATA
APPEARANCE AND ODOR: Coarse red powder. Little odor.

VOC CONTENT: None

BOILING POINT: Not Applicable

MELTING POINT: Not Determined

VAPOR PRESSURE: Not Determined

EVAPORATION RATE: Not Applicable

SOLUBILITY IN WATER: Soluble

VAPOR DENSITY: Not Applicable

SPECIFIC GRAVITY: 0.22 - 0.27

pH: 11 - 13 (cement)

FIRE AND EXPLOSION HAZARD DATA


FLASH POINT: Not Applicable

FLAMMABLE LIMITS: Not Applicable

EXTINGUISHING MEDIA: Not Applicable


SPECIAL FIRE FIGHTING PROCEDURES: None Known. A self-contained breathing apparatus should be worn when fighting
fires involving chemical products.
UNUSUAL FIRE AND EXPLOSION HAZARDS: None known
REACTIVITY DATA
INCOMPATIBILITY: Strong alkalies. Hydrofluoric acid

STABILITY: Stable.

HAZARDOUS DECOMPOSITION PRODUCTS: Not Applicable Will not occur


CONDITIONS TO AVOID: None known
HEALTH HAZARD DATA
KNOWN HAZARDS: Eye, skin and respiratory irritant.
CARCINOGENICITY: Respirable silica (sand) is considered by IARC to be a Group-2A carcinogen based upon studies of quarry
and foundry workers. The use of a NIOSH-approved dust mask in any dusty situation will reduce the potential for exposure to
silica. The nature and use of this product, however, does not pose a cancer risk to humans.
PRIMARY ROUTES OF EXPOSURE: Dermal. Inhalation.
SIGNS AND SYMPTOMS OF EXPOSURE: Contact with the eyes or moist skin can lead to irritation and possibly burns.
Prolonged and repeated exposure to the hands can lead to drying of the skin and dermatitis. Overexposure to dusts

Simplicity

Confidence

Value

136

1-800-879-8000

Material Safety Data Sheet


can lead to breathing difficulty.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Eye, skin, and respiratory conditions.
EMERGENCY AND FIRST AID PROCEDURES
EYES: Immediately flush with plenty of water for at least 15 minutes while holding eyelids apart. See a physician.
SKIN: Flush immediately with plenty of water and dry thoroughly. Remove and wash any contaminated clothing before reuse.
INHALATION: Get fresh air immediately. If symptoms occur and persist, consult a physician.
INGESTION: Give large volumes of water or milk to drink for dilution effect. Do not induce vomiting unless directed to by
medical personnel. Get medical attention. Never give anything by mouth to an unconscious person.
OTHER: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
VENTILATION: Exhaust fans may be necessary when mixing in enclosed areas.
EYE PROTECTION: Safety glasses or goggles are recommended.
SKIN PROTECTION: Work gloves (or barrier creams) are recommended to prevent irritation or drying of skin.
RESPIRATORY PROTECTION: Wear a NIOSH-approved dust mask when exposure to dusts is encountered.
PRECAUTIONS FOR SAFE HANDLING AND USE
HANDLING AND STORING PRECAUTIONS: Avoid generating dust. Store in a dry location preferably between 45 and 90 F.
Follow label instructions for proper mixing.
SPILL PROCEDURES: Sweep up and place in suitable containers for recycle or disposal.
REGULATORY INFORMATION
OSHA HAZARD COMMUNICATION: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard.
HMIS CODES: Health 1, Flammability 0, Reactivity 0, PPE B
DOT SHIPPING INFO: Not regulated
TSCA INVENTORY STATUS: Chemical components listed on TSCA inventory.
SARA TITLE III, SECTION 313: This product does not contain any toxic chemicals which are subject to reporting under
Section 313 of SARA Title III (40 CFR Part 372).
WASTE DISPOSAL METHODS: Consult with regulatory agencies or corporate personnel for disposal methods that comply
with local, state, and federal health and environmental regulations.
CONTACTS:

TECHNICAL:
HEALTH/SAFETY:

Jim Taite
Steve Gerrard

(x6772)
(x6309)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS No.: 212

Page: PAGE 2 of 2

Simplicity

Confidence

Value

137

1-800-879-8000

Certificate of Compliance FS-ONE

138

1-800-879-8000

Certificate of Compliance FS 657 Fire Block

139

1-800-879-8000

Certificate of Compliance CP 672

140

1-800-879-8000

Certificate of Compliance CP 601S

141

1-800-879-8000

Certificate of Compliance CP 606

142

1-800-879-8000

Certificate of Compliance CP 642

143

1-800-879-8000

Certificate of Compliance CP 643

144

1-800-879-8000

Certificate of Compliance FS 635

145

1-800-879-8000

Certificate of Compliance CP 617 Fire Rated Putty Pad

146

1-800-879-8000

Certificate of Compliance CP 618 Fire Rated Putty Stick

147

1-800-879-8000

Hiltis Firestop Technical


Information System
We offer a comprehensive line of firestop products backed by a strong network of sales, service
and technical professionals. We also offer the Hilti Firestop Systems Electronic Suite98 to help
you to select or specify Hilti Firestop. For additional information call 1-800-879-4000
or fax 1-800-879-3636.

p
o
t
s
e
r
i
F
s
m
e
t
s
Sy onic Suite98
Electr

Hiltis Windows -compatible


Firestop Systems Electronic Suite98
can help you select or specify Hilti Firestop!

New!

Updated edition available


View or print U.L. system drawings
View or print product data or material safety data sheets
Transfer U.L. drawings to your plans using your CAD system

Estimation Program
Submittal Section
Specification Information

- Windows is a trademark of the Microsoft Corporation.

Simplicity

Confidence

Value

1-800-879-8000

You might also like