time equal to rate at which heat is generated by people, machinery, and processes, plus the net flow of
heat into the system not associated with the cooling machinery.
Assumptions
Walls:
Roof:
Window glass:
Lighting:
Occupancy:
Other power equipment:
140 mm brick
200 mm brick
13.5 mm clear plate glass
4 pieces of tube light (per light 40 watt)
15 people
printer (14 watts), 2 set of Computer (300 watts per set), 2 pieces of Fan
(75 watt per piece), Photocopy machine (1 kW)
Several loads to be calculated for summing the total cooling load. Loads are- Transmission load, solar
heat gain, internal load, occupancy.
Location Statistics
For Chittagong
-
Q= UA (CLTD)
U= Overall heat transfer coefficient. (kW/m2K)
A= Area of roof and wall (m2)
CLTD= Cooling load temperature difference. (oC)
Area Calculation
Wall area with window
A= width height [Considering 10 ft roof height]
North
93= 27 m2
East
7.53= 22.66 m2
West
7.53= 22.66 m2
South
93= 27 m2
Window area
2 windows are there, one is (0.604 m 1.81 m) and the other one is (1.21 m 1.81 m). All 2 windows
are mounted at the North wall side of the room.
Window 1 area
0.6041.81= 1.09 m2
Window 2 area
1.211.81= 2.19 m2
Total Window Area= 3.28 m2
Roof area
97.5= 67.5 m2
Door Area
Considering one door at the south side wall, 1.51 m 1.81 m)
There for, door area
1.511.81= 2.74 m2
(27-1.09-2.19) m2 = 23.72 m2
22.66 m2
22.66 m2
(27-2.74) m2 = 24.26 m2
U value calculation
U value calculation for roof
Component
Outside air film
R (m2K/W)
0.004
200 mm brick
0.625
0.160
Reference
ASHRAE Fundamentals 1989,
Table 1
ASHRAE Fundamentals 1989,
Table 4
ASHRAE Fundamentals 1989,
Table 1
Total 0.789
U= 1/R= 1/0.789= 1.27 W/ m2K
U value calculation for wall
Component
Outside air film
R (m2K/W)
0.004
140 mm brick
0.44
0.120
Total 0.56
Reference
ASHRAE Fundamentals 1989,
Table 1
ASHRAE Fundamentals 1989,
Table 4
ASHRAE Fundamentals 1989,
Table 1
Exposure
N
E
S
W
Roof
CLTD
(ASHRAE
Table
31)
7
15
11
11
36
LM
(ASHRAE
Table
32)
6.6
-1.6
-4.4
-1.6
-2.7
25.5
Tr
To
29.4
CLTDc
1
1
1
1
1
25.5
25.5
25.5
25.5
25.5
25.5
25.5
25.5
25.5
25.5
28
28
28
28
28
29.4
29.4
29.4
29.4
29.4
1
1
1
1
1
12.2
12
5.2
8
31.9
Description
North
South
East
West
Roof
Glass
Area (m2)
23.72
24.26
22.66
22.66
67.5
3.28
CLTDc (o C)
12.2
5.2
12
8
31.9
7
Total
Area (m2)
Shading Coefficient
(ASHRAE Table 20)
North
3.28
0.88
Internal Load
Q= P (CLF)
P= Input operating power (W)
CLF= Cooling load factor
SHGF
(ASHRAE
Table 34)
407
CLF
QSHG (W)
0.75
881.07
QTransmission (W)
518
225.82
486.74
324.5
2746.78
144.65
4446.49
Item
Input (W)
160
14
600
150
10000
Q (W)
129.6
14
600
150
10000
1893
Occupancy
Q= N G (CLF)
N= Number of occupant.
G= Sensible or latent heat. (W)
CLF= Cooling load factor. (Dimensionless for people)
Sensible
Latent
Number
15
15
SHG
75
LHG
55
CLF
1
1
Q
1125
825
Total 1950
Q (W)
4446.9
881.07
1893
1950
In Total 9170.97
So the total load is 9170.97 watt converting this to Air conditioning unit ton we get 2.61 Ton, so we
need to select an air conditioning system around 2.5 to 3 ton.