Professional Documents
Culture Documents
The equipment used in this experiment is the air pressure process control training system,
Model WF922 (Figure 1). This liquid flow model, WF922 consists of a stainless steel tank
(T21), three (3) centrifugal pumps (P21, P22A/B) and the associated piping, valves and
fittings.
The flowmeters are:
a) FT22: Vortex flowmeter
b) FI22: Rotameter or variable area flowmeter
c) FE21: Orifice plate
FT21: Differential pressure flow transmitter. Square root linearization of differential pressure
signal (FT21) is required because FT21 measures the pressure drop (h) across the orifice plate
and flow F= k h. Two pressure gauges PG21 and PG22 are installed at the inlet and outlet of
the flow control valve, FCV21 to measure the valve pressure drop which is related to the
flowrate.
Sensor/ Transmitter
FE21/FT21
Controller
FIC21
PV1=FT21
MV1 to FCY21/FCV21
Note that FIC21 is Single Loop Controller. For FIC21, its PV1 is always the Controlled Flow
CF.
METHODOLOGY
1) The following is checked quickly:
The main power supply (415V/50Hz/3 phase) is ON and the panel instruments are lit.
Tanks T21 is adequately filled with water up to almost the level of its lower overflow
pipe.
The pump manual by-pass valves B21, B22A and B22B are opened. Make sure all
the
pumps are switched OFF.
The Instrument air supply is set at the pressure indicated at the air pressure regulator
(IAS). Exact pressure adjustment of the air regulator (IAS) is not necessary. Once set,
it need not be readjusted frequently. The air regulator is purged using its bottom and
drain valve regularly.
The pipelines and control must be in normal operation position. First, manual valves
CF1/WF1 must be fully opened but CF2/WF2 are totally shut. Next, the Controller
selector switch is in Position 1: FT21=PV1=CF. Lastly, the interconnecting manual
valve MVX is fully shut.
Controller FIC21 is in Manual (M) mode with MV1=100% so that the control valve
FCV21 is fully opened. The control valve Positioner (PP) must be connected i.e. use
the positioned (PP).
d) With FIC21 in Manual (M) mode, adjust MV1=100% to make sure FCV21 is fully
opened.
e) Press RCD at the recorder FR21 to start its chart drive.
f) Open fully B21, the manual by-pass valve of pump P21. Start pump P21 only. Shut
fully its manual by-pass valve B21 but open fully its manual discharge valve for
maximum flow. Note down the flow rates and pressure gauge readings of the
following:FI22 : Variable Area Flow meter, read at FI22.
Note down the reading at the recorder chart, beside the Red response.
Read FT21 at Channel 1.
Note down the reading at the recorder chart, beside the Green
response.
PG21, PG22 : Pressure drop across the control valve FCV21 is PG21 PG22. Note
down the Pressure drop reading LAST (after reading FI22, FE21/FT21
and FT22) when they are steady, on the recorder chart paper.
Note that the flow rate is maximum if
- at FIC21, MV1 = 100% i.e. FCV21 is fully opened.
- discharge valve is fully opened.
- and by-pass valve B21 is fully shut.
Take readings only when they are stable and refer to the typical result sheets at the
results section. Take the pressure gauges readings last.
After taking the set of four (4) readings for Reading No1, proceed to the next
procedure for the next set of readings (Reading No.2). Then refer to the result sheet to
perform the calculation using the set of four (4) readings For Reading No.1 that were
just taken, allowing Reading No.2 to stabilize before taking them. The detailed
procedures are as follows,
Reading No. 1
Operate at maximum flow rate and record the 4 readings into the typical result
sheet. The pressure drop reading (PG21-PG22) should be taken last. Proceed to
the procedures below, described in Reading No.2.
Reading No. 2
Manually open the pump manual by-pass valve B21 by about 1 turn so that FI22
reads about 10% less flow. Perform the measurement calculation for Reading
No.1. Then record the 4 readings for Reading No.2, with the pressure drop
readings done last. Proceed to the procedures below, described in Reading
No.3.
Reading No. 3
With FIC21 in Manual (M) mode, adjust MV1 = 70% and check that FCV21 is
also about 70% opened. Perform the measurement calculation for Reading
No.2. Then record the 4 readings for Reading No.3, with the pressure drop
readings done last. Proceed to the procedures below, described in Reading
No.4.
Reading No. 4
With FCV21 at 50% opened, shut fully the pump by-pass valve B21. Perform the
measurement calculation for Reading No.3. Then record the 4 readings for
Reading No.4, with the pressure drop reading last. Proceed to the procedures
below, described in Reading No.5.
Reading No. 5
Manually shut the manual discharge valve of pump P21 until the Variable Area.
Flow meter FI22 reads about 1.2 m3/Hr. If the control valve Pressure drop is be
too low to be taken, take only the 3 flow meter readings. Perform the
measurement calculation for Reading No.4. Then record the readings for
Reading No.5, and perform the measurement calculation.
g) Switch off pump P21 and open fully its manual discharge valve.
a) Check that the manual discharge valve of pump P21 is fully opened.
b) Start pump P21 and shut its manual by-pass valve B21 fully.
Use the first (I) trial Linear PID values:
PB1 = 100%, TI1 = 5 sec, TD1 = 0 sec, GW1 = 0%, GG1 = 1.0
Change the set point at FIC21 to SV1 = 3.0 m/Hr.
Make sure the Recorder FR21 chart drive is running. Otherwise press its RCD
push button ON.
Check that the control valve Positioner (PP) is connected i.e. use the Positioner at
FCV21.
Switch FIC21 to Auto (A) mode and observe patiently the chart response (Red
pen) of FT21 for about 1 minute.
c) Introduce Derivative control mode to the PID controller by changing TD1 from 0 sec
to 5 sec i.e.
PB1 = 100%, TI1 = 5 sec, TD1 = 5 sec
Observe the chart response similarly for any oscillation due to the addition of
Derivative control mode. (If there is no oscillation, apply a load step disturbance by
switching FIC21 to Manual (M), step changing MV1 by about 10% and then
switching FIC21 back to Auto (A) mode. Observe for any oscillation).
d) If there is instability (oscillation), double the PB i.e. set PB1 from 100% to 200%.
Observe similarly if the instability can be damped.
e) Apply a load step disturbance test by switching FIC21 to Manual (M) mode, step
changing MV by about 10%, and then switching FIC21 back to Auto (A) mode.
Observe similarly, noting also whether the overall response and recovery to the set
point has been slowed down due to the larger PB1% required to damp the Derivativeinduced
oscillation.
f) Remove the Derivative control mode by setting TD1 to 0 sec, restoring back to the
first (I) trial Linear PID values:
PB1 = 100%, TI1 = 5 sec, TD1 = 0 sec, GW1 = 0%, GG1 =1.0
Apply a similar load step disturbance test as in the previous (e). Observe similarly. Is it
sound advice not to use Derivative mode for flow control?
5) To shut down WF922,
- Stop all pumps. Open fully their manual suction and discharge valves
- Switch the SWC selector switch back to Position 1.
- Check that the controller selector switch is at position : FT21 = PV1 = CF