MODBUSADDRESSLIST

PRJOECTNAME:UTILITYTUNNELCONTROLCENTERANDVIPBUILDINGIRRIGATIONCONTROLSYSTEM
PROJECTNUMBER:GAS_PRJ_15_034

PROJECT

UtilityTunnelControlCentreandVIPBuildingIrrigationControlSystem

ENDCLIENT

NICC

CONTRACTOR

SIDRA

SYSTEMINTEGERATOR

GulfAutomationSystemCo.

JOBNO

GAS_PRJ_15_034

DATE

6_2_2016

STATUS

ForApproval

DOC.NO-GAS-SID-MAL-0216-02

REV
0

DocumentName
DocumentNumber

Page 1 of 4

ModbusAddressList
GASSIDMAL021602

Location:
Doha

AR

HP

PBR

Preparedby

Reviewedby

Aprovedby

REV-0

UTILITYTUNNELCONTROLCENTERANDVIPBUILDINGIRRIGATIONCONTROLSYSTEM
MODBUSADDRESSLIST

SYSTEM IP ADDRESS- 192.XX.XX.XX


Tag Name

Read/Write

Description

OFFState
=0

ON State
=1

Signal Type

ABB PLC Address

Modbus Address

MOV101_ON_STS

Read

Motorized Valve 1 ON Status

BOOL

OPEN

NOT OPEN

%MX0

60

481

MOV101_OFF_STS

Read

Motorized Valve 1 OFF Status

BOOL

CLOSE

NOT CLOSE

%MX0

60

482

FV101_ON_STS

Read

Float Valve 1 ON Status

BOOL

OPEN

NOT OPEN

%MX0

60

483

FC101_OFF_STS

Read

Float Valve 1 OFF Status

BOOL

CLOSE

NOT CLOSE

%MX0

60

484

FSH101_ON_STS

Read

Gate Valve_FSH 1 ON Status

BOOL

OPEN

NOT OPEN

%MX0

60

485

FSH101_OFF_STS

Read

Gate Valve_FSH 1 OFF Status

BOOL

CLOSE

NOT CLOSE

%MX0

60

486

IR_PU1_A_M

Read

Irrigation Pump 1 Auto/Man

BOOL

AUTO

MANUAL

%MX0

60

487

IR_PU1_TR

Read

Irrigation Pump 1 Trip Feedback

BOOL

ALARM

HEALTYH

%MX0

60

488

%MX0

61

489

%MX0

61

490

IR_PU1_ST_FB

Read

Irrigation Pump 1 Stopped Feedback

BOOL

ON

OFF

IR_PU1_AV_FB

Read

Irrigation Pump 1 Available Feedback

BOOL

AVAILABLE

NOT AVAILABLE

IR_PU1_RU_FB

Read

Irrigation Pump 1 Running Feedback

BOOL

RUN

STOP

%MX0

61

491

IR_PU2_AU_MA

Read

Irrigation Pump 2 Auto/Man

BOOL

AUTO

MANUAL

%MX0

61

492

IR_PU2_TR

Read

Irrigation Pump 2 Trip Feedback

BOOL

ALARM

HEALTYH

%MX0

61

493

IR_PU2_ST_FB

Read

Irrigation Pump 2 Stopped Feedback

BOOL

ON

OFF

%MX0

61

494

IR_PU2_AV_FB

Read

Irrigation Pump 2 Available Feedback

BOOL

AVAILABLE

NOT AVAILABLE

%MX0

61

495

IR_PU2_RU_FB

Read

Irrigation Pump 2 Running Feedback

BOOL

RUN

STOP

%MX0

61

496

PDT101_ON_STS

Read

Solenoid Valve 1 ON Status

BOOL

OPEN

NOT OPEN

%MX0

62

497

PDT101_OFF_STS

Read

Solenoid Valve 1 OFF Status

BOOL

CLOSE

NOT CLOSE

%MX0

62

498

PS_STS

Read

Pressure Switch

BOOL

ALARM

NORMAL

%MX0

62

499

IR_TK_HH

Read

Level Switch High High

BOOL

ALARM

NORMAL

%MX0

62

500

IR_TK_LL

Read

Level Switch Low Low

BOOL

ALARM

NORMAL

%MX0

62

501

EMG_PB

Read

Emergency

BOOL

ALARM

NORMAL

%MX0

62

502

FLT_RST

Read

Fault Reset

BOOL

ON

OFF

%MX0

62

503

LOCAL_REMOTE

Read

LOCAL REMOTE SELECTOR SWITCH

BOOL

REMOTE

LOCAL

%MX0

62

504

SPARE

Read

SPARE

BOOL

%MX0

63

505

SPARE

Read

SPARE

BOOL

%MX0

63

506

SPARE

Read

SPARE

BOOL

%MX0

63

507

SPARE

Read

SPARE

BOOL

%MX0

63

508

SPARE

Read

SPARE

BOOL

%MX0

63

509

SPARE

Read

SPARE

BOOL

%MX0

63

510

SPARE

Read

SPARE

BOOL

%MX0

63

511

SPARE

Read

SPARE

BOOL

%MX0

63

512

SPARE

Read

SPARE

BOOL

%MX0

64

513

SPARE

Read

SPARE

BOOL

%MX0

64

514

SPARE

Read

SPARE

BOOL

%MX0

64

515

SPARE

Read

SPARE

BOOL

%MX0

64

516

SPARE

Read

SPARE

BOOL

%MX0

64

517

SPARE

Read

SPARE

BOOL

%MX0

64

518

SPARE

Read

SPARE

BOOL

%MX0

64

519

SPARE

Read

SPARE

BOOL

%MX0

64

520

MOV101_CMD

Read

Motorized Valve 1 ON/OFF Command

BOOL

OPEN COMMAND

CLOSE COMMAND

%MX0

65

521

FV101_CMD

Read

Float Valve 1 ON/OFF Command

BOOL

OPEN COMMAND

CLOSE COMMAND

%MX0

65

522

FSH101_CMD

Read

Gate Valve_FSH 1 ON/OFF Command

BOOL

OPEN COMMAND

CLOSE COMMAND

%MX0

65

523

IR_PU1_STA_CMD

Read

Irrigation Pump 1 Start Command

BOOL

ONCOMMAND

OFF COMMAND

%MX0

65

524

IR_PU1_STP_CMD

Read

Irrigation Pump 1 Stop Command

BOOL

OFF COMMAND

ONCOMMAND

%MX0

65

525

IR_PU2_STA_CMD

Read

Irrigation Pump 2 Start Command

BOOL

ONCOMMAND

OFF COMMAND

%MX0

65

526

IR_PU2_STP_CMD

Read

Irrigation Pump 2 Stop Command

BOOL

OFF COMMAND

ONCOMMAND

%MX0

65

527

DOC.NO-GAS-SID-MAL-0216-02

Page 2 of 4

Remarks

REV-0

UTILITYTUNNELCONTROLCENTERANDVIPBUILDINGIRRIGATIONCONTROLSYSTEM
MODBUSADDRESSLIST

SYSTEM IP ADDRESS- 192.XX.XX.XX


Tag Name

Read/Write

Description

Signal Type

ON State
=1

OFFState
=0

ABB PLC Address

Modbus Address

PDT101_CMD

Read

Solenoid Valve 1 ON/OFF Command

BOOL

OPEN COMMAND

CLOSE COMMAND

%MX0

65

528

SPARE

Read

SPARE

BOOL

%MX0

66

529

SPARE

Read

SPARE

BOOL

%MX0

66

530

SPARE

Read

SPARE

BOOL

%MX0

66

531

SPARE

Read

SPARE

BOOL

%MX0

66

532

SPARE

Read

SPARE

BOOL

%MX0

66

533

SPARE

Read

SPARE

BOOL

%MX0

66

534

SPARE

Read

SPARE

BOOL

%MX0

66

535

SPARE

Read

SPARE

BOOL

%MX0

66

536

MOV101_F2ST

Read

Motorized Valve Fail to start

BOOL

FAULT

NORMAL

%MX0

67

537

MOV101_F2SP

Read

Motorized Valve Fail to stop

BOOL

FAULT

NORMAL

%MX0

67

538

FV101_F2ST

Read

Float Valve 1 Fail to start

BOOL

FAULT

NORMAL

%MX0

67

539

FV101_F2SP

Read

Float Valve 1 Fail to stop

BOOL

FAULT

NORMAL

%MX0

67

540

FSH101_F2ST

Read

Gate Valve_FSH 1 Fail to start

BOOL

FAULT

NORMAL

%MX0

67

541

FSH101_F2SP

Read

Gate Valve_FSH 1 Fail to stop

BOOL

FAULT

NORMAL

%MX0

67

542

IR_PU1_F2ST

Read

Irrigation Pump 1 Fail to start

BOOL

FAULT

NORMAL

%MX0

67

543

IR_PU1_F2SP

Read

Irrigation Pump 1 Fail to stop

BOOL

FAULT

NORMAL

%MX0

67

544

IR_PU2_F2ST

Read

Irrigation Pump 2 Fail to start

BOOL

FAULT

NORMAL

%MX0

68

545

IR_PU2_F2SP

Read

Irrigation Pump 2 Fail to stop

BOOL

FAULT

NORMAL

%MX0

68

546

PDT101_F2ST

Read

Solenoid Valve 1 Fail to start

BOOL

FAULT

NORMAL

%MX0

68

547

PDT101_F2SP

Read

Solenoid Valve 1 Fail to stop

BOOL

FAULT

NORMAL

%MX0

68

548

IR_TK_HH_ALM

Read

Level Switch High High

BOOL

HIGH HIGH LEVEL

NORMAL

%MX0

68

549

IR_TK_LL_ALM

Read

Level Switch Low Low

BOOL

LOW LOW LWVEL

NORMAL

%MX0

68

550

LIT101_HH_ALM
LIT101_H_ALM

Read
Read

Level Indicating Transmitter High High


Level Indicating Transmitter High

BOOL
BOOL

HIGH HIGH LEVEL


HIGH LEVEL

NORMAL
NORMAL

%MX0
%MX0

68
68

6
7

551
552

LIT101_LL_ALM

Read

Level Indicating Transmitter Low

BOOL

LOW LWVEL

NORMAL

%MX0

69

553

LIT101_L_ALM

Read

Level Indicating Transmitter Low Low

BOOL

LOW LOW LWVEL

NORMAL

%MX0

69

554

NORMAL

LIT101_L_FLT

Read

Level Indicating Transmitter Fault

BOOL

FAULT

%MX0

69

555

PIT101_H_ALM

Read

Pressure Indicating Transmitter High

BOOL

HIGH PRESSURE

%MX0

69

556

PIT101_L_ALM

Read

Pressure Indicating Transmitter Low

BOOL

LOW PRESSURE

%MX0

69

557

PIT101_FLT

Read

Pressure Indicating Transmitter Fault

BOOL

FAULT

%MX0

69

558

PDT101_H_ALM

Read

Pressure Differential Transmitter High

BOOL

HIGH PRESSURE

%MX0

69

559

PDT101_L_ALM

Read

Pressure Differential Transmitter Low

BOOL

LOW PRESSURE

%MX0

69

560

PDT101_FLT

Read

Pressure Differential Transmitter Fault

BOOL

FAULT

%MX0

70

561

D1_STS

Read

Decoder 1 Status

BOOL

ON

OFF

%MX0

70

562

D2_STS

Read

Decoder 2 Status

BOOL

ON

OFF

%MX0

70

563

D3_STS
D4_STS
D5_STS
D6_STS
STATION_FAIL
CONTROLLER_TEM_ALM
SENSOR_FAIL
COMM_FAIL
PWR_FAIL
2WIRE_CUR
L_PRESSURE_ALM_RTU
FLOW_L_ALM
FLOW_H_ALM
FALUT_STATION
SPARE

Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read

Decoder 3 Status
Decoder 4 Status
Decoder 5 Status
Decoder 6 Status
Station failed
RM2 Over Temperature
Sensors Fail
BT Comms Fail
Power Fail
2 Wire Over Current
Low Pressure During Program
Low Flow During Run
High Flow During Run
Flow When Stations are not Running

BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL

ON
ON
ON
ON
FAULT
ALARM
FAULT
FAULT
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
-

OFF
OFF
OFF
OFF
HEALTYHY
NORMAL
HEALTYHY
HEALTYHY
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
-

%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0

70
70
70
70
70
71
71
71
71
71
71
71
71
72
72

3
4
5
6
7
0
1
2
3
4
5
6
7
0
1

564
565
566
567
568
569
570
571
572
573
574
575
576
577
578

DOC.NO-GAS-SID-MAL-0216-02

SPARE

Page 3 of 4

Remarks

REV-0

UTILITYTUNNELCONTROLCENTERANDVIPBUILDINGIRRIGATIONCONTROLSYSTEM
MODBUSADDRESSLIST

SYSTEM IP ADDRESS- 192.XX.XX.XX


Tag Name
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read

Tag Name
IR_PU1_SPD_FB
IR_PU2_SPD_FB
PIT101
PDT101
LIT101
SPARE
SPARE
SPARE
IR_PU1_SET_FB
IR_PU2_SET_FB
SPARE
SPARE
SPARE
SPARE
SPARE
FLOW_TT_VAL
IR_PU1_RH
IR_PU2_RH
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

Description
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read

BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
Description

Irrigation Pump 1 VFD Actual Speed Feedback


Irrigation Pump 2 VFD Actual Speed Feedback
Pressure Indicating Transmitter
Pressure Differential Transmitter
Level Indicating Transmitter
SPARE
SPARE
SPARE
Irrigation Pump 1 VFD Set Speed
Irrigation Pump 2 VFD Set Speed
SPARE
SPARE
SPARE
SPARE
SPARE
Flow Transmitter Reading
Irrigation Pump 1 Run Hour
Irrigation Pump 2 Run Hour
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

OFFState
=0

ON State
=1

Signal Type
Signal Type

ABB PLC Address


%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0
%MX0

Range

REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
DINT
DINT
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL

0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
0-65535(Hours)
0-65335(Hours)
-

72
72
72
72
72
72
73
73
73
73
73
73
73
73
74
74
74
74
74
74
74
74
75
75
75
75
75
75
75

2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6

100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Remarks

Modbus Address

Remarks

579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607

ABB PLC Address


%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD0
%MD1
%MD2
%MD3
%MD4
%MD5
%MD6
%MD7
%MD8
%MD9
%MD10
%MD11
%MD12

Modbus Address

200
202
204
206
208
210
212
214
216
218
220
222
224
226
228
230
232
234
236
238
240
242
244
246
248
250
252
254

Note
1 Refference Documents- ICA Material Submittal-GAS-1534-MS-0824-REV1
2.Internal variables May be changed based on client Requirment/Engineering Submittal Appoval.

DOC.NO-GAS-SID-MAL-0216-02