Alarms In NOKIA FLEXI BTS

BY : KETANKUMAR WANKHEDE

1.)

7401 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Mains Failure
N/C
Major
Green & Green/White
7, 25
PIU

Root cause
Cause

Verification

2.)

DDF

BTS

Alarm occurs when there is no AC power supply on site


1. AC gets failure due to regular AC cut.
2. AC gets failure due to any s/c.
3. AC gets failure due to any o/c.
To check the alarm Switch off the mains MCB from
PIU.
To remove alarm turn on the mains mcb.

7402 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Rectifier Fail
N/O
Minor
Blue & Blue /White
8, 26
Alarm panel
Of P.P.

DDF

BTS

Root cause
Cause

Verification

3.)

7403 Alarm

Syntex
Type
Severity
Colour
Pin
Root
Root cause
Cause

Verification

4.)

Alarm occurs when any one of the SMPS gets failure.


1. Any SMPS gets failure.
2. Due to failure of MCB.
3. Due to any s/c.
To check the alarm firstly remove the rectifier from
the SMPS or switch off the MCB of rectifier from
SMPS.
To remove alarm switch on the.MCB of the
rectifier moduleor insert the new rectifier module.

Low Battery Voltage


N/O
Criticle
Violet & Violet /White
9, 27
Alarm panel
Of P.P.

BTS

Alarm occurs when Battery voltage reaches 46V/47V.


1. When AC gets failure and D.G. is not working & site
on battery from last 3-4 hrs.
2. When Battery is not fully charged and load on
battery.
To check the alarm set the o/p load vtg of battery
less then 48V & switch off the MCB & D.G..
To remove alarm switch on the.MCB (mains) or
switch on the D.G. if AC is not available.

7404 Alarm

Syntex
Type
Severity

DDF

Site On Battery
N/O
Major

Colour
Pin
Root
Root cause
Cause

Verification

5.)

Gray & Gray /White


10, 28
Alarm panel
Of P.P.

DDF

BTS

Alarm occurs when all SMPS & Rectifiers gets failure.


1. When AC gets failure and D.G. does not start.
2. AC gets fail DG is off.
3. DG is not working properly.
4. AC gets failure & DG is not available at site.
5. All SMPS & rectifires gets failure.
To check the alarm switch off the mains MCB from
PIU & switch off DG also.
To remove alarm switch on the mains MCB or DG
(if mains is not available).

7405 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Site On DG
N/O
Minor
Pink & Pink /White
11, 29

Root cause
Cause

Alarm occurs when load of site on DG.


1. When AC gets failure due to cutting time.
2. AC gets fail due to s/c.
3. MCB gets failure.
To check the alarm switch off the mains MCB from
PIU & switch on the DG (if it is not in auto mode).
To remove alarm switch on the mains MCB (if
mains is available).

Verification

PIU

DDF

BTS

6.)

7406 Alarm

Syntex
Type
Severity
Colour
Pin
Root

DG LLOP
N/O
Criticle
Light Green & Black /Green
12, 30

Root cause

Alarm occurs when lube oil pressure gets below then


specified level.
1. Due to leakage of lubricant.
2. Due to overflow of lubricant.
3. Due to no service on time.
4. Due to no oil change on the time.
To check the alarm switch off the mains MCB from
PIU & switch off the DG also.
To remove alarm maintain the lubricant oil
pressure till specified level.

Cause

Verification

7.)

LLOP Sensor

PIU

DDF

BTS

7407 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Low Fuel Level


N/O
Minor
Light Blue & Black /Blue
13, 31

Root cause

Alarm occurs when fuel level goes below then 40% of the

Fuel Sensor

PIU

DDF

BTS

Cause

Verification

8.)

capacity.
1. When site on DG from long time.
2. When fuel tank is not fully filled.
3. Tank have leakage.
To check the alarm see if the desired fuel level of DG
is set on 40% or not.
To remove alarm fill the tank of DG.

7408 Alarm

Syntex
Type
Severity
Colour
Pin
Root

DG Fails To Start
N/O
Major
White & Black /White
13, 31

Root cause

Alarm occurs when PIU is not able to start DG in 3


attempts.
1. Due to problem in self.
2. Self battery is not charge.
3. No fuel in DG.
4. No connection b/w PIU & Self.
To check the alarm switch off the mains mcb from
PIU and check dg set is not in auto mode or remove
the connection b/w PIU and Self.
To remove alarm start DG in manual mode.

Cause

Verification

9.)

PIU

7409 Alarm

Syntex
Type

AC Failure
N/O

DDF

BTS

Severity
Colour
Pin
Root
Root cause
Cause

Verification

10.)

Major
Light Gray & Black /light gray
15, 33
C

DDF

BTS

Alarm occurs when both AC gets failure.


1. Due to problem in C.
2. Site on battery.
3. Level of gas in AC goes below then the
specified level.
4. Switching problem.
To check the alarm switch off the ACs.
To remove alarm switch on/repair/replace ACs.

7410 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Door Open
N/C
Minor/Major/Criticle (Accd. to condition)
Red/ Black & Red/Blue
16, 34
Door Sensor

Root cause
Cause

Verification

PIU

DDF

BTS

Alarm occurs when Door is open.


1. Unauthorisd person is in the shelter.
2. Work on progress inside the shelter.
3. Someone (may be technician, engineer or guard)
forget to close the door.
4. Sealing of door is not proper.
5. Lock of door is not correct.
To check the alarm open the door.
To remove alarm close and seal proper the door.

11.)

7411 Alarm

Syntex
Type
Severity
Colour
Pin
Root

High Room Temp.


N/O
Major
Orange/Red & orange/Light gray
16, 34

Root cause
Cause

Alarm occurs when Temp reaches 35 c.


1. AC is not working.
2. Door of shelter is open.
3. Site on battery.
To check the alarm rub thermister in b/w hands .
To remove alarm switch on the AC & set AC temp
on desired value.

Verification

12.)

Temp.Sensor

c of AC

DDF

BTS

7412 Alarm

Syntex
Type
Severity
Colour
Pin
Root

Fire & Smoke.


N/O
Criticle
Orange/Black & Orange/Green
18, 36

Root cause
Cause

Alarm occurs when Fire & Smoke at site.


1. Fire & Smoke at site.
2. Due to any inflammable object at site.
To check the alarm create a small fire by paper or

Verification

F& S sensor

PIU

DDF

BTS

jute.
To remove alarm Reset smoke & fire sensor and
clean the smoke from the sensor.