EVCB14NIT0S
EVCB14NIT2S
EVCB14NIT4S
EVCB14NDT4S
EVCB14NIT0SF
EVCB14NIT4SF
TRL54
(Thermostat 3x3)
Description
Typical Application
Applications
Features
Network Communication
Operational Features
EVCB14N-TRL54-150622-ESA
BACnet MS/TP
Modbus
Page | 1
Controller Specifications
Description
Torque
Power consumption
Running time through 90
Power supply
EVCB Series
70 in.lb. [8 Nm] at rated voltage
10 VA max
90 seconds
22 to 26 Vac 50/60 Hz
2 Universal inputs (Thermistor 10K Type 3, digital 24Vac/dry contact, or 0-10Vdc)
2 digital inputs
0-1.0 WC (available on pressure independent models)
2 analog outputs (0-10 Vdc or 2-10Vdc; selectable)
Up to 4 TRIAC outputs 24 Vac, 500mA max fused (on/off, pulse, or 2 floating outputs)
Inputs
On-board differential pressure sensor
Outputs
Real Time Clock
BACnet
Modbus
Communication connection
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
Weight
A = 2.85 | 73mm
B = 4.85 | 123mm
C = 1.00 | 24mm
D = 2.36 | 60mm
E = 3.27 | 83mm
The actuator performs an auto-stroke on power up. When changing the actuator adjustment screws, cycle power
to initiate the auto-stroke. Auto-stroke is not available on EVC pressure independent without feedback.
Thermostat Specifications
Description
TRL54
Sensor
Temperature
Setpoint range
Control accuracy
Display resolution
Electrical connection
Neywork service port
Power supply
Power consumption
Operating temperature
Storage temperature
Relative humidity
Enclosure protection
Weight
Dimensions
Note
www.neptronic.com
A = 3.00 in (78mm)
B = 3.00 in (78mm)
C = 1.00 in (24mm)
D = 2.36 in (60mm)
The thermostat functions only with the EVCB Series controller. All the inputs/outputs are located on the EVCB Series
except for the temperature sensor built-in the thermostat.
Page | 2
TRL54 Interface
Cooling ON
A: Automatic
Heating ON
A: Automatic
Minimum/Maximum
Cor F
Programming mode
(Technician setting)
Alarm status
C: Celsius scale
F: Fahrenheit scale
Mechanical Installation
MOUNTING
BRACKET
CLUTCH
Mounting Instructions
CAUTION: Remove power to avoid a risk of malfunction.
A.
B.
C.
D.
E.
Remove the captive screw thats holding the base and the front cover of the unit together.
Lift the front cover of the unit to separate it from the base.
Pull all wires through the holes in the base.
Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
Mount the control module on the base and secure using the screw.
DS.1 = 1
DS.2 = 2
DS.3 = 4
DS.4 = 8
DS.5 = 16
DS.6 = 32
DS.7 = 64
DS.8 = 128
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
153000
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
153001
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
153002
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
153003
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
153004
126
OFF
ON
ON
ON
ON
ON
ON
OFF
153126
127
ON
ON
ON
ON
ON
ON
ON
OFF
153127
www.neptronic.com
Page | 3
Wiring
We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service
only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
Room Module (TRL54)
Mode Selector Jumper
RUN = Operation Mode
PGM = Programming Mode
JP1
RUN
PGM
TB1
COM
24V
COMM. BUS
A+
B-
Temperature
Sensor
EOL
TB6
JP3
RXD
ON
TXD
1 2 3 4 5 6 7 8
DS1
DI1
TO4
COM
TO3
24Vac input
(TO3/TO4)
TO2
COM
TO1
24Vac input
(TO2/TO1)
24Vac
24Vac
COM
TB5
COM
TB4
DI2
TB3
AO1
TB2
COM
TB1
AO2
Power Status
AI1
EXT
COM
INT
JP2
AI2
EXT
To other
BACnet
devices
INT
JP1
A+ (in)
www.neptronic.com
B- (in)
COM
A+ (out)
B- (out)
COM
Pwr
Data
TB7
BACnet
service port
Optional:
connect
to enable
service port
COM
Power Input/Output
24Vac
Page | 4
For a description of the default settings for each application refer to Annex A: Control Apps on page 14.
Main Menu
Sub Menu
Configuration
*** You must press the
button to save any changes ***
*** Pressing the
button returns to the previous step without saving ***
Main Menu
= scroll menu items
PrS MM (Pressure)
APP MM
(Applications)
InP MM(Inputs)
OUT MM (Outputs)
BV.50
BV.52
APP MM
APP MM
InP MM
The APPS represent pre-defined default settings
for selected applications. If you select Yes, the
settings in Annex A will be applied and override
any values already configured.
We recommend selecting the `Control Apps` before changing any other configurations. Once selected, certain
configurations, such as NSB, proportional bands, and deadbands, will be erased and reset to factory default values.
tNP MM (Temperature)
Mt MM (Motor)
SEt MM (Settings)
rNP MM (Ramps)
NEt MM (Network)
www.neptronic.com
Page | 5
Sub Menu
Configuration
Main Menu
= scroll menu items
PrS MM (Pressure)
APP MM
(Applications)
InP MM (Inputs)
OUT MM (Outputs)
tNP MM (Temperature)
Mt MM (Motor)
SEt MM (Settings)
MSV.1
AI1 (AI1 signal type)
OFF (disabled)
EtS (external temp sensor)
SEN (sensor)
nCL (C) (normally cool)
nHt (H) (normally heat)
StF (F) (stpnt airflw 0-10Vdc)
CO2 (carbon dioxide)
ASt (Air supply temp sensor)
Mr (motor input)
AI1
Go to AI2" InP
Go to AI2" InP
Go to AI2" InP
Go to AI2" InP
AV.141
Go to AI2" InP
AI2
Go to dI1" InP
Go to dI1" InP
Go to dI1" InP
Go to dI1" InP
AV.141
Go to dI1" InP
dI1
Go to dI2" InP
AV.61
10-40C (50-104F)
10-40C (50-104F)
AV.18
BV.20
rNP MM (Ramps)
= select / set value
MSV.14 dI2
NEt MM (Network)
www.neptronic.com
Go to OuT" MM
BV.36
Go to
dI2" InP
MSV.36
Go to
dI2" InP
Go to OuT" MM
AV.64
Go to OuT" MM
Page | 6
Configuration
Sub Menu
Main Menu
Main Menu
PrS MM (Pressure)
APP MM
(Applications)
InP MM (Inputs)
OUT MM (Outputs)
tNP MM (Temperature)
Mt MM (Motor)
SEt MM (Settings)
rNP MM (Ramps)
NEt MM (Network)
www.neptronic.com
= Auto and On
options are for fan
powered box
applications and
are only available
with models:
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
MSV.25
tO1 (TO1 ramp)
OFF
Cr1 (cooling ramp 1)
Cr2 (cooling ramp 2)
Hr1 (heating ramp 1)
Hr2 (heating ramp 2)
CO2 (carbon dioxide)
Aut (fan follows demand)
On (fan continuously on)
tO1
Go to tO2"
MSV.26
40% (15-80%)
AV.78
AV.75
BV.32
dIr (direct)
rEv (reverse)
BV.30
Go to
tO3"
BV.33
Go to
tO3"
BV.32
Go to
tO4"
dIr (direct)
rEv (reverse)
Go to
tO2"
tO2
Go to tO3"
t2C (TO2 close percent)
tO2
MSV.28
AV.79
dIr (direct)
rEv (reverse)
On (on/off)
PuL (pulsed)
Go to t2C TO2 Close Percent
Go to to2 TO2 DIR-REV
tO3
Go to tO4"
MSV.30
40% (15-80%)
AV.77
AV.78
dIr (direct)
rEv (reverse)
FLt (TO3 TO4 direction)
AV.75
BV.30
dIr (direct)
rEv (reverse)
Go to
AO1"
tO4
Go to AO1"
40% (15-80%)
AV.83
BV.35
Go to AO1"
dIR (direct)
rEv (reverse)
Page | 7
Main Menu
Configuration
Main Menu
PrS MM (Pressure)
APP MM
(Applications)
InP MM (Inputs)
OUT MM (Outputs)
tNP MM (Temperature)
Mt MM (Motor)
MSV.20
AO1(AO1 ramp)
OFF
Cr1 (C) (cooling ramp 1)
Cr2 (C) (cooling ramp 2)
Hr1 (H) (heating ramp 1)
Hr2 (H) (heating ramp 2)
CO2 (carbon dioxide)
StF (setpnt airflow 0-10Vdc)*
Aut (fan follows demand)
On (fan continuously on)
AO1
Go to AO2"
Ao1 (Direction)
dIR (direct)
rEv (reverse)
BV.25
Go to
AO2"
Ao2 (Direction)
BV.26
Go to
tNP" MM
AO2
Go to tNP" MM
dIr (direct)
rEv (reverse)
SEt MM (Settings)
rNP MM (Ramps)
NEt MM (Network)
www.neptronic.com
Page | 8
Sub Menu
Configuration
Main Menu
PrS MM (Pressure)
( 5C/ 10F)
( 5C / 10F)
(10-40C/50-104F)
APP MM
(Applications)
InP MM (Inputs)
(Temperature)
Mt MM (Motor)
www.neptronic.com
(10-40C / 50-104F)
AV.15
Go to Mt" MM
Mr (Motor direction)
dIr (direct)
rEv (reverse)
BV.40
is set to EtS
Go to SEt" MM
MSV.4
MSV.17
BV.3
NO
NEt MM (Network)
AV.17
Go to
Mt" MM
AV.145
AV.51
tNP MM
rMP MM (Ramps)
OUT MM (Outputs)
SEt MM (Settings)
AV.16
BV.6
(0-60 min)
AV.106
AV.30
MSV.95
dIS (Display info)
tC (C/F, %RH & demand)
StP (setpoints & demand)
tC (C/F and %RH)
StP (setpoints)
OFF (none of the above)
AV.56
BV.100
BV.100
Fco (Fan Always On Mode)
on (always on)
OFF (follows NSB/NoOcc)
AV.57
Go to Cr1"
AV.42
db1 (Cl dead band1)
0.3C/0.6F (0-5C/0-9F)
Go to Cr2"
Go to Hr1"
Go to Hr2"
Go to NEt" MM
Go to
rMP"
Go to
rMp"
Page | 9
Configuration
Sub Menu
Main Menu
PrS MM (Pressure)
APP MM
(Applications)
InP MM (Inputs)
Mt MM (Motor)
SEt MM (Settings)
OUT MM (Outputs)
tNP MM (Temperature)
Go to
HrS"
MM
MA (Modbus address)
1 (1-246)
Modifiable only if all DS2 DIP
switches are set to OFF.
set to No.
AV.165
127 (1-127)
Go to HrS" MM
Go to
CPY"
Copy Config
in (in progress)
Go to
HrS"
rNP MM (Ramps)
NEt MM (Network)
HrS MM
(Time & Date)
www.neptronic.com
AV.167
Hrs (Hours)
Local Time
MI (Minutes)
00 (00-59)
Mo (Month)
1 (1-12)
Local Time
Local Date
yr (Year)
15 (15-99)
dAy
Local Date
Local Date
Go to Prs"
1 (1-31)
Page | 10
Operation Menus
This menu is accessible through normal operation mode. The Mode Selector jumper (JP1) of the thermostat must be set to the
RUN position (Operation Mode). Refer to Wiring on page 4.
Press the [*] and [] buttons simultaneously for 5 seconds. The Enter Password screen appears.
Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the [*] and [] buttons to
toggle between the digits.
a. Password 372 = Temperature Offset Menu
b. Password 637 = Network Settings Menu
c. Password 757 = Air Balance Mode
3. If you enter the wrong password, the thermostat displays Eror and returns to Operation Mode. The thermostat will return to
normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5
minutes. The changed values will be saved automatically.
1.
2.
Range:
10 to 40C
[50 to 104F]
Offset:
Max 5C
Increment:
0.1C
[0.2F]
Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the
arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read
is slightly different than the rooms actual temperature. For example, a thermostat placed right under the air diffuser.
If the thermostat is set to use an external temperature sensor (EtS), the thermostat displays OFF.
Range:
0 to 50C
[41 to 122F]
Offset:
Max 5C
Increment:
0.1C
[0.2F]
This option appears if youve set one of the analog inputs to EtS (External temperature sensor). When the thermostat is
connected to the appropriate analog input, the display shows the temperature read by the external temperature sensor. Adjust
the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the display is
blank Error.
Displays the voltage output value in mV of the pressure sensor. Does not appear for EVCB14NDT4S (pressure dependent)
models.
Range:
10mV to 180mV
Default:
60mV
This setting represents the deadband of the pressure sensor in mV. For advanced users or special applications only. We
recommend that you use the default setting of 60mV. Does not appear for EVCB14NDT4S (pressure dependent) models.
nEt
tYP (Type)
Md (Modbus)
bAC (BACnet)
CPY (copy config)
End (exit menu)
www.neptronic.com
Go to ENd"
1 (1-246)
Modifiable only if all DS2 DIP
switches are set to OFF.
AV.165
Go to CPYc"
MA (Modbus address)
BV.90
Copy Config
in (in progress)
AV.167
Go to
ENd"
Page | 11
AV.100
VAV (Configuration)
COn (configuration)
SEt (settings)
bAL (balancing)
mt (motor)
End (exit menu)
AV.103
AV.105
AF1
0.0 (see note)
bAL (Airflow balance)
MSV.42
MSV.37
Aut (automatic)
OPn (open)
CLs (close)
FLo (airflow low)
FLo (airflow high)
AV.114
AV.114
AF2
0.0 (same as Close Motor)
AF3
0.0 (see note)
AV.112
AV.112
AF4
0.0 (same as Maximum Airflow)
MSV.41
1
10
100
AV.102
HEAt
SEtc
AV.104
Go to bAL"
VAV Config
mt (motor)
End (exit menu)
Exit menu and return
to normal operation
Mr (Motor override)
MSV.37
Aut (automatic)
OPn (open)
CLs (close)
Returns to
run mode
During the power up sequence of the thermostat (when the firmware versions are displayed), press and hold both the
buttons.
2. The PAS screen appears. Enter 372 within 1 minute by using the arrow keys to increase or decrease the value and the
and
buttons to toggle between the digits.
3. Use the arrow buttons to select YES and then press
.
www.neptronic.com
and
Page | 12
Operation Mode
The Mode Selector Jumper (JP1) of the thermostat must be set to the RUN position (Operation Mode). Refer to Wiring on
page 3.
Power Up
Upon power up, the LCD illuminates and all segments appear for 2 sec. The thermostat then displays its current version of the
thermostat for 2 seconds followed by the current version of the controller for 2 seconds. Pressing any key on the thermostat
illuminates the LCD for 4 seconds.
Temperature
The thermostat displays the temperature reading for 8 seconds. If the sensor is disconnected or short circuited, then OFF, - - - and
alarm symbol
are displayed. To toggle the temperature scale between C and F, press the
button.
Temperature Setpoint
To display the setpoint, press the
or
key twice. The set point appears for 5 seconds. To adjust the setpoint, press the arrow
keys while the temperature is displayed. If the setpoint adjustment has been locked, the lock symbol appears.
Control Mode
To access the Control Mode, press the
button. The Control Mode appears for 5 seconds. Press the
button to scroll
through the following control modes. These options can vary depending on the options selected in "Temp Control Mode" and
"Enable OnOff Control Mode.
www.neptronic.com
Page | 13
Refer to Pressure & Applications Menu Overview (1 of 6) on page Error! Bookmark not defined. for more information.
Description
Min. Setpoint
Max. Setpoint
Changeover Setpnt
TO1 Ramp
TO1 Signal Type
TO1 Close Pos.
TO1 Open Pos.
TO2 Ramp
TO2 Signal Type
TO2 Close Pos.
TO2 Open Pos.
TO3 Ramp
TO3 Signal Type
TO3 Close Pos.
TO3 Open Pos.
TO4 Ramp
TO4 Signal Type
TO4 Close Pos.
TO4 Open Pos.
Motor Ramp
AO1 ramp
AO2 Ramp
AI1 Input
AI2 Input
DI1 Input
Heat Prop Band 2
Heat Deadband 2
Cool Deadband 2
(cool only)
CL
(cool/heat)
(cool/heat/reheat)
CHrH
CO2
ITOS
(ITOS)
20C (68F)
28C (82F)
20C (68F)
28C (82F)
20C (68F)
20C (68F)
28C (82F)
20C (68F)
HR1
20C (68F)
28C (82F)
20C (68F)
15C (59F)
30C (86F)
24C (75F)
OFF
15C (59F)
30C (86F)
24C (75F)
HR1
15C (59F)
30C (86F)
24C (75F)
HR1
On/Off
40%
0%
OFF
On/Off
35%
On/Off
35%
0%
HR1
On/Off
70%
35%
Fan Auto
24C (75F)
HR1
On/Off
40%
0%
HR1
Pulse
40%
0%
HR2
On/Off
40%
0%
HR2
Pulse
40%
0%
CR1
HR1
HR2
CLHt
CR1
On/Off
40%
0%
HR1
On/Off
40%
0%
CR2
On/Off
40%
0%
HR2
On/Off
40%
0%
COr
On/Off
40%
0%
HR1
Pulse
40%
0%
HR2
On/Off
40%
0%
HR2
Pulse
OFF
OFF
nSb.o
CR1
HR1
SENS
40%
0%
COr
HR1
HR2
SENS
OFF
nSb.o
OFF
nSb.o
2C (4F)
1.3C (2.6F)
1.3C (2.6F)
2C (4F)
1.3C (2.6F)
1.3C (2.6F)
2C (4F)
1.3C (2.6F)
1.3C (2.6F)
(CO2)
CR1
On/Off
40%
0%
CO2
FPbo
FPbA
On/Off
40%
0%
HR1
On/Off
40%
0%
OFF
0%
HR1
On/Off
70%
35%
Fan ON
On/Off
40%
0%
HR1
On/Off
40%
0%
OFF
On/Off
40%
0%
HR1
On/Off
40%
0%
OFF
On/Off
40%
0%
COr
On/Off
40%
0%
CR1
HR1
OFF
On/Off
40%
0%
CR1
HR1
HR2
OFF
OFF
Occ.o
2C (4F)
0.3C (0.6F)
0.3C (0.6F)
OFF
OFF
nSb.o
1C (2F)
1.3C (2.6F)
On/Off
40%
0%
COr
HR1
Fan Auto
SENS
OFF
nSb.o
1C (2F)
1.3C (2.6F)
0.3C (0.6F)
0.3C (0.6F)
CR1
HR1
SENS
CO2
Occ.o
2C (4F)
1.3C (2.6F)
1.3C (2.6F)
Legend
Grey Text = Standard default value
Bold Text = Special default value for selected application
HR
CR
COr
SENS
Fan ON
Fan Auto
nSb.o
Occ.o
= Heating ramp
= Cooling ramp
= Changeover ramp
= Changeover temperature sensor
= Fan powered box in continuous mode
= Fan powered box in automatic mode (follows demand)
= Night Set Back (normally open)
= Occupancy mode (normally open)
TO
AO
AI
DI
= Triac output
= Analog output
= Analog input
= Digital input
www.neptronic.com
Page | 14
Notes
Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest
Neptronic authorized distributor, please consult www.neptronic.com.