Professional Documents
Culture Documents
Circuit Breakers
PTPH/HV - Page 1
Product Presentation
Edition 2, 2005-01
Company Location
PTPH/HV - Page 2
Ludvika
PTPH/HV - Page 3
World
Class
Technology
PTPH/HV - Page 4
Example: 420 kV
the sixties
the seventies
& the eighties
the eighties
& the nineties
Air Blast
Oil Minimum
SF6 Gas
Product
Range
On request
63
On request
50
40
31.5
PTPH/HV - Page 5
25
2 breaking
elements
per pole
1 breaking
element
per pole
72
170
245 300
420
4 breaking
elements
per pole
550
800
1150
PTPH/HV - Page 6
Design
Breaking Chamber
Support Insulator
Support Structure
Trip Spring
Position Indicator
Function
PTPH/HV - Page 7
HPL B
LTB D
LTB E
Product
Range
PTPH/HV - Page 8
PTPH/HV - Page 9
References
References
PTPH/HV - Page 10
BLG 1002A
PTPH/HV - Page 11
Product
Range
A revolutionary concept
for the operation of the CB
A Motor Drive is a
digitally controlled motor
directly moving the circuit
breaker contacts.
1- or 3-pole operated
PTPH/HV - Page 12
Product
Range
LTB D1 (Standard)
72.5 - 170 kV
40 kA
3150 A
Spring operated
Single-, Two or
Three-pole operation
PTPH/HV - Page 13
Product
Range
72.5 - 170 kV
40 kA
3150 A
Spring operated /
Motor Drive
Single- or Three-pole
operation
PTPH/HV - Page 14
References
Type LTB D
PTPH/HV - Page 15
Product
Range
LTB E1
245 kV
40 - 50 kA
4000 A
Spring operated
Single-, Two- or
Three-pole operation
PTPH/HV - Page 16
Product
Range
LTB E2
362 - 550 kV
50 kA
4000 A
Spring operated
PTPH/HV - Page 17
References
Type LTB E
Product
Range
Breaker
Type
LTB
Insulation Level
LIWL
Breaking
Current
Normal
Current
(kV)
(kA)
(A)
72.5 D1
1/3
325
40
3150
145 D1
1/3
650
40
3150
170 D1
1/3
750
40
3150
170 E1
1/3
750
50 (40kA, 60Hz)
4000
245 E1
1/3
1050
50 (40kA, 60Hz)
4000
362 E2
1175 (+205)
50
4000
420 E2
1425 (+240)
50
4000
550 E2
1550 (+315)
50
4000
PTPH/HV - Page 18
Options:
COMPOSITE INSULATORS
CT BRACKETS UP TO 170 kV
PTPH/HV - Page 19
Product
Range
HPL B1
72,5 300 kV
63 kA
4000 A
PTPH/HV - Page 20
Technology
HPL B1
PTPH/HV - Page 21
Product
Range
HPL B2
362 550 kV
63 kA
4000 A
Spring operated
PTPH/HV - Page 22
Technology
HPL B4
800 kV
50 / 63 kA
4000 A
Spring operated
PTPH/HV - Page 23
References
Type HPL
Product
Range
Breaker
Type
HPL
Type of operation
(Single/Three Phase)
Insulation Level
LIWL
(kV)
Breaking
Current
(kA)
Normal
Current
(A)
72.5 B1
1/3
325
63
4000
145 B1
1/3
650
63
4000
170 B1
1/3
750
63
4000
245 B1
1/3
1050
63
4000
300 B1
1/3
1050 (+170)
63
4000
362 B2
1175 (+205)
63
4000
420 B2
1425 (+240)
63
4000
550 B2
1550 (+315)
63
4000
800 B4
2100 (+455)
63
4000
PTPH/HV - Page 24
Options:
COMPOSITE INSULATORS
CT BRACKETS UP TO 170 kV
Advantages
Composite Insulators
Non-brittle
Low weight
PTPH/HV - Page 25
Easier handling
Reduced foundation loads
Excellent seismic withstand
Silicon Rubber
Insulation
Flashover resistant
Ageing withstand
UV stability
PTPH/HV - Page 26
Composite
Insulators
Earthquake
PTPH/HV - Page 27
Installation
PTPH/HV - Page 28
Hove, Denmark
CB LTB
PTPH/HV - Page 29
Maintenance
PTPH/HV - Page 30
Maintenance
Operating Mechanism
Operating test
PTPH/HV - Page 31
Operating times
Corrosion, Lubrication
Spare
Parts
PTPH/HV - Page 32
Application
PTPH/HV - Page 33
Application
PTPH/HV - Page 34
Application
L183
PTPH/HV - Page 35
More information
Further information about controlled switching applications and
Switchsynccontrollers is found in Controlled Switching, Buyers
Guide/Application Guide.
Application
PTPH/HV - Page 36
Switchsync
Controller
Main Application
Controls
Circuit Breaker
Operation
Circuit Breaker
Operation
E113
Open or Close
Three-pole
E213
Three-pole
F236
Single-pole
T183
Transformers
Close
Single-pole
L183
Uncompensated
Transmission Lines
Close
Single-pole
Switchsync
PTPH/HV - Page 37
Higher availability
Longer life time
Simple, self monitoring electronic device
Reduced stresses on system components
(e.g. transformers, reactors and circuit breaker)
Lower system operating cost
Monitoring
Times
Currents
Contact
Travel
Speed, Over-travel, Damping
Motor
Current
Incl. Spring Charging Time
SF6-Density
PTPH/HV - Page 38
Optional
Measuring
Accessories
PTPH/HV - Page 39
Flexibility
Identically the same standard and well proven LTB/HPL circuit breaker is used in all applications
LTB Withdrawable
Circuit Breaker
LTB Disconnecting
Circuit Breaker
PTPH/HV - Page 40
LTB Conventional
Flexibility
Identically the same standard and well proven LTB/HPL circuit breaker is used in all applications
PTPH/HV - Page 41
HPL Conventional
HPL Disconnecting
Circuit Breaker
Product range
Breaker
Type
Type of
operation
(Single/Three
Phase)
Insulation Level
LIWL
(kV)
Breaking
Current
(kA)
Normal
Current
(A)
LTB 145 D1
650
40
3150
HPL 170 B1
1/3
750
50
4000
HPL 245 B1
1/3
1050
50
4000
HPL 300 B1
1/3
1050 (+170)
50
4000
HPL 420 B2
1425 (+240)
63
4000
PTPH/HV - Page 42
Options:
CT BRACKETS UP TO 170 kV
Product range
Breaker
Type
Type of
operation
(Single/Three
Phase)
Insulation Level
LIWL
(kV)
Breaking
Current
(kA)
Normal
Current
(A)
LTB 145 D1
650
40
3150
LTB 245 E1
1050
50
4000
HPL 245 B1
1050
50
4000
HPL 300 B1
1050 (+170)
50
4000
PTPH/HV - Page 43
Options:
COMPOSITE INSULATORS
PTPH/HV - Page 44
World Class
Production
Environment
PTPH/HV - Page 45
ISO 9001
ISO 14001
PTPH/HV - Page 46