Catalogue
2005
Web enabled
Power & Control
MCset
MCset range
1 to 17.5 kV
Contents
Presentation
MCset range
Presentation
Technical characteristics
Operating conditions
Protection of people
Motor protection and control
Choice of functional units
8
8
10
11
12
13
14
Cubicle description
AD type cubicles incomer and feeder
CL - GL type cubicles line-up bussectioning
TT type cubicles metering and busbar earthing
DI type cubicles switch-fuse feeder
Motorpact transition cubicle
16
16
17
18
19
20
22
22
23
24
26
28
Switchgear
Withdrawable parts
32
32
Evolis circuit-breaker
Vacuum type contactor
34
38
40
Installation
Implementation examples
Connections
41
41
42
Appendices
Cubicle equipment
Current transformers (Selection guide)
44
44
45
A few references
46
Personal notes
47
Presentation
Field of application
MT20051
MT20052
The MCset offer is further enhanced to include a vacuum type circuitbreaker (Evolis range) and contactor.
This switchgear offers you:
b high mechanical and electrical endurance;
b a comprehensive range of performance levels;
b optimal operating safety;
b environmental protection.
Presentation
MT20058FR
Reliability
b type testing was carried out for each performance level in the MCset range;
b the design, manufacturing and testing of MCset was carried out
according to ISO 9001 : 2000 quality standard;
b three-dimensional computer modeling techniques were used to study
the electrical fields.
MT20059
Simplicity
b a user interface which is easily understood by everybody;
b interlocks and padlocks preventing operator errors;
b Sepam-type protection units enabling on-site information retrieval
without any additional devices;
b maintenance limited to simple, routine operating checks and cleaning
and greasing every 5 to 10 years;
b easy installation due to identical civil engineering dimensions for
all cubicles and installation being possible against a wall.
Safety
b operations are all performed from the front, including access to
connections and busbars;
b racking in and out is only possible with the door closed;
b the power-on indicator is situated on the front of the functional unit;
b the earthing switch has making capacity;
b one single "anti-reflex" handle is used for all MCset operations;
b internal arc withstand developed for all functional units.
Presentation
MCset provides the most efficient means to control and protect a wide
range of applications.
Due to the devices it comprises, MCset can be easily integrated into a
monitoring and control system.
Sepam series 20, series 40 and series 80 digital protection relays take full
advantage of Merlin Gerin experience in electrical network protection.
Sepam series 20, series 40 and series 80 provides all the necessary
functions:
b effective protection of people and property;
b accurate measurements and detailed diagnosis;
b integral equipment control;
b local or remote indication and operation.
Easy evolution
Addition of communication, digital I/Os, analog output, or temperature
acquisition are possible due to its modular design.
PE55134
Presentation
DE55465
PE55137
Hub
Front socket
EGX400
Simple choice
A simple choice between TRe-1 and TRe-2 service levels allows you to
easily order your Transparent Ready Motorpact switchboard.
A customized level is also available.
Your Transparent Ready MCset switchoard comes equipped with a web
server including web pages dedicated to power equipment data.
Sepam
Sepam
CM/PM
MCset switchboard
Easy commissioning
Transparent Ready equipment is delivered ready to connect and
commission.
A Quick Start guide, packaged with your switchboard, provides three
easy-to-follow steps.
PE55140
PE55139
PE55138
Functionalities provided
Instantaneous readings
Displays automatically updated meter values
TRe-1 TRe-2
b
b
Circuit summary
Displays the RMS current 3-phase average (A),
the real power (kW), the power factor, the circuit-breaker
status (if applicable), etc.
Power summary
Displays the present demand (kW), the peak demand (kW)
and the times and dates of the records
Energy summary
Displays the energy (kWh) the reactive energy (kvarh)
and the times and dates of the records
Log displays
Displays data as time curves, or tables
Presentation
(contd)
Specifying
Modernizing
Specifying
Implementing
We oversee the completion and commissioning of your installation:
design, cost optimization, guaranteed performances and dependability,
commissioning tests, etc.
Operating
Operating
Implementing
Modernizing
We can bring the performance of your installation up to date:
installation audit, switchgear diagnosis, adaptation and modification,
end of life recycling, etc.
MT20065FR
Warranty extension
A warranty extension is proposed if your installation is checked
by ourselves before being commissioned.
Circuit-breaker-contactor diagnosis
Throughout the life of the equipment, it is possible to carry out routine
measurement of its characteristics in order to optimize maintenance.
This service may be part of a global installation maintenance contract.
End-of-life recycling
Schneider Electric Services has an operational subsidiary allowing you
to recycle your medium voltage switchgear.
Presentation
MT20066
MT20068
MT20067
MT20069FR
Protected environment
In order to help you protect the environment and to relieve you of any
concerns about storing or dismantling this equipment, Schneider Electric
Services offers to recover your equipment at the end of its life.
MCset has been designed with environmental protection in mind:
the materials used, insulators and conductors are identified,
easily separable and recyclable.
Production sites are certified to ISO 14000.
Presentation
PE60120
MCset range
Busbars
Low voltage
control cabinet
Sepam
Circuit-breaker
Current
transformers
Cables connection
Voltage
transformers
compartment
MCset range
Presentation
(cont.)
The cubicle
The cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by
IEC standard 62271-200, in other words the medium voltage parts are
compartmented using metal partitions (PM class) which are connected to earth and
which separate:
b the busbars;
b the withdrawable part (circuit-breaker, fuse-contactor, disconnector truck or
earthing truck);
b MV connections, earthing switch, current sensors and voltage transformers as
required.
MCset guarantees a high level of protection of people; when a compartment
containing a main circuit is open, the other compartments and/or functional units may
remain energised.
The low voltage auxiliaries and monitoring unit are in a control cabinet separated
from the medium voltage section.
Four basic cubicle layouts are offered:
b incomer or feeder
AD
b line up bussection
CL - GL
b busbar metering and earthing
TT
b switch-fuse feeder
DI
AD and CL cubicles have withdrawable vacuum type circuit-breaker and contactor
switchgear.
MCset range
Technical characteristics
MT20071
The values below are given for normal operating conditions as defined in
IEC 62271-200 and 60694.
Rated voltage (kV)
7.2
12
17.5
28
75
38
95
rated current
rated current
(kA/1 s)
In max. busbar (A)
In CB
(A)
25
31.5
40
40
2500
630
1250
2500
25
31.5
40
40
2500
630
1250
2500
25
31.5
40
40
2500
630
1250
2500
50 (2)
50 (2)
31.5 (2)
200
200
200
50 (2)
250
25 to 40
10
MCset range
Operating conditions
MT20073
MT20072
Operating conditions
Normal operating conditions, according to IEC 60694 for indoor switchgear
b ambient air temperature:
v less than or equal to 40C,
v less than or equal to 35C on average over 24 hours,
v greater than or equal to -5C.
b altitude:
v less than or equal to 1000 m,
v above 1000 m, a derating coefficient is applied (please consult us).
b atmosphere:
v no dust, smoke or corrosive or inflammable gas and vapor, or salt
(clean industrial air).
b humidity:
v average relative humidity over a 24 hour period y 95%,
v average relative humidity over a 1 month period y 90%,
v average vapor pressure over a 24 hour period y 2.2 kPa,
v average vapor pressure over a 1 month period y 1.8 kPa.
Specific operating conditions (please consult us)
MCset has been developed to meet the following specific conditions:
b temperature (possible derating);
b corrosive atmospheres, vibrations, (possible adaptation).
Storage conditions
In order to retain all of the functional units qualities when stored for prolonged
periods, we recommend that the equipment is stored in its original packaging,
in dry conditions sheltered from the sun and rain at a temperature of between
25C and +55C.
Standards
The MCset range meets the following international standards:
IEC 60694: clauses common to high voltage switchgear
IEC 62271-200 (60298): metal-enclosed switchgear for alternating current at rated
voltages of between 1 and 52 kV
IEC 62271-100 (60056): high voltage alternating current circuit-breakers
IEC 60470: high voltage alternating current contactors
IEC 60265-1: high voltage alternating current switches
IEC 60282-2: high voltage fuses
IEC 62271-102 (60129): alternating current disconnectors and earthing switches
IEC 60255: measurement relay and protection unit (Sepam)
IEC 60044-1: current transformers
IEC 60044-2: voltage transformers.
11
MCset range
Protection of people
MT20076
MCset
Basic version (gas exhaust): MCset is designed to eliminate the effects of internal
arcing in total safety, due to:
b metal flaps positioned above the enclosure, which in the case of internal fault,
limit overpressure in the compartments.
b nonflammable materials used for the cubicle.
MT20077
All operations are carried out from the front face, including access to connections and
busbars.
The user is guided through icon-diagrams on each front panel making it easy
to understand the operating sequence and device status.
Interlocks and padlocks prevent operator errors.
Several additional levels of security also protect operators:
b racking in and out is only possible with the door closed;
b the very extensive set of mechanical and electrical interlocks do not allow operator
error. These can be added to by key locks or padlocks according to specific operating
procedures. Each selector can be fitted with one to three padlocks;
b all operations are carried out from the front face, including access to connections
and busbars;
b the voltage present indicator is located on the front face of the functional unit,
in the immediate vicinity of the earthing switch control.
Options
b disarming of circuit-breaker when racking out. This function enables
the circuit-breaker control springs to be disarmed during the extraction
operation.
b disabling of racking in. This function disables the possibility of racking
the withdrawable part in if the busbar is energized.
12
MCset range
PE60122
DE60175
b They are suitable for all MV motor applications in markets such as: oil & gas,
mining, water, pulp and paper, for starting:
b pumps,
b fans,
b compressors,
b crushers,
b conveyors, etc.
Compactness
b Compact dimensions thanks to a 375 mm width.
b Softarter and Autotransfo built into the switchboard.
Safety
b Full cubicle protection for internal arc withstand (AFLR 4 sides).
b Electrical and mechanical interlocking, closed door operation.
b Visible insulation by means of portholes
Reliability
b Fewer components and fasteners.
Less maintenance
b Corrosive atmosphere withstand.
b Maintenance free disconnector (capacity: 5000 operations).
b Front access to compartments.
13
MCset range
Function
Incomer (1)
Feeder
line
transformer
generator
line
transformer
transformer
Functional unit
LI-B
TI-B
GI-B
LF-B
TF-B
TF-S
cubicle
AD (1 to 3)
AD (1 to 3)
AD (1 to 3)
AD (1 to 3)
AD (1 to 3)
DI 2
device
circuit-breaker
circuit-breaker
circuit-breaker
circuit-breaker
circuit-breaker
fuse-switch
substation
transformer
generator
substation
transformer
Sepam
protection relay
application
MT20082
Sepam
MT20081
MT20080
(1) The direct incomer (functional unit without a circuit-breaker, equipped with a fixed
busbar bridge) is produced using cubicles AD1-2-3.
14
MCset range
(cont.)
motor
motor
capacitor
capacitor
switchboard
substation
MF-B
MF-C
CB-B
CB-C
BS-B
SS-B
BB-V
AD (1 to 3)
AD1
AD (1 to 3)
AD1
AD (1 to 3)
TT (1-2)
circuit-breaker
fuse-contactor
circuit-breaker
fuse-contactor
CL (1 to 3) and
GL (1 to 3)
circuit-breaker
motor
motor
capacitor
capacitor
busbar
substation
MT20081
MT20083
MT20084
DE55076
Metering
and busbar
earthing
MT20083
Bussectioning
MT20081
Motorpact
transition
MT20078
circuit-breaker
DE60167
Feeder
15
AD type cubicles
incomer and feeder
Cubicle description
DE60168
DE55082
DE55081
7
2
5
4
6
3
L
L
AD2
MV compartments
1 busbars for cubicle interconnection
2 withdrawable part
3 MV connections by cables accessible from the front face
4 earthing switch
5 current sensors
6 voltage transformers (optionally equipped with withdrawable fuses).
DE55083
AD1
LV control cabinet
7 low voltage auxiliaries and the protection, monitoring and control unit
are in a control cabinet which is separated from the medium voltage part.
L
AD3
Characteristics
AD
1
rated voltage
rated insulation level
kV
kV rms 50 Hz - 1 mn
kV impulse 1.2/50 s
rated current
A
250
630
1250
2500
breaking capacity
kA
short time withstand current (kA rms 1 s)
short time withstand current (kA rms 3 s)
weight and dimensions
H (mm)
W (mm)
D (mm) (1)
approximate
weight (kg) (2)
AD1
contactor
7.2
20
60
12
28
75
b
b
b
b
25
25
25
25
25
25
2300
570
1550
850
7.2
20
60
b
50 (3)
50 (3)
50 (3)
AD
2
AD
3
7.2
20
60
12
28
75
17.5
38
95
b
b
b
b
b
b
31.5 31.5 25
31.5 31.5 25
31.5 31.5 25
2300
700
1550
1000
7.2
20
60
b
b
b
31.5 25
31.5 25
31.5 25
2300
900
1550
1300
12
28
75
b
b
b
b
31.5 40
31.5 40
31.5 40
b
25
25
25
17.5
38
95
b
b
b
b
31.5 40
31.5 40
31.5 40
b
25
25
25
b
b
b
b
31.5 40
31.5 40
31.5 40
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CTs.
(2) Fully equipped cubicle.
(3) Limited by fuses.
16
CL - GL type cubicles
line-up bussectioning
Cubicle description
1
6
3
DE60170
DE60169
DE55087
2
H
4
L
CL1-2-3 or GL1-2-3
MV compartments
1 busbars to connect the bussectioning functional unit with other switchboard
functional units
2 withdrawable part
3 current sensors
4 voltage transformers (optionally equipped with withdrawable fuses).
LV control cabinet
5 low voltage auxiliaries and protection, monitoring and control unit
are in one control cabinet, separated from the medium voltage part.
Characteristics
CL1 - GL1 CL2 - GL2
rated voltage
rated insulation level
kV
kV rms 50 Hz - 1 mn
kV impulse 1.2/50 s
rated current
A
630
1250
2500
breaking capacity
kA
short time withstand current (kA rms 1 s)
short time withstand current (kA rms 3 s)
weight and dimensions
H (mm)
W (mm)
D (mm) (1)
approximate
weight (kg) (2)
CL3 - GL3
7.2
20
60
12
28
75
7.2
20
60
12
28
75
17.5
38
95
b
b
b
b
b
b
b
b
b
b
25
25
25
25
25
25
2300
570 (x 2)
1550
1300
(CL1 + GL1)
31.5 31.5 25
31.5 31.5 25
31.5 31.5 25
2300
700 (x 2)
1550
1500
(CL2 + GL2)
7.2
20
60
b
b
31.5
31.5
31.5
b
b
25
31.5
25
31.5
25
31.5
2300
900 (x 2)
1550
1700
(CL3 + GL3)
12
28
75
b
b
b
40
40
40
b
25
25
25
17.5
38
95
b
31.5
31.5
31.5
b
b
b
40
40
40
b
25
25
25
b
31.5
31.5
31.5
b
b
b
40
40
40
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CTs.
(2) Fully equipped cubicle.
17
TT type cubicles
metering and
busbar earthing
Cubicle description
1
4
DE60171
DE55094
DE55093
TT1, TT2
2
3
L
TT1
TT2
MV compartments
1 busbars to connect the TT functional unit with other switchboard cubicles
2 earthing switch
3 voltage transformers (optionally equipped with withdrawable fuses).
LV control cabinet
4 low voltage auxiliaries and the protection, monitoring and control unit
are in a control cabinet which is separate from the medium voltage part.
Characteristics
TT1
rated voltage
rated insulation level
kV
kV rms 50 Hz - 1 mn
kV impulse 1.2/50 s
rated current
A
630
1250
2500
short time withstand current (kA rms 1 s)
short time withstand current (kA rms 3 s)
weight and dimensions
H (mm)
W (mm)
D (mm) (1)
approximate
weight (kg) (2)
7.2
20
60
b
b
b
31.5
31.5
2300
570
1550
500
TT2
12
28
75
b
b
b
7.2
20
60
b
b
b
50
50
2300
700
1550
550
18
12
28
75
b
b
b
50
40
17.5
38
95
b
b
b
31.5
31.5
b
b
b
40
40
DI type cubicles
switch-fuse feeder
Cubicle description
4
1
DE60172
DE55098
DI2
L
DI2
MV compartments
1 busbars to connect the DI functional unit with other switchboard cubicles
2 switch-earthing switch
3 MV fuses.
LV control cabinet
4 low voltage auxiliaries and the protection, monitoring and control unit
are in a control cabinet which is separate from the medium voltage part
Characteristics
DI2
rated voltage
rated insulation level
kV
kV rms 50 Hz - 1 mn
kV impulse 1.2/50 s
rated current
A
200
short time withstand current (kA rms) (3)
weight and dimensions
H (mm)
W (mm)
D (mm) (1)
approximate
weight (kg) (2)
7.2
20
60
b
50
2300
700
1550
750
12
28
75
b
50
17.5
38
95
b
31.5
MT20093
Switch
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.04 MPa (0.4 bar).
The system offers maximum operating reliability:
b gas tightness
The SF6 filled enclosure is of the "sealed pressure system type".
Sealing tightness is always checked in the factory.
b safety
v the switch may be in one of three positions: "closed", "open", or "earthed",
giving a natural interlocking system that prevents operator error.
Moving contact rotation is driven by a fast acting mechanism that is independent
of the operator.
v the device combines the breaking and disconnecting functions,
v the SF6-enclosed earthing switch has a short circuit making capacity
in compliance with standards.
19
DE60174
DE60176
Cubicle description
Composition
b Basic equipment:
v 1 enclosure (standard IP3X),
v 1 set of busbars in separate compartment,
v 1 removable front panel.
b
v
v
v
Options
internal arc withstand,
IP4X or IPX1 enclosure,
encapsulated busbars.
Characteristics
maximum rated voltage
impulse withstand voltage (1.2/50 s, peak value)
power frequency withstand voltage (1 mn)
busbars rating
dimensions
approximate weight
20
21
Protection, monitoring
and control
Thermal diagnosis
MT20119
PE55160
Components
The thermal diagnosis system comprises the following components:
b 1 or 2 modules mounted in the low voltage control cabinet;
b 3 -point temperature probes (spread over the 3 phases) can be installed
in various monitored zones:
v 3 sensors in the busbar compartment,
v 3 sensors in the cable connector compartment,
v 3 sensors in the switchgear compartment;
b fibre optic links to transmit the signal.
22
Protection, monitoring
and control
MT20094
protection relays
metering equipment
switchgear (circuit-breaker or
contactor)
instrument transformers
PE55170
Sepam advantages
Reliability
b Over 20 years of experience in multi-function digital protection relays.
b Over 150 000 Sepam units in service in more than 90 countries.
Quality
b Quality design based on dependability studies and strict definition of
environmental constraints: temperature, pollution, EMC, dielectric strength
b Quality manufacturing based on procurement agreements with suppliers and
inspection throughout all manufacturing phases.
Simplicity of use
b Ergonomic and intuitive user machine interface (UMI).
b User friendly and powerful PC setting software.
23
Protection, monitoring
and control
Sepam 2000
Sepam 100
0
The Sepam 2000 range of digital protection, monitoring and control units
provides a comprehensive solution for all applications: substation, busbar,
transformer and motor, as well as generators and capacitors.
Different types of Sepam 2000 ddis la protection are proposed for each type of
equipment to be protected.
For example, there are 30 different types of Sepam 2000 dedicated to protection,
monitoring and control of transformers.
Each Sepam 2000 is an optimized solution, designed to provide an exact response
to the actual requirements of a functional application, including all the required
functions, ready to use.
Sepam 2000
E61780
PE60118
PE60117
PE60116
Sepam 100MI
24
Sepam 100LD
Sepam 100LA
Protection, monitoring
and control
Sepam 2000
selection table
Fonctions
Sepam 2000
Measurements
currents
Applications
Substation busbar
Transformer Motor
Generator
Capacitor
I1/I2/I3/I0
IM1/IM2/IM3
Itrip 1/2/3/0
U21/U32/U13
V1,V2,V3
V0
Vd
f
P/Q, PM/QM, cosM
Ea/Er
b
b
b
b
b
67N
87M
b
b
b
b
87M
b
b
49
27/59
ANSI codes
50/51
50N/51N
46
67/67N
87T/87M/87B
64REF
49/49T/38
37/48/51LR/66
59/27
59N
81H/81L
81R
Network diagnosis
disturbance recording
Switchgear diagnosis
operation time
trip currents, sum of breaking currents A2
trip circuit monitoring
watchdog
Communication
protocol
interface
Monitoring and control
inputs/outputs
basic
maximum
breaking device control
logical selectivity
customizing
parameter setting
programming
b
b
b
b
b
87T
b
b
b
b
32P
79
27R
b
b
25
27D
b
b
b
b
b
50N/51
(neutral point)
50/51
(tank earth)
27R
32P and
32Q/40
27D/47
32P, 32Q/40
25
50V/51V
cap. bank
imbalance
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
2 recording of 86 periods
b
b
b
b
b
b
1output/4 contacts: 2 x (1NO + 1NC)
Modbus
RS485, 2 or 4 wire
10I/6O in/out
26I/14O in/out
b
b
b
b
b
b
b
b
b
b
b
b
b available functions
25
PE55170
Protection, monitoring
and control
7
6
Simplicity
Easy installation
b The same, easy-to-install remote modules for all Sepam units.
Commissioning assistance
b Predefined functions implemented by simple parameter setting;
b user-friendly, powerful PC setting software tool.
Intuitive use
b Clear graphic LCD display of all data required for local operation and installation
diagnosis;
b working language may be customized to be understood by all users.
26
Protection, monitoring
and control
Sepam
Protections
DE50114
Sepam series 20
b 10 logic inputs
b 8 relay outputs
b 8 temperature probe
inputs
b 1 Modbus
communication port
DE50113
Basic
Specific
Current
protection
Applications
Substation
Transfo.
Motor
S20
T20
M20
Generator
B21
Voltage
and
frequency
protection
DE50115
DE50116
Sepam series 80
b 42 logic inputs
b 23 relay outputs
b 16 temperature probe
inputs
b 2 Modbus
communication port
b Logic equations editor
DE50104
Loss of mains
(ROCOF)
Sepam series 40
b 10 logic inputs
b 8 relay outputs
b 16 temperature probe
inputs
b 1 Modbus
communication port
b Logic equations editor
Busbar
B22
S40
Current
voltage and
frequency
protection
Directional
earth fault
S41
Directional
earth fault
and phase
overcurrent
S42
Current
voltage and
frequency
protection
T40
G40
M41
T42
S80
Directional
earth fault
S81
T81
Directional
earth fault
and phase
overcurrent
Transformer
or machinetransformer
differential
Machine
differential
S82
T82
T87
M81
G82
M88
G88
M87
G87
27
Protection, monitoring
and control
Instrument transformers
E28676
10
20
1.2
2.4
1
1
15 VA
2.5 VA
30
3.6
1
50
6
1
75
10
1
100
10
1
150
10
1
200
10
1
250
10
1
ARJP1, 2 or 3
75-150
40
1
100-200
31.5-40
1
5-10VA
2.5-5VA 2.5-5VA
150-300
40
1
10-20 VA
2.5-5VA
200-400
40
1
7.5-15VA
5-10VA
250-500
40
1
10-20 VA
5-10VA
600
50
1
20VA
7.5VA
750
50
1
20VA
7.5VA
1250
50
1
30 VA
10 VA
E74399
2000
50
1
30 VA
15 VA
2500
50
1
30 VA
15 VA
ARJA1
* The secondary current for measuring and protection can be of 1 A or 5 A.
28
Protection, monitoring
and control
Instrument transformers
(cont.)
E72965
5P20
75
50
1
2.5 VA
100
50
1
2.5 VA
150
50
1
5 VA
200
50
1
5 VA
250
50
1
5 VA
300
50
1
5 VA
400
50
1
5 VA
200
50
1
5 VA cl.1
2.5 VA
250
50
300
50
400
50
600
50
10 VA cl.0.5
5 VA
10 VA cl.0.5
5 VA
15 VA cl.0.5
5 VA
15 VA cl.0.5
5 VA
750
50
1
20 VA
7.5 VA
1000
50
1250
50
30 VA
10 VA
30 VA
10 VA
E34400
CSP sensor
CSP type current sensors, designed for the Sepam 2000, work on the Rogowski
coil principle.
CSP sensors use a winding around an insulating core with no magnetic circuit, which
prevents saturated and residual flux.
Therefore, they are completely linear, and deliver an accurate secondary signal,
a perfect image of the primary current, without distortion for both steady and transient
states in the primary circuits. These sensors have much wider primary current ranges
than current transformers do.
The combining of CSP sensors and Sepam 2000 gives a consistent protection
and measurement system. This in turn makes current sensor specification simpler
(choosing from 3 sensors for a rated insulation level of 17.5 kV).
Sensors
Rated current
CSP 3110
CSP 3210
CSP 3310
CSP 3410
30 to 300 A
160 to 640 A
160 to 1600 A
500 to 2500 A
For Sepam 2000, the primary current is chosen to be lower than the indicated range.
Cubicle type
AD1 - AD2
AD1 - AD2
CL1 - CL3
AD3 - CL3
I rated
Isc (kA) 1 s
Type
30 - 300
160 - 1250
40
50
500 - 2500
50
CSP 3110
CSP 3310
CSP 3210
CSP 3410
29
Protection, monitoring
and control
Instrument transformers
(cont.)
Voltage transformers
These supply power to:
b measuring, metering and monitoring devices;
b relays or protective devices;
b auxiliary LV sources for various types of switchgear; all these devices are protected
and insulated from the MV section.
They are installed at the bottom of the functional unit. In the withdrawable fuse version,
the voltage transformers are attached to a side wall. The energized part is entirely
encapsulated in an epoxy resin, which provides both electrical insulation and
excellent mechanical strength.
They include the following models:
b with one insulated MV terminal, for connection between neutral and phase
conductors in three-phase systems with withdrawable MV fuses;
b with two insulated MV terminals, for connection between phase conductors.
Transformer VRQ3n/S2
b phase-earth
b frequency 50-60 Hz
VRQ3
primary voltage
(kV)
1st secondary
voltage (V)
2nd secondary
voltage (V)
1st secondary
accuracy class
(VA)
2nd secondary
accuracy class
(VA)
3/3
6.6/3 10/3
11/3
13.8/3 15/3
50 VA cl.0.5
Transformer VRC1/S1F
b phase-phase
b frequency 50-60 Hz
primary voltage (kV)
secondary voltage (V)
accuracy class (VA)
VRC1/S1F
30
3.3
5.5
110
110
75 VA cl.0.5
6.6
110
11
110
13.8
110
15
100
Protection, monitoring
and control
Instrument transformers
(cont.)
Transformer VRCR/S1
b phase-phase
b frequency 50-60 Hz
primary voltage (kV)
secondary voltage (V)
accuracy class (VA)
3.3
110
50 VA cl.0.5
5.5
110
6.6
110
VRCR
E28678
CSH toroid CT
CSH 120 and CSH 200 core balance CTs, provide more sensitive protection
by direct measurement of earth fault currents.
Specifically designed for the Sepam range, they can be directly connected to
the Sepam "residual current" input.
They are only different in terms of their diameter:
b CSH 120 - 120 mm internal diameter;
b CSH 200 - 200 mm internal diameter.
31
Switchgear
Withdrawable parts
PE55048
Withdrawable
part
Extraction
table
32
Switchgear
Withdrawable parts
(cont.)
hese include:
b the circuit-breaker or contactor, the disconnector truck or the earthing truck;
b the lever-type propulsion mechanism for racking in-out;
b interlocks to fix the withdrawable parts onto the fixed part.
The live parts are housed in an insulating enclosure in the sealed pressure system
in compliance with IEC 6271-100.
The devices used to equip the MCset range of functional units have outstanding
features:
b long service life;
b maintenance-free live parts;
b high electrical endurance;
b operating safety;
b insensitivity to the environment.
Withdrawable parts
MT20101
Circuit-breaker
A circuit-breaker is a safety device enabling switching and protection of electrical
distribution networks. Installed in the MCset cubicle, it protects all components
situated downstream during a short-circuit.
MT20102
Earthing truck
The earthing truck is a safety feature which allows the cubicle busbar to be earthed.
It is installed instead of the circuit-breaker and has the same interlock possibilities.
MT20103
Disconnector truck
The disconnector truck enables the upper and lower part of the cubicle to be shortcircuited. It is installed instead of the circuit-breaker and has the same interlock
possibilities.
33
Switchgear
Withdrawable parts
Evolis circuit-breaker
0
Presentation
MT20105
MT20106
xx Px xxxx
Rated current:
630 (630 A)
1250 (1250 A)
2500 (2500 A)
Breaking capacity:
1 (P1 = 25 kA)
2 (P2 = 31.5 kA)
3 (P3 = 40 kA)
Rated voltage:
7 (7.2 kV)
12 (12 kV)
17 (17.5 kV)
E.g. (in grey in the table): 7 P1 630 (7.2 kV; 25 kA; 630 A)
rated voltage
insulation level
rated current
breaking capacity
short time withstand current
short time withstand current
capacitor breaking capacity
rated operating sequence
34
kV
kV rms 50 Hz - 1 mn
kV impulse 1.2/50 s
A
630
1250
2500
kA
kA rms 1 s
kA rms 3 s
A
Evolis/
MCset 1
Evolis/
MCset 2
7.2
20
60
12
28
75
7.2
20
60
12
28
75
17.5
38
95
b
b
b
b
b
b
b
b
b
b
25
25
25
400
25
25
25
31.5 31.5 25
31.5 31.5 25
31,5 31.5 25
400
O - 0.3 s - FO - 15 s - FO
Evolis/
MCset 3
7.2
20
60
b
b
b
31.5 25
31.5 25
31.5 25
400
12
28
75
b
b
b
b
31.5 40
31.5 40
31.5 40
b
25
25
25
17.5
38
95
b
b
b
b
31.5 40
31.5 40
31.5 40
b
25
25
25
b
31.5
31.5
31.5
b
40
40
40
Switchgear
Withdrawable parts
Evolis circuit-breaker (cont.)
0
MT20108
General diagram
opening
order
closing
order
ready
to close
closed
MCH
PF
MX
OF
OF
OF
XF
CH
35
Switchgear
Withdrawable parts
Evolis circuit-breaker (cont.)
0
The MCH unit arms and rearms the energy storage springs as soon as the circuitbreaker is closed. This enables instant reclosing of the device after opening.
The arming lever is only used as back up control in the absence of an auxiliary
voltage.
The MCH is equipped as standard with a CH limit switch.
This contact indicates the "armed" position of the mechanism (spring armed).
Characteristics
supply
V AC 50/60 Hz
V DC
threshold
consumption (VA or W)
motor overcurrent
arming time
switching rate
mechanical endurance
CH contact
48/60
100/130
200/240
24/30
48/60
100/125
200/250
0.85 to 1.1 Un
180
2 to 3 In during 0.1 s
4 s max.
3 cycles per minute max.
10000 remote controlled opening operations
for 25 and 31.5 kA circuit-breaker
5000 remote controlled opening operations
for 40 kA circuit-breaker
10 A to 240 V
24/30
48/60
24/30
48/60
0.7 to 1.1 Un
0.85 to 1.1 Un
pick-up: 200
latched: 4.5
50 ms 10
100/130
100/130
200/250
200/250
MT55169
The switching operation counter is visible from the front panel. It gives a total number
of switching cycles that the device has been through.
MT55168
MT55180
PF contact
V AC
V DC
240/380
5A
24/48
3A
125
0.3 A
250
0.15 A
minimum load: 10 mA/24 V
PAF contact
36
V AC
V DC
220
220
16 A
16 A (cos M: 0.4)
0.8 A (L/R y 40 ms)
Switchgear
Withdrawable parts
Evolis circuit-breaker (cont.)
0
MT55164
V AC 50/60 Hz
V DC
operating
opening
threshold
closing
consumption (VA or W)
response time
of the circuit-breaker at Un
24/30
48/60
24/30
48/60
0.35 to 0.7 Un
0.85 Un
20
90 ms 5
100/130
100/130
200/250
200/250
MT55170
V AC 50/60 Hz
V DC
operating
opening
threshold
closing
consumption (VA or W)
response time
of the circuit-breaker at Un
48/60
48/60
100/130
100/130
200/250
200/250
0.35 to 0.7 Un
0.85 Un
200
0.5 s - 0.9 s - 1.5 s - 3 s
MT55167
standard
low level
V AC
V DC
240/380
6A
24/48
2.5 A
125
0.5 A
250
0.3 A
minimum load: 10 mA/24 V
V AC 24/48
240
5A
380
5A
V DC 24/48
5/2.5 A
125
0.5 A
250
0.3 A
minimum load: 1 mA/4 V
10/6
10/6
10/6
3
10/6
3
10/6
10/6
3
37
Switchgear
Withdrawable parts
Vacuum type contactor
0
Description
MT20107
kV (50/60 Hz)
kV, rms 50 Hz - 1 mn
kV, impulse 1.2/50 s
operating current
A
rated current
A
short time withstand current (kA rms 2 s)
short time withstand current (kA rms 12 s)
short time withstand current (kA rms 30 s)
mechanical endurance (number of operations)
electrical endurance (number of operations)
(1) For greater values: please consult us.
(2) Version with mechanical latching.
7.2
20
60
250 (1)
400
8
4
2.4
2 500 000
250 000
Control unit
Supply voltage (3)
V DC: 110, 120 and 220 V
V AC: 100, 110, 120 and 220 V
possible variations: +10% -15%
(3) Possibility of supplying power through an auxiliary transformer, optional (see page 31).
Consumption
Closing is achieved via the inrush coils.
The latching coils are inserted in the circuit at the end of travel.
under 100-110 V
inrush
with magnetic latching
5A
with mechanical latching
5.5 A
latched
0.6 A
Auxiliary contacts
The auxiliary contacts are of changeover type with a common point.
The following are available :
v 3 NO + 3 NC for the magnetic latching version,
v 2 NO + 2 NC for the mechanical latching version.
Contact characteristics
operating voltage
rated current
breaking capacity:
38
Switchgear
Withdrawable parts
Vacuum type contactor
0
(cont.)
E32151
E32130
Figure 1
Figure 2
Transformer
(kVA)
with 315 A fuses
1130
1420
1710
1880
2050
2250
Capacitor
(kvar)
with 315 A fuses
1000
1260
1520
1670
1820
2000
Fuses
The fuses used are of the Fusarc CF or Ferraz type (Standard IEC 60282.1
and DIN 43625) with high breaking capacity.
Substantial fault current limitation reduces the electrodynamic stresses on
the load-side components (contactor, cables, CT, etc).
A "blown fuse" device is used to open the three poles of the contactor.
Trip curves
The trip curves for Fusarc CF (figure 1) and Ferraz (figure 2)
fuses are shown above.
These are the average curves with an rms current value
tolerance I 10%.
7.2
315*
50
E32131
Schematic diagrams
Figure 3
+C
M1
MT20110
Sepam
S4
verrouillage
enclenchement
closing
interlock
XE
XE
XU
X20
32
33
40
36
20
X61
4
FU1
K1
FU1
S61
XE
K1
P61 O 000
DU
YD
7
M2
-C
10
21
-C
+C
Sepam
MT20111
E32152
K1
K1
Figure 4
K1
YF
21
XU
FU1
S61
verrouillage
enclenchement
closing
interlock
XE
XE
XU
X20
32
33
X61
22
21
22
4
FU1
K1
5
YF
21
XU
Limitation curves
Fusarc CF (figure 3) and Ferraz (figure 4) fuses have current
limiting capacity.
These curves give the maximum value of the limited breaking
current Ic (in kA peak), as a function of the value Ip (in kA rms)
of the presumed current that would be created if there were no
protection. For further details, ask for the fuse catalogues.
K1
XE
P61 O 000
DU
2
M2
-C
2
-C
K1: MV contactor
S61: latching contact
FU1: MV fuses
XE: auxiliary control relay
XU: auxiliary relay
39
Switchgear
Extraction table
MT20112
MT20113
MT20114
Racking handle
This handle enables:
b the withdrawable part to be racked in/out;
b the earthing switch to be open/closed.
40
Implementation examples
MCset 1-2-3
Installation
Line up switchboard
DE55075
570
570
2 feeders
cubicle AD1
900
incomer
cubicle AD3
900
900
bussection
cubicles CL3/GL3
900
incomer
cubicle AD3
570
570
3 feeders
cubicle AD1
570
500
500
room
entrance
1550
200
420
810
1520
(3)
- 1720
2500
(1)
(1)(5)
2800
(4)
(1)
A
1100
(2)
(1) Minimum dimensions to be complied with when installing the MCset switchboard.
(2) Minimum dimensions to be defined according to the cable bending radius.
(3) Operating distance.
(4) Distance needed to extract a functional unit from the switchboard without moving
the other units.
(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres
(see page 14).
A anchor point
B adjustment point
Note: for further information, refer to the civil engineering, user and instruction manual.
41
Installation
Connections
E72901R
AD1
b (1)
b (1)
b
b (1)
b (1)
b
b (1)
b (1)
b
b
b
b
b
b
b
b
b
b
42
AD3
DI2
b
b
b
b
b
b
b
Installation
Connections
(cont.)
MT20117
630 A
1250 A
AD3
2500 A
H (mm)
LV toroid CT
1 set of 3 CTs
2 sets of 3 CTs
LV toroid CT
1 set of 3 CTs
2 sets of 3 CTs
1 set of 3 CTs
2 sets of 3 CTs
DI2
650 (1)
500
465
650 (1)
480
465
435
435
450
(1) When installing with a LV core balance CT, use a LV core balance CT of type ARC3
when connecting with 2 cables (see page 31).
Figure 1
MT20118
b The cubicles and cables requiring the maximum depth should be taken into
consideration when determining the depth P of a switchboard cable duct (figure 1).
b When using cables of length greater than 460 mm, install an additional
compartment as marked (A) under the cubicle (figure 2).
Figure 2
DE60173
Figure 3
43
Cubicle equipment
Appendices
Equipment
Type of cubicle
AD1 AD1 AD2 AD3 CL1 CL2 CL3 GL1 GL2 GL3 TT1 TT2 DI2
cont.
Switchgear
circuit-breaker
contactor
fuse switch
disconnector truck
earthing truck
fixed busbars
racking position indication contact
for the withdrawable part
v
v
v
v
v
v
v
v
v
v
b
v
v
v
v
b
b
v
v
b
v
v
v
v
b
b
v
v
b
v
v
v
v
v
b
v
v
b
v
v
v
v
v
b
v
v
b
v
v
v
v
v
b
v
v
b
b
v
v
b
3 NO + 3 NC
6 NO + 6 NC
b
v
v
v
v
b
b
v
v
b
v
v
b
b
v
v
(1)
(1)
(1)
b
v (4)
v
3 NO + 3 NF
v
v
v
v
(1)
(1)
v
v
v
v
(1)
(1)
v
v
v
v
(1)
(1)
v
v
v
v
(1)
(1)
v
v
v
v
(1)
(1)
v
v
v
v
(1)
(1)
v
v
v
v
v
v
v
v
(1)
(1)
(1)
(1)
v
v
v
v
(1)
Transformers
voltage transformers
(1 per phase)
without fuse
with plug-in fuses
phase-phase
phase-earth
phase-phase
phase-earth
1 NO
3 CTs
6 CTs
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
b
v
v
v
b
v
v
v
b
v
v
v
b
b
b
v
b
v
b
b
v
b
v
v
v
b
v
v
b
v
v
v
b
b
v
b
v
b
b
v
b
v
v
v
b
v
v
v
v
b
v
v
v
v
b
v
v
v
v
b
v
v
v
v
b
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
v
Connections
connection with cable terminal height > 460 mm
connection from top bar
connection by cable from the top
connection by cable from the bottom
Cubicle
protection index
enclosure
compartments (5)
anti-arcing protection (2)
IP3X
IP4X
IPX1
IP2XC
25 kA - 1 s
40 kA - 1 s
lightning arrester
b
b
v
b
v
v
b
v
v
b
v
v
b
b
v
b
v
v
b
b
v
b
v
v
v
b
v
v
b
v
v
v
b
v
v
v
v
b
v
v
v
v
b
v
v
v
v
b
b
v
b
v
b
b
v
b
v
b
b
v
b
v
v
v
b
v
v
v
v
b
v
v
v
v
b
v
v
v
v
Busbars
1250 A/2500 A
LV control cabinet key locking
LV control cabinet lighting
anti-condensation heating element
exposed
insulated
key:
b: basic equipment
v: option
(1) basic equipment with earthing switch option.
(2) according to the room in which the MCset switchboard is installed, you can choose option 3 or 4 sides,
and possibly an exhaust tunnel for hot gases (see page 14).
(3) Connection 1 or 2 cables per phase.
(4) 1 NO + 1 NC available.
(5) Compartment protection.
44
b
v
v
v
b
v
v
v
Current transformers
(Selection guide)
Appendices
Accuracy class
and ratio
AD1
AD1 fusecontactor
AD2
AD2
AD3
CL3
CL1
CL2
31,5
NA (1)
1
10/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
40
50
50
31,5
50
40-80/1 or 5
2.5-5 VA - 5P20
50-100/1-5
2.5-5 VA - 5P20
20/1-1
2.5 VA - 5P20
15 VA - cl 0.5
75-150/1 or 5
2.5-5 VA - 5P20
30/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
100-200/1-1 or 5-5
2.5-5 VA - 5P20
40/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
150-300/1-1 or 5-5
2.5-5 VA - 5P20
10-20 VA - cl 0.5
50/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
200-400/1-1 or 5-5
5-10 VA - 5P20
7.5-15 VA - cl 0.5
75/1-1 or 5/5
2.5 VA - 5P20
15 VA - cl 0.5
250-500/1-1 or 5-5
5-10 VA - 5P20
10-20 VA - cl 0.5
100/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
600/1-1 or 5-5
7.5 VA - 5P20
20 VA - cl 0.5
150/1-1 or 5-5
7.5 VA - 5P10
15 VA - cl 0.5
750/1-1 or 5-5
7.5 VA - 5P20
20 VA - cl 0.5
200/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
1000/1-1 or 5-5
10 VA - 5P20
30 VA - cl 0.5
250/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
1250/1-1 or 5-5
10 VA - 5P20
30 VA - cl 0.5
300/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
1500/1-1 or 5-5
15 VA - 5P20
30 VA - cl 0.5
400/1-1 or 5-5
2.5 VA - 5P20
15 VA - cl 0.5
2000/1-1 or 5-5
15 VA - 5P20
30 VA - cl 0.5
2500/1-1 or 5-5
15 VA - 5P20
30 VA - cl 0.5
(1) Short-circuit current withstand is co-ordinated with the current limited through the fuses.
Other characteristics are available, including the possibility of having 3 secondary windings.
Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling.
45
A few references
Energy
MAPP
b EPM, Colombia
b CHE-POIANA-TEIULUI, Roumania
Infrastructure
b Heathrow airport, United Kingdom
b commercial building, ATIRAU, Azerbaijan
Industry
E74226
E74223
b
b
b
b
b
b
b
b
b
b
b
b
b
b
46
Appendices
Personal notes
47
Appendices
48
Personal notes
89 boulevard F. Roosevelt
F-92500 Rueil Malmaison
France
Tel: +33 (0)1 41 29 85 00
Fax : +33 (0)1 41 29 89 01
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.