Technical Overview
Introduction
The 9401 Isolated Digital Input
Module has an adaptable and failsafe design; it interfaces 8 field input channels.
By employing one and up to three
input modules in a simplex, dual or
triple arrangement, the input module can easily be configured for
simplex SIL2 applications, or fault
tolerant SIL3 safety related applications.
Each input channel is galvanically
isolated from the others and the
FEATURES:
Built in diagnostic
testing and independent Watchdog
SDS-9401
AADvance Industrial Control System
9401 Isolated Digital Input Module
Electrical Specification
Number of inputs:
8 Channels
Channel Isolation:
(channel to channel and channel
to chassis):
Sustained Working:
250Vdc
Maximum Withstanding:
1.5KV dc
Input Voltage:
+24V dc nominal.
Voltage Accuracy:
0.5Vdc
Channel Termination Resistance:
5.12K.
Power consumption:
< 1.5W (from system 24V)
Sample Update Interval (no filter):
1 ms
Self- Test Interval:
1 application scan period
Sequence of Events
Event Resolution: 1 ms
Time-stamp Accuracy: 5 ms
Fusing:
For extreme overload only, see
TA data sheet.
Intrinsic Safety:
External barrier.
Circuit Type:
1oo1D, 1oo2D and 2oo3D
Mechanical Specification
Dimensions (H x W x D):
166mm x 42mm x 118mm
6 in x 1 in x 4in
Weight:
360g
13oz
Casing:
Plastic Non-flammable
Environmental Specification
Operating Temperature:
-20C to 70C.
-4F to 158F.
Storage and Transport (in original packaging): -40C to 70C
-40F to 158F
Operating Humidity
10% to 95%