Professional Documents
Culture Documents
This article was published in ASHRAE Journal, July 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not
be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE
Journal, visit www.ashrae.org.
Stephen W. Duda
Anecdotally, I am aware that some HVAC engineers and designers are uncertain of
the requirements for fire dampers and smoke dampers, especially with regard to
the difference between partition types. Some play it safe and specify fire and smoke
dampers where they really are not required. Some may even find they have been overspecifying protective dampers throughout their career. So I have compiled this Fire
and Smoke Damper Summary for HVAC engineers and designers based on the 2012
International Building Code1 (the 2009 edition has the same requirements but with
different paragraph numbering). Most states and local jurisdictions in North America
use the International Building Code, either outright or as a state adaptation. Where
the IBC is not enforced, NFPA 90A2 can be used for guidance.
Fire-Rated Construction
There are four types of fire-resistance rated walls.
Before you can know what type (if any) fire damper to
use, you first must know which of the four types of walls
you have.
Fire Walls (IBC Section 706) are major separation
walls between buildings or are used to divide one
building into separate buildings. A fire wall actually
allows you to treat the spaces on opposite sides of the
wall as totally separate buildings. These are usually
three- to four-hour rated, and are usually structurally
independent. You cannot run a duct or air transfer
opening through a fire wall located on a property or
lot linenot at allnot even with a fire damper. If
you run a duct or air transfer opening through a fire
wall located within a building, use a three-hour fire
damper. This is the most restrictive of the various
types of fire-rated walls, and is rather rare on most
building projects. Most fire-rated walls within buildings are not this extreme.
Fire Barriers (IBC Section 707) are the medium-rating
level of the various types of fire-rated walls. Examples
aNFPA 90A is slightly more forgiving here. It allows omission of a fire damper at ducted penetrations
of fire barriers and partitions rated less than two hours, even if the building is not fully sprinklered
(5.3.1.1).
42
A S H R A E J O U R N A L a s h r a e . o r g J U LY 2 0 1 4
Smoke-Rated Construction
There are three types of smoke-rated walls. Before you
can know what type (if any) smoke damper to use, you
first must know which of the three types of smoke walls
you have to address.
Smoke Barriers (Section 709) are found in hospitals and
prisons, and are used to completely divide a building
floor into two compartments. A telltale sign of a smoke
barrier on a hospital floor is to look for a double opposite-swing door in the corridor; that door will be on the
smoke barrier wall. Smoke barriers are a more restrictive classification than smoke partitions. A Class I or
II smoke damper is required at each duct penetration
of a smoke barrier. Smoke barriers are also automatically one-hour fire partitions, so review the relevant
section above to determine a possible fire damper
requirement.
In a hospital, every floor that features patient
care or patient sleeping rooms (as opposed to floors
that are exclusively administrative or educational)
must have a smoke barrier that runs straight (or
reasonably close to straight) across the entire floor,
from one exterior wall to the other, that divides
the floor into two distinct halves. The purpose is
that patients may not be mobile enough to evacuate the building very quickly in a fire. To give them
additional time to exit, and to help give rescue
personnel additional time to provide assistance, all
the patients on the fire side of the smoke barrier
will be moved to the other side of the barrier. If the
floors footprint is so big that one side of the smoke
barrier exceeds 22,500 ft2 (2090 m), then an additional smoke barrier is required to divide the floor
into thirds.
Ask the architects you work with to be very careful
about their terminology used on the drawings. Some
use the terms smoke partition and smoke barrier interchangeably, or worsethey just call both a
smoke wall. For HVAC reasons, architects must use
the terms correctly, and to only use the term smoke
barrier where they truly apply. If the terminology is
used correctly, we can eliminate a lot of unnecessary
smoke dampers. Use smoke dampers only in smoke
barriers (or unducted transfer openings in smoke
partitions).
bClass I smoke dampers are rated for a maximum leakage of 8 cfm/ft2 at 4.0 in. static pressure (3.8 L/s at 1 kPa). Class II smoke dampers are rated for a maximum leakage of 20 cfm/ft2 at 4.0 in. static
pressure (9.4 L/s at 1 kPa). Either is acceptable under the codes quoted.
J U LY 2 0 1 4 a s h r a e . o r g A S H R A E J O U R N A L
43
Other Rules
1. Do not put any dampers in Type 1 grease exhaust
and clothes dryer exhaust systems (IBC 717.5.3). If your
hood or dryer exhaust duct crosses a rated wall or floor,
then instead of a damper you must encase the duct itself
in a rated enclosure such as a fire-rated gypsum board
shaft or a listed/labeled fire-wrap insulation material.
Use sub-ducts in lieu of dampers at vertical shafts.
2. If a fire or smoke damper placement will interfere
with the operation of an engineered smoke exhaust
system (such as for an atrium), approved alternate protection shall be used (IBC 717.2.1). What I have usually
done in this case is to specify a remotely resettable fire/
smoke damper addressable by the fire department at a
fire command center.
3. Fire dampers are available in 1.5 hour and threehour ratings. Those are generally the only two choices.
44
A S H R A E J O U R N A L a s h r a e . o r g J U LY 2 0 1 4
Summary
It is important to learn the differences between a
fire wall, fire barrier, and fire partition and between
a smoke barrier and smoke partition, so that you can
properly apply (or not apply) fire and smoke dampers. Unwillingness by some mechanical engineers and
designers to explore the architectural portions of the
International Building Code, and not learn of these distinctions, has led some to over-specify fire and smoke
dampers in HVAC systems.
References
1. ICC. 2012. International Building Code. Chicago: International
Code Council, Inc.
2. NFPA. 2012. Standard 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Quincy, MA: National Fire Protection
Association.