You are on page 1of 6

www.edocuments.co.

uk

| Mechanical O&M Manual | Project XXXXX |

3 GENERAL DESCRIPTION OF THE PROJECT


3-1 MECHANICAL SCOPE OF WORKS...............................................................................................................1
3-2 DESIGN CRITERIA............................................................................................................................................ 1
3-3 ABOVE GROUND DRAINAGE......................................................................................................................... 3
3-4 COLD WATER SERVICE.................................................................................................................................. 4
3-4-1 SYSTEM OVERVIEW....................................................................................................................... 4
3-4-2 SYSTEM DESCRIPTION.................................................................................................................4
3-4-3 CONTROL.......................................................................................................................................... 5
3-4-4 EQUIPMENT...................................................................................................................................... 5
3-4-5 CLEANING AND CHEMICAL TREATMENT.................................................................................6

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 1

www.edocuments.co.uk

| Mechanical O&M Manual | Project XXXXX |

3.1 MECHANICAL SCOPE OF WORKS


The Mechanical Engineering Services provided to the premises comprise of the following systems:

Installation of Above Ground Drainage

Installation of mains cold water service

Installation of boosted cold water service

Installation of gas pipework from meter to boilers only

Installation of heating system comprising biomass boiler and, gas fired boilers

Installation of chilled water system

Installation of fan coil units

Installation of air conditioning systems

Installation of ventilation systems

BMS Controls

Testing and Commissioning

3.2 DESIGN CRITERIA


Area
Treatment Rooms

Changing Areas

Parameters
24oC Winter - no humidity control
18oC Summer - no humidity control
With local set point control
Summer - 21oC - no humidity control
24oC Winter - no humidity control

Ventilation

Front of House WC's - 10 ach / hr


Back of House WC's / Changing Areas - 10 ach / hr
Pantry - 10 ach / hr
Basement Plant / Storage Area - 3 ach / hr

Restaurant

22oC Winter - no humidity control


20oC Summer - no humidity control
With local set point control

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 2

www.edocuments.co.uk

| Mechanical O&M Manual | Project XXXXX |

3.3 ABOVE GROUND DRAINAGE


The foul drainage above ground systems has been installed to discharge effluent and waste products
from the Building as detailed on the schematic record drawings ref XXXXXXXXXXX located in Section
9 of this manual.
The system has been installed to comply with relevant BS 8000 Part 13, BS EN12056-2 and Building
Regulations guidance. The above ground gravity system has been terminated into the underground
drainage system with main venting pipework installed to internal automatic air admittance valves or
venting to atmosphere above Roof Level.
The drainage from all sanitary appliances, plant rooms and mechanical equipment has been
connected to the foul drainage above ground system. The main soil stacks are located within service
risers and connect into the below ground drainage system.
Waste pipe work for the gravity drainage of condensate from fan coil units has been installed in
Geberit pipe with electrofusion fittings. Gravity condense drainage from the fan coil units have been
installed from the condense pump discharges connected to the local soil stack via a HEPvO self
sealing waste valve.
In the kitchen area drainage / waste pipe work terminate into a main horizontal drainage pipe with
final connections, including traps provided by the kitchen fit out contractor.
Surface water sump pumps have been installed within a pump chamber located in the Energy Centre
Basement and these discharge into the below ground drainage.
Service

Material & BS Reference No

Main Soil and Vent Pipework

Geberit HDPE silent 20 pipe work with butt fusion weld fittings
conforming to BS6367, BS5572, BS6437 & BS5114.

Pipework from sanitary fittings

Combination of Geberit DB20 & UPVC pipework and fittings to


BS 4514 with solvent weld joints.

Plantroom Floor gullies

Installed by others

Sanitaryware has been installed and was provided free issue by the Client.

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 3

www.edocuments.co.uk

| Mechanical O&M Manual | Project XXXXX |

3.4 COLD WATER SERVICE


3.4.1 SYSTEM OVERVIEW
A cold water service installation has been provided to serve the Buildings domestic water services
requirements as well as to provide a cold feed to the appliances to the hot water system, heating
system and chilled water system. A separate cold water system has been installed to serve the
Energy Centre.
The systems have been designed and installed to comply with the Water Supply (Water Fittings)
Regulations 1999, BS 6700, and The Building Regulations and all relevant Local and Statutory
Authority regulations or bylaws.
3.4.2 SYSTEM DESCRIPTION
A metered mains cold water service has been run from the site boundary across the site to serve the
Building, the external pipework has been run below ground in blue MDPE/HDPE pipework. The
incoming water supply terminates at the External Tank Room into a stop cock, and provides a down
service to the Energy Centre booster set. The Main Building water supply can be isolated at this point.
The mains cold water service also serves the heating and chilled water systems pressurisation units.
The water from the tank is boosted by a multistage inverter driven packaged booster set. The boosted
water supply distributes potable cold water to the cold water outlets located throughout the Main
House as shown on the schematic record drawings XXXXXXXX located in section 10. A water
softener has also been provided on the feed side of the water tank to reduce the water hardness to
the requirements of Part L2A.
From the booster set pressure reducing valves have been installed in the risers and before the hot
water cylinders to reduce the pressure. A fast acting pressure relief valve is provided to the BCWS
(boosted cold water service) to provide protection against pressure rises, with the discharge side
terminated over the Basement Gullies. A fault alarm is provided to the BMS.
The BCWS distribution pipe work has been routed from the Energy Centre and rises to each floor
level via a number of vertical service risers. At each floor level, the BCWS water pipe work is routed at
high Level to each area. The branch from the risers is complete with a ball isolation valve and double
check valve assemblies. The branch connections at each floor have also been provided with a
pressure regulating valve.
Each room zone has been provided with isolation valves as denoted on the schematic record
drawings XXXXXXXXX located in Section 9 of this manual to enable areas to be shut down for
maintenance purposes.

All final connections to appliances and equipment have been provided with isolation valves.

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 4

www.edocuments.co.uk

| Mechanical O&M Manual | Project XXXXX |

3.4.3 CONTROL
Following activation, either manually or from the pump-set mounted control panel, the booster pump
set will operate continuously and fully automatically to maintain the boosted water system pressure
subject to other interlocks and safety devices being satisfactory.
In the event of fault occurring on the pump-set or tank level monitoring a common fault alarm is
provided to the BMS. An alarm has been provided to the pump mounted Control Panel in the event of
a fault occurring on individual pumps within the pump-set.
A pressure sensing device has been provided with indication to the BMS of the system operating
pressure and generates an alarm should the pressure fall below a predetermined level. Should the
pressure rise above a preset maximum level this will shut down the pump-set and provide an alarm to
the control panel.
Booster pump-set operation is inhibited in the event of selected water storage tank low level
detection.
Each tank section (2 No) is monitored and provides the following alarm indication to the BMS:
1. Low level
2. Tank overflowing
3. Water over temperature
4. Tank room high temperature
5. Tank room low temperature
In the event of the tank overflowing the motorised valve on the main water supply to the tank will be
driven to the fully closed position and provide alarm to the BMS.
The control system allows tank level monitoring system to be temporarily isolated to facilitate tank
section maintenance without shutdown of the boosted water system.
3.4.4 EQUIPMENT
Cold Water Storage Tank
The 6000 litre potable standard cold water storage tank installed within the External GRP Tank Room
provides 2 No sections to serve domestic cold water system to the Main Building. The cold water
storage tank is as detailed on the equipment schedule in Section 6-1-2.
The tank is constructed from glass reinforced polyester resin insulated panels. All nuts, bolts and
washers are stainless steel to flanged tanks. Reinforcement of the tank sidewalls is by means of a
maintenance free internal stainless steel tie-rod system, thus eliminating the need for external steel
support members. The stainless steel is grade 316 to BS 970 Part 1 1996.

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 5

www.edocuments.co.uk

| Mechanical O&M Manual | Project XXXXX |

Cold Water Booster Set


A packaged cold water booster set has been installed within the Ground Floor Plantroom.
The cold water booster set comprises of 3 No. (duty, assist and standby) inverter driven pumps. Each
pump is provided with isolating valves on suction and delivery and non-return valves on delivery.
The pressure booster set control panel is provided with a single common alarm signal initiated by any
individual alarm received at the set, sent to the plant room MCC panel and BMS, via volt free
contacts.
The booster set incorporates an integral low suction pressure switch and low level float switch at the
tank which will raise an alarm at the plant room MCC panel and BMS. Power and control for the
booster set is from the MCC Control Panel.

Pressure Reducing Valve


Pressure reducing valves to each branch connection is set at the bar pressure detailed in the testing
and commissioning section of this manual.

3.4.5 CLEANING AND CHEMICAL TREATMENT


The water systems have been sterilised and chlorinated in accordance with BS6700.
The details of the tests and commissioning data are located in the Test and Commissioning Section of
this document.

| Your Company Name |


Version 1.0

Section: 3
GENERAL DESCRIPTION OF THE PROJECT

Page: 6

You might also like