SITE INSPECTION AND TEST RECORD

Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

Panel / Designation / Location #:

1 of 17
Project no.:

S/S 8194 132/13.8kV

1. General Data and Information:


Bay Name
:
Bay Number
:
Order #
: HBDCACADNHA1BNN1XC
Contact Reset
: Self & Latched Reset
Serial Number
:
Drawing & Sheet no :

CT Ratio

Aux. Voltage
Manufacture
Frequency
Software Version
Function
Rated Current

: 100-240VAC / 48-250VDC
: ABB
: 60Hz.
: 2.0.9
: Line Diff, O/C, E/F & CBF
: 1A

: 800/1 A

2. Mechanical Checks & Visual Inspection:


Serial
Number
1

Description

Checked

Inspect for physical damage / defects

Verify connections as per approved drawings

Check tightness of all connections

Check ferrules

Check apparatus list

Relay module serial number matched with Relay case

Relay Case Earthing checked

3. Electrical Tests:
3.1 Functional Tests:
Serial
Number
1

Description

Checked

Test switch / plug checked for correct function

Indications checked

All output contacts resistance measured

C.T shorting facility checked when relay module removed

Display test power up

Language has been set to English

Relay date and time have been checked

Resetting of alarms through HMI checked

Recorded data has been checked

10

LEDs position has been not changed during DC supply fail

COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

2 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

3.2 Relay Burden:


DC Current w/o
Fault

DC Voltage

DC Current With
Fault

Calculated Watts in Operated


mode (W)

Burden of auxiliary voltage supply: < 12W under quiescent condition & < 18W in operated condition, as per
technical manual # 1MRS756887, Page # 725.

3.3 Measurement Test:


CT Ratio=800/1
Display Measurement Readings
I Injected /
ph

IL1

IL2

IL3

Io

0.5In
1.0In

3.4 IRF (Internal Relay Fault) Output Test:


The IRF contact functions as an output contact for the self-supervision system of the Protection IED
X100: 3-4 (Open in Healthy Condition / Close in IRF) [
]
X100: 3-5 (Close in Healthy Condition / Open in IRF) [
]

4 Relay Function Test:


4.1 Binary Inputs Contacts Test:
Relay Binary
Inputs

Function Assigned

Input Relay Terminal


Numbers

X110 BI1

Spare

X110 1 & 2

X110 BI2

DC Supply Healthy

X110 3 & 4

X110 BI3

VT Fuse Fail

X110 5 & 6

X110 BI4

Trip CCT Healthy

X110 7 & 6

X110 BI5

VCB Service Position

X110 8 & 9

X110 BI6

VCB Test Position

X110 10 & 9

X110 BI7

Earth Switch On

X110 11 & 12

X110 BI8

Earth Switch Off

X110 13 & 12

X120 BI1

VCB Remote Mode

X120 1 & 2

X120 BI2

VCB Close

X120 3 & 2

X120 BI3

VCB Open

X120 4 & 2

X120 BI4

CB Spring Charge

X120 5 & 6

COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

checked

Remarks

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

3 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

4.2 Relay Output Contacts Test:

5.

Relay Binary
Outputs

Protection Assigned

Output Relay Terminal


Numbers

X100 - PO1

VCB Remote Close

6 7 (NO)

X100 - PO2

CBF Operated

8 9 (NO)

X100 - PO3

O/C, E/F Prot Trip.

16 17 & 18 19 (NO)

X100 - PO4

CBF trip to Incomer LV Breaker

21 22 & 23 24 (NO)

X100 - SO1

VCB Close Block

10 11 (NC) / 10 12 (NO)

X100 - SO2

VCB Remote Trip

13 14 (NO)

X110 - SO1

SCADA Remote Alarm feeder Prot.


Operated

14 16 (NC) / 14 15 (NO)

X110 - SO2

CBF trip for Bus Section A/B

17 19 (NC) / 17 18 (NO)

X110 - SO3

Spare

20 22 (NC) / 20 21 (NO)

X110 - SO4

Spare

23 24 (NO)

checked

Remarks

Operating Characteristics Test For Line Differential Unit:

NC = Normally Closed, NO = Normally Open

4.3 Relay Alarm LED Test:


Alarm LED

Alarm LED Assigned

Alarm LED Mode

LED 1

START L1

LATCHED S

LED 2

START L2

LATCHED S

LED 3

START L3

LATCHED S

LED 4

START N

LATCHED S

LED 5

OVERCURRENT TRIP

LATCHED S

LED 6

EARTH FAULT TRIP

LATCHED S

LED 7

BREAKER FAILURE OPERATED

LATCHED S

LED - 8

TRIP CIRCUIT FAULTY

FOLLOW S

LED - 9

CB SPRING FAIL TO CHARGE

FOLLOW S

LED - 10

SPARE

LED - 11

SPARE

FOLLOW S
FOLLOW F
LATCHED S
LATCHEDACK F S

COMPANY
NAME
SIGNATURE
DATE

Checked

Remarks

= Non-Latched mode
= Non Latched Blinking mode
= Latched mode
= Latched Blinking mode

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

4 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

5.1 Pick up and Drop off Test For Low Stage Differential Current (Section 1):
- Using communication channel between two relays.
- Inject IRemote = 0 Amp and inject ILocal by increasing the current gradually till the relay picked
up and assign one LED with (STR_LS_LOC) to indicate Idiff Low Stage pick up.
Phase

Setting

Pick up Value (Amp)

Idiff LS (Amp)

Drop off Value (Amp)

0.2
0.4
0.6
0.2
0.4
0.6
0.2
0.4
0.6

R
Y
B

Operating accuracy:
Depending on the frequency of the current measured: fn 2 Hz, low stage operating accuracy =
2.5% of the set value as per technical manual # 1MRS756887, Page # 281.

5.2 Timing Test for Low Stage Differential Current (Section 1):
-Idiff L.S=0.1
Tp = 1.0
-assign Output contact with OPR_LS_LOC (to indicate the Idiff low stage trip) and take this
output contact to stop the FREJA

Function

Injected Current
Amps

Expected
Time in
Seconds
0.2

Operating Time in Seconds


R

Range in
Seconds

Note:
2 X Is
0.222-0.178
To test the relay, communication shall be arranged between two relays through the Fiber
Definite Time
5 X Is
0.1
0.121-0.079
Optic
cable.

Normal Inverse

COMPANY
NAME
Very Inverse
SIGNATURE
DATE
Extremely
Inverse

8 X Is

0.045

0.06545 0.02455

2 X Is

10.03

10.53-9.53

5 X Is

4.28

4.49-4.06

8 X Is

3.297

3.46-3.13

AL 13.5
FANAR
EBRAHIEM
5 X Is
3.37M.ESSAM
2 X Is

SEC COA14.18-12.83
ABDULLAH M. ALOTAIBI
3.54-3.21

8 X Is

1.93

2.03-1.83

2 X Is

26.67

28.0-25.34

5 X Is

3.33

3.50-3.16

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

5 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

-Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
-Operate time accuracy in inverse time mode 5.0% of the set value or 20 ms as per technical
manual # 1MRS756887, Page # 282.

NOTE:
During the Pickup and Timing tests for the I diff Low stage increase the value for the
Idiff High stage and also increase the value for the End Section 1.
5.3 Operate and Non Operate Test For High Stage Differential Current:
- IRemote = 0 Amp and inject ILocal by increasing the current gradually till the relay picked up
- assign one LED and one Binary output with OPR_HS_LOC
Phase

R
Y
B

Setting
Idiff HS (A)

Operate
Value (A)

Non Operate
Value (A)

2
3
4
2
3
4
2
3
4

-Operating accuracy:
High Stage Operate Time:

Minimum
22 ms
Depending on the frequency of the current measured: fn 2 Hz
High stage operating accuracy = 2.5% of the set value
as per technical manual # 1MRS756887, Page # 281.

Trip Delay
Time (ms)

Operating time
at 2*Idiff HS (ms)

0
0
0
0
0
0
0
0
0
Typical
25 ms

Maximum
29 ms

NOTE:
-During the Pickup for the Idiff High stage decrease the value for the Idiff Low stage.
-Idiff High stage is not depend on the slopes just this value is achieved the relay will trip
Instantaneously.
-The operate value of the instantaneous high stage can be multiplied by a predefined setting if the
ENA_MULT input is activated. In this configuration it is activated by the open status information of
the remote end circuit breaker, disconnectors and earth switch. The intention of this connection is
to lower the setting value of the instantaneous high stage by multiplying with setting High Op value
Mult in case of internal fault.
Set Idiff High Set=200xIn
COMPANY
AL FANAR
Set High Op Value Multiplier=0.5
NAME
EBRAHIEM M.ESSAM
Assign one Binary input with ENA_MULT_HS
SIGNATURE
Operational Value For the Idiff High Set=
amp.
DATE

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Site:

Sheet:
SEC COA

Panel / Designation / Location #:

6 of 17
Project no.:

S/S 8194 132/13.8kV

5.4 Differential Slope Test:


-Idiff Low Stage
=0.2
-Slope Section.1
=0.5
-Slope=Id /Ib
Calculations:

-Idiff High Stage =3.0


-End Section.2 =3.0

-End Section.1
-Slope Section.2

=1.0
=1.0

At point no.1
Slope Section 2=Idiff/Ibias-K where K is the intersection for the Line in Section 2 with the X-axis
Slope Section 2=0.5 , Idiff=0.2 , Ibias=End Section 1=1
So K=0.6
At point no.2
Slope Section 2= Idiff/Ibias-K
Slope Section 2=0.5 , Ibias=End Section 1=3, K=0.6
So Idiff=1.2
Also at point no.2
Slope Section 3=Idiff/Ibias-L where L is the Intersection for the Line in Section 3 with the X-axis
Slope Section 3=1 , Idiff=1.2 , Ibias=End Section 2=3
So L=1.8
Now For example Let I1=2 we need to get the value for I2 to be injected to achieve Slope Section 2=0.5

Idiff=ILocal-IRemote
= 2-I2
Ibias= (ILocal+IRemote)/2 =(2+I2)/2
Slope Section 2=Idiff/Ibias-K
So I2=1.44
And Hence Idiff=0.56 and Ibias=1.72
COMPANY
AL FANAR
NAME
EBRAHIEM M.ESSAM
SIGNATURE
DATE

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

7 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

5.4.1 Slope Section 2 Check:


Fault
Type

R-N

Y-N

B-N

INJECTED
CURRENT
Local
Relay

Remote
Relay

Calculated
Remote
current

Calculated
Values
(Secondary)

Idiff

Ibias

1.44

0.56

1.72

2.5

1.74

0.76

2.12

1.44

0.56

1.72

2.5

1.74

0.76

2.12

1.44

0.56

1.72

2.5

1.74

0.76

2.12

Calculated
values(Primary)

Idiff

Ibias

Measured Values

Idiff

Ibias

Slop
e%

5.4.2 Slope Section 3 Check:

Fault
Type

R-N

Y-N

B-N

INJECTED
CURRENT
Local
Relay

Remote
Relay

Calculated
Remote
current

Calculated
Values
(Secondary)

Idiff

Ibias

2.533

1.467

3.266

2.866

2.134

3.933

2.533

1.467

3.266

2.866

2.134

3.933

2.533

1.467

3.266

2.866

2.134

3.933

Calculated
values(Primary)

Idiff

Ibias

Measured Values

Idiff

Ibias

Slop
e%

5.5 Inrush Restrain Current (2nd Harmonic Blocked Test):


-Set Start Value 2.H=Setting=20%
-At the Local Relay Inject one phase current, 1A at 60HZ. Inject 0.22A at 120HZ, from the
other phase at the same point with same angle and the Remote Relay Current =0.The relay
COMPANY
AL FANAR
SEC COA
will not trip because of 2nd harmonic inrush block. Reduce 2nd harmonic current till the relay
NAME
EBRAHIEM M.ESSAM
ABDULLAH M. ALOTAIBI
operates.
SIGNATURE
DATE

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:

Sheet:

AL FANAR

SEC COA

Site:

8 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

2nd Harmonic Set

Non Block

Block Value

20%
Note:
The second harmonic based local blocking is selected into use with the Restraint mode parameter.
The blocking for the low stage on the local end is issued when the second harmonic blocking is
selected and the inrush is detected.

5.6 Testing Binary Signal Transfer function (BSTGGIO1:1):


5.6.1

Testing for Binary Signal Transfer:


- Local Relay: Assign Binary Input with SEND_SIG_1 and LED with RECV_SIG_1
- Remote Relay: Assign LED with RECV_SIG_1 and Binary Input with SEND_SIG_1
-Check the LED Indications=

5.6.2 Testing for Internal Signal Transfer:


-You can use The Function BSTGGIO as Inter trip SEND and RECEIVE, where you can
send the trip from the Line Differential or the Circuit Breaker Failure from the Local Relay
to the Remote End .
Diff Protection
Status

I/T Setting
Local Relay

I/T Setting
Remote Relay

Test Indication of Local Relay

Send

Send

Active

No

Yes

LED 1
Inter Trip Send
Off

Active

Yes

Yes

On

Time for Signal Receiving =

LED 2
Inter Trip Receive
On
On

Test
Result

milliseconds

Binary signal send


The status of the inputs is continuously sent in the line differential protection telegrams.
SEND_SIG_A can be used for alarming based on the status of SEND_SIG_1...8. By selecting the
signal mode as "In use, alarm sel.", the sending status of the corresponding signal affects also the
activation criteria of SEND_SIG_A. Further, in case more than one signal channels are selected into
the alarm logic, the activation criteria can be defined according to "Any of selected" (OR) or "All of
selected" (AND).
Binary signal receive
g
The function receives continuous binary data within the protection telegrams from the remote end
IED. This received binary data status
then available as the RECV_SIG_1...8
outputs
COMPANY
AL isFANAR
SEC
COAon the local
end
IED.
RECV_SIG_A
can
be
used
for
alarming
based
on
the
status
of
RECV_SIG_1...8.
By
NAME
EBRAHIEM M.ESSAM
ABDULLAH M. ALOTAIBI
selecting
the
signal
mode
as
"In
use,
alarm
sel.",
the
received
status
of
the
corresponding
signal
SIGNATURE
affects the activation criteria of RECV_SIG_A. Further, in case more than one signal channels
DATE
are selected into the alarm logic, the activation criteria can be defined according to "Any of selected"
(OR) or "All of selected" (AND).
Please refer to technical manual # 1MRS756887, Page # 455.

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Site:

Sheet:
SEC COA

Panel / Designation / Location #:

9 of 17
Project no.:

S/S 8194 132/13.8kV

5.7 Secondary Injection for O/C & E/F:


COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

10 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

5.7.1 Low Stage Pick Up & Drop Off Test:


Unit of Start Value Is [In] =1.0A
3 Phase Non directional O/C High stage, Instance1 = PHHPTOC1 [3I>> (1)] = OFF
3 Phase Non directional O/C High stage, Instance 2 = PHHPTOC2 [3I>> (2)] =OFF
3 Phase Non directional O/C Instantaneous stage = PHIPTOC1 [3I>>>] = OFF
Non directional E/F High stage = EFHPTOC1 [Io>>] = OFF
Non directional E/F Instantaneous stage = EFIPTOC1 [Io>>>] = OFF
Current
Settings [3I>]
= Is x In Amps

O/C PHLPTOC1 [3I>]


R
P/U

Y
D/O

P/U

B
D/O

P/U

D/O

Current
Setting Io>(1)
= Is x In Amps

0.3 X 1 = 0.3

0.1 X 1 = 0.1

1 X 1 = 1.0

0.2 X 1 = 0.2

2 X 1 = 2.0

0.4 X 1 = 0.4

3 X 1 = 3.0

0.8 X 1 = 0.8

E/F EFLPTOC1
[Io>(1)]
N
P/U

D/O

Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 X In, as per technical manual #
1MRS756887, Page # 123

5.7.2 Low Stage Definite Time Characteristics:


Current start value [Is] = 0.3 A
Injected
Current
= x Is
Amps

Unit of Start Value Is [In] =1 A

Operating Time (Seconds) PHLPTOC [3I>]


Time Set
(Seconds)

3 X 0.3 =0.9

3.0

2 X 0.3 = 0.6

10.0

1.5 X 0.3=0.45

30.0

Operating Time
(Seconds) EFLPTOC1
[Io>(1)]
N

Note: Operate time accuracy in definite time mode = 1.0% of the set value or 20ms, as per technical
manual # 1MRS756887, Page # 124.

5.7.3 Low Stage Time Multiplier Test:


COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Site:

Sheet:
SEC COA

11 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

In = 1.0A,
3 Phase Non directional O/C Protection Low stage = PHLPTOC1 [3I>] = 0.3In,
PHLPTOC1 [3I>] Injected = 5xIs = 1.5A
PHHPTOC1 [3I>> (1)] = OFF
PHHPTOC2 [3I>> (2)] = OFF
PHIPTOC1 [3I>>>] = OFF
Non-directional E/F Protection Low stage = EFLPTOC1 [Io> (1)] = 0.4In,
Io> injected = 5xIs = 2.0A
EFHPTOC1 [Io>>]
=OFF
EFIPTOC1 [Io>>>]
= OFF
R

TMS
Value K

Calc

0.1

0.428

0.428

0.428

0.428

0.4494-0.4066

0.4

1.712

1.712

1.712

1.712

1.7976-1.6264

Actual

Calc

Actual

Calc

Actual

Calc

Range in
Seconds

Actual

Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per
technical manual # 1MRS756887, Page # 124.

5.7.4 Low Stage Relay Operating Time as per Curve:


T(s) = {(A x K) / ((I/Is) C 1)} + B
When:
Curve

Normal Inverse
Very Inverse
Extremely Inverse
Long Time Inverse

0.14
13.5
80.0
120.0

0
0
0
0

0.02
1.00
2.00
1.00

Normal Inverse

T (s) = 0.14 K
(I/Is) 0.02 1

Very Inverse

T (s) = 13.5 K
(I/Is) 1 1

Extremely Inverse

T (s) = 80 K
(I/Is) 2 1

Long Inverse

T (s) = 120 K
(I/Is) 1 1

RI Type

T (s) =

RD Type

T (s) = 5.8 1.358 loge (I/ (K * Is))

T (s)
I
Is

COMPANY
NAME
SIGNATURE
DATE

K
0.339 0.236 (I/Is)-1
.

: Operate time in seconds


: measured current
: Set Start value

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

12 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

: Set Time multiplier

In=1A, Is (3I>) =0.3 x In


PHHPTOC1 [3I>> (1)]
PHHPTOC2 [3I>> (2)]
PHIPTOC1 [3I>>>]
Is [Io> (1)] = 0.3*In
EFHPTOC1 [Io>>]
EFIPTOC1 [Io>>>]

Function

= 0.3A
= 0FF
= 0FF
= OFF
= 0.3A
= OFF
= OFF

Injected
Current
Amps

Expected
Time in
Seconds

2 X Is

10.03

10.53-9.53

5 X Is

4.28

4.49-4.06

8 X Is

3.297

3.46-3.13

2 X Is

13.5

14.18-12.83

5 X Is

3.37

3.54-3.21

8 X Is

1.93

2.03-1.83

2 X Is

26.67

28.0-25.34

5 X Is

3.33

3.50-3.16

8 X Is

1.27

1.33-1.21

2 X Is

120

126-114

5 X Is

30

31.5-28.5

8 X Is

17.14

17.99-16.28

2 X Is

4.53

4.752-4.299

5 X Is

3.43

3.598-3.256

8 X Is

3.23

3.39-3.06

2 X Is

4.86

5.11-4.62

5 X Is

3.63

3.81-3.45

8 X Is

2.99

3.14-2.84

Normal
Inverse

Very
Inverse

Extremely
Inverse

Long
Inverse

RI Type
Inverse

RD Type
Inverse

Operating Time in sec K = 1, Ko = 1


R
PHLPTOC1

Y
PHLPTOC1

B
PHLPTCO1

N
EFLPTOC1

Range in
Seconds

Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per manual
# 1MRS756887, Page # 124.

5.7.5 High Stage Element -1 & 2 Pick Up & Drop - Off Test:

COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

14410004/00

Customer:

End Client:
AL FANAR

Sheet:
SEC COA

Site:

13 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

Protection
Element

Settings

N
P/U

D/O

P/U

D/O

P/U

D/O

EFHPTOC1
[Io>>]

PHHPTOC
1 [3I>>1]

0.3 x In

PHHPTOC
2 [3I>>2]

0.5 x In

0.4 x In

1.0 x In

0.7 x In

P/U

0.8 x In

D/O

Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.1
10 x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 124.

5.7.6 High Stage Element-1 Definite Time Characteristics:


Is = 1.0 A,

In=1 A
Operating Time
(Seconds) EFHPTOC1
[Io>>]

Operating Time (Seconds)


PHHPTOC1 [3I>>1]

Injected
Current
= x Is
Amps

Time Set

2.5 X 1.0 = 2.5

0.5

2.0 X 1.0 = 2.0

3.0

1.5 X 1.0 = 1.5

5.0

Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per
technical manual # 1MRS756887, Page # 124.

5.7.7 High Stage Element-2 Definite Time Characteristics:


Is = 1.5 A,

In=1 A
Operating Time (Seconds)
PHHPTOC2 [3I>>2]

Injected Current
= x Is
Amps

Time Set

2.5 X 1.5 = 3.75

0.5

2.0 X 1.5 = 3.0

3.0

1.5 X 1.5 = 2.25

5.0

Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per
technical manual # 1MRS756887, Page # 124.

5.7.8 Instantaneous Element Trip and Non Trip:

COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

14 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

PHIPTOC1 [3I>>>]
Setting

R
Trip

EFIPTOC1 [Io>>>]

Y
Non Trip

Trip

B
Non Trip

Trip

N
Non Trip

Trip

Non Trip

1 x In
3 x In
Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.1
10 x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 123.

5.7.9 Instantaneous Element Timing Test:


In = 1A

1 X In

Operate Time PHIPTOC1


[3I>>>] (ms)
R
Y
B

Operate Time EFIPTOC1


[Io>>>] (ms)
N

Injected
Current
(A)

Set
Time
(ms)

2 X Is = 2A

40

15 - 65

5 X Is = 5A

40

15 - 65

I Set

Range in
(ms)

5.8 CBF Test:


COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

15 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

5.8.1 Circuit Breaker Failure Pick Up & Drop Off Test:


Circuit Breaker Failure Protection CCBRBRF1 [3I>/Io> BF] = ON

6.

Current
CCBRBRF1 [3I>BF]
Setting
[3I>BF] =
R
Y
B
Is x In
Testing
Amps at Final
P/U Settings:
D/O
P/U
D/O P/U D/O
0.1 x 1 =0.1

Issue #: 9735

Drop Off To Pickup Ratio %


N
P/U

D/O

Date: 18/09/2011

0.3 x 1 =0.3

CT xData:
0.5
1=0.5

CT Primary Amps: 800A

CT Secondary Amps: 1A

0.9
1=0.9
In =x 1.0A

Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 x In , as per technical manual #
1MRS756887
Page
449.
For Low Set
O/C# &
E/F:

Is for O/C PHLPTOC1 [3I>] = 900A (1.125A)


Is for E/F EHLPTOC1 [Io>] = 80A (0.1A)
IEC
Operating
Curve
for
PHLPTOC1&
E/F
EHLPTOC1
= Normally Inverse
5.8.2 Circuit Breaker Failure Timing Test:
Time Multiplier Setting TMS for PHLPTOC1& EHLPTOC1 = 0.2
Time
Circuit Breaker
Operating Time at 2 X I set (Seconds)
For High
Set O/C &Set
E/F:
Circuit
Breaker
in[3I>>] = 4000A
Failure
Pick Up
Is
for
O/C
PHHPTOC1
(5A)
Is for E/F EHHPTOC1 [Io>>] = 600A (0.75)
Failure Mode
(Seconds)
Current
Amps
R
B
N
IEC Operating Curve
for PHHPTOC1&
EHHPTOC1
= Definite
Time Y

Time Multiplier Setting TMS for PHHPTOC1& EHHPTOC1 = 0.4 Sec


0.25
0.5
ForCurrent
CBF Function:

0.5

0.5

1.0 =80A (0.1A) (Per


0.5 Phase only, E/F not used i.e. 1 out of 3)
Is = Current value [3I>BF]
Circuit Breaker Failure0.25
Delay Time = 150ms
0.5
Circuit Breaker Trip Pulse Time = 150ms
Breaker Status
0.5
0.5
1.0
For the Disturbance Recorder:

0.5

Note: Operate time accuracy is 1.0% of the set value or 20ms, as per technical manual # 1MRS756887
Page # 449.

Record Length
= 240 Cycles
Pre-Trig Length
= 2%
-Trip Pulse
Time
Analog
Channel
1 Test: =IL1A
SettingChannel
For Pulse
Re-trip and Backup Trip Outputs =150 milliseconds
Analog
2 Length of=IL2A
Measured Pulse Length of Re-trip and Backup Trip Outputs=
milliseconds
Analog Channel 3
=IL3A
Analog Channel 4
=I0A
Digital Channel 1
=PHLPTOC1:1 START
Digital Channel 2
=PHHPTOC1:1 START
Digital Channel 3
=EFLPTOC1:1 START
Digital Channel 4
=EFHPTOC1:1 START
Digital Channel 5
=PHLPTOC1:1 OPERATE
Digital Channel 6
=PHHPTOC1:1 OPERATE
Digital Channel 7
=EFLPTOC1:1 OPERATE
Digital Channel 8
=EFHPTOC1:1 OPERATE
Digital Channel 9
=CBF START
Digital Channel 10
= CBF OPERATE
COMPANY
AL FANAR
SEC COA
NAME
EBRAHIEM M.ESSAM
ABDULLAH M. ALOTAIBI
SIGNATURE
DATE

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

16 of 17
Project no.:

Panel / Designation / Location #:


S/S 8194 132/13.8kV

6.1 Low Stage Pick-Up & Drop-Off Test:


Phase

Current
Setting
(Ip) Amps

R
P/U (A)

Y
D/O(A)

P/U (A)

Current
Setting (IEp)
Amps

B
D/O(A)

P/U (A)

D/O(A)

1.13

E/F Relay (N)


P/U (A)

D/O(A)

0.1

Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 x In, as per technical manual #
1MRS756887, Page # 123.

6.2 Operating Time On Selected Curve:


In = 1A, (Ip pick up) =1.13

Injected
Current
(A)
2*Is=2.26

(IEp pick up) = 0.1A

Applied Curve: Normal Inverse, TP = 0.2

Operating Time In Seconds


R-Phase
CALC

B-Phase

Y-Phase

Actual

2.005

CALC

Injecte
d
Current
(A)

Actual

CALC

2.005

Actual

2.005

2*Is=0.2

Operating Time
In Seconds

E/F-N
CALC

Range
Seconds

Actual

2.005

1.9045-2.105

Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per
technical manual # 1MRS756887, Page # 124.

Normal Inverse Curve equation: -

T (s) = 0.14 Tp
(I/Ip) 0.02 1

6.3 High Stage Element 1 Pick Up Test:

Phase
Current Setting
(I>>)Amp

R
P/U(A)

Y
D/O(A)

P/U(A)

B
D/O(A)

P/U(A)

D/O(A)

Current
Setting
(IE>>)
Amps

E/F Relay (N)


P/U(A)

D/O(A)

5
0.75
Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.110
x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 124.

COMPANY
NAME
SIGNATURE
DATE

AL FANAR
EBRAHIEM M.ESSAM

SEC COA
ABDULLAH M. ALOTAIBI

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

Feeder Protection Relay, Type RED615

Customer:

14410004/00

End Client:
AL FANAR

Sheet:
SEC COA

Site:

17 of 17

Panel / Designation / Location #:

Project no.:

S/S 8194 132/13.8kV

6. High Stage Element 1 Timing Test:


Injected
Current
(A)

Time Setting
in ms

1.2*Is= 6

400

Injected
Current
(A)

Operating Time In ms
R-Phase

Y-Phase

B-Phase

Time
Setting
in ms

1.2*Is=.9

Operating
Time in ms
E/F-N

400

Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per technical manual
# 1MRS756887, Page # 124.

6.5 Breaker Failure Pick-Up & Drop-Off Test:


Is = Current value [3I>BF] =0.1
Current Setting
= Is x In (Amps)

R
P/U

Y
D/O

P/U

B
D/O

P/U

D/O

Final Setting=0.1
Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 X In , as per technical manual #
1MRS756887 Page # 449.

6.6 Breaker Failure Operating Time:


Current Setting =
Is x In (Amps)

Injected
Current
(A)

Set Time
(ms)

Operating time mSec


R

0.1
0.2
150
Note: Operate time accuracy is 1.0% of the set value or 20ms, as per technical manual # 1MRS756887
Page # 449.

6.7 Trip Pulse Time Measurement:


Trip Pulse Time Setting (ms)

Measured value

150

6.8 CB Spring Charging Time Measurement:


Motor Charging time: Seconds
Time measured by stop watch
COMPANY
AL FANAR
7. Oscillograph & Event
Attached:
NAME
EBRAHIEM
M.ESSAM
SIGNATURE
8.
Printout of the Final Settings Attached:
DATE

SEC COA
Yes/NoM. ALOTAIBI
ABDULLAH

Yes/No