Description:
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
1 of 17
Project no.:
CT Ratio
Aux. Voltage
Manufacture
Frequency
Software Version
Function
Rated Current
: 100-240VAC / 48-250VDC
: ABB
: 60Hz.
: 2.0.9
: Line Diff, O/C, E/F & CBF
: 1A
: 800/1 A
Description
Checked
Check ferrules
3. Electrical Tests:
3.1 Functional Tests:
Serial
Number
1
Description
Checked
Indications checked
10
COMPANY
NAME
SIGNATURE
DATE
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
2 of 17
Project no.:
DC Voltage
DC Current With
Fault
Burden of auxiliary voltage supply: < 12W under quiescent condition & < 18W in operated condition, as per
technical manual # 1MRS756887, Page # 725.
IL1
IL2
IL3
Io
0.5In
1.0In
Function Assigned
X110 BI1
Spare
X110 1 & 2
X110 BI2
DC Supply Healthy
X110 3 & 4
X110 BI3
VT Fuse Fail
X110 5 & 6
X110 BI4
X110 7 & 6
X110 BI5
X110 8 & 9
X110 BI6
X110 10 & 9
X110 BI7
Earth Switch On
X110 11 & 12
X110 BI8
X110 13 & 12
X120 BI1
X120 1 & 2
X120 BI2
VCB Close
X120 3 & 2
X120 BI3
VCB Open
X120 4 & 2
X120 BI4
CB Spring Charge
X120 5 & 6
COMPANY
NAME
SIGNATURE
DATE
AL FANAR
EBRAHIEM M.ESSAM
checked
Remarks
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
3 of 17
Project no.:
5.
Relay Binary
Outputs
Protection Assigned
X100 - PO1
6 7 (NO)
X100 - PO2
CBF Operated
8 9 (NO)
X100 - PO3
16 17 & 18 19 (NO)
X100 - PO4
21 22 & 23 24 (NO)
X100 - SO1
10 11 (NC) / 10 12 (NO)
X100 - SO2
13 14 (NO)
X110 - SO1
14 16 (NC) / 14 15 (NO)
X110 - SO2
17 19 (NC) / 17 18 (NO)
X110 - SO3
Spare
20 22 (NC) / 20 21 (NO)
X110 - SO4
Spare
23 24 (NO)
checked
Remarks
LED 1
START L1
LATCHED S
LED 2
START L2
LATCHED S
LED 3
START L3
LATCHED S
LED 4
START N
LATCHED S
LED 5
OVERCURRENT TRIP
LATCHED S
LED 6
LATCHED S
LED 7
LATCHED S
LED - 8
FOLLOW S
LED - 9
FOLLOW S
LED - 10
SPARE
LED - 11
SPARE
FOLLOW S
FOLLOW F
LATCHED S
LATCHEDACK F S
COMPANY
NAME
SIGNATURE
DATE
Checked
Remarks
= Non-Latched mode
= Non Latched Blinking mode
= Latched mode
= Latched Blinking mode
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
4 of 17
Project no.:
5.1 Pick up and Drop off Test For Low Stage Differential Current (Section 1):
- Using communication channel between two relays.
- Inject IRemote = 0 Amp and inject ILocal by increasing the current gradually till the relay picked
up and assign one LED with (STR_LS_LOC) to indicate Idiff Low Stage pick up.
Phase
Setting
Idiff LS (Amp)
0.2
0.4
0.6
0.2
0.4
0.6
0.2
0.4
0.6
R
Y
B
Operating accuracy:
Depending on the frequency of the current measured: fn 2 Hz, low stage operating accuracy =
2.5% of the set value as per technical manual # 1MRS756887, Page # 281.
5.2 Timing Test for Low Stage Differential Current (Section 1):
-Idiff L.S=0.1
Tp = 1.0
-assign Output contact with OPR_LS_LOC (to indicate the Idiff low stage trip) and take this
output contact to stop the FREJA
Function
Injected Current
Amps
Expected
Time in
Seconds
0.2
Range in
Seconds
Note:
2 X Is
0.222-0.178
To test the relay, communication shall be arranged between two relays through the Fiber
Definite Time
5 X Is
0.1
0.121-0.079
Optic
cable.
Normal Inverse
COMPANY
NAME
Very Inverse
SIGNATURE
DATE
Extremely
Inverse
8 X Is
0.045
0.06545 0.02455
2 X Is
10.03
10.53-9.53
5 X Is
4.28
4.49-4.06
8 X Is
3.297
3.46-3.13
AL 13.5
FANAR
EBRAHIEM
5 X Is
3.37M.ESSAM
2 X Is
SEC COA14.18-12.83
ABDULLAH M. ALOTAIBI
3.54-3.21
8 X Is
1.93
2.03-1.83
2 X Is
26.67
28.0-25.34
5 X Is
3.33
3.50-3.16
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
5 of 17
Project no.:
-Operate time accuracy in definite time mode 1.0% of the set value or 20 ms
-Operate time accuracy in inverse time mode 5.0% of the set value or 20 ms as per technical
manual # 1MRS756887, Page # 282.
NOTE:
During the Pickup and Timing tests for the I diff Low stage increase the value for the
Idiff High stage and also increase the value for the End Section 1.
5.3 Operate and Non Operate Test For High Stage Differential Current:
- IRemote = 0 Amp and inject ILocal by increasing the current gradually till the relay picked up
- assign one LED and one Binary output with OPR_HS_LOC
Phase
R
Y
B
Setting
Idiff HS (A)
Operate
Value (A)
Non Operate
Value (A)
2
3
4
2
3
4
2
3
4
-Operating accuracy:
High Stage Operate Time:
Minimum
22 ms
Depending on the frequency of the current measured: fn 2 Hz
High stage operating accuracy = 2.5% of the set value
as per technical manual # 1MRS756887, Page # 281.
Trip Delay
Time (ms)
Operating time
at 2*Idiff HS (ms)
0
0
0
0
0
0
0
0
0
Typical
25 ms
Maximum
29 ms
NOTE:
-During the Pickup for the Idiff High stage decrease the value for the Idiff Low stage.
-Idiff High stage is not depend on the slopes just this value is achieved the relay will trip
Instantaneously.
-The operate value of the instantaneous high stage can be multiplied by a predefined setting if the
ENA_MULT input is activated. In this configuration it is activated by the open status information of
the remote end circuit breaker, disconnectors and earth switch. The intention of this connection is
to lower the setting value of the instantaneous high stage by multiplying with setting High Op value
Mult in case of internal fault.
Set Idiff High Set=200xIn
COMPANY
AL FANAR
Set High Op Value Multiplier=0.5
NAME
EBRAHIEM M.ESSAM
Assign one Binary input with ENA_MULT_HS
SIGNATURE
Operational Value For the Idiff High Set=
amp.
DATE
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Site:
Sheet:
SEC COA
6 of 17
Project no.:
-End Section.1
-Slope Section.2
=1.0
=1.0
At point no.1
Slope Section 2=Idiff/Ibias-K where K is the intersection for the Line in Section 2 with the X-axis
Slope Section 2=0.5 , Idiff=0.2 , Ibias=End Section 1=1
So K=0.6
At point no.2
Slope Section 2= Idiff/Ibias-K
Slope Section 2=0.5 , Ibias=End Section 1=3, K=0.6
So Idiff=1.2
Also at point no.2
Slope Section 3=Idiff/Ibias-L where L is the Intersection for the Line in Section 3 with the X-axis
Slope Section 3=1 , Idiff=1.2 , Ibias=End Section 2=3
So L=1.8
Now For example Let I1=2 we need to get the value for I2 to be injected to achieve Slope Section 2=0.5
Idiff=ILocal-IRemote
= 2-I2
Ibias= (ILocal+IRemote)/2 =(2+I2)/2
Slope Section 2=Idiff/Ibias-K
So I2=1.44
And Hence Idiff=0.56 and Ibias=1.72
COMPANY
AL FANAR
NAME
EBRAHIEM M.ESSAM
SIGNATURE
DATE
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
7 of 17
Project no.:
R-N
Y-N
B-N
INJECTED
CURRENT
Local
Relay
Remote
Relay
Calculated
Remote
current
Calculated
Values
(Secondary)
Idiff
Ibias
1.44
0.56
1.72
2.5
1.74
0.76
2.12
1.44
0.56
1.72
2.5
1.74
0.76
2.12
1.44
0.56
1.72
2.5
1.74
0.76
2.12
Calculated
values(Primary)
Idiff
Ibias
Measured Values
Idiff
Ibias
Slop
e%
Fault
Type
R-N
Y-N
B-N
INJECTED
CURRENT
Local
Relay
Remote
Relay
Calculated
Remote
current
Calculated
Values
(Secondary)
Idiff
Ibias
2.533
1.467
3.266
2.866
2.134
3.933
2.533
1.467
3.266
2.866
2.134
3.933
2.533
1.467
3.266
2.866
2.134
3.933
Calculated
values(Primary)
Idiff
Ibias
Measured Values
Idiff
Ibias
Slop
e%
Contract no.:
Customer:
14410004/00
End Client:
Sheet:
AL FANAR
SEC COA
Site:
8 of 17
Project no.:
Non Block
Block Value
20%
Note:
The second harmonic based local blocking is selected into use with the Restraint mode parameter.
The blocking for the low stage on the local end is issued when the second harmonic blocking is
selected and the inrush is detected.
I/T Setting
Local Relay
I/T Setting
Remote Relay
Send
Send
Active
No
Yes
LED 1
Inter Trip Send
Off
Active
Yes
Yes
On
LED 2
Inter Trip Receive
On
On
Test
Result
milliseconds
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Site:
Sheet:
SEC COA
9 of 17
Project no.:
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
10 of 17
Project no.:
Y
D/O
P/U
B
D/O
P/U
D/O
Current
Setting Io>(1)
= Is x In Amps
0.3 X 1 = 0.3
0.1 X 1 = 0.1
1 X 1 = 1.0
0.2 X 1 = 0.2
2 X 1 = 2.0
0.4 X 1 = 0.4
3 X 1 = 3.0
0.8 X 1 = 0.8
E/F EFLPTOC1
[Io>(1)]
N
P/U
D/O
Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 X In, as per technical manual #
1MRS756887, Page # 123
3 X 0.3 =0.9
3.0
2 X 0.3 = 0.6
10.0
1.5 X 0.3=0.45
30.0
Operating Time
(Seconds) EFLPTOC1
[Io>(1)]
N
Note: Operate time accuracy in definite time mode = 1.0% of the set value or 20ms, as per technical
manual # 1MRS756887, Page # 124.
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Site:
Sheet:
SEC COA
11 of 17
Project no.:
In = 1.0A,
3 Phase Non directional O/C Protection Low stage = PHLPTOC1 [3I>] = 0.3In,
PHLPTOC1 [3I>] Injected = 5xIs = 1.5A
PHHPTOC1 [3I>> (1)] = OFF
PHHPTOC2 [3I>> (2)] = OFF
PHIPTOC1 [3I>>>] = OFF
Non-directional E/F Protection Low stage = EFLPTOC1 [Io> (1)] = 0.4In,
Io> injected = 5xIs = 2.0A
EFHPTOC1 [Io>>]
=OFF
EFIPTOC1 [Io>>>]
= OFF
R
TMS
Value K
Calc
0.1
0.428
0.428
0.428
0.428
0.4494-0.4066
0.4
1.712
1.712
1.712
1.712
1.7976-1.6264
Actual
Calc
Actual
Calc
Actual
Calc
Range in
Seconds
Actual
Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per
technical manual # 1MRS756887, Page # 124.
Normal Inverse
Very Inverse
Extremely Inverse
Long Time Inverse
0.14
13.5
80.0
120.0
0
0
0
0
0.02
1.00
2.00
1.00
Normal Inverse
T (s) = 0.14 K
(I/Is) 0.02 1
Very Inverse
T (s) = 13.5 K
(I/Is) 1 1
Extremely Inverse
T (s) = 80 K
(I/Is) 2 1
Long Inverse
T (s) = 120 K
(I/Is) 1 1
RI Type
T (s) =
RD Type
T (s)
I
Is
COMPANY
NAME
SIGNATURE
DATE
K
0.339 0.236 (I/Is)-1
.
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
12 of 17
Project no.:
Function
= 0.3A
= 0FF
= 0FF
= OFF
= 0.3A
= OFF
= OFF
Injected
Current
Amps
Expected
Time in
Seconds
2 X Is
10.03
10.53-9.53
5 X Is
4.28
4.49-4.06
8 X Is
3.297
3.46-3.13
2 X Is
13.5
14.18-12.83
5 X Is
3.37
3.54-3.21
8 X Is
1.93
2.03-1.83
2 X Is
26.67
28.0-25.34
5 X Is
3.33
3.50-3.16
8 X Is
1.27
1.33-1.21
2 X Is
120
126-114
5 X Is
30
31.5-28.5
8 X Is
17.14
17.99-16.28
2 X Is
4.53
4.752-4.299
5 X Is
3.43
3.598-3.256
8 X Is
3.23
3.39-3.06
2 X Is
4.86
5.11-4.62
5 X Is
3.63
3.81-3.45
8 X Is
2.99
3.14-2.84
Normal
Inverse
Very
Inverse
Extremely
Inverse
Long
Inverse
RI Type
Inverse
RD Type
Inverse
Y
PHLPTOC1
B
PHLPTCO1
N
EFLPTOC1
Range in
Seconds
Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per manual
# 1MRS756887, Page # 124.
5.7.5 High Stage Element -1 & 2 Pick Up & Drop - Off Test:
COMPANY
NAME
SIGNATURE
DATE
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
14410004/00
Customer:
End Client:
AL FANAR
Sheet:
SEC COA
Site:
13 of 17
Project no.:
Protection
Element
Settings
N
P/U
D/O
P/U
D/O
P/U
D/O
EFHPTOC1
[Io>>]
PHHPTOC
1 [3I>>1]
0.3 x In
PHHPTOC
2 [3I>>2]
0.5 x In
0.4 x In
1.0 x In
0.7 x In
P/U
0.8 x In
D/O
Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.1
10 x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 124.
In=1 A
Operating Time
(Seconds) EFHPTOC1
[Io>>]
Injected
Current
= x Is
Amps
Time Set
0.5
3.0
5.0
Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per
technical manual # 1MRS756887, Page # 124.
In=1 A
Operating Time (Seconds)
PHHPTOC2 [3I>>2]
Injected Current
= x Is
Amps
Time Set
0.5
3.0
5.0
Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per
technical manual # 1MRS756887, Page # 124.
COMPANY
NAME
SIGNATURE
DATE
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
14 of 17
Project no.:
PHIPTOC1 [3I>>>]
Setting
R
Trip
EFIPTOC1 [Io>>>]
Y
Non Trip
Trip
B
Non Trip
Trip
N
Non Trip
Trip
Non Trip
1 x In
3 x In
Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.1
10 x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 123.
1 X In
Injected
Current
(A)
Set
Time
(ms)
2 X Is = 2A
40
15 - 65
5 X Is = 5A
40
15 - 65
I Set
Range in
(ms)
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
15 of 17
Project no.:
6.
Current
CCBRBRF1 [3I>BF]
Setting
[3I>BF] =
R
Y
B
Is x In
Testing
Amps at Final
P/U Settings:
D/O
P/U
D/O P/U D/O
0.1 x 1 =0.1
Issue #: 9735
D/O
Date: 18/09/2011
0.3 x 1 =0.3
CT xData:
0.5
1=0.5
CT Secondary Amps: 1A
0.9
1=0.9
In =x 1.0A
Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 x In , as per technical manual #
1MRS756887
Page
449.
For Low Set
O/C# &
E/F:
0.5
0.5
0.5
Note: Operate time accuracy is 1.0% of the set value or 20ms, as per technical manual # 1MRS756887
Page # 449.
Record Length
= 240 Cycles
Pre-Trig Length
= 2%
-Trip Pulse
Time
Analog
Channel
1 Test: =IL1A
SettingChannel
For Pulse
Re-trip and Backup Trip Outputs =150 milliseconds
Analog
2 Length of=IL2A
Measured Pulse Length of Re-trip and Backup Trip Outputs=
milliseconds
Analog Channel 3
=IL3A
Analog Channel 4
=I0A
Digital Channel 1
=PHLPTOC1:1 START
Digital Channel 2
=PHHPTOC1:1 START
Digital Channel 3
=EFLPTOC1:1 START
Digital Channel 4
=EFHPTOC1:1 START
Digital Channel 5
=PHLPTOC1:1 OPERATE
Digital Channel 6
=PHHPTOC1:1 OPERATE
Digital Channel 7
=EFLPTOC1:1 OPERATE
Digital Channel 8
=EFHPTOC1:1 OPERATE
Digital Channel 9
=CBF START
Digital Channel 10
= CBF OPERATE
COMPANY
AL FANAR
SEC COA
NAME
EBRAHIEM M.ESSAM
ABDULLAH M. ALOTAIBI
SIGNATURE
DATE
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
16 of 17
Project no.:
Current
Setting
(Ip) Amps
R
P/U (A)
Y
D/O(A)
P/U (A)
Current
Setting (IEp)
Amps
B
D/O(A)
P/U (A)
D/O(A)
1.13
D/O(A)
0.1
Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 x In, as per technical manual #
1MRS756887, Page # 123.
Injected
Current
(A)
2*Is=2.26
B-Phase
Y-Phase
Actual
2.005
CALC
Injecte
d
Current
(A)
Actual
CALC
2.005
Actual
2.005
2*Is=0.2
Operating Time
In Seconds
E/F-N
CALC
Range
Seconds
Actual
2.005
1.9045-2.105
Note: Operate time accuracy in inverse time mode 5.0% of the theoretical value or 20ms, as per
technical manual # 1MRS756887, Page # 124.
T (s) = 0.14 Tp
(I/Ip) 0.02 1
Phase
Current Setting
(I>>)Amp
R
P/U(A)
Y
D/O(A)
P/U(A)
B
D/O(A)
P/U(A)
D/O(A)
Current
Setting
(IE>>)
Amps
D/O(A)
5
0.75
Note: Operation accuracy for Pick up is 1.5% of set value or 0.002 x In (at currents in the range of 0.110
x In) OR 5.0% of the set value at current in the range of 1040 x In, as per technical manual #
1MRS756887, Page # 124.
COMPANY
NAME
SIGNATURE
DATE
AL FANAR
EBRAHIEM M.ESSAM
SEC COA
ABDULLAH M. ALOTAIBI
Contract no.:
Customer:
14410004/00
End Client:
AL FANAR
Sheet:
SEC COA
Site:
17 of 17
Project no.:
Time Setting
in ms
1.2*Is= 6
400
Injected
Current
(A)
Operating Time In ms
R-Phase
Y-Phase
B-Phase
Time
Setting
in ms
1.2*Is=.9
Operating
Time in ms
E/F-N
400
Note: Operate time accuracy in definite time mode 1.0% of the set value or 20ms , as per technical manual
# 1MRS756887, Page # 124.
R
P/U
Y
D/O
P/U
B
D/O
P/U
D/O
Final Setting=0.1
Note: Operation accuracy for Pick up is 1.5% of the set value or 0.002 X In , as per technical manual #
1MRS756887 Page # 449.
Injected
Current
(A)
Set Time
(ms)
0.1
0.2
150
Note: Operate time accuracy is 1.0% of the set value or 20ms, as per technical manual # 1MRS756887
Page # 449.
Measured value
150
SEC COA
Yes/NoM. ALOTAIBI
ABDULLAH
Yes/No