Professional Documents
Culture Documents
10
Control
1) Introduction
This Installation Work Manual employs the following symbols to ensure safe installation work of
the product. As these instructions are very important, ensure they are observed.
Warning
Caution
Warning
Do not perform installation yourself. Ask your dealer or a qualified technician to install the system. If the
unit is not installed correctly this could lead to issues such as poisoning if exhaust gas enters buildings,
water leakage, electric shock, or fire.
(2)
Warning
Carefully follow the instructions in this manual when performing installation. If the unit is not installed
correctly this could lead to issues such as poisoning if exhaust gas enters buildings, water leakage,
electric shock, or fire.
(3)
Warning
Confirm that the fuel gas supplied is the same as the category specified on the unit. Use of a fuel gas other
than the specified category could cause incomplete combustion, leading to carbon monoxide poisoning.
64
Warning
When the unit is installed outside a building, it should be located so that exhaust gas does not enter the
building via windows or ventilation ducts and piping connected to the building, etc. Inflow of exhaust gas
into buildings could cause poisoning or other problems. When extending the exhaust piping, install the
exhaust piping extension kit (option) with reference to the Exhaust Piping Work Manual.
(2)
Warning
When the unit is installed inside a building, the exhaust gas piping should be routed so that it discharges into
the open air outside the building. Locate the exhaust gas outlet with care so that exhaust gas does not enter
the building via windows or ventilation ducts and piping connected to the building, etc. The accumulation of
exhaust gas inside the building could cause poisoning or other problems. When extending the exhaust piping,
install the exhaust piping extension kit (option) with reference to the Exhaust Piping Work Manual.
(3)
Warning
When the unit is installed inside a building, install a gas leakage alarm and an incomplete combustion
alarm (CO detector) in the vicinity of the unit. If leaked gas accumulates inside the building, it could
cause an explosion or fire. The signal lines of the alarms should be connected to the terminals for the
external stop signals of the unit.
(4)
Warning
When the unit is installed inside a building, maintain the required ventilation level for the unit. If the
ventilation level is inadequate, it could cause incomplete combustion, resulting in poisoning or
performance degradation and malfunctioning of the unit. Connect a ventilation fan so that it is linked to
the operation signal of the unit and thus runs during operation of the unit.
(5)
Warning
Install the unit in an open space so that exhaust gas does not accumulate. If the exhaust gas enters a
building, it could cause poisoning, etc.
(6)
Warning
Discharge the exhaust gas into the open air at a location where it will not negatively affect the
surrounding area. (Exhaust gas must not be discharged into drainage gullies or ditches.) If the exhaust
gas enters a building, it could cause poisoning, etc.
(7)
Warning
Install the unit in a place that can fully support the weight of the unit. If the location is not strong enough,
the unit could topple over or fall, causing injuries, etc.
(8)
Caution
When the unit is installed near a parking lot or in similar places where there is a possibility of it being
accidentally hit by a car, take preventative measures such as positioning a car barrier.
65
(9)
Caution
Maintain the specified distance between the unit and flammable substances. If the distance is
insufficient, the unit could cause a fire.
(10)
Caution
Do not install the unit in a place where there is a possibility of the generation, inflow, accumulation, or
leakage of flammable gases, or where volatile flammable substances are handled. This could result in a
fire due to the ignition of flammable materials or gases.
(11)
Caution
Do not install the unit in a place where exhaust gas or air expelled by the fan will hit garden trees, etc.
This exhaust gas or air discharge could cause damage to the trees, etc.
(12)
Caution
Maintain the specified space for inspection and maintenance work. If the space is insufficient, personnel
could fall from the installation site and suffer injuries.
(13)
Caution
When the unit is installed on a rooftop or in a high place, set permanent ladders or handrails along the
route to the unit, and fences or handrails around the unit to prevent falls.
(14) Install the unit in a place where there will be no short circuit due to hot air from the radiator or the
accumulation of exhaust gases. When the unit is installed inside a building, use the specified duct to
route the hot exhaust air from the radiator to the outside without air leakage and expel it with a
pressure fan.
(15) Install the unit so that the hot air from the radiator or the exhaust gas has no direct effect on other
equipment.
(16) Install the unit in a place where there will be no adhesion of foreign substances to the radiator and no
materials (exhaust outlet, exhaust flue, etc.) that could cause significant deterioration of the exterior of
the unit.
(17) Install the unit in a place where noise or vibration will not cause problems around or below the
installation site. (Particularly in residential areas, care is required regarding the periods of operation.)
(18) Install the unit in a place where there are no walls near the unit that could reflect or resonate with the
operation noise.
(19) It must be possible to carry in, carry out, disassemble, and maintain the equipment. Depending on the
work processes, other equipment may be installed along the route or in the entrance after the unit is
carried in. Care is required as this could make it difficult to carry out the unit at a later date.
(20) Refer to Section 3 when installing two or more units in parallel.
(21) Avoid places with a large amount of dust or litter.
(22) Avoid sloping areas.
66
600 or more
600 (300)
or more*2
2000 or more
3790 or more
2000 or more
2000 or more
4040 or more
2270 or more
3790 or more
(300 or more)*2
800 or more
200 (600)
or more
800 or more
600 (300)
or more*2
2200 or more
800 or more
2200 or more
200 (600)
or more
600 or more
600 or more
Unit: mm
029013-00E
Notes
1: When surrounding the unit with soundproof walls, attach openings (louvers or the like) to the
bottom of the soundproof walls. (To prevent the short cycle of radiating air.)
2: Decide installation space after consideration of the piping space.
3: If the distance of retention is specified by local-government fire prevention ordinances and
enforcement regulations, secure the installation space according to these regulations.
4: Give consideration not to cause problems for neighboring houses due to operating noise,
radiating air, or hot ventilation air.
5: Depending on the situation, the site may be filled with radiating air and this has an effect on
performance. Prevent a short cycle with the optional wind direction boards, etc.
67
Anti-vibration mount
4-100 hole
For use of box-out L-type/
LA-type bolt
F.L.
1900
150
90
200
Reinforcing bar 10
150
90
200
Reinforcing bar 10
F.L.
310
310
310
150
150
F.L.
310
(280)
(200)
M12
300
300
300
300
300
(200)
029014-00E
L-type/LA-type
350
840
1800
(280)
1300
1250
F.L.
850
4-14.5 hole
For use of resin
anchor bolt or
mechanical anchor bolt
350
350
4-14.5 hole
For use of resin
anchor bolt or
mechanical anchor bolt
350
860
1300
350
350
4-100 hole
For use of box-out L-type/
LA-type bolt
60 or more
70 or more
60 or more
70 or more
30 or more
40 or more
Notes
1. For use of box-out L-type/LA-type bolt
When laying the concrete for the base, provide a box-out for fixing
the anchor bolts, fix the anchor bolts, and then secure them in the
concrete.
2. It is sometimes necessary to change the thickness of the base
depending on the foundation strength, so carry out the work after
consulting construction engineers.
3. Earthquake-resistance strength: Horizontal seismic coefficient of 0.6
(Numeric values with * show the dimensions in the case of a
horizontal seismic coefficient 1.0.)
4. When using a smaller base, join the base and the structure with
reinforcing bars.
68
5) Carrying-in
Warning
Lift the unit in the specified places in the specified way. If it is lifted in other places or in other ways,
there is a possibility of damage or dropping.
Keep out from under the lifted unit.
The carrying-in and installation processes involve risk. It is important to carry in and install the unit properly in
the specified place, while paying attention to safety.
Carry out the loading and unloading work
Lifting belt (Nylon sling)
to and from vehicles calmly with due
For 1.5 t (Width of belt: 50 mm or more)
consideration to the center of gravity.
Never load or unload the units on their
sides and pile up.
At the time of lifting, use the lifting belts
(nylon slings), and be careful not to cause
Insert a blanket cloth so as
damage to the unit.
not to damage the unit.
(Local procurement)
Depending on the situation, decide the
work method, personnel, and mechanical
handling equipment. In addition, when
using mechanical handling equipment,
have qualified personnel handle it.
Mass (Including lubricating oil and cooling water): 790 kg
Caution
When lifting the unit with a crane, lift
the unit with the nylon slings as shown
in the figure. Use two nylon slings with
a lifting load of more than 1.5 t and a
width of more than 50 mm.
69
029015-00E
Rear Side
Flexible pipe
Thermometer
Cock
Front Side
Front Side
Rear Side
70
029016-00E
(1)
Caution
Confirm that the fuel gas supplied is the same as the type specified on the unit.
Use of a fuel gas other than the specified type could cause incomplete combustion,
leading to carbon monoxide poisoning
(2)
Caution
Use reinforced gas hoses approved for gas or low-pressure gas hoses with a joint fixture for liquefied
petroleum gas hoses between the gas cocks of the fuel gas piping and the unit. If a gas hose other than
the specified ones is used and it is damaged by vibration, it may cause a fire, etc. due to a fuel gas leak.
(3)
Caution
After the completion of the fuel gas fitting work, check that there is no gas leak along the fuel gas piping
route. If there is any fuel gas leak, it may cause a fire, etc.
(4) Before connecting the piping to the unit, clean inside the fuel gas pipes to remove any dust or dirt.
(5) When there is contamination in the fuel gas piping, attach a strainer between the reinforced gas hose
and the cock.
(6) If sealing tape is used on the thread of the screw, it eats the valve seat of the gas regulator and may
cause a gas leak. Use tight seals, etc.
(7) Be careful that the piping of the fuel gas inlet does not become an obstacle to maintenance work.
(8) Fix the piping of the fuel gas inlet with supports.
(9) When the cogeneration main unit is installed on an anti-vibration mount, be sure to take adequate
measures against any vibration.
(10) When the unit is installed inside a building, install a gas leakage alarm and an incomplete combustion
alarm (CO detector) in the vicinity of the unit. If leaked gas accumulates inside the building, it could
cause an explosion or fire. The signal lines of the alarms should be connected to the terminals for the
external stop signals of the unit.
Reinforced gas hose
Gas cock
25A or more (Gas inlet pipe)
Customers
arrangement
Rear Side
Front Side
71
Caution
Use the supplied hose for an exhaust drain. After checking the local regulations of the jurisdictional area,
extend it to the appropriate place for the drainage of the discharge and secure the tip. When installing
multiple units, install the piping of each unit separately. When installing multiple units as a group, install
the specified exhaust drain piping as indicated in the diagram below.
(2)
Caution
When the cogeneration main unit is installed above a room, extend the exhaust drain piping to an outlet
that is appropriate for the discharge of water. If drainage is discharged directly onto floor surfaces, it may
cause staining of waterproof sheeting or damage to concrete surfaces.
(3)
Caution
(4)
Inner syphon
(neutralizer)
Exhaust drain piping
Drain outlet
Caution
Indoor
029021-01E
Exhaust
ventilation according national or local requirements
Drain piping
The Base
The syphon and neutralizer must be
ordered as an optional kit.
Neutralizer
Syphon select
72
Generator room
Package
Reference
Ventilation airflow
rate inside package:
850 m3/h
Engine room
Generator
room
Eng
030992-00E
Required ventilation airflow rate for generator room, Q: Ensure that Q is greater than the result of
the calculations , and below.
For electricity-oriented operation: Q > + +
For heat-oriented operation:
Q>+
Calculation example 1
Calculation example 2
Conditions
- Temperature of ventilation air to generator room: 30C
When controlling generator room temperature to 40C max.
(Room temperature increase: 10C max. (: Q2 = 850 m3/h)
- Natural gas G20 (calorific value: 35.9 MJ/m3N)
Conditions
- Temperature of ventilation air to generator room: 35C
When controlling generator room temperature to 40C max.
(Room temperature increase: 5C max. (: Q2 = 1,700 m3/h)
- Natural gas G20 (calorific value: 35.9 MJ/m3N)
Detailed calculations
(1) Radiator exhaust rate*: 5,500 m3/h min ......................................................
(2) Required airflow rate for gas engine combustion: Q1 (m3/h)
* Guide the exhaust air from radiator to outdoors via a duct and use a positive pressure fan.
<Formula> Q1 = B 3.6 9.524 0//35.9 ..........................................
where, B
: fuel gas consumption (32.34 kW)
3.6
: 1 kW = 3.6 MJ
9.524 : theoretical air requirement (for natural gas) (m3N/m3N)
: excess air factor (1.51)
73
(3) Required airflow rate for controlling room temperature increase Q2 (m3/h)
<Formula> Q2 = B 3.6 0.08/T//Cp ........................................................
where, B
: fuel gas consumption (32.34 kW)
3.6
: 1 kW = 3.6 MJ
0.08 : ratio of heat radiation from engine and generator
T
: permissible room temperature increase (C)
: intake air density (1.128 kg/m3 at 40C)
Cp
: specific heat of air at constant pressure (9.75 10-4 MJ/kgC at 40C)
Design generator room so that the room temperature will not exceed 40C.
<Calculation example 1> Required airflow rate for controlling room temperature to 40C max.
when temperature of ventilation air to generator room is 30C (temperature increase T = 10C max.)
Q2 = 32.34 3.6 0.08/10/1.128/0.000975 = 847 850 (850 m3/h min.)
<Calculation example 2> Required airflow rate for controlling room temperature to 40C max.
when temperature of ventilation air to generator room is 35C (temperature increase T = 5C max.)
Q2 = 32.34 3.6 0.08/5/1.128/0.000975 = 1,694 1,700 (1,700 m3/h min.)
Decide the required ventilation airflow rate for generator room according to the permissible temperature
increase.
If operators enter the room while the system is in operation, add 30 m3/h per person ............
74
Warning
Construct the piping of the exhaust extension alone without the confluence of other piping.
Connect each piping by the welding or the flange connection. Confirm there is no leakage from all
joints in the test run.
Locate the outlet port of the exhaust gas to the position in which the exhaust gas doesn't hazardously
affect surroundings. Note that the exhaust gas doesn't enter indoor again.
Warning
When the unit is installed on an anti-vibration mount, be sure to use flexible pipes and adequately deal
with any potential vibration. Construct the flexible pipes vertically so that the condensed water is not
collected in the piping.
Construct the total extension of the exhaust-piping so that the back pressure is 1.5 kPa or less. If the
back pressure exceeds 200 Pa, use the stainless flue system completely welded and verify that the
system is sound (no leakage).
Construct the exhaust piping applying the inclination (2 degree or more) so that the condensed water
is not collected in the piping.
Adjust the direction of flue exit or install the cover so that the falling object don't enter from the
flue exit.
Construct the exhaust piping so that there is not obstacles around the flue exit.
Refer to the table below. The table is the result of the calculation of the diameter/maximum-length of a
straight-tube as 200 Pa.
Use the pipe of 1 1/2 (O.D. 48mm) or more.
Use the adapted pipe to AlSl 316L, 316 Tl or 304L, or the same quality pipe.
Joint
(The joint is supplied as option.)
Top cover
Mist separator
The inclination of pipe
Customers
arrangement
CP10WE
029019-01E
75
198
19
150
150
120
280
399
92
150
030994-00X
500mm min
500mm min
600mm min.
030995-01X
When installing multiple Inverters, leave a space of 500 mm minimum to the side of the Inverter. Do not
install multiple Inverters vertically.
Incorrect
500 mm min
030996-00E
76
Incorrect
Correct
Incorrect
60min.
Mount Inverter straight or tilted to back
030997-00E
030998-00X
Mount the mounting base plate to the wall using the enclosed mounting screws. Install the product in a
location that will be able to support its weight (24 kg). The installation location must be able to withstand
the force of 80 Nm of torque at each mounting screw. Refer to P18 for the mounting dimensions.
*Be sure to mount it using all six screws.
030999-00X
Hang the KP40G main body on the two support ridges of the mounting base plate.
031000-00X
Use the M5 body mounting screw included with the enclosed screw set to secure the KP40G main body
to the mounting base plate. Tighten the screw with 2.5 to 3.0 Nm of torque.
031003-00X
77
In Case of Defects
Water leakage
Has flexible piping been used for the hot water inlet/outlet of the unit?
Are the water volume, water speed, piping size, and pressure of the hot water piping appropriate?
Vibration
Has the heat insulation for the hot water piping been completed?
Gas leakage
Is there any gas leakage along the path of the fuel gas piping?
Fire
Has an independent exhaust gas pipe been routed to outside the room?
Is there any gas leakage from the connection areas of the exhaust gas piping?
Gas poisoning
Is there any gas leakage from the flange area of the exhaust gas piping?
Gas poisoning
Is the discharge point for the exhaust gas located so that the gas is released into the open air and
there is no negative effect on the surrounding area?
Have adequate measures been taken to prevent the exhaust gas entering the room?
Gas poisoning
Has the specified type of stainless steel pipe been used for the exhaust gas piping?
Has the exhaust piping been installed with an upward slope so that drainage does not back-up?
Discharge of drainage
Has the exhaust piping been fully wound with heat insulation?
Has the exhaust drain been routed to an outdoor water discharge outlet?
When the unit is installed indoors, have the additional drain filter and the syphon been installed
correctly?
When the unit is installed indoors, does the ventilation fan run during operation of the unit, and is
the required ventilation level maintained?
When the unit is installed indoors, is the exhaust airflow from the radiator routed to outside the
room using a dedicated duct and expelled using a pressure fan?
When the unit is installed indoors, are both a gas leakage alarm and an incomplete combustion
alarm (CO detector) installed in the vicinity of the unit?
Gas poisoning
When the unit is installed indoors, are the signal lines for the alarm devices connected to the
external stop signal terminals of the unit?
Gas poisoning
78
Check
Column
Wiring M an u al
CP10WE
This Wiring Manual describes how to perform the wiring for the YANMAR Cogeneration
Package CP10WE, and includes work procedures and points to note during the wiring
process.
Single installation covered by G83/1 notification at or before day of commissioning
followed by G83/1 paperwork (G83/1 appendix 3) within 30 days.
Multiple installation covered by G83/1 application to proceed (G83/1 appendix 2). On
commissioning notification and appendix 3 as above.
1) Introduction
This Wiring Manual employs the following symbols to ensure the wiring is performed safely for the
product. As these instructions are very important, ensure they are observed.
Warning
Caution
Denotes a case in which operating errors may cause dangerous conditions leading
to light or moderate injury and conditions where only equipment damage may occur.
Caution markings can also indicate conditions that can have serious
consequences.
(1)
Warning
Do not perform installation yourself. Ask your dealer or a qualified technician to install the system. If the unit is not installed
correctly, this could lead to issues such as poisoning if exhaust gas enters buildings, water leakage, electric shock, or fire.
(2)
Warning
Carefully follow the instructions in this manual when performing installation. If the unit is not installed correctly, this
could lead to issues such as poisoning if exhaust gas enters buildings, water leakage, electric shock, or fire.
(3)
Warning
The wiring must be performed by a qualified wiring technician according to the relevant laws and regulations.
Incorrect work could cause electric shock, fire, etc.
79
Warning
Use the specified cables and connect the wiring securely. The wiring must be fixed securely so that external force
from the cables is not transmitted to the terminal connections. If the wiring is not properly connected or secured, it
could cause the generation of heat or fire.
(2)
Caution
Be sure to carry out the grounding work. If the grounding work is not carried out, it may cause electric shock.
(3)
Caution
When the unit is installed on an anti-vibration mount, carry out the work so that the wiring is not affected by vibration. If excessive
force is applied to the wiring by vibration, it could cause the breakage of wires, electric shock due to short circuiting, fire, etc.
part A
Accessories
Cable gland 8 pieces
8-29.0 hole
80
029042-01E
862
841
Hot water
storage unit Unit Failure
malfunction signal
signal
LC1
(+)
LC1
(-)
Remote monitor
communication
wiring
DC1 DC1
(+)
(-)
RDA RDB
842
843
844
Operation
signal
RS485 RS485
(+)
(-)
881
882
External start
signal
DC3 DC3
(+)
(-)
H1
H2
main
External stop External stop Hot
operation
signal 1
signal 2
signal
UK
DC2 DC2
(+)
(-)
UL
VK
VL
WK
WL
L1
L2
L3
AC230V INPUT
032818-00E
For connection to this unit, install the wiring in a plastic-coated 2nd-type flexible conduit.
The wiring should not interfere with the maintenance of the unit. Vibration should not cause damage to
the wiring.
Secure the wiring using fixing bands so that excessive force is not applied to the wiring.
Use the crimp terminal for the terminal to be connected.
81
For connection to this unit, use the cable gland of the attachment.
032806-00E
Size of terminal
For M4 (Width of terminal: 10 mm or less)
For M4 (Width of terminal: 10 mm or less)
For M3 (Width of terminal: 7.3 mm or less)
For M3 (Width of terminal: 5.5 mm or less)
Duct (or flexible conduit)
NG
N
G N
NG
G O
OK
K
Communication/
Signal line
Communication/
Signal line
Power source
line
82
Communication/
Signal line
Power source
line
025411-01E
Cogeneration
Package
UK
UL
VK
VL
WK
WL
L2
L3
K
L
K
L
K
L
Terminating resistance
(It is attached to Remote monitor)
TB3
LC1 (+)
LC1 (-)
E
L1
1+
1Shield
Shield
earth
Shield
earth
B+
B+
-
TB1
TB5
Load
+
FG
*3 Rmote monitor
Load
DC1 (+)
DC1 (-)
E
RS485 (+)
RS485 (-)
E
Shield
earth
CV-S (Shield cable) 3.5sq or more (2core)
DC Power DC380V
DC (+)
DC (-)
Shield
earth
Shield
earth
Load
*1
ELB
Inverter KP40G
Pin4 (RS485+)
Pin3 (RS485-) COM1
Pin4 (RS485+)
Pin3 (RS485-) COM2
same as *8
DC2 (+)
DC2 (-)
E
No.1
AC
CV 4sq (3core)
AC power AC230V
Shield earth
Shield
earth
CV-S (Shield cable) 3.5sq or more (2core)
DC Power DC380V
No.2
DC (+)
DC (-)
Shield
earth
ELB
L
N
FG
Pin4 (RS485+)
Pin3 (RS485-) COM1
Pin4 (RS485+)
Pin3 (RS485-) COM2
*1
Inverter KP40G
same as *8
DC3 (+)
DC3 (-)
E
Shield
earth
CV-S (Shield cable) 3.5sq or more (2core)
DC Power DC380V
AC
CV 4sq (3core)
AC power AC230V
Shield
earth
No.3
DC (+)
DC (-)
Shield
earth
ELB
L
N
FG
Pin4 (RS485+)
Pin3 (RS485-)
COM1
Pin10 (RS485END)
Pin6 (RS485END)
*1
Inverter KP40G
AC
ELB
L
N
FG
CV 4sq (3core)
AC power AC230V
Terminating resistance
(It is attached to System controller)
ELB
RDA
RDB
E
RDA
RDB
Shield
earth
*2
System controller
X
Y
E2
E1
ELB
L1
L2
L3
N
E
Conact rating
125V AC,1A
Conact rating
125V AC,1A
*7 Customers
control panel
861
862
GS1
GS2
881
882
841
844
H1
H2
GS3
GS4
842
843
WH1
WH2
Conact rating
24V DC,2A or more
Conact rating
24V DC,2A or more
Conact rating
24V DC,2A or more
*5 *6
Same as
GS1,GS2
*7 Hot-water
strage unit
Unused
Hot-water strage unit mulfunction signal CVV1.25 or more (2core)
No-voltage A contact input (ONHot-water strage unit mulfunctionON)
Conact rating
24V DC,2A or more
*1.
*2.
*3.
*4.
Perform the Inverter wiring according to the term of For inverter wiring.
Perform the system controller wiring according to the term of For system controller wiring, and Install manual of system controller.
Perform the Remote monitor wiring according to the Install manual of Remote monitor.
When customer prevents the reverse power, CT need to be connected.
And select the CT accoring to the term of Installation and wiring of CT.
Perform the transducer installation into the CHP according to the install manual of TRC10W (Option).
*5. These are short-circuited at the time of shipping.
Disconnect the short circuit line for use.
*6. Used to enable emergency stops initiated from outside by,for example, gas-leak alarms or fire alarms.
(When installing the unit indoors, be sure to connect a gas-leak alarm.)
*7. Customers Arrangement
83
032819-00E
Rmote monitor
1+
1E
Shield
earth
CVV-S (Shield cable)
1.25sq or more (2core)
Shield
earth
CP10WE No.2
CP10WE No.3
Shield
earth
CVV-S (Shield cable)
0.5sq or more (2core)
Shield
earth
84
LC1(+)
LC1(-)
E
CP10WE No.1
LC1(+)
LC1(-)
E
RDA
RDB
E
Shield
earth
CVV-S (Shield cable)
1.25sq or more (2core)
Shield
earth
RDA
RDB
E
Shield
earth
CVV-S (Shield cable)
1.25sq or more (2core)
Shield
earth
LC1(+)
LC1(-)
E
RDA
RDB
E1
RDA
RDB
E
System controller
Shield
earth
CVV-S (Shield cable)
0.5sq or more (2core)
Shield
earth
Terminating resistance
(It is attached to Remote monitor)
031013-00E
AC breaker
(25A)
AC breaker
(25A)
Communication wiring
AC breaker
(25A)
DC3 (+)
DC3 ()
E
DC2 (+)
DC2 ()
E
DC1 (+)
DC1 ()
E
029035-02E
Connector specifications
Maker
Contact
DC(+)
Multi-Contact USA
PV-BP3/4
DC(-)
Multi-Contact USA
P-SP3/4
Communication HIROSE ELECTRIC CO.,LTD JRC-PC2-112
85
Cover
PV-T3II/B
PV-T3II/S
JR16WP-10PC(72)
As required
3
3
5
DC wiring
Perform the DC side wiring as shown in the diagram below. The connector for the KP40G inverter
should be obtained locally. Use a wire with 3.5 to 5.5 mm2 and shielded wire. Use shielded wires, and
connect both ends of the shielding part to the earth of the inverter side and the unit side.
Be sure to attach the MC caps (standard accessory) to the unused holes of DC.
AC wiring
Perform the AC side wiring according to the Technical Manual (section titled Wiring/Processing the AC
Plug) supplied with the inverter.
[Processing the AC Plug]
Use the following procedure to wire to the AC connector and AC connector cover.
AC connector
AC connector cover
Tightening cap
031040-00E
3.4 mm max.
9 to 9.5 mm
3.4 to 4.1 mm
12.5 to 13 mm
B
4 mm2
Insulation
Conductor
031041-00E
031042-00X
86
The diameter of cables that can be inserted into the AC connector cover is 11 to 16 mm.
11 to 16 mm
031043-00X
Wire
Screwdriver
031044-00E
Model
210-119
210-619
0.4 -0.2
10
2.5 -0.2
031045-00X
87
031046-00X
Recommended dimension of A
0.0 mm
0.9 mm
1.5 mm
1.8 mm
3.2 mm
4.0 mm
031048-00X
88
Communication wiring
Perform the communication wiring according to the Technical Manual (section titled Wiring/Processing
the Communications Plug) supplied with the inverter. Please see the following drawing.
Use shielded wires, and connect both ends of the shielding part to the earth of the inverter side and the
unit side.
About RS485, connect the RS485 (-) of the unit and the "3" of the plug, connect the RS485 (+) of the
unit and the "4" of the plug, and short the "6" and "10" of the plug of the inverter 3. Do not use the "1",
"2", "5", "7", "8", and "9" of the plug for the unit.
Inverter 1
Inverter 2
Inverter 3
E
RS485 ()
RS485 (+)
E L1 L2 L3 N
Short
Cap
029040-02E
89
3 2 1
7
4
10 9 8
031049-00X
Fig, 9 Communication plug pin numbers (seen from the wiring side)
Terminal
Coupling
Cord tube
C
Clamp
Gasket
Washer
P shell unit
Clamp piece
Conductor Insulator
Cable sheath
B
Size
031050-00E
A
B
C
3.5 to 4.0 mm Approx.19 mm 39 mm or less
D
7.5 to 8.5 mm
[Disassembly of connector]
To remove the plug, remove the set screw, fit a communication plug to fix, and remove the cord tube.
To remove the cord clamp, remove the cord tightening screws.
[Connection]
Use a wire with 0.3 to 0.7 mm2 (AWG20~24) is allowed for the communications plug, and a cable with
diameter of 7.5 to 8.5 mm for the communications plug.
After the terminal treatment of the cable size given in Fig, 10, thread on the cable the clamp, washer,
gasket, cord tube and coupling in this order and direction as shown in Fig, 10. When strip the covering
from the connection cable, use the applicable tool to securely crimp it.
After crimping the crimp terminals to the conductor with the following applicable tool, insert the crimp
terminals into terminal holes of the P shell unit. After inserting, adjust to meet the C size. Keep the size
until assembling is completed. Insert the communications cable to the pin number corresponding to the
contact as given below. Carefully confirm the pin number of the plug connector prior to inserting the
contact pin. (Refer to Fig, 9 for the pin numbers.)
After connecting, be sure to confirm that it cannot be pulled out by pulling.
90
[Assembly of connector]
Fit the connected P shell unit to the receptacle fixed with a vice or the like. Tighten the cord tube to the
specified torque (3 to 3.5 Nm).
Fit the gasket, washer, and clamp. Tighten the clamp to the specified torque (3 to 3.5 Nm) while
preventing the cable from being rotated.
Torque the set screw to 0.2 to 0.25 Nm.
Torque the cord tightening screws (two positions) to 0.3 to 0.35 Nm.
78
901
23
456
12345678
23
ON
78
901
456
DipSW1: ON
DipSW2-8: OFF
Table 1
Unit number
Inverter 1
Inverter 2
Inverter 3
91
Setting
(RotarySW)
0
1
2
L1 L2 L3 N E
Shield
earth
E2
E1
System controller
92
Shielded
communication line
Shield earth
Y RDA RDB
032816-00E
CT spec
Primaly [A]
Transducer Primaly
side Power [kW]
Secondary [A]
< 10kW
50
10
100
20
200
40
* The setting for the primaly side power to exceed 40kW cannot be done.
CP10WE
Other
device
CP10WE
Other
device
CP10WE
Note: Do not install grounding jumper wiring for units unless they are of the same type.
93
CP10WE
CP4WE
or other
cogeneration
unit
Other
device
029041-00E
Load
INV
Distribution
board
INV
(ELB25A)
System
side
CP10WE
ELB
40A
ELB
Load
Load
029043-01E
Connection example 2
Load
Distribution
board
System
side
ELB
(If necessary)
ELB
ELB
40A
Load
Load
INV
INV
INV
(ELB25A)
CP10WE
029044-01E
94
3) DNO approval
Be sure to take corrective actions properly in accordance with E.R.G83/1.
The following provides the major content on Engineering Recommendation G83/1 (E.R.G83/1).
(1) Compliance with DNO requirements will include
Dual supply labeling should be provided at the service termination, meter position and all points
of isolation to indicate the presence of on-site generation and indicating the position of the main
a.c. switch disconnector (for suitable label see ER G83/1 or see the sample reproduced in
Example Signs and on the back cover of this guide).
At the point of interconnection, the following information is to be displayed
(typically all displayed on the circuit diagram).
Circuit diagram showing the relationship between the inverter equipment and supply.
A summary of the protection settings incorporated within the equipment.
A contact telephone number for the supplier/installer/maintainer of the equipment.
(2) Labeling
Requirements for labeling are contained within the relevant sections of this guide. Example labels
can be seen below.
All labels must be clear, easily visible, constructed and affixed to last and remain legible for the
lifetime of the system.
WARNING
dual supply
95
In Case of Defects
Malfunction, heat
generation, fire
Check
Column
Check Items
In Case of Defects
Not possible to
output, failure
Electrostatically
charged, noise
Not possible to
output
Malfunction,
incorrect indication
96
Ungainly, unstable
Malfunction
Check
Column
Te st Run M an u al
CP10WE
This Test Run Manual describes how to perform the test run for the YANMAR Cogeneration
Package CP10WE, and includes work procedures and points to note when conducting the test
run.
Single installation covered by G83/1 notification at or before day of commissioning
followed by G83/1 paperwork (G83/1 appendix 3) within 30 days.
Multiple installation covered by G83/1 application to proceed (G83/1 appendix 2). On
commissioning notification and appendix 3 as above.
1) Introduction
This Test Run Manual employs the following symbols to ensure the test run is performed safely for
the product. As these instructions are very important, ensure they are observed.
Warning
Caution
Warning
Do not perform installation yourself. Ask your dealer or a qualified technician to install the system. If the unit is not installed
correctly this could lead to issues such as poisoning if exhaust gas enters buildings, water leakage, electric shock, or fire.
(2)
Warning
Carefully follow the instructions in this manual when performing installation. If the unit is not installed correctly this
could lead to issues such as poisoning if exhaust gas enters buildings, water leakage, electric shock, or fire.
97
Caution
Confirm whether adequate space for safe maintenance is secured.
Caution
Confirm whether the unit is properly isolated from flammable materials.
Warning
Confirm whether the base is firm and horizontal.
Warning
Confirm whether the unit is fixed firmly with anchor bolts.
Warning
Confirm whether the piping and wiring are installed as designed.
Caution
Confirm with the tester whether the input power supply voltage to the unit is single-phase 230 V.
Power on
Caution
Confirm whether the unit is grounded.
Warning
Check the connection of the exhaust drain piping of the unit.
Warning
Check the isolation of the exhaust gas outlet (installed outdoors) and the connection of exhaust gas ducts (installed indoors).
Warning
Check the inlet and outlet of the unit (clogging, isolation from the windows, etc.).
Warning
Check whether there is a fuel gas leak.
Warning
Confirm the proper performance of installation work to enable correct ventilation and discharge of exhaust gas
when the unit is installed inside a building.
Warning
Confirm the installation of alarms and proper connection of the signal lines to the unit when the unit is installed
inside a building.
98
DSW1
DIP SW
SW2
UP
SW6
Operation SW
SW1
ON
Normal
1 2 3 4 5 6 7 8
SW13
1 2 3 4 1 2 3 4
Gas category Option
DSW3
SW4
DOWN
DSW2
Set value
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 1 2 3
Remote setting System
NEXT
SW5
Menu
ENTER
SW3
BACK
Set
ON
1 2 3 4
Normal
1 2 3 4
System
Check
SW1
Normal
SW13
Set
Normal
Stop
Start
Power
transmission
Normal
Normal
Stop
Emergency
stop
Interrupt
SW11
SW10
SW11
Interrupt
SW9
SW12
Emergency
stop
Power
transmission
SW10
SW8
SW7
SW12
Normal
Start
SW7
SW9
Remote Automatic
Remote Automatic
Check
SW8
Operation button
Normal
025412-00E
Control board
CN3
CN10
DSW2
CN11
CN1
ON
1 2
Terminal1 Terminal2
DIP SW
CN2
DSW2
CN12
ON
1 2
CPU2
CPU2
SW3
Normal
CN15
CN4
Normal SW1
CPU Select
CN13
Terminal1 Terminal2
CN5
RY1
CN18
Control Unit
CN16
CPU2
Normal
SW2
CPU Writing
CN8
CN7
RY3
RY2
RY4
CN19
CN14
CN6
CPU1
CN17
028200-00E
MCB
MCB2
031005-00X
99
Name
SW No.
Setting item
DIP SW1
ON
Setting details
4
Status at
shipment
Setting
required on
site
All OFF
Setting is
required
during remote
monitoring.
All OFF
Setting is
required
when
installing
multiple
units.
Address No.
OFF OFF OFF OFF OFF Not valid (Address has not been set.)
1 2 3 4 5 6 7 8
15
ON
ON
ON ON OFF OFF
68
DIP SW2
ON
1 2 3 4 5 6 7 8
14
Address No.
System address
Gas fuel
category
Unit No. 1
ON OFF OFF
Unit No. 2
OFF ON OFF
Unit No. 3
Gas category
2H
Based on the
specifications at
shipment.
Check
58
Unused
14
Unused
DIP SW3
ON
1 2 3 4
100
DIP SW No.
2-1
2-2
2-1
2-2
2-1
2-2
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
Control board
DIP SW2
12
ON
OFF
System controller
032817-00E
Control board
Control board
DIP SW2
DIP SW2
12
ON
12
OFF
ON
OFF
System controller
025415-00E
Unit No. 2
Control board
Control board
Control board
DIP SW2
DIP SW2
DIP SW2
12
ON
OFF
12
ON
OFF
System controller
12
ON
OFF
025414-00E
101
Name
Unit
Range
0 (Without remote controller)
-1 (Unused)
-2 (With system controller)
ON/OFF
Setting required
on site
Check
ON
Check
1 to 6
ON/OFF
OFF
1 to 6
ON/OFF
OFF
ON/OFF
OFF
Check
1(step)
-20 to 0 to 20
Not required
ON/OFF
ON
Not required
1(sec)
ON/OFF
OFF
Setting at
shipment
*1. When installing multiple units, this setting is for the function that continues operation or stop of unit based on the set values
of power source for operation start and stop before generation of U4 keeping these set values when judging communication
error [U4] by each unit with system controller.
102
1.
Name
Remarks
ON/OFF Turned ON for maximum 10 seconds. Disabled for 15 seconds after turned ON
1 Starter transformer
ON/OFF
2 Gas Valve 1
ON/OFF
3 Gas Valve 2
ON/OFF
ON/OFF
5 Throttle valve
6 GVM
2.
Unit
0 Starter motor
H/L
H/L
0 Oil pump
ON/OFF Turned ON for maximum 90 seconds. Disabled for 20 seconds after turned ON
1 Radiator fan
ON/OFF
2 Ventilation fan 1
ON/OFF
600/0
ON/OFF
A Operation signal
ON/OFF
During operation or immediately after a stop, be careful not to touch the exhaust
manifold, exhaust duct, and engine, etc. As the whole engine is very hot, there is a
possibility of burns.
During operation, do not touch or even go near the rotating parts. There is a possibility
of being caught in the radiator fan or ventilation fan, etc.
During operation, do not touch the terminal parts and high-voltage cord of the spark
plug. There is a possibility of electric shock. When inspecting the system, turn off the
power.
When operating the system controller, pay close attention and prevent people from
going near the unit. The engine may start suddenly and there is a possibility of injury.
103
, and SW10 to Power transmission . Then start the engine and check that electricity
is transmitted.
Check that LED4 and LED5 on the display board are lit.
Check the power output on the display board.
Check the engine data for the unit.
On the display board, switch SW10 to Interrupt and SW9 to Stop , and then stop the unit.
Preparation for automatic operation
On the display board, change SW7 to Remote .
On the display board, change SW1 to Normal , SW8 to Automatic , SW9 to
Stop
, and
SW10 to Interrupt .
(8) Procedure for Grid-Connected Operation Using System Controller (Automatic Mode)
Manual operation
Start up the unit in the manual mode and check the operation from the start-up to when the
electricity transmission turns ON.
Stop the manual operation and check the process from electricity transmission OFF to
operation stop.
Check the activation of the stop operation if the unit is shut down using an emergency stop.
(Check the buzzer.)
* Refer to the Operation Manual supplied with the system controller regarding the operation procedure for the controller.
Check the activation of an emergency stop. (Do not forget to reset the alarm after checking the
activation of the emergency stop.)
Turn the grid-connection breaker OFF and check the operation stop. Then, turn the breaker ON
again and check that the system reboots automatically after three minutes.
Scheduled operation
Set the present time using the system controller.
Set the operation date and operation time on the schedule screen, and then perform the test
operation. (Ensure that the operation date is not set to a holiday. Set the operation time to start
a few minutes after the present time and to stop after 15 minutes.)
* Refer to the Operation Manual supplied with the system controller regarding the operation procedure for the controller.
104
After the test run checks, on the display board, change SW7 to Remote , SW8 to
Automatic , SW9 to Stop , and SW10 to Interrupt .
[Adjusting the O2 concentration]
Check the density value of O2 during rated power generation.
Adjust the main adjusting screw(MAS) of the mixer of the engine in order to set the density value
of O2 to the density standard value(7.1%~8.1%) during rated power generation.
Loosen the fixing nut of the main adjusting screw (MAS).
Using a slotted screwdriver, turn the main adjusting screw (MAS) clockwise or counterclockwise
little by little.
* The main adjusting screw should be gradually turned till the O2 concentration satisfies the
requirement. (Standard value: 7.60.5%)
Once the O2 concentration meets the requirement, tighten the fixing nut of the main adjusting
screw (MAS).
* Take care to keep the main adjusting screw at the adjusted point.
105
027907-00E
106
Alarm Code
A1
A2
A9
AA
AF
C0
C1
C5
CE
CF
E0
E1
E2
E3
E4
E7
EA
EC
EH
F0
F3
F4
F5
F7
FA
FC
FE
FJ
H0
HA
HC
HE
HF
HH
HJ
J3
J4
J6
J7
J8
JA
JC
JH
JJ
L1
L7
L8
LA
LE
P0
P6
P8
U2
U3
U4
U5
U6
Description
Alarm level
Inverter malfunction 1B
Inverter malfunction 1C
Inverter malfunction 2B
Inverter malfunction 2C
Inverter malfunction D
Grid malfunction A
Grid malfunction B
Grid malfunction C
Inverter malfunction 3B
Inverter malfunction 3C
Engine start malfunction
Over speed of engine
Engine stall
Low hydraulic pressure
Cooling water temperature malfunction
Low cooling water
EEPROM malfunction
Engine room temperature malfunction
Software incompatibility
Starter system malfunction
Malfunction of hydraulic pressure switch
Disconnection/short-circuit of cooling water temperature sensor
Lubricant supply function Malfunction
Transformer temperature malfunction
Emergency stop1
External emergency stop1
Emergency stop2(communication)
External emergency stop2
Detection of engine misfire
Fail-safe device malfunction
Control box temperature malfunction
Gas valve malfunction
Low gas pressure
Difference between dual CPUs
Disconnection/short-circuit of Transducers
Disconnection/short-circuit of outside air temperature sensor
Disconnection/short-circuit of Heat Exchanger inlet temperature sensor
Disconnection/short-circuit of Heat Exchanger outlet temperature sensor
Disconnection/short-circuit of generator temperature sensor
Disconnection of exhaust temperature sensor
Disconnection/short-circuit of lubricant temperature sensor
Disconnection/short-circuit of engine room temperature sensor
Disconnection/short-circuit of hydraulic pressure sensor
Disconnection/short-circuit of transformer temperature sensor
Abnormal exhaust temperature
Continuation of no/low-load operation
200 hours or less until next periodic inspection (no malfunction)
Malfunction of engine pulse sensor
Malfunction of starter relay
Over current of generator
Generator temperature malfunction
Generator malfunction
Transmission malfunction between CPUs
Transmission malfunction between Control board and Ignition board
Transmission malfunction between CHP system and System controller
Transmission malfunction between Control board and Display board
Transmission malfunction between CHP system and Inverter
5
6
5
6
5
4
4
4
5
6
4
5
4
5
5/8
4
1/3
8
3/5
4
5
4
1/2
9
7
7
7
7
8
8
8
8
8
8
2
4
1
4
4
4
1
4
4
4
5
2
2/4
8
9
5
5
5
3
3
2/3
1/3
4
*1. Alarm codes are shown on the hour-meter display area of the unit. The operating time is also usually displayed.
*2. The buzzer sounds, the display changes to the alarm screen, and the alarm code is displayed.
107
Display of alarms
Cogeneration
System
package*1
controller*2
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
3) DNO approval
Be sure to take corrective actions properly in accordance with E.R.G83/1.
The following provides the major content on Engineering Recommendation G83/1 (E.R.G83/1).
(1) Compliance with DNO requirements will include
Dual supply labeling should be provided at the service termination, meter position and all points
of isolation to indicate the presence of on-site generation and indicating the position of the main
a.c. switch disconnector (for suitable label see ER G83/1 or see the sample reproduced in
Example Signs and on the back cover of this guide).
At the point of interconnection, the following information is to be displayed
(typically all displayed on the circuit diagram).
Circuit diagram showing the relationship between the inverter equipment and supply.
A summary of the protection settings incorporated within the equipment.
A contact telephone number for the supplier/installer/maintainer of the equipment.
(2) Labeling
Requirements for labeling are contained within the relevant sections of this guide. Example labels
can be seen below.
All labels must be clear, easily visible, constructed and affixed to last and remain legible for the
lifetime of the system.
WARNING
dual supply
108
(3) APPENDIX
APPENDIX 1
Note: The processes shown here only refer to the interface between the Installer and the DNO, it
may also be necessary for the Installer / User to inform the relevant Meter Operator and
Supplier that a SSEG has been installed.
Stage 1 Process
(Single installation)
Stage 2 Process
(Planned / Multiple installation)
Planned installation of
multiple SSEGs in the
same geographic area.
Installer submits
Commissioning pro-forma
(Appendix 3) to local DNO
within 30 days of
commissioning.
Installer submits
Commissioning pro-forma for
each SSEG (Appendix 3)
to the local DNO within 30 days
of commissioning.
031007-00E
109
APPENDIX 2
Application for the connection of multiple SSEG units in parallel with the public distribution
Network - in accordance with Stage 2 of Engineering Recommendation G83/1. It is only necessary
to submit one Application Pro-forma per multiple installation project.
This information is to be provided to the DNO prior to the installation of a SSEG unit(s) in order
that a DNO can assess the potential impact that the connection will have on the Network.
Project Details
Site/project address (inc. post code)
Telephone number
Customer supply number(s) (MPAN)
use separate sheet if necessary
Distribution Network Operator (DNO)
Installer Details
Installer
Accreditation/Qualification:
Address (incl post code)
Contact person
Telephone Number
Fax Number
E-mail address
SSEG Details
SSEG owner
SSEG location within the installation
Total number of SSEG units to be installed
under this project, to include SSEG Unit
capacity in kVA and location.
110
I declare that this installation has been designed to comply with the requirements of ER G83/1
Name and signature:
Date:
Accreditation/Qualification:
yes / no
As a representative of the DNO, I give, in principle, permission for the connection of these SSEG units. If "no",
see comments below
yes / no
Comments
DNO:
Contact:
111
Date:
APPENDIX 3
Confirmation of commissioning of a SSEG unit connected in parallel with the public distribution
Network - in accordance with Engineering Recommendation G83/1. One Commissioning Proforma per installation is to be submitted to the DNO.
Site Details
Property address (inc. post code)
Telephone number
Customer supply number (MPAN)
Distribution Network Operator (DNO)
Contact Details
SSEG owner
Contact person
Contact telephone number
SSEG Details
Manufacturer and model type
Serial number of SSEG
Serial number / version numbers of software
(where appropriate)
SSEG rating (A) and power factor
(under normal running conditions)
Maximum peak short circuit current (A)
Type of prime mover and fuel source
Location of SSEG within the installation
Location of multi pole isolator
112
Installer Details
Installer
Accreditation/Qualification:
Address (incl post code)
Contact person
Telephone Number
Fax Number
E-mail address
Information to be Enclosed
Final copy of circuit diagram
SSEG Test Report or web address if appropriate (not necessary if already provided
e.g. under a Stage 2 connection)
Computer print out (where possible) or other schedule of protection settings
Electricity meter(s) make and model:
Signature:
Date:
113
Title
Type of Business:
Completion date:
Completion date:
Witness (signature):
Tel:
Company Name:
Completion date:
Tel:
Company Name:
Tel:
Company Name:
Tel:
Company Name:
Department
Address:
Tel:
Customers Name:
hr
Special Notes
Measurement
Defects are described
in the Special Notes.
Supplement
Fastening
None
Repair
Adjustment
Good
Check the manual start and stop. (Check the operation, the lamps of the system
controller, or the switch-over.)
Check the start and the stop of the timer.
Check the emergency stop. (Check using a buzzer.)
Is the cogeneration unit installed outdoors? If it is installed indoors, has the installation
work, including that for the discharge of exhaust gas, been performed correctly?
Is the space for safe maintenance secured?
Is the isolation distance from flammable substances secured?
Is the base firm and horizontal?
Is the unit fixed firmly with anchor bolts?
Are the piping and wiring installed as designed?
Check the cooling water level.
Check the engine oil level.
Confirm whether there is a power earth leakage breaker to the unit
or not. Check the capacity. (40 A or more)
Check the supply voltage of the unit. (Single-phase 230 V)
Check the grounding work.
Exhaust drain piping of the unit
Check the isolation of the exhaust gas outlet.
Check the air inlet and outlet of the unit (clogging, isolation from the windows).
Check the presence of fuel gas leaks.
(Cogeneration Package)
Installation Site:
Serial Number:
hr
Hour-Meter
Model:
Cogeneration Package
Entry Method
Upstream of the
grid connected point /
(Hz)
(Hz)
Items
(A)
(C)
Timer Value
Stop
(MPa)
(C)
(C)
(min-1)
(%)
(C)
(V)
(Hz)
(A)
(mA)
(sec.)
(sec.)
(sec.)
(sec.)
mm2
Junction
box
mA
kW
mm2
(Appendix 7)
Transmission start power
Transmission stop power
From
(%)
(%)
to
Start
Outlet:
N phase
Contents
(V)
(V)
Setting Value
Setting Items
Others (
AT /
Via a junction
box
mm2 / DC side
AF /
Directly to the
distribution board
AC side
Demand power