Professional Documents
Culture Documents
Reinforced concrete slabs are one of the most widely used structural elements. In many
structures, in addition to providing a versatile and economical method of supporting gravity loads,
the slab also forms an integral portion of the structural frame to resist lateral forces.
Usually a slab is a broad, flat plate, with top and bottom surfaces parallel or nearly so. It may
be supported by reinforced concrete beams, by masonry or reinforced concrete walls, by structural
steel members, directly by columns, or continuously by the ground.
The design of any slab system may be divided into the following steps:
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
FLAT PLATE
For relatively light loads as in apartments or offices, suitable span from 4.5m to 6m with live
load LL = 3~5kN/m2.
Advantages
Low cost formwork
Exposed flat ceilings
Fast
Disadvantages
Low shear capacity
Low stiffness (notable deflection)
FLAT SLAB
WAFFLE SLAB
Two-way joist system, suitable span from 7.5m to 12m with LL = 4~7.5kN/m2.
Advantages
Carries heavy loads
Attractive exposed ceilings
Fast
Disadvantages
Formwork with panels is expensive
2
One-way Slab on beams suitable span 3m to 6m with LL = 3~5kN/m2. Can be used for
larger spans with relatively higher cost and higher deflections.
One-way joist system suitable span 6m to 9m with LL = 4~6kN/m2.
Deep ribs, the concrete and steel quantities are relative low,
Expensive formwork expected.
ln/20
ln/24
ln/28
Cantilever
ln/10
Table1. One way slab design thickness (ACI 318-14 table 7.3.1.1).
Where
lb, long direction (m);
la, short direction (m);
ln, clear span in long direction (m);
TWO WAY SLAB DESIGN
la / lb < 0.5
Thickness slab
Where
lb, long direction (m);
la, short direction (m);
P, panel perimeter (m)
= 1.2DL + 1.6LL
Where
DL
supports.
LL
Dead Load includes own weight of the slab in addition to the covering materials it
Live Load is dependent on the intended use of the slab.
Interior Spans :
Mu = wuln2 / 16
Negative Moment
Coefficient
Ca,neg , Cb,neg , Ca,pos,dl , Cb,pos,dl, Ca,pos,ll, Cb,pos,ll
Where
lna, length of clear span in short direction (m);
lnb, length of clear span in long direction (m);
Ca , Cb , tabulated moment coefficients by table 2~5.
Table 5. Ratio of load W in la and lb directions for shear in slab and load on supports.
= Ca,negWula2
= Cb,negWulb2
= Ca,pos,dlWu,dlla2 + Ca,pos,llWu,llla2
= Cb,pos,dlWu,dllb2 + Cb,pos,llWu,lllb2
= 1/3*Ma,pos
= 1/3*Mb,pos
9
Where
Wu,
Wu
Wu,dl
Wu,ll
The moments in column strips should be taken as 2/3 of middle strip moment in respective
directions.
shrinkage = 0.0018
fc 28 MPa
1 = 0.85
28 MPa < fc 56 MPa
fc > 56 MPa.
1= 0.65
Reinforcement
10
Where
At first assumed a to calculate As ; that value can substituted in equation of a to get a better
estimate of a and hence a new (d-a/2) can be determined.
For structural slabs of uniform thickness the minimum area of tensile reinforcement, As,min in
the direction of the span shall be the same as temperature and shrinkage reinforcement area. In no
case is the reinforcement ration to be less than 0.0014.
In slabs, primary, flexural reinforcement shall be spaced not farther apart than three times
slab thickness or 450mm. Shrinkage and temperature reinforcement shall be spaced not farther
apart than 5times the slab thickness or 450mm.
TWO WAY SLAB DESIGN
Reinforcement shall be determined for short direction and long direction separately as
follows;
Short Direction
Mid-span
Continuous Edge
Discontinuous Edge
Long Direction
Mid-span
Continuous Edge
Discontinuous Edge
Where
min s max OK
As = s b d
Where
b, slab section 1m;
d, effective depth (m).
s = b/n
11
Where
n, number of reinforcements n = As/A .
smax = min(3h, 450mm)
s > 1.5h
Reinforcement for Column Strip
Bars selected for middle strip are used in column strips, with the spacing 3/2 times that in the
middle strip, but spacing 2h.
Make sure that the net tensile strain in the reinforcement, t doesnt exceed 0.004. Compute
the area of shrinkage reinforcement,
Where
Shrinkage Reinforcement
As = shrinkage b h
smax = min(5h, 450mm)
At d distance Vu,
Vc > Vu , slab design for shear is OK, otherwise slab thickness should be revised.
Or calculate the maximum spacing for a given bar size (or Av) from:
1. Live load deflection
l = 3Mblb2/32EcIe
if
Stirrup is minimum
if
Stirrup is required
if
Concrete is enough
if
Immediate deflection is also termed as Short-Term deflection and calculated using the
formula given in Table 6.
13
Determination of Ie
Where
yt
= distance from centroid axis of gross section, neglecting reinforcement, to
extreme fiber in tension, m.
fr
= modulus of rupture of concrete,
, N/mm2.
Ie for Continuous Span
Ie
= 0.5Iem + 0.25(Ie1 + Ie2)
Where
Iem
= effective moment of inertia for the mid-span section,
Ie1, Ie2 = negative moment sections at the respective beam ends.
long
= d,short *
Where,
=
=
=
2.0
12 months
1.4
6 months
3 months
Type of member
Flat roofs not supporting or attached to
nonstructural
elements likely to be damaged by large
deflection.
Floors not supporting or attached to
nonstructural
elements likely to be damaged by large
deflection.
Roof or floor construction supporting
or attached to
nonstructural elements likely to be
damaged by large
deflection.
Roof or floor construction supporting
or attached to
nonstructural elements not likely to be
damaged by
large deflection.
Table7. Value of
1.2
1.0
Deflection to be considered
Deflection
limitation
l/180
l/360
l/480
l/240
Total Deflection
Total
= long + short
Deflection should be calculated along both direction and maximum values will be considered
(ACI code 9.5.2.6).
15
RECTANGULAR BEAM
STEPS 1 ASSUME h
Simply
Supported
One End
Continuous
Both End
Continuous
Cantilever
L/16
L/18.5
L/21
L/8
STEPS 2 CALCULATE d
d = h Effective cover
16
Mn Mu
Calculate
Calculate
Calculate
Calculate
Doubly Reinforced Section Design:
Calculate
Calculate
In accordance with the safety provisions of the ACI Code, the net tensile strain is checked,
and if t 0.005, this nominal capacity is reduced by the factor = 0.9. For t between 0.005 and
0.004, must be adjusted, as discussed earlier.
1.
a.
b.
c. determine
d. As,max = bd(max + ) As
6. If compression steel is not yield,
a.
determine
= 0.85fcab
b. determine
check max (-f s/fy), As,max = bd(max + fs/fy) As
c.
d.
e. determine
determine
Vu Vn
18
Where Av
s
If
Stirrup is minimum
If
Stirrup is required
if
Concrete is enough if
Case
Case
Where
T-SHAPE BEAM
1.
2.
3.
4.
Compute the practical moment strength (Mn) assuming the total effective flange is
supporting the compression.
5.
If the practical moment strength (Mn) is bigger than the design moment (Mu), the
beam will be calculated as a rectangular T-beam with the effective flange width b. If the practical
moment strength (Mn) is smaller than the design moment (M u), the beam will behave as a true Tshape beam.
6.
Find the approximate lever arm distance for the internal couple.
7.
8.
9.
10.
20
Column Design
The design procedure for the reinforced concrete columns of the structure involves the
following steps:
Generate axial force/biaxial moment interaction surfaces for all of the different concrete section
types of the model. A typical biaxial interaction surface is shown in Figure 1. When the steel is
undefined, the program generates the interaction surfaces for the range of allowable reinforcement 1 to 8 percent for Ordinary and Intermediate moment resisting frames (ACI 10.9.1) and 1 to 6
percent for Special moment resisting frames (ACI 21.4.3.1).
Calculate the capacity ratio or the required reinforcing area for the factored axial force and biaxial
(or uniaxial) bending moments obtained from each loading combination at each station of the
column. The target capacity ratio is taken as one when calculating the required reinforcing area.
Design the column shear reinforcement.
The following four sections describe in detail the algorithms associated with this process.
Spiral Columns
Spiral columns are cylindrical columns with a continuous helical bar wrapping around the
column. The spiral acts to provide support in the transverse direction and prevent the column from
barreling. The amount of reinforcement is required to provide additional load-carrying capacity
greater than or equal to that attributed from the shell as to compensate for the strength lost when the
shell spalls off. With further thickening of the spiral rebar, the axially loaded concrete becomes the
weakest link in the system and the strength contribution from the additional rebar does not take
effect until the column has failed axially. At that point, the additional strength from spiral comes
into play and prevents catastrophic failure, instead giving rise to a much slower ductile failure.
Tied Columns
Tied columns have closed lateral ties spaced approximately uniformly across the column. The
spacing of the ties is limited in that they must be close enough to prevent barreling failure between
them, and far enough apart that they do not interfere with the setting of the concrete. The ACI
codebook puts an upward limit on the spacing between ties.
The strength of short columns is controlled by the strength of the material and the geometry
of the cross section. Reinforcing rebar is placed axially in the column to provide additional axial
stiffness. Accounting for the additional stiffness of the steel, the nominal loading capacity P n for the
column in terms of the maximum compressive stress of the concrete f c, the yield stress of the steel
fy, the gross cross section area of the column Ag, and the total cross section area of the steel rebar
Ast.
Ast
= 0.75
Tied column:
Pn(max) = 0.80[0.85 fc (Ag - Ast) + fyAst],
= 0.70
g = Ast /Ag
g = Ast /Ag
Length Effects
ACI permits neglect of length effect when
The clear distance between longitudinal bars must not be less than 1.5 times the nominal bar
diameter nor 1.5in.
Cover
Cover shall be 1.5in. Minimum over primary reinforcement ties or spirals.
Step 1:
Step 2:
Type of Colum
Tie
Spiral
Step 3:
Where
Ag
Ast
23
1.
I.
k
Flexure Design
M As
Shear Design
V As,bar , gap
tor
con
24
In castin-place construction, the single reinforced rectangular beam is uncommon. The Tshape and L-shape beams are typical types of beam because the beams are built monolithically with
the slab. When slab and beams are poured together, the slab on the beam serves as the flange of a Tbeam and the supporting beam below slab is the stem or web. For positive applied bending
moment, the bottom of section produces the tension and the slab acts as compression flange. But
negative bending on a rectangular beam puts the stem in compression and the flange is ineffective
in tension. Joists consist of spaced ribs and a top flange.
Design Procedure
Rectangular Beam
1.
Assume the depth of beam using the ACI Code reference, minimum thickness unless
consideration the deflection.
2.
3.
4.
5.
6.
Compute maximum possible nominal moment for singly reinforced beam (Mn).
7.
Decide reinforcement type by Comparing the design moment (M u) and the
maximum possible moment for singly reinforced beam (Mn). If Mn is less than Mu, the beam is
designed as a doubly reinforced beam else the beam can be designed with tension steel only.
8.
couple)
9.
10.
Find necessary residual moment, subtracting the total design moment and the
moment capacity of singly reinforced section.
11.
12.
13.
14.
T-shape Beam
1.
2.
3.
4.
Compute the practical moment strength (Mn) assuming the total effective flange is
supporting the compression.
5. If the practical moment strength (Mn) is bigger than the design moment (Mu), the beam
will be calculated as a rectangular T-beam with the effective flange width b. If the practical moment
strength (Mn) is smaller than the design moment (Mu), the beam will behave as a true T-shape
beam.
6. Find the approximate lever arm distance for the internal couple.
7. Compute the approximate required steel area.
8. Design the reinforcement.
9. Check the beam width.
10. Compute the actual effective depth and analyze the beam.
26
27