SITE INSPECTION AND TEST RECORD

Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)
ALGIHAZ CO. LTD
Site:

25/02/2013

SEC-WOA
Panel Ref:

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

1 of 3

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

30/31

FINAL SETTING TEST:


1. RELAY DETAILS:
Type No :

P122

Designation

51NER

Model No :

MiCOM P122B00Z112CD0

Nominal Current : In

1/5 A, 50/60Hz

Serial Number

360418

Aux. Volts

24-250 V DC, 48-240 V AC

Make

ALSTOM

: Vx

2. VISUAL INSPECTION:
Sl. No

Description

Inspect For Physical Damage / Defects

Verify Connections As Per Approved Drawing

Check Tightness Of All Connections

Check relay version and switching elements on printed circuit board

Checked

3. GENERAL CHECK:
Description

Sl. No
1

Auxiliary voltage value on terminals 33 ( + ) and 34 ( - )

Watchdog contact when relay OFF

Watchdog contact when relay ON

Check if the frequency is set on required value

Checked

Terminals 35- 36

Close

Terminals 37- 36

Open

Terminals 35- 36

Open

Terminals 37- 36

Close

4. BINARY INPUT OPERATION CHECK:


Test equipment used
FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Over Current & Earth Fault Relay


(MICOM P122)

Date:

25/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

Terminal No.

Input No.

30/31

Active

Function Assigned

24

High

Future use

26

28

High

Future use

17

19

High

Not Used

(+)

(-)

OPTO 1

22

OPTO 2
OPTO 3

2 of 3

Result

5. BINARY OUTPUT CONTACT CHECK:


Commission Test Test Mode Contacts Blocked. Check Test Pattern Each BO.
Output No.

Terminal No.

Type

Function Assigned

42

NC

Spare

62

NO

Trip Stage-2

10 8

NC

Spare

12 8

NO

Trip Stage-1

RL 3

14 16

NO

Trip Stage-2

RL 4

18 20

NO

Trip Stage-2

RL 5

13

NO

Trip Stage-2

RL 6

57

NO

Spare

RL 1
RL 2

6.1.

6.2.

Result

FIXED LED INDICATIONS TEST:


LED No.

LED Label

Color

LED HI

Trip

Red

LED H2

Alarm

Yellow

LED H3

Warning

Yellow

LED H4

Healthy

Green

Result

LED INDICATIONS TEST: (RIGHT SIDE LED)


LED No.

LED Label

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Color
Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :

Result

SITE INSPECTION AND TEST RECORD


Description:

End Client:

Date:

Over Current & Earth Fault Relay


(MICOM P122)

25/02/2013

SEC-WOA
Panel Ref:

ALGIHAZ CO. LTD

Sheet:

+R06.2- 13.8/11 kV Transformer T1 Protn. Panel 2

Site:

Device ID:

project no.:

13.8/11kV Tabuk Air Base S/S

51NER

30/31

LED H5

NER Pickup

Red

LED H6

Stage 1 Trip

Red

LED H7

Stage 2 Trip

Red

LED H8

Spare

Red

7.

3 of 3

MEASUREMENT VALUE TEST:


CT Ratio: 300/1

Inj. Current
(A)

Calculated
Current
( A)

0.25

75.0

0.50

150.0

Relay Reading ( A )
R
Prim.

1.00
300.0
Deviation: Typical 0.5% at In ,
8.
8.1

Y
%Error

Prim.

B
%Error

Prim.

%Error

Manual : Schneider Technical Guide P12x/EN AD/Eb6

STAGE 1 (Ie>) EARTH FAULT :


PICK UP TEST:
Measured Current IN ( A )

Set Current
( A)

Pick up

Drop off

0.20
Deviation: Pickup: DT =Ies 2%, IDMT =1.1Ies2%
Drop off: DT =0.95Ies 2%, IDMT =1.05Ies2%
8.2

TIMING TEST:

Stage

Set Current ( A )

Set Time ( S )

Injected Current ( A )

Stage 1

0.20

1.20

0.40

Stage 2
0.20
1.40
Deviation : DT = 2%<50ms, IDMT =5%<50ms

0.40

Test equipment used


FREJA 300

SL.NO. of Test equipment


1202561

Multimeter -Fluke 289

20130020

Measured Time IN ( S )

Calibration valid up to
17/09/2013
23/10/2013

Tested by:

Witnessed by: SEC Consultant Engineer

Name: Engr. Ganesan Selvam


Signature & Date :

Name: Engr. Sajid Rafique


Signature & Date :