Professional Documents
Culture Documents
VersionV1.01
Doc. Code: 0SF.455.058 (E)
Issued Date2012.8
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipments do not
agree with the instruction at anywhere, please contact our company in time. We will
provide you with corresponding service.
Preface
Purpose of this manual
This manual describes the functions, operation, installation, and placing into
service of IED CSC-121. In particular, one will find:
Target Audience
Protection engineers, commissioning engineers, personnel concerned with
adjustment, checking, and service of selective protective equipment,
automatic and control facilities, and personnel of electrical facilities and power
plants.
Indication of Conformity
Additional Support
In case of further questions concerning IED CSC-121 system, please contact
SIFANG representative.
Safety information
Avoid to touching the circuitry when covers are removed. The IED
contains electirc circuits which can be damaged if exposed to static
electricity. Lethal high voltage circuits are also exposed when covers
are removed
Using the isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present
Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change
Contents
Chapter 1
Introduction ................................................................................................................. 1
1 Overview ................................................................................................................................... 2
2 Features .................................................................................................................................... 3
3 Functions ................................................................................................................................... 5
3.1
Protection functions..................................................................................................... 5
3.2
Monitoring functions ................................................................................................... 6
3.3
Station communication ................................................................................................ 6
3.4
IED software tools ....................................................................................................... 6
Chapter 2
General IED application .............................................................................................. 9
1 Display information ................................................................................................................ 10
1.1
LCD screen display function ..................................................................................... 10
1.2
Analog display function ............................................................................................ 10
1.3
Report display function ............................................................................................. 10
1.4
Menu dispaly function ............................................................................................... 10
2 Report record ...........................................................................................................................11
3 Disturbance recorder ............................................................................................................. 12
3.1
Introduction ............................................................................................................... 12
3.2
Setting........................................................................................................................ 12
4 Self supervision function ....................................................................................................... 14
4.1
Introduction ............................................................................................................... 14
4.2
Self supervision principle .......................................................................................... 14
4.3
Self supervision report............................................................................................... 14
5 Time synchronization............................................................................................................. 16
5.1
Introduction ............................................................................................................... 16
5.2
Synchronization principle.......................................................................................... 16
5.2.1
Synchronization from IRIG ....................................................................................... 17
5.2.2
Synchronization via PPS or PPM .............................................................................. 17
5.2.3
Synchronization via SNTP ........................................................................................ 17
6 Setting ...................................................................................................................................... 18
6.1
Introduction ............................................................................................................... 18
6.2
Operation principle .................................................................................................... 18
7 Authorization ........................................................................................................................... 19
7.1
Introduction ............................................................................................................... 19
Chapter 3
Overcurrent protection .............................................................................................. 21
1 Overcurrent protection .......................................................................................................... 22
1.1
Introduction ............................................................................................................... 22
1.2
Protection principle ................................................................................................... 22
1.2.1
Time characteristic .......................................................................................... 22
1.2.2
Inrush restraint feature ................................................................................... 23
1.2.3
Direciton determination feature ..................................................................... 24
1.2.4
Logic diagram .................................................................................................. 25
1.3
Input and output signals ............................................................................................ 26
6
1.4
1.1
1.2
Introduction ............................................................................................................... 68
Protection principle ................................................................................................... 68
1.2.1
Protection function description ...................................................................... 68
1.2.2
Logic diagram .................................................................................................. 69
1.3
Input and output signals ............................................................................................ 70
1.4
Setting parameters ..................................................................................................... 71
1.4.1
Setting lists ....................................................................................................... 71
1.5
Reports ...................................................................................................................... 72
1.6
Technical data............................................................................................................ 72
Chapter 8
Thermal overload protection ..................................................................................... 75
1 Thermal overload protection ................................................................................................ 76
1.1
Introduction ............................................................................................................... 76
1.2
Function principle...................................................................................................... 76
1.2.1
Function description........................................................................................ 76
1.3
Input and output signals ............................................................................................ 78
1.4
Setting parameters ..................................................................................................... 78
1.4.1
Setting lists ....................................................................................................... 78
1.5
Reports ...................................................................................................................... 79
1.6
Technical data............................................................................................................ 79
Chapter 9
Overload protection ................................................................................................... 81
1 Overload protection ............................................................................................................... 82
1.1
Protection principle ................................................................................................... 82
1.1.1
Function description........................................................................................ 82
1.1.2
Logic diagram .................................................................................................. 82
1.2
Input and output signals ............................................................................................ 82
1.3
Setting parameters ..................................................................................................... 83
1.3.1
Setting lists ....................................................................................................... 83
1.4
Reports ...................................................................................................................... 83
Chapter 10 Overvoltage protection .............................................................................................. 85
1 Overvoltage protection .......................................................................................................... 86
1.1
Introduction ............................................................................................................... 86
1.2
Protection principle ................................................................................................... 86
1.2.1
Phase to phase overvoltage protection ....................................................... 86
1.2.2
Phase to earth overvlotage protection ......................................................... 86
1.2.3
Logic diagram .................................................................................................. 87
1.3
Input and output signals ............................................................................................ 87
1.4
Setting parameters ..................................................................................................... 88
1.4.1
Setting lists ....................................................................................................... 88
1.5
Reports ...................................................................................................................... 88
1.6
Technical data............................................................................................................ 89
Chapter 11 Undervoltage protection ............................................................................................ 91
1 Undervoltage protection ........................................................................................................ 92
1.1
Introduction ............................................................................................................... 92
1.2
Protection principle ................................................................................................... 92
8
1.2.1
Phase to phase underovltage protection ..................................................... 92
1.2.2
Phase to earth undervoltage protection....................................................... 93
1.2.3
Depending on the VT location ....................................................................... 93
1.2.4
Logic diagram .................................................................................................. 94
1.3
Input and output signals ............................................................................................ 96
1.4
Setting parameters ..................................................................................................... 96
1.4.1
Setting lists ....................................................................................................... 97
1.5
Reports ...................................................................................................................... 97
1.6
Technical data............................................................................................................ 98
Chapter 12 Displacement voltage protection ............................................................................... 99
1 Displacement voltage protection ....................................................................................... 100
1.1
Introduction ............................................................................................................. 100
1.2
Protection principle ................................................................................................. 100
1.2.1
Function description...................................................................................... 100
1.2.2
Logic diagram ................................................................................................ 101
1.3
Input and output signals .......................................................................................... 101
1.4
Setting parameters ................................................................................................... 102
1.4.1
Setting lists ..................................................................................................... 102
1.5
Reports .................................................................................................................... 103
1.6
Technical data.......................................................................................................... 103
Chapter 13 Circuit breaker failure protection ............................................................................ 105
1 Circuit breaker failure protection........................................................................................ 106
1.1
Introduction ............................................................................................................. 106
1.2
Function Description ............................................................................................... 107
1.2.1
Current criterion evaluation ......................................................................... 107
1.2.2
Circuit breaker auxiliary contact evaluation .............................................. 107
1.2.3
Logic diagram ................................................................................................ 108
1.3
Input and output signals ...........................................................................................113
1.4
Setting parameters ....................................................................................................114
1.4.1
Setting lists ......................................................................................................114
1.5
Reports .....................................................................................................................115
1.6
Technical data...........................................................................................................115
Chapter 14 Dead zone protection ................................................................................................117
1 Dead zone protection ...........................................................................................................118
1.1
Introduction ..............................................................................................................118
1.2
Protection principle ..................................................................................................118
1.2.1
Function description.......................................................................................118
1.2.2
Logic diagram ................................................................................................ 121
1.3
Input and output signals .......................................................................................... 122
1.4
Setting parameters ................................................................................................... 123
1.4.1
Setting lists ..................................................................................................... 123
1.5
Reports .................................................................................................................... 123
1.6
Technical data.......................................................................................................... 124
Chapter 15 STUB protection...................................................................................................... 125
1.2.7
Auto-reclosing logic ...................................................................................... 157
1.2.8
AR blocked conditions .................................................................................. 159
1.2.9
Logic diagram ................................................................................................ 160
1.3
Input and output signals .......................................................................................... 163
1.4
Setting parameters ................................................................................................... 164
1.4.1
Setting lists ..................................................................................................... 164
1.5
Reports .................................................................................................................... 165
1.6
Technical data.......................................................................................................... 166
Chapter 19 Secondary system supervision................................................................................. 168
1 Current circuit supervision .................................................................................................. 169
1.1
Function description ................................................................................................ 169
1.2
Input and output signals .......................................................................................... 169
1.3
Setting parameters ................................................................................................... 169
1.3.1
Setting lists ..................................................................................................... 170
1.4
Reports .................................................................................................................... 170
2 Fuse failure supervision ...................................................................................................... 171
2.1
Introduction ............................................................................................................. 171
2.2
Function principle.................................................................................................... 171
2.2.1
Three phases (symmetrical) VT Fail .......................................................... 171
2.2.2
Single/two phases (asymmetrical) VT Fail ................................................ 172
2.2.3
Logic diagram ................................................................................................ 172
2.3
Input and output signals .......................................................................................... 173
2.4
Setting parameters ................................................................................................... 174
2.4.1
Setting list ....................................................................................................... 174
2.5
Reports .................................................................................................................... 175
2.6
Technical data.......................................................................................................... 175
Chapter 20 Monitoring ............................................................................................................... 176
1 Synchro-check reference voltage supervision................................................................. 177
2 Check auxiliary contact of circuit breaker......................................................................... 177
Chapter 21 Station communication ............................................................................................ 178
1 Overview ............................................................................................................................... 179
1.1
Protocol ................................................................................................................... 179
1.1.1
IEC61850-8 communication protocol ......................................................... 179
1.1.2
IEC60870-5-103 communication protocol ................................................. 179
1.2
Communication port ................................................................................................ 180
1.2.1
Front communication port ............................................................................ 180
1.2.2
RS485 communication ports ....................................................................... 180
1.2.3
Ethernet communication ports .................................................................... 180
1.3
Technical data.......................................................................................................... 180
1.4
Typical substation communication scheme ............................................................. 183
1.5
Typical time synchronizing scheme ........................................................................ 183
Chapter 22 Hardware ................................................................................................................. 186
1 Introduction ........................................................................................................................... 187
1.1
IED structure ........................................................................................................... 187
12
1.2
IED module arrangement ........................................................................................ 187
Local human-machine interface ........................................................................................ 188
2.1
Introduction ............................................................................................................. 188
2.2
Liquid crystal display (LCD) .................................................................................. 189
2.3
LED ......................................................................................................................... 189
2.4
Keyboard ................................................................................................................. 190
2.5
IED menu ................................................................................................................ 191
2.5.1
Menu construction ......................................................................................... 191
2.5.2
Operation status ............................................................................................ 193
2.5.3
Reports search .............................................................................................. 194
2.5.4
Set time........................................................................................................... 194
2.5.5
Contrast .......................................................................................................... 195
2.5.6
Settings ........................................................................................................... 195
2.5.7
IED setting ...................................................................................................... 195
2.5.8
Test binary output .......................................................................................... 196
2.5.9
Testing operation ........................................................................................... 196
Analog input module ............................................................................................................ 197
3.1
Introduction ............................................................................................................. 197
3.2
Terminals of analog input module ........................................................................... 197
3.3
Technical data.......................................................................................................... 200
Communication module ...................................................................................................... 201
4.1
Introduction ............................................................................................................. 201
4.2
Terminals of Communication module ..................................................................... 201
4.3
Substaion communication port ................................................................................ 202
4.3.1
RS232 communication ports ....................................................................... 202
4.3.2
RS485 communication ports ....................................................................... 202
4.3.3
Ethernet communication ports .................................................................... 202
4.3.4
Time synchronization port ............................................................................ 203
4.4
Technical data.......................................................................................................... 203
Binary input module ............................................................................................................. 205
5.1
Introduction ............................................................................................................. 205
5.2
Terminals of Binary Input Module .......................................................................... 205
5.3
Technical data.......................................................................................................... 206
Binary output module .......................................................................................................... 208
6.1
Introduction ............................................................................................................. 208
6.2
Terminals of Binary Output Module ....................................................................... 208
6.3
Technical data.......................................................................................................... 213
Power supply module .......................................................................................................... 214
7.1
Introduction ............................................................................................................. 214
7.2
Terminals of Power Supply Module........................................................................ 214
7.3
Technical data.......................................................................................................... 216
Techinical data ..................................................................................................................... 217
8.1
Type tests................................................................................................................. 217
8.1.1
Product safety-related tests ......................................................................... 217
8.1.2
Electromagnetic immunity tests .................................................................. 218
8.1.3
DC voltage interruption test ......................................................................... 220
8.1.4
Electromagnetic emission test .................................................................... 220
8.1.5
Mechanical tests............................................................................................ 220
8.1.6
Climatic tests.................................................................................................. 221
8.2
CE Certificate .......................................................................................................... 222
8.3
IED design ............................................................................................................... 222
Chapter 23 Appendix ................................................................................................................. 224
1 General setting list ............................................................................................................... 225
1.1
Function setting list ................................................................................................. 225
1.2
Binary setting list..................................................................................................... 230
2 General report list ................................................................................................................ 238
3 Typical connection ............................................................................................................... 244
4 Time inverse characteristic ................................................................................................. 247
4.1
11 kinds of IEC and ANSI inverse time characteristic curves ................................ 247
4.2
User defined characteristic ...................................................................................... 247
4.3
Typical inverse curves ............................................................................................. 248
5 CT requirement .................................................................................................................... 261
5.1
Overview ................................................................................................................. 261
5.2
Current transformer classification ........................................................................... 261
5.3
Abbreviations (according to IEC 60044-1, -6, as defined)...................................... 262
5.4
General current transformer requirements............................................................... 263
5.4.1
Protective checking current ......................................................................... 263
5.4.2
CT class .......................................................................................................... 264
5.4.3
Accuracy class ............................................................................................... 265
5.4.4
Ratio of CT ..................................................................................................... 265
5.4.5
Rated secondary current.............................................................................. 266
5.4.6
Secondary burden ......................................................................................... 266
5.5
Rated equivalent secondary e.m.f requirements ...................................................... 267
5.5.1
Line differential protection ............................................................................ 267
5.5.2
Transformer differential protection .............................................................. 268
5.5.3
Busbar differential protection....................................................................... 269
5.5.4
Distance protection ....................................................................................... 269
5.5.5
Definite time overcurrent protection and earth fault protection .............. 270
5.5.6
Inverse time overcurrent protection and earth fault protection .............. 271
Chapter 1 Introduction
Chapter 1 Introduction
Chapter 1 Introduction
Overview
The CSC-121 is selective, reliable and high speed breaker management and
backup protection IED (Intelligent Electronic Device), which is used as
backup protection cooperating with main protection in different applications
such as overhead line, cable, transformer, reactor and busbar protection. It
can also work as a dedicated breaker management relay for circuit breaker.
The IED has powerful capabilities to cover following applications:
Chapter 1 Introduction
Features
Chapter 1 Introduction
substation automation system by IEC60870-5-103 protocol
Chapter 1 Introduction
Functions
3.1
Protection functions
Description
ANSI Code
IEC 61850
IEC 60617
Logical Node
graphical
Name
symbol
Current protection
3IINV>
Overcurrent protection
50,51,67
PTOC
3I >>
3I >>>
I0INV>
PEFM
I0>>
I0>>>
50Ns, 51Ns,
3INE>
67Ns
3INE>>
46
protection
Thermal overload protection
49
PTTR
Ith
Overload protection
50OL
PTOC
3I >OL
Voltage protection
Overvoltage protection
59
PTOV
Undervoltage protection
27
PTUV
64
3U>
3U>>
3U<
3U<<
VE>
50BF
RBRF
I0>BF
I2>BF
50SH-Z
STUB protection
50STUB
PTOC
50PD
RPLD
3I>STUB
3I< PD
I0>PD
I2>PD
25
RSYN
Auto-recloser
79
RREC
OI
5
Chapter 1 Introduction
Description
ANSI Code
94-1/3
IEC 61850
IEC 60617
Logical Node
graphical
Name
symbol
PTRC
3.2
97FF
Monitoring functions
Description
3.3
Station communication
Description
Front communication port
3.4
Chapter 1 Introduction
Functions
Reading measuring value
Reading IED report
Setting
IED testing
Disturbance recording analysis
IED configuration
Printing
Chapter 1 Introduction
Display information
1.1
1.2
1.3
1.4
10
Report record
The report record includes tripping, alarm and operation reports. See Chapter
23 General report list for detail.
11
Disturbance recorder
3.1
Introduction
To get fast, complete and reliable information about fault current, voltage,
binary signal and other disturbances in the power system is very important.
This is accomplished by the disturbance recorder function and facilitates a
better understanding of the behavior of the power system and related primary
and secondary equipment during and after a disturbance. An analysis of the
recorded data provides valuable information that can be used to explain a
disturbance, basis for change of IED setting plan, improvement of existing
equipment etc.
The disturbance recorder, always included in the IED, acquires sampled data
from measured analogue quantities, calculated analogue quantity, binary
input and output signals.
The function is characterized by great flexibility and is not dependent on the
operation of protection functions. It can even record disturbances not tripped
by protection functions.
The disturbance recorder information is saved for each of the recorded
disturbances in the IED and the user may use the local human machine
interface or dedicated tool to get some general information about the
recordings. The disturbance recording information is included in the
disturbance recorder files. The information is also available on a station bus
according to IEC 61850 and IEC 60870-5-103.
Fault wave recorder with great capacity, can record full process of any fault,
and can save the corresponding records. Optional data format or wave format
is provided, and can be exported through serial port or Ethernet port by
COMTRADE format.
3.2
Setting
Abbr.
T_Pre Fault
T_Post Fault
DR_Sample Rate
12
Explanation
Time setting for recording time
before fault occurred
Time setting for recording time
after fault occurred
Sample rate for fault recording
Default
Unit
Min.
Max.
0.05
0.05
0.3
0.50
4.50
Explanation
Default
Unit
Min.
Max.
13
4.1
Introduction
The IED may test all hardware components itself, including loop out of the
relay coil. Watch can find whether or not the IED is in fault through warning
LED and warning characters which show in liquid crystal display and display
reports to tell fault type.
The method of fault elimination is replacing fault board or eliminating external
fault.
4.2
4.3
Abbr.(LCD Display)
14
Description
Sample Err
EquipPara Err
Setting Err
BO No Response
Description
BO Breakdown
BI Config Err
BI configuration error
BO Config Err
BO configuration error
BI Comm Fail
BI communication error
BO Comm Fail
BO communication error
Test BO Un_reset
Test BO unreset
BI Breakdown
BI breakdown
DI Input Err
BI input error
NO/NC Discord
NO/NC discordance
BI Check Err
BI check error
BI EEPROM Err
BI EEPROM error
BO EEPROM Err
BO EEPROM error
Battery Off
Battery Off
Not Used
Not used
Trip Fail
Trip fail
AI Channel Err
AI channel error
3I0 Reverse
3I0 reverse
3I0 Imbalance
3I0 imbalance
15
Time synchronization
5.1
Introduction
Use the time synchronization source selector to select a common source of
absolute time for the IED when it is a part of a protection system. This makes
comparison of events and disturbance data between all IEDs in a SA system
possible.
5.2
Synchronization principle
Time definitions
The error of a clock is the difference between the actual time of the clock, and
the time the clock is intended to have. The rate accuracy of a clock is
normally called the clock accuracy and means how much the error increases,
i.e. how much the clock gains or loses time. A disciplined clock is a clock that
knows its own faults and tries to compensate for them, i.e. a trained clock.
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical
structure. A module is synchronized from a higher level and provides
synchronization to lower levels.
5.2.1
5.2.2
5.2.3
17
Setting
6.1
Introduction
Settings are divided into separate lists according to different functions. The
printed setting sheet consists of two parts -setting list and communication
parameters.
6.2
Operation principle
The setting procedure can be ended at the time by the key SET or QUIT. If
the key SET is pressed, the display shows the question choose setting
zone. The range of setting zone is from 1 to 16. After confirming with the
setting zone-key SET, those new settings will be valid. If key QUIT is
pressed instead, all modification which have been changed will be ignored.
18
Authorization
7.1
Introduction
To safeguard the interests of our customers, both the IED and the tools that
are accessing the IED are protected, subject of authorization handling. The
concept of authorization, as it is implemented in the IED and the associated
tools is based on the following facts:
There are different levels (or types) of guest, super user and protection
engineer that can access or operate different areas of the IED and tools
functionality.
19
20
21
Overcurrent protection
1.1
Introduction
The directional/non-directional overcurrent protection function can be applied
as backup protection functions in various applications for transmission lines.
The directional overcurrent protection can be used based on both the
magnitude of the fault current and the direction of power flow to the fault
location such as parallel lines. Main features of the overcurrent protection are
as follows:
1.2
Protection principle
1.2.1
Time characteristic
The IED is designed with three overcurrent protection stages of which two
22
t=
A_OC
p _OC
i
I_OC
+ B_OC K_OC
Equation 1
where:
A_OC: Time factor for inverse time stage
B_OC: Delay time for inverse time stage
P_OC: index for inverse time stage
K_OC: Time multiplier
1.2.2
1.2.3
90
IA
Ph_Char
U BC_Ref
IA
24
Reverse
where:
Ph_Char: The settable characteristic angle
The assignment of the applied measuring values used in direction
determination shows in Table 2 for different types of faults.
Table 2 Assignment of current and reference voltage for directional element
Phase
Current
Voltage
Ia
U bc
Ib
U ca
Ic
U ab
1.2.4
Logic diagram
The following logic diagram is applicable for phase A. Phase B and phase C
logic diagrams are similar with the phase A logic.
25
AND
AND
VT fail
OR
OC Dir To Equip
AND
VT fail
OC1 Inrush Block Off
0
<Imax_2H_UnBlk
AND
Ia2/Ia1>
T_OC1
Func_OC1
AND
Trip
OC_Inrush Block On
Cross blocking
Ia2/Ia1 >
OR
Ib2/Ib1 >
AND
Ic2/Ic1 >
Cross blocking
T2h_Cross_Blk<
1.3
26
IP1
IP2
IP3
UP1
UP2
UP3
Relay Startup
OC1_Trip
OC2_Trip
OC Inv Trip
Description
IP1
IP2
IP3
UP1
UP2
UP3
Signal
Description
Relay Startup
Relay startup
Trip 3Ph
OC1_Trip
OC2_Trip
OC Inv Trip
1.4
Setting parameters
1.4.1
Setting list
Table 5 Overcurrent protection function setting list
Parameter
Description
Default
Unit
Min.
Max.
I_OC1
2In
0.05
100.0
T_OC1
0.1
0.00
60.00
I_OC2
1.2In
0.05
100.0
T_OC2
0.3
0.00
60.00
12
0.05
100.0
Curve_OC Inv
I_OC Inv
1
1.2In
27
Description
Default
Unit
Min.
Max.
0.05
999.0
stage
K_OC Inv
A_OC Inv
stage
Time factor for inverse time
stage
0.14
0.005
200.0
0.00
60.00
0.005
10.00
B_OC Inv
P_OC Inv
Angle_OC
60
Degree
0.00
90.00
5In
0.10
100.0
0.07
0.50
0.00
60.00
Imax_2H_UnBlk
0.02
current to fundamental
0.2
component
T2h_Cross_Blk
OC1 Inrush
Block
enabled or disabled
Func_OC2
OC2 Direction
OC2 Dir To Sys
OC2 Inrush
Block
enabled or disabled
Func_OC Inv
OC Inv Direction
28
Description
OC Inv Dir To
Sys
OC Inv Inrush
Block
enabled or disabled
Blk OC at VT
Default
Unit
Min.
Max.
Description
Fail
Unit
Min.
Max.
enabled or disabled
OC Init CBF
1.5
Default
Reports
Table 7 Event report list
Information
Description
OC1 Trip
OC2 Trip
OC Inv Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 8 Overcurrent protection technical data
Item
Rang or Value
Tolerance
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
Time delay
1% setting or +40ms, at
200% operating setting
Reset time
approx. 40ms
Reset ratio
Current
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
IEC standard
Normal inverse;
5% setting + 40ms, at 2
Very inverse;
Extremely inverse;
with IEC60255-151
Long inverse
ANSI
Inverse;
5% setting + 40ms, at 2
Short inverse;
Long inverse;
Moderately inverse;
C37.112,
Very inverse;
Extremely inverse;
29
T=
A
i
(
)P 1
I_SET
+B k
5% setting + 40ms, at 2
<I/ISETTING < 20, in accordance
with IEC60255-151
A
Delay of inverse time, B
k
Minimum operating time
Maximum operating time
20ms
100s
Reset mode
instantaneous
Reset time
approx. 40ms,
Directional element
170
0to 90, step 1
3, at phase to phase
voltage >1V
Item
Upper function limit
Range or value
0.25 Ir to 20.00 Ir
Tolerance
3% setting value or
0.02Ir
restraint
nd
to fundamental component
current
Cross-block (IL1, IL2, IL3)
(settable time)
30
1% setting or +40ms
31
1.1
Introduction
The earth fault protection can be used to clear phase to earth faults as system
back-up protection. The earth fault protection is can also be applied for
coordination based on both magnitude of earth fault current and the direction
of power flow to the fault location.
The protection provides the following features:
32
11 kinds of the IEC and ANSI inverse time characteristic curves as well
as optional user defined characteristic
1.2
Protection principle
1.2.1
Time characteristic
The IED is designed with three earth fault protection stages of which two
stages operate as definite earth fault stages and the other one operates with
inverse time-current characteristic. All stages can operate in conjunction with
the integrated inrush restraint and directional functions. This protection
function can operate based on the zero-sequence current which is calculated
by summation of three phase currents or measured from earth phase CT
Furthermore, the stages are independent from each other and can be
combined as desired. They can be enabled or disabled by dedicated binary
setting.
Individual pickup value for each definite stage can be defined in setting value.
By applying the settings, the measured zero sequence current is compared
separately with the setting value for each stage. If zero-sequence current
exceed the associated pickup value, after expiry of the time delay, the trip
command is issued.
The time delay of inverse time characteristic is calculated based on the type
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available, and any user-defined characteristic can be defined using the
following equation:
t=
A_EF
p _EF
i
1
I_EF
+ B_EF K_EF
Equation 2
where:
A_EF: Time factor for inverse time stage
B_EF: Delay time for inverse time stage
P_EF: index for inverse time stage
33
1.2.2
1.2.3
34
Bisector
-3I 0
90
Reverse
0
3U 0_Ref
0_Char
Forward
-3I 0
Bisector
1.2.3.2
90
Reverse
0
3 U 2_ Ref
2_Char
Forward
-3I 2
Bisector
1.2.4
36
Logic diagram
3I0 measured
AND
AND
I02/I01 > Ratio I02/I01
3I01 > 3I0max_2H_UNBLK
1
1
1
OR
3I0 calculated
3I0 measured
OR
Inrush BLK EF
AND
OR
AND
OR
37
VT Fail
OR
Blk EF at VT Fail
AND
U0/I0-
OR
3U0>1V
Direction Meet
3U0 Calculated
EF U2/I2 Dir On
1
VT Fail
AND
Blk EF at VT Fail
U2/I2-
OR
AND
UnBlk EF at VT Fail
UnBlk EF at VT Fail
V1p VT Fail
OR
Blk EF at VT Fail
AND
U0/I0-
Direction Meet
OR
3U0>1V
3U0 Measured
EF U2/I2 Dir On
1
VT Fail
AND
Blk EF at VT Fail
U2/I2-
OR
AND
UnBlk EF at VT Fail
38
Blk EF at CT Fail
Direction Meet
T_EF1
EF1 Trip
T_EF2
EF2 Trip
Func_EF1 On
EF1 Direction On
1
Inrush BLK EF
EF1 Inrush Block On
Direction Meet
Func_EF2 On
EF2 Direction On
1
Inrush BLK EF
EF2 Inrush Block On
AND
Direction Meet
EF INV Direction On
Func_EF INV On
1
Inrush BLK EF
EF INV Inrush Block On
1.3
Relay Startup
EF1 Trip
EF2 Trip
EF Inv Trip
UP1
UP2
UP3
UP4
Description
IP1
39
IP3
IP0
UP1
UP2
UP3
UP4
Signal
Description
Trip 3Ph
EF1 Trip
EF2 Trip
EF Inv Trip
Relay Startup
Relay Startup
1.4
Setting parameters
1.4.1
Setting lists
Table 12 EF protection function setting list
Parameter
3I0_EF1
T_EF1
3I0_EF2
T_EF2
Curve_EF Inv
Explanation
Zero sequence current
setting for stage 1
Time setting for stage 1
Zero sequence current
setting for stage 2
Time setting for stage 2
Inverse time curve of
zero-sequence current
Default
Unit
Min.
Max.
0.5In
0.05
100
0.1
0.00
60.00
0.2In
0.05
100
0.3
0.00
60.00
12
0.05
100
0.05
999.0
0.005
200.0
0.2In
stage
Time Multiplier setting for
K_EF Inv
zero-sequence inverse
time stage
Coefficient setting for
A_EF Inv
zero-sequence inverse
time stage
40
0.14
zero-sequence inverse
0.00
60.00
0.005
10.00
time stage
P_EF Inv
0.02
Direction characteristic
Angle_EF
70
Degree
0.00
90.00
70
Degree
0.00
90.00
0.07
0.50
0.10
100.0
0.07
0.50
0.10
100.0
direction
Direction characteristic
Angle_Neg
angle for
negative-sequence
direction
Ratio for second harmonic
Ratio_I2/I1
current to fundamental
0.2
component
Imax_2H_UnBlk
5In
0.2
fundamental component
3I0max_2H_UnBlk
5In
Explanation
Earth fault stage 1 enabled or
disabled
Direction of earth fault stage 1
enabled or disabled
Default
Unit
Min.
Max.
41
disabled
Func_EF Inv
EF Inv Direction
EF U2/I2 Dir
Blk EF at VT Fail
Blk EF at CT Fail
3I0 Calculated
3U0 Calculated
EF Init CBF
1.5
Reports
Table 14 Event report list
Information
Description
EF1 Trip
EF2 Trip
EF Inv Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
42
Item
Rang or value
Tolerance
3% setting or 0.02Ir
1% setting or +40ms, at 200%
operating setting
Reset time
Reset ratio
Current
Time delay
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
IEC standard
Normal inverse;
IEC60255-151
Very inverse;
5% setting + 40ms, at 2
Extremely inverse;
<I/ISETTING < 20
Long inverse
ANSI
Inverse;
ANSI/IEEE C37.112,
Short inverse;
5% setting + 40ms, at 2
Long inverse;
<I/ISETTING < 20
Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic
T=
A
i
(
)P 1
I_SET
+B k
IEC60255-151
5% setting + 40ms, at 2
<I/ISETTING < 20
20ms
100s
Reset mode
instantaneous
Reset time
approx. 40ms
Directional element
160
3, at 3U01V
43
160
element
Characteristic angle
44
45
1.1
Introduction
The neutral earth fault protection focus on phase to earth faults. The
measuring current is the one from dedicated neutral CT.
The following features are provided:
11 kinds of the IEC and ANSI inverse time characteristic curves as well
as optional user defined characteristic
1.2
Protection principle
1.2.1
Time characteristic
The neutral earth fault protection is provided with three stages from which two
stages operate as definite neutral earth fault stages and the other one
operates with inverse time-current characteristic. 11 kinds of inverse time
characteristics are available. It is also possible to create a user defined time
characteristic. Each stage can operate in conjunction with the integrated
inrush restraint and operate based on measured phase current.
Furthermore, each stage is independent from each other and can be
combined as desired. They can be enabled or disabled by dedicated binary
setting.
46
t=
A_NOC
i
I_NOC
p _NOC
+ B_NOC K_NOC
Equation 3
where:
A_NOC: Time factor for inverse time stage
B_NOC: Delay time for inverse time stage
P_NOC: index for inverse time stage
K_NOC: Time multiplier
By applying proper setting of the aforementioned parameters, the IED
calculates the tripping or alarming time from the measured current in each
phase separately. Once the calculated time has been elapsed, the trip signal
or alarm signal is issued.
1.2.2
1.2.3
Direction determination
The direction determination is performed by comparing the zero sequence
quantities. In current path, the neutral current is measured from the dedicated
neutral CT. In the voltage path, the calculated or measured zero sequence
voltage (3V0) can be used as reference voltage.
In order to satisfy different network conditions and applications, the reference
voltage can be rotated by adjustable angle between 0and 90in clockwise
direction (negative sign). It should be noted that the settings affect all the
directional stages of earth fault element. In this way, the vector of rotated
reference voltage can be closely adjusted to the vector of fault current -3I0
which lags the fault voltage 3V0 by the fault angle 0_Char. This would
provide the best possible result for the direction determination. The rotated
reference voltage defines the forward and reverse area.
Figure 8 shows an example of direction determination.
Bisector
-3I 0
90
Reverse
0
3U 0_Ref
0_Char
Forward
48
-3I 0
Bisector
1.2.4
Logic diagram
>3I0_NOC1
NOC1 Dir To Sys
AND
Func_NOC1
AND
T_NOC1
Trip
VT fail
OR
NOC1 Dir To Equip
AND
VT fail
NOC1 Inrush Block Off
0
<3I0max_2H_UnBlk
AND
I02/I01>
Figure 9 Logic diagram for stage 1 of neutral earth fault protect ion
1.3
Relay Startup
NOC1_Trip
NOC2_Trip
NOC Inv Trip
Description
I5
UP1
UP2
UP3
UP4
Description
Relay Startup
Relay Startup
Trip 3Ph
NOC1 Trip
NOC2 Trip
stage trip
1.4
Setting parameters
1.4.1
Setting lists
Table 18 Neutral earth fault protection function setting list
Parameter
Description
Default
Unit
Min.
Max.
3I0_NOC1
0.5In
0.05
100.0
0.1
0.00
60.00
0.2In
0.05
100.0
0.3
0.00
60.00
12
0.05
100.0
0.05
999.0
T_NOC1
3I0_NOC2
T_OC2
Curve_NOC Inv
3I0_NOC Inv
stage
Time multiplier for inverse time
K_NOC Inv
stage
1
0.2In
A_NOC Inv
0.14
0.005
200.0
B_NOC Inv
0.00
60.00
P_NOC Inv
0.005
10.00
Angle_NOC
70
Degree
0.00
90.00
2In
0.10
100.0
0.07
0.50
Min.
Max.
3I0max_2H_UnBlk
0.02
current to fundamental
0.2
component
Table 19 Neutral earth fault protection binary setting list
Name
Func_NOC1
NOC1 Direction
50
Description
Neutral earth fault stage 1 enabled or
disabled
Direction of neutral earth fault stage 1
enabled or disabled
Default
Unit
Description
NOC1 Dir To
Sys
NOC1 Inrush
Block
Func_NOC2
NOC2 Direction
NOC2 Dir To
Sys
NOC2 Inrush
Block
Func_NOC Inv
NOC Inv
Direction
or disabled
Unit
Min.
Max.
Block
enabled or disabled
Blk NOC at VT
Fail
3U0 Calculated
1.5
Default
1
1
Reports
Table 20 Event report list
Information
Description
NOC1 Trip
NOC2 Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
51
Item
Rang or value
Tolerance
3% setting or 0.02Ir
1% setting or +40ms, at 200%
operating setting
Reset time
Reset ratio
Current
Time delay
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
IEC standard
Normal inverse;
5% setting + 40ms, at 2
Very inverse;
Extremely inverse;
with IEC60255-151
Long inverse
ANSI
Inverse;
5% setting + 40ms, at 2
Short inverse;
Long inverse;
Moderately inverse;
C37.112,
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic
T=
A
i
)P 1
I_SET
+B k
5% setting + 40ms, at 2
<I/ISETTING < 20, in accordance
with IEC60255-151
20ms
100s
Reset mode
instantaneous
Reset time
approx. 40ms
Directional element
52
160
Characteristic angle
160
Characteristic angle
3, at 3U01V
3, at 3U22V
53
54
55
1.1
Introduction
In power networks with high impedance earthing, the phase to earth fault
current is significantly smaller than the short circuit currents. Another difficulty
for earth fault protection is that the magnitude of the phase to earth fault
current is almost independent of the fault location in the network.
Sensitive earth fault protection can be used to detect and give selective trip of
phase to earth faults in isolated or compensated networks. The protection
function also can be applied to detect high impedance earth faults in solidly or
low-resistance earthed networks.
Sensitive earth fault protection integrated in the IED provides following
features:
Dedicated sensitive CT
1.2
Protection principle
1.2.1
Time characteristic
The IED is provided with three sensitive earth fault protection stages of which
56
t=
A_SEF
p _SEF
i
I_SEF
+ B_SEF K_SEF
Equation 4
where:
A_SEF: Time factor for inverse time stage
B_SEF: Delay time for inverse time stage
P_SEF: index for inverse time stage
K_SEF: Time multiplier
By applying proper setting of the aforementioned parameters, the IED
calculates the tripping or alarming time from the measured current in each
phase separately. Once the calculated time has been elapsed, the trip signal
or alarm signal is issued.
1.2.2
57
1.2.2.1
U0/I0- measurement
In this method, the direction determination is performed by comparing the
displacement angle between zero sequence system quantities. In current
path, the measured current Is from the sensitive input is applied. In the
voltage path, the displacement voltage VN is used as reference voltage, if it is
connected. Otherwise the IED calculates the zero sequence voltage 3V0 from
the summation of the three phase voltages. The condition for direction
determination with 3V0 quantity is that the magnitude of 3V0 is larger than the
setting value.
Contrary to the directional phase elements, which work with the un-faulted
voltage as reference voltage, for the sensitive earth fault protection, the zero
sequence voltage is used as the reference voltage for direction determination.
Depending on the connection of voltage transformer, the corresponding
reference voltage is VN or 3V0 (3V0=VA+VB+VC).
58
90
- I NS
Bisector
NS_Char
0
3U0_Ref
I NS
1.2.2.2
Cos measurement
Similar to U0/I0- method, the direction determination is performed in cos
method by using the measured current Is from sensitive current input together
with the measured or calculated displacement voltage. In this context, the
measured displacement voltage is used if it is connected. Otherwise the IED
calculates the zero sequence voltage 3V0 from the summation of the three
phase voltages. The condition for direction determination with 3V0 quantity is
that the magnitude of 3V0 is larger than the setting value.
Unlike to U0/I0- method, direction determination is performed in Cos
method by using those component of the residual current which is
perpendicular to the directional characteristic (axis of symmetry). Figure 11
shows how the IED adopts complex vector diagram for direction
determination. As can be seen, displacement voltage 3V0 is the reference
59
IS
90
Forward
3U0_Ref
- IS
1.2.3
Logic diagram
U0/I0-
AND
Forward
3U0>
IsCOS
AND
Forward
3U0>
60
VT Fail
OR
3U0 Calculated On
AND
Forward
OR
Forward Release
AND
V1p VT Fail
OR
Is >
Func_SEF1
1
Forward Release
T_SEF1
AND
Trip/Alarm
Figure 15 Logic diagram for the first definite stage of sensitive earth fault protection
Is Inverse
Func_SEF Inv
1
Forward Release
AND
Trip/Alarm
Figure 16 Logic diagram for the inverse time stage of sensitive earth fault protection
1.3
61
Relay Startup
SEF1 Trip
SEF1 Alarm
SEF2 Trip
SEF2 Alarm
SEF Inv Trip
SEF Inv Alarm
Description
Is
UP1
UP2
UP3
UP4
Signal
Description
Relay Startup
Relay Startup
Trip 3Ph
SEF1 Trip
SEF1 Alarm
SEF2 Trip
SEF2 Alarm
stage trip
Sensitive earth fault protection inverse time
stage alarm
1.4
Setting parameters
1.4.1
Setting list
Table 24 Sensitive earth fault protection function setting list
Parameter
62
Description
Default
Unit
Min.
Max.
Description
0.005
1.00
0.1
0.00
60.00
0.1
0.005
1.00
0.5
0.00
60.00
12
0.00
1.00
0.05
999.0
P_SEF Inv
Angle_SEF
U_SEF
stage 2
Curve_SEF Inv
IsCOS_SEF
0.2
T_SEF2
B_SEF Inv
Max.
I_SEF2
A_SEF Inv
Min.
stage 1
T_SEF1
K_SEF Inv
Unit
I_SEF1
I_SEF Inv
Default
1
0.5
1
0.14
0.005
200.0
0.00
60.00
0.02
0.005
10.00
70
0.00
90.00
0.2
0.005
1.00
2.00
100.0
Description
Sensitive earth fault stage 1 enabled or
disabled
Sensitive earth fault stage 1 trip or
alarm
Direction of sensitive earth fault stage 1
enabled or disabled
Sensitive earth fault stage 2 enabled or
disabled
Sensitive earth fault stage 2 trip or
alarm
Direction of sensitive earth fault stage 2
enabled or disabled
Sensitive earth fault inverse time stage
enabled or disabled
Sensitive earth fault inverse time stage
trip or alarm
Direction of sensitive earth fault inverse
Default
Min.
Max.
Unit
1
0
63
Description
Direction
Default
Unit
Min.
Max.
Blk SEF at VT
Fail
3U0 Calculated
1.5
IED report
Table 26 Event report list
Information
Description
SEF1 Trip
SEF2 Trip
Information
Description
SEF1 Alarm
SEF2 Alarm
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 28 Technical data for sensitive earth fault protection
Item
Range or value
Tolerance
input
Current from neutral CT input
3 % setting value or 1
mA
0.08 Ir to 20.00 Ir
64
Reset ratio
Reset time
Approx. 40 ms
Inverse time characteristics
3 % setting value or 1
mA
0.08 Ir to 20.00 Ir
IEC standard
Normal inverse;
5% setting + 40ms, at 2
Very inverse;
Extremely inverse;
accordance with
Long inverse
ANSI
IEC60255-151
Inverse;
5% setting + 40ms, at 2
Short inverse;
Long inverse;
Moderately inverse;
C37.112,
Very inverse;
Extremely inverse;
Definite inverse
5% setting + 40ms, at 2
user-defined characteristic
T=
A
i
)P1
I_SET
+B k
20ms
100s
Reset mode
instantaneous
Reset time
approx. 40ms
Directional element for sensitive earth-fault protection
principles
I cos
(V0 / I0)
Direction measurement
IE and VE measured
or 3V0 calculated
160
_SEFChar
Operating area range
66
67
1.1
Introduction
Negative-sequence overcurrent protection detects unbalanced loads on the
system. It is especially useful to monitor the unbalanced load of motors. This
is due to the fact that unbalanced loads result in counter-rotating fields in
three-phase induction motors, which cause overheating in rotor end zones. In
addition, the protection function may be used to detect interruptions, short
circuits and polarity problems with current transformers. Furthermore, it is
suitable for detecting single-phase and two-phase faults with fault currents
lower than load currents.
The protection provide following features:
The first definite stage and inverse stage can be set individually as alarm
or trip stage
1.2
Protection principle
1.2.1
68
t=
A_NSOC
i
I_NSOC
p _NSOC
+ B_NSOC K_NSOC
Equation 6
where:
A_NSOC: Time factor for inverse time stage
B_NSOC: Delay time for inverse time stage
P_NSOC: index for inverse time stage
K_NSOC: Time multiplier
By applying proper setting of the aforementioned parameters, the IED
calculates the tripping or alarming time from the measured current in each
phase separately. Once the calculated time has been elapsed, the trip signal
or alarm signal is issued.
1.2.2
Logic diagram
69
T_NSOC1
NS1 Trip/Alarm
T_NSOC2
NS2 Trip
Func_NSOC1 On
AND
Func_NSOC2 On
AND
3I2 > 3I2_NSOC Inv
NS INV Trip/Alarm
Func_NSOC Inv
1.3
IP1
IP2
IP3
Relay Startup
NSOC1 Trip
NSOC1 Alarm
NSOC2 Trip
NSOC Inv Trip
NSOC Inv Alarm
Description
IP1
IP2
IP3
Signal
Description
Relay Startup
Relay startup
Trip 3Ph
NSOC1 Trip
70
NSOC1 Alarm
stage 1 alarm
Negative sequence overcurrent protection
NSOC2 Trip
stage 2 trip
Negative sequence overcurrent protection
1.4
Setting parameters
1.4.1
Setting lists
Table 31 Negative sequence overcurrent protection function setting list
Parameter
3I2_NSOC1
T_NSOC1
3I2_NSOC2
T_NSOC2
Curve_NOC Inv
3I2_NSOC Inv
K_NSOC Inv
A_NSOC Inv
B_NSOC Inv
P_NSOC Inv
Description
Default
Unit
Min.
Max.
0.5In
0.05
100.0
0.1
0.00
60.00
0.2In
0.05
100.0
0.3
0.00
60.00
12
0.05
100.0
0.05
999.0
1
0.2In
1
0.14
0.005
200.0
0.00
60.00
0.005
10.00
0.02
Description
Negative sequence overcurrent
protection stage 1 enabled or disabled
Negative sequence overcurrent stage 1
trip or alarm
Negative sequence overcurrent
Default
Unit
Min.
Max.
1
71
Description
Default
Unit
Min.
Max.
1.5
Reports
Table 33 Event report list
Information
Description
NSOC1 Trip
NSOC2 Trip
Information
Description
NSOC1 Alarm
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 35 T Technical data for negative sequence overcurrent protection
Item
Rang or Value
Tolerance
0.08 Ir to 20.00 Ir
Time delay
Reset time
40 ms
Reset ratio
72
3% setting value or
0.02Ir
1% setting or +40ms, at
200% operating setting
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
IEC standard
Normal inverse;
5% setting + 40ms, at 2
Very inverse;
Extremely inverse;
accordance with
Long inverse
ANSI
IEC60255-151
Inverse;
5% setting + 40ms, at 2
Short inverse;
Long inverse;
Moderately inverse;
C37.112,
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic
T=
A
i
)P1
I_SET
+B k
5% setting + 40ms, at 2
<I/ISETTING < 20, in
accordance with
IEC60255-151
A
Delay of inverse time, B
n: k
Minimum operating time
Maximum operating time
Reset time
20ms
100s
approx. 40ms
73
74
75
1.1
Introduction
The thermal overload protection represents an essential requirement to
prevent protected equipment from thermal damaging due to overloads.
Thermal damage mostly affects the insulating material surrounding the phase
current conductors in transformers, cables or any other power equipment. As
a matter of fact, the insulation material ages too rapidly if the equipment
temperature exceeds the design limit value. Thus, a special protection is
needed to prevent over-temperature condition for the protected object. Since
severity of over-temperature condition is directly proportional to current
squared, the thermal protection operates based on the square of measured
current flowing through the protected object. Furthermore, because the
cumulative nature of over-temperature condition, it is necessary to integrate
previous thermal history of equipment in the protection. This is achieved in
the IED by providing a comprehensive thermal replica of the protected object.
In this regard the IED provides an overload protection with memory capability
by taking into account both the previous history of an overload and the heat
loss to the environment.
1.2
Function principle
1.2.1
Function description
The thermal overload protection in the IED is provided with one trip stage as
well as one alarm stage. It is possible to set the alarm stage at a certain
percentage of the setting value applied at the trip stage. The protection
function operates based on an approximate replica of the protected object in
the event of temperature rise caused by overload. The thermal replica is
implemented based on thermal models (Cold or Hot Curve) of IEC60255-8
standard. The temperature rise is calculated separately for each phase in a
thermal replica from the square of the respective phase current. The
maximum calculated temperature rise of the three phases is decisive for
evaluation of the thresholds.
The IED calculates the temperature rise of the protected equipment in each
phase, based on following differential equation:
76
+ =
: is thermal time constant of heating for the protected object, in seconds. It is usually
determined by manufacturer of the protected object. This parameter can be set in
setting value.
I: is the measured fundamental current flowing through each phase of the protected
object.
I : is the maximum permissible continuous thermal overload current. It is usually
specified by manufacturer of the protected object. This parameter can be set in
setting value.
: is temperature rise of the protected object in per unit of the final temperature rise
at maximum allowed phase current I .
t = ln
Equation 8
where:
IP: is steady state current previous to the overload.
t = ln
Equation 9
From the Equation 8 and Equation 9 can be seen, the cold curve provides
77
1.3
Relay Startup
Thermal OL Trip
Thermal OL Alarm
Description
IP1
IP2
IP3
Signal
Description
Relay Startup
Relay startup
Trip 3Ph
Thermal OL Trip
Thermal OL Alarm
1.4
Setting parameters
1.4.1
Setting lists
Table 38 Thermal overload protection function setting list
78
Parameter
Description
Default
Unit
Min.
Max.
I_Thermal OL Trip
1.1In
0.10
25.00
Description
Default
Unit
Min.
Max.
1.1In
0.10
25.00
60
1.00
9999
60
1.00
9999
Min.
Max.
for tripping
I_Thermal OL Alarm
T_Const Thermal
T_Const Cool Down
Description
Func_Thermal OL
Cold Curve
enabled or disabled
Cold Curve or Hot Curve
1.5
Default
Unit
Reports
Table 40 Event report list
Information
Description
Thermal OL Trip
Information
Description
Thermal OL Alarm
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 42 Technical data for thermal overload protection
Item
Rang or Value
Current
0.1 Ir to 5.00 Ir
1 to 9999 s
Tolerance
3% setting or 0.02Ir
79
80
1 to 9999 s
I eq2
t ln 2
2
I eq I
IEC 602558,
5% setting or +40ms
I eq2 I P2
t ln 2
2
I eq I
IEC 602558,
5% setting or +40ms
81
Overload protection
1.1
Protection principle
1.1.1
Function description
The IED supervises load flow in real time. If each phase current is greater
than the dedicated setting for a set delay time, the protection will alarm.
1.1.2
Logic diagram
Ia>I_OL Alarm
OR
Ib>I_OL Alarm
Ic>I_OL Alarm
AND
T_OL Alarm
Func_OL
1.2
Overload Alarm
Description
IP1
IP2
IP3
82
Signal
Description
Overload Alarm
Alarm
Setting parameters
1.3.1
Setting lists
Table 45 Function setting list for overload protection
Parameter
Description
Default
Unit
Min.
Max.
I_OL Alarm
2In
0.05
100.0
T_OL Alarm
60
0.00
6000
Unit
Min.
Max.
Default
Func_OL
1.4
Description
disabled
Reports
Table 47 Alarm information list
Information
Description
Overload Alarm
83
84
85
Overvoltage protection
1.1
Introduction
The overvoltage protection detects abnormal network and machine high
voltage conditions. Overvoltage conditions may occur possibly in the power
system during abnormal conditions such as no-load, light load, or open line
end on long line. The protection can be used as open line end detector or as
system voltage supervision normally.
The protection provides following features:
1.2
Protection principle
1.2.1
1.2.2
86
1.2.3
Logic diagram
Ua>
OV Chk PE Enabled
OR
Ub>
OV Trip Enabled
Uc>
Trip
OR
T_OV
OV Trip Disabled
Uab>
Alarm
OR
Ubc>
OV Chk PE Disabled
Uca>
1.3
Relay Startup
OV1_Trip
OV2_Trip
OV1 Alarm
OV2 Alarm
Description
UP1
UP2
UP3
Signal
Description
Relay Startup
Relay Startup
Trip 3Ph
OV2 Alarm
OV1_Trip
OV2_Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 50 Function setting list for overvoltage protection
Parameter
Description
Voltage setting for overvoltage
U_OV1
protection stage 1
Time setting for overvoltage protection
T_OV1
stage 1
Voltage setting for overvoltage
U_OV2
protection stage 2
Time setting for overvoltage protection
T_OV2
stage 2
Dropout_OV
Default
Unit
Min.
Max.
65
40.00
200.0
0.3
0.00
60.00
63
40.00
200.0
0.6
0.00
60.00
0.90
0.99
Min.
Max.
0.95
Description
Overvoltage stage 1 enabled or
Func_OV1
disabled
OV1 Trip
Func_OV2
disabled
OV2 Trip
Default
Unit
OV Init CBF
1.5
Reports
Table 52 Event report list
88
Description
OV1 Trip
OV2 Trip
Description
OV1 Alarm
OV2 Alarm
1.6
Technical data
Table 54 Technical data for overvoltage protection
Item
Voltage connection
Rang or Value
Phase-to-phase voltages or
Tolerance
3 % setting or 1 V
phase-to-earth voltages
Phase to earth voltage
40 to 100 V, step 1 V
3 % setting or 1 V
80 to 200 V, step 1 V
3 % setting or 1 V
Reset ratio
3 % setting
Time delay
Reset time
<40ms
89
90
91
Undervoltage protection
1.1
Introduction
Undervoltage protection has the function to protect electrical equipment
against undervoltage. It can detect voltage collapses on transmission lines,
power transformer and electrical machines and prevents inadmissible
operation condition and a possible stability problem.
The protection provides following features:
1.2
Protection principle
1.2.1
92
1.2.2
1.2.3
Protection
IED
A
B
C
N
A
B
C
Protection
IED
A
B
C
N
93
When a tripping command is issued and the circuit breaker is open, full
voltage remains on the source side while the line side voltage drops to zero.
In this case, undervoltage protection may remain pickup which can be solved
in the IED by integrating additional current criterion. With the current criterion,
undervoltage protection can be maintained only when the undervoltage
criterion satisfied and a minimum current are exceeded. The undervoltage
protection would dropout as soon as the current fall below the corresponding
setting. If the voltage transformer is installed on the busbar side and it is not
desired to check the current flow, this criterion can be disabled by binary
setting.
When the VT located at line side, there is another circuit breaker auxiliary
contact supervision criterion for more security. With this feature, the IED
would issue a trip command when the circuit breaker is closed. This criterion
can be enabled or disabled via binary setting. If the voltage transformer is
installed on the line side and it is not desired to supervise the circuit breaker
position for undervoltage protection, the criterion can be disabled in binary
setting.
1.2.4
94
Logic diagram
Ub<
OR
Uc<
UV Chk PE enabled
OR
Ua<
Ub<
AND
UV Chk All Phase enabled
Uc<
OR
Uab<
UV Chk All Phase disabled
Ubc<
OR
Uca<
UV Chk PE disabled
OR
Uab<
Ubc<
AND
UV Chk All Phase enabled
Uca<
OR
PhA(B,C)
CB Open
UV Trip enabled
Trip
AND
Func_UV
T_UV
OR
IA(IB,IC)>
Alarm
UV Chk Current enabled
UV Trip disabled
VT fail
95
Relay Startup
UV1 Trip
UV2 Trip
UV1 Alarm
UV2 Alarm
Description
UP1
UP2
UP3
IP1
IP2
IP3
Signal
Description
Ph A CB Open
Ph B CB Open
Ph C CB Open
Signal
Description
Relay Startup
Relay Startup
Trip 3Ph
UV1 Alarm
UV2 Alarm
UV1_Trip
UV2_Trip
1.4
96
Setting parameters
Setting lists
Table 58 Undervoltage protection function setting list
Parameter
Description
Voltage setting for undervoltage
U_UV1
protection stage 1
Time setting for undervoltage protection
T_UV1
stage 1
Voltage setting for undervoltage
U_UV2
protection stage 2
Time setting for undervoltage protection
T_UV2
stage 2
Dropout_UV
I_UV_Chk
Default
Unit
Min.
Max.
40
5.00
150.0
0.3
0.00
120.00
45
5.00
150.0
0.6
0.00
120.00
1.01
2.00
0.05
10.00
1.05
0.1In
Description
Undervoltage stage 1 enabled or
Func_UV1
disabled
Undervotage stage 1 tripping
UV1 Trip
enabled or disabled
Undervoltage stage 2 enabled or
Func_UV2
disabled
Undervotage stage 2 tripping
UV2 Trip
enabled or disabled
Default
Unit
Min.
Max.
1.5
Reports
Table 60 Event report list
97
Description
UV1 Trip
UV2 Trip
Information
Description
UV1 Alarm
UV2 Alarm
1.6
Technical data
Table 62 Technical data for undervoltage protection
Item
Voltage connection
Rang or Value
Phase-to-phase voltages or
Tolerance
3 % setting or 1 V
phase-to-earth voltages
Phase to earth voltage
5 to 75 V , step 1 V
3 % setting or 1 V
10 to 150 V, step 1 V
3 % setting or 1 V
Reset ratio
3 % setting
Time delay
98
Current criteria
0.08 to 2.00 Ir
Reset time
50 ms
3% setting or 0.02Ir
99
1.1
Introduction
The displacement voltage protection is able to monitor the displacement
voltage to detect the earth fault in power system. It is usually applied in
non-solidly earthed networks where the earth fault current is limited.
The protection provide following features:
1.2
Protection principle
1.2.1
Function description
The displacement voltage 3U0 can be either directly measured from VT or
calculated based on connected three phases to earth voltages (3V0= VA+ VB+
VC). In the latter case, the three voltages transformers input must be
connected in an earth-wye configuration.
If the displacement voltage is directly applied to the IED and binary setting
3U0 Calculated is disabled, the protection is not affected by VT fail detection
on three-phase connected voltage. Similarly, if the displacement voltage is
calculated based on the three-phase voltages and binary setting 3U0
Calculated is enabled, it would not be blocked as a result of failure detection
in U4 voltage transformer. However, in case of a failure in U4 voltage
transformer and the displacement voltage protection based on measured
value 3V0 would be blocked.
Two definite time stages are provided by the displacement voltage protection
for detecting earth faults. The provided stages can be set to issue an alarm
signal or a trip command. This can be achieved by binary setting. Generally,
stage 1 is applied to monitor light earth faults and hence is usually used as
the alarm stage. However, stage 2 is applied to detect heavy earth faults and
therefore is set for trip stage.
100
1.2.2
Logic diagram
3U0 Calculated
U3P VT Fail
CB Open A
CB Open B
AND
OR
CB Open C
Func_3V01
AND
T_3V01
Trip/Alarm
T_3V02
Trip/Alarm
3U0>U_3V01
Func_3V02
AND
3U0>U_3V02
1.3
Relay Startup
3V01_Trip
3V02_Trip
3V01 Alarm
3V02 Alarm
101
Description
UP1
UP2
UP3
UP4
Signal
Description
Relay Startup
Relay Startup
Trip 3Ph
3V01 Alarm
alarm
Displacement voltage protection stage 2
3V02 Alarm
alarm
3V01_Trip
3V02_Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 65 Function setting list for displacement voltage protection
Parameter
Description
Voltage setting for displacement voltage
U_3V01
protection stage 1
Time setting for displacement voltage
T_3V01
protection stage 1
Voltage setting for displacement voltage
U_3V02
protection stage 2
Time setting for displacement voltage
T_3V02
protection stage 2
Default
Unit
Min.
Max.
20
2.00
100.0
0.1
0.00
60.00
10
2.00
100.0
0.00
60.00
Min.
Max.
102
Description
Displacement voltage stage 1
enabled or disabled
Displacement voltage stage 1 trip
or alarm
Default
Unit
Description
Displacement voltage stage 2
Func_3V02
enabled or disabled
Displacement voltage stage 2 trip
3V02 Trip
or alarm
3U0 Calculated
Displacement voltage is
calculated or measured form VT
Displacement voltage protection
1.5
Default
Unit
Min.
Max.
Reports
Table 67 Event report list
Information
Description
3V01 Trip
3V02 Trip
Information
Description
3V01 Alarm
3V02 Alarm
1.6
Technical data
Table 69 Technical data for displacement voltage protection
Item
Pickup threshold 3V0
Rang or Value
Tolerance
2 to 100 V, step 1 V
5 % setting value or 1 V
(calculated)
Time delay
Approx. 0.95
103
104
105
1.1
Introduction
The circuit breaker failure (CBF) protection function monitors proper tripping
of the relevant circuit breaker. Normally, the circuit breaker should be tripped
and therefore interrupt the fault current whenever a short circuit protection
function issues a trip command. Circuit breaker failure protection provides
rapid back-up fault clearance, in the event of circuit breaker malfunction to
respond to a trip command.
Line2
Line3
LineN
Bus
Trip
IFAULT
106
Function Description
Circuit breaker failure protection can be enabled or disabled in the IED by
binary setting. If the CBF protection is enabled, by operation of a protection
function and subsequent CBF initiation by respective protection function or
externally, a programmed timer will run toward a preset time delay limit. This
time delay is set by settings T_CBF1. If the circuit breaker has not been
opened after expiration of the preset time limit, the IED issues a command to
trip circuit breaker (e.g. via a second trip coil). If the circuit breaker doesnt
respond to the repeated trip command, until another preset delay time which
is set to T_CBF2, the protection will issue a trip command to isolate the fault
by tripping other surrounding backup circuit breakers (e.g. the other CBs
connected to the same bus section as the faulty CB).
Initiation of CBF protection can be performed by both internal and external
protection functions. If CBF protection is desired to be initiated by means of
external protection functions, specified binary inputs (BI) should be
marshaled. This IED provides 4 binary inputs for externally initiation of
integrated CBF function. One of them is 3-phase CBF initiation and other
three are for phase selective CBF initiation in the case of single phase
tripping when single phase AR is allowed.
There are two criteria for breaker failure detection: the first one is to check
whether the actual current flow effectively disappeared after a tripping
command had been issued. The second one is to evaluate the circuit breaker
auxiliary contact status.
1.2.1
1.2.2
1.2.3
Logic diagram
Ia > I_CBF
OR
OR
AND
OR
Ib > I_CBF
Ic > I_CBF
Ib > I_CBF
OR
Ic > I_CBF
Ia > I_CBF
Ic > I_CBF
AND
OR
Ia > I_CBF
Ib > I_CBF
OR
108
AND
CB A is
closed
AND
CB B is
closed
AND
CB C is
closed
AND
CB 1P is closed
OR
BI_PhB CB Open
PhB Init CBF
AND
CBF Curr. Crit.
3P
OR
BI_PhC CB Open
PhC Init CBF
AND
CBF Curr. Crit.
3P
OR
BI_PhA CB Open
BI_PhB CB Open
AND
BI_PhC CB Open
BI_3Ph CB Close
1
3Ph Init CBF
CBF Curr. Crit.
3P
AND
OR
109
OR
Talm
BI_CBF Err
OR
OR
OR
BI_PhC Init
CBF
Inter PhC Init
CBF
AND
AND
AND
AND
OR
AND
BI_3Ph Init CBF
Inter 3Ph Init CBF
110
OR
AND
CBF A Startup
AND
CBF B Startup
AND
CBF C Startup
AND
CBF 3P Startup
OR
CB C is closed
CBF Curr. Crit.
C
OR
CB 1P is closed
CBF Curr. Crit.
3P
OR
111
CBF A Startup
Func_CBF On
OR
OR
OR
T_CBF1
CBF B Startup
Func_CBF On
T_CBF1
CBF C Startup
Func_CBF On
AND
AND
OR
AND
CBF 3P Startup
T_CBF1
Func_CBF On
CBF A Startup
CBF B Startup
CBF C Startup
AND
AND
AND
Func_CBF
On
Func_CBF
On
T_CBF 1P Trip 3P
CBF 1P Trip 3P On
T_CBF 1P Trip 3P
OR
CBF 1P Trip 3P On
Func_CBF
On
CBF1 1P Trip
3P
T_CBF 1P Trip 3P
CBF 1P Trip 3P On
Figure 30 Logic diagram for three-phase trip initiated by single phase startup
T_CBF2
CBF A Startup
Func_CBF On
T_CBF2
CBF B Startup
Func_CBF On
OR
T_CBF2
CBF C Startup
Func_CBF On
T_CBF2
CBF 3P Startup
Func_CBF On
112
CBF2 Trip
1.3
Relay Startup
Trip PhA
Trip PhB
Trip PhC
Trip 3Ph
CBF1 Trip
CBF2 Trip
Description
IP1
IP2
IP3
IN
Signal
Description
PhA CB Open
PhaseA CB open
PhB CB Open
PhaseB CB open
PhC CB Open
PhaseC CB open
3Ph CB Close
Signal
Description
Relay Startup
Relay Startup
Trip PhA
Trip phase A
113
Trip phase B
Trip PhC
Trip phase C
Trip 3Ph
CBF1 Trip
CBF2 Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 73 CBF protection function setting list
Parameter
I_CBF
3I0_CBF
3I2_CBF
T_CBF1
Description
Phase current setting for circuit breaker
fail startup
Zero sequence current setting for
circuit breaker fail startup
Negative sequence current setting for
circuit breaker fail startup
Delay time setting for stage 1 of circuit
breaker fail startup
Default
Unit
Min.
Max.
0.5In
0.05 100.0
0.2In
0.05 100.0
0.2In
0.05 100.0
0.00 32.00
0.1
0.05 32.00
0.2
0.10 32.00
T_CBF2
Description
Default
Func_CBF
Unit
Min.
Max.
114
Reports
Table 75 Event report list
Information
Description
CBF1 Trip
CBF2 Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 76 Technical data for circuit breaker failure protection
Item
Rang or Value
Tolerance
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
Reset ratio
>0.95
< 20ms
phase current
Negative sequence current
zero sequence current
115
116
117
1.1
Introduction
The IED provides this protection function to protect dead zone, namely the
area between circuit breaker and CT in the case that CB is open. Therefore,
by occurrence of a fault in dead zone, the short circuit current is measured by
protection IED while CB auxiliary contacts indicate the CB is open.
1.2
Protection principle
1.2.1
Function description
This protection can be enabled or disabled by dedicated binary setting. If the
protection function is enabled, by operation of a protection function, and
subsequent CBF initiation by respective protection function, a programmed
timer runs toward a preset time delay limit. This time delay is set by user in
setting. If the fault current has not been disappeared after expiration of the
preset time limit even now the circuit breaker has been opened, the dead
zone protection would issue a trip command to isolate the fault by tripping
other surrounding backup circuit breakers (e.g. the other CBs connected to
the same bus section as the faulty CB).
When one bus side CT of feeder or transformer is applied, once a fault occurs
in the dead zone, the IED trips the relevant busbar zone. Tripping logic is
illustrated in Figure 32.
118
Trip
Bus
IFAULT
Line1
Line2
LineN
Legend:
Opened CB
Closed CB
When one line side CT is applied and a fault occurs in the dead zone,
protection IED sends a transfer trip to remote end relay to isolate the fault.
Tripping logic is illustrated in Figure 33.
119
Inter trip
Bus
IFAULT
Line1
Line2
Trip
LineN
Relay
Legend:
Opened CB
Closed CB
When one transformer side CT is applied and a fault occurs in the dead zone,
protection relay trip the circuit breakers of the others transformer winding.
Tripping logic is illustrated in Figure 34.
120
trip
Bus1
IFAULT
Ln
L1
T1
Bus2
Bus3
Legend:
Opened CB
Closed CB
1.2.2
Logic diagram
121
OR
BI_PhA CB
Open
BI_PhB CB
Open
BI_PhC CB
Open
AND
T_Dead Zone
AND
Func_Dead Zone On
AND
BI_3Ph CB
Close
1.3
Description
IP1
IP2
IP3
122
Description
PhA CB Open
PhaseA CB open
PhB CB Open
PhaseB CB open
PhC CB Open
PhaseC CB open
3Ph CB Close
Signal
Description
Relay Startup
Relay startup
DeadZone_Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 80 Dead zone protection function setting list
Parameter
T_Dead Zone
Description
Time delay setting for dead zone
protection
Default
Unit
Min.
Max.
0.00
32.00
Unit
Min.
Max.
1.5
Description
Dead Zone protection operating
mode
Default
1
Reports
Table 82 Event report list
Information
Description
123
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 83 Technical data for dead zone protection
Item
Rang or Value
Tolerance
Current
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
Time delay
Reset ratio
124
>0.95
125
STUB protection
1.1
Introduction
The VT is mostly installed at line side of transmission lines. Therefore, for the
cases that transmission line is taken out of service and the line disconnector
is opened, the distance protection will not be able to operate and must be
blocked.
The STUB protection protects the zone between the CTs and the open
disconnector. The STUB protection is enabled when the open position of the
disconnector is connected to IED binary input. The function supports one
definite stage which related concept is shown in Figure 36.
1.2
Protection principle
1.2.1
Function description
Busbar A
CT1-1
CB1
CT1-2
Stub fault
CT3-1
Feeder1
Disconnector1
CB3
CT3-2
CT2-2
Feeder2
Disconnector2
CB3
CT2-1
Busbar B
If a short circuit current flows while the line disconnector is open, this implies
that a fault in the STUB range between the current transformers and the line
126
1.2.2
Logic diagram
Ia(b,c)>I_STUB
T_STUB
Func_STUB
AND
Permanent trip
STUB Enable
1.3
Description
IP1
IP2
IP3
127
Description
STUB Enable
STUB Enable
Table 86 Binary output list
Signal
Description
Relay Startup
Relay Startup
STUB Trip
STUB Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 87 Setting value list for STUB protection
Parameter
Description
I_STUB
T_STUB
Default
Unit
Min.
Max.
1.2In
0.05
100.0
0.00
60.00
Min.
Max.
Description
Func_STUB
STUB Init CBF
1.5
Default
Reports
Table 89 Event report list
Information
Description
STUB Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 90 Technical data for STUB protection
128
Unit
Rang or Value
Tolerance
Current
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
Time delay
Reset ratio
>0.95
129
130
131
1.1
Introdcution
Under steady-state operating condition, all three poles of circuit breaker must
be closed or open at the same time. The phase separated operating circuit
breakers can be in different positions (close-open) due to electrical or
mechanical failures. This can cause negative and zero sequence currents
which gives thermal stress on rotating machines and can cause unwanted
operation of zero sequence or negative sequence current functions.
The pole discordance function operates based on information from auxiliary
contacts of the circuit breaker for the three phases with additional criteria from
unsymmetrical phase current.
1.2
Protection principle
1.2.1
Function description
The CB position signals are connected to IED via binary input in order to
monitor the CB state. Poles discordance condition is established when at
least one pole is closed and at the same time not all three poles are closed.
Additionally, the current criteria are processed. Pole discordance can be
detected when current is not flowing through all three poles, i.e. through only
one or two poles. When current is flowing through all three poles, all three
poles must be closed even if the breaker auxiliary contacts indicate a different
status.
1.2.2
132
Logic diagram
PhB CB Open
AND
OR
Ib > 0.06IN
PhC CB Open
AND
AND
Ic > 0.06IN
5s
500ms
CB Err Blk PD
PhA CB Open
PhB CB Open
AND
PhC CB Open
PhA CB Open
AND
Ia < 0.06IN
PhB CB Open
AND
OR
Ib < 0.06IN
AND
Func_PD On
PD Trip
PhC CB Open
AND
Ic < 0.06IN
1.3
133
Description
IP1
IP2
IP3
IN
Signal
Description
PhA CB Open
PhaseA CB open
PhB CB Open
PhaseB CB open
PhC CB Open
PhaseC CB open
Table 93 Binary output list
Signal
Description
Relay Startup
Relay startup
Trip 3Ph
PD_Trip
1.4
Setting parameters
1.4.1
Setting lists
Table 94 Function setting list for poles discordance protection
Parameter
3I0_PD
134
Description
Zero sequence current setting value for
PD protection
Default
Unit
Min.
Max.
0.4In
0.05
100.0
Description
Negative sequence current setting value
3I2_PD
for PD protection
T_PD
Default
Unit
Min.
Max.
0.4In
0.05
100.0
0.00
60.00
Min.
Max.
Description
Enable or disable poles discordance
Func_PD
protection
Enable or disable 3I0/3I2 checking
PD Chk 3I0/3I2
criteria
PD Init CBF
1.5
Default
Unit
Reports
Table 96 Event report list
Information
Description
PD Trip
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 97 Technical data for poles discordance protection
Item
Rang or Value
Tolerance
Current
0.08 Ir to 20.00 Ir
3% setting or 0.02Ir
Time delay
Reset ratio
>0.95
135
136
137
1.1
Introduction
The synchronism and voltage check function ensures that the stability of the
network is not endangered when switching a line onto a busbar. The voltage
of the feeder to be energized is compared to that of the busbar to check
conformances in terms of magnitude, phase angle and frequency within
certain tolerances.
The synchro-check function checks whether the voltages on both sides of the
circuit breaker are synchronizing, or at least one side is dead to ensure
closing can be done safely.
When comparing the two voltages, the synchro check uses the voltages from
busbar and outgoing feeder. If the voltage transformers for the protective
functions are connected to the outgoing feeder side, the reference voltage
has to be connected to a busbar voltage.
If the voltage transformers for the protective functions are connected to the
busbar side, the reference voltage has to be connected to a feeder voltage.
Note:
1.2
Function principle
1.2.1
Synchro-check mode
The voltage difference, frequency difference and phase angle difference
values are measured in the IED and are available for the synchro-check
function for evaluation.
By any synchronization request, the synchronization conditions will be
138
1.2.2
All three phases voltage U(a,b,c) should be above the setting value
Umin_Syn.
139
1.2.3
Energizing check for dead line and live bus for AR enabled or disabled,
when the control word AR_EnergChkDLLB is on
Energizing check for live line and live bus for AR enabled or disabled,
when the control word AR_EnergChkLLDB is on
Energizing check for dead line and dead bus for AR enabled or disabled,
when the control word AR_EnergChkDLDB is on
Override mode
In this mode, auto-reclosing will be released without any check.
1.2.4
140
Logic diagram
AND
AND
T_Syn Check
Synchr-check
meet
Freqdiff<Freq_Syn Diff
Udiff<U_Syn Diff
AR_EnergChkDLLB on
T_MaxSynExt
Synchr-check fail
U4 <Umax_Energ
Ua(Ub,Uc) >Umin_Syn
AND
VT_Line off
AR_EnergChkLLDB on
U4>Umin_Syn
AND
Ua(Ub,Uc)
<Umax_Energ
OR
VT_Line off
AR_EnergChkDLDB on
U4<Umax_Energ
AND
Ua(Ub,Uc)
<Umax_Energ
AR_EnergChkDLLB on
U4 >Umin_Syn
Ua(Ub,Uc)
<Umax_Energ
AND
VT_Line on
AR_EnergChkLLDB on
U4<Umax_Energ
Ua(Ub,Uc)
>Umin_Syn
AND
VT_Line on
1.3
141
Description
UP1
UP2
UP3
UP4
1.4
Setting parameters
1.4.1
Setting lists
Table 99 Synchro-check function setting list
Parameter
Angle_Syn Diff
U_Syn Diff
Freq_Syn Diff
T_Syn Check
T_MaxSynExt
Umin_Syn
Umax_Energ
Description
Angle difference for synchronization
check
Voltage difference for synchronization
check
Frequency difference for
synchronization check
Time for synchronization check
Maximum time for exiting
synchronization check
Minimum voltage for synchronization
check
Maximum voltage for Energizing
check
Default
Unit
Min.
Max.
30
Degree
1.00
80.00
10
1.00
40.00
0.05
Hz
0.02
2.00
0.05
0.00
60.00
10
0.05
60.00
40
30.00
65.00
30
10.00
50.00
Min.
Max.
142
Description
Override mode for AR enabled or
disabled
Dead line live bus of energizing
Default
Unit
Description
Default
Unit
Min.
Max.
AR_EnergChkDLDB
AR_Syn check
1.5
enabled or disabled
Reports
Table 101 Event report list
Information
Description
Syn Request
AR_EnergChk OK
Energizing check OK
Syn Failure
Syn OK
Synchronization check OK
EnergChk fail
Information
Description
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 103 Synchro-check and voltage check technical data
Item
Operating mode
Rang or Value
Synchronization check:
Synch-check
Tolerance
143
Override
Energizing check:
10 to 50 V (phase to earth),
or bus
step 1 V
30 to 65 V (phase to earth),
or bus
step 1 V
V-measurement
Voltage
difference
f-measurement
1 to 40 V (phase-to-earth),
3 % setting or 1 V
3 % setting or 1 V
1V
steps 1 V
(f2>f1;
20 mHz
f2<f1)
Hz,
-measurement (2>1;
1 to 80 , step, 1
2<1)
Minimum measuring time
ms
Maximum synch-check
extension time
144
145
Auto- reclosing
1.1
Introduction
For restoration of the normal service after a fault, an auto-reclosing attempt is
mostly made for overhead lines. Experiences show that about 85% of faults
are transient and can disappear when an auto-reclosing attempt is performed.
This means that the line can be connected again; the reconnection is
accomplished after a dead time via the automatic reclosing system. If the fault
still exists after auto-reclosing, for example, arc has not been cleared, the
protection will re-trip the circuit breaker (hereinafter is referred as CB).
Auto-reclosing is only permitted on overhead lines because a short circuit arc
can be extinguished only in overhead lines and not cable feeders. Main
features of the auto-reclosing function (hereinafter is referred as AR) are as
following:
1.2
Individually settable dead time for three phase and single phase fault and
for each zone
External AR initiation
CB ready supervision
CB Aux. interrogation
Function principle
The AR is able to cooperate with single-pole operated CB as well as
three-pole operated CB. The function provides up to 4 auto-reclosing shots
that can be determined by setting, Times_AR. Moreover, since the time
required for extinguishing short circuit arc is different for single or three phase
faults, the different dead time settings, T_1P ARn and T_3P ARn ( n
represents 1, 2, 3, or 4), AR have been provided to set single-pole tripping
dead time and three-pole tripping dead time of each shot separately.
1.2.1
146
Single-shot reclosing
2)
3)
After the auto-reclosing delay time, T_1P AR1 (or T_3P AR1), elapses,
the reclosing command is issued if all reclosing conditions (e.g. synchro-check for 3-pole tripping) are satisfied without any blocking reclosing
input.
4)
5)
At the moment that the closing signal is issued, reclaim timer T_Reclaim
is started. By the end of this period, T_Reclaim, If there is not fault
happening, auto-reclosing operation is successful and then the report,
AR Success, is issued.
6)
From the end of reclaim time, auto-reclosing function is blocked for the
AR reset time T AR reset.
7)
If another fault occurs after the time, T_AR Reset, elapses, the auto-reclosing is ready now, and then a new tripping-reclosing procedure is
started and performed in same way.
147
Fault
Trip Command
CB Open PosItion
AR Initiate
T_3P AR1
Synchro-check or
voltage check OK
T_Action
T_Action
Closing Command
T_Reclaim
T_Reset
1.2.2
Multi-shot reclosing
The first reclosing shot is, in principle, the same as the single-shot
auto-reclosing. If the first reclosing is unsuccessful, it doesnt result in a final
trip, if multi-shot reclosing is set to be performed. In this case, if a fault occurs
during reclaim time of the first reclosing shot, it would result in the start of the
next reclose shot with dead time T_1pAR1, T_1p AR2, T_1p AR3, T_1p
AR4, T_3P AR2, T_3P AR3 or T_3P AR4. This procedure can be
repeated until the whole reclosing shots which are set inside the device is
performed. Different dead times can be set to various shots of AR function.
This can be performed through settings T_1pAR1, T_1p AR2, T_1p AR3,
T_1p AR4, T_3p AR1, T_3p AR2, T_3p AR3, T_3p AR4. However, if
none of reclosing shots is successful, i.e. the fault doesnt disappear after the
last programmed shot, a final trip is issued, and reclosing attempts are
announced to be unsuccessful.
The typical tripping-reclosing procedure of two shots reclosing scheme, is
illustrated in time sequence diagrams,
, and is described as following:
148
1)
2)
After the auto-reclosing delay time, T_1P AR1 (or T_3P AR1), elapses,
the reclosing command is issued if all reclosing conditions (e.g. synchro-check for 3-pole tripping) are satisfied without any blocking reclosing
input.
4)
5)
At the moment that the closing signal is issued, reclaim timer T_Reclaim
is started.
6)
If the circuit breaker is closed on a fault during the period between the
dropout of closing command and the end of T_Reclaim, second tripping-reclosing procedure for second shot is started and performed like the
first tripping-reclosing procedure.
7)
8)
9)
10) From the end of reclaim time, auto-reclosing function is blocked for the
AR reset time T AR Reset.
11) If another fault occurs after the time, T_AR Reset, elapses, the auto-reclosing is ready now, and then a new multi shots tripping-reclosing
procedure is started and performed in same way.
149
Fault
Trip Command
CB Open PosItion
AR Initiate
T_3P AR1
Synchro-check or
voltage check OK
T_Action
T_Action
Closing Command
T_Reclaim
T_Reset
Figure 41 A permanent three-phase fault, two reclosing shots and final tripping
1.2.3
150
Busbar A
BO: AR WaitToSlave
CT1-1
BO: AR Fail
CB1
CT1-2
Feeder 1
CT3-1
BI: MC/AR Block
BI: AR Wait
CB3
CT3-2
Feeder 2
CT2-1
CB2
CT2-2
Busbar B
After trip command issued, side CB and tie CB are opened in a short
time.
2)
The auto-reclosing for side CB and for tie CB are initiated when the fault
current is cleared.
3)
4)
The AR for tie CB can wait only and cannot issue the reclosing command,
until the binary input, AR_Wait dropout before the timer, T_WaitMater
of AR for tie CB elapses, even if the timer, T_1P AR1 (or T_3P AR1) of
AR for tie CB has elapsed.
5)
After the auto-reclosing delay time, T_1P AR1 (or T_3P AR1) of AR for
151
152
6)
At the moment that the closing signal for side CB is issued, reclaim timer
T_Reclaim of AR for side CB is started.
7)
8)
9)
If the auto-reclosing delay time, T_1P AR1 (or T_3P AR1) of AR for side
CB, has elapsed, the reclosing command is issued at once if all reclosing
conditions (e.g. synchro- -check for 3-pole tripping) are satisfied without
any blocking reclosing input. The tie CB is reclosed.
Fault
Trip Command
T_Action
AR for side CB: Closing command
T_Action
AR for tie CB: Closing command
Figure 43 A transient fault, single shot scheme, coordination between AR for tie
CB and AR for side CB
153
154
1)
After trip command issued, side CB and tie CB are opened in a short
time.
2)
The auto-reclosing for side CB and for tie CB are initiated when the fault
current is cleared.
3)
4)
The AR for tie CB can wait only and cannot issue the reclosing command,
until the binary input, AR_Wait dropout before the timer, T_WaitMater
of AR for tie CB elapses, even if the timer, T_1P AR1 (or T_3P AR1) of
AR for tie CB has elapsed.
5)
After the auto-reclosing delay time, T_1P AR1 (or T_3P AR1) of AR for
side CB, elapses, the reclosing command is issued if all reclosing
conditions (e.g. synchro- -check for 3-pole tripping) are satisfied without
any blocking reclosing input. The side CB is reclosed.
6)
At the moment that the closing signal for side CB is issued, reclaim timer
T_Reclaim of AR for side CB is started.
7)
During the reclaim timer T_Reclaim of AR for side CB, if the side CB is
reclosed on a permanent fault, the protection IED will trip the CB
instantaneously. At same time, the binary output, AR Failure is
transmitted to AR for tie CB as the binary input, MC/AR Block.
8)
Fault
Trip Command
T_Action
AR for side CB: Closing command
155
AR_1p mode
In this mode of operation, auto-reclosing function will be initiated by
single phase tripping condition as well as using the external single pole
binary input initiation. If the three-phase AR initiation binary input, 3Ph
Init AR, is active, the closing function will be blocked.
AR_3p mode
In this mode of operation, auto-reclosing function only operates for
three pole closing.
AR_1p(3p) mode
In this mode of operation, auto-reclosing function operates for both
single pole tripping as well as three pole tripping.
AR_Disable
By setting this binary setting to 1, auto-reclosing function will be off or
out of service.
Note: If any illegal setting has been done, AR FUNC Alarm is
reported.
AR Final Trip
By setting this binary setting to 1, auto-reclosing function generates
a three pole trip command for an unsuccessful single pole reclosing.
In the AR_1P mode, after a single pole tripping, if auto- -reclosing
function is blocked suddenly during the dead time of a 1-pole reclosing
cycle, the circuit breaker will be kept in poles discordance state. To
avoiding this state, by binary setting AR Final Trip at 1, the IED will
issue a 3-pole trip command to open the rest of circuit breaker poles.
This binary setting is always used in the situation without pole
156
1.2.5
Auto-reclosing initiation
AR can be initiated by external functions via four binary inputs:
PhA Init AR
External phase A tripping output initiates AR
PhB Init AR
External phase B tripping output initiates AR
PhC Init AR
External phase C tripping output initiates AR
3Ph Init AR
External three-phase tripping output initiates AR
1.2.6
Protection
IED
BO-Trip PhA
BI-PhA Init AR
BO-Trip PhB
BI-PhB Init AR
BO-Trip PhC
BI-PhC Init AR
BO-Trip 3Ph
BI-3Ph Init AR
BO Relay Block AR
BI-MC/AR Block
On
Off
Protection
IED with AR
BI-AR OFF
1.2.7
Auto-reclosing logic
Some important points regarded to auto-reclosing logic are described as
157
Fault
Trip Command
CB Open PosItion
AR Initiate
T_3P AR1
t1
t2
t3
t4
t5
t6
Synchro-check or
voltage check OK
T_Syn Check
T_MaxSynExt
T_Action
Closing Command
T_Reclaim
T_Reset
Note:
T_Syn Check > t1, t2, t4, t5, t6;
T_Syn Check t3
Close command pulse lasts for T_Action at most. During this time, it
does not check synchronization conditions any longer. Before the end of
close command pulse, if any function tripping happen, the close
command is terminated.
Fault
Trip Command
CB Open Position
1.2.8
To prevent automatic reclosing during feeder dead status (CB Open), for
example, in the IED testing, AR is initiated at first shot only when the CB
has been closed for more than setting time, T_AR Reset.
AR blocked conditions
1.2.9
Logic diagram
OR
B Phase no current
AND
AND
3 Phase no current
BI_PhB Init AR 1-0
BI_PhC Init AR 1-0
AND
3 Phase no current
OR
3 phase Startup AR
AND
3 Phase no current
160
1P CBOpen Init AR on
AND
OR
1P CBOpen Init AR on
1P CBOpen Init AR on
AND
3P CBOpen Init AR on
3 phase Startup AR
OR
AND
3P CBOpen Init AR on
AND
3P CBOpen Init AR on
AR_Chk3PVol =0
1)
AR_Chk3PVol =1
OR
AND
Ua(Ub,Uc) >Umin_Syn
AND
t
Note:
1) t = T_Syn Check
2) t = T_3P AR
3) t = T_MaxSynExt
3)
2)
t
Check 3 Ph failure
161
1)
OR
AND
AR_1p mode = 1
AR_1p(3p) mode =1
OR
AND
3 phase initiate AR
2)
AND
NO check
Energizing check OK
3)
t
OR
Synchro-check OK
BI_MC/AR block: 0-1
AND
OR
AR Closing
AND
OR
4)
BI_CB Faulty
Mode_3/2CB =1
5)
CB_Master =0
AND
BI_AR Wait: 0-1
Mode_3/2CB =0
OR
CB_Master =1
Mode_3/2CB =1
AR fail
AND
AND
AR_3p mode =1
Ph A Tripping: 0-1
OR
Ph B Tripping: 0-1
AND
Ph B Tripping: 0-1
OR
3 Ph Tripping: 0-1
Relay trip 3 Ph = 1
AND
AR_1p mode = 1
Note:
1) t = T_1P AR; 2) t = T_3P AR; 3) t = T_MaxSynExt; 4) t = T_CB Faulty; 5) t = T_WaitMaster
162
AR Lockout
AR Close
IP2
AR Lockout
IP3
AR Not Ready
UP1
AR Final Trip
UP2
AR In Progress
UP3
AR Successful
UP4
PhA Init AR
AR Fail
AR WaitToSlave
PhB Init AR
PhC Init AR
3Ph Init AR
AR Wait
MC/AR Block
AR off
CB Faulty
PhA CB Open
PhB CB Open
PhC CB Open
3Ph CB Close
V1P MCB Fail
Description
IP1
IP2
IP3
UP1
UP2
UP3
UP4
Signal
Description
AR Off
AR function off
MC/AR Block
AR block
PhA Init AR
PhaseA initiate AR
PhB Init AR
PhaseB initiate AR
PhC Init AR
PhaseC initiate AR
3Ph Init AR
AR Wait
AR Wait
163
CB faulty
PhA CB Open
Phase A CB Open
PhB CB Open
Phase B CB Open
PhC CB Open
Phase C CB Open
3Ph CB Close
Signal
Description
AR Close
AR Close
AR Lockout
AR Lockout
AR Not Ready
AR Not Ready
AR Final Trip
AR Final Trip
AR In Progress
AR In Progress
AR Successful
AR Successful
AR Fail
AR Fail
AR for tie breaker blocked by AR for side
AR WaitToSlave
breaker
1.4
Setting parameters
1.4.1
Setting lists
Table 107 Auto-reclosing function setting list
Parameter
T_1P AR1
T_1P AR2
T_1P AR3
T_1P AR4
T_3P AR1
T_3P AR2
T_3P AR3
164
Description
Time delay setting 1 for single phase
auto-reclosing
Time delay setting 2 for single phase
auto-reclosing
Time delay setting 3 for single phase
auto-reclosing
Time delay setting 4 for single phase
auto-reclosing
Time delay setting 1 for three phase
auto-reclosing
Time delay setting 2 for three phase
auto-reclosing
Time delay setting 3 for three phase
auto-reclosing
Default
Unit
Min.
Max.
0.6
0.05
10.00
0.7
0.05
10.00
0.8
0.05
10.00
0.9
0.05
10.00
1.1
0.05
60.00
1.2
0.05
60.00
1.3
0.05
60.00
0.05
60.00
1.4
80
0.05
60.00
auto-reclosing number
60.00
4
60.00
auto-reclosing
pulse length setting for auto-reclosing
Time setting for successful auto-reclosing
determination
80.00 500.0
0.05
0.50
1
0.00
10
0.05
60.00
0.50
60.00
20
0.01
60.00
Min.
Max.
Final trip by AR
1P CBOpen Init AR
3P CBOpen Init AR
Mode_3/2CB
CB_Master
AR_1p mode
AR_3p mode
AR_1p(3p) mode
AR_Disable
AR_Override
Description
Single phase mode for auto-reclosing
function
Three phase mode for auto-reclosing
function
One and three phase mode for
auto-reclosing function
auto-reclosing function disabled
Override mode for AR enabled or
disabled
1.5
Default
Unit
0
0
0
Reports
Table 109 Event report list
165
Description
1st Reclose
First reclose
2nd Reclose
Second reclose
3rd Reclose
Third reclose
4th Reclose
Fourth reclose
AR Block
Auto-reclose blocked
BI MC/AR BLOCK
Auto-reclose BI blocked
AR Success
Auto-reclose success
AR Final Trip
AR in progress
Auto-reclose is in progress
AR Failure
Auto-reclosing failed
Relay Reset
Relay reset
Table 110 Alarm report list
Information
Description
AR Mode Alarm
1.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 111 Technical data for auto-reclosing function
Item
Number of reclosing shots
Rang or Value
Tolerance
Up to 4
Shot 1 to 4 is individually
selectable
AR initiating functions
166
ms
Reclaim time
reset time)
Circuit breaker ready
supervision time
Dead time extension for
167
168
1.1
Function description
Open or short circuited current transformer cores can cause unwanted
operation of many protection functions such as, earth fault current and
negative sequence current functions.
It must be remembered that a blocking of protection functions at an occurring
open CT circuit will mean that the situation will remain and extremely high
voltages will stress the secondary circuit.
To prevent IED from wrong trip, interruptions in the secondary circuits of
current transformers is detected and reported by the device. When the
zero-sequence current is always larger than the setting value of 3I0_CT Fail
for 12s, CT Fail will be reported and each zone of zero-sequence current
protection will be blocked.
1.2
CT Fail
Description
IP1
IP2
IP3
IN
Signal
Description
CT Fail
CT Fail
1.3
Setting parameters
169
Setting lists
Table 114 CT failure function setting list
Parameter
3I0_CT Fail
Description
Default
Unit
Min.
Max.
0.2In
0.05
10.00
Explanation
CT fail function enabled or
Func_CT Fail
disabled
1.4
Reports
Table 116 Alarm report list
Information
Description
CT Fail
CT fail
170
Default
Unit
Min.
Max.
2.1
Introduction
In the event of a measured voltage failure due to a broken conductor or a
short circuit fault in the secondary circuit of voltage transformer, those
protection functions which are based on voltage criteria may be mistakenly
considered as a voltage of zero. VT failure supervision function is provided to
inform those functions about a voltage failure. VT supervision can be used to
monitor the voltage transformer circuit, single-phase VT failures, two-phase or
three-phase VT failures. Its main features are as:
2.2
Function principle
VT failure supervision function can be enabled or disabled through binary
setting VT Fail. By applying setting 1 to the binary setting, VT failure
supervision function would monitor the voltage transformer circuit. As
mentioned, the function is able to detect single-phase broken, two-phase
broken or three-phase broken faults in secondary circuit of voltage
transformer, if a three-phase connection is applied.
There are three main criteria for VT failure detection; the first is dedicated to
detect three-phase broken faults. The second and third ones are to detect
single or two-phase broken faults in solid earthed and isolated/resistance
earthed systems, respectively. A precondition to meet these three criteria is
that IED should not be picked up and the calculated zero sequence and
negative sequence currents should be less than setting of 3I02_ VT Fail.
The criteria are as follows:
2.2.1
2.2.2
2.2.3
Logic diagram
If VT failure supervision detects a failure in voltage transformer secondary
circuit, either by means of the above mentioned criteria or reception of a VT
MCB fail indication, all the protection functions, which are based on direction
component or low voltage criteria, will be blocked. Furthermore, Alarm report
VT fail is issued after 10s delay time. The blocking condition would be
removed if one of the following conditions is met within the 10 sec delay time
(previous to Alarm VT fail).
Without IED pickup, minimum phase voltage becomes more than setting of
Upe_VT Normal for 500ms.
Without IED pickup, minimum phase voltage becomes more than setting of
Upe_VT Normal and at the same time, the calculated zero sequence and
negative sequence current of corresponding side becomes more than the
setting of 3I02_ VT Fail.
Subsequent to VT fail alarm, the blocking condition of respective protection
functions would be removed if without IED pickup, the minimum phase
voltage becomes more than the setting of Upe_VT Normal for a duration
172
AND
Isolated
Max{Uab,Ubc,Uca}Min{Uab,Ubc,Uca}>
Upp_VT Fail
OR
AND
AND
OR
Relay Start up
BI MCB Fail
AND
VT Fail
block
OR
VT Fail
unblock
10S
Alarm
VT Fail
VT Fail block
min{Ua,Ub,Uc}>
Upe_VT Normal
AND
AND
500ms
Relay Start up
AND
3I0>3I02_VT Fail or
3I2>3I02_VT Fail
min{Ua,Ub,Uc}>
Upe_VT Normal
AND
AND
10S
Relay Start up
2.3
173
Description
IP1
IP2
IP3
IN
UP1
UP2
UP3
Signal
Description
Signal
Description
VT Fail
VT Fail
2.4
Setting parameters
2.4.1
Setting list
Table 120 Fuse failure supervision function setting list
Parameter
I_VT Fail
Description
Maximum current of VT fail to detect
VT fail
Default
Unit
Min.
Max.
0.1In
0.05
1.00
0.1In
0.05
1.00
7.00
20.00
16
10.00
30.00
40
40.00
65.00
Upe_VT Fail
Upp_VT Fail
Upe_VT Normal
Explanation
VT Fail
Solid Earthed
2.5
Default
Unit
Min.
Max.
Reports
Table 122 Alarm report list
Information
Description
VT Fail
VT fail
V3P_MCB VT Fail
2.6
Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
In: nominal current of the reference side of transformer;
Table 123 Technical data for VT secondary circuit supervision
Item
Range or value
Tolerances
Minimum current
3% setting or 0.02Ir
5% setting or 0.02Ir
3% setting or 1 V
3% setting or 1 V
3% setting or 1 V
sequence current
Maximum phase to earth
voltage
Maximum phase to phase
voltage
Normal phase to earth
voltage
175
Chapter 20 Monitoring
Chapter 20 Monitoring
176
Chapter 20 Monitoring
177
178
Overview
Each IED is provided with a communication interface, enabling it to connect to
one or many substation level systems or equipment.
Following communication protocols are available:
1.1
Protocol
1.1.1
1.1.2
1.2
Communication port
1.2.1
1.2.2
1.2.3
1.3
Technical data
Front communication port
Item
Data
Number
Connection
Communication speed
9600 baud
15 m
180
Data
Number
0 to 2
Connection
2-wire connector
Rear port in communication module
1.0 km
Test voltage
Data
Electrical communication port
Number
0 to 3
Connection
RJ45 connector
Rear port in communication module
100m
100 Mbit/s
100 Mbit/s
Optical communication port ( optional )
Number
0 to 2
Connection
SC connector
Rear port in communication module
Multi-mode
2.0km
100 Mbit/s
100 Mbit/s
181
Data
Mode
Pulse mode
IRIG-B000
Connection
2-wire connector
Rear port in communication module
Voltage levels
182
differential input
Work Station 3
Server or
Work Station 2
Switch
Work Station 4
Switch
Switch
Switch
Switch
Gateway
or
converter
Switch
Gateway
or
converter
1.5
183
SNTP
Ethernet port
IRIG-B
IRIG-B port
Pulse
Binary input
184
185
Chapter 22 Hardware
Chapter 22 Hardware
186
Chapter 22 Hardware
Introduction
1.1
IED structure
The enclosure for IED is 19 inches in width and 4U in height.
1.2
The modules can be combined through the bus on the rear board.
Both the equipment and the other system can be combined through
the rear interfaces.
Test port
X10
PSM
X9
X8
X7
X6
Ethernet ports
X5
X4
X3
COM
X1
AIM
187
Chapter 22 Hardware
2.1
Introduction
The HMI is simple and easy to be used for routine operation, the front
panel of the HMI consists of LCD, LED and keyboard. As shown in the
following picture, the setting, configuration, monitoring, maintenance and
fault analysis can be performed in HMI.
4
CSC-121
4
CSC-121
188
Chapter 22 Hardware
2.2
1.
2.
LEDs
3.
4.
Arrow keys
5.
Reset key
6.
Quit key
7.
Set key
8.
2.3
LED
The definitions of the LEDs are fixed and described below for 8 LEDs.
Table 124 Definition of 8 LEDs
No
LED
Color
Description
Steady lighting: Operation normally
Run
Green
Flashing: IED startup
Steady lighting: Alarm II, meaning abnormal situation,
only the faulty function is out of service. Power supply
Alarm
Red
189
Chapter 22 Hardware
No
LED
Color
Description
tripping outputs is blocked as well.
The definitions of the LEDs are fixed and described below for 20 LEDs.
Table 125 Definition of 20 LEDs
No
LED
Color
Description
Steady lighting: Operation normally
Run
Green
Flashing: IED startup
Steady lighting: Alarm II, meaning abnormal situation,
only the faulty function is out of service. Power supply
for tripping output is not blocked.
11
Alarm
Red
Flashing: Alarm I, meaning severe internal fault, all
protections are out of service. And power supply for
tripping outputs is blocked as well.
The other LEDs which are not described above can be configured.
2.4
Keyboard
The keyboard is used to monitor and operate IED. The keyboard has the
same look and feel in CSC family. As shown in Figure 56, keyboard is
divided into Arrow keys, Reset key, Quit key, Set key and shorcut function
keys. The specific instructions on the keys as the following table
described:
Table 126 HMI keys on the front of the IED
Key
Function
Up arrow key
Move up in menu
190
Chapter 22 Hardware
Key
Function
Reset key
Set key
Quit key
2.5
IED menu
2.5.1
Menu construction
191
Chapter 22 Hardware
AI
Status
Version
EquipCode
BI
Measure
EventRpt
AlarmRpt
StartRpt
Log
Set Time
Cur Time
Set Time
Contrast
TestEffect
Status
Reports
MainMenu
Settings
Setup
CommuPara
EquipPara
ProtSet
ProtContWd
SOE_Reset
Protocol
ModifyPW
103Type
SetPrint
Test BO
Testing
SimuReSig
SwSetGr
ViewDrift
AdjDrift
ViewScale
AdjScale
PrtSample
192
Chapter 22 Hardware
Table 127 Full name for the menu
Sub-menu
Status
Reports
Full name
Operation status
Reports search
Set time
Setting time
Contrast
LCD contrast
Settings
Setup
Test BO
Testing
2.5.2
Sub menu
Setting value
IED setting
Full name
AI
Analog input
Version
IED version
BI
Binary input
Status
Operation status
EquipCode
Equipment code
Measure
Measurement quantity
EventRpt
Event reports
AlarmRpt
Alarm reports
StartRpt
Startup Rpt
Log
Operation logging
Cur Time
Current time
Set Time
Set time
TestEffect
Test effect
CommuPara
Communication parameter
ProtSet
Protection setting
EquipPara
Equipment parameter
PortContwd
SOE_Reset
ModifyPW
Modify password
SetPrint
Protocol
Protocol selection
103Type
SimuReSig
ViewDrift
ViewScale
View scale
PrtSample
SwSetGr
AdjDrift
AdjScale
Adjust scale
Testing operation
Operation status
Sub-sub
Sub-sub-sub
menu
menu
AI
Status
Sub-sub-sub menu
Explanation
Read the secondary analogure of the
selected CPU module
Version
BI
193
Chapter 22 Hardware
Sub menu
Sub-sub
Sub-sub-sub
menu
menu
Explanation
Off or On
Status
EquipCode
Measure
2.5.3
Sub
Reports search
Sub-sub menu
menu
Sub-sub-sub
Latest Rpt
EventRpt
Last 6 Rpts
Search
Date
AlarmRpt
Search
Date
Reports
Last 6 Rpts
QueryRpt
Date
Search
Date
194
Set time
Last 6 Rpts
Log
Latest Rpt
StartRpt
Last 6 Rpts
2.5.4
Explanation
menu
Chapter 22 Hardware
Sub
Sub-sub menu
menu
Set time
2.5.5
Sub
2.5.6
Sub
Explanation
menu
Cur Time
Set Time
Contrast
Sub-sub menu
menu
Contrast
Sub-sub-sub
Sub-sub-sub
Explanation
menu
TestEffect
Settings
Sub-sub menu
menu
Sub-sub-sub
Explanation
menu
BayName
TimeMode
NetworkTimeMode
PulseTimeMode
IRIG-B TimeMode
EquipAddr
Settings
CommuPara
BaudR485
Voltage
Reclose
Common
Current
CBF
EquipPara
PortContwd
2.5.7
IED setting
Sub
Sub-sub menu
menu
Sub-sub-sub
Explanation
menu
Manual Reset
SOE_Reset
Automatic
Reset
Setup
ModifyPW
103Type
IEC60870-5-103 code
Protocol
195
Chapter 22 Hardware
2.5.8
Sub
menu
Sub-sub-sub
Explanation
menu
Test BO
2.5.9
Sub
Testing operation
Sub-sub menu
menu
Sub-sub-sub
Explanation
menu
Simu Alarm
Simu Linker
TransRecData
SimuReSig
Simu Trip
Simu BI
Simu MST
Alarm
Testing
ViewDrift
ViewScale
PrtSample
SwSetGr
AdjDrift
AdjScale
196
Chapter 22 Hardware
3.1
Introduction
The AI module functions are to transform the secondary signals, from
voltage and current transformers in power system, into weak electric
signals, and perform isolation and anti-interference.
3.2
b01
a01
b02
a02
b03
a03
b04
a04
b05
a05
b06
a06
b07
a07
b08
a08
b09
a09
b10
a10
b11
a11
b12
a12
Analogue
Remark
Input
a01
IA
b01
IA
a02
IB
Star point
Star point
197
Chapter 22 Hardware
b02
IB
a03
IC
b03
IC
a04
IN
b04
IN
a05
Null
b05
Null
a06
Null
b06
Null
a07
Null
b07
Null
a08
Null
b08
Null
a09
Null
b09
Null
a10
Null
b10
Null
a11
Null
b11
Null
a12
Null
b12
Null
Star point
Star point
198
Chapter 22 Hardware
b
b01
a01
b02
a02
b03
a03
b04
a04
b05
a05
b06
a06
b07
a07
b08
a08
b09
a09
b10
a10
b11
a11
b12
a12
Analogue
Remark
Input
a01
IA
b01
IA
a02
IB
b02
IB
a03
IC
b03
IC
a04
IN
b04
IN
a05
I5
b05
I5
a06
Null
b06
Null
a07
Null
b07
Null
a08
Null
Star point
Star point
Star point
Star point
Star point
199
Chapter 22 Hardware
3.3
b08
Null
a09
Null
b09
Null
a10
U4
b10
U4
a11
UB
Star point
b11
UC
Star point
a12
UA
Star point
b12
UN
Star point
Technical data
Internal current transformer
Item
Rated current Ir
Standard
IEC 60255-1
Data
1 or 5 A
0.05 Ir to 30 Ir
0.005 to 1 A
sensitive CT
Power consumption (per
0.1 VA at Ir = 1 A;
phase)
0.5 VA at Ir = 5 A
0.5 VA for sensitive CT
IEC 60255-1
100 Ir for 1 s
IEC 60255-27
4 Ir continuous
IEC 60255-27
100 A for 1 s
sensitive CT
DL/T 478-2001
3 A continuous
Standard
IEC 60255-1
Data
100 V /110 V
0.4 V to 120 V
0.1 VA per phase
IEC 60255-27
DL/T 478-2001
IEC 60255-27
(phase-neutral voltage)
DL/T 478-2001
200
Chapter 22 Hardware
Communication module
4.1
Introduction
The communication module performs communication between the internal
protection system and external equipments such as HMI, engineering
workstation, substation automation system, RTU, etc., to transmit remote
metering, remote signaling, SOE, event reports and record data.
4.2
Ethernet port A
03
04
05
06
Ethernet port B
07
08
09
10
11
Ethernet port C
12
13
14
15
16
Definition
01
Null
02
Null
03
Null
04
Null
05
201
Chapter 22 Hardware
06
07
08
09
Time synchronization
10
11
Null
12
Null
13
Null
14
Null
15
Null
16
Null
Ethernet
Port A
Ethernet
Port B
Ethernet
Port C
4.3
4.3.1
4.3.2
4.3.3
202
Chapter 22 Hardware
Up to 3 electrical or optical Ethernet communication ports are provided to
connect with substation automation system. Two out of these three ports
can work in parallel for protocol, IEC61850 or IEC60870-5-103.
4.3.4
4.4
Technical data
Front communication port
Item
Data
Number
Connection
Communication speed
9600 baud
15 m
Data
Number
0 to 2
Connection
2-wire connector
Rear port in communication module
1.0 km
Test voltage
Chapter 22 Hardware
Item
Data
Electrical communication port
Number
0 to 3
Connection
RJ45 connector
Rear port in communication module
100m
100 Mbit/s
100 Mbit/s
Optical communication port ( optional )
Number
0 to 2
Connection
SC connector
Rear port in communication module
Multi-mode
2.0km
100 Mbit/s
100 Mbit/s
Time synchronization
Item
Data
Mode
Pulse mode
IRIG-B000
Connection
2-wire connector
Rear port in communication module
Voltage levels
204
differential input
Chapter 22 Hardware
5.1
Introduction
The binary input module is used to connect the input signals and alarm
signals such as the auxiliary contacts of the circuit breaker (CB), etc.
5.2
c02
a02
c04
a04
c06
a06
c08
a08
c10
a10
c12
a12
c14
a14
c16
a16
c18
a18
c20
a20
c22
a22
c24
a24
c26
a26
c28
a28
c30
a30
DC -
DC -
c32
a32
Terminal
Definition
Remark
a02
BI1
BI group 1
c02
BI2
BI group 2
a04
BI3
BI group 1
205
Chapter 22 Hardware
c04
BI4
BI group 2
a06
BI5
BI group 1
c06
BI6
BI group 2
a08
BI7
BI group 1
c08
BI8
BI group 2
a10
BI9
BI group 1
c10
BI10
BI group 2
a12
BI11
BI group 1
c12
BI12
BI group 2
a14
BI13
BI group 1
c14
BI14
BI group 2
a16
BI15
BI group 1
c16
BI16
BI group 2
a18
BI17
BI group 1
c18
BI18
BI group 2
a20
BI19
BI group 1
c20
BI20
BI group 2
a22
BI21
BI group 1
c22
BI22
BI group 2
a24
BI23
BI group 1
c24
BI24
BI group 2
a26
BI25
BI group 1
c26
BI26
BI group 2
a28
BI27
BI group 1
c28
BI28
BI group 2
a30
BI29
BI group 1
c30
BI30
BI group 2
Common
a32
DC - Input
terminal of BI
group 1
Common
c32
DC - Input
terminal of BI
group 2
5.3
206
Technical data
Chapter 22 Hardware
Item
Input voltage range
Standard
IEC60255-1
Data
110/125 V
220/250 V
Threshold1: guarantee
IEC60255-1
operation
Threshold2: uncertain
operation
Response time/reset time
Power consumption,
energized
IEC60255-1
207
Chapter 22 Hardware
6.1
Introduction
The binary output modules mainly provide tripping output contacts,
initiating output contacts and signaling output contacts. All the tripping
output relays have contacts with a high switching capacity and are blocked
by protection startup elements.
Each output relay can be configured to satisfy the demands of users.
6.2
208
Chapter 22 Hardware
R
1
R
3
R
5
R
7
R
9
R
11
R
13
R
15
c02
a02
c04
a04
c06
a06
c08
a08
c10
a10
c12
a12
c14
a14
c16
a16
c18
a18
c20
a20
c22
a22
c24
a24
c26
a26
c28
a28
c30
a30
c32
a32
R
2
R
4
R
6
R
8
R
10
R
12
R
14
R
16
209
Chapter 22 Hardware
Table 132 Definition of terminals of BOM A
210
Terminal
Definition
Related relay
a02
Output relay 1
c02
Output relay 1
a04
Output relay 2
c04
Output relay 2
a06
Output relay 3
c06
Output relay 3
a08
Output relay 4
c08
Output relay 4
a10
Output relay 5
c10
Output relay 5
a12
Output relay 6
c12
Output relay 6
a14
Output relay 7
c14
Output relay 7
a16
Output relay 8
c16
Output relay 8
a18
Output relay 9
c18
Output relay 9
a20
Output relay 10
c20
Output relay 10
a22
Output relay 11
c22
Output relay 11
a24
Output relay 12
c24
Output relay 12
a26
Output relay 13
c26
Output relay 13
a28
Output relay 14
c28
Output relay 14
a30
Output relay 15
c30
Output relay 15
a32
Output relay 16
c32
Output relay 16
Chapter 22 Hardware
Binary Output Module C
The module provides 16 output relays for signal, with total 19 contacts.
R
4
R
5
R
1
R
2
R
3
R
6
R
7
c02
a02
c04
a04
c06
a06
c08
a08
c10
a10
c12
a12
c14
a14
c16
a16
c18
a18
c20
a20
c22
a22
c24
a24
c26
a26
c28
a28
c30
a30
c32
a32
R
8
R
9
R
10
R
11
R
12
R
13
R
14
R
15
R
16
211
Chapter 22 Hardware
Table 133 Definition of terminals of BOM C
212
Terminal
Definition
Related relay
a02
c02
a04
Output relay 1
c04
Output relay 1
a06
Output relay 2
c06
Output relay 2
a08
Output relay 3
c08
Output relay 3
a10
c10
a12
Output relay 4
c12
Output relay 7
a14
Output relay 5
c14
Output relay 6
a16
Output relay 8
c16
Output relay 8
a18
Output relay 9
c18
Output relay 9
a20
Output relay 10
c20
Output relay 10
a22
Output relay 11
c22
Output relay 11
a24
Output relay 12
c24
Output relay 12
a26
Output relay 13
c26
Output relay 13
a28
Output relay 14
c28
Output relay 14
a30
Output relay 15
c30
Output relay 15
a32
Output relay 16
c32
Output relay 16
Chapter 22 Hardware
6.3
Technical data
Item
Standard
Data
IEC60255-1
250V
/~
IEC60255-1
5 A continuous,
30A200ms ON, 15s OFF
Making capacity
IEC60255-1
1100 W(
) at inductive load
with L/R>40 ms
1000 VA(AC)
Breaking capacity
Mechanical endurance,
IEC60255-1
IEC60255-1
Unloaded
220V
, 0.15A, at L/R40 ms
110V
, 0.30A, at L/R40 ms
50,000,000 cycles (3 Hz
switching frequency)
IEC60255-1
1000 cycles
Mechanical endurance,
IEC60255-1
1000 cycles
IEC60255-1
UL/CSATV
breaking
Specification state verification
IEC60255-23
IEC61810-1
Contact circuit resistance
IEC60255-1
measurement
IEC60255-23
30m
IEC61810-1
Open Contact insulation test
IEC60255-1
IEC60255-27
IEC60255-1
AC1000V 1min
55
and materials
213
Chapter 22 Hardware
7.1
Introduction
The power supply module is used to provide the correct internal voltages and
full isolation between the terminal and the battery system.
7.2
a
DC 24V +
OUTPUTS
a08
c08
DC 24V OUTPUTS
a10
c12
a12
c14
a14
c16
a16
c18
a18
c20
c22
AUX.DC +
INPUT
c24
c26
c28
a20
a22
a24
AUX. DC INPUT
a26
a28
c30
a30
c32
a32
214
a04
a06
c06
c10
a02
Chapter 22 Hardware
Table 134 Definition of terminals of PSM
Terminal
Definition
a02
c02
a04
c04
a06
c06
a08
c08
a10
c10
a12
c12
a14
c14
a16
c16
a18
c18
a20
c20
a22
c22
a24
c24
a26
c26
a28
c28
a30
215
Chapter 22 Hardware
7.3
c30
a32
c32
Technical data
Item
Standard
Data
IEC60255-1
110 to 250V
Permissible tolerance
IEC60255-1
%20 Uaux
Power consumption at
IEC60255-1
quiescent state
Power consumption at
module
IEC60255-1
maximum load
Inrush Current
IEC60255-1
216
Chapter 22 Hardware
Techinical data
8.1
Type tests
8.1.1
Standard
Data
IEC60255-27
Category III
Pollution degree
IEC60255-27
Degree 2
Insulation
IEC60255-27
Basic insulation
IEC60255-27
IEC 60529
IEC 60255-5
2KV, 50Hz
withstand test
EN 60255-5
2.8kV
ANSI C37.90
GB/T 15145-2001
DL/T 478-2001
CT / VT inputs
binary inputs
binary outputs
case earth
500V, 50Hz
between the following circuits:
Communication ports to
case earth
time synchronization
terminals to case earth
IEC60255-5
IEC 60255-27
If Ui63V
EN 60255-5
1kV if Ui<63V
ANSI C37.90
GB/T 15145-2001
circuits:
DL/T 478-2001
217
Chapter 22 Hardware
Item
Insulation resistance
Standard
Data
100 M at 500 V
IEC60255-5
IEC 60255-27
EN 60255-5
ANSI C37.90
GB/T 15145-2001
DL/T 478-2001
IEC60255-27
0.1
Fire withstand/flammability
IEC60255-27
Class V2
8.1.2
Standard
Data
IEC60255-22-1
Class III
IEC60255-26
2.5 kV CM ; 1 kV DM
IEC61000-4-18
EN 60255-22-1
ANSI/IEEE C37.90.1
CT / VT inputs
binary inputs
binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
communication ports
Electrostatic discharge
IEC 60255-22-2
Level 4
IEC 61000-4-2
8 kV contact discharge;
EN 60255-22-2
IEC 60255-22-3
Frequency sweep:
disturbance test
EN 60255-22-3
IEC 60255-22-3
Pulse-modulated
disturbance test
EN 60255-22-3
218
Chapter 22 Hardware
Item
Standard
Data
IEC 60255-22-4,
Class A, 4KV
immunity test
IEC 61000-4-4
EN 60255-22-4
ANSI/IEEE C37.90.1
CT / VT inputs
binary inputs
binary outputs
Class A, 1KV
Tested on the following circuits:
communication ports
IEC 60255-22-5
4.0kV L-E
IEC 61000-4-5
2.0kV L-L
Tested on the following circuits:
auxiliary power supply
CT / VT inputs
binary inputs
binary outputs
500V L-E
Tested on the following circuits:
communication ports
IEC 60255-22-6
IEC 61000-4-6
MHz
spot frequencies: 27 MHz and
68 MHz
10 V
AM, 80%, 1 kHz
IEC60255-22-7
Class A
300 V CM
150 V DM
IEC 61000-4-8
test
100 kHz burst immunity test
Level 4
30 A/m cont. / 300 A/m 1 s to 3 s
IEC61000-4-18
2.5 kV CM ; 1 kV DM
Tested on the following circuits:
auxiliary power supply
CT / VT inputs
binary inputs
binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
communication ports
219
Chapter 22 Hardware
8.1.3
DC voltage dips
Standard
IEC 60255-11
Data
100% reduction 20 ms
60% reduction 200 ms
30% reduction 500 ms
DC voltage interruptions
IEC 60255-11
100% reduction 5 s
DC voltage ripple
IEC 60255-11
IEC 60255-11
/start-up
8.1.4
IEC 60255-11
1 min
Radiated emission
Standard
Data
IEC60255-25
EN60255-25
up to 5 GHz)
CISPR22
Conducted emission
IEC60255-25
0.15MHz to 30MHz
EN60255-25
CISPR22
8.1.5
Mechanical tests
Item
Standard
Data
IEC60255-21-1
Class 1
test
EN 60255-21-1
10 Hz to 60 Hz: 0.075 mm
60 Hz to 150 Hz: 1 g
1 sweep cycle in each axis
Relay energized
Sinusoidal Vibration
IEC60255-21-1
Class 1
endurance test
EN 60255-21-1
10 Hz to 150 Hz: 1 g
20 sweep cycle in each axis
Relay non-energized
220
IEC60255-21-2
Class 1
EN 60255-21-2
5 g, 11 ms duration
Chapter 22 Hardware
3 shocks in both directions of 3
axes
Relay energized
Shock withstand test
IEC60255-21-2
Class 1
EN 60255-21-2
15 g, 11 ms duration
3 shocks in both directions of 3
axes
Relay non-energized
Bump test
IEC60255-21-2
Class 1
10 g, 16 ms duration
1000 shocks in both directions of
3 axes
Relay non-energized
Seismic test
IEC60255-21-3
Class 1
X-axis 1 Hz to 8/9 Hz: 7.5 mm
X-axis 8/9 Hz to 35 Hz :2 g
Y-axis 1 Hz to 8/9 Hz: 3.75 mm
Y-axis 8/9 Hz to 35 Hz :1 g
1 sweep cycle in each axis,
Relay energized
8.1.6
Climatic tests
Item
Standard
IEC60255-27
Data
-10C, 16 hours, rated load
IEC60068-2-1
Cold test Storage
IEC60255-27
-25C, 16 hours
IEC60068-2-1
Dry heat test Operation
[IEC60255-27
IEC60068-2-2
Dry heat test Storage
IEC60255-27
+70C, 16 hours
IEC60068-2-2
Change of temperature
Damp heat static test
Damp heat cyclic test
IEC60255-27
IEC60068-2-14
-10C / +55C
IEC60255-27
IEC60068-2-78
load
IEC60255-27
IEC60068-2-30
load
221
Chapter 22 Hardware
8.2
CE Certificate
Item
EMC Directive
8.3
Data
IED design
Item
Data
Case size
4U19inch
Weight
10kg
222
Chapter 22 Hardware
223
Chapter 23 Appendix
Chapter 23 Appendix
224
Chapter 23 Appendix
1.1
No
Parameter
Description
U_Primary
U_Secondary
CT_Primary
CT_Secondary
3I0_Primary
3I0_Secondary
Min.
Max.
kV
100.0
800.0
100.0
120.0
kA
0.05
5.00
1.00
5.00
kA
0.05
5.00
1.00
5.00
I5_Primary
Primary I5 current
kA
0.05
5.00
I5_Secondary
Secondary I5 current
1.00
5.00
T_Relay Reset
0.50
10.00
10
I_VT Fail
0.05
1.00
0.05
1.00
7.00
20.00
10.00
30.00
40.00
65.00
0.05
10.00
Unit
3I02_VT Fail
12
Upe_VT Fail
13
Upp_VT Fail
14
Upe_VT Normal
15
3I0_CT Fail
16
I_OL Alarm
0.05
100.0
17
T_OL Alarm
0.10
6000.
18
I_OC1
0.05
100.0
19
T_OC1
0.00
60.00
20
I_OC2
0.05
100.0
21
T_OC2
0.00
60.00
22
Curve_OC Inv
12
23
I_OC Inv
0.05
100.0
24
K_OC Inv
0.05
999.0
25
A_OC Inv
0.005
200.0
225
Chapter 23 Appendix
No
Parameter
Description
Unit
Min.
Max.
overcurrent
26
B_OC Inv
27
P_OC Inv
28
Angle_OC
29
Ratio_I2/I1
30
Imax_2H_UnBlk
31
T2h_Cross_Blk
32
3I0_EF1
33
T_EF1
34
3I0_EF2
35
T_EF2
36
Curve_EF Inv
37
3I0_EF Inv
38
K_EF Inv
39
A_EF Inv
40
B_EF Inv
41
P_EF Inv
42
Angle_EF
43
Angle_Neg
44
Ratio_I2/I1
45
Imax_2H_UnBlk
46
Ratio_I02/I01
0.00
60.00
0.005
10.00
0.00
90.00
0.07
0.50
0.10
100.0
0.00
60.00
0.05
100.0
0.00
60.00
0.05
100.0
0.00
60.00
12
0.05
100.0
0.05
999.0
0.005
200.0
0.00
60.00
0.005
10.00
0.00
90.00
0.00
90.00
0.07
0.50
0.10
100.0
0.07
0.50
0.10
100.0
0.05
100.0
47
3I0max_2H_UnBlk
48
226
3I0_NOC1
Chapter 23 Appendix
No
Parameter
49
T_NOC1
50
3I0_NOC2
51
T_NOC2
52
Curve_NOC Inv
53
3I0_NOC Inv
54
K_NOC Inv
55
A_NOC Inv
56
B_NOC Inv
57
P_NOC Inv
58
Angle_NOC
59
Ratio_I02/I01
Description
Delay time for first stage neutral
Unit
Min.
Max.
0.00
60.00
0.05
100.0
0.00
60.00
12
0.05
100.0
0.05
999.0
0.005
200.0
0.00
60.00
0.005
10.00
0.00
90.00
0.07
0.50
0.10
100.0
0.005
1.00
0.00
60.00
0.005
1.00
0.00
60.00
12
0.00
1.00
0.05
999.0
0.005
200.0
0.00
60.00
0.005
10.00
0.00
90.00
current
Second stage neutral current
Delay time for second stage neutral
current
Inverse time curve of neutral current
Current setting for neutral inverse time
current
60
3I0max_2H_UnBlk
61
I_SEF1
62
T_SEF1
63
I_SEF2
64
T_SEF2
65
Curve_SEF Inv
66
I_SEF Inv
67
K_SEF Inv
68
A_SEF Inv
69
B_SEF Inv
70
P_SEF Inv
71
Angle_SEF
227
Chapter 23 Appendix
No
Parameter
Description
Unit
Min.
Max.
sequence direction
Sensitive angle for sensitive zero
72
IsCOS_SEF
73
U_SEF
74
3I2_NSOC1
75
T_NSOC1
76
3I2_NSOC2
77
T_NSOC2
78
Curve_NSOC Inv
79
3I2_NSOC Inv
80
K_NSOC Inv
81
A_NSOC Inv
82
B_NSOC Inv
83
P_NSOC Inv
84
I_STUB
85
T_STUB
86
I_Thermal OL Trip
87
I_Thermal OL Alarm
88
T_Const Thermal
89
90
U_3V01
91
T_3V01
92
U_3V02
93
T_3V02
94
U_OV1
228
0.005
1.00
2.00
100.0
0.05
100.0
0.00
60.00
0.05
100.0
0.00
60.00
12
0.05
100.0
0.05
999.0
0.005
200.0
0.00
60.00
0.005
10.00
0.05
100.0
0.00
60.00
0.10
25.00
0.10
25.00
1.00
9999.
1.00
9999.
2.00
100.0
0.00
60.00
2.00
100.0
0.00
60.00
40.00
200.0
Chapter 23 Appendix
No
Parameter
95
T_OV1
96
U_OV2
97
T_OV2
98
Dropout_OV
99
U_UV1
100
T_UV1
101
U_UV2
102
T_UV2
103
Dropout_UV
104
I_UV Chk
105
I_CBF
106
3I0_CBF
107
3I2_CBF
108
T_CBF1
109
T_CBF 1P Trip 3P
110
T_CBF2
111
3I0_PD
112
3I2_PD
113
T_PD
114
T_Dead Zone
115
T_1P AR1
116
T_1P AR2
Description
Time delay setting for first stage
overvoltage protection
Voltage setting for second stage
overvoltage protection
Time delay setting for second stage
overvoltage protection
Unit
0.00
60.00
40.00
200.0
0.00
60.00
0.90
0.99
5.00
150.0
0.00
120.0
5.00
150.0
0.00
120.0
1.01
2.00
0.05
10.00
0.05
100.0
0.05
100.0
0.05
100.0
0.00
32.00
0.05
32.00
0.10
32.00
0.05
100.0
0.05
100.0
0.00
60.00
0.00
32.00
0.05
10.00
0.05
10.00
protection
undervoltage protection
Time delay setting for first stage
undervoltage protection
Voltage setting for second stage
undervoltage protection
Time delay setting for second stage
undervoltage protection
Dropout coefficient for undervoltage
protection
Current setting for undervoltage check
Phase current setting for circuit
breaker fail startup
Zero sequence current setting for
circuit breaker fail protection
Negative sequence current setting for
circuit breaker fail protection
Delay time setting for stage 1 of circuit
breaker fail protection
Prolonged three trip
Time for stage 1 of circuit breaker fail
Delay time setting for stage 2 of circuit
breaker fail protection
Zero sequence current setting for
three pole discordance
Negative sequence current setting for
three pole discordance
Time delay setting for three pole
discordance
Time delay setting for dead zone
protection
Time delay setting 1 for single phase
auto-reclosing
Time delay setting 2 for single phase
Max.
Min.
229
Chapter 23 Appendix
No
Parameter
Description
Unit
Min.
Max.
auto-reclosing
Time delay setting 3 for single phase
117
T_1P AR3
118
T_1P AR4
119
T_3P AR1
120
T_3P AR2
121
T_3P AR3
122
T_3P AR4
123
Angle_Syn Diff
124
U_Syn Diff
125
Freq_Syn Diff
126
T_Action
127
T_Reclaim
128
T_CB Faulty
129
Times_AR
130
T_Syn Check
131
T_MaxSynExt
132
T_AR Reset
133
Umin_Syn
134
Umax_Energ
135
T_WaitMaster
1.2
0.05
10.00
0.05
10.00
0.05
60.00
0.05
60.00
0.05
60.00
0.05
60.00
1.00
80.00
1.00
40.00
Hz
0.02
2.00
ms
80.00
500.0
0.05
60.00
0.50
60.00
0.00
60.00
0.05
60.00
0.50
60.00
30.00
65.00
10.00
50.00
0.01
60.00
auto-reclosing
Time delay setting 4 for single phase
auto-reclosing
Time delay setting 1 for three phase
auto-reclosing
Time delay setting 2 for three phase
auto-reclosing
Time delay setting 3 for three phase
auto-reclosing
Time delay setting 4 for three phase
auto-reclosing
Angle difference setting for
synchronization check
Voltage difference setting for
synchronization check
Frequency difference setting for
synchronization check
Pulse length setting for auto-reclosing
Time setting for successful
auto-reclosing determination
Time setting for spring charging
auto-reclosing number
No
Setting
VT_Line
Description
VT installed at line side or source
side
Unit
Min.
Max.
BI SetGrp Switch
230
Chapter 23 Appendix
No
Setting
Description
Enable or disable the test mode
Unit
Min.
Max.
I5 for SEF
Func_VT Fail
Solid Earth
Func_CT Fail
10
Func_OL
11
Func_OC1
12
OC1 Direction
13
14
15
Func_OC2
16
OC2 Direction
17
18
19
Func_OC Inv
20
OC Inv Direction
21
22
23
Blk OC at VT Fail
24
OC Init CBF
231
Chapter 23 Appendix
No
Setting
Description
Unit
Min.
Max.
Func_EF1
26
EF1 Direction
27
28
29
Func_EF2
30
EF2 Direction
31
32
33
Func_EF Inv
34
EF Inv Direction
35
36
37
EF U2/I2 Dir
38
39
Blk EF at VT Fail
40
Blk EF at CT Fail
41
3I0 Calculated
42
3U0 Calculated
232
Chapter 23 Appendix
No
Setting
43
EF Init CBF
44
Func_NOC1
45
NOC1 Direction
Description
EF protection initiate CBF
protection or not
Neutral earth fault stage 1 enabled
or disabled
Direction of neutral earth fault stage
1 enabled or disabled
Unit
Min.
Max.
47
48
Func_NOC2
49
NOC2 Direction
50
51
52
Func_NOC Inv
53
54
55
56
57
3U0 Calculated
58
59
Func_SEF1
60
SEF1 Trip
61
SEF1 Direction
62
Func_SEF2
233
Chapter 23 Appendix
No
Setting
63
SEF2 Trip
64
SEF2 Direction
65
Func_SEF Inv
66
Description
Sensitive earth fault stage 2 trip or
alarm
Direction of sensitive earth fault
stage 2 enabled or disabled
Sensitive earth fault inverse time
stage enabled or disabled
Sensitive earth fault inverse time
stage
trip or alarm
Unit
Min.
Max.
68
69
70
3U0 Calculated
71
72
Func_NSOC1
73
NSOC1 Trip
74
Func_NSOC2
75
Func_NSOC Inv
76
77
78
Func_STUB
79
80
Func_Thermal OL
234
Chapter 23 Appendix
No
Setting
81
Cold Curve
82
83
Func_3V01
84
3V01 Trip
85
Func_3V02
86
3V02 Trip
87
3U0 Calculated
88
89
Func_OV1
90
OV1 Trip
91
Func_OV2
92
OV2 Trip
Description
Cold Curve or Hot Curve
Thermal overload protection initiate
CBF protection
Displacement voltage stage 1
enabled or disabled
Displacement voltage stage 1 trip or
alarm
Displacement voltage stage 2
enabled or disabled
Displacement voltage stage 2 trip or
alarm
Displacement voltage is calculated
or measured form VT
Displacement voltage protection
initiate CBF enabled or disabled
Overvoltage stage 1 enabled or
disabled
Overvoltage stage 1 trip or alarm
Overvoltage stage 2 enabled or
disabled
Overvoltage stage 2 trip or alarm
Unit
Min.
Max.
OV Chk PE
94
OV Init CBF
95
Func_UV1
96
UV1 Trip
97
Func_UV2
98
UV2 Trip
99
UV Chk Current
100
UV Chk CB Status
101
UV Chk PE
235
Chapter 23 Appendix
No
Setting
102
103
Func_CBF
Description
Checking three phase voltage for
undervoltage protection
CBF protection enabled or disabled
Unit
Min.
Max.
CBF 1P Trip 3P
105
106
108
Func_PD
109
PD Chk 3I0/3I2
110
PD Init CBF
111
Func_Dead Zone
112
AR_1p mode
113
AR_3p mode
114
AR_1p(3p) mode
115
AR_Disable
116
AR_Override
117
AR_EnergChkDLLB
118
AR_EnergChkLLDB
119
AR_EnergChkDLDB
120
AR_Syn check
121
AR_Chk3PVol
122
AR Final Trip
123
1P CBOpen Init AR
236
enabled or disabled
Checking 3I0/3I2 criteria for PD
protection enabled or disabled
PD protection initiate CBF
protection
Dead zone protection enabled or
disabled
Single phase mode for
auto-reclosing function
Three phase mode for
auto-reclosing function
One and three phase mode for
auto-reclosing function
auto-reclosing function disabled
Override mode for AR enabled or
disabled
Chapter 23 Appendix
No
Setting
124
3P CBOpen Init AR
125
Mode_3/2CB
126
CB_Master
Description
AR initiated by three phase CB
open
One and a half breaker
arrangement
Side breaker or tie breaker
Unit
Min.
Max.
237
Chapter 23 Appendix
Description
Relay Startup
BI Change
BI SetGroup Mode
Not Used
Not used
OC1 Trip
OC2 Trip
OC Inv Trip
Inrush Blk OC
Not Used
Not used
10
EF1 Trip
11
EF2 Trip
12
EF Inv Trip
13
Inrush Blk EF
14
Not Used
Not used
15
NOC1 Trip
16
NOC2 Trip
17
18
19
Not Used
Not used
20
SEF1 Trip
21
SEF2 Trip
22
23
Not Used
24
NSOC1 Trip
25
NSOC2 Trip
26
27
STUB Trip
28
Therm OL Startup
29
Thermal OL Trip
30
3V01 Trip
31
3V02 Trip
32
OV1 Trip
33
OV2 Trip
34
UV1 Trip
35
UV2 Trip
36
CBF Startup
238
Protection startup
Binary input change
Binary input setting group mode
Chapter 23 Appendix
No
Description
37
CBF1 Trip
38
CBF 1P Trip 3P
39
CBF2 Trip
40
PD Trip
41
Not Used
42
43
1st Reclose
44
2nd Reclose
45
3rd Reclose
46
4th Reclose
47
48
49
50
51
52
53
54
AR Block
Auto-reclosing blocking
55
Not Used
Not Used
56
Syn Request
57
AR_EnergChk OK
58
Syn Failure
59
Syn OK
60
61
62
63
EnergChk fail
64
AR Success
Auto-reclosing success
65
AR Final Trip
66
AR in progress
67
AR Failure
68
AR Wait
Synchro-check request
Energizing check for Auto-reclosing ok
Synchro-check failure
Synchro-check ok
Auto-reclosing in progress
Auto-reclosing failure
Auto-reclosing wait
Table 136 alarming report list
No
1
Description
Displacement voltage protection trip fail
239
Chapter 23 Appendix
No
Description
3V01 Alarm
3V02 Alarm
AI Channel Err
AR Mode Alarm
Battery Off
BI Breakdown
BI Check Err
BI Comm Fail
10
BI Config Err
11
BI EEPROM Err
12
BI Input Err
13
14
BI_V1P_MCB Err
15
BI_V3P_MCB Err
16
BO Breakdown
17
BO Comm Fail
18
BO Config Err
19
BO EEPROM Err
20
BO No Response
21
CB Err Blk PD
22
CT Fail
23
EF Trip Fail
24
EquipPara Err
25
26
NO/NC Discord
27
28
29
30
NSOC1 Alarm
31
OC Trip Fail
32
OV Trip Fail
33
OV1 Alarm
34
OV2 Alarm
35
Overload Alarm
36
PD Trip Fail
37
38
39
40
41
Sampling Err
240
Battery off
Chapter 23 Appendix
No
Description
Sensitive earth fault protection inverse time stage
42
43
44
SEF1 Alarm
45
SEF2 Alarm
46
SetGroup Err
47
Setting Err
48
49
50
51
52
SysConfig Err
53
Test BO Un_reset
54
55
Thermal OL Alarm
56
UV Trip Fail
57
UV1 Alarm
58
UV2 Alarm
59
V1P_MCB VT Fail
60
V3P_MCB VT Fail
61
VT Fail
alarm
Setting error
Software version error
SRAM check error
VT fail
Table 137 operation report list
No
Description
SwSetGroup OK
Write Set OK
WriteEquipParaOK
WriteConfig OK
AdjScale OK
Not Used
Not used
Not Used
Not used
ClrConfig OK
Clear configuration OK
Reset Config
Reset configuration
10
Test BO OK
11
AdjDrift OK
12
13
14
VT Recovery
VT recovery
15
CaluFreqOK
Calculation frequency OK
16
Test mode On
Test mode On
17
241
Chapter 23 Appendix
No
Description
18
Func_OC On
19
Func_OC Off
20
Func_EF On
21
Func_EF Off
22
Func_NOC On
23
Func_NOC Off
24
Func_SEF On
25
Func_SEF Off
26
Func_NSOC On
27
Func_NSOC Off
28
Func_STUB On
29
Func_STUB Off
30
Func_Therm OL On
31
Fun_Therm OL Off
32
Func_OL On
33
Func_OL Off
34
Func_3V0 On
35
Func_3V0 Off
36
Func_OV On
37
Func_OV Off
38
Func_UV On
39
Func_UV Off
40
Func_CBF On
41
Func_CBF Off
42
Func_PD On
43
Func_PD Off
44
Func_DZ On
45
Func_DZ Off
46
Func_AR On
47
Func_AR Off
48
AR Syn On
Synchro-check for AR on
49
AR Syn Off
50
AR EnergChk On
51
AR EnergChk Off
52
AR Override On
Override for AR on
53
AR Override Off
54
Func_VT Fuse On
55
56
Func_CT Fail On
Function of CT fail on
57
242
Chapter 23 Appendix
No
58
Description
CPU reset
243
Chapter 23 Appendix
Typical connection
A. Application for line
A
B
C
Protection IED
a01
b01
IA
a02
b02
IB
a03
b03
IC
a04
b04
a12
a11
b11
b12
IN
UA
UB
UC
UN
a10
b10
244
U4
Chapter 23 Appendix
B. Application for transformer
A
B
C
Protection IED
a12
a11
b11
b12
UA
UB
UC
UN
a01
b01
IA
a02
b02
IB
a03
b03
IC
a04
b04
IN
A B C
b05
I5
a05
A
B
C
245
Chapter 23 Appendix
C. Application for sensitive earth fault protection
A
B
C
Protection IED
a01
b01
IA
a02
b02
IB
a03
b03
IC
a04
b04
a12
a11
b11
b12
IN
UA
UB
UC
UN
b05
I5
a05
246
Chapter 23 Appendix
4.1
Curves No.
4.2
IDMTL Curves
Parameter A
Parameter P
Parameter B
IEC INV.
0.14
0.02
13.5
1.0
80.0
2.0
120.0
1.0
ANSI INV.
8.9341
2.0938
0.17966
0.2663
1.2969
0.03393
5.6143
2.18592
ANSI MODERATELY
INV.
0.0103
0.02
0.0228
3.922
2.0
0.0982
10
5.64
2.0
0.02434
11
0.4797
1.5625
0.21359
t=
i p
1
I
+B K
Equation 10
247
Chapter 23 Appendix
where:
A: Time factor for inverse time stage
B: Delay time for inverse time stage
P: index for inverse time stage
K: Time multiplier
4.3
248
Chapter 23 Appendix
The typical 11 curves where K=0.025 is shown in the following figure:
0.1
Time in Seconds
IEC INV.
IEC VERY INV.
IEC EXTE INV.
IEC LONG INV.
ANSI INV.
ANSI SHORT INV.
ANSI LONG INV.
ANSI MODE INV.
0.01
0.001
0.0001
1
10
100
Id/I_Inv
249
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC INV. Curve in the
following figure:
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1.0
K=1.25
0.1
0.01
1
10
I/Is
250
100
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC VERY INV. Curve in
the following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
100
I/Is
251
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC EXTREMELY INV.
Curve in the following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
I/Is
252
100
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC LONG INV. Curve in
the following figure:
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1
10
100
I/Is
253
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ASNI INV. Curve in the
following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
100
I/Is
254
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI SHOTR INV. Curve
in the following figure:
Time in Seconds
0.1
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
0.0001
10
100
I/Is
Figure 74 Typical ANSI SHORT INV. Curves
255
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI LONG INV. Curve in
the following figure:
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1
10
I/Is
Figure 75 Typical ANSI LONG INV. Curves
256
100
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI MODETATELY INV.
Curve in the following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
100
I/Is
Figure 76 Typical ANSI MODETATELY INV. Curve
257
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSIVERY INV. Curve in
the following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
I/Is
Figure 77 Typical ANSI VERY INV. Curves
258
100
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI EXTREMELY INV.
Curve in the following figure:
Time in Seconds
0.1
K=0.025
K=0.2
K=0.5
K=1
0.01
K=1.5
0.001
1
0.0001
10
100
I/Is
259
Chapter 23 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI DEFINITE INV.
Curve in the following figure:
Time in Seconds
K=0.025
0.1
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1
10
I/Is
Figure 79 Typical ANSI DEFINITE INV. Curves
260
100
Chapter 23 Appendix
CT requirement
5.1
Overview
In practice, the conventional magnetic- core current transformer (hereinafter
as referred CT) is not able to transform the current signal accurately in whole
fault period of all possible faults because of manufactured cost and
installation space limited. CT Saturation will cause distortion of the current
signal and can result in a failure to operate or cause unwanted operations of
some functions. Although more and more protection IEDs have been
designed to permit CT saturation with maintained correct operation, the
performance of protection IED is still depended on the correct selection of CT.
5.2
Chapter 23 Appendix
Accuracy limit defined by peak instantaneous error during specified transient
duty cycle. No limit for remanent flux.
Class TPY CT
Accuracy limit defined by peak instantaneous error during specified transient
duty cycle. Remanent flux not to exceed 10% of the saturation flux..
Class TPZ CT
Accuracy limit defined by peak instantaneous alternating current component
error during single energization with maximum d.c. offset at specified
secondary loop time constant. No requirements for d.c. component error limit.
Remanent flux to be practically negligible.
TPE class CT (TPE represents transient protection and electronic type
CT)
5.3
Description
Esl
Eal
Ek
Uk
Kalf
Kssc
Kssc
Kssc
Kpcf
Ks
Kx
Dimensioning factor
Ktd
Ipn
Isn
Ipsc
Ipcf
Isscmax
Rct
Rb
Rb
Rs
262
Chapter 23 Appendix
corrected to 75, unless otherwise specified,
and inclusive of all external burden connected.
Rlead
Zbn
Zb
Tp
Ts
5.4
5.4.1
To reduce the influence of transient state, Kalf, Accuracy limit factor of CT,
should be larger than the following requirement
>
+ +
+ +
263
Chapter 23 Appendix
=
5.4.2
CT class
The selected CT should guarantee that the error is within the required
accuracy limit at steady symmetric short circuit current. The influence of short
circuit current DC component and remanence should be considered, based
on extent of system transient influence, protection function characteristic,
consequence of transient saturation and actual operating experience. To fulfill
the requirement on a specified time to saturation, the rated equivalent
secondary e.m.f of CTs must higher than the required maximum equivalent
secondary e.m.f that is calculated based on actual application.
For the CTs applied to transmission line protection, transformer differential
protection with 330kV voltage level and above, and 300MW and above
generator-transformer set differential protection, the power system time
constant is so large that the CT is easy to saturate severely due to system
transient state. To prevent the CT from saturation at actual duty cycle, TP
class CT is preferred.
For TPS class CT, Eal (rated equivalent secondary limiting e.m.f) is generally
determined as follows:
= ( + )
Where
Ks: Specified transient factor
Kssc: Rated symmetrical short-circuit current factor
For TPX, TPY and TPZ class CT, Eal (rated equivalent secondary limiting
e.m.f) is generally determined as follows:
= ( + )
Where
Ktd: Rated transient dimensioning factor
Considering at short circuit current with 100% offset
For C-t-O duty cycle,
K td =
t
t
Tp Ts
e TP e T s + 1
Tp Ts
Chapter 23 Appendix
K td
t
t
Tp Ts
=
e TP e Ts
Tp Ts
t fr +t
e Ts
"
"
t
t
Tp Ts
+
e TP e T s
Tp Ts
+1
5.4.3
Accuracy class
The CT accuracy class should guarantee that the protection relay applied is
able to operate correctly even at a very sensitive setting, e.g. for a sensitive
residual overcurrent protection. Generally, the current transformer should
have an accuracy class, which have an current error at rated primary current,
that is less than 1% (e.g. class 5P).
If current transformers with less accuracy are used it is advisable to check the
actual unwanted residual current during the commissioning.
5.4.4
Ratio of CT
265
Chapter 23 Appendix
The current transformer ratio is mainly selected based on power system data
like e.g. maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to
be detected with the selected CT ratio. The minimum operating current is
different for different functions and settable normally. So each function should
be checked separately.
5.4.5
5.4.6
Secondary burden
Too high flux will result in CT saturation. The secondary e.m.f is directly
proportional to linked flux. To feed rated secondary current, CT need to
generate enough secondary e.m.f to feed the secondary burden.
Consequently, Higher secondary burden, need Higher secondary e.m.f, and
then closer to saturation. So the actual secondary burden Rb must be less
than the rated secondary burden Rb of applied CT, presented
Rb > Rb
The CT actual secondary burden Rb consists of wiring loop resistance Rlead
and the actual relay burdens Zb in whole secondary circuit, which is
calculated by following equation
Rb = Rlead + Zb
The rated relay burden, Zbn, is calculated as below:
=
Where
Sr: the burden of IED current input channel per phase, in VA;
For earth faults, the loop includes both phase and neutral wire, normally twice
the resistance of the single secondary wire. For three-phase faults the neutral
current is zero and it is just necessary to consider the resistance up to the
point where the phase wires are connected to the common neutral wire. The
most common practice is to use four wires secondary cables so it normally is
sufficient to consider just a single secondary wire for the three-phase case.
266
Chapter 23 Appendix
In isolated or high impedance earthed systems the phase-to-earth fault is not
the considered dimensioning case and therefore the resistance of the single
secondary wire always can be used in the calculation, for this case.
5.5
5.5.1
"
" =
267
Chapter 23 Appendix
To 220kV transmission line protection, Class 5P20 CT is preferred. Because
the system time constant is less relatively, and then DC component is less,
the probability of CT saturation due to through fault current at external fault is
reduced more and more.
Esl can be verified as below:
> = +
Where
Ks: Specified transient factor, 2 recommended
Only at special case, e.g. short output feeder of large power plant, the PX
class CT is recommended. Ek should be verified based on below equation.
> = +
Where
Ks: Specified transient factor, 2 recommended
5.5.2
268
Chapter 23 Appendix
> = +
Where
Ks: Specified transient factor, 2 recommended
For PX class CT, Ek can be verified as below:
> = +
Where
Ks: Specified transient factor, 2 recommended
5.5.3
>
5.5.4
Distance protection
For 330kV and above transmission line protection, TPY CT is preferred. To
guarantee the accuracy, Kssc should be satisfied following requirement:
> , ", 20
Where
"
" =
Chapter 23 Appendix
Considering auto-reclosing operation, Eal should meet the following
requirement, at C-O-C-O duty cycle
> ( + )
Where
Ktd: Recommended transient dimensioning factor for verification, 3.
recommended for line which length is shorter than 50kM, 5 recommended for
line which length is longer than 50kM
To 220kV voltage and below transmission line protection, P Class CT is
preferred, e.g. 5P20.
Esl can be verified as below:
> = +
Where
Ks: Specified transient factor, 2 recommended
Only at special case, e.g. short output feeder of large power plant, the PX
class CT is recommended. Ek should be verified based on below equation.
> = +
Where
Ks: Specified transient factor, 2 recommended
5.5.5
"
" =
Chapter 23 Appendix
Where
Ktd: Recommended transient dimensioning factor for verification, 1.2
recommended
For P Class and PR class CT,
Kalf should be satisfied following requirement:
>
+
+
Where
= , ", 20
"
" =
5.5.6
271
Chapter 23 Appendix
Ipcf: Maximum applied primary startup current setting value (A)
Considering auto-reclosing operation, Eal should meet the following
requirement, at C-O duty cycle
> ( + )
Where
Ktd: Recommended transient dimensioning factor for verification, 1.2
recommended
For P Class and PR class CT,
Kalf should be satisfied following requirement:
>
+
+
Where
= 20
=
272