Professional Documents
Culture Documents
I. INTRODUCTION
valid under both steady state and transient conditions. The GIC
concept has been used to realize a series negative inductance
compensator for high power distribution/transmission systems
as a potential flexible ac transmission system (FACTS) device
[2]. The GIC realized series negative inductance compensator
offers the same fundamental frequency characteristics as a series capacitor, without the subsynchronous resonance problem
associated with fixed series capacitor compensation systems.
Further, it provides variable VAR compensation capabilities
and greatly reduced size compared to conventional thyristor
switched capacitor systems. A similar concept of a series
negative inductance compensator has been recently proposed
as variable activepassive reactance in [3][5].
In this paper, a new control scheme is proposed to achieve
dynamically varying negative or positive inductances at single
or multiple dominant harmonic frequencies, based on the GIC
principle. This concept of variable inductance has been applied
to a parallel hybrid active filter system intended for harmonic
compensation of high power nonlinear loads up to 50 MW.
Synchronous reference frame (SRF) based controller implementation of the proposed dynamically variable inductance
concept for a parallel hybrid active filter system is validated
by simulation results.
Proliferation of power electronic loads, such as three phase
diode and thyristor bridge rectifiers for dc power supplies,
adjustable speed drives (ASDs), and uninterruptible power
systems (UPSs), which are prerequisites for realizing energy
efficiency and productivity benefits, has brought utilities to
crossroads. Utilities frequently encounter harmonic related
problems, including substantially higher transformer and line
losses, reactive power and resonance problems, required derating of distribution equipment, and severe harmonic interactions
between customers or between the utility and load, reduced
system stability, and safe operating margins. To alleviate harmonic related problems, utilities are beginning to implement
IEEE 519 recommended harmonic standards. It is important
to note that IEEE 519 harmonic standard is a customerutility
point of common coupling (PCC) specification and not an
equipment specification.
Passive filters have traditionally been used to absorb harmonics generated by large industrial loads, because of their
low cost and high efficiency. However, they have several
drawbacks. The supply impedance strongly influences the
compensation characteristics of passive filters, and they are
highly susceptible to undesirable series and parallel resonances
with the supply and load. Passive filters are also sensitive to
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
733
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
734
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
(1)
735
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
736
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
737
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
738
frequency by inductor
, as validated by simulation results
in Section V-B. In this case, the active filter is controlled
to provide harmonic compensation only at seventh harmonic
frequency. This requires a systems based design to optimize
coupling transformer ratio, dc bus capacitance
and voltage
and PWM switching frequency.
Note that the SRF controller is based on local measurements
of load current
and filter currents
and
and does
measurement. This allows only
not require supply current
harmonic compensation of the nonlinear load, as opposed to
harmonic isolation between the supply and load, and results
in lower active filter inverter rating and inverter current
bandwidth requirements. Since the generation of the
value is based on the direct measurement of load current, ,
which forms the reference filter current magnitude
the
value dynamically varies under load dynamics or load
changes and supply voltage variations.
The SRF variable inductance
controlled parallel
hybrid active filter system does not change the quality
factor of the
passive filter. This ensures damping of
any supply current and load terminal voltage oscillations,
due to load changes, supply voltage distortions, and supply
voltage sags or surges. This is an important distinction from
the controller proposed in [24] where the active filter inverter
is controlled to actively drive the load terminal harmonic
voltage
to zero, under all conditions, including supply
voltage distortions. This controller [24] compensates for the
resistive voltage drop across the
passive filter, thereby
actively increasing its quality factor. In this case, the inverter
is controlled to emulate a negative resistance and requires a
dc energy source, such as a battery or auxiliary dc power
supply, due to real power transfer at harmonic frequencies.
This controller also results in large circulating current between
the fifth and seventh passive filters.
The supply current harmonics
and filter current harmonics
for the fifth passive filter and
for the
seventh filter), for the parallel hybrid active filter system
shown in Figs. 5 and 6, are given by steady state phasor
equations (2)(5), in terms of load current harmonics
and supply voltage harmonics
In (2)(9),
, and
represent supply, fifth, and seventh passive filter impedances,
respectively, and
represents combined fifth and seventh
passive filter impedance:
(2)
(3)
(4)
(5)
Fig. 5. Simulation model for Case Afifth, seventh parallel hybrid active
filter system.
where
(6)
at
and
(7)
and
(9)
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
TABLE I
HARMONIC SPECTRUM OF SUPPLY AND LOAD CURRENTS FOR Case A.1, Case A.2,
739
AND
TABLE II
PASSIVE FILTER TUNED AND MIS-TUNED COMPONENT VALUES
Three topologies of parallel hybrid active filter system characterized by their passive filter structures have been simulated.
passive filters which are misCase A: fifth and seventh
10% and
10%,
tuned due to component tolerances of
as shown in Fig. 5 and given in Table II. Passive filters can also
be mistuned due to out of specification inductors or discrete
inductor taps. Mistuning of passive filters significantly reduces
their harmonic compensation capability, especially for stiff
supply systems, as validated by simulation results. Simulation
results in Case A.1 are without supply voltage distortion and
Case A.2 are with supply voltage distortions. The fifth and
seventh passive filters provide 135 kVAR and 65 kVAR,
respectively, for both Case A.1 and Case A.2. In Case B,
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
740
filter currents
and
are actively controlled and limited
to
and
peak values of 191.6 A (135.5 A rms) and
98.5 A (69.7 A rms), respectively, under all supply and load
conditions. The supply
load , and total filter
currents are shown under transient and steady state conditions.
A. Simulation Model A with Fifth and Seventh
Parallel Hybrid Active Filter System
The simulation model A is shown in Fig. 5 with fifth and
seventh passive filters which are mistuned, due to
component tolerances of 10%, as given in Table II. The fifth
and seventh passive filters are tuned at 4.5 and 6.35, respectively, reducing their effectiveness for harmonic compensation,
depending on the supply inductance
value. Note that the
passive filters are tuned below resonance, hence, there is no
The
potential for series resonance with supply inductance
simulation model A with mistuned passive filters, as given in
Table II, has been considered for both Case A.1 and Case A.2.
The active filters are interfaced by coupling transformers in
series with passive filters for both Case A.1 and Case A.2.
1) Case A.1Operation Under Mistuned Passive Filters;
Parallel Hybrid Active Filters Implemented With Square-Wave
Inverter Without Supply Voltage Harmonics: Case A.1 demonstrates the harmonic compensation capability with the active
filters implemented by square-wave inverters for both fifth
and seventh passive filter branches. The fifth active filter
square-wave inverter is operated at 300 Hz (fifth harmonic
frequency). Similarly, the seventh active filter square-wave
inverter is operated at 420 Hz (seventh harmonic frequency).
The coupling transformer ratio is 1:10 and the fifth and seventh
active filter inverter dc bus nominal voltages
and
are 750 V. The dc bus capacitances are
F
and
F The supply voltage has no background
harmonic distortion. The supply system is considered stiff
with supply inductance
of 50 H, which is 3.25% with
a SCR of 30.6. Stiff supply system constitutes the worstcase condition for harmonic compensation, as the passive
filter impedance has to be substantially lower than supply
impedance to sink a significant portion of load harmonic
current. The filter/load terminal voltage
THD without
passive and active filters is 6.2%.
In the absence of supply voltage harmonics, the SRF controlled active filter provides tuning for mistuned passive filters,
by actively inserting required positive or negative
and
inductance values. They effectively improve passive
filter compensation characteristics, provide insensitivity to
supply inductance
and eliminate field retuning and passive
filter redesign costs.
Fig. 8 shows the transient and steady state simulation results
before and after the fifth and seventh active filters are started at
s. Before both active filters are started at
s, mistuned passive filters do not absorb all fifth and seventh
load current harmonics as shown by steady state fifth and
seventh harmonic filter current magnitudes
A
peak (93.6 A rms) and
A peak (34.0 A rms)
and supply current THD is 22.4%. The values
and
indicate that due to mistuning, only 69.0% of fifth harmonic
TABLE III
SQUARE-WAVE INVERTER ACTIVE FILTER RATINGS UNDER
MISTUNED FIFTH AND SEVENTH PASSIVE FILTERS
load current
and only 48.8% of seventh harmonic load
flow into their respective passive filters. The
current
THD before the active filters
filter/load terminal voltage
are started is 3.1%.
s, they provide
After both active filters are started at
tuning of passive filters at the fifth and seventh harmonic
A peak (141.4 A
frequencies as shown by increased
A peak (71.1 A rms). This is achieved
rms) and
H and negative
by generating negative
H inductances, by the fifth and seventh
active filters, respectively. Active filter inverter voltages
and
(lineneutral) in Fig. 8 show square-wave inverter
value is slightly higher than
operation in steady state. The
, as
has not reached
the fifth harmonic load current
its steady state value. This results in 17.0 A of fifth harmonic
supply current, whereas the seventh harmonic supply current
THD is reduced to
is driven to zero. The supply current
4.68% (Table I) and meets the IEEE 519 allowable THD limit
THD after the
of 8.0%. The filter/load terminal voltage
active filters are started is reduced to 1.7%. Note that the
and
values are nonoscillatory in steady state,
as shown in Fig. 8.
Startup of the active filters results in oscillations in
values, due to the interaction of passive filter and supply
inductance
with square-wave inverter based active filters.
oscillations are because the PI gains are
The startup
not tuned for the square-wave inverter case and initial inverter
oscillations do not
dc bus voltage is high. The startup
exist with a PWM inverter implementation, as shown in Case
A.2 and Fig. 9.
Square-wave inverter implementation increases the practical
viability and cost effectiveness of this attractive scheme for
harmonic compensation of large nonlinear loads up to 50
MVA. The active filter inverter ratings are given in Table
III. The 2.2% of fifth and 0.73% of seventh active filter
inverter ratings (as percentages of load kilovoltampere rating)
are cost-effective and imply 1.1 MVA and 365 kVA squarewave inverters, respectively, for harmonic compensation of a
50 MVA load. The active filter kilovoltampere rating is given
by the product of the rms harmonic voltage requirement and
the total rms passive filter current.
2) Case A.2Filter Harmonic Current Rejection Capability
Under Supply Voltage Distortion and Mistuned Passive Filter Components With PWM Inverter Active Filters: Case A.2
demonstrates the current limiting function to prevent passive
filter overloading in presence of 3% each of fifth and seventh
supply voltage distortion. In this case, the fifth and seventh
active filters are implemented by 5 kHz PWM inverters. The
coupling transformer ratio is 1:20 and inverter dc bus nominal
and
are 750 V. The dc bus capacitances
voltages
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
TABLE IV
PASSIVE FILTER HARMONIC CURRENTS DUE TO ONLY 3% EACH OF FIFTH
TABLE V
PWM INVERTER ACTIVE FILTER RATINGS UNDER MISTUNED PASSIVE FILTERS
WITH 3% EACH OF FIFTH AND SEVENTH SUPPLY VOLTAGE HARMONICS
are
F and
F The supply
inductance
is
H which is 6.5% with an SCR of
15.3. The filter/load terminal voltage
THD without passive
and active filters is 15.1%.
In the presence of supply voltage harmonics, the SRF controlled active filter provides insensitivity to supply inductance
, by actively limiting the passive filter currents to their rated
values. This is achieved by actively inserting required positive
inductance values at dominant harmonic frequencies.
Fig. 9 shows the system response for Case A.2 before
and after the fifth and seventh active filters are started at
s. Before both active filters are started
s), the steady state fifth and seventh harmonic filter current
magnitudes are
A peak (148.5 A rms) and
A peak (53.4 A rms). Hence, the fifth harmonic
current in the fifth passive filter
exceeds its rated value
of 191.6 A peak (135.5 A rms), due to fifth harmonic supply
voltage distortion. However, note that the seventh passive filter
is not overloaded. The supply current THD is 11.3%. The
THD before the active filters
filter/load terminal voltage
are started is 16.4%.
Note that before the active filters are started, the mistuned
seventh harmonic passive filter does not sink all the seventh
harmonic load current
This demonstrates the effect of
the phase of supply voltage harmonics which determines the
seventh harmonic current into the mistuned seventh harmonic
passive filter. Note that the fifth harmonic current is negative
sequence, whereas the seventh harmonic current is positive
sequence with respect to fundamental positive sequence supply
voltage. The supply voltage harmonics are synchronized with
the fundamental supply voltage for all simulation results.
Table IV shows harmonic currents in the supply and passive
filters under tuned and mistuned conditions, due to only supply
voltage harmonics for Case A.1, Case A.2, and Case B. Table
IV shows the effect of phase of supply voltage harmonics and
supply inductance
and gives the distribution of fifth and
AND
741
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
742
ratings (as percentages of load kilovoltampere rating) are costeffective and imply 900 kVA and 175 kVA PWM inverters,
respectively, for harmonic compensation of 50 MVA load.
The inverter ratings are slightly lower than Case A.1, due
to higher magnitude of seventh harmonic filter current in the
seventh passive filter before the active filters are started. This
is due to seventh harmonic supply voltage and higher supply
inductance
in Case A.2 compared to Case A.1. Higher value
results in insensitivity to mistuning of passive filters
of
and results in smaller active filter ratings. Case A.2 provides
current limiting and
and
are generated in
such a way so as not to tune the passive filters at the fifth and
and
seventh harmonic frequencies, but to generate
passive filter terminal voltagesaccording to supply voltage
harmonicsto limit fifth and seventh harmonic currents in
the respective passive filters.
TABLE VI
SYSTEM PARAMETERS AND PASSIVE FILTER COMPONENT
VALUES FOR POWER FACTOR CORRECTION CAPACITOR CASE
TABLE VII
PWM INVERTER ACTIVE FILTER RATINGS FOR MULTIPLE TUNING WITH
POWER FACTOR CORRECTION CAPACITOR PASSIVE FILTER CASE
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
743
Fig. 8. Square-wave inverter fifth and seventh active filter operation under mistuned passive filter conditions without supply voltage harmonics. Note
different time scales for m5 ; m7 ; Lcmd ; Lcmd :
passive filter
which is tuned at fifth harmonic frequency. This simulation shows dynamic regulation of
active inductance value and corresponding fifth harmonic
inverter voltage
component to zero.
H the passive
Due to high supply inductance
filter sinks 73.2% of seventh harmonic load current
as
A peak (51.0 A rms) in Fig. 11.
shown by
After the active filter is started, it generates negative active
inductance at seventh harmonic frequency to provide tuning,
H
The supply current
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
744
Fig. 9. PWM inverter fifth and seventh active filter with dc bus controller operation under supply voltage harmonics and mistuned passive filter conditions.
Note different time scales for m5 ; m7 ; Lcmd ; Lcmd :
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
Fig. 10.
PWM inverter active filter operation with power factor correction capacitor passive filter. Note different time scales for
745
m5 ; m7 ; Lcmd ; Lcmd :
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
746
Fig. 11. PWM inverter active filter operation with power factor correction capacitor and
time scales for m5 ; m7 ; Lcmd ; Lcmd :
Lf
Cf
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.
747
REFERENCES
[1] D. M. Divan, Non dissipative switched networks for high power
applications, Electron. Lett., vol. 20, no. 7, pp. 277279, Mar. 1984.
[2] ECE 714 class notes and project reports, University of Wisconsin,
Madison, 1992.
[3] H. Funato and A. Kawamura, Proposal Of variable active-passive
reactance, in Conf. Rec. IEEE IECON, 1992, vol. 1, pp. 381388.
[4] H. Funato and A. Kawamura, Analysis of variable active-passive
reactance, in Conf.. Rec. IEEE PCC, Yokohama, Japan, 1993, pp.
647652.
[5] H. Funato and A. Kawamura, Control of variable active-passive reactance and negative inductance, in Conf. Rec. IEEE PESC, 1994, pp.
189196.
[6] S. Bhattacharya and D. M. Divan, Active filter solutions for utility
interface of industrial loads, in Conf. Rec. IEEE Power Electronics,
Drives and Energy Systems (PEDES) Conf., 1996, pp. 10781084.
[7] H. Sasaki and T. Machida, A new method to eliminate AC harmonic
currents by magnetic flux compensationConsideration on basic design, IEEE Trans. Power App. Syst., vol. PAS-90, pp. 20092019,
Sept./Oct. 1971.
[8] A. Ametani, Harmonic reduction in thyristor converters by harmonic
current injection, IEEE Trans. Power App. Syst., vol. PAS-95, pp.
441449, Mar./Apr. 1976.
[9] L. Gyugyi and E. C. Strycula, Active AC power filter, in Conf. Rec.
IEEE-IAS Annu. Meeting, 1976, pp. 529535.
[10] N. Mohan et al., Active filters for AC harmonic suppression, IEEE
Trans. Power App. Syst., vol. PAS-96, pp. 10681074, July/Aug. 1977.
[11] H. Akagi, A. Nabae, and S. Atoh, Control strategy of active power filters using voltage-source PWM converters, IEEE Trans. Ind. Applicat.,
vol. IA-22, pp. 460465, May/June 1986.
[12] F. Z. Peng, H. Akagi, and A. Nabae, A new approach to harmonic compensation in power systems, in Conf. Rec. IEEE-IAS Annu. Meeting,
1988, pp. 874880.
[13] H. Fujita and H. Akagi, A practical approach to harmonic compensation
in power systemsSeries connection of passive and active filters, in
Conf. Rec. IEEE-IAS Annu. Meeting, 1990, pp. 11071112.
[14] H. Fujita and H. Akagi, Design strategy for the combined system of
shunt passive and series active filters, in Conf. Rec. IEEE IAS Annu.
Meeting, 1991, pp. 898903.
[15] S. Bhattacharya, D.M. Divan, and B. Banerjee, Synchronous frame
harmonic isolator using active series filter, in Conf. Rec. EPE91,
Florence, Italy, 1991, vol. 3, pp. 3035.
[16] S. Bhattacharya and D. M. Divan, Synchronous reference frame based
controller implementation for a hybrid series active filter system, in
Conf. Rec. IEEE-IAS Annu. Meeting, 1995, pp. 25312540.
[17] H. Akagi, New trends in active filters, in Conf. Rec. EPE91, Sevilla,
Spain, 1995, pp. 017026.
[18] D. A. Paice, Power Electronic Converter HarmonicsMultipulse Methods for Clean Power Piscataway, NJ: IEEE Press, 1995.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY DELHI. Downloaded on February 25,2010 at 07:13:36 EST from IEEE Xplore. Restrictions apply.