HOSPITAL GENERAL
GUASMO SUR - ZOFRAGUA
GUAYAQUIL - PROVINCIA DE GUAYAS
MINISTERIO DE SALUD PBLICA
ESPECIFICACIONES TECNICAS
SISTEMA DE AIRE
ACONDICIONADO Y
VENTILACION MECANICA
INTERPLAN
COMPAIA GENERAL DE CONSULTORES Cia. LTDA.
QUITO-ECUADOR
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Contenido
RUBRO: UNIDAD CONDENSADORA DE VOLUMEN VARIABLE ............................. 5
CONTENIDO DEL RUBRO ................................................................................... 5
DETALLE DE ESPECIFICACIONES .................................................................... 9
RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DE TIPO
CASSSETTE .............................................................................................................. 13
CONTENIDO DEL RUBRO ................................................................................. 13
ESPECIFICACIN .............................................................................................. 17
RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DEL TIPO FAN COIL
................................................................................................................................... 20
CONTENIDO DEL RUBRO ................................................................................. 20
ESPECIFICACIN .............................................................................................. 22
RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO RUEDA ENTALPICA
................................................................................................................................... 27
CONTENIDO DEL RUBRO ................................................................................. 27
ESPECIFICACIN .............................................................................................. 28
RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO PLACAS EXTERIOR
................................................................................................................................... 37
CONTENIDO DEL RUBRO ................................................................................. 37
ESPECIFICACIN .............................................................................................. 39
RUBRO: VENTILADOR DE EXTRACCION TIPO HONGO DE ALUMINIO ................ 45
CONTENIDO DEL RUBRO ................................................................................. 45
ESPECIFICACION .............................................................................................. 47
RUBRO: VENTILADOR DE EXTRACCION CUADRADO EN LINEA DE ALETAS
HACIA ATRAS ........................................................................................................... 49
CONTENIDO DEL RUBRO ................................................................................. 49
ESPECIFICACIN .............................................................................................. 51
RUBRO: VENTILADOR DE EXTRACCION TIPO VEKTOR ALTA PLUMA DE
DESCARGA HACIA ARRIBA .................................................................................... 54
CONTENIDO DEL RUBRO ................................................................................. 54
ESPECIFICACIONES.......................................................................................... 56
RUBRO: VENTILADOR DE SUMINISTRO TIPO CENTRIFUGO DOBLE ENTRADA 57
CONTENIDO DEL RUBRO ................................................................................. 57
ESPECIFICACION .............................................................................................. 58
pg. 2
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 4
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-01.01
al 14
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 6
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Estas unidades debern ser controladas por microprocesador y este ser capaz de
permitir: la proteccin de los componentes, capacidad de arranque-parada suave y
controlar la temperatura y presin del refrigerante as como del ambiente controlado
Todas las unidades debern contar con dispositivos de control de flujo del aceite que
ayuden a prevenir la mezcla de aceite y refrigerante en el lado de succin del
compresor.
Debern contar con sistemas de control que monitoreen el nivel de aceite al interior del
compresor y no permitan que el compresor opere a bajos niveles de aceite.
Sistema Elctrico
Todas las unidades debern estar en condiciones de suministro elctrico de 460 V, 60
Hz, 3Ph, igualmente estarn en capacidad de operar con variaciones de voltaje de
10% del voltaje establecido y contarn con un dispositivo de proteccin para
sobrecarga.
Todos los componentes elctricos, electrnicos o mecnicos necesarios y que formen
parte de las unidades externas debern ser montados en fbrica.
El cableado en todas las unidades deber estar acorde a las normas NEC.
Cumplimiento de estndares
Todas las unidades externas debern contar con certificacin de cumplimiento del
ANSI.AHRI.Standard 1230-2010
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garantas
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
pg. 7
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 8
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
DETALLE DE ESPECIFICACIONES
AA-01.01
RUBRO
AA-01.03
AA-01.04
16
UC-72
UC-96
UC-120
UC-144
72,000
96,000
120,000
144,000
scroll inverter
scroll inverter
scroll inverter
scroll inverter
Kw x n
4.96
PVE
6.13
PVE
6.13
PVE
4.96x2
PVE
23-120
23-120
23-120
23-120
Hlice
hlice
hlice
hlice
CANTIDAD
UNIDAD
CAPACIDAD
BTU/hr.
Certificada
AA-01.02
COMPRESOR
tipo
cantidad
potencia
aceite
RANGO DE OPERACIN
Rango de enfriamiento
VENTILADOR
tipo
W
400x1
620x2
620x2
620x2
cfm
7239.00
9132.00
9132.00
9535.00
in H2O
0.31
31.00
31.00
0.31
liquido
plg
3/8
3/8
1/2
1/2
gas
PESO
plg
3/4
7/8
1-1/8
1-1/8
peso neto
kg
190.00
278.00
278.00
293.00
dBA
60/81
61/81
61/81
62/83
potencia x n
caudal
SP
TUBERIAS
R410A
R410A
R410A
R410A
kg
5.50
7.40
7.40
8.70
Volts/ph./ Hz.
460/3/60
460/3/60
460/3/60
460/3/60
tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.
pg. 9
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
AA-01.05
AA-01.06
AA-01.07
AA-01.08
12
22
12
10
UC-168
UC-192
UC-216
UC-240
168,000
192,000
216,000
240,000
scroll inverter
2
4.96+6.13
PVE
scroll inverter
2
4.96+6.13
PVE
scroll inverter
3
14.88
PVE
scroll inverter
2
12.26
PVE
23-120
23-120
23-120
23-120
hlice
400+620x2
16421.00
0.31
hlice
400+620x2
16421.00
0.31
hlice
400+620x2
16774.00
0.31
hlice
2480.00
18364.00
0.31
pulg
5/8
1-1/8
5/8
1-1/8
5/8
1-1/8
5/8
1-1/8
kg
463.00
463.00
483.00
546.00
kg
R410A
12.90
R410A
12.90
R410A
14.20
R410A
14.30
Volts/ph./ Hz.
460/3/60
460/3/60
460/3/60
460/3/60
CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR
BTU/hr.
tipo
cantidad
potencia
aceite
RANGO DE OPERACIN
Kw x n
Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS
W
cfm
in H2O
pulg
liquido
gas
PESO
peso neto
nivel de ruido Pres/Pot.
REFRIGERANTE
dBA
tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.
RESPONSABLE: F.CH.
pg. 10
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
AA-01.09
AA-01.10
AA-01.11
UC-264
UC-288
UC-312
UC-336
264,000
288,000
312,000
336,000
scroll inverter
3
16.05
PVE
scroll inverter
4
19.84
PVE
scroll inverter
4
21.01
PVE
scroll inverter
4
21.01
PVE
23-120
23-120
23-120
23-120
hlice
2480.00
18667.00
0.31
hlice
2480.00
19070.00
0.31
hlice
2900.00
25956.00
0.31
hlice
2880.00
25906.00
0.31
pulg
3/4
1-3/8
3/4
1-3/8
3/4
1-3/8
3/4
1-3/8
kg
566.00
586.00
761.00
761.00
kg
R410A
16.10
R410A
17.40
R410A
21.60
R410A
21.60
Volts/ph./ Hz.
460/3/60
460/3/60
460/3/60
460/3/60
RUBRO
CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR
BTU/hr.
tipo
cantidad
potencia
aceite
RANGO DE OPERACIN
Kw x n
Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS
W
cfm
in H2O
pulg
liquido
gas
PESO
peso neto
Nivel de ruido Pres/Pot.
REFRIGERANTE
AA-01.12
dBA
tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.
RESPONSABLE: F.CH.
pg. 11
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
AA-01.14
UC-96.1
UC-53
96000
53000
scroll inverter
2
4.96*2
Pve
scroll inverter
1
4.12
Poe
23-120
23-120
hlice
620*2
9182
0.31
hlice
125*2
3884
3/8
7/8
3/8
dBA
278
61/81
103
53
kg
R410A
7.4
R410A
3.2
Volts/ph./ Hz.
220/3/60
220/3/60
CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR
BTU/hr.
tipo
cantidad
potencia
aceite
RANGO DE OPERACIN
Kw x n
Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS
W
cfm
in H2O
pulg
liquido
gas
PESO
pulg
kg
peso neto
Nivel de ruido Pres/Pot.
REFRIGERANTE
tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.
RESPONSABLE: F.CH.
pg. 12
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-02.01
al 11
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 14
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 15
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 16
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIN
UNIDADES TIPO CASSETE UNA VIA
RUBRO
CAPACIDAD
UNIDAD
CANTIDAD
BTU/hr.
Energa
Volt/ph/Hz.
Potencia
watt
VENTILADOR
Tipo
Potencia x n
watt
Caudal
cfm
TUBERIAS
Lquido
pulg
Gas
pulg.
drenaje
mm
Nivel de ruido
dBA
REFRIGERANTE
Tipo
mtodo de
control
Peso
kg
DIMENSIONES
ancho/alto/fondo
mm
AA-02.01
7,500
C1-07
58
AA-02.02
9,500
C1-09
24
AA-02.03
12,000
C1-12
33
208/1/60
40
208/1/60
45
208/1/60
50
crossflow
20x1
247/211/176
crossflow
20x1
247/211'176
crossflow
20x1
282/247/211
1/4
1/2
26
27/25/23
1/4
1/2
26
29/27/24
1/4
1/2
26
35/31/27
R410A
R410A
R410A
EEV
EEV
EEV
10.50
10.50
10.50
1164/212/478
1164/212/478
1164/212/478
pg. 17
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO
CAPACIDAD
BTU/hr.
CANTIDAD
UNIDAD
AA-02.07
AA-02.08
AA-02.09
AA-02.10
AA-02.11
18,000
24,000
30,000
36,000
48,000
69
C4-18
C4-24
C4-30
C4-36
C4-48
Energa
Volt/ph/Hz.
208/1/60
208/1/60
208/1/60
208/1/61
208/1/62
Potencia
watt
32
40
65
75
95
turbo fan
turbo fan
turbo fan
turbo fan
turbo fan
65x1
65x1
97x1
97x1
97x1
VENTILADOR
Tipo
Potencia x n
watt
Caudal
cfm
TUBERIAS
Lquido
pulg
1/4
1/4
3/8
3/8
3/8
Gas
pulg.
1/2
1/2
5/8
5/8
5/8
drenaje
mm
32
32
32
32
32
Nivel de ruido
dBA
34/333/31
36/35/34
39/34/30
40/37/33
44/42/39
R410A
R410A
R410A
R410A
R410A
EEV
EEV
EEV
EEV
EEV
15.00
15.00
18.50
18.50
18.50
REFRIGERANTE
Tipo
mtodo de
control
Peso
kg
DIMENSIONES
ancho/alto/fondo
mm
898/357/898
pg. 18
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
BTU/hr.
CANTIDAD
AA-02.04
AA-02.05
AA-02.06
9,500
12,000
18,000
49
43
122
CM-09
CM-12
CM-18
Energa
Volt/ph/Hz.
208/1/60
208/1/60
208/1/60
Potencia
watt
24
28
36
UNIDAD
VENTILADOR
Tipo
Turbo fan
Turbo fan
Turbo fan
Potencia x n
watt
65x1
65x1
65x1
Caudal
cfm
353/300'264
370/335'282
459/388'335
Lquido
pulg
1/4
1/4
1/4
Gas
Pulg.
1/2
1/2
1/2
TUBERIAS
drenaje
mm
25
25
32
Nivel de ruido
dBA
34/30/26
36/34/31
40/37/34
R410A
R410A
R410A
REFRIGERANTE
Tipo
mtodo de control
Peso
EEV
EEV
EEV
kg
12.00
12.00
12.00
mm
575x250x575
575x250x575
575x250x575
DIMENSIONES
ancho/alto/fondo
pg. 19
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-02.12
al 21
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
ESPECIFICACIN
UNIDADES TIPO FANCOIL BAJA PRESION
RUBRO
CAPACIDAD
AA-02.12
BTU/hr.
12,000
CANTIDAD
FL-12
UNIDAD
Energa
Volt/ph/Hz.
208/1/60
Potencia
watt
75
VENTILADOR
Tipo
scirocco
Potencia x n
watt
60x1
Caudal
cfm
353/300/247
Lquido
pulg
1/4
Gas
pulg.
1/2
drenaje
mm
32
Nivel de ruido
dBA
29/28/27
TUBERIAS
REFRIGERANTE
Tipo
mtodo de
control
Peso
R410A
EEV
kg
24.50
mm
900/199/600
DIMENSIONES
ancho/alto/fondo
pg. 22
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
BTU/hr.
CANTIDAD
UNIDAD
AA-02.13
AA-02.14
AA-02.15
18,000
24,000
30,000
24
FM-18
5
FM-24
2
FM-30
Energa
Volt/ph/Hz.
208/1/60
208/1/61
208/1/62
Potencia
watt
165
220
260
scirocco
scirocco
scirocco
VENTILADOR
Tipo
Potencia x n
watt
124x1
124x1
180x1
Caudal
cfm
51/459'406
653/600/547
882/812/700
Lquido
pulg
1/4
3/8
3/8
Gas
pulg.
1/2
5/8
5/8
drenaje
mm
32
32
32
Nivel de ruido
dBA
35/33/31
39/35/31
40/37/34
R410A
R410A
R410A
EEV
EEV
EEV
kg
29
29
37
mm
900/260/480
900/260/480
1150/320/480
TUBERIAS
REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo
pg. 23
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
CAPACIDAD
BTU/hr.
CANTIDAD
UNIDAD
RESPONSABLE: F.CH.
AA-02.16
AA-02.17
36,000
48,000
6
FM-36
10
UI-14
Energa
Volt/ph/Hz.
208/1/63
208/1/64
Potencia
watt
290
430
scirocco
scirocco
VENTILADOR
Tipo
Potencia x n
watt
180x1
218x1
Caudal
cfm
953/882/812
1236/1165/1059
Lquido
pulg
3/8
3/8
Gas
pulg.
5/8
5/8
TUBERIAS
drenaje
mm
32
32
Nivel de ruido
dBA
41/40/38
42/39/36
R410A
R410A
EEV
EEV
kg
37
48
mm
1150/320/480
1200/360/650
REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo
pg. 24
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
BTU/hr.
CANTIDAD
UNIDAD
AA-02.18
AA-02.19
36,000
48,000
6
FA-36
16
FA-48
Energa
Volt/ph/Hz.
208/1/60
208/1/61
Potencia
watt
210
330
VENTILADOR
Tipo
scirocco
scirocco
Potencia x n
watt
183x2
183x2
Caudal
cfm
988/882/776
1377/1183/988
Lquido
pulg
3/8
3/8
Gas
pulg.
5/8
5/8
drenaje
mm
32
32
Nivel de ruido
dBA
40/39/37
44/42/40
R410A
R410A
EEV
EEV
kg
62
62
mm
1200/360/650
1200/360/650
TUBERIAS
REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo
pg. 25
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO
CAPACIDAD
BTU/hr.
CANTIDAD
UNIDAD
AA-02.20
AA-02.21
76,000
96,000
50
FA-76
22
FA-96
Energa
Volt/ph/Hz.
208/1/62
208/1/63
Potencia
watt
530
790
Potencia x n
watt
400x1
400x1
Caudal
cfm
2048/1836/1659
2542/2295/2048
Lquido
pulg
3/8
3/8
Gas
pulg.
3/4
7/8
drenaje
mm
32
32
Nivel de ruido
dBA
4/43/41
48/46/43
R410A
R410A
EEV
EEV
kg
89
89
mm
1240/470/1040
1240/470/1040
VENTILADOR
Tipo
TUBERIAS
REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo
pg. 26
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-05.01
al 31
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
ESPECIFICACIN
pg. 28
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS
RESPONSABLE: F.CH.
AA-05.01
ERV-20-30L
2
1750
1550
AA-05.02
ERV-20-15L
1
1400
1200
AA-05.03
ERV-20-30L
2
2050
1850
AA-05.04
ERV-20-15L
1
1400
1200
end
end
end
end
end
end
end
end
end
end
end
end
end
end
side
end
208/60/3
13.5
208/60/3
8.8
208/60/3
16.6
208/60/3
8.8
1.04
1444
1-1/2
0.854
1366
1
1.229
1634
2
0.654
1281
1
0.698
1232
1
0.613
1146
1/2
0.868
1431
1-1/2
0.613
1146
1/2
11
28.26
11
22.81
11
24.49
11
22.81
332
UL1995
332
UL1995
332
UL1995
332
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-A-01
ERV-C-02
ERV-A-02
ERV-A-03
ERV-C-01
ERV-A-04
pg. 29
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.05
ERV-20-15L
3
1600
1400
AA-05.06
ERV-20-15L
1
1400
1200
AA-05.07
ERV-45-30L
1
3500
3300
AA-05.08
ERV-45-15L
2
2300
2100
end
end
end
end
end
end
side
end
end
end
end
end
end
end
side
end
208/60/3
12.4
208/60/3
8.8
208/60/3
25.1
208/60/3
14.1
0.801
1445
1-1/2
0.754
1324
1
1.161
1259
3
0.913
1089
1-1/2
0.654
1256
3/4
0.613
1146
1/2
0.932
1255
3
0.694
1025
1
11
20.01
11
22.81
11
31.62
11
31.04
332
UL1995
332
UL1995
469
UL1995
518
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
3-16X25
2" MERV 8
3-16X25
2" MERV 8
3-16X25
2" MERV 8
3-16X25
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-A-05
ERV-C-05
ERV-C-06
ERV-A-06
ERV-B-01
ERV-B-02
ERB-C-04
pg. 30
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.09
ERV-20-15L
2
1500
1300
AA-05.10
ERV-20-15L
1
1100
900
AA-05.11
ERV-20-30L
1
1900
1700
AA-05.12
ERV-45-15L
1
2200
2000
end
end
side
end
end
end
side
end
end
end
end
end
end
end
side
end
208/60/3
9.9
208/60/3
5.4
208/60/3
15.5
208/60/3
14.1
0.776
1386
1
0.595
1114
1/2
1.083
1522
1-1/2
0.903
1065
1-1/2
0.632
1201
3/4
0.563
991
1/3
0.826
1351
1-1/2
0.785
1037
1
11
21.31
11
27.54
11
28.26
11
32.18
332
UL1995
302
UL1995
302
UL1995
469
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
3-16X25
2" MERV 8
3-16X25
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-B-03
ERV-C-03
ERV-B-04
ERV-B-05
ERV-B-06
pg. 31
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.13
ERV-20-15L
1
1450
1250
AA-05.14
ERV-20-15L
1
1500
1300
AA-05.15
ERV-20-15L
1
1100
900
AA-05.16
ERV-20-15L
1
1250
1050
end
end
side
end
end
end
end
end
end
end
side
end
end
end
end
end
208/60/3
12.4
208/60/3
9.9
208/60/3
6.8
208/60/3
7.4
0.965
1439
1-1/2
0.876
1426
1
0.895
1259
3/4
0.622
1192
3/4
0.622
1173
3/4
0.632
1201
3/4
0.563
991
1/3
0.586
1070
1/2
11
22.01
11
21.31
11
27.54
11
25.01
332
UL1995
332
UL1995
332
UL1995
332
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-D-01
ERV-D-02
ERV-D-03
ERV-D-04
pg. 32
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.17
Minivent-750
1
600
400
aa-05.18
ERV-20-15L
1
1400
1100
AA-05.19
ERV-10-20H
2
900
700
AA-05.20
ERV-20-15L
2
1600
1400
side/top
side/top
side/bottom
side
end
end
side
end
end
end
side
end
end
end
side
end
220/60/1
9.3
208/60/3
8.8
220/60/1
12.2
208/60/3
12.4
0.6
1243
1/3
1.054
1450
1
0.755
1423
1/2
1.001
1521
1-1/2
0.5
946
1/3
0.795
1195
1/2
0.594
1146
1/2
0.754
1302
3/4
11
27.61
11
22.96
11
22.26
11
20.01
109
UL1995
302
UL1995
132
UL1995
332
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
1-16X25
2" MERV 8
1-16X25
2" MERV 8
2-16X20
2" MERV 8
2-16X20
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-E-01
ERV-E-02
ERV-G-01
ERV-E-03
ERV-E-05
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS
ERV-D-05
pg. 33
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.21
ERV-10-20H
1
1000
800
AA-05.22
ERV-20-30L
1
1800
1600
AA-05.23
ERV-20-30L
1
1750
1550
AA-05.24
ERV-10-20H
1
750
850
end
end
side
end
end
end
side
end
end
end
side
end
end
end
end
end
220/60/1
12.2
208/60/3
13.5
208/60/3
13.5
220/60/1
12.2
0.792
1555
1/2
1.054
1469
1-1/2
1.04
1444
1-1/2
0.708
1237
1/2
0.623
1270
1/2
0.901
1334
1
0.888
1310
1
1.039
1433
1/2
11
20.65
11
27.54
11
28.26
11
23.33
119
UL1995
302
UL1995
302
UL1995
132
UL1995
2" MERV 8
1-16X25
2" MERV 8
1-16X25
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-E-04
ERV-E-06
ERV-E-07
ERV-A-07
1-16*25
2" MERV 8
1-16*25
pg. 34
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
MOD. SUGERIDO
CANTIDAD
RESPONSABLE: F.CH.
AA-05.25
ERVe-55-15H
1
AA-05.26
ERV-10-20L
1
AA-05.27
ERV-10-20H
1
AA-05.28
ERVe-20-30L
1
6000
4200
650
550
1000
1000
2100
1600
end
end
side
end
end
end
end
end
end
end
side
end
end
side
bottom
bottom
208/60/3
29.6
220/60/1
220/60/1
208/60/3
12.2
12.4
0.971
1030
5
0.761
1140
1/3
0.837
1564
1/2
1.015
1540
1-1/2
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
0.816
828
2
0.558
965
1/3
1.145
1626
1/2
0.98
1376
3/4
EER
ER-COP
PESO
11
22.32
11
29.77
11
22.23
11
27
831
UL1995
119
UL1995
135
UL1995
401
UL1995
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
6-16X20
2" MERV 8
1-16X25
2" MERV 8
1-16X25
2" MERV 8
2-20X20
2" MERV 8
6-16X20
1-16X25
1-16X25
2-20X20
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-A-08
ERV-F-01
ERV-F-02
ERV-F-03
Caudal A. externo
Caudal A. extrado
UBICACIN E/S AIRE
cfm
cfm
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS
Kgr.
pg. 35
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS
RESPONSABLE: F.CH.
AA-05.29
ERV-20-15L
1
1650
1450
AA-05.30
ERV-20-15L
1
1100
900
AA-05.31
ERV-20-15L
1
1700
1500
end
end
side
end
end
end
side
end
end
end
side
end
208/60/3
13.5
208/60/3
5.4
208/60/3
13.5
1.013
1549
1-1/2
0.695
1165
1/2
1.026
1581
1-1/2
0.665
1290
1
0.583
991
1/3
0.776
1360
1
11
19.38
11
27.54
11
18.73
332
UL1995
332
UL1995
332
UL1995
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
2" MERV 8
2-16X20
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si
ERV-G-02
ERV-G-03
ERV-G-04
pg. 36
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-05.32
al 48
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Ventiladores
Los ventiladores sern del tipo centrfugo, doble ancho, doble entrada y labes
curvados hacia adelante
Debern contar tambin con aislamiento de neopreno
Centro de control
La unidad tendr todo su circuito de control a 24 VAC y contar con su propio
transformador, switch de desconexin y otros componentes.
El centro de control deber ser instalado y cableado en fbrica y estar ubicado al
interior de la unidad.
ACCESORIOS
Control de velocidad VFD
Permite aumentar o disminuir el flujo del aire controlando la velocidad de los motores a
travs de la variacin de la frecuencia.
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
pg. 38
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIN
RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
AA-05.32
Pve-20-SC
8
1950
1950
AA-05.33
Pve-20-SC
7
1400
1400
AA-05.34
Pve-20-SC
1
1700
1300
AA-05.35
Pve-20-SC
1
1500
1200
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
208/60/3
11.8
208/60/3
4.8
208/60/3
6.2
208/60/3
4.8
0.553
1169
3/4
0.382
903
1/3
0.468
1050
3/4
0.409
952
1/2
1.14
1430
1-1/2
0.924
1202
1/2
0.607
1014
1/3
0.591
980
1/3
11
13.96
11
21.44
11
21.76
11
27.37
Certificacin
FILTROS
aire externo
606
UL-1995
606
UL-1995
606
UL-1995
606
UL-1995
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
aire extraccin
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
BMS interfaz
si
BACNetIP
VFD
BMS interfaz
si
BACNetIP
VFD
BMS interfaz
si
BACNetIP
VFD
BMS interfaz
si
BACNetIP
VFD
PVE-D-03
PVE-D-04
ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS
pg. 39
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
AA-05.33
PVE-A-02
PVE-B-02
PVE-C-02
PVE-D-02
PVE-E-03
PVE-G-03
PVE-G-05
pg. 40
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.36
Pve-20-SC
1
1700
1700
AA-05.37
Pve-35-SC
1
2100
2300
AA-05.38
Pve-45-SC
1
3550
3760
AA-05.39
Pve-35-SC
1
2900
3080
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
208/60/3
7.9
208/60/3
12.9
208/60/3
20.8
208/60/3
16
0.968
1294
3/4
1.088
1185
1
0.759
1002
2
0.759
1227
1-1/2
0.882
1253
3/4
1.089
1220
1-1/2
1.182
1155
3
1.239
1427
2
11
18.68
11
25.69
11
12.55
11
10.57
606
UL-1995
712
UL-1995
859
UL-1995
712
UL-1995
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
BMS interfaz
si
BACNetIP
VFD
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
PVE-D-05
PVE-G-01
PVE-A-03
PVE-A-04
pg. 41
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.40
Pve-35-SC
1
3000
3200
AA-05.41
Pve-35-SC
1
2400
2980
AA-05.42
Pve-35-SC
1
2300
2000
AA-05.43
Pve-45-SC
1
4100
3000
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
208/60/3
20.8
208/60/3
14
208/60/3
10.4
208/60/3
19.9
0.785
1261
2
0.646
1070
1
0.826
1121
1
1.179
1203
3
1.266
1462
3
1.117
1367
2
1.043
1150
1
1.18
1061
1-1/2
11
9.7
11
11.94
11
27.4
11
15.33
712
UL-1995
712
UL-1995
712
UL-1995
859
UL-1995
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
PVE-A-05
PVE-A-06
PVE-F-01
PVE-F-02
pg. 42
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
Kgr.
RESPONSABLE: F.CH.
AA-05.44
Pve-20-SC
1
2100
1710
AA-05.45
Pve-20-SC
1
1200
1450
AA-05.46
Pve-20-SC
2
1950
1950
AA-05.47
Pve-20-SC
1
1400
1400
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
side
end
side
bottom
208/60/3
12.9
208/60/3
6.2
208/60/3
12.9
208/60/3
6.9
1.109
1456
1-1/2
0.634
1004
1/3
0.853
1306
1
0.692
1078
1/2
1.184
1386
1
1.033
1265
3/4
1.34
1509
1-1/2
1.024
1249
3/4
11
13.2
11
29.89
11
13.96
11
28.03
606
UL-1995
606
UL-1995
606
UL-1995
606
UL-1995
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
2" MERV 8
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
BMS interfaz
si
BACNetIP
PVE-F-03
PVE-H-01
PVE-H-02
PVE-H-03
PVE-H-04
pg. 43
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
AA-05.48
Pve-20-SC
2
1200
1200
side
end
side
bottom
208/60/3
4.8
0.534
943
1/3
0.791
1092
1/2
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo
2" MERV 8
aire extraccin
2" MERV 8
ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS
RESPONSABLE: F.CH.
11
39.61
606
UL-1995
BMS interfaz
si
BACNetIP
PVE-H-05
PVE-H-06
pg. 44
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-06.24
al 26
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 46
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACION
CUADRO DE VENTILADORES DE EXTRACCION TIPO HONGO DE TECHO
AA-06.24
300
4
abajo
AA-06.25
900
1
abajo
AA-06.26
7200
4
arriba
Kgr.
26
27
130
Dimensiones (LxL)
mm x mm
368X368
368X368
826X826
SP ext.
SP total
velocidad
potencia
tip speed
voltaje/frec/fase
potencia motor
FLA
sonido
CODIGO DE UNIDADES
pulg H2O
pulg H2O
rpm
hp
m/seg.
V/Hz./ph.
hp
amps
dBA
0.8
0.8
1404
0.11
20.88
115/60/1
1/4
5.8
55
0.7
0.7
1215
0.2
21.11
115/60/1
1/3
7.2
58
2.5
2.5
1039
5.25
42.14
230/60/3
7-1/2
22
78
VE-A-06
VE-B-07
VE-C-06
VE-D-06
VE-B-08
VE-E-01
VE-E-02
VE-E-03
VE-E-04
RUBRO
caudal
CANTIDAD
DESCARGA
s/accesorios
cfm
pg. 47
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
AA-06.31
650
1
Arriba
Kgr.
47
30
Dimensiones (LxL)
mm x mm
521x521
470X470
SP ext.
SP total
velocidad
potencia
tip speed
voltaje/frec/fase
potencia motor
FLA
sonido
CODIGO DE UNIDADES
pulg H2O
pulg H2O
rpm
hp
m/seg.
V/Hz./ph.
hp
amps
dBA
1.2
1.2
1118
0.95
27.49
460/60/3
1
2.1
1.1
1.1
1464
0.27
28.47
115/60/1
1/3
7.2
VE-F-07
VE-F-08
RUBRO
caudal
cfm
CANTIDAD
DESCARGA
s/accesorios
pg. 48
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ATRAS
UNIDAD DE MEDIDA Y PAGO: u
CODIGO: N2.AA-06.05
al 21
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 50
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIN
RUBRO
CANTIDAD
AA-06.05
AA-06.06
AA-06.07
AA-06.08
kg-
44
145
41
145
47
145
40
145
cfm
pulg
H2O
pulg
H2O
rpm
m/seg.
HP
%
1040
880
1700
900
0.8
0.7
0.5
1.1
1529
26.68
0.42
47
0.8
0.7
0.5
1334
23.282
0.27
47
1234
24.003
0.43
48
1153
20.12
0.18
45
HP
rpm
amps
V/Hz/ph
1/2
1725
9.8
115/60/1
1/3
1725
7.2
115/60/1
1/2
1725
9.8
115/60/1
1/4
1725
5.8
115/60/1
VE-A-04
VE-A-05
VE-B-01
VE-B-02
CARACTERISTICAS
peso
motor frame
CARACTERISTICAS
OPERATIVAS
caudal
presin externa SP
presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES
1.1
pg. 51
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
CANTIDAD
CARACTERISTICAS
peso
motor frame
CARACTERISTICAS OPERATIVAS
caudal
RESPONSABLE: F.CH.
AA-06.09
AA-06-10
AA-06.11
AA-06.12
kg-
43
145
43
145
45
145
43
145
cfm
presin externa SP
pulg H2O
940
0.9
980
0.9
1200
0.75
1020
0.9
presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES
pulg H2O
rpm
m/seg.
HP
%
0.9
1383
24.14
0.32
47
0.9
1393
24.32
0.33
47
0.75
1129
21.95
0.32
50
0.9
1407
24.56
0.34
47
HP
rpm
amps
V/Hz/ph
1/2
1725
9.8
115/60/1
1/2
1725
9.8
115/60/1
1/3
1725
7.2
115/60/1
1/2
1725
9.8
115/60/1
VE-B-05
VE-G-05
VE-G-07
VE-B-06
VE-C-01
VE-D-04
VE-E-07
AA-06.13
1
AA-06.14
1
AA-06.15
1
AA-06.16
1
kg-
43
145
44
145
43
145
44
145
cfm
RUBRO
CANTIDAD
CARACTERISTICAS
peso
motor frame
CARACTERISTICAS OPERATIVAS
caudal
presin externa SP
pulg H2O
900
0.9
1220
0.9
1000
0.9
1200
0.9
presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES
pulg H2O
rpm
m/seg.
HP
%
0.9
1403
24.48
0.3
47
0.9
1477
25.77
0.41
47
0.9
1400
24.44
0.34
47
0.9
1470
25.65
0.4
47
HP
rpm
amps
V/Hz/ph
1/2
1725
9.8
115/60/1
1/2
1725
9.8
115/60/1
1/2
1725
9.8
115/60/1
'1/2
1725
9.8
'115/60/1
VE-D-05
VE-E-06
VE-E-08
VE-E-09
pg. 52
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
CANTIDAD
CARACTERISTICAS
DIMENSIONALES
peso
motor frame
CARACTERISTICAS
OPERATIVAS
caudal
RESPONSABLE: F.CH.
AA-06.17
1
AA-06.18
1
AA-06.19
1
AA-06.20
1
AA-06.21
2
kg-
41
145
48
145
47
145
109
184
43
145
cfm
800
1800
1500
3200
1040
presin externa SP
pulg H2O
0.7
0.8
0.7
1.5
0.9
presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES
pulg H2O
rpm
m/seg.
HP
%
0.7
0.8
0.7
1.5
0.9
1239
21.63
0.22
47
1314
25.55
0.52
48
1172
22.78
0.37
50
1293
31.8
1.52
52
1414
24.6
0.35
47
HP
rpm
amps
V/Hz/ph
1/3
1725
7.2
115/60/1
3/4
1725
3.5
115/60/1
1/2
1725
9.8
115/60/1
2
1725
7.5
208/60/3
1/2
1725
9.8
115/60/1
VE-A-07
VE-A-10
VE-A-11
VE-G-02
VE-G-04
VE-G-06
pg. 53
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
HACIA ARRIBA
UNIDAD DE MEDIDA Y PAGO: u
CODIGO: N2.AA-06.22-23
pg. 54
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
El damper de aislamiento ser del tipo actuado por gravedad y ser construido en
lmina de aluminio y tendr el mismo recubrimiento de proteccin de toda la unidad.
Ambos dampers sern de fcil acceso desde el exterior de la unidad.
El damper de bypass ser del tipo aletas opuestas.
Certificaciones
Esta unidad deber estar certificada bajo las normas AMCA
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
pg. 55
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIONES
RUBRO
MOD. SUGERIDO
CANTIDAD
AA-06.23
VEKTOR-H-16-13
1
VEKTOR-H-12-10
1
VE-A-09
VE-A-12
cfm
3600
2100
220/3/60
UNIDAD
CAUDAL
AA-06.22
V/PH/HZ
220/3/60
SP. Ext
in H20
0.116
1.1
SP total
VENTILADOR
in H20
1.316
1.25
rpm
2183
2986
hp
3.76
2.45
E.ELECTRICA
revoluciones
potencia
alt efectiva descarga
velocidad de salida
MOTOR
potencia
velocidad de rotacin
mts
8.35
7.09
mts/seg
19.87
19.39
hp
rpm
1725
3600
TEFC
TEFC
320
243
tipo
PESO
kg
pg. 56
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA.-06.02
al 04
pg. 57
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante
ESPECIFICACION
RUBRO
CANTIDAD
UNIDAD
AA-06.02
AA-06.03
AA-06.04
VS-E-01
VS-G-01
VS-F-01
VENTILADOR
CAUDAL
cfm
23.040
5.300
4.000
SP total
in.H2O
1.5
1.5
1.2
Tip speed
m/s
44,16
32.18
27.15
Velocidad giro
rpm
1.230
1.352
1.119
nivel de ruido
dBA
85/85
73/69
69/64
V/F/PH
208/60/3
208/60/3
460/60/3
RPM motor
rpm
1.725
1725
1.725
POTENCIA
hp
15
1-1/2
TH
TH
TH
kg
287
131
131
MOTOR
E.ELECTRICA
DESCARGA
POSICION
PESO
pg. 58
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 59
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ATRAS
UNIDAD DE MEDIDA Y PAGO: u
CODIGO: N2.AA-06.27
al 29,32,33
pg. 60
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Certificaciones
Esta unidad deber estar certificada bajo las normas AMCA
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.
pg. 61
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACION
RUBRO
AA-06.27
AA-06.28
AA-06.29
CANTIDAD
UNIDAD
1
VE-F-01
2
VE-F-02
1
VE-F-06
VE-M-03
CAUDAL
cfm
1350
1000
5000
in.H2O
0.9
VELOCIDAD
POTENCIA
rpm
HP
1244
0.42
1340
0.30
1297
2.76
TIP SPEED
NIVEL DE RUIDO
MOTOR
m/s
dBA
24.19
62/58
23.39
60/56
36.86
73/68
POTENCIA
HP
1/2
1/3
V/HZ/PH
RPM
115/60/1
1725
115/60/1
1725
460/60/3
1725
amps
kg
9.8
47
7.20
152
5
152
AA-06.32
AA-06.33
SP TOTAL
VENTILADOR
VOLT/FREC/FASE
VELOCIDAD
FLA amps
PESO
RUBRO
CANTIDAD
VE-H-03
VE-M-04
cfm
1050
850
in.H2O
0.8
0.5
rpm
1357
1126
UNIDAD
CAUDAL
SP TOTAL
VENTILADOR
VELOCIDAD
POTENCIA
HP
0.31
0.17
TIP SPEED
m/s
23.68
19.64
NIVEL DE RUIDO
MOTOR
dBA
61/57
54/52
POTENCIA
HP
1/3
1/4
VOLT/FREC/FASE
V/HZ/PH
115/60/1
115/60/1
VELOCIDAD
RPM
1725
1725
FLA amps
amps
7.2
5.8
kg
41
40
PESO
pg. 62
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-06.34
pg. 63
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.
ESPECIFICACIN
RUBRO
UNIDAD
Area Utilizacin
Caudal (cfm)
Presin (c.a.)
Potencia
Giro (rpm)
Volt/Fase/Frecuencia
Tipo
Cantidad
Accesorios
SIMILAR A :
AA-06.34
EB-02
Baos
100
0.24
100 W
950
115/1/60
Bao
186
Sensor de Movimiento
SP-B110
pg. 64
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-004.01
al 37
pg. 65
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
MATERIALES EXTRAS
El fabricante proveer de filtros adicionales para la etapa de pruebas y un juego
para la etapa de arranque final
El fabricante de la unidad proveer de un juego extra de bandas en adicin a
aquellas que vinieran instaladas desde la fbrica.
MONTAJE
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
EXPERIENCIA DEL PROVEEDOR
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
GARANTA
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
INVENTARIO DE PIEZAS Y PARTES ORIGINALES
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.
DESCRIPCION GENERAL
Cada unidad estar conformada por las siguientes partes:
Base estructural
Gabinete con aislamiento acstico y trmico
pg. 66
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Puertas de acceso
Ventiladores
Motores
Controles de motores elctricos
Serpentines
Filtros
Dampers
Controles
Componentes y partes que consten en los planos de referencia
Cada unidad deber cumplir los niveles de rendimientos para los siguientes
parmetros:
Flujo de aire
Presin esttica
Capacidad de enfriamiento
Capacidad de calentamiento
Servicio elctrico
Niveles de sonido
Niveles de filtracin
Seguridad estructural del gabinete.
Cada unidad deber mantener sin ninguna alteracin su integridad estructural aun as
fueran removidos todos sus paneles.
De preferencia toda unidad deber ser entregada en una sola pieza salvo que se
considere necesario separarla para su transportacin o instalacin.
El fabricante deber proveer instrucciones detalladas paso a paso para instalacin y
desmontaje de la unidad.
En el caso de que fuera necesario segmentar la unidad, los trabajos de montaje
debern ser realizados por personal debidamente entrenado y calificado por el
fabricante.
1. CUMPLIMIENTO DE NORMAS
La unidad deber cumplir con todos los estndares y normas referidos en esta
especificacin.
Los fabricantes que no pudieren cumplir con el estndar ARI-430 debern evidenciar
el haber realizado pruebas en cada unidad sobre:
Verificacin de potencia al freno de los motores
Cumplimiento de parmetros de flujo de aire.
Cumplimiento de parmetros de presin esttica
2. BASE SOPORTANTE
La unidad estar provista de una base estructural de acero galvanizado
ubicada bajo todo el permetro estructural.
Deber tener el espacio adecuado y suficiente para la disposicin de
condensados y similares
Deber contar con los dispositivos necesarios para la manipulacin e izaje
integro de la misma.
pg. 67
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
3. CUBIERTA EXTERIOR
Todo el conjunto de la unidad es del tipo doble-pared, material de aislamiento
expuesto no podr ser aceptado.
La instalacin de los paneles deber cumplir con los estndares UL-1995 para
seguridad contra incendios y tambin los requerimientos de NFPA 90
El material que compone el aislamiento ser tal que evite el crecimiento de
mohos y hongos en concordancia con el mtodo de ensayos UL-181
El aislamiento de los paneles deber estar completamente encapsulado por las
placas metlicas de tal manera que el aire no est en contacto con el material,
aquellos paneles que contengan como aislamiento lana de vidrio (fiberglass)
debern estar sellados en cada esquina y en todo el permetro para eliminar la
posibilidad de flujo de aire a travs del panel y el crecimiento de hongos o
moho dentro del mismo.
La resistencia trmica de la cubierta ser mnimo de R12 es decir 12 hr-ft2F/BTU
Las lminas de acero empleadas en la cubierta sern de acero galvanizado o
inoxidable.
La unidad deber tener una estructura en acero galvanizado que provea la
resistencia necesaria para la operacin de la unidad y no dependa del montaje
de los paneles para el desempeo de su integridad.
La estructura de la cubierta deber contar con el mismo aislamiento con que se
instalen los paneles.
El nivel de fugas de aire de la unidad deber ser menos a 1% del caudal de
diseo y con una presin esttica de +/- 8 plg de H2O
Los paneles y puertas de acceso de la unidad no podrn tener deflexiones
mayores a L/240 cuando estn sometidas a una presin de +/- 8 plg. H2O en
este caso L es el largo del panel y L/240 la deflexin en la mitad.
La unidad estar provista de un panel de cubierta con un mnimo de por
cada pie, esta cubierta deber sobresalir por lo menos 2 a cada lado de la
unidad.
La unidad deber tener un recubrimiento superficial que permita soportar las
caractersticas del ambiente predominante en la zona tales como salinidad, alta
humedad y temperatura.
4. BANDEJAS DE DRENAJE
La unidad estar provista de una bandeja bajo cada serpentn de enfriamiento
o humidificador y deber cumplir con ASHRAE STANDARD 62
Las tuberas de conexin a estas bandejas sern del mismo material y sus
acoples sern soldados.
Las bandejas de drenaje debern tener las mismas caractersticas de
aislamiento que los paneles
Todas las caeras que conecten a estas bandejas igualmente debern estar
aisladas.
Debern estar montadas de tal manera que permitan inspeccin visual y
limpieza fsica en el 100% de la misma sin necesidad de retirarla
pg. 68
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 71
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 72
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
TERMINOLOGIA DE SEGMENTOS:
IP
FF
CC
FS
DI
XA
RF
DP
pg. 73
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.01
UNIDAD:
ver listado
CAUDAL (cfm)
1950
SECCION (plg x plg):36X33
CANTIDAD:
7
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.33
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2
Filter Media Type: Pleated 30% (MERV 8)
Filter Area (ft): 4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8)
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 74
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.71/ 1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2067
BHP: 2.34
Fan BHP w/ Belt Loss: 2.51
Outlet Velocity (ft/min): 2125
pg. 75
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158
input
3 Phase 208-240 VAC +/-10% 48/63Hz +/Rated Input Voltage:
5%
Rated Input Current Amps:
11.8
Heat Loss in Watts 100% Load:
116
Efficiency (%):
98
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18
pg. 76
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 27 "
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
Prefilter Air Pressure Drop (in. w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop (in.
w.g.):
High Eff. Filter Dirty Allowance (in. w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):
(1)24x24
4
Side
2"
Pleated 30%
(MERV 8)
0.26
0.1
12" Rigid
90-95% Eff,
(MERV 14)
0.56
0.2
Pleated 30% (MERV 8)
1
90-95% Eff, (MERV 14)
1
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: Bottom
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
11
6
27.5
21
4
left
1-5/8
7/8
1
none
1950
30
pg. 78
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
80
77
55.8
55.6
488
SEGMENT
IP Inlet Plenum
FF Flat Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.33
0.26
0.1
0.79
1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.71
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
20
10
19
40
10
27
21
17
164
width
(in)
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
171
83
490
529
74
164
164
153
1828
pg. 79
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.02
UNIDAD:
ver listado
CAUDAL (cfm)
1400
SECCION (plg x plg):30x39
CANTIDAD:
6
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
3.3"
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8)
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 80
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.71/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2026
BHP: 1.43
Fan BHP w/ Belt Loss: 1.56
Outlet Velocity (ft/min): 1925
Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158
pg. 81
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):
Output
Output Current Amps: 7.5
Overload Current Rating: 110% for 1
minute every 10 minutes
Drives are rated for use below 3,300 ft and
104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use
above these limits.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14
SEGMENTO XA
Access Segment Details
Segment Length: 27 "
pg. 82
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
(1)24x20
3.3
Filter Loading:
Side
Prefilter Depth:
2"
Prefilter Media:
Pleated 30%
(MERV 8)
90-95% Eff,
90-95% Eff,
(MERV 14)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: Bottom
pg. 83
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
20
27
3.8
left
1-5/8
7/8
1
none
1400
30
80
77
56.3
56.1
368
pg. 84
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.16
0.21
0.1
0.38
1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.71
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
18
10
19
40
10
27
21
15
width
(in)
39
39
39
39
39
39
39
39
height
(in)
30
30
30
30
30
30
30
30
weight
(lbs.)
160
85
471
511
72
167
167
141
pg. 85
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.03
UNIDAD:
UMA-C-01
CAUDAL (cfm)
2.000
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in.
w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
0.37
Outside Air (OA)
2000
15.25Hx19.00W
2.01
Front-Low(Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked
Return/Mixed Air
15.25Hx19.00W
2.01
Top
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked
8
(4)24x12
side
0.1
0.05
2"Pleated 30% (MERV
8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 9
TSP/ESP (in. w.g.): 3.75/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2117
BHP: 2.08
Fan BHP w/ Belt Loss: 1.562.23
Outlet Velocity (ft/min): 2002
pg. 87
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.16
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
(1)24x24
4
Filter Loading:
Side
Prefilter Depth:
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.27
0.1
12" Rigid
80-85% MERV 13
0.53
0.2
Pleated 30%
(MERV 8)
1
80-85% Eff,
(MERV 13)
1
pg. 88
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: Bottom
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
3.8
left
1-5/8
5/8
1
none
2000
9
76
66
55
53.9
500
pg. 89
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.17
0.05
0.1
0.05
0.57
1.2
0.16
0.27
0.1
0.53
0.2
0.35
3.75
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
31
19
39
10
12
21
17
149
width
(in)
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
weight
(lbs.)
217
461
382
68
64
149
143
1484
pg. 90
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.04
UNIDAD:
UMA-C-02
CAUDAL (cfm)
2.150
SECCION (plg x plg):39X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.41
Outside Air (OA)
2150
15.25Hx19.00W
2.01
Front-High(Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked
Return/Mixed Air
15.25Hx19.00W
2.01
Top
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked
8
(4)24x12
side
0.1
0.05
2"Pleated 30% (MERV 8)
pg. 91
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2150
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.75/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1878
BHP: 2.37
Fan BHP w/ Belt Loss: 2.54
Outlet Velocity (ft/min): 1785
pg. 92
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.12
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.3
0.1
12" Rigid
80-85% MERV
13
0.6
0.2
Pleated 30%
(MERV 8)
1
80-85% Eff,
(MERV 13)
1
pg. 93
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: TOP
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
6
30
21
4.4
left
1-5/8
7/8
1
none
pg. 94
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
2150
30
76
66
55
53.9
489
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.19
0.06
0.11
0.05
0.55
1.1
0.12
0.3
0.1
0.6
0.2
0.33
3.71
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
30
19
41
10
12
18
18
148
width
(in)
33
33
33
33
33
33
33
33
height
(in)
39
39
39
39
39
39
39
39
weight
(lbs.)
223
473
412
70
67
138
156
1539
pg. 95
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.05
UNIDAD:
UMA-C-03
CAUDAL (cfm)
1.950
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.33
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 96
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.81/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2091
BHP: 2.4
Fan BHP w/ Belt Loss: 2.57
Outlet Velocity (ft/min): 2125
pg. 97
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
12
6
27.5
21
4
left
1-5/8
7/8
1
none
pg. 99
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1950
30
76
66
55
53.9
488
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.33
0.26
0.1
0.89
1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.81
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
20
10
19
40
10
27
21
17
164
width
(in)
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
171
83
492
529
74
164
164
153
1830
pg. 100
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.06
UNIDAD:
UMA-C-04
CAUDAL (cfm)
1.400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 101
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.83/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2058
BHP: 1.47
Fan BHP w/ Belt Loss: 1.6
Outlet Velocity (ft/min): 1925
pg. 102
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 103
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
12
5
20
27
3.8
left
1-5/8
7/8
1
none
pg. 104
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1400
30
80
77
54.8
54.7
368
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.16
0.21
0.1
0.5
1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.83
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
18
10
19
40
10
27
21
15
160
width
(in)
39
39
39
39
39
39
39
39
39
height
(in)
30
30
30
30
30
30
30
30
30
weight
(lbs.)
160
85
476
511
72
167
167
141
1779
pg. 105
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.07
UNIDAD:
UMA-D-03
CAUDAL (cfm)
5300
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.64
Outside Air (OA)
5300
15.25Hx43.00W
4.55
Front-High(Front)
(1)15.25x43
control
25% MIN/MAX
cd60
galvanized
parallel
n/a
UNlinked
Return/Mixed Air
5300
15.25Hx43.00W
4.55
BOTTOM
(1)15.25x43
control
100%
cd60
galvanized
parallel
n/a
UNlinked
16
(8)24x12
side
0.15
0.05
2"Pleated 30% (MERV 8)
pg. 106
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 5300
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.0/1.1
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 15-15
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1387
BHP: 5.92
Fan BHP w/ Belt Loss: 6.25
Outlet Velocity (ft/min): 2315
pg. 107
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.21
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
8
13
35.2
45
10.2
left
2-1/8
1-3/8
1
none
pg. 109
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
5300
30
77
67
55
54
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
0.06
0.1
0.23
0.05
0.15
0.05
0.55
1.1
0.21
0.27
0.1
0.58
0.2
0.35
4
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
29
19
50
11
27
18
19
173
width
(in)
57
57
57
57
57
57
57
57
height
(in)
42
42
42
42
42
42
42
42
weight
(lbs.)
409
632
824
115
231
213
262
2686
pg. 110
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.08
UNIDAD:
UMA-D-04
CAUDAL (cfm)
4900
SECCION (plg x plg):42X57
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.57
Outside Air (OA)
4900
15.25Hx43.00W
4.55
Front-High(Front)
(1)15.25x43
control
25% MIN/MAX
cd60
galvanized
parallel
n/a
UNlinked
Return/Mixed Air
4900
15.25Hx43.00W
4.55
BOTTOM
(1)15.25x43
control
100%
cd60
galvanized
parallel
n/a
UNlinked
16
(8)24x12
side
0.13
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 4900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.62/0.90
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 15-11
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1263
BHP: 4.64
Fan BHP w/ Belt Loss: 4.96
Outlet Velocity (ft/min): 2666
pg. 112
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.27
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
(2)24x20;(2)24X12
10.7
Filter Loading:
Side
Prefilter Depth:
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95% MERV14
0.51
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV14
1
pg. 113
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
13
32.5
45
10.2
left
2-1/8
1-1/8
1
none
pg. 114
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
4900
30
77
67
55
54
480
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
0.06
0.1
0.19
0.04
0.13
0.05
0.53
0.9
0.27
0.24
0.1
0.51
0.2
0.3
3.62
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
29
19
37
11
27
18
19
160
width
(in)
57
57
57
57
57
57
57
57
height
(in)
42
42
42
42
42
42
42
42
weight
(lbs.)
409
621
724
111
231
213
262
2571
pg. 115
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.09
UNIDAD:
UMA-D-05
CAUDAL (cfm)
1700
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.25
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 4.0
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 116
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.47/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1770
BHP: 1.5
Fan BHP w/ Belt Loss: 1.62
Outlet Velocity (ft/min): 1853
pg. 117
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.13
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24X24
4
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 118
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.25
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
7/8
1
none
pg. 119
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1700
30
80
77
57.6
57.4
425
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.25
0.21
0.1
0.47
1.1
0.13
0.21
0.1
0.45
0.2
0.25
3.47
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
20
10
19
40
10
27
21
17
164
width
(in)
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
171
83
475
511
74
164
164
153
1795
pg. 120
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.10
UNIDAD:
UMA-G-04
CAUDAL (cfm)
1400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 121
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.84/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2060
BHP: 1.47
Fan BHP w/ Belt Loss: 1.61
Outlet Velocity (ft/min): 1925
pg. 122
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14
SEGMENTO XA
Access Segment Details
Segment Length: 27"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24X20
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 123
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
8
20
24
3.8
left
1-5/8
7/8
1
none
pg. 124
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1500
30
80
77
57.6
57.4
395
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
SUPPLY(in.wg)
0.16
0.21
0.1
0.51
DP Discharge Plenum
1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.84
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
18
10
19
40
10
27
21
15
160
width
(in)
39
39
39
39
39
39
39
39
39
height
(in)
30
30
30
30
30
30
30
3
39
weight
(lbs.)
160
85
482
511
72
167
167
141
1785
pg. 125
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.11
UNIDAD:
UMA-A-03
CAUDAL (cfm)
3550
SECCION (plg x plg):42X51
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.21
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (4) 20X16
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 8.9
Filter Air Pressure Drop (in. w.g.): 0.19
Dirty Filter Allowance (in. w.g.): 0.05
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 126
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3550
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.04/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-12
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1484
BHP: 3.0
Fan BHP w/ Belt Loss: 3.2
Outlet Velocity (ft/min): 2138
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18
SEGMENTO XA
Access Segment Details
Segment Length: 12"
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(4)20X16
8.9
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
0.41
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.21
Opening: BOTTOM
pg. 128
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
13
32.5
39
8.8
left
2-1/8
1-3/8
1
none
3550
30
80
77
57.6
57.4
403
pg. 129
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.21
0.19
0.05
0.5
0.8
0.18
0.19
0.1
0.41
0.2
0.21
3.04
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
19
10
19
47
10
12
18
19
154
width
(in)
51
51
51
51
51
51
51
51
51
height
(in)
42
42
42
42
42
42
42
42
42
weight
(lbs.)
243
119
595
632
99
97
201
243
2229
pg. 130
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.12
UNIDAD:
UMA-A-04
CAUDAL (cfm)
2900
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.24
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 6.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 131
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.43/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1507
BHP: 2.55
Fan BHP w/ Belt Loss: 2.73
Outlet Velocity (ft/min): 2194
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19
SEGMENTO XA
Access Segment Details
Segment Length: 12"
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: BOTTOM
pg. 133
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
6
11
27.5
36
6.9
left
2-1/8
1-3/8
1
none
2900
30
80
77
57.6
57.4
420
pg. 134
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.24
0.26
0.1
0.49
0.8
0.19
0.26
0.1
0.55
0.2
0.24
3.43
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
17
10
19
34
10
12
21
17
140
width
(in)
48
48
48
48
48
48
48
48
48
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
199
104
561
471
89
90
206
199
1919
pg. 135
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.13
UNIDAD:
UMA-A-05
CAUDAL (cfm)
3000
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.26
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 6.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 136
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.55/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1533
BHP: 2.74
Fan BHP w/ Belt Loss: 2.93
Outlet Velocity (ft/min): 2270
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.20
SEGMENTO XA
Access Segment Details
Segment Length: 12"
pg. 137
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.26
Opening: BOTTOM
pg. 138
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
11
27.5
36
6.9
left
2-1/8
1-3/8
1
none
3000
30
80
77
57.6
57.4
435
pg. 139
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
OVERALL
SUPPLY(in.wg)
0.26
0.27
0.1
0.51
Section
RESPONSABLE: F.CH.
Length
(in)
17
10
19
34
10
12
21
17
140
width
(in)
48
48
48
48
48
48
48
48
48
0.8
0.2
0.27
0.1
0.58
0.2
0.26
3.55
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
199
104
561
471
89
90
206
199
1919
pg. 140
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.14
UNIDAD:
UMA-A-06
CAUDAL (cfm)
3000
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.24
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)20X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
5.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 141
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.24/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1464
BHP: 1.95
Fan BHP w/ Belt Loss: 2.1
Outlet Velocity (ft/min): 1816
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.13
SEGMENTO XA
Access Segment Details
Segment Length: 12"
pg. 142
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(1)20X24;
(1)12X24
5.3
Side
2"
Prefilter Media:
Pleated 30%
(Quantity)Filter Sizes:
(MERV 8)
Prefilter Air Pressure Drop (in. w.g.): 0.23
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):
0.1
12" Rigid
90-95%
MERV14
0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENT DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: BOTTOM
pg. 143
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
11
27.5
30
5.7
left
2-1/8
1-3/8
1
none
2400
30
80
77
57.6
57.4
421
pg. 144
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.24
0.23
0.1
0.48
0.8
0.13
0.23
0.1
0.49
0.2
0.24
3.24
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
17
10
19
44
10
12
21
17
150
width
(in)
42
42
42
42
42
42
42
42
42
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
181
95
531
513
84
83
190
181
1858
pg. 145
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.15
UNIDAD:
UMA-A-07
CAUDAL (cfm)
1400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 146
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.97/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2095
BHP: 1.52
Fan BHP w/ Belt Loss: 1.64
Outlet Velocity (ft/min): 1925
pg. 147
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24X20
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
12" Rigid
90-95%
MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 148
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
8
20
27
3.8
left
1-5/8
1-1/8
1
none
pg. 149
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1400
30
80
77
57.6
57.4
368
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.16
0.21
0.1
0.44
1.8
0.14
0.21
0.1
0.45
0.2
0.16
3.97
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
18
10
19
37
10
12
21
15
142
width
(in)
39
39
39
39
39
39
39
39
39
height
(in)
30
30
30
30
30
30
30
30
30
weight
(lbs.)
160
85
482
472
72
75
167
141
1654
pg. 150
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.16
UNIDAD:
UMA-A-08
CAUDAL (cfm)
1500
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.18
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 151
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1500
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.25/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: II
Bearing Options: EXTENDED LUBE
Fan RPM: 2168
BHP: 1.75
Fan BHP w/ Belt Loss: 1.89
Outlet Velocity (ft/min): 2062
pg. 152
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.17
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24X20
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.23
0.1
12" Rigid
90-95%
MERV14
0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 153
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.18
Opening: BOTTOM
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
11
8
20
27
3.8
left
1-5/8
1-1/8
1
none
pg. 154
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1500
30
80
77
57.6
57.4
395
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.18
0.23
0.1
0.57
1.8
0.17
0.23
0.1
0.49
0.2
0.18
4.25
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
18
10
19
37
10
12
21
15
142
width
(in)
39
39
39
39
39
39
39
39
39
height
(in)
30
30
30
30
30
30
30
30
30
weight
(lbs.)
160
85
484
485
72
75
167
141
1669
pg. 155
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.17
UNIDAD:
UMA-A-09
CAUDAL (cfm)
6000
SECCION (plg x plg):48X60
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.30
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (2)24x24; (2)24x12
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
12.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 156
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 6000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.53/1.4
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 15-15
Construction: II
Bearing Options: EXTENDED LUBE
Fan RPM: 1477
BHP: 7.55
Fan BHP w/ Belt Loss: 7.96
Outlet Velocity (ft/min): 2621
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.26
SEGMENTO XA
Access Segment Details
Segment Length: 12"
pg. 157
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.40
Opening: BOTTOM
pg. 158
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
15
37.5
48
12.5
left
2-1/8
1-3/8
1
none
6000
30
80
77
57.6
57.4
480
pg. 159
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY(in.wg)
0.3
0.27
0.1
0.65
1.4
0.26
0.27
0.1
0.58
0.2
0.4
4.53
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
pg. 160
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.18
UNIDAD:
UMA-F-01
CAUDAL (cfm)
2700
SECCION (plg x plg):33X45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.6
Outside Air (OA)
2700
9.50HX31.0W
2.05
Front-LOW(Front)
(1)9.5X31
control
100%
cd60
galvanized
parallel
n/a
linked
Return/Mixed Air
2700
9.50HX31.0W
2.05
TOP
(1)9.5X31
control
100%
cd60
galvanized
parallel
n/a
linked
8.89
(4)16X20
side
0.13
0.05
2"Pleated 30% (MERV 8)
pg. 161
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.23/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: permanent seal
Fan RPM: 2016
BHP: 3.3
Fan BHP w/ Belt Loss: 3.53
Outlet Velocity (ft/min): 2242
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.20
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.31
Opening: BOTTOM
pg. 163
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
9
22.5
33
5.2
left
1-5/8
1-1/8
1
none
2700
30
80
77
57.6
57.4
519
pg. 164
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.29
0.13
0.13
0.05
0.64
1.5
0.2
0.23
0.1
0.45
0.2
0.31
4.23
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
37
19
41
10
12
21
16
156
width
(in)
45
45
45
45
45
45
45
45
height
(in)
33
33
33
33
33
33
33
33
weight
(lbs.)
286
500
467
74
71
169
161
1728
pg. 165
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.19
UNIDAD:
UMA-F-02
CAUDAL (cfm)
2400
SECCION (plg x plg):33X42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.57
Outside Air (OA)
2400
9.50HX28.0W
1.85
Front-LOW(Front)
(1)9.5X28
control
100%
cd60
galvanized
parallel
n/a
linked
Return/Mixed Air
2400
9.50HX28.0W
1.85
TOP
(1)9.5X28
control
100%
cd60
galvanized
parallel
n/a
linked
8.89
(4)16X20
side
0.11
0.05
2"Pleated 30% (MERV 8)
pg. 166
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.17/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: permanent seal
Fan RPM: 2016
BHP: 3.01
Fan BHP w/ Belt Loss: 3.22
Outlet Velocity (ft/min): 1993
pg. 167
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
pg. 168
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: TOP
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
5
22.5
30
4.7
left
1-5/8
7/8
1
none
pg. 169
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
2400
30
80
77
57.6
57.4
511
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.28
0.13
0.11
0.05
0.67
1.5
0.15
0.23
0.1
0.45
0.2
0.3
4.17
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
37
19
41
10
12
21
16
156
width
(in)
42
42
42
42
42
42
42
42
height
(in)
33
33
33
33
33
33
33
33
weight
(lbs.)
274
482
457
72
69
164
153
1671
pg. 170
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.20
UNIDAD:
UMA-F-03
CAUDAL (cfm)
4200
SECCION (plg x plg):33X42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.38
Outside Air (OA)
4200
15.25HX37.00W
3.92
Front-high (Front)
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
4200
15.25HX37.00W
3.92
TOP
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
unlinked
17.78
(8)20x16
side
0.1
0.05
2"Pleated 30% (MERV 8)
pg. 171
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 4200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.84/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1632
BHP: 4.7
Fan BHP w/ Belt Loss: 5.03
Outlet Velocity (ft/min): 31778
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.35
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(4)30X16
8.9
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.25
0.1
12" Rigid
90-95%
MERV14
0.53
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: TOP
pg. 173
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
9
32.5
39
8.8
left
1-5/8
1-1/8
1
none
4200
30
76
67
55
54.2
477
pg. 174
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.19
0.04
0.1
0.05
0.53
1.2
0.35
0.25
0.1
0.53
0.2
0.3
3.84
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
pg. 175
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.21
UNIDAD:
UMA-F-04
CAUDAL (cfm)
3900
SECCION (plg x plg):36x60
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.28
Outside Air (OA)
3900
15.25hx46w
4.87
Front-low (Front)
(1)15.25x46
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
3900
15.25hx46w
4.87
TOP
(1)15.25x46
control
100%
cd60
galvanized
parallel
n/a
unlinked
16
(8)24x12
side
0.1
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.81/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1612
BHP: 4.2
Fan BHP w/ Belt Loss: 4.49
Outlet Velocity (ft/min): 2951
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.35
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(2)24X24
8
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.26
0.1
12" Rigid
90-95%
MERV14
0.56
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: TOP
pg. 178
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
9
11
27.5
48
9.2
left
2-1/8
1-1/8
1
none
3900
30
76
67
55
54.2
424
pg. 179
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
RESPONSABLE: F.CH.
0.11
0.02
0.1
0.05
0.36
1.5
0.31
0.26
0.1
0.56
0.2
0.24
3.81
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
31
19
34
10
12
21
17
144
width
(in)
60
60
60
60
60
60
60
60
height
(in)
36
36
36
36
36
36
36
36
weight
(lbs.)
316
560
501
87
86
203
216
1969
pg. 180
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.22
UNIDAD:
UMA-F-05
CAUDAL (cfm)
1800
SECCION (plg x plg):36x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.28
SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge
fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)
fc
10-10
S
permanent
seal
1283
0.88
0.97
1495
pg. 181
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.41
Return/Exhaust Air Pressure Drop (in. w.g.) 0.41
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Outside Air(OA)
1800
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a
1800
21HX10W
1.46
midle-angled
(1)21x10
control
200%
CD61
Galvanized
parallel
n/a
1800
21HX11W
1.6
right(right)
(1)21x11
control
300%
CD62
Galvanized
parallel
n/a
1800
N/A
N/A
none
none
none
none
none
none
none
n/a
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1800
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.23/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
pg. 183
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%
pg. 184
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(2)24X24
4
Side
4"
Prefilter Media:
Pleated 30%
(MERV 8)
0.2
0.1
21" Rigid
90-95% MERV15
0.48
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV15
pg. 185
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.28
Opening: bottom
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
7/8
1
none
pg. 186
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
1800
30
79.5
68.5
55.3
54.2
450
FF Flat Filter
CC Variable Length Cooling
Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
Return
(in.wg)
0.28
1.1
0.02
0.1
0.21
0.08
0.02
0.1
0.21
0.08
0.23
0.1
0.48
1.6
0.15
0.2
0.1
0.48
0.2
0.28
4.23
1.79
pg. 187
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
17
41
41
10
19
40
10
12
30
17
237
width
(in)
33
33
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
36
36
weight
(lbs.)
153
406
327
83
475
529
74
74
220
153
2494
pg. 188
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.23
UNIDAD:
UMA-F-06
CAUDAL (cfm)
3200
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.33
Outside Air (OA)
3200
15.25Hx34W
3.6
Front-low (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
3200
15.25Hx34W
3.6
TOP
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked
11.11
(2)24x20;(2)16x20
side
0.12
0.05
2"Pleated 30% (MERV 8)
pg. 189
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3200
Altitude (ft.): 9
TSP/ESP (in. w.g.): 3.98/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1622
BHP: 3.29
Fan BHP w/ Belt Loss: 3.52
Outlet Velocity (ft/min): 2421
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.22
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.2
Opening: TOP
pg. 191
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
8
7
32.5
36
8.1
left
1-5/8
1-1/8
1
none
3200
9
76.5
67.5
58.1
56.4
395
pg. 192
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
Supply (in.wg)
0.13
0.03
0.12
0.05
0.24
1.8
0.22
0.3
0.1
0.59
0.2
0.2
3.98
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
32
17
34
10
12
18
19
142
width
(in)
48
48
48
48
48
48
48
48
height
(in)
42
42
42
42
42
42
42
42
weight
(lbs.)
306
499
478
84
82
178
217
1844
pg. 193
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.24
UNIDAD:
UMA-F-07
CAUDAL (cfm)
3700
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.42
Outside Air (OA)
3700
15.25Hx34W
3.6
Front-low (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
3700
15.25Hx34W
3.6
TOP
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked
11.11
(2)24x20;(2)16x20
side
0.15
0.05
2"Pleated 30% (MERV 8)
pg. 194
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3700
Altitude (ft.): 9
TSP/ESP (in. w.g.): 4.61/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1749
BHP: 4.5
Fan BHP w/ Belt Loss: 4.82
Outlet Velocity (ft/min): 2800
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.29
pg. 195
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.27
Opening: TOP
pg. 196
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
10
32.5
36
8.1
left
1-5/8
1-1/8
1
none
3700
9
76.5
67.5
57.5
55.9
457
pg. 197
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
Supply (in.wg)
0.18
0.04
0.15
0.05
0.39
1.8
0.29
0.38
0.1
0.76
0.2
0.27
4.61
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
32
17
34
10
12
18
19
142
width
(in)
48
48
48
48
48
48
48
48
height
(in)
42
42
42
42
42
42
42
42
weight
(lbs.)
306
508
478
84
82
178
217
1853
pg. 198
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.25
UNIDAD:
UMA-F-08/9
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
2
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35
SEGMENTO FR
return segment fan
Segment Air Pressure Drop
(in. w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge
fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)
fc
10-10
S
permanent seal
1332
1.05
1.15
1661
pg. 199
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Outside Air(OA)
2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a
2000
21HX10W
1.46
midle-angled
(1)21x10
control
200%
CD60
Galvanized
parallel
n/a
2000
21HX11W
1.6
right(right)
(1)21x11
control
300%
CD60
Galvanized
parallel
n/a
2000
N/A
N/A
none
none
none
none
none
none
none
n/a
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.68/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
pg. 201
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%
Motor Control
Electrical Details
Full Load Amps (FLA):
11.8
Environmental
Ambient Temperature
(F): 5 to 104
Storage Temperature
(F): -40 to 158
Humidity: MAX 95% RH
non-condensing
Altitude: 3,300 ft. without
derate (1% derate
for each additional 330
ft.)
Enclosure: NEMA 3R
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.
pg. 202
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
4
Prefilter Media:
Pleated 30%
(MERV 8)
0.24
0.1
21" Rigid
90-95%
MERV15
0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1
pg. 203
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: bottom
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
7/8
1
none
pg. 204
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
2000
30
80.5
69.5
55.2
54.3
500
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter
DP Discharge Plenum
return
(in.wg)
0.35
1.1
0.03
0.1
0.26
0.1
0.03
0.1
0.26
0.1
0.27
0.1
0.59
1.6
0.19
0.24
0.1
0.55
0.2
0.35
4.68
1.94
pg. 205
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
17
41
41
10
19
40
10
12
30
17
237
width
(in)
33
33
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
36
36
weight
(lbs.)
153
416
327
83
483
529
74
74
220
153
2512
pg. 206
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.26
UNIDAD:
UMA-F-10
CAUDAL (cfm)
2900
SECCION (plg x plg):39x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.45
Outside Air (OA)
2900
15.25Hx34W
3.6
Front-high (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
2900
15.25Hx34W
3.6
bottom
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked
12
(2)24x24;(2)12x24
side
0.1
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.73/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1573
BHP: 2.76
Fan BHP w/ Belt Loss: 2.95
Outlet Velocity (ft/min): 2194
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19
pg. 208
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(1)24x24,
(1)12x24
6
Side
4
Prefilter Media:
Pleated 30%
(Quantity)Filter Sizes:
(MERV 8)
Prefilter Air Pressure Drop (in. w.g.): 0.23
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):
0.1
12" Rigid
90-95%
MERV14
0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom
pg. 209
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
30
36
7.5
left
1-5/8
7/8
1
none
2900
30
76.5
67
55.9
54.6
387
pg. 210
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
0.11
0.03
0.1
0.05
0.31
1.5
0.19
0.23
0.1
0.55
0.2
0.2
3.73
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
31
17
34
10
12
20
18
142
width height
(in)
(in)
48
39
48
39
48
39
48
39
48
39
48
39
48
39
48
39
weight
(lbs.)
369
517
478
92
92
209
216
1973
pg. 211
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.27
UNIDAD:
UMA-F-11
CAUDAL (cfm)
2700
SECCION (plg x plg):39x45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.44
Outside Air (OA)
2700
15.25Hx31W
3.28
Front-high (Front)
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
2700
15.25Hx31W
3.28
bottom
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unlinked
12
(2)24x24;(2)12x24
side
0.09
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.95/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: AF
Size: 12-12
Construction: S
Bearing Options: extended lube
Fan RPM: 2628
BHP: 2.41
Fan BHP w/ Belt Loss: 2.58
Outlet Velocity (ft/min): 1626
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.09
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(1)24x24,
(1)12x24
6
Side
4
Prefilter Media:
Pleated 30%
(Quantity)Filter Sizes:
(MERV 8)
Prefilter Air Pressure Drop (in.
w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):
0.2
0.1
12" Rigid
90-95%
MERV14
0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Discharge Plenum Options
Segment Air Pressure Drop (in. w.g.) 0.21 Interior Galvanized Liner
Opening: bottom
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33hX12W
Multi-Point Door Latch, No Lock, Outward
Opening
pg. 214
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
10
30
33
6.9
left
1-5/8
1-1/8
1
none
2700
30
78
71.5
55.1
54.6
391
pg. 215
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
supply
(in.wg)
0.06
0.1
0.11
0.03
0.09
0.05
0.42
1.8
0.09
0.2
0.1
0.49
0.2
0.21
3.95
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
31
19
47
10
12
20
18
157
width
(in)
45
45
45
45
45
45
45
45
height
(in)
39
39
39
39
39
39
39
39
weight
(lbs.)
353
544
591
91
89
199
206
2073
pg. 216
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.28
UNIDAD:
UMA-F-12
CAUDAL (cfm)
2800
SECCION (plg x plg):39x45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.45
Outside Air (OA)
2800
15.25Hx31W
3.28
Front-high (Front)
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unllinked
Return/Mixed Air
2800
15.25Hx31W
3.28
bottom
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unlinked
12
(2)24x24;(2)12x24
side
0.09
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2800
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.67/1.40
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1552
BHP: 2.58
Fan BHP w/ Belt Loss: 2.76
Outlet Velocity (ft/min): 2119
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(1)24x24,
(1)12x24
6
Side
4
Prefilter Media:
Pleated 30%
(Quantity)Filter Sizes:
(MERV 8)
Prefilter Air Pressure Drop (in.
w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):
0.22
0.1
12" Rigid
90-95%
MERV14
0.52
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.22
Opening: bottom
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
11
8
30
33
6.9
left
1-5/8
7/8
1
none
2800
30
77
68.7
56.2
55.1
406
pg. 220
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
supply
(in.wg)
0.06
0.1
0.12
0.03
0.09
0.05
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
0.38
1.4
0.18
0.22
0.1
0.52
0.2
0.22
3.67
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
31
17
44
10
12
20
18
152
width
(in)
45
45
45
45
45
45
45
45
height
(in)
39
39
39
39
39
39
39
39
weight
(lbs.)
353
507
536
90
89
199
206
1980
pg. 221
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.29
UNIDAD:
UMA-F-13
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.53
Outside Air (OA)
2000
15.25Hx19W
2.01
Front-high (Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
Linked
Return/Mixed Air
2000
15.25Hx19W
2.01
bottom
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
Linked
8
(2)24x24
side
0.1
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.15/1.40
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1920
BHP: 2.10
Fan BHP w/ Belt Loss: 2.25
Outlet Velocity (ft/min): 2180
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19
SEGMENTO XA
pg. 223
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
4"
Prefilter Media:
Pleated 30%
(MERV 8)
24
0.1
12" Rigid
90-95%
MERV14
0.58
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: bottom
pg. 224
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
5/8
1
none
2000
30
76
66.5
55.3
54.1
500
pg. 225
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
supply
(in.wg)
0.06
0.1
0.17
0.05
0.1
0.05
0.56
1.4
0.19
0.24
0.1
0.58
0.2
0.35
4.15
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
41
19
39
10
12
23
17
161
width height
(in)
(in)
33
36
33
36
33
36
33
36
33
36
33
36
33
36
33
36
weight
(lbs.)
339
475
407
74
74
176
153
1698
pg. 226
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.30
UNIDAD:
UMA-F-14
CAUDAL (cfm)
3300
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.5
Outside Air (OA)
3300
15.25Hx34W
3.6
Front-high (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
Unlinked
Return/Mixed Air
3300
15.25Hx34W
3.6
bottom
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
Unlinked
12
(2)24x24;(2)12X24
side
0.12
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3300
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.05/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-12
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1717
BHP: 3.81
Fan BHP w/ Belt Loss: 4.08
Outlet Velocity (ft/min): 1987
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.22
Opening: bottom
pg. 229
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
32.5
36
801
left
1-5/8
7/8
1
none
3300
30
75.5
65.5
56.4
54.6
407
pg. 230
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
supply
(in.wg)
0.06
0.1
0.14
0.03
0.12
0.05
0.33
1.6
0.15
0.28
0.1
0.67
0.2
0.22
4.05
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
34
17
47
10
12
20
19
159
width
(in)
48
48
48
48
48
48
48
48
height
(in)
42
42
42
42
42
42
42
42
weight
(lbs.)
405
524
620
96
94
216
233
2188
pg. 231
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.31
UNIDAD:
ver listado
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
4
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35
SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge
fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)
FC
9-9
S
permanent
seal
1410
1.03
1.12
2002
pg. 232
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Outside Air(OA)
2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a
2000
21HX10W
1.46
midle-angled
(1)21x10
control
100%
CD60
Galvanized
parallel
n/a
2000
21HX11W
1.6
right(right)
(1)21x11
control
100%
CD60
Galvanized
parallel
n/a
2000
N/A
N/A
none
none
none
none
none
none
none
n/a
pg. 233
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.18/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
pg. 234
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19
SEGMENTO XA
Access Segment Details
Segment Length: 12"
pg. 235
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
4"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
21" bag
90-95%
MERV15
0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: REAR-REAR
pg. 236
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
5/8
1
none
2000
30
80.5
69
55.1
54
500
pg. 237
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter
DP Discharge Plenum
return
(in.wg)
0.35
0.8
0.03
0.1
0.26
0.1
0.03
0.1
0.26
0.1
0.27
0.1
0.59
1.1
0.19
0.24
0.1
0.55
0.2
0.35
4.18
1.64
Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
17
39
41
10
19
40
10
12
30
17
235
width
(in)
33
33
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
36
36
weight
(lbs.)
153
392
327
83
483
529
74
74
220
153
2488
pg. 238
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.32
UNIDAD:
ver listado
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
3
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35
SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge
fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)
FC
9-9
S
permanent
seal
1409
1.03
1.12
2002
pg. 239
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Outside Air(OA)
2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a
2000
21HX10W
1.46
midle-angled
(1)21x10
control
100%
CD60
Galvanized
parallel
n/a
2000
21HX11W
1.6
right(right)
(1)21x11
control
100%
CD60
Galvanized
parallel
n/a
2000
N/A
N/A
none
none
none
none
none
none
none
n/a
pg. 240
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.18/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
pg. 241
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%
SEGMENTO XA
Access Segment Details
Segment Length: 12"
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x24
4
Side
4"
Prefilter Media:
Pleated 30%
(MERV 8)
0.1
21" bag
90-95%
MERV15
0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: REAR-REAR
pg. 243
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
5/8
1
none
2000
30
80.5
69
55.1
54
500
pg. 244
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter
DP Discharge Plenum
return
(in.wg)
0.35
0.8
0.03
0.1
0.26
0.1
0.03
0.1
0.26
0.1
0.27
0.1
0.59
1.1
0.19
0.24
0.1
0.55
0.2
0.35
4.18
1.64
Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
17
39
41
10
19
40
10
12
30
17
235
width
(in)
33
33
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
36
36
weight
(lbs.)
153
392
327
83
483
529
74
74
220
153
2488
pg. 245
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.33
UNIDAD:
UMA-F-17
CAUDAL (cfm)
2400
SECCION (plg x plg):36x42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.24
SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge
fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)
FC
9-9
S
permanent
seal
1407
1.33
1.45
2403
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.35
Return/Exhaust Air Pressure Drop (in. w.g.) 0.35
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Outside Air(OA)
2400
21HX16W
2.33
left(left)
(1)21X16
control
100%
CD60
Galvanized
parallel
n/a
2400
21HX14W
2.04
midle-angled
(1)21x14
control
100%
CD60
Galvanized
parallel
n/a
2400
21HX16W
2.33
right(right)
(1)21x16
control
100%
CD60
Galvanized
parallel
n/a
2400
N/A
N/A
none
none
none
none
none
none
none
n/a
pg. 247
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)20x24;(1)12x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
5.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.65/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
pg. 248
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.26
SEGMENTO XA
Access Segment Details
Segment Length: 12"
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: REAR-REAR
pg. 250
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
8
6
27.5
30
5.7
left
1-5/8
7/8
1
none
2400
30
81.5
70.5
55.3
54.5
421
pg. 251
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter
DP Discharge Plenum
return
(in.wg)
0.24
0.8
0.02
0.1
0.18
0.05
0.02
0.1
0.18
0.05
0.23
0.1
0.39
1.1
0.26
0.2
0.1
0.48
0.2
0.24
3.65
1.39
Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
17
39
46
10
22
43
10
12
30
17
246
width
(in)
42
42
42
42
42
42
42
42
42
42
42
height
(in)
36
36
36
36
36
36
36
36
36
36
36
weight
(lbs.)
181
430
406
95
545
596
82
83
254
181
2853
pg. 252
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.34
UNIDAD:
UMA-H-01
CAUDAL (cfm)
1200
SECCION (plg x plg):30x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: TOP
Segment Air Pressure Drop (in. w.g.) 0.20
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.17
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 253
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.49/1.4
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1965
BHP: 1.14
Fan BHP w/ Belt Loss: 1.25
Outlet Velocity (ft/min): 1650
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.10
SEGMENTO XA
Access Segment Details
Segment Length: 12"
pg. 254
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x20
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.17
0.1
12" RIGID
90-95%
MERV14
0.36
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: TOP
pg. 255
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
6
20
21
2.9
left
1-5/8
5/8
1
none
1200
30
80
77
54.9
54.8
414
pg. 256
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SUPPLY
(in.wg)
0.2
0.17
0.05
COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
0.54
1.4
0.1
0.17
0.1
0.36
0.2
0.2
3.49
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
15
10
19
37
10
12
21
15
139
width
(in)
33
33
33
33
33
33
33
33
33
height
(in)
30
30
30
30
30
30
30
30
30
weight
(lbs.)
116
67
441
326
59
59
135
116
1319
pg. 257
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.35
UNIDAD:
UMA-H-02/03
CAUDAL (cfm)
1950
SECCION (plg x plg):36X33
CANTIDAD:
2
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: front (front)
Segment Air Pressure Drop (in. w.g.) 0.33
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 258
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.61/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 2042
BHP: 2.29
Fan BHP w/ Belt Loss: 2.45
Outlet Velocity (ft/min): 2125
Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158
pg. 259
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18
SEGMENTO XA
Access Segment Details
Segment Length: 27"
pg. 260
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x20
4
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.26
0.1
12" RIGID
90-95%
MERV14
0.56
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: bottom
pg. 261
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
6
27.5
21
4
left
1-5/8
5/8
1
none
1950
30
80
77
56.6
56.4
488
pg. 262
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SUPPLY
(in.wg)
0.33
0.26
0.1
COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
0.69
1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.61
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
20
10
19
40
10
27
21
17
164
width
(in)
33
33
33
33
33
33
33
33
33
height
(in)
36
36
36
36
36
36
36
36
36
weight
(lbs.)
171
83
486
529
74
164
164
153
1824
pg. 263
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.36
UNIDAD:
UMA-H-05
CAUDAL (cfm)
3200
SECCION (plg x plg):39x51
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY
0.46
Outside Air (OA)
3200
15.25Hx37.00W
3.92
Front-high (Front)
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
Unlinked
Return/Mixed Air
3200
15.25Hx37.00W
3.92
bottom
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
Unlinked
11.11
(2)24x20; (2)16x20
side
0.12
0.05
2"Pleated 30% (MERV 8)
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO CC
Coil Segment Details
Coil Space: 7"
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.79/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1575
BHP: 3.12
Fan BHP w/ Belt Loss: 3.34
Outlet Velocity (ft/min): 2421
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.22
pg. 265
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO XA
Access Segment Details
Segment Length: 12"
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
(1)20x24
6.7
Side
2"
Pleated 30%
(MERV 8)
0.25
0.1
12" RIGID
90-95%
MERV14
0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom
pg. 266
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
30
39
8.1
left
1-5/8
7/8
1
none
3200
30
76
66.5
55.8
54.5
395
pg. 267
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter
DP Discharge Plenum
SUPPLY
(in.wg)
0.06
0.1
0.11
0.02
0.12
0.05
0.31
1.5
0.22
0.25
0.1
0.55
0.2
0.2
3.79
Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL
Length
(in)
33
17
34
10
12
18
18
142
width height
(in)
(in)
51
39
51
39
51
39
51
39
51
39
51
39
51
39
51
39
weight
(lbs.)
401
529
517
95
94
190
225
2051
pg. 268
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
RUBRO:
N2.AA-04.37
UNIDAD:
UMA-H-06
CAUDAL (cfm)
1200
SECCION (plg x plg):30x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: front (front)
Segment Air Pressure Drop (in. w.g.) 0.20
SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.17
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1
SEGMENTO CC
Coil Segment Details
Coil Space: 10"
pg. 269
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.65/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 2011
BHP: 1.2
Fan BHP w/ Belt Loss: 1.31
Outlet Velocity (ft/min): 1650
Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158
pg. 270
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):
Output
Output Current Amps: 7.5
Overload Current Rating: 110% for 1 minute
every 10 minutes
Drives are rated for use below 3,300 ft and
104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.
SEGMENTO DI
SEGMENTO XA
Access Segment Details
Segment Length: 27"
pg. 271
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
(1)24x20
3.3
Side
2"
Prefilter Media:
Pleated 30%
(MERV 8)
0.17
0.1
12" RIGID
90-95%
MERV14
0.36
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom
pg. 272
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
20
21
2.9
left
1-5/8
7/8
1
none
1200
30
80
77
57.2
56.9
414
pg. 273
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
DP Discharge Plenum
SUPPLY
(in.wg)
0.2
0.17
0.1
COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
Cooling 5 rows 10 fins
External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL
0.45
1.6
0.1
0.17
0.1
0.36
0.2
0.2
3.65
Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
Length
(in)
18
10
19
40
10
27
21
15
160
width height
(in)
(in)
33
30
33
30
33
30
33
30
33
30
33
30
33
30
33
30
33
30
weight
(lbs.)
141
74
447
486
66
153
149
125
1641
pg. 274
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-09.01
al 20
ESPECIFICACIN
El plenum de difusores y rejillas es construido en acero galvanizado, con un cuello de
dimetro especificado en los planos y tendr un regulador de flujo del tipo de hojas
paralelas opuestas, de fcil acceso y mantenimiento.
Los colores de rejillas y difusores estn indicados en el presupuesto referencial.
DIFUSORES DE SUMINISTRO
De acuerdo a lo que se indica en los planos, para los sistemas de aire acondicionado y
ventilacin mecnica mediante ventiladores, equipos de tipo paquete y unidades
manejadoras de aire, se instalarn difusores de volumen fijo, los cuales sern
construidos en perfiles de aluminio extruido, iguales al modelo JS-OB, fabricados por
AIR GUIDE Corp. o similares.
El difusor tendr montado un disco interior de dispersin de aire para obtener una
distribucin horizontal de 360.
Cada difusor de suministro tendr un regulador de flujo del tipo de hojas paralelas
opuestas, de fcil acceso y mantenimiento.
REJILLAS DE RETORNO
Las rejillas de extraccin y de retorno sern construidas en perfiles de aluminio
extruido iguales al modelo RA-OB fabricadas por AIR GUIDE Corp.
Cada rejilla de extraccin tendr un regulador de flujo del tipo de hojas paralelas
opuestas, de fcil acceso y mantenimiento.
A continuacin se adjunta un detalle de las dimensiones, especificaciones y
cantidades de este rubro en cada sistema de ventilacin:
pg. 275
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
RESPONSABLE: F.CH.
# VIAS COLOR
DIMENS. OBSERV
AA-09.01
490
DIFUSOR
SUMINIST.
BLANCO
6"x6"
AA-09.02
168
DIFUSOR
SUMINIST.
BLANCO
8"x8"
AA-09.03
17
DIFUSOR
SUMINIST.
BLANCO
18"x18"
AA-09.04
62
DIFUSOR
SUMINIST.
BLANCO
16"x16"
AA-09.08
22
REJILLA
RETORN.
22"X14"
AA-09.09
REJILLA
RETORN.
20"X10"
AA-09.10
REJILLA
RETORN.
20"X10"
AA-09.11
46
REJILLA
RETORN.
BLANCO
AA-09.12
REJILLA
DESCARG
BLANCO
AA-09.13
47
REJILLA
DESCARG
BLANCO
20"X10"
6"X6"
8"X8"
aluminio +damper
48"X24"
AA-09.14
LOUVER
SUMINIST/
DESCARG.
AA-09.15
LOUVER
SUMINIST/
DESCARG.
36"X24
AA-09.16
51
LOUVER
SUMINIST/
DESCARG.
24"X24"
AA-09.17
40
LOUVER
SUMINIST/
DESCARG.
24"X12"
AA-09.18
27
LOUVER
SUMINIST/
DESCARG.
12"X12"
AA-09.19
LOUVER
SUMINIST/
DESCARG.
48"X36"
AA-09.20
LOUVER
SUMINIST/
DESCARG.
36"X36"
pg. 276
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-09.21
al 26
ESPECIFICACIN
La manguera flexible ser aislada o sin aislamiento, el material ser compuesto de un
polister metalizado, lmina de aluminio y una pelcula de polister que encapsulan un
anillo helicoidal de acero. El material aislante ser lana de vidrio con foil de aluminio,
exterior al material antes indicado.
El ducto deber cumplir con normas de Underwriters Laboratories UL181 y NFPA 90A
& 90B y son exclusivamente para uso interior bajo sombra.
Los ductos sin aislamiento sern fabricados con forma circular con tres capas de
lminas de polister aluminizado recubriendo a ambos lados a una estructura helicoide
de alambre de acero y en longitudes de 25ft.
Los ductos con aislamiento sern similares en su construccin a los anteriores pero
adicionalmente tendrn una capa aislante trmica exterior con R-6.0 segn UL 181,
Class 1 Air Ducts, la capa de aislamiento estar compuesta por una lmina de lana de
vidrio tridireccional reforzada y una lmina exterior de material de polyester reforzada
para evitar la rasgadura.
INSTALACION
Las mangas de ducto flexible sern instaladas tratando de que estn longitudinalmente
extendidas y buscando el camino ms corto a seguir.
En el recorrido debern evitarse contacto con materiales o bordes cortantes, tuberas o
conductos.
El radio de curvatura en una trayectoria siempre deber ser mnimo igual al dimetro
del ducto.
No se deber instalar ducto flexible muy cerca de equipos o conductos que emanen
calor.
Los tramos de ductos flexibles podrn ser juntados a travs de mangas de lmina de
acero galvanizado con una longitud no menor a 4 y los collares exteriores sern
elaborados en el mismo material con una longitud mnima de 2
Todas las juntas sern selladas adicionalmente con cinta adhesiva especifica para
ductos y que cumpla con UL Standard 181B
En la situacin que el ducto flexible deba quedar suspendido, ser soportado en
tramos no mayores de 4
El collar que soporte el ducto colgante deber tener un mnimo de 1-1/2 y deber
instalarse de manera de no deformar el perfil circular del ducto no poner en riesgo su
integridad.
pg. 277
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
En el caso de los ductos con aislamiento el trabajo de unin se har en la parte interna
del ducto y luego el aislamiento deber quedar completamente sellado con la cinta
adhesiva apropiada, cuidando siempre de que la capa de aislamiento se conserve
completa.
RUBRO
DESCRIPCION
AISLAMIENTO
DIAMETRO
AA-09.21
AA-09.22
AA-09.23
AA-09.24
AA-09.25
AA-09.26
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
NO
NO
NO
NO
SI
SI
4"
6"
8"
10"
4"
14"
CANTIDAD
658
293
74
4
1,429
1,112
pg. 278
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-10.01
al 08
ESPECIFICACIN
El Contratista construir todo el sistema de distribucin de refrigerante de acuerdo con
los planos del proyecto, para lo cual suministrar todos los materiales que sean
necesarios, cindose a las especificaciones de materiales y montaje detallados a
continuacin.
Adems, deber limpiar, proteger y mantener los sistemas hasta la entrega de la obra.
Tubera, accesorios y vlvulas de corte se emplearn de acuerdo a especificaciones
detalladas a continuacin, para tubos de dimetro nominal de a 1-5/8:
- Material:
- Tipo:
- Espesor de pared:
0.032 plg
- Fabricacin:
Fundicin de Cobre.
- Presin de trabajo:
400 psi
- Presin de prueba:
600 psi
Cada unin se realizar con soldadura oxiacetilnica con soldadura de plata al 15%.
El Contratista Mecnico suministrar la mano de obra especializada para efectuar el
montaje completo de la tubera y accesorios de cobre, aislamiento trmico, as como
tambin las conexiones elctricas necesarias de fuerza y control para su
funcionamiento, desde la salida de la unidad exterior hasta las unidades interiores.
Examinar los planos del sistema con el objeto de tener pleno conocimiento del
mismo, y notificar al Propietario de cualquier anomala, tanto en el diseo como en
los materiales, en su debida oportunidad, con el objeto de no causar ningn retraso en
la obra.
Todas las lneas de las tuberas deben instalarse con secciones completas, evitando
tramos cortos.
Se eliminar toda tensin indebida, evitando dobleces que entorpezcan el flujo normal.
Antes de empezar la instalacin de la red de tuberas deber tomarse mucho cuidado
en la limpieza de los bordes cortados y en sellar las mismas para evitar el ingreso de
suciedad en la red.
pg. 279
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
F(W/Mk)
F(W/Mk)
Kg/(s*m*Pa)
C
pulg
0.036
0.037
0.725x10
-13
0.20%
-180 A 100
1/2
pg. 280
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 281
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
AA-10.01
AA-10.02
AA-10.03
AA-10.04
AA-10.05
AA-10.06
AA-10.07
AA-10.08
DESCRIPCION
FLEXIBLE TIPO "L"
FLEXIBLE TIPO "L"
FLEXIBLE TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "K"
AISLAMIENTO
SI
SI
SI
SI
SI
SI
SI
SI
RESPONSABLE: F.CH.
DIAMETRO
1/4"
3/8"
1/2"
5/8"
3/4"
7/8"
1-1/8"
1-3/8"
CANTIDAD
1,466
2,181
2,431
2,236
931
491
2,194
294
pg. 282
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-03.07
ESPECIFICACIN
El R410A es una mezcla no azeotrpica compuesta de R125 y R32.
Es un producto qumicamente estable, con un bajo deslizamiento (Glide) de
temperatura y baja toxicidad. A pesar del carcter inflamable del R32, la formulacin
global del producto hace que este no sea inflamable, incluso en caso de fugas.
El producto deber contar con Certificacin AHRI calidad y pureza
CANTIDAD= 1007 Kg,
PROPIEDADES FISICAS
Mezcla binaria
Composicin (%)
Peso molecular (Kg/Kmol)
R-410A
R32 / R125
50 / 50
72.6
52.7
0.5
72.5
49.5
1.07
1.27
4.2
16.5
Ninguno
3.34
2500
0.013
0.091
1.28
1.71
257
3.34
1000
pg. 283
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
al 15
ESPECIFICACIN
Se instalar el cableado de fuerza y control, desde las unidades exteriores de volumen
de refrigerante variable, hacia sus respectivas unidades interiores, as como tambin
entre las unidades internas y externas de los equipos Inverter sueltos, y el cableado
hacia los controles de temperatura de los diferentes equipos, con conductor tipo AWG
de acuerdo a la siguiente especificacin:
- Material:
Conductor de cobre
- Calibre:
- Especificacin:
- Seccin aprox.
- Capacidad conduccin:
30 Amp, 15 Amp
600 V.
- Recubrimiento:
- Accesorios:
El cableado de fuerza y control, especificado arriba, deber estar protegido por medio de
tubera conduit EMT, de acuerdo a la siguiente especificacin:
- Material:
- Especificaciones:
INEN 1374
- Presin de prueba:
- Flexin:
- Aplastamiento:
- Impacto:
- Uniones, y conectores:
Accesorios EMT.
pg. 284
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RUBRO
RESPONSABLE: F.CH.
DESCRIPCION
CANT
6,376
7,187
3,086
7,803
2,007
634
5
pg. 285
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: 9636-37
ESPECIFICACIN DUCTOS
SIN AISLAMIENTO: RUBRO 9636
RUBRO 9637 ANTES DEL AISLAMIENTO
El Contratista fabricar e instalar todos los sistemas de ductos de conformidad con
los planos de proyecto, para lo cual suministrar todos los materiales que sean
necesarios, cindose a las siguientes especificaciones de materiales, fabricacin y
montaje y aquellas establecidas en la normativa SMACNA.
En la fabricacin de ductos de aire acondicionado y ventilacin se emplear lmina lisa
de acero galvanizado ASTM A525 de primera calidad "lock-forming grade", de acuerdo
con los calibres indicados segn el tamao de los ductos.
En ningn caso se aceptar el empleo de lmina galvanizada que muestre deterioro
de sus condiciones y/o en los dobleces o quiebres.
Los espesores de lmina, estn determinados de la siguiente manera, ductos cuyo
lado mayor est comprendido entre:
LADO MAYOR
CALIBRE DE LAMINA
0" y 30"
24 USG (0.6mm)
31" y 54"
22 USG (0.7mm)
55" y 84"
20 USG (0.9mm)
Superior a 85"
18 USG (1.0mm)
Todos los codos debern tener un radio medio igual al lado del ducto. En sitios donde
por dificultades de espacio no se pueda obtener este radio mnimo, se instalarn guas o
deflectores internos en lmina galvanizada de acuerdo con el detalle de los planos y las
recomendaciones constructivas de las normas SMACNA.
pg. 286
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Las piezas de transicin entre ductos de dos secciones diferentes, sern fabricadas con
pendientes que no excedan 1:5 en cualquier cara del ducto y preferiblemente 1:7 en
donde ello sea posible.
Donde los planos indican, y en los que el Contratista considere necesarios, se instalarn
compuertas o reguladores de volumen de fcil manejo y acceso desde el exterior, para el
correcto balanceo del sistema. Toda compuerta ajustable tendr un dispositivo exterior
que indique su posicin.
Todas las dimensiones de los ductos de conduccin de aire que se muestran en los
planos o lminas de diseo se refieren al tamao interior libre necesario. El aislamiento
trmico en el caso del ducto aislado ser externo.
INSTALACION DE SOPORTES
Para todos los ductos horizontales se utilizarn soportes de acuerdo con los detalles de
los planos, es decir varilla roscada galvanizada de 5/16" y canal troquelado galvanizado,
para ductos de hasta 15", para ductos de ms de 16" se deber usar varilla roscada
galvanizada de 3/8". Los ductos verticales sern soportados utilizando perfiles de ngulo
de acero arriostrados a la estructura del edificio en cada uno de los pisos y sujetos de
manera apropiada.
El canal troquelado para soporte tendr las siguientes caractersticas fsicas, y ser de un
espesor de 2.6mm, o calibre 12. Para el adecuado soporte se debern usar (accesorios
galvanizados) arandelas planas cuadradas para facilitar el apriete de la tuercas que
sujetan el canal a la varilla roscada
UNIONES LONGITUDINALES
Las uniones longitudinales, en las esquinas de todos los ductos se harn utilizando la
unin tipo "Pittsburgh" fabricados en mquina formadora por rollos (roll forming) de
manera a garantizar la calidad y dimensiones de la junta. Se aceptarn nicamente
juntas longitudinales que cumplan lo especificado por la norma SMACNA.
pg. 287
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Para las uniones longitudinales que no correspondan a esquinas, se utilizar unin tipo
"Standing Seam" segn la norma SMACNA.
Todas las juntas debern ser hermticas y construidas en forma tal que los salientes
interiores apunten en la direccin del flujo de aire.
UNIONES TRANSVERSALES
Para el caso de Uniones Transversales de ductos, se utilizarn tres alternativas de
acuerdo a la aplicacin de la red de ductos a la que corresponde:
o C y S slip. Este tipo de juntas transversales se utilizarn para ductos cuya
aplicacin sea extraccin de baos, recirculacin de Fan Coils, recuperadores de
energa de rueda para oficinas, habitaciones de cuidado bsico, suministro de
aire con nivel de filtrado menor al 40%. Los perfiles S y C deber ser fabricado en
mquina formadora por rollos (roll forming) de manera a garantizar la calidad y
dimensiones segn SMACNA.
o TDC o TDF. Este tipo de junta se utilizar para sistemas de ventilacin y
climatizacin que atiendan a ambientes correspondientes a unidades
manejadoras de aire de doble pared, recuperadores de energa de placas y de
rueda entlpica y en ambientes de cuidado medio en adelante
o Bridado. Este tipo de ductos se utilizarn para la extraccin de aire con grasa y
humo de la cocina, y en los casos en los cuales lo indica la especificacin que se
muestra a continuacin.
UNIONES TRANSVERSALES TIPO C y S SLIP
Este tipo de uniones transversales sern elaboradas en proceso de conformado en
rodillos roll forming en el misma lmina galvanizada que se fabrica el ducto y
adicionalmente se deber aplicar sellante especfico para ductos de aire acondicionado y
ventilacin de manera a garantizar la hermeticidad de las mismas, a continuacin se
presenta el esquema constructivo de este tipo de junta.
pg. 288
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
UNION TRANSVERSAL
0" y 24"
S-Slip
25" y 40"
Bar-Slip de 1"
41" y 60"
Superior a 60"
pg. 289
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
REFUERZO DE DUCTOS
Los ductos tendrn refuerzos de acuerdo a la siguiente tabla:
LADO MAYOR
0" y 15"
16" y 24"
25" y 41"
42" y 84"
Mayor a 85"
TIPO DE REFUERZO
Lamina acanalada cada 60cm
Lamina acanalada cada 40cm
Lamina acanalada cada 40cm y refuerzo de
ngulo de 1"x1"x1/8"
Lamina acanalada cada 40cm y refuerzo de
ngulo de 1"x1"x1/8
Lamina acanalada cada 40cm y refuerzo en
ngulo de 2"x2"x "
Los ngulos de refuerzo requeridos y los de uniones con brida sern remachados y no
atornillados a la lmina del ducto.
El proceso de acanalado de la lmina debe ser realizado en una mquina de rodillos
especial para este propsito, no se aceptar lmina con quiebre en diamante o sin el
reforzamiento especificado.
ESPECIFICACION TECNICA DEL AISLAMIENTO RUBRO 9637
Los ductos del sistema de aire acondicionado se debern aislar con lana de vidrio de
2." de espesor y 2 lbs./pie2 de densidad con lmina de papel de aluminio adherido al
aislante, montado por la parte exterior de los ductos de tol galvanizado. Se debern
utilizar zunchos de plstico de manera a asegurar el aislamiento y evitar la separacin
del aislamiento trmico de la pared del ducto.
Para las juntas del aislamiento se aplicar cinta adhesiva de aluminio de manera a
mantener la integridad de la membrana a prueba de vapor de agua.
Los ductos de extraccin y suministro, que estn expuestos a la intemperie, debern
llevar adicionalmente al aislamiento el impermeabilizante de asfalto con foil de aluminio,
en todas las caras.
pg. 290
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 291
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Para la ejecucin de estos rubros se requiere el siguiente equipo mnimo para cada
tipo de actividad:
1. GRUPO DE INGENIERIA SUPERVIOR Y RESIDENTES
El equipo de ingeniera deber disponer de equipos para:
Computador personal de escritorio con la suficiente capacidad de trabajo para
procesar toda la informacin del proyecto sin causar retrasos al avance de
obra.
Medicin de caudales de aire en ductos.
Medicin de presin esttica
Medicin de espesores de lmina galvanizada
Medicin de flujos de aire en difusores y rejillas
Balanza calibrada y certificada para pesaje de ductos.
2. GRUPO DE CONSTRUCCION DE DUCTOS
Cada grupo de construccin deber disponer de los siguientes equipos:
Maquina elaboracin de junta tipo Pittsburg por conformado con rodillos.
Maquina elaboracin de perfiles S y C por conformado con rodillos
Mquina de rodillos para elaborar acanalado de refuerzo en la lmina
Dobladora de muelas calibrada segn el espesor de la lmina.
Cizalla de corte mecnica o hidrulica.
Rebordeadora con diferentes rodillos para elaboracin de cuellos, codos y
dems accesorios.
Kits completos de herramientas para fabricacin y montaje de ductos: picado,
doblez, y sellado de ductos.
3. GRUPO DE MONTAJE DE DUCTOS
Cada grupo de montaje deber disponer de los siguientes equipos:
Andamios y escaleras en buenas condiciones
Taladro de percusin de tipo roto martillo
Kits completos de herramientas para montaje y sellado de ductos.
Todo el personal deber cumplir con la normativa de seguridad industrial respectiva.
CUADRO DE PESOS APROXIMADOS DE DUCTOS
A continuacin se presenta el cuadro resumen de los pesos aproximados de los dos
tipos de ductos:
TOTAL (Kg)
PESO TOTAL
SIN AISLAMIENTO RUBRO 9636
PESO TOTAL
CON AISLAMIENTO RUBRO
9637
28,775.23
72,159.95
pg. 292
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 293
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO:
ESPECIFICACIN
Filtros de Aire 40% (MERV 6):
Los filtros de aire para los ventiladores de suministro de aire fresco de 40% de
eficiencia sern de tipo desechable construidos con un medio filtrante diseado para
una gran capacidad de captura de polvo y baja resistencia al paso de aire.
Estos filtros permitirn el paso de aire entre 300 y 700 pies/minuto con una resistencia
inicial mxima de 0.10" c.a.
En el caso en el que se especifiquen ventiladores de suministro con filtros
incorporados, los filtros de aire se instalarn de acuerdo a las especificaciones de
estos equipos.
Se aceptar los filtros de fibras multidireccionales o mantas filtrantes cuya
especificacin corresponda a un prefiltro.
Filtros de aire 30% de eficiencia (MERV 1):
Los filtros de aire de 30% de eficiencia sern del tipo permanente y lavable construidos
con un marco de aluminio y con el medio filtrante de por lo menos 6 capas de aluminio
expandido diseado para una gran capacidad de captura de polvo y baja resistencia al
paso de aire.
Estos filtros permitirn el paso de aire entre 300 y 700 pies/minuto con una resistencia
mxima de 0.18" c.a.
En el caso en el que se especifiquen ventiladores de suministro con filtros
incorporados, los filtros de aire se instalarn de acuerdo a las especificaciones de
estos equipos.
Cuando se especifique en los planos, se debern colocar bancos de filtros de alta
eficiencia respetando las siguientes especificaciones:
Filtros de 65% (MERV 10) y 95% (MERV 12) de eficiencia:
Los filtros de alta eficiencia sern construidos con fajas continuas de fibra fina plegada
con separadores de aluminio, sellados en fbrica en un marco de madera aglomerada
resistente al fuego (U.L. Class 1).
Estos filtros se montarn en un marco construido en chapa galvanizada con clips
retenedores y empaque para sello hermtico.
Los filtros sern iguales o similares al modelo RIGID AIR fabricado por FLANDERS
PRECISION AIR.
Los filtros tendrn una eficiencia promedio de 60%, 90% 95% de acuerdo a lo que se
especifique (ASHRAE Std 52-68) usando polvo atmosfrico.
pg. 294
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 295
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO:
ESPECIFICACIN
Cdigos y Estndares
ASHRAE: American Society of Heating Refrigerating and Air Conditioning Engineers.
ASTM: American Society for Testing and Materials.
NPC: National Plumbing Code.
APC: American Plumbing Code
Planos:
Se proveern al Contratista los planos de ingeniera y diseos del sistema.
A medida que progrese la instalacin, el Contratista realizar los planos de "Obra Como
Construida" para ser entregados al Propietario.
El Contratista inspeccionar el sitio en que se realizarn los trabajos de esta
especificacin a fin de comprobar si est listo para proseguir con los trabajos e informar
al Fiscalizador sobre cualquier anomala que amenace perjudicar la bondad de dicho
trabajo.
Deber especficamente:
Examinar todos los estudios propios de esta instalacin, as como otros que deban
desarrollarse en forma conjunta a fin de proceder coordinadamente.
Revisar los estudios de esta instalacin tales como planos, especificaciones tcnicas,
cdigos y estndares, para que en base a este estudio plantee el programa de trabajo
total.
Evitar posibles interferencias con otros rubros de trabajo.
Proveer seguridades para el personal con el objeto de evitar cualquier accidente de
trabajo, y precauciones para evitar daos en estructuras, otras instalaciones, etc.
El Contratista ser responsable de la bondad de las instalaciones y equipos. Cualquier
comentario u observacin a las especificaciones de los materiales y equipos deber
comunicarlo al Propietario, ya que el contratista ser el responsable por el buen
funcionamiento del sistema.
El Contratista Elctrico suministrar la debida alimentacin, acometida elctrica, tablero
de breakers y arrancadores para todos los ventiladores y equipos de los sistemas de
Ventilacin Mecnica, listados en estas memorias.
El Contratista Mecnico se encargar de proporcionar la ingeniera necesaria para el
montaje, instalacin y puesta a punto de los tableros de arrancadores de acuerdo a las
caractersticas y ubicacin de los equipos y dispositivos que as lo requieran, desde los
breakers instalados por el Contratista Elctrico hasta los equipos.
pg. 296
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Dichos tableros debern cumplir con todas las normas y sern fabricados segn
especificaciones NEMA tipo 1, de uso general, formado por secciones verticales de
servicio sencillo, con todos sus lados cerrados inclusive el piso.
Los tableros de control elctrico de los ventiladores suministrados por el Contratista
elctrico, debern contar con los respectivos contactores trifsicos y protector trmico
automtico debidamente dimensionados, con pulsadores de arranque-parada asociados
con su luz indicadora verde-roja, respectivamente y su placa identificadora (EncendidoApagado START/STOP).
El contratista mecnico suministrar mano de obra especializada para efectuar el
montaje completo de los equipos de ventilacin mecnica, y hacer las conexiones
elctricas finales de los mismos.
El Contratista balancear y ajustar los sistemas de distribucin de aire como sigue:
Examinar los sistemas de manejo de aire con el objeto de determinar que estn libres
de obstrucciones.
Determinar que todas las compuertas y registros estn abiertos, que todas las partes
mviles estn lubricadas, que los filtros estn limpios y operando debidamente y
efectuar todas las actividades de inspeccin y mantenimiento necesarios para la
correcta operacin de los sistemas.
Instalar los accesorios necesarios en los ductos para poder realizar la medicin de flujo
de aire, presin esttica, en todos los ductos principales, a fin de garantizar el correcto
funcionamiento de los sistemas.
Demostrar que el equipo de manejo de aire trabaja de acuerdo con lo especificado.
Ajustar las poleas de dimetro variable y las compuertas de volumen. Cada unidad
terminal retirar la cantidad de CFM especificada en forma dispuesta.
Tabular los resultados de las pruebas en formatos previamente aprobados y
suministrar tres copias de cada uno para aprobacin y archivo.
Se pondr en marcha el sistema completo, se graduar y ajustar para poder efectuar las
pruebas completas.
Las tuberas de drenaje debern ser diseadas e instaladas por el Contratista
Hidrosanitario bajo las instrucciones del Contratista Mecnico y siguiendo las
siguientes normas bsicas:
Las tuberas horizontales que deban ser suspendidas, debern tener pendiente y
todas las entradas se conectarn a los ramales, de arriba hacia abajo, y donde esto no
sea posible, todos los ramales se conectarn a la lnea principal por arriba de sta.
Los dimetros de la tubera de drenaje los definir el Contratista Mecnico y dependern
de la capacidad de las unidades interiores, de acuerdo a la tabla siguiente:
pg. 297
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
CAPACIDAD
RESPONSABLE: F.CH.
TUBERIA DE DRENAJE
20 mm.
25 mm
30 mm
40 mm
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 299
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: N2.AA-07.01
al 04
ESPECIFICACIN
Unidades de refrigeracin equipadas con compresores hermticos destinadas a
aplicaciones de alta, mediana y baja temperatura.
UNIDADES CONDENSADORAS
Los condensadores debern ser diseados para operar en ambientes de alta
temperatura y humedad.
Los motores debern estar cubiertos y protegidos para un correcto funcionamiento en
ambientes hmedos y con presencia de suciedad.
Todas las unidades estarn pintadas con pintura electrosttica probada para
resistencia a la corrosin.
Todos los compresores tendrn vlvulas de servicio de succin y descarga para un
adecuado mantenimiento y operacin.
Los ventiladores de las unidades debern contar con rejillas metlicas con una
aplicacin de pintura electrosttica.
Todas las unidades irn montadas sobre soportes anti vibracin apropiados.
Los presostatos de alta y baja presin sern ajustables o del tipo sellado para evitar
escapes y/o alteraciones del set-point.
Todas las unidades contarn con su respectivo tanque de lquido y vlvula de servicio.
Los compresores contarn con un visor para verificar el nivel de aceite del carter y
adems vlvula de servicio tipo Schroeder para la toma de presin y recarga de aceite.
Todos los compresores contarn con protector trmico interno bimetlico.
Las unidades incluirn una caja elctrica de fcil acceso con kit de arranque completo
(capacitores y rel volumtrico)
UBICACIN
Las unidades condensadoras debern estar correctamente ubicadas en reas bien
ventiladas, en la cual el flujo de aire no tenga restricciones, es importante evitar
retornos en el flujo de aire, adems deber estar apropiadamente protegida contra la
intemperie.
CONEXIONES
Para el circuito de tuberas se utilizar exclusivamente tubera de cobre limpia y
deshidratada.
La tubera del compresor deber tener el grado de libertad suficiente en las 3
direcciones a fin de absorber vibraciones y evitando quedar muy cerca del compresor.
pg. 300
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
Los tramos de tubera tendern a ser simples y cortos, evitando puntos bajos en los
que el aceite pudiera acumularse.
En la lnea de succin las secciones horizontales deben tener un declive del 1% para
abajo en direccin al compresor.
Cuando el evaporador est situado por encima del compresor, se instalarn las lneas
de succin de manera que la refrigeracin lquida no migre para el compresor durante
el ciclo de parada.
La lnea de succin deber estar debidamente aislada para evitar condensacin y
sobrecalentamiento.
Todas las unidades contarn con filtros secadores correctamente dimensionados para
evitar una cada de presin exagerada en la lnea de lquido.
UNIDADES EVAPORADORAS
La unidad evaporadora ser de bajo perfil con una altura mxima de 14 pulgadas.
Deber contar con soportes para ser instalada bajo techo.
Los paneles laterales sern fcilmente removibles para tareas de mantenimiento as
como la bandeja de drenaje.
Los paneles sern construidos con lmina de aluminio texturada
El intercambiador de calor ser construido con tubera de cobre y aletas de aluminio.
Los motores de los ventiladores sern del tipo permanentemente sellado y con
proteccin trmica, cableados en fbrica.
Todos los modelos de evaporadores tendrn instaladas vlvulas para verificacin de la
presin de succin y el control de desempeo.
Todos los motores de los ventiladores sern de alta eficiencia y bajo consumo de
energa.
En cada unidad existirn rejillas metlicas de proteccin sobre las hlices de los
ventiladores las cuales debern estar recubiertas con pintura electrosttica.
El panel de conexin elctrica de las resistencias de deshielo estar ubicado en el
lateral opuesto de las conexiones de refrigerante de la unidad, permitiendo un
excelente acceso para mantenimiento.
pg. 301
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
DETALLE DE ESPECIFICACIONES
RUBRO
CANTIDAD
UNIDAD EVAPORADORA
Tipo de defrost
DIMENSIONES
frente
fondo
alto
CAPACIDAD
@25 F temp. Evap
Temp. evaporacin
SUMINISTRO ELECTRICO
Voltaje
VENTILADOR
No. De ventiladores
alcance
CONEXIONES
refrigerante
lquido
gas
drenaje
UNIDAD CONDENSADORA
Rango de operacin
potencia
presin de diseo baja
presin de diseo alta
suministro elctrico
plg.
plg.
plg.
BTU/hr.
C
volt/frec/ph
ft.
plg.
plg.
plg.
F
watt
psig
psig
volt/frec/ph
AA-07.01
1
AA-07.02
1
AA-07.03
4
AA-07.04
3
aire
aire
resistencia
resistencia
38
12-1/4
13 1/2
33
12-1/4
13 1/2
54
12-1/4
13-1/2
81
12-1/4
13-1/2
7500
0
6000
0
10200
0
16100
-15
230/60/1
115/60/1
230/60/1
230/60/1
2
18
1
15
2
18
4
22
R507
1/2
7/8
1
R507
1/2
7/8
1
R507
1/2
7/8
1
R404A
1/2
1-1/8
1
-10 a 45
1300
181
450
208/60/1
-10 a 45
1300
181
450
115/60/1
-10 a 45
1700
181
450
208/60/1
-10 a 45
2800
181
450
208/60/1
pg. 302
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO: 9580-9581
ESPECIFICACIN
Los equipos de calentamiento para ductos tendrn como elemento de calefaccin
resistencias elctricas y estarn certificados por UL adems de cumplir con todos los
requisitos establecidos en el cdigo NEC
Las estructuras y cubiertas de los equipos sern construidas en lmina de acero
galvanizada de calibre 20 o superior.
Los equipos contarn con un panel de control elctrico construido por separado en
lmina de acero galvanizado calibre 20 o superior.
Todo el cableado elctrico ser realizado en fbrica y cada unidad contendr impreso
el diagrama elctrico respectivo.
La unin con los ductos del circuito de aire acondicionado ser bridada con un ancho
de brida de 1 pulgada de acuerdo a las normas SMACNA
PROTECCION POR SOBRECALENTAMIENTO
Los equipos contarn con mnimo dos dispositivos que supriman el suministro de
energa en caso de sobrecalentamiento y su operacin ser en cascada es decir el
segundo dispositivo actuar en caso de falla del primero.
PROTECCCION POR SOBRECARGA DE CORRIENTE
Todos los equipos contarn con dispositivos para proteccin en caso de sobrecarga de
corriente del tipo fusible o breakers limitado a 60 amps mximo.
PROTECCION ANTE FALLO DEL FLUJO DE AIRE
Se requiere que todos los equipos tengan un esquema de control y los dispositivos
adecuados para que el equipo no sea energizado si el ventilador no lo est y adems
no existe flujo de aire en el ducto tal como recomiendan las normas UL y NEC
PROTECCION DE TRANSFORMADORES
Todos los transformadores debern contar con dispositivos de proteccin por
sobrecarga.
SWITCH DE DESCONEXION
Todos los equipos contarn con un dispositivo de desconexin remoto instalado cerca
de cada equipo.
INSTALACION
Todos los procedimientos de instalacin se harn cumpliendo con los estndares
establecidos por SMACNA en lo referente a ductos y UL y NEC en lo referente a la
instalacin elctrica.
pg. 303
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
En el lugar de la instalacin siempre se deber prever el espacio libre para las tareas
de mantenimiento.
Se deber verificar que el sentido del flujo del equipo corresponda al del ducto.
El equipo deber estar instalado mnimo a 4 pies de distancia de la unidad manejadora
de aire.
El equipo deber contar con una separacin no menor a 4 pies de cualquier dispositivo
de la red que pudiera producir turbulencias tales como, codos, transiciones etc.
El ducto podr ser reforzado de ser necesario para prevenir deflexin.
DETALLE DE UNIDADES
CANTIDAD
RUBRO
9580
9581
65
22
CAUDAL
(cfm)
600
1050
DIMENSIONES
(in x in.)
12x8
16x10
POTENCIA
(Kw)
2.9
5.08
ENERGIA
(volt/fr/ph)
208/60/3
460/60/3
pg. 304
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
CODIGO:N2.AA-07.06
ESPECIFICACIN
Unidad de aire acondicionado tipo auto contenida de precisin y enfriada por aire para
aplicaciones de cuartos de control o computadores data centers.
El equipo deber contar con las siguientes caractersticas:
Controlar de manera precisa la temperatura, humedad y calidad de filtrado del
aire
Su tamao deber ser al mnimo adecuado para ser instalado dentro del Data
Center.
Acceso por la parte frontal a todos los componentes crticos del equipo.
Controles electrnicos de precisin que permitan una ptima eficiencia del
sistema.
Uso de compresores con tecnologa inverter y empleo de refrigerantes
ecolgicos del tipo R407 C
El sentido del flujo ser del tipo Downflow
Todo el circuito de tuberas de refrigeracin y cableado elctrico deber ser
montado y probado en fbrica.
La cabina ser de lmina de acero con recubrimiento apropiado a prueba de
corrosin.
Los ventiladores debern ser del tipo centrifugo de alabes orientados hacia
adelante.
El motor deber estar montado sobre una base ajustable que permita un fcil
acceso para las tareas de servicio Los motores elctricos debern tener
rodamientos del tipo cojinetes de bolas sellados y permanentemente
lubricados.
Todos los elementos de sujecin debern ser de materiales resistentes a la
corrosin
Las poleas del ventilador debern contar con dispositivos que permitan regular
la tensin de las bandas
Los equipos debern instalarse con bandas del tipo static-free
El suministro de energa ser de 220/3/60.
pg. 305
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
DETALLE DE ESPECIFICACIONES
CAPACIDAD (29C, 33%RH)
Total
BTU/HR.
Sensible
BTU/HR.
CAPACIDAD (24C, 45%RH)
Total
BTU/HR.
Sensible
BTU/HR.
VENTILADOR
Caudal
cfm
potencia
hp
presin esttica
pulg H2O
EVAPORADOR
Area
ft2
# de filas
velocidad de flujo
fpm
FILTROS
dimensin
mm
tipo
HUMIDIFICADOR
Tipo
capacidad
lb/hr.
67,900.00
67,900.00
60,500.00
56,600.00
2,800.00
2.00
0.30
6.67
4.00
405.00
724*749
MERV 8
infrarrojo
11.00
pg. 306
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
al 11
CANTIDAD POTENCIA
LONGITUD
(watt)
(In.)
AA-11.09
11
100
17
AA-11.10
100
22
AA-11.11
100
36
pg. 307
ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL
RESPONSABLE: F.CH.
pg. 308