You are on page 1of 308

MINISTERIO DE SALUD PBLICA

HOSPITAL GENERAL
GUASMO SUR - ZOFRAGUA
GUAYAQUIL - PROVINCIA DE GUAYAS
MINISTERIO DE SALUD PBLICA

ESPECIFICACIONES TECNICAS
SISTEMA DE AIRE
ACONDICIONADO Y
VENTILACION MECANICA

INTERPLAN
COMPAIA GENERAL DE CONSULTORES Cia. LTDA.
QUITO-ECUADOR

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Contenido
RUBRO: UNIDAD CONDENSADORA DE VOLUMEN VARIABLE ............................. 5
CONTENIDO DEL RUBRO ................................................................................... 5
DETALLE DE ESPECIFICACIONES .................................................................... 9
RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DE TIPO
CASSSETTE .............................................................................................................. 13
CONTENIDO DEL RUBRO ................................................................................. 13
ESPECIFICACIN .............................................................................................. 17
RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DEL TIPO FAN COIL
................................................................................................................................... 20
CONTENIDO DEL RUBRO ................................................................................. 20
ESPECIFICACIN .............................................................................................. 22
RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO RUEDA ENTALPICA
................................................................................................................................... 27
CONTENIDO DEL RUBRO ................................................................................. 27
ESPECIFICACIN .............................................................................................. 28
RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO PLACAS EXTERIOR
................................................................................................................................... 37
CONTENIDO DEL RUBRO ................................................................................. 37
ESPECIFICACIN .............................................................................................. 39
RUBRO: VENTILADOR DE EXTRACCION TIPO HONGO DE ALUMINIO ................ 45
CONTENIDO DEL RUBRO ................................................................................. 45
ESPECIFICACION .............................................................................................. 47
RUBRO: VENTILADOR DE EXTRACCION CUADRADO EN LINEA DE ALETAS
HACIA ATRAS ........................................................................................................... 49
CONTENIDO DEL RUBRO ................................................................................. 49
ESPECIFICACIN .............................................................................................. 51
RUBRO: VENTILADOR DE EXTRACCION TIPO VEKTOR ALTA PLUMA DE
DESCARGA HACIA ARRIBA .................................................................................... 54
CONTENIDO DEL RUBRO ................................................................................. 54
ESPECIFICACIONES.......................................................................................... 56
RUBRO: VENTILADOR DE SUMINISTRO TIPO CENTRIFUGO DOBLE ENTRADA 57
CONTENIDO DEL RUBRO ................................................................................. 57
ESPECIFICACION .............................................................................................. 58
pg. 2

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO: VENTILADOR DE EXTRACCION CUADRADO EN LINEA DE ALETAS


HACIA ATRAS ........................................................................................................... 60
CONTENIDO DEL RUBRO ................................................................................. 60
ESPECIFICACION .............................................................................................. 62
RUBRO: VENTILADOR DE EXTRACCION TIPO PLAFON ....................................... 63
CONTENIDO DEL RUBRO ................................................................................. 63
ESPECIFICACIN .............................................................................................. 64
RUBRO: UNIDADES MANEJADORAS DE DOBLE PARED DE EXPANSION
DIRECTA.................................................................................................................... 65
CONTENIDO DEL RUBRO ................................................................................. 65
DESCRIPCION GENERAL.................................................................................. 66
RUBRO: DIFUSORES, REJILLAS Y LOUVERS DE VENTILACION ....................... 275
CONTENIDO DEL RUBRO ............................................................................... 275
ESPECIFICACIN ............................................................................................ 275
RUBRO: DUCTO FLEXIBLE CON/SIN AISLAMIENTO ........................................... 277
CONTENIDO DEL RUBRO ............................................................................... 277
ESPECIFICACIN ............................................................................................ 277
RUBRO: TUBERIA DE COBRE Y ACCESORIOS ................................................... 279
CONTENIDO DEL RUBRO ............................................................................... 279
ESPECIFICACIN ............................................................................................ 279
RUBRO: REFRIGERANTE ADICIONAL R-410A ..................................................... 283
CONTENIDO DEL RUBRO ............................................................................... 283
ESPECIFICACIN ............................................................................................ 283
RUBRO: CABLEADO DE FUERZA CONTROL ....................................................... 284
CONTENIDO DEL RUBRO ............................................................................... 284
ESPECIFICACIN ............................................................................................ 284
RUBRO: DUCTOS DE TOL GALVANIZADO CON Y SIN AISLAMIENTO TERMICO
................................................................................................................................. 286
CONTENIDO DEL RUBRO ............................................................................... 286
ESPECIFICACIN DUCTOS............................................................................. 286
RUBRO: FILTROS DE AIRE ACONDICIONADO ..................................................... 294
CONTENIDO DEL RUBRO ............................................................................... 294
ESPECIFICACIN ............................................................................................ 294
pg. 3

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO: ESPECIFICACIONES COMPLEMENTARIAS ........................................... 296


CONTENIDO DEL RUBRO ............................................................................... 296
ESPECIFICACIN ............................................................................................ 296
RUBRO: EQUIPO DE REFRIGERACION PARA CUARTO FRIO ............................ 300
CONTENIDO DEL RUBRO ............................................................................... 300
ESPECIFICACIN ............................................................................................ 300
RUBRO: EQUIPO DE CALENTAMIENTO DE AIRE PARA DUCTOS ..................... 303
CONTENIDO DEL RUBRO ............................................................................... 303
ESPECIFICACIN ............................................................................................ 303
RUBRO: EQUIPO DE AIRE ACONDICIONADO DE PRECISION TIPO AUTO
CONTENIDO ENFRIADO POR AIRE ....................................................................... 305
CONTENIDO DEL RUBRO ............................................................................... 305
ESPECIFICACIN ............................................................................................ 305
RUBRO: LAMPARA ULTRAVIOLETA PARA INSTALACION EN DUCTO DE
EXTRACCION .......................................................................................................... 307
CONTENIDO DEL RUBRO ............................................................................... 307
DETALLES DEL RUBRO ................................................................................... 307

pg. 4

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: UNIDAD CONDENSADORA DE VOLUMEN VARIABLE
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-01.01

al 14

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Cada unidad condensadora tendr como mnimo:
2 compresores del tipo scroll de los cuales por lo menos uno ser del tipo
INVERTER
Motor del ventilador tipo INVERTER
Intercambiador de calor
Circuito de sub-enfriamiento
Vlvula de expansin electrnica EEV
Vlvula solenoide
Vlvula de cuatro vas
Filtro
Separador de aceite
Acumulador
Mdulo de control elctrico
Tambin debern contar con un circuito para bypass de gases calientes, que
contenga:
Switch de presin
Sensor de presin alta
Sensor de baja presin
Proteccin contra sobre carga de corriente
Proteccin de fases
Este circuito deber estar integrado al compresor como una proteccin en caso de
malfuncionamiento
Compresores
Todas las unidades externas tendrn suministro elctrico trifsico y estarn equipadas
con compresores hermticos del tipo scroll con tecnologa INVERTER y digitalmente
controlados con capacidad de modular su capacidad de carga entre 15-150 Hz. En
incrementos de 0.5 Hz.
El compresor operar con un dispositivo de inyeccin de vapor de refrigerante, con
bajo consumo de energa y bajo nivel de ruido, estar diseado para manejo de varios
evaporadores, y deber tener un control digital de carga por medio de una vlvula
solenoide digital instalada para hacer un by-pass entre la succin y descarga de
refrigerante en el compresor, proceso que controla el tiempo de encendido y apagado
de la vlvula y el flujo de refrigerante de acuerdo a la diferencia de temperatura
interior, para conseguir un funcionamiento entre el 10% al 100%
pg. 5

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Deber poseer dispositivos para auto diagnstico y verificacin del cableado de


control.
Las conexiones de la tubera de refrigerante al compresor se realizaran mediante
juntas soldadas
La unidad deber tener dispositivos aislantes de vibracin y de ruido hacia el exterior
El nivel de ruido operando a plena carga no deber exceder los 63.5 dBA.
Intercambiadores de Calor
Los serpentines de los intercambiadores de calor sern construidos con aletas
dispuestas sobre la tubera de cobre y recubiertas con una capa protectora tipo anticorrosin y repelente al agua.
Las unidades condensadoras sern fabricadas en condiciones de trabajar dentro de un
rango de temperaturas ambiente de 14-122F
Ventiladores
Todas las unidades externas debern contar con ventiladores para forzar la circulacin
del aire a travs del condensador estos equipos debern ser de hlice, tipo directo y
con velocidad variable, tambin debern contar con rodamientos permanentemente
lubricados y su velocidad variable no deber exceder las 1100 rpm, igualmente sern
provistos de rejillas protectoras en el lado exterior para evitar el contacto accidental
con las partes en movimiento.
El flujo de descarga de los ventiladores ser preferiblemente vertical de abajo hacia
arriba y una presin esttica de 0.32 plg. H2O
Cabinas
El material del cual estarn construidas los gabinetes ser lmina de acero
galvanizado con un recubrimiento de pintura en polvo resistente a la corrosin e
intemperie, Los gabinetes tienen en el frente louvers estampados para proteger al
serpentn del condensador y facilitar el mantenimiento.
Al remover el panel frontal se dar fcil acceso a las instalaciones de control,
compresor, motor del ventilador, sin afectar el normal funcionamiento de la unidad.
Todos los componentes internas de las unidades externas sean estas tuberas,
equipos, etc, debern ser instaladas verificados y probadas en fbrica.
Circuito de Refrigerante
El circuito de refrigerante de las unidades deber usar refrigerante R410A y la unidad
adems ser suministrada con estrangulador de refrigerante, vlvulas check,
separador de aceite, acumulador, vlvula reversible de 4 vas, vlvula de expansin
controlada electrnicamente, puertos de carga en alta y baja presin, switch de
seguridad de presin alta, y vlvulas de servicio as como todos aquellos dispositivos
que permitan una operacin eficiente y automtica.
Sistema de Control
Los circuitos de control entre las unidades del sistema debern ser a 24 VDC usando
conductores dobles trenzados y apantallados para el protocolo de comunicaciones RS485.

pg. 6

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Estas unidades debern ser controladas por microprocesador y este ser capaz de
permitir: la proteccin de los componentes, capacidad de arranque-parada suave y
controlar la temperatura y presin del refrigerante as como del ambiente controlado
Todas las unidades debern contar con dispositivos de control de flujo del aceite que
ayuden a prevenir la mezcla de aceite y refrigerante en el lado de succin del
compresor.
Debern contar con sistemas de control que monitoreen el nivel de aceite al interior del
compresor y no permitan que el compresor opere a bajos niveles de aceite.
Sistema Elctrico
Todas las unidades debern estar en condiciones de suministro elctrico de 460 V, 60
Hz, 3Ph, igualmente estarn en capacidad de operar con variaciones de voltaje de
10% del voltaje establecido y contarn con un dispositivo de proteccin para
sobrecarga.
Todos los componentes elctricos, electrnicos o mecnicos necesarios y que formen
parte de las unidades externas debern ser montados en fbrica.
El cableado en todas las unidades deber estar acorde a las normas NEC.
Cumplimiento de estndares
Todas las unidades externas debern contar con certificacin de cumplimiento del
ANSI.AHRI.Standard 1230-2010
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garantas
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 7

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 8

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

DETALLE DE ESPECIFICACIONES
AA-01.01

RUBRO

AA-01.03

AA-01.04

16

UC-72

UC-96

UC-120

UC-144

72,000

96,000

120,000

144,000

scroll inverter

scroll inverter

scroll inverter

scroll inverter

Kw x n

4.96
PVE

6.13
PVE

6.13
PVE

4.96x2
PVE

23-120

23-120

23-120

23-120

Hlice

hlice

hlice

hlice

CANTIDAD
UNIDAD
CAPACIDAD
BTU/hr.

Certificada

AA-01.02

COMPRESOR
tipo
cantidad
potencia
aceite
RANGO DE OPERACIN
Rango de enfriamiento
VENTILADOR
tipo
W

400x1

620x2

620x2

620x2

cfm

7239.00

9132.00

9132.00

9535.00

in H2O

0.31

31.00

31.00

0.31

liquido

plg

3/8

3/8

1/2

1/2

gas
PESO

plg

3/4

7/8

1-1/8

1-1/8

peso neto

kg

190.00

278.00

278.00

293.00

dBA

60/81

61/81

61/81

62/83

potencia x n
caudal
SP
TUBERIAS

Nivel de ruido Pres/Por.


REFRIGERANTE

R410A

R410A

R410A

R410A

kg

5.50

7.40

7.40

8.70

Volts/ph./ Hz.

460/3/60

460/3/60

460/3/60

460/3/60

tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.

pg. 9

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO

AA-01.05

AA-01.06

AA-01.07

AA-01.08

12

22

12

10

UC-168

UC-192

UC-216

UC-240

168,000

192,000

216,000

240,000

scroll inverter
2
4.96+6.13
PVE

scroll inverter
2
4.96+6.13
PVE

scroll inverter
3
14.88
PVE

scroll inverter
2
12.26
PVE

23-120

23-120

23-120

23-120

hlice
400+620x2
16421.00
0.31

hlice
400+620x2
16421.00
0.31

hlice
400+620x2
16774.00
0.31

hlice
2480.00
18364.00
0.31

pulg

5/8
1-1/8

5/8
1-1/8

5/8
1-1/8

5/8
1-1/8

kg

463.00

463.00

483.00

546.00

kg

R410A
12.90

R410A
12.90

R410A
14.20

R410A
14.30

Volts/ph./ Hz.

460/3/60

460/3/60

460/3/60

460/3/60

CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR

BTU/hr.

tipo
cantidad
potencia
aceite
RANGO DE OPERACIN

Kw x n

Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS

W
cfm
in H2O
pulg

liquido
gas
PESO
peso neto
nivel de ruido Pres/Pot.
REFRIGERANTE

dBA

tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.

RESPONSABLE: F.CH.

pg. 10

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

AA-01.09

AA-01.10

AA-01.11

UC-264

UC-288

UC-312

UC-336

264,000

288,000

312,000

336,000

scroll inverter
3
16.05
PVE

scroll inverter
4
19.84
PVE

scroll inverter
4
21.01
PVE

scroll inverter
4
21.01
PVE

23-120

23-120

23-120

23-120

hlice
2480.00
18667.00
0.31

hlice
2480.00
19070.00
0.31

hlice
2900.00
25956.00
0.31

hlice
2880.00
25906.00
0.31

pulg

3/4
1-3/8

3/4
1-3/8

3/4
1-3/8

3/4
1-3/8

kg

566.00

586.00

761.00

761.00

kg

R410A
16.10

R410A
17.40

R410A
21.60

R410A
21.60

Volts/ph./ Hz.

460/3/60

460/3/60

460/3/60

460/3/60

RUBRO
CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR

BTU/hr.

tipo
cantidad
potencia
aceite
RANGO DE OPERACIN

Kw x n

Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS

W
cfm
in H2O
pulg

liquido
gas
PESO
peso neto
Nivel de ruido Pres/Pot.
REFRIGERANTE

AA-01.12

dBA

tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.

RESPONSABLE: F.CH.

Capacidad Certificada bajo ANSI.AHRI Standard 1230

pg. 11

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


AA-01.13

RUBRO

AA-01.14

UC-96.1

UC-53

96000

53000

scroll inverter
2
4.96*2
Pve

scroll inverter
1
4.12
Poe

23-120

23-120

hlice
620*2
9182
0.31

hlice
125*2
3884

3/8
7/8

3/8

dBA

278
61/81

103
53

kg

R410A
7.4

R410A
3.2

Volts/ph./ Hz.

220/3/60

220/3/60

CANTIDAD
UNIDAD
CAPACIDAD
Certificada
COMPRESOR

BTU/hr.

tipo
cantidad
potencia
aceite
RANGO DE OPERACIN

Kw x n

Rango de enfriamiento
VENTILADOR
tipo
potencia x n
caudal
SP
TUBERIAS

W
cfm
in H2O
pulg

liquido
gas
PESO

pulg
kg

peso neto
Nivel de ruido Pres/Pot.
REFRIGERANTE
tipo
carga
SUMINISTRO ELECTRICO
Voltaje, fase, frec.

RESPONSABLE: F.CH.

Capacidad certificada bajo ANSI.AHRI 1230

pg. 12

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DE TIPO CASSSETTE
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-02.01

al 11

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Carcasa
La caja que contiene a esta unidad ser construida con lmina de acero galvanizado y
con la aplicacin de un recubrimiento resistente a la corrosin y humedad.
En la parte inferior contar con una rejilla que permita el paso del aire que ingresa al
serpentn evaporador.
Evaporador
Los serpentines de evaporacin estarn construidos con tubera de cobre con aletas
de aluminio que tengan aplicado un recubrimiento repelente de la humedad.
Cada unidad tendr un mnimo de dos hileras de serpentines y sern probadas mnimo
a 400 psig de presin en la fbrica.
La unidad podr tener una o cuatro salidas del aire de suministro las cuales estarn
dispuestas al costado de la rejilla de ingreso del aire de retorno, las salidas de aire
contarn con vanos o aletas motorizadas de tal manera que permitan variar la
direccin del flujo del aire para lograr una mejor distribucin de temperaturas en el
ambiente.
Ventilador
Los ventiladores sern de operacin silenciosa, construidos en una estructura
unificada de aspas y difusor de aire en 3 dimensiones para mejorar la propagacin del
aire dentro del equipo.
Los ventiladores sern balanceados esttica y dinmicamente en fbrica.
Los motores sern monofsicos 220/1/60, y tendrn proteccin trmica de sobrecarga,
sern de acople directo al ventilador y se montarn sobre bases amortiguadores de
caucho a prueba de vibraciones
Se suministrar motores con variacin de velocidad controlados por
microprocesadores.
Estos motores sern del tipo BLDC con rodamientos sellados y permanentemente
lubricados.
Refrigerante
La unidad estar diseada y construida para trabajar con refrigerante R410A
El circuito de refrigerante deber ser probado a presin en fbrica y mantendr una
carga de gas inerte hasta el momento de su instalacin.
Control de Flujo de Refrigerante
El control del flujo de refrigerante en esta unidad ser realizado mediante vlvulas de
expansin controladas electrnicamente del tipo EEV
pg. 13

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 14

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Bomba de condensado interna


Todos los acondicionadores tipo Consola tendrn un panel de drenaje construido en
el mismo material del equipo, con un forro de espuma resistente al fuego y ubicado
bajo el serpentn de la evaporadora.
La bomba de drenaje estar en capacidad de elevar el condensado hasta 60 cm desde
la parte inferior de la unidad.
Adicionalmente deber contar con un switch de seguridad que detenga la operacin de
la unidad en el caso que el nivel de condensado rebase la bandeja correspondiente.
Suministro elctrico
Esta unidad trabajar bajo condiciones de suministro elctrico de 208-230 V.
monofsico a 60Hz. Con variaciones de 10% incluyendo una proteccin por
sobrecarga.
Componentes internos.
Todos los componentes internos de las unidades tales como: componentes de control
elctricos, circuitos impresos, termistores, sensores y los bloques de terminales
debern ser instalados en fbrica.
El sistema podr ser operado a travs de un control remoto.
Filtro de aire.
La unidad contar con un filtro de aire de retorno ubicado en la parte inferior de la
misma el cual deber ser de fcil acceso y con la posibilidad de ser lavado
peridicamente con agua y detergente
Control Remoto
El microprocesador que realiza las tareas de control deber estar en capacidad de
iniciar arranques suaves y controlar variables del refrigerante tales como: presin,
temperatura descongelacin y control de la temperatura en el ambiente.
Para el control de este sistema se usar un sistema remoto con pantalla de cristal
lquido (LCD). El cual podr ser configurado de acuerdo a los requerimientos de uso
del hospital.
Para cada equipo se podr configurar las siguientes opciones.
Control de las rejillas de distribucin del aire.
Control de encendido remoto del equipo.
Programacin durante las 24 horas del da.
Programacin de temperatura durante las 24 horas.
Conservacin de los parmetros de control establecidos despus de una falla
de energa.
Auto diagnstico, que facilita el proceso de mantenimiento
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor

pg. 15

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El proveedor deber evidenciar que comercializa en Ecuador al menos durante los


cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garantas
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 16

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACIN
UNIDADES TIPO CASSETE UNA VIA
RUBRO
CAPACIDAD
UNIDAD
CANTIDAD

BTU/hr.

Energa
Volt/ph/Hz.
Potencia
watt
VENTILADOR
Tipo
Potencia x n
watt
Caudal
cfm
TUBERIAS
Lquido
pulg
Gas
pulg.
drenaje
mm
Nivel de ruido
dBA
REFRIGERANTE
Tipo
mtodo de
control
Peso
kg
DIMENSIONES
ancho/alto/fondo
mm

AA-02.01
7,500
C1-07
58

AA-02.02
9,500
C1-09
24

AA-02.03
12,000
C1-12
33

208/1/60
40

208/1/60
45

208/1/60
50

crossflow
20x1
247/211/176

crossflow
20x1
247/211'176

crossflow
20x1
282/247/211

1/4
1/2
26
27/25/23

1/4
1/2
26
29/27/24

1/4
1/2
26
35/31/27

R410A

R410A

R410A

EEV

EEV

EEV

10.50

10.50

10.50

1164/212/478

1164/212/478

1164/212/478

pg. 17

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

UNIDADES TIPO CASSETE 4 VIAS

RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD
UNIDAD

AA-02.07

AA-02.08

AA-02.09

AA-02.10

AA-02.11

18,000

24,000

30,000

36,000

48,000

69

C4-18

C4-24

C4-30

C4-36

C4-48

Energa

Volt/ph/Hz.

208/1/60

208/1/60

208/1/60

208/1/61

208/1/62

Potencia

watt

32

40

65

75

95

turbo fan

turbo fan

turbo fan

turbo fan

turbo fan

65x1

65x1

97x1

97x1

97x1

VENTILADOR
Tipo
Potencia x n

watt

Caudal

cfm

547/494'423 618/565/494 776/688'600 847/776/706 1024/953/847

TUBERIAS
Lquido

pulg

1/4

1/4

3/8

3/8

3/8

Gas

pulg.

1/2

1/2

5/8

5/8

5/8

drenaje

mm

32

32

32

32

32

Nivel de ruido

dBA

34/333/31

36/35/34

39/34/30

40/37/33

44/42/39

R410A

R410A

R410A

R410A

R410A

EEV

EEV

EEV

EEV

EEV

15.00

15.00

18.50

18.50

18.50

REFRIGERANTE
Tipo
mtodo de
control
Peso

kg

DIMENSIONES
ancho/alto/fondo

mm

840/204/840 840/204/840 898/357/898 898/357/898

898/357/898

pg. 18

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

UNIADES TIPO CASSETE MIINI 4 VIAS


RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD

AA-02.04

AA-02.05

AA-02.06

9,500

12,000

18,000

49

43

122

CM-09

CM-12

CM-18

Energa

Volt/ph/Hz.

208/1/60

208/1/60

208/1/60

Potencia

watt

24

28

36

UNIDAD

VENTILADOR
Tipo

Turbo fan

Turbo fan

Turbo fan

Potencia x n

watt

65x1

65x1

65x1

Caudal

cfm

353/300'264

370/335'282

459/388'335

Lquido

pulg

1/4

1/4

1/4

Gas

Pulg.

1/2

1/2

1/2

TUBERIAS

drenaje

mm

25

25

32

Nivel de ruido

dBA

34/30/26

36/34/31

40/37/34

R410A

R410A

R410A

REFRIGERANTE
Tipo
mtodo de control
Peso

EEV

EEV

EEV

kg

12.00

12.00

12.00

mm

575x250x575

575x250x575

575x250x575

DIMENSIONES
ancho/alto/fondo

pg. 19

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: UNIDAD EVAPORADORA DE VOLUMEN VARIABLE DEL TIPO FAN COIL
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-02.12

al 21

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Estas especificaciones corresponden a unidades evaporadoras de aire acondicionado
del tipo FAN COIL y cada uno de sus componentes.
Caja
La unidad ser diseada y construida para ser instalada dentro del ambiente de cielos
falsos, el material que estar construida es de lmina de acero galvanizado recubierto
con un acabado resistente a la humedad y corrosin.
Las superficies fras debern estar recubiertas por material aislante trmico.
La caja contar con soportes adecuados instalados en fbrica en cada esquina que
permitan soportar el peso de la misma y su instalacin soportada desde la losa
superior.
Ventilador
La unidad contar con dos ventiladores centrfugos montados sobre el mismo eje a
cada lado de un motor elctrico del tipo BLDC con rodamientos sellados y
permanentemente lubricados.
El motor del ventilador estar montado sobre bases anti vibracin de caucho o
similares.
La velocidad del ventilador ser controlada a travs de un microprocesador que
emplear un algoritmo de control digital directo que provea un mnimo de tres
velocidades pre-programadas HI-MED-LOW las cuales podrn ser modificadas de su
condicin de fbrica de acuerdo a las necesidades que se pudieren presentar en el
montaje.
Evaporador
Los serpentines de evaporacin estarn construidos con tubera de cobre con aletas
de aluminio que tengan aplicado un recubrimiento repelente de la humedad.
Cada unidad tendr un mnimo de dos hileras de serpentines y sern probadas mnimo
a 400 psig de presin en fbrica
Filtro de aire
La unidad deber tener instalado un filtro del aire de retorno, lavable y fcilmente
desmontable.
Circuito de control
La unidad estar provista de un sistema de control basado en microprocesador, tendr
un dispositivo tipo termistor montado en el lado del aire de retorno, todos los
parmetros de operacin excluyendo los de programacin de eventos sern
guardados en la memoria no voltil del circuito de microprocesador.
pg. 20

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El circuito de control estar en condiciones de realizar las siguientes funciones: auto


diagnstico, arranque automtico luego de falla en el suministro elctrico y arranque
de prueba.
El circuito de control ser capaz de recibir seal de temperatura tanto del termistor
como de un control remoto cableado.
Componentes internos.
Todos los componentes internos de las unidades tales como: componentes de control
elctricos, circuitos impresos, termistores, sensores y los bloques de terminales
debern ser instalados en fbrica.
Suministro elctrico
Esta unidad trabajar bajo condiciones de suministro elctrico de 208-230 V.
monofsico a 60Hz. Con variaciones de 10% incluyendo una proteccin por
sobrecarga
Bomba de drenaje de condensado interna
Todos los acondicionadores tipo Consola tendrn un panel de drenaje construido en
el mismo material del equipo, con un forro de espuma resistente al fuego y ubicado
bajo el serpentn de la evaporadora.
La bomba de drenaje estar en capacidad de elevar el condensado hasta 60 cm desde
la parte inferior de la unidad.
Adicionalmente deber contar con un switch de seguridad que detenga la operacin de
la unidad en el caso que el nivel de condensado rebase la bandeja correspondiente
Control de Flujo de Refrigerante
El control del flujo de refrigerante en esta unidad ser realizado mediante vlvulas de
expansin controladas electrnicamente del tipo EEV
Refrigerante
La unidad estar diseada y construida para trabajar con refrigerante R410A
El circuito de refrigerante deber ser probado a presin en fbrica y mantendr una
carga de gas inerte hasta el momento de su instalacin
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
pg. 21

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

ESPECIFICACIN
UNIDADES TIPO FANCOIL BAJA PRESION
RUBRO
CAPACIDAD

AA-02.12
BTU/hr.

12,000

CANTIDAD

FL-12

UNIDAD
Energa

Volt/ph/Hz.

208/1/60

Potencia

watt

75

VENTILADOR
Tipo

scirocco

Potencia x n

watt

60x1

Caudal

cfm

353/300/247

Lquido

pulg

1/4

Gas

pulg.

1/2

drenaje

mm

32

Nivel de ruido

dBA

29/28/27

TUBERIAS

REFRIGERANTE
Tipo
mtodo de
control
Peso

R410A
EEV
kg

24.50

mm

900/199/600

DIMENSIONES
ancho/alto/fondo

pg. 22

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

UNIDADES TIPO FANCOIL DE MEDIA PRESION


RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD
UNIDAD

AA-02.13

AA-02.14

AA-02.15

18,000

24,000

30,000

24
FM-18

5
FM-24

2
FM-30

Energa

Volt/ph/Hz.

208/1/60

208/1/61

208/1/62

Potencia

watt

165

220

260

scirocco

scirocco

scirocco

VENTILADOR
Tipo
Potencia x n

watt

124x1

124x1

180x1

Caudal

cfm

51/459'406

653/600/547

882/812/700

Lquido

pulg

1/4

3/8

3/8

Gas

pulg.

1/2

5/8

5/8

drenaje

mm

32

32

32

Nivel de ruido

dBA

35/33/31

39/35/31

40/37/34

R410A

R410A

R410A

EEV

EEV

EEV

kg

29

29

37

mm

900/260/480

900/260/480

1150/320/480

TUBERIAS

REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo

pg. 23

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD
UNIDAD

RESPONSABLE: F.CH.

AA-02.16

AA-02.17

36,000

48,000

6
FM-36

10
UI-14

Energa

Volt/ph/Hz.

208/1/63

208/1/64

Potencia

watt

290

430

scirocco

scirocco

VENTILADOR
Tipo
Potencia x n

watt

180x1

218x1

Caudal

cfm

953/882/812

1236/1165/1059

Lquido

pulg

3/8

3/8

Gas

pulg.

5/8

5/8

TUBERIAS

drenaje

mm

32

32

Nivel de ruido

dBA

41/40/38

42/39/36

R410A

R410A

EEV

EEV

kg

37

48

mm

1150/320/480

1200/360/650

REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo

pg. 24

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

UNIDADES TIPO FANCOIL DE ALTA PRESION


RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD
UNIDAD

AA-02.18

AA-02.19

36,000

48,000

6
FA-36

16
FA-48

Energa

Volt/ph/Hz.

208/1/60

208/1/61

Potencia

watt

210

330

VENTILADOR
Tipo

scirocco

scirocco

Potencia x n

watt

183x2

183x2

Caudal

cfm

988/882/776

1377/1183/988

Lquido

pulg

3/8

3/8

Gas

pulg.

5/8

5/8

drenaje

mm

32

32

Nivel de ruido

dBA

40/39/37

44/42/40

R410A

R410A

EEV

EEV

kg

62

62

mm

1200/360/650

1200/360/650

TUBERIAS

REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo

pg. 25

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

UNIDADES TIPO FANCOIL DE ALTA PRESION cont.

RUBRO
CAPACIDAD

BTU/hr.

CANTIDAD
UNIDAD

AA-02.20

AA-02.21

76,000

96,000

50
FA-76

22
FA-96

Energa

Volt/ph/Hz.

208/1/62

208/1/63

Potencia

watt

530

790

Potencia x n

watt

400x1

400x1

Caudal

cfm

2048/1836/1659

2542/2295/2048

Lquido

pulg

3/8

3/8

Gas

pulg.

3/4

7/8

drenaje

mm

32

32

Nivel de ruido

dBA

4/43/41

48/46/43

R410A

R410A

EEV

EEV

kg

89

89

mm

1240/470/1040

1240/470/1040

VENTILADOR
Tipo

TUBERIAS

REFRIGERANTE
Tipo
mtodo de control
Peso
DIMENSIONES
ancho/alto/fondo

pg. 26

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO RUEDA ENTALPICA
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-05.01

al 31

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Unidad de acondicionamiento de aire que utiliza un dispositivo de transferencia de
energa para pre-acondicionar el aire exterior aprovechando la energa presente en el
aire de extraccin del ambiente, mediante un mecanismo de rueda entlpica.
La unidad estar compuesta por:
Gabinete
La caja exterior de la unidad deber ser construida en lmina de acero galvanizado.
La caja deber tener 4 soportes a los costados que permitan una fcil instalacin.
El conjunto ventilador y motor elctrico deber ser construido con rodetes de lmina de
acero galvanizado.
La rueda entlpica o de transferencia de energa deber tener fcil acceso desde un
costado y poder ser retirada de la unidad simplemente deslizndola.
Las puertas debern contar con cerraduras que desactiven la energa de la unidad.
Ventilador
Los ventiladores debern ser del tipo centrifugo de alabes orientados hacia adelante.
El motor deber estar montado sobre una base ajustable que permita un fcil acceso
para las tareas de servicio Los motores elctricos debern tener rodamientos del tipo
cojinetes de bolas sellados y permanentemente lubricados.
Todos los elementos de sujecin debern ser de materiales resistentes a la corrosin
Las poleas del ventilador debern contar con dispositivos que permitan regular la
tensin de las bandas.
Los equipos debern instalarse con bandas del tipo static-free.
La salida del aire de extraccin deber tener instalado un damper actuado por
gravedad para evitar contraflujos.
El tablero de control de motores deber ser instalado dentro del gabinete con
arrancadores, transformadores de 24 VAC y fusibles para el circuito.
Filtros.
La unidad contar con filtros interiores de 2 del tipo MERV 8
Aislamiento acstico
Todo el conjunto deber tener doble pared y aislamiento trmico y acstico de por lo
menos 1 de espesor.
Certificaciones
La unidad deber evidenciar que cumple con los requisitos establecidos por la AMCA
Publication 211 y tambin con la norma ARI Standard 1060 y UL 1995
pg. 27

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

ESPECIFICACIN

pg. 28

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

RESPONSABLE: F.CH.

AA-05.01
ERV-20-30L
2
1750
1550

AA-05.02
ERV-20-15L
1
1400
1200

AA-05.03
ERV-20-30L
2
2050
1850

AA-05.04
ERV-20-15L
1
1400
1200

end
end
end
end

end
end
end
end

end
end
end
end

end
end
side
end

208/60/3
13.5

208/60/3
8.8

208/60/3
16.6

208/60/3
8.8

1.04
1444
1-1/2

0.854
1366
1

1.229
1634
2

0.654
1281
1

0.698
1232
1

0.613
1146
1/2

0.868
1431
1-1/2

0.613
1146
1/2

11
28.26

11
22.81

11
24.49

11
22.81

332
UL1995

332
UL1995

332
UL1995

332
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-A-01
ERV-C-02

ERV-A-02

ERV-A-03
ERV-C-01

ERV-A-04

pg. 29

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.05
ERV-20-15L
3
1600
1400

AA-05.06
ERV-20-15L
1
1400
1200

AA-05.07
ERV-45-30L
1
3500
3300

AA-05.08
ERV-45-15L
2
2300
2100

end
end
end
end

end
end
side
end

end
end
end
end

end
end
side
end

208/60/3
12.4

208/60/3
8.8

208/60/3
25.1

208/60/3
14.1

0.801
1445
1-1/2

0.754
1324
1

1.161
1259
3

0.913
1089
1-1/2

0.654
1256
3/4

0.613
1146
1/2

0.932
1255
3

0.694
1025
1

11
20.01

11
22.81

11
31.62

11
31.04

332
UL1995

332
UL1995

469
UL1995

518
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
3-16X25
2" MERV 8
3-16X25

2" MERV 8
3-16X25
2" MERV 8
3-16X25

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-A-05
ERV-C-05
ERV-C-06

ERV-A-06

ERV-B-01

ERV-B-02
ERB-C-04

pg. 30

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.09
ERV-20-15L
2
1500
1300

AA-05.10
ERV-20-15L
1
1100
900

AA-05.11
ERV-20-30L
1
1900
1700

AA-05.12
ERV-45-15L
1
2200
2000

end
end
side
end

end
end
side
end

end
end
end
end

end
end
side
end

208/60/3
9.9

208/60/3
5.4

208/60/3
15.5

208/60/3
14.1

0.776
1386
1

0.595
1114
1/2

1.083
1522
1-1/2

0.903
1065
1-1/2

0.632
1201
3/4

0.563
991
1/3

0.826
1351
1-1/2

0.785
1037
1

11
21.31

11
27.54

11
28.26

11
32.18

332
UL1995

302
UL1995

302
UL1995

469
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
3-16X25
2" MERV 8
3-16X25

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-B-03
ERV-C-03

ERV-B-04

ERV-B-05

ERV-B-06

pg. 31

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.13
ERV-20-15L
1
1450
1250

AA-05.14
ERV-20-15L
1
1500
1300

AA-05.15
ERV-20-15L
1
1100
900

AA-05.16
ERV-20-15L
1
1250
1050

end
end
side
end

end
end
end
end

end
end
side
end

end
end
end
end

208/60/3
12.4

208/60/3
9.9

208/60/3
6.8

208/60/3
7.4

0.965
1439
1-1/2

0.876
1426
1

0.895
1259
3/4

0.622
1192
3/4

0.622
1173
3/4

0.632
1201
3/4

0.563
991
1/3

0.586
1070
1/2

11
22.01

11
21.31

11
27.54

11
25.01

332
UL1995

332
UL1995

332
UL1995

332
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-D-01

ERV-D-02

ERV-D-03

ERV-D-04

pg. 32

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo

Kgr.

RESPONSABLE: F.CH.

AA-05.17
Minivent-750
1
600
400

aa-05.18
ERV-20-15L
1
1400
1100

AA-05.19
ERV-10-20H
2
900
700

AA-05.20
ERV-20-15L
2
1600
1400

side/top
side/top
side/bottom
side

end
end
side
end

end
end
side
end

end
end
side
end

220/60/1
9.3

208/60/3
8.8

220/60/1
12.2

208/60/3
12.4

0.6
1243
1/3

1.054
1450
1

0.755
1423
1/2

1.001
1521
1-1/2

0.5
946
1/3

0.795
1195
1/2

0.594
1146
1/2

0.754
1302
3/4

11
27.61

11
22.96

11
22.26

11
20.01

109
UL1995

302
UL1995

132
UL1995

332
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
1-16X25
2" MERV 8
1-16X25

2" MERV 8
2-16X20
2" MERV 8
2-16X20

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-E-01

ERV-E-02
ERV-G-01

ERV-E-03
ERV-E-05

aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS
ERV-D-05

pg. 33

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.21
ERV-10-20H
1
1000
800

AA-05.22
ERV-20-30L
1
1800
1600

AA-05.23
ERV-20-30L
1
1750
1550

AA-05.24
ERV-10-20H
1
750
850

end
end
side
end

end
end
side
end

end
end
side
end

end
end
end
end

220/60/1
12.2

208/60/3
13.5

208/60/3
13.5

220/60/1
12.2

0.792
1555
1/2

1.054
1469
1-1/2

1.04
1444
1-1/2

0.708
1237
1/2

0.623
1270
1/2

0.901
1334
1

0.888
1310
1

1.039
1433
1/2

11
20.65

11
27.54

11
28.26

11
23.33

119
UL1995

302
UL1995

302
UL1995

132
UL1995

2" MERV 8
1-16X25
2" MERV 8
1-16X25

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-E-04

ERV-E-06

ERV-E-07

ERV-A-07

1-16*25
2" MERV 8
1-16*25

pg. 34

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
MOD. SUGERIDO
CANTIDAD

RESPONSABLE: F.CH.

AA-05.25
ERVe-55-15H
1

AA-05.26
ERV-10-20L
1

AA-05.27
ERV-10-20H
1

AA-05.28
ERVe-20-30L
1

6000
4200

650
550

1000
1000

2100
1600

end
end
side
end

end
end
end
end

end
end
side

end
end
side

bottom

bottom

208/60/3
29.6

220/60/1

220/60/1

208/60/3

12.2

12.4

0.971
1030
5

0.761
1140
1/3

0.837
1564
1/2

1.015
1540
1-1/2

SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA

0.816
828
2

0.558
965
1/3

1.145
1626
1/2

0.98
1376
3/4

EER
ER-COP
PESO

11
22.32

11
29.77

11
22.23

11
27

831
UL1995

119
UL1995

135
UL1995

401
UL1995

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

6-16X20
2" MERV 8

1-16X25
2" MERV 8

1-16X25
2" MERV 8

2-20X20
2" MERV 8

6-16X20

1-16X25

1-16X25

2-20X20

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-A-08

ERV-F-01

ERV-F-02

ERV-F-03

Caudal A. externo
Caudal A. extrado
UBICACIN E/S AIRE

cfm
cfm

OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION

peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

Kgr.

pg. 35

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
Control de rueda entalp.
sensor CO2/filtro sucio
paredes
protocolo de red
sensor de rotacin
CODIGOS EQUIPOS

RESPONSABLE: F.CH.

AA-05.29
ERV-20-15L
1
1650
1450

AA-05.30
ERV-20-15L
1
1100
900

AA-05.31
ERV-20-15L
1
1700
1500

end
end
side
end

end
end
side
end

end
end
side
end

208/60/3
13.5

208/60/3
5.4

208/60/3
13.5

1.013
1549
1-1/2

0.695
1165
1/2

1.026
1581
1-1/2

0.665
1290
1

0.583
991
1/3

0.776
1360
1

11
19.38

11
27.54

11
18.73

332
UL1995

332
UL1995

332
UL1995

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

2" MERV 8
2-16X20
2" MERV 8
2-16X20

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

OA/EA T.dif
si/si
24ga. Doble
BACNetIP
si

ERV-G-02

ERV-G-03

ERV-G-04

pg. 36

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR RECUPERADOR DE ENERGIA TIPO PLACAS EXTERIOR
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-05.32

al 48

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Unidad de acondicionamiento de aire que utiliza un dispositivo de transferencia de
energa para pre-acondicionar el aire de suministro aprovechando la energa presente
en el aire de extraccin del ambiente, mediante un dispositivo de flujo cruzado y
transferencia de calor aire/aire de placas de aluminio.
Las caractersticas principales de esta unidad son:
Campana de ingreso de aire
La apertura para el ingreso del aire estar ubicada en la parte inferior de la campana.
La campana tendr un filtro de malla de aluminio de mnimo 2 de espesor
La campana de salida del aire de extraccin tendr un damper para evitar el flujo de
retorno.
Cabina
La cabina ser del tipo doble pared con lmina de acero galvanizado y un aislamiento
trmico acstico de 1 de espesor entre ambas laminas.
La densidad del aislamiento ser de por lo menos 1.5 Lbs./ft3
Las puertas sern fcilmente desmontables a travs de las bisagras donde se apoyan.
Los picaportes de las puertas sern del tipo de cuarto de vuelta
La base ser rgida y la lmina en sus bordes tendr un doblado de por lo menos
para evitar que salga agua de la unidad.
Las cerraduras de las puertas sern del tipo door interlocking disconnect switch
Dampers
Los dampers sern del tipo de mnima filtracin o fuga y sern instalados y cableados
en fbrica.
Filtros
Cada unidad tendr filtros tipo MERV 8 de 2 de espesor tanto para el aire de
suministro como el de extraccin
Intercambiador de energa
Ser construido ntegramente con lminas de aluminio resistente a la corrosin
La eficacia de transferencia de calor ser mnimo del 70%
El rendimiento deber ser certificado bajo la norma AHRI Standard 1060
Bandeja de drenaje
Cada unidad deber contar con una bandeja de recoleccin de condensado construida
con lmina de acero inoxidable, con doble inclinacin para asegurar la recoleccin del
fluido.
pg. 37

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Ventiladores
Los ventiladores sern del tipo centrfugo, doble ancho, doble entrada y labes
curvados hacia adelante
Debern contar tambin con aislamiento de neopreno
Centro de control
La unidad tendr todo su circuito de control a 24 VAC y contar con su propio
transformador, switch de desconexin y otros componentes.
El centro de control deber ser instalado y cableado en fbrica y estar ubicado al
interior de la unidad.
ACCESORIOS
Control de velocidad VFD
Permite aumentar o disminuir el flujo del aire controlando la velocidad de los motores a
travs de la variacin de la frecuencia.
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 38

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACIN
RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto

AA-05.32
Pve-20-SC
8
1950
1950

AA-05.33
Pve-20-SC
7
1400
1400

AA-05.34
Pve-20-SC
1
1700
1300

AA-05.35
Pve-20-SC
1
1500
1200

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

208/60/3
11.8

208/60/3
4.8

208/60/3
6.2

208/60/3
4.8

0.553
1169
3/4

0.382
903
1/3

0.468
1050
3/4

0.409
952
1/2

1.14
1430
1-1/2

0.924
1202
1/2

0.607
1014
1/3

0.591
980
1/3

11
13.96

11
21.44

11
21.76

11
27.37

Certificacin
FILTROS
aire externo

606
UL-1995

606
UL-1995

606
UL-1995

606
UL-1995

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

aire extraccin

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

BMS interfaz
si
BACNetIP
VFD

BMS interfaz
si
BACNetIP
VFD

BMS interfaz
si
BACNetIP
VFD

BMS interfaz
si
BACNetIP
VFD

ver lista adj.

ver lista adj.

PVE-D-03

PVE-D-04

ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS

pg. 39

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

LISTADO DE UNIDADES DE LOS RUBROS AA-05.32 Y 33


AA-05.32
PVE-A-01
PVE-B-01
PVE-C-01
PVE-D-01
PVE-E-01
PVE-E-02
PVE-G-02
PVE-G-04

AA-05.33
PVE-A-02
PVE-B-02
PVE-C-02
PVE-D-02
PVE-E-03
PVE-G-03
PVE-G-05

pg. 40

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.36
Pve-20-SC
1
1700
1700

AA-05.37
Pve-35-SC
1
2100
2300

AA-05.38
Pve-45-SC
1
3550
3760

AA-05.39
Pve-35-SC
1
2900
3080

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

208/60/3
7.9

208/60/3
12.9

208/60/3
20.8

208/60/3
16

0.968
1294
3/4

1.088
1185
1

0.759
1002
2

0.759
1227
1-1/2

0.882
1253
3/4

1.089
1220
1-1/2

1.182
1155
3

1.239
1427
2

11
18.68

11
25.69

11
12.55

11
10.57

606
UL-1995

712
UL-1995

859
UL-1995

712
UL-1995

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

BMS interfaz
si
BACNetIP
VFD

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

PVE-D-05

PVE-G-01

PVE-A-03

PVE-A-04

pg. 41

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.40
Pve-35-SC
1
3000
3200

AA-05.41
Pve-35-SC
1
2400
2980

AA-05.42
Pve-35-SC
1
2300
2000

AA-05.43
Pve-45-SC
1
4100
3000

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

208/60/3
20.8

208/60/3
14

208/60/3
10.4

208/60/3
19.9

0.785
1261
2

0.646
1070
1

0.826
1121
1

1.179
1203
3

1.266
1462
3

1.117
1367
2

1.043
1150
1

1.18
1061
1-1/2

11
9.7

11
11.94

11
27.4

11
15.33

712
UL-1995

712
UL-1995

712
UL-1995

859
UL-1995

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

PVE-A-05

PVE-A-06

PVE-F-01

PVE-F-02

pg. 42

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia
EFICIENCIA ENERGETICA
EER
ER-COP
PESO
peso neto
Certificacin
FILTROS
aire externo
aire extraccin
ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS

Kgr.

RESPONSABLE: F.CH.

AA-05.44
Pve-20-SC
1
2100
1710

AA-05.45
Pve-20-SC
1
1200
1450

AA-05.46
Pve-20-SC
2
1950
1950

AA-05.47
Pve-20-SC
1
1400
1400

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

side
end
side
bottom

208/60/3
12.9

208/60/3
6.2

208/60/3
12.9

208/60/3
6.9

1.109
1456
1-1/2

0.634
1004
1/3

0.853
1306
1

0.692
1078
1/2

1.184
1386
1

1.033
1265
3/4

1.34
1509
1-1/2

1.024
1249
3/4

11
13.2

11
29.89

11
13.96

11
28.03

606
UL-1995

606
UL-1995

606
UL-1995

606
UL-1995

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

2" MERV 8

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

BMS interfaz
si
BACNetIP

PVE-F-03

PVE-H-01

PVE-H-02
PVE-H-03

PVE-H-04

pg. 43

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
MOD. SUGERIDO
CANTIDAD
cfm
Caudal A. externo
cfm
Caudal A. extrado
UBICACIN E/S AIRE
OA descarga
OA entrada
EA descarga
RA entrada
E.ELECTRICA
V/Hz/Ph.
Voltaje/frec/fase
amps.
corriente MCA
VENTILADOR SUMINISTRO
SP total
rpm
velocidad
hp
potencia
VENTILADOR EXTRACCION
SP total
rpm
velocidad
hp
potencia

AA-05.48
Pve-20-SC
2
1200
1200
side
end
side
bottom
208/60/3
4.8
0.534
943
1/3
0.791
1092
1/2

EFICIENCIA ENERGETICA
EER
ER-COP
PESO
Kgr.
peso neto
Certificacin
FILTROS
aire externo

2" MERV 8

aire extraccin

2" MERV 8

ACCESORIOS
monitoreo y control
sensor CO2/filtro sucio
protocolo de red
control de motor
CODIGOS EQUIPOS

RESPONSABLE: F.CH.

11
39.61
606
UL-1995

BMS interfaz
si
BACNetIP

PVE-H-05
PVE-H-06

pg. 44

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE EXTRACCION TIPO HONGO DE ALUMINIO
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-06.24

al 26

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Descripcin de los componentes:
Ventilador
El rodete del ventilador ser del tipo centrfugo con aletas orientadas hacia atrs y de
construccin en lmina de aluminio.
El rodete del ventilador deber contar con un diseo de alteas auxiliares que permitan
tambin el enfriamiento del motor elctrico.
En la parte de descarga del ventilador, la unidad deber tener una malla metlica
apropiada para evitar el ingreso de aves o animales pequeos
Switch de desconexin
Cada unidad deber tener un switch de desconexin que cumpla con las normas NEC
y haya sido instalado en fbrica
Motor
Toda unidad deber contar con un motor elctrico debidamente balanceado con la
carga del ventilador e instalado sin tener contacto con el flujo de aire del mismo.
El motor tambin deber tener una tapa de aluminio sujeta con tornillos que permita
una proteccin segura de la unidad y un fcil acceso para las tareas de
mantenimiento.
El motor deber contar con rodamientos sellados y de lubricacin permanente que
excedan un ciclo de vida de 100.000 hrs.
El motor deber estar apoyado sobre bases que permitan aislamiento de vibraciones
de la unidad.
Bandas, poleas y componentes debern estar sobredimensionados en un 150% con
respecto a la potencia nominal del motor.
Carcasa
La carcasa del ventilador ser tipo hongo de aluminio construido en una sola pieza
para un mejor desempeo ante las condiciones del ambiente.
Cumplimiento de estndares
Todas las unidades debern evidenciar su cumplimiento con los estndares AMCA
Publication 211 y Publication 311
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
pg. 45

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El proveedor deber evidenciar que comercializa en Ecuador al menos durante los


cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado.
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 46

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACION
CUADRO DE VENTILADORES DE EXTRACCION TIPO HONGO DE TECHO
AA-06.24
300
4
abajo

AA-06.25
900
1
abajo

AA-06.26
7200
4
arriba

Kgr.

26

27

130

Dimensiones (LxL)

mm x mm

368X368

368X368

826X826

SP ext.
SP total
velocidad
potencia
tip speed
voltaje/frec/fase
potencia motor
FLA
sonido
CODIGO DE UNIDADES

pulg H2O
pulg H2O
rpm
hp
m/seg.
V/Hz./ph.
hp
amps
dBA

0.8
0.8
1404
0.11
20.88
115/60/1
1/4
5.8
55

0.7
0.7
1215
0.2
21.11
115/60/1
1/3
7.2
58

2.5
2.5
1039
5.25
42.14
230/60/3
7-1/2
22
78

VE-A-06
VE-B-07
VE-C-06
VE-D-06

VE-B-08

VE-E-01
VE-E-02
VE-E-03
VE-E-04

RUBRO
caudal
CANTIDAD
DESCARGA
s/accesorios

cfm

pg. 47

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

CUADRO DE VENTILADORES DE EXTRACCION TIPO HONGO DE


TECHO
AA-06.30
2800
1
arriba

AA-06.31
650
1
Arriba

Kgr.

47

30

Dimensiones (LxL)

mm x mm

521x521

470X470

SP ext.
SP total
velocidad
potencia
tip speed
voltaje/frec/fase
potencia motor
FLA
sonido
CODIGO DE UNIDADES

pulg H2O
pulg H2O
rpm
hp
m/seg.
V/Hz./ph.
hp
amps
dBA

1.2
1.2
1118
0.95
27.49
460/60/3
1
2.1

1.1
1.1
1464
0.27
28.47
115/60/1
1/3
7.2

VE-F-07

VE-F-08

RUBRO
caudal

cfm

CANTIDAD
DESCARGA
s/accesorios

pg. 48

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE EXTRACCION CUADRADO EN LINEA DE ALETAS HACIA

ATRAS
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-06.05

al 21

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Ventiladores de extraccin centrfugos cuadrados de tipo compacto y flujo alineado
con el ducto, para instalacin interior.
Cabina
La cabina de la unidad deber ser construida con paneles de lmina de acero
galvanizado que formen una estructura rgida y segura.
La cabina deber tener accesos laterales para revisin, instalacin y mantenimiento.
Todos los ventiladores tendrn una caja elctrica fcilmente accesible, y ser precableada en fbrica.
Las unidades debern contar con collarines que permitan montaje sobre ductos tanto
en el ingreso como en la salida del flujo de aire.
Ventilador
El rodete del ventilador ser del tipo centrifugo, doble entrada, con alabes inclinados
hacia atrs y esttica y dinmicamente balanceado en fbrica.
Motor elctrico
Todas las unidades debern poseer motores elctricos con rodamientos sellados y
permanentemente lubricados y diseados para un ciclo de vida mnimo de 100.000
hrs.
Todas las poleas debern ser de hierro fundido y dinmicamente balanceadas.
Las bandas de transmisin sern del tipo static free, todas las poleas y bandas sern
dimensionadas sobre un 150% de la potencia del motor.
La base del motor ser diseada de tal manera que permita un ajuste sencillo de la
tensin en la banda de transmisin.
Tanto el ventilador como el motor tendrn aisladores de vibracin montados de fbrica
La unidad deber contar con switch de desconexin instalada en fbrica y de fcil
acceso del tipo NEMA-1
Cumplimiento de estndares
Todas las unidades debern evidenciar su cumplimiento con los estndares AMCA
Publication 211 y Publication 311
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
pg. 49

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El proveedor deber evidenciar que comercializa en Ecuador al menos durante los


cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 50

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACIN
RUBRO
CANTIDAD

AA-06.05

AA-06.06

AA-06.07

AA-06.08

kg-

44
145

41
145

47
145

40
145

cfm
pulg
H2O
pulg
H2O
rpm
m/seg.
HP
%

1040

880

1700

900

0.8

0.7

0.5

1.1
1529
26.68
0.42
47

0.8

0.7

0.5

1334
23.282
0.27
47

1234
24.003
0.43
48

1153
20.12
0.18
45

HP
rpm
amps
V/Hz/ph

1/2
1725
9.8
115/60/1

1/3
1725
7.2
115/60/1

1/2
1725
9.8
115/60/1

1/4
1725
5.8
115/60/1

VE-A-04

VE-A-05

VE-B-01

VE-B-02

CARACTERISTICAS
peso
motor frame
CARACTERISTICAS
OPERATIVAS
caudal
presin externa SP
presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES

1.1

pg. 51

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
CANTIDAD
CARACTERISTICAS
peso
motor frame
CARACTERISTICAS OPERATIVAS
caudal

RESPONSABLE: F.CH.

AA-06.09

AA-06-10

AA-06.11

AA-06.12

kg-

43
145

43
145

45
145

43
145

cfm

presin externa SP

pulg H2O

940
0.9

980
0.9

1200
0.75

1020
0.9

presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES

pulg H2O
rpm
m/seg.
HP
%

0.9
1383
24.14
0.32
47

0.9
1393
24.32
0.33
47

0.75
1129
21.95
0.32
50

0.9
1407
24.56
0.34
47

HP
rpm
amps
V/Hz/ph

1/2
1725
9.8
115/60/1

1/2
1725
9.8
115/60/1

1/3
1725
7.2
115/60/1

1/2
1725
9.8
115/60/1

VE-B-05
VE-G-05
VE-G-07

VE-B-06

VE-C-01

VE-D-04
VE-E-07

AA-06.13
1

AA-06.14
1

AA-06.15
1

AA-06.16
1

kg-

43
145

44
145

43
145

44
145

cfm

RUBRO
CANTIDAD
CARACTERISTICAS
peso
motor frame
CARACTERISTICAS OPERATIVAS
caudal
presin externa SP

pulg H2O

900
0.9

1220
0.9

1000
0.9

1200
0.9

presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES

pulg H2O
rpm
m/seg.
HP
%

0.9
1403
24.48
0.3
47

0.9
1477
25.77
0.41
47

0.9
1400
24.44
0.34
47

0.9
1470
25.65
0.4
47

HP
rpm
amps
V/Hz/ph

1/2
1725
9.8
115/60/1

1/2
1725
9.8
115/60/1

1/2
1725
9.8
115/60/1

'1/2
1725
9.8
'115/60/1

VE-D-05

VE-E-06

VE-E-08

VE-E-09

pg. 52

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
CANTIDAD
CARACTERISTICAS
DIMENSIONALES
peso
motor frame
CARACTERISTICAS
OPERATIVAS
caudal

RESPONSABLE: F.CH.

AA-06.17
1

AA-06.18
1

AA-06.19
1

AA-06.20
1

AA-06.21
2

kg-

41
145

48
145

47
145

109
184

43
145

cfm

800

1800

1500

3200

1040

presin externa SP

pulg H2O

0.7

0.8

0.7

1.5

0.9

presin total SP
velocidad de giro
tip speed
potencia
eficiencia esttica
MOTOR
Potencia motor
rpm motor
FLA
volt/freq/fase
UNIDADES

pulg H2O
rpm
m/seg.
HP
%

0.7

0.8

0.7

1.5

0.9

1239
21.63
0.22
47

1314
25.55
0.52
48

1172
22.78
0.37
50

1293
31.8
1.52
52

1414
24.6
0.35
47

HP
rpm
amps
V/Hz/ph

1/3
1725
7.2
115/60/1

3/4
1725
3.5
115/60/1

1/2
1725
9.8
115/60/1

2
1725
7.5
208/60/3

1/2
1725
9.8
115/60/1

VE-A-07

VE-A-10

VE-A-11

VE-G-02

VE-G-04
VE-G-06

pg. 53

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE EXTRACCION TIPO VEKTOR ALTA PLUMA DE DESCARGA

HACIA ARRIBA
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-06.22-23

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Son ventiladores de extraccin auto contenidos denominados de alta pluma o de
laboratorio y estn diseados para remover aire de ambientes txicos o altamente
contaminados, diluirlos con una corriente de aire exterior y luego expulsarlos a gran
altura del edificio de tal manera de evitar su reingreso al mismo o la contaminacin de
reas circundantes.
Sus caractersticas principales son:
CABINA Y TOBERA CONICA
La cabina ser construida con lmina de acero unida mediante soldadura.
Las superficies interior y exterior de la cabina sern recubiertas en fbrica con
acabados que protejan la lmina de acero de la corrosin y el ataque qumico.
Todos los elementos de sujecin tales como pernos o tornillos sern de acero
inoxidable.
La tobera de descarga cnica tendr el mismo recubrimiento de la cabina.
La cabina tendr un sistema de drenaje mediante tuberas roscadas.
La unidad tendr un panel de acceso para inspeccin o cambio de rodete, eje o
rodamientos sin necesidad de desmontar la cabina del ventilador.
VENTILADOR
El ventilador ser del tipo centrfugo con aletas inclinadas hacia atrs de aluminio y
recubierto con resinas de polister.
El eje del ventilador ser construido en acero torneado y con una capa del
recubrimiento de toda la unidad.
MOTOR
El motor elctrico ser grado premiun TEFC, con factor de servicio 1.0
Las poleas y bandas de transmisin sern sobredimensionadas al 200% de la potencia
nominal del motor y su cantidad mnima ser dos.
La unidad tendr instalado en fbrica un switch de desconexin externo del tipo NEMA
3R para cuando se realicen tareas de mantenimiento.
El motor y sus poleas y bandas estarn protegidos por una cubierta construida con
lmina de acero con el mismo recubrimiento de toda la unidad.
La unidad deber contar con un circuito de lubricacin mediante grasa sinttica que
abastezca a los rodamientos del ventilador.
DAMPERS
La unidad contar con dispositivos dampers tanto de aislamiento como de bypass.

pg. 54

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El damper de aislamiento ser del tipo actuado por gravedad y ser construido en
lmina de aluminio y tendr el mismo recubrimiento de proteccin de toda la unidad.
Ambos dampers sern de fcil acceso desde el exterior de la unidad.
El damper de bypass ser del tipo aletas opuestas.
Certificaciones
Esta unidad deber estar certificada bajo las normas AMCA
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

pg. 55

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACIONES
RUBRO
MOD. SUGERIDO
CANTIDAD

AA-06.23

VEKTOR-H-16-13
1

VEKTOR-H-12-10
1

VE-A-09

VE-A-12

cfm

3600

2100
220/3/60

UNIDAD
CAUDAL

AA-06.22

V/PH/HZ

220/3/60

SP. Ext

in H20

0.116

1.1

SP total
VENTILADOR

in H20

1.316

1.25

rpm

2183

2986

hp

3.76

2.45

E.ELECTRICA

revoluciones
potencia
alt efectiva descarga
velocidad de salida
MOTOR
potencia
velocidad de rotacin

mts

8.35

7.09

mts/seg

19.87

19.39

hp

rpm

1725

3600

TEFC

TEFC

320

243

tipo
PESO

kg

pg. 56

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE SUMINISTRO TIPO CENTRIFUGO DOBLE ENTRADA
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA.-06.02

al 04

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles
Son ventiladores de suministro de aire, centrfugos del tipo aletas inclinadas hacia
atrs con doble entrada de aire y accionados mediante un sistema de bandas y
poleas.
Sus caractersticas principales son:
CARCASA
La carcasa del ventilador ser construida con lmina de acero con una aplicacin de
recubrimiento para proteccin de la corrosin basado en un primer de zinc y
recubrimiento exterior del tipo epxico aplicada electrostticamente.
La unidad tendr una compuerta de acceso que estar asegurada a la carcasa
mediante pernos.
La unidad deber incluir bases anti vibracin instaladas en fbrica.
VENTILADOR
Los ejes de los ventiladores sern fabricados mediante proceso de torno y pulidos de
tal manera que la velocidad crtica en esta condicin sea superior en un 25% sobre la
mxima velocidad de operacin.
El impulsor o rodete ser del tipo airfoil con aletas inclinadas hacia atrs de operacin
de bajo nivel de ruido.
El rodete ser esttica y dinmicamente balanceado en el grado G6.3 de acuerdo a la
ANSI S2.19
Las chumaceras sern del tipo auto alineadas con rodamientos de bolas y un ndice de
resistencia a la fatiga L10 sobre las 80.000 hrs de operacin.
La unidad deber ser probada y balanceada en fbrica para eliminar el riesgo de un
nivel de vibraciones elevado de acuerdo a AMCA estndar 204-05
MOTOR
El motor elctrico tendr un aislamiento Clase B o superior, un factor de servicio
mnimo de 1.5 y cumplir con el estndar NEMA Table 12-12
El motor estar instalado sobre una base de lmina de acero adecuada que permita
asegurar una tensin ptima y desmontaje de bandas.
Las poleas y bandas debern contar con una proteccin en lmina de acero
recubierta.
Certificaciones
Esta unidad deber estar certificada bajo las normas AMCA
Montaje

pg. 57

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante

ESPECIFICACION
RUBRO
CANTIDAD
UNIDAD

AA-06.02

AA-06.03

AA-06.04

VS-E-01

VS-G-01

VS-F-01

VENTILADOR
CAUDAL

cfm

23.040

5.300

4.000

SP total

in.H2O

1.5

1.5

1.2

Tip speed

m/s

44,16

32.18

27.15

Velocidad giro

rpm

1.230

1.352

1.119

nivel de ruido

dBA

85/85

73/69

69/64

V/F/PH

208/60/3

208/60/3

460/60/3

RPM motor

rpm

1.725

1725

1.725

POTENCIA

hp

15

1-1/2

TH

TH

TH

kg

287

131

131

MOTOR
E.ELECTRICA

DESCARGA
POSICION
PESO

pg. 58

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 59

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE EXTRACCION CUADRADO EN LINEA DE ALETAS HACIA

ATRAS
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-06.27

al 29,32,33

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Ventiladores de extraccin centrfugos cuadrados de tipo compacto cabina cuadrada
tipo ducto y flujo alineado con el ducto, para instalacin interior.
Cabina
La cabina de la unidad deber estar construida con paneles de lmina de acero
galvanizado que formen una estructura rgida y segura.
La cabina deber tener accesos laterales para revisin, instalacin y mantenimiento.
Todos los ventiladores tendrn una caja elctrica fcilmente accesible, y ser precableada en fbrica.
Las unidades debern contar con collarines que permitan montaje sobre ductos tanto
en el ingreso como en la salida del flujo de aire.
Ventilador
El rodete del ventilador ser del tipo centrifugo, doble entrada, con alabes inclinados
hacia atrs y esttica y dinmicamente balanceado en fbrica.
Motor elctrico
Todas las unidades debern poseer motores elctricos con rodamientos sellados y
permanentemente lubricados y diseados para un ciclo de vida mnimo de 100.000
hrs.
Todas las poleas debern ser de hierro fundido y dinmicamente balanceadas.
Las bandas de transmisin sern del tipo static free, todas las poleas y bandas sern
dimensionadas sobre un 150% de la potencia del motor.
La base del motor ser diseada de tal manera que permita un ajuste sencillo de la
tensin en la banda de transmisin.
Tanto el ventilador como el motor tendrn aisladores de vibracin montados de fbrica
La unidad deber contar con switch de desconexin instalada en fbrica y de fcil
acceso del tipo NEMA-1
Cumplimiento de estndares
Todas las unidades debern evidenciar su cumplimiento con los estndares AMCA
Publication 211 y Publication 311

pg. 60

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Certificaciones
Esta unidad deber estar certificada bajo las normas AMCA
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.

pg. 61

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

ESPECIFICACION
RUBRO

AA-06.27

AA-06.28

AA-06.29

CANTIDAD
UNIDAD

1
VE-F-01

2
VE-F-02

1
VE-F-06

VE-M-03
CAUDAL

cfm

1350

1000

5000

in.H2O

0.9

VELOCIDAD
POTENCIA

rpm
HP

1244
0.42

1340
0.30

1297
2.76

TIP SPEED
NIVEL DE RUIDO
MOTOR

m/s
dBA

24.19
62/58

23.39
60/56

36.86
73/68

POTENCIA

HP

1/2

1/3

V/HZ/PH
RPM

115/60/1
1725

115/60/1
1725

460/60/3
1725

amps
kg

9.8
47

7.20
152

5
152

AA-06.32

AA-06.33

SP TOTAL
VENTILADOR

VOLT/FREC/FASE
VELOCIDAD
FLA amps
PESO

RUBRO
CANTIDAD

VE-H-03

VE-M-04

cfm

1050

850

in.H2O

0.8

0.5

rpm

1357

1126

UNIDAD
CAUDAL
SP TOTAL
VENTILADOR
VELOCIDAD
POTENCIA

HP

0.31

0.17

TIP SPEED

m/s

23.68

19.64

NIVEL DE RUIDO
MOTOR

dBA

61/57

54/52

POTENCIA

HP

1/3

1/4

VOLT/FREC/FASE

V/HZ/PH

115/60/1

115/60/1

VELOCIDAD

RPM

1725

1725

FLA amps

amps

7.2

5.8

kg

41

40

PESO

pg. 62

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: VENTILADOR DE EXTRACCION TIPO PLAFON
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-06.34

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles.
Estos ventiladores cumplen con los estndares de mxima calidad en la industria, son
iguales o similares a los modelos SP-B80 fabricados por Greenheck.
Todas las conexiones de salida sern de forma circular que permitan una fcil y rpida
conexin, adems contarn con dampers que eviten el retorno del flujo cuando la unidad
no est en operacin.
El motor podr ser removido de manera sencilla para mantenimiento por su lado inferior.
El acceso a las conexiones elctricas ser de manera fcil evitando la necesidad de
realizar perforaciones o agujeros.
La unidad ser fcilmente desconectable elctricamente para servicio y mantenimiento.
La rejilla exterior ser sujeta a la cabina mediante tornillos adecuadamente ocultos.
Cada unidad deber contar con dispositivos de sujecin externos para diferentes
condiciones de instalacin.
La cabina ser de construccin en lmina de acero galvanizado para una mejor
resistencia y de bajo perfil para facilitar su instalacin en ambientes con restricciones de
espacio.
Certificaciones
Todas las unidades debern evidenciar su cumplimiento con los estndares AMCA
Publication 211 y Publication 311
Montaje
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
Experiencia del proveedor
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
Garanta
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.

pg. 63

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
Inventario de piezas y partes originales
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.

ESPECIFICACIN
RUBRO
UNIDAD
Area Utilizacin
Caudal (cfm)
Presin (c.a.)
Potencia
Giro (rpm)
Volt/Fase/Frecuencia
Tipo
Cantidad
Accesorios
SIMILAR A :

AA-06.34
EB-02
Baos
100
0.24
100 W
950
115/1/60
Bao
186
Sensor de Movimiento
SP-B110

pg. 64

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: UNIDADES MANEJADORAS DE DOBLE PARED DE EXPANSION DIRECTA
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-004.01

al 37

CONTENIDO DEL RUBRO


GENERAL

Consiste en el suministro, montaje, instalacin y puesta en operacin


de
herramientas, mano de obra especializada y materiales que conforman la Unidad
Manejadora de Aire para uso Exterior que adems cumplirn obligatoriamente con las
especificaciones que se indican a continuacin.
RANGOS Y CERTIFICACIONES
Las unidades manejadoras de Aire deben cumplir y estar sometidos sus procesos de
fabricacin de las diferentes partes a los siguientes estndares y normas:
A. Seguridad de la manejadora de aire: standard ETL o UL 1995
B. Uso eficiente de la energa en el manejador: ASHRAE 90.1-2010
C. Ventiladores: AMCA 210
D. serpentines: ARI 410
E. Certificacin de la unidad: ARI 430
F. Filtros: ANSI/UL 900 listed Class I o Class II
G. Cableado de control: cdigo NEC
DOCUMENTACION A ENTREGAR POR EL FABRICANTE
Curvas de rendimiento de los ventiladores con los puntos de operacin claramente
indicados.
Planos que indiquen claramente: dimensiones de la unidad, espacios libres
necesarios, conexiones de suministros, cableados y de embalaje.
Reportes de detalles de rendimiento de: ventilador, motor elctrico y serpentines.
Informacin sobre operacin y mantenimiento de la unidad que incluya:
instrucciones sobre lubricacin, reemplazo de filtros, limpieza de bandeja de
condensado y servicio del motor y sistema de transmisin de potencia,
Reporte del rendimiento de la manejador de acuerdo al Standard ARI-430
Reportes de cumplimiento con el Standard ARI-410 de los serpentines
Reporte de los niveles de ruido de la unidad en concordancia con el Standard ARI260
Reporte indicando la distribucin del peso en la unidad.
Reporte de producto para los filtros, donde se indique: tipo de material empleado
reporte de desempeo, instrucciones de montaje
Requerimientos de suministros elctricos tale como diagramas elctricos que
indiquen claramente las partes instaladas en fbrica y las que se instalen en obra.
Reporte de caractersticas tcnicas de los motores elctricos
ENTREGA, MANIPULACIN Y ALMACENAMIENTO
Cumplimiento con el Standard ASHRAE 62 Seccin 5 sobre el diseo de gabinetes
de manejadoras y otros.

pg. 65

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Cumplimiento con el Standard ASHRAE 62 que recomienda las prcticas a seguir


durante la construccin y montaje de estas unidades y durante el transporte hasta
el sitio.
Tener claramente definidos las recomendaciones y procedimientos sobre:
manipulacin, descarga y almacenamiento de la unidad, proteccin contra la
intemperie, aseguramiento de piezas sueltas incluyendo packing lists de aquellas
que no estn aseguradas a la unidad, proteger todos los componentes elctricos y
electrnicos, no almacenar la unidad en lugares muy hmedos o con riesgo de
inundacin y mantener la unidad sellada durante todas estas etapas.

MATERIALES EXTRAS
El fabricante proveer de filtros adicionales para la etapa de pruebas y un juego
para la etapa de arranque final
El fabricante de la unidad proveer de un juego extra de bandas en adicin a
aquellas que vinieran instaladas desde la fbrica.
MONTAJE
Todas las tareas de montaje debern ser dirigidas y ejecutadas por personal que
acredite experiencia en este tipo de unidades y capacitado por el fabricante.
EXPERIENCIA DEL PROVEEDOR
El proveedor deber evidenciar que comercializa en Ecuador al menos durante los
cinco aos anteriores los productos de la marca que oferta para este proceso. El
proveedor deber adjuntar un listado de los equipos similares vendidos durante los
ltimos cinco aos. El listado constar de los siguientes campos: ao de venta,
nombre del proyecto, nombre del cliente, direccin del proyecto, telfonos del proyecto
o cliente (para confirmar la veracidad de la informacin).
GARANTA
La garanta tcnica de los equipos ofertados deber ser de al menos sobre CINCO
aos contados a partir de la fecha de comisionamiento, durante este perodo cualquier
parte que falle o funcione de manera incorrecta debido a fallas de fabricacin, deber
ser inmediatamente cambiada por el Fabricante.
La garanta de vida til de los equipos ofertados debe ser de al menos 15 aos desde
la entrega para lo que se garantizar un servicio ininterrumpido de mantenimiento
calificado
INVENTARIO DE PIEZAS Y PARTES ORIGINALES
El proveedor deber mantener un inventario local de piezas y partes originales de los
equipos ofertados por al menos 10 aos desde la entrega.
El Proveedor deber presentar certificados de calidad del Fabricante.

DESCRIPCION GENERAL
Cada unidad estar conformada por las siguientes partes:
Base estructural
Gabinete con aislamiento acstico y trmico
pg. 66

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Puertas de acceso
Ventiladores
Motores
Controles de motores elctricos
Serpentines
Filtros
Dampers
Controles
Componentes y partes que consten en los planos de referencia
Cada unidad deber cumplir los niveles de rendimientos para los siguientes
parmetros:
Flujo de aire
Presin esttica
Capacidad de enfriamiento
Capacidad de calentamiento
Servicio elctrico
Niveles de sonido
Niveles de filtracin
Seguridad estructural del gabinete.
Cada unidad deber mantener sin ninguna alteracin su integridad estructural aun as
fueran removidos todos sus paneles.
De preferencia toda unidad deber ser entregada en una sola pieza salvo que se
considere necesario separarla para su transportacin o instalacin.
El fabricante deber proveer instrucciones detalladas paso a paso para instalacin y
desmontaje de la unidad.
En el caso de que fuera necesario segmentar la unidad, los trabajos de montaje
debern ser realizados por personal debidamente entrenado y calificado por el
fabricante.
1. CUMPLIMIENTO DE NORMAS
La unidad deber cumplir con todos los estndares y normas referidos en esta
especificacin.
Los fabricantes que no pudieren cumplir con el estndar ARI-430 debern evidenciar
el haber realizado pruebas en cada unidad sobre:
Verificacin de potencia al freno de los motores
Cumplimiento de parmetros de flujo de aire.
Cumplimiento de parmetros de presin esttica
2. BASE SOPORTANTE
La unidad estar provista de una base estructural de acero galvanizado
ubicada bajo todo el permetro estructural.
Deber tener el espacio adecuado y suficiente para la disposicin de
condensados y similares
Deber contar con los dispositivos necesarios para la manipulacin e izaje
integro de la misma.
pg. 67

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

3. CUBIERTA EXTERIOR
Todo el conjunto de la unidad es del tipo doble-pared, material de aislamiento
expuesto no podr ser aceptado.
La instalacin de los paneles deber cumplir con los estndares UL-1995 para
seguridad contra incendios y tambin los requerimientos de NFPA 90
El material que compone el aislamiento ser tal que evite el crecimiento de
mohos y hongos en concordancia con el mtodo de ensayos UL-181
El aislamiento de los paneles deber estar completamente encapsulado por las
placas metlicas de tal manera que el aire no est en contacto con el material,
aquellos paneles que contengan como aislamiento lana de vidrio (fiberglass)
debern estar sellados en cada esquina y en todo el permetro para eliminar la
posibilidad de flujo de aire a travs del panel y el crecimiento de hongos o
moho dentro del mismo.
La resistencia trmica de la cubierta ser mnimo de R12 es decir 12 hr-ft2F/BTU
Las lminas de acero empleadas en la cubierta sern de acero galvanizado o
inoxidable.
La unidad deber tener una estructura en acero galvanizado que provea la
resistencia necesaria para la operacin de la unidad y no dependa del montaje
de los paneles para el desempeo de su integridad.
La estructura de la cubierta deber contar con el mismo aislamiento con que se
instalen los paneles.
El nivel de fugas de aire de la unidad deber ser menos a 1% del caudal de
diseo y con una presin esttica de +/- 8 plg de H2O
Los paneles y puertas de acceso de la unidad no podrn tener deflexiones
mayores a L/240 cuando estn sometidas a una presin de +/- 8 plg. H2O en
este caso L es el largo del panel y L/240 la deflexin en la mitad.
La unidad estar provista de un panel de cubierta con un mnimo de por
cada pie, esta cubierta deber sobresalir por lo menos 2 a cada lado de la
unidad.
La unidad deber tener un recubrimiento superficial que permita soportar las
caractersticas del ambiente predominante en la zona tales como salinidad, alta
humedad y temperatura.
4. BANDEJAS DE DRENAJE
La unidad estar provista de una bandeja bajo cada serpentn de enfriamiento
o humidificador y deber cumplir con ASHRAE STANDARD 62
Las tuberas de conexin a estas bandejas sern del mismo material y sus
acoples sern soldados.
Las bandejas de drenaje debern tener las mismas caractersticas de
aislamiento que los paneles
Todas las caeras que conecten a estas bandejas igualmente debern estar
aisladas.
Debern estar montadas de tal manera que permitan inspeccin visual y
limpieza fsica en el 100% de la misma sin necesidad de retirarla
pg. 68

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Deber tener un mnimo de 1 de separacin con el serpentn.


Deber permitir la evacuacin calculada de condensado independientemente
de la operacin del ventilador.
5. PUERTAS DE ACCESO
Las puertas de acceso debern tener bisagras de acero inoxidable que
permitan el giro en 180 de las mismas.
Debern tener pestillos con mecanismo de leva giratoria de tal manera que
asegure al cerrar un sello hermtico.
Las puertas de servicio debern tener acceso al pestillo desde adentro de la
unidad.
Debern tener una ventana con doble vidrio para inspeccin del interior de la
unidad, las dimensiones mnimas sern 3x8
6. CANALES PARA TUBERIAS
La unidad deber tener canales apropiados para las tuberas los cuales debern
cumplir con las mismas caractersticas de aislamiento que los paneles de la unidad.
7. BORDILLOS TIPO ROOF CURB
La unidad deber contar con bordillos tipo roof curb que faciliten su montaje y adems
sean fabricados en acero galvanizado y en capacidad de soportar sobre su permetro
el equipo.
8. VENTILADORES
Los ventiladores sern centrfugos del tipo de doble entrada, doble ancho (DWDI) o
tambin una entrada, ancho simple (SWSI)
Los labes de los ventiladores debern ser del tipo airfoil y cumplir con los estndares
de AMCA 210 y todos los requisitos que esta exige en su programa de certificacin.
Todos los ventiladores debern adjuntar los siguientes accesorios:
Pantallas protectoras en los ingresos a los ventiladores
Puerta de acceso en la pantalla protectora.
Protector de banda y polea
Los labes de los ventiladores debern ser fabricados en aluminio extruido.
Los ejes de los ventiladores debern ser de acero pulido y con un recubrimiento
anticorrosivo.
El motor deber estar sobre una base metlica que permita una fcil regulacin de la
tensin de la banda, adems deber contar con apoyos anti vibracin.
Los ventiladores debern conectarse a los ductos mediante una junta flexible
preferiblemente a base de lona.
9. POLEAS Y RODAMIENTOS
Los rodamientos empleados en la unidad debern cumplir con ANSI/AFMA 9
relacionados a su duracin por fatiga.
Los rodamientos de los ventiladores debern tener una duracin mnima de
200.000 horas
10. MOTORES ELECTRICOS
Las caractersticas mnimas que deben cumplir los motores elctricos son:
Condiciones de operacin 60 Hz y 1750 rpm
Factor de servicio 1.15
Rodamientos acorde con NEMA
pg. 69

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Diseado para servicio continuo a plena carga in ambientes a 40C


Tipo Open Drip Proof ODP o TEFC totally enclosed fan cooled
Adaptable para uso con tecnologa INVERTER
11. SISTEMAS DE ARRANQUE DE MOTORES
Los sistemas de arranque de motores cumplirn con las certificaciones UL y NEMA 3R
Tambin debern tener las siguientes caractersticas:
Bornera principal
Contactores
Protecciones de sobrecarga
Dos fusibles de control primario y uno secundario para lnea de control
Cableados en fbrica
Switch on-off integrado
Cableado a los motores de los ventiladores
Diseados para trabajo en altas temperaturas ambientales
12. CONTROLES DE VELOCIDAD EN MOTORES DE VENTILADORES (VFD)
Todos los componentes de los circuitos de control de velocidad sern
certificados UL y debern cumplir con las normas NEC
Estarn montados en un compartimiento del tipo NEMA1 localizado de
preferencia en el acceso primario al ventilador asociado.
Debern estar en capacidad de trabajar en condiciones ambientales tales como
5-104F
Luego de la instalacin de la unidad, el dispositivo VFD deber ser arrancado y
programado por un tcnico certificado por el fabricante.
Deber contar con proteccin para distorsin por armnicos
Tendr un interfaz para usuario que disponga de:
o Display alfanumrico de 30 o ms caracteres
o Configuracin de parmetros y data de operaciones.
o La informacin que puede mostrar ser:
Frecuencia, rpm, corriente, torque del motor
Potencia del motor
Voltaje DC
Voltaje de salida
Temperatura del heat sink
Cronometro, temporizador
Kwh
Mensajes de falla
Mensajes de alarma
La unidad VFD tendr las siguientes protecciones:
o Sobre carga
o Falla de tierra
o Sobre voltaje
o Bajo voltaje
o Sobre temperatura
o Pedida de fase o de poder
pg. 70

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

o Perdida de referencia feedback


Tendr las siguientes funciones de comunicacin:
o Dos entradas programables analgicas
o Seis entradas digitales programables
o Tres salidas programables con relay digital
o Protocolo de comunicacin Modbus RTU
o Filtros ajustables tanto en las entradas como salidas analgicas
o Las seales de entrada de velocidad sern 4-20mA 0-10VDC
o Auto encendido seleccionable y ajustable por el usuario
o Control integrado de interfaz que permita trabajar bajo SIEMES FLN,
JOHNSON N2, MODBUS RTU o BACnet, LONworks sobre RS-485
13. COMPONENTES DE CIRCUITOS DE ENFRIAMIENTO Y CALOR
Los intercambiadores de calor debern cumplir o exceder los requerimientos
establecidos en el diseo
Los serpentines de enfriamiento estarn en capacidad de operar a una velocidad de
flujo de aire mxima de 550 fpm
El espacio entre serpentines ser mnimo de 18
Debern tener paneles que sean fcilmente desmontables sin la necesidad de
herramientas.
Debern contar con soportes verticales adecuados a la longitud del serpentn.
Todos los serpentines del tipo DX debern ser probados a presin en fbrica y
cumplirn con las normas ANSI B9.1
Las aletas de los serpentines sern de aluminio o cobre conformado y sus collares
sern montados de manera precisa, le espesor ser de 0.006 a 0.01
14. FILTROS
Las caractersticas de los filtros debern estar acorde a las especificaciones de
referencia
Para el caso de filtros que estn ubicados aguas arriba del serpentn de enfriamiento,
la unidad deber contar con accesos laterales que permitan su montaje y desmontaje
a travs de una puerta de acceso.
En el caso de filtros ubicados aguas-abajo del serpentn, la unidad dispondr de filtros
que puedan cargarse por su lado frontal, para lo cual dispondr de un espacio mnimo
de 18 y puerta de acceso lateral.
Los filtros debern tener un rack apropiado dentro de la unidad y construido en acero
galvanizado.
La unidad deber contar con dispositivos del tipo magnehelic para medir la presin
diferencial a ambos lados del filtro este dispositivo deber estar instalado con su
circuito completo de tuberas.
15. ACABADOS
Las unidades debern ser pintadas en fbrica.
Las unidades habrn recibido una capa de primer antes de la pintura final
La pintura final ser del tipo poliuretano acrlico.
16. ENSAYOS E INSPECCIONES
El fabricante deber entregar la unidad balanceada dinmicamente en un rango de 10100% de su velocidad de rotacin para el caso de unidades que cuenten con VFD

pg. 71

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

A continuacin se incluyen las especificaciones detalladas de cada una de las UMAs

RUBRO N2.AA-04.01 N2.AA-04.02 N2.AA-04.03 N2.AA-04.04 N2.AA-04.05


UNIDAD
A-01
A-02
C-01
C-02
C-03
B-01
B-02
D-01
D-02
E-01
E-03
E-02
G-02
G-01
H-04
G-03
7
6
1
1
1
TOTAL

RUBRO N2.AA-04.06 N2.AA-04.07 N2.AA-04.08 N2.AA-04.09 N2.AA-04.10


UNIDAD
C-04
D-03
D-04
D-05
G-04
1
1
1
1
1
TOTAL
RUBRO N2.AA-04.11 N2.AA-04.12 N2.AA-04.13 N2.AA-04.14 N2.AA-04.15
UNIDAD
A-03
A-04
A-05
A-06
A-07
1
1
1
1
1
TOTAL

RUBRO N2.AA-04.16 N2.AA-04.17 N2.AA-04.18 N2.AA-04.19 N2.AA-04.20


UNIDAD
A-08
A-09
F-01
F-02
F-03
1
1
1
1
1
TOTAL

RUBRO N2.AA-04.21 N2.AA-04.22 N2.AA-04.23 N2.AA-04.24 N2.AA-04.25


UNIDAD
F-04
F-05
F-06
F-07
F-08
1
1
1
1
2
TOTAL
RUBRO N2.AA-04.26 N2.AA-04.27 N2.AA-04.28 N2.AA-04.29 N2.AA-04.30
UNIDAD
F-10
F-11
F-12
F-13
F-14
1
1
1
1
1
TOTAL

pg. 72

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO N2.AA-04.31 N2.AA-04.32 N2.AA-04.33 N2.AA-04.34


UNIDAD
F-15
F-16
F-17
H-01
F-18
F-19
F-20
F-21
F-22
TOTAL

RUBRO N2.AA-04.35 N2.AA-04.36 N2.AA-04.37


UNIDAD
H-02
H-05
H-06
2
1
1
TOTAL

TERMINOLOGIA DE SEGMENTOS:
IP
FF
CC
FS
DI
XA
RF
DP

INLET PLENUM SEGMENT


FLAT FILTER SEGMENT
COOLING COIL SEGMENT
SUPPLY FAN SEGMENT
DIFFUSER SEGMENT
ACCES SEGMENT
HIGH EFFICIENCY FILTER SEGMENT
DISCHARGE PLENUM

pg. 73

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.01
UNIDAD:
ver listado
CAUDAL (cfm)
1950
SECCION (plg x plg):36X33
CANTIDAD:
7
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.33

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 14W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2
Filter Media Type: Pleated 30% (MERV 8)
Filter Area (ft): 4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8)

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 74

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.71/ 1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)


Motor Type: TECO ODP Premium
Efficiency
HP 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.60
Efficiency: 89.5%

Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2067
BHP: 2.34
Fan BHP w/ Belt Loss: 2.51
Outlet Velocity (ft/min): 2125

pg. 75

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Motor Control Details


Motor Control Type: Variable Frequency
Drive
Motor HP: 3.0

Motor Control Electrical Details

Motor Control Options


Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks
(LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5%
Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN,
BACnet

Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158

Full Load Amps (FLA): 11.8

Humidity: MAX 95% RH non-condensing


Altitude: 3,300 ft. without derate (1% derate
for each additional 330 ft.)
Enclosure: NEMA 3R

input
3 Phase 208-240 VAC +/-10% 48/63Hz +/Rated Input Voltage:
5%
Rated Input Current Amps:
11.8
Heat Loss in Watts 100% Load:
116
Efficiency (%):
98
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

pg. 76

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 27 "

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
Prefilter Air Pressure Drop (in. w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop (in.
w.g.):
High Eff. Filter Dirty Allowance (in. w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

(1)24x24
4
Side
2"
Pleated 30%
(MERV 8)
0.26
0.1
12" Rigid
90-95% Eff,
(MERV 14)
0.56
0.2
Pleated 30% (MERV 8)
1
90-95% Eff, (MERV 14)
1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic) (0 - 2
in. w. c.)
Access Door on Left Side(Left) 30H x
18W
Multi-Point Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement
pg. 77

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam
Insulation
Galvanized Floor Liner STD
Gauge
Exterior Galvanized Liner
Access Door on Left
Side(Left) 30H x 14W

Opening: Bottom

Coil General/Physical Details


Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
11
6
27.5
21
4
left
1-5/8
7/8
1
none

1950
30
pg. 78

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.
80
77
55.8
55.6
488

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter

CC Variable Length Cooling Coil


FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.33
0.26
0.1

Cooling 6 rows 11 fins


External Static Pressure User Entered Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance Prefilter
12" Rigid 90-95% Eff, (MERV
14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.79
1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.71

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
20
10
19
40
10
27
21
17
164

width
(in)
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
171
83
490
529
74
164
164
153
1828

pg. 79

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.02
UNIDAD:
ver listado
CAUDAL (cfm)
1400
SECCION (plg x plg):30x39
CANTIDAD:
6
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24H x 12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
3.3"
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8)

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 80

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.71/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 24HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2026
BHP: 1.43
Fan BHP w/ Belt Loss: 1.56
Outlet Velocity (ft/min): 1925

Motor Detail (per motor)


Motor Type: TECO ODP Premium
Efficiency
HP=2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency
Drive
Motor HP= 2.0

Motor Control Electrical Details

Motor Control Options


Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks
(LON)

Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158

RFI/EMI EMC Filter


Swinging DC Line Choke (equivalent to 5%
Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN,
BACnet

Altitude: 3,300 ft. without derate (1% derate

Full Load Amps (FLA): 7.5

Humidity: MAX 95% RH non-condensing

for each additional 330 ft.)


Enclosure: NEMA 3R

pg. 81

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):

3 Phase 208-240 VAC +/-10% 48/63Hz +/5%


7.5
73
98%

Output
Output Current Amps: 7.5
Overload Current Rating: 110% for 1
minute every 10 minutes
Drives are rated for use below 3,300 ft and
104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use
above these limits.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27 "

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

pg. 82

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

(1)24x20
3.3

Filter Loading:

Side

Prefilter Depth:

2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


0.21
w.g.):
Prefilter Dirty Allowance (in. w.g.): 0.1
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

90-95% Eff,

High Eff. Filter Air Pressure Drop


0.45
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:

90-95% Eff,
(MERV 14)

Spare Filter Quantity Set(s):

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: Bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 83

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
20
27
3.8
left
1-5/8
7/8
1
none

1400
30
80
77
56.3
56.1
368

pg. 84

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.16
0.21
0.1
0.38

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.71

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
18
10
19
40
10
27
21
15

width
(in)
39
39
39
39
39
39
39
39

height
(in)
30
30
30
30
30
30
30
30

weight
(lbs.)
160
85
471
511
72
167
167
141

pg. 85

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.03
UNIDAD:
UMA-C-01
CAUDAL (cfm)
2.000
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in.
w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage

0.37
Outside Air (OA)
2000
15.25Hx19.00W
2.01
Front-Low(Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked

Return/Mixed Air
15.25Hx19.00W
2.01
Top
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked

Filter media detail


Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

2"Pleated 30% (MERV


8)

8
(4)24x12
side
0.1
0.05
2"Pleated 30% (MERV
8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 28W
Standard Door Latch, No Lock, Outward
Opening
pg. 86

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 9
TSP/ESP (in. w.g.): 3.75/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 9-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2117
BHP: 2.08
Fan BHP w/ Belt Loss: 1.562.23
Outlet Velocity (ft/min): 2002

Motor Type: TECO ODP Premium


Efficiency
HP=3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

pg. 87

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.16

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

(1)24x24
4

Filter Loading:

Side

Prefilter Depth:

2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.27
0.1
12" Rigid
80-85% MERV 13

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
30HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.53
0.2
Pleated 30%
(MERV 8)
1
80-85% Eff,
(MERV 13)
1

pg. 88

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: Bottom

Coil General/Physical Details


Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
3.8
left
1-5/8
5/8
1
none

2000
9
76
66
55
53.9
500
pg. 89

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

0.17
0.05
0.1
0.05

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.57
1.2
0.16
0.27
0.1
0.53
0.2
0.35
3.75

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
31
19
39
10
12
21
17
149

width
(in)
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36

weight
(lbs.)
217
461
382
68
64
149
143
1484

pg. 90

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.04
UNIDAD:
UMA-C-02
CAUDAL (cfm)
2.150
SECCION (plg x plg):39X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.41
Outside Air (OA)
2150
15.25Hx19.00W
2.01
Front-High(Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked

Return/Mixed Air
15.25Hx19.00W
2.01
Top
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
linked

2"Pleated 30% (MERV 8)

8
(4)24x12
side
0.1
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33HX27W
Standard Door Latch, No Lock, Outward
Opening

pg. 91

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2150
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.75/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 33HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)


Motor Type: TECO ODP Premium
Efficiency
HP=3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Type: FC
Size: 10-10
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1878
BHP: 2.37
Fan BHP w/ Belt Loss: 2.54
Outlet Velocity (ft/min): 1785

pg. 92

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.12

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.3
0.1
12" Rigid
80-85% MERV
13

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
33HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.6
0.2
Pleated 30%
(MERV 8)
1
80-85% Eff,
(MERV 13)
1

pg. 93

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

COILS AND SPACERS LISTED STARTING IN DIRECTION OF AIR FLOW


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
6
30
21
4.4
left
1-5/8
7/8
1
none

pg. 94

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

2150
30
76
66
55
53.9
489

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

0.19
0.06
0.11
0.05

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.55
1.1
0.12
0.3
0.1
0.6
0.2
0.33
3.71

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
30
19
41
10
12
18
18
148

width
(in)
33
33
33
33
33
33
33
33

height
(in)
39
39
39
39
39
39
39
39

weight
(lbs.)
223
473
412
70
67
138
156
1539

pg. 95

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.05
UNIDAD:
UMA-C-03
CAUDAL (cfm)
1.950
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.33

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx14w
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx10w
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 96

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.81/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2091
BHP: 2.4
Fan BHP w/ Belt Loss: 2.57
Outlet Velocity (ft/min): 2125

Motor Type: TECO ODP Premium Efficiency


HP=3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 11.8
Motor HP: 3.0
Rated Input Voltage: 3 Phase 208-240 VAC +/-10% 48/63Hz +/- 5%
Rated Input Current Amps: 11.80
Heat Loss in Watts 100% Load: 116.00
Efficiency (%): 98.00

pg. 97

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.26


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
30HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

High Eff. Filter Air Pressure Drop (in.


0.56
w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
80-85%
Spare Filter Media:
MERV13
Spare Filter Quantity Set(s):
1
pg. 98

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow

Coil General/Physical Details


Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
12
6
27.5
21
4
left
1-5/8
7/8
1
none

pg. 99

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

1950
30
76
66
55
53.9
488

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.33
0.26
0.1
0.89

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.81

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
20
10
19
40
10
27
21
17
164

width
(in)
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
171
83
492
529
74
164
164
153
1830

pg. 100

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.06
UNIDAD:
UMA-C-04
CAUDAL (cfm)
1.400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx10w
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 101

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.83/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 24HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2058
BHP: 1.47
Fan BHP w/ Belt Loss: 1.6
Outlet Velocity (ft/min): 1925

Motor Type: TECO ODP Premium Efficiency


HP=2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 7.5
Motor HP: 2.0
Motor Control Options
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

pg. 102

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.21


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

pg. 103

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow

Coil General/Physical Details


Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
12
5
20
27
3.8
left
1-5/8
7/8
1
none

pg. 104

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Air Side Performance


ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

1400
30
80
77
54.8
54.7
368

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.16
0.21
0.1
0.5

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.83

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
18
10
19
40
10
27
21
15
160

width
(in)
39
39
39
39
39
39
39
39
39

height
(in)
30
30
30
30
30
30
30
30
30

weight
(lbs.)
160
85
476
511
72
167
167
141
1779

pg. 105

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.07
UNIDAD:
UMA-D-03
CAUDAL (cfm)
5300
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.64
Outside Air (OA)
5300
15.25Hx43.00W
4.55
Front-High(Front)
(1)15.25x43
control
25% MIN/MAX
cd60
galvanized
parallel
n/a
UNlinked

Return/Mixed Air
5300
15.25Hx43.00W
4.55
BOTTOM
(1)15.25x43
control
100%
cd60
galvanized
parallel
n/a
UNlinked

2"Pleated 30% (MERV 8)

16
(8)24x12
side
0.15
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX26W
Standard Door Latch, No Lock, Outward
Opening
FILTER GAUGE (MINIHELIC)(0-0.5 IN WC)

pg. 106

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 5300
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.0/1.1
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 36HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 15-15
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1387
BHP: 5.92
Fan BHP w/ Belt Loss: 6.25
Outlet Velocity (ft/min): 2315

Motor Type: TECO ODP Premium Efficiency


HP=7.5
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 213
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 19.1
Efficiency: 91.0%

pg. 107

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.21

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(2)24x20;(2)24X12 Interior Galvanized Liner
10.7
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
2"
Exterior Galvanized Liner
Combined Filter Gauge
Prefilter Media:
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
24HX18W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.27
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
90-95% MERV14
High Eff. Filter Air Pressure Drop
0.58
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
90-95%MERV14
Spare Filter Quantity Set(s):
1
pg. 108

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
8
13
35.2
45
10.2
left
2-1/8
1-3/8
1
none

pg. 109

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Air Side Performance


ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

5300
30
77
67
55
54

STATIC PRESSURE SUMMARY


Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

0.06
0.1
0.23
0.05
0.15
0.05
0.55

Cooling 6 rows 8 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.1
0.21
0.27
0.1
0.58
0.2
0.35
4

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
29
19
50
11
27
18
19
173

width
(in)
57
57
57
57
57
57
57
57

height
(in)
42
42
42
42
42
42
42
42

weight
(lbs.)
409
632
824
115
231
213
262
2686

pg. 110

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.08
UNIDAD:
UMA-D-04
CAUDAL (cfm)
4900
SECCION (plg x plg):42X57
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.57
Outside Air (OA)
4900
15.25Hx43.00W
4.55
Front-High(Front)
(1)15.25x43
control
25% MIN/MAX
cd60
galvanized
parallel
n/a
UNlinked

Return/Mixed Air
4900
15.25Hx43.00W
4.55
BOTTOM
(1)15.25x43
control
100%
cd60
galvanized
parallel
n/a
UNlinked

2"Pleated 30% (MERV 8)

16
(8)24x12
side
0.13
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX26W
Standard Door Latch, No Lock, Outward
Opening
pg. 111

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

FILTER GAUGE (MINIHELIC)(0-0.5 IN WC)


birdsccreen

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 4900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.62/0.90
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 36HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 15-11
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1263
BHP: 4.64
Fan BHP w/ Belt Loss: 4.96
Outlet Velocity (ft/min): 2666

Motor Type: TECO ODP Premium Efficiency


HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

pg. 112

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.27

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:

(2)24x20;(2)24X12

Filter Area (ft)

10.7

Filter Loading:

Side

Prefilter Depth:

2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.24


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95% MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam
Insulation
Galvanized Floor Liner STD
Gauge
Exterior Galvanized Liner
Combined Filter Gauge
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
36HX18W
Multi-Point Door Latch, No
Lock, Outward Opening
Optimized Filter Arrangement

0.51
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV14
1
pg. 113

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
13
32.5
45
10.2
left
2-1/8
1-1/8
1
none

pg. 114

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Air Side Performance


ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

4900
30
77
67
55
54
480

STATIC PRESSURE SUMMARY


Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

0.06
0.1
0.19
0.04
0.13
0.05

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.53
0.9
0.27
0.24
0.1
0.51
0.2
0.3
3.62

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
29
19
37
11
27
18
19
160

width
(in)
57
57
57
57
57
57
57
57

height
(in)
42
42
42
42
42
42
42
42

weight
(lbs.)
409
621
724
111
231
213
262
2571

pg. 115

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.09
UNIDAD:
UMA-D-05
CAUDAL (cfm)
1700
SECCION (plg x plg):36X33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.25

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 4.0
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 116

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.47/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 10-7
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1770
BHP: 1.5
Fan BHP w/ Belt Loss: 1.62
Outlet Velocity (ft/min): 1853

Motor Type: TECO ODP Premium Efficiency


HP= 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 7.5
Motor HP: 2.0
Motor Control Options Environmental
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

pg. 117

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.13

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24X24
4
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.21


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
30HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 118

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.25
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
7/8
1
none

pg. 119

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Air Side Performance


ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

1700
30
80
77
57.6
57.4
425

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.25
0.21
0.1
0.47

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.1
0.13
0.21
0.1
0.45
0.2
0.25
3.47

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
20
10
19
40
10
27
21
17
164

width
(in)
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
171
83
475
511
74
164
164
153
1795

pg. 120

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.10
UNIDAD:
UMA-G-04
CAUDAL (cfm)
1400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 121

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.84/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 24HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2060
BHP: 1.47
Fan BHP w/ Belt Loss: 1.61
Outlet Velocity (ft/min): 1925

Motor Type: TECO ODP Premium Efficiency


HP= 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 7.5
Motor HP: 2.0
Motor Control OptionS
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

pg. 122

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24X20
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.21


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1
pg. 123

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.16
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
8
20
24
3.8
left
1-5/8
7/8
1
none

pg. 124

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Air Side Performance


ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

1500
30
80
77
57.6
57.4
395

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil

SUPPLY(in.wg)
0.16
0.21
0.1
0.51

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

FS-DWDI Supply Fan


DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

1.6
0.14
0.21
0.1
0.45
0.2
0.16
3.84

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
18
10
19
40
10
27
21
15
160

width
(in)
39
39
39
39
39
39
39
39
39

height
(in)
30
30
30
30
30
30
30
3
39

weight
(lbs.)
160
85
482
511
72
167
167
141
1785

pg. 125

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.11
UNIDAD:
UMA-A-03
CAUDAL (cfm)
3550
SECCION (plg x plg):42X51
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.21

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (4) 20X16
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 8.9
Filter Air Pressure Drop (in. w.g.): 0.19
Dirty Filter Allowance (in. w.g.): 0.05
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 126

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3550
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.04/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 36HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 12-12
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1484
BHP: 3.0
Fan BHP w/ Belt Loss: 3.2
Outlet Velocity (ft/min): 2138

Motor Type: TECO ODP Premium Efficiency


HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.20
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth
pg. 127

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(4)20X16
8.9
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.19


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
36HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.41
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.21
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 128

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
13
32.5
39
8.8
left
2-1/8
1-3/8
1
none

3550
30
80
77
57.6
57.4
403

pg. 129

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.21
0.19
0.05
0.5

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.8
0.18
0.19
0.1
0.41
0.2
0.21
3.04

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
19
10
19
47
10
12
18
19
154

width
(in)
51
51
51
51
51
51
51
51
51

height
(in)
42
42
42
42
42
42
42
42
42

weight
(lbs.)
243
119
595
632
99
97
201
243
2229

pg. 130

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.12
UNIDAD:
UMA-A-04
CAUDAL (cfm)
2900
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.24

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 6.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 131

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.43/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1507
BHP: 2.55
Fan BHP w/ Belt Loss: 2.73
Outlet Velocity (ft/min): 2194

Motor Type: TECO ODP Premium Efficiency


HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth
pg. 132

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(1)24X24;(1)24X24 Interior Galvanized Liner
6
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
2"
Exterior Galvanized Liner
Combined Filter Gauge
Prefilter Media:
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
30HX18W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.26
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
90-95% MERV14
High Eff. Filter Air Pressure Drop
0.55
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
90-95%MERV14
Spare Filter Quantity Set(s):
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 133

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
6
11
27.5
36
6.9
left
2-1/8
1-3/8
1
none

2900
30
80
77
57.6
57.4
420

pg. 134

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.24
0.26
0.1
0.49

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.8
0.19
0.26
0.1
0.55
0.2
0.24
3.43

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
17
10
19
34
10
12
21
17
140

width
(in)
48
48
48
48
48
48
48
48
48

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
199
104
561
471
89
90
206
199
1919

pg. 135

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.13
UNIDAD:
UMA-A-05
CAUDAL (cfm)
3000
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.26

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2) . 6.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 136

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.55/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1533
BHP: 2.74
Fan BHP w/ Belt Loss: 2.93
Outlet Velocity (ft/min): 2270

Motor Type: TECO ODP Premium Efficiency


HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.20

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

pg. 137

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(1)24X24;(1)2X24 Interior Galvanized Liner
6
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
2"
Exterior Galvanized Liner
Combined Filter Gauge
Prefilter Media:
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
30HX18W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.27
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
90-95% MERV14
High Eff. Filter Air Pressure Drop
0.58
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
90-95%MERV14
Spare Filter Quantity Set(s):
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.26
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 138

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
11
27.5
36
6.9
left
2-1/8
1-3/8
1
none

3000
30
80
77
57.6
57.4
435

pg. 139

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

IP Inlet Plenum Segment


FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment

OVERALL

SUPPLY(in.wg)
0.26
0.27
0.1
0.51

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

Section

DP Discharge Plenum Segment

RESPONSABLE: F.CH.

Length
(in)
17
10
19
34
10
12
21
17
140

width
(in)
48
48
48
48
48
48
48
48
48

0.8
0.2
0.27
0.1
0.58
0.2
0.26
3.55

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
199
104
561
471
89
90
206
199
1919

pg. 140

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.14
UNIDAD:
UMA-A-06
CAUDAL (cfm)
3000
SECCION (plg x plg):36X48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.24

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)20X24; (1)12X24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
5.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 141

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.24/0.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 12-9
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1464
BHP: 1.95
Fan BHP w/ Belt Loss: 2.1
Outlet Velocity (ft/min): 1816

Motor Type: TECO ODP Premium Efficiency


HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.13

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

pg. 142

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details

Filter Segment Options

Filter Area (ft)


Filter Loading:
Prefilter Depth:

(1)20X24;
(1)12X24
5.3
Side
2"

Prefilter Media:

Pleated 30%

(Quantity)Filter Sizes:

(MERV 8)
Prefilter Air Pressure Drop (in. w.g.): 0.23
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Interior Galvanized Liner


Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
30HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENT DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 143

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
11
27.5
30
5.7
left
2-1/8
1-3/8
1
none

2400
30
80
77
57.6
57.4
421

pg. 144

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.24
0.23
0.1
0.48

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.8
0.13
0.23
0.1
0.49
0.2
0.24
3.24

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
17
10
19
44
10
12
21
17
150

width
(in)
42
42
42
42
42
42
42
42
42

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
181
95
531
513
84
83
190
181
1858

pg. 145

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.15
UNIDAD:
UMA-A-07
CAUDAL (cfm)
1400
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.16

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.21
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24hx10w
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 146

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.97/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 24HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 9-6
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 2095
BHP: 1.52
Fan BHP w/ Belt Loss: 1.64
Outlet Velocity (ft/min): 1925

Motor Type: TECO ODP Premium Efficiency


HP= 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 2.61
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 4.1
Motor HP: 2.0
Motor Control Options
Fused Disconnect
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

pg. 147

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.14

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24X20
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.21


Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.45
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

pg. 148

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

Discharger Plenum Details


Segment Air Pressure Drop (in. w.g.) 0.16
Opening: BOTTOM

RESPONSABLE: F.CH.

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
8
20
27
3.8
left
1-5/8
1-1/8
1
none

pg. 149

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

1400
30
80
77
57.6
57.4
368

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.16
0.21
0.1
0.44

Cooling 6 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.8
0.14
0.21
0.1
0.45
0.2
0.16
3.97

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
18
10
19
37
10
12
21
15
142

width
(in)
39
39
39
39
39
39
39
39
39

height
(in)
30
30
30
30
30
30
30
30
30

weight
(lbs.)
160
85
482
472
72
75
167
141
1654

pg. 150

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.16
UNIDAD:
UMA-A-08
CAUDAL (cfm)
1500
SECCION (plg x plg):30X39
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.18

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24X20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24hx10w
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 151

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1500
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.25/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 24HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 9-6
Construction: II
Bearing Options: EXTENDED LUBE
Fan RPM: 2168
BHP: 1.75
Fan BHP w/ Belt Loss: 1.89
Outlet Velocity (ft/min): 2062

Motor Type: TECO ODP Premium Efficiency


HP= 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 2.61
Efficiency: 86.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive Full Load Amps (FLA): 4.1
Motor HP: 2.0
Motor Control Options
Fused Disconnect
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

pg. 152

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.17

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24X20
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.23
0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

pg. 153

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.18
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
11
8
20
27
3.8
left
1-5/8
1-1/8
1
none

pg. 154

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

1500
30
80
77
57.6
57.4
395

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY(in.wg)
0.18
0.23
0.1
0.57

Cooling 6 rows 11 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.8
0.17
0.23
0.1
0.49
0.2
0.18
4.25

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
18
10
19
37
10
12
21
15
142

width
(in)
39
39
39
39
39
39
39
39
39

height
(in)
30
30
30
30
30
30
30
30
30

weight
(lbs.)
160
85
484
485
72
75
167
141
1669

pg. 155

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.17
UNIDAD:
UMA-A-09
CAUDAL (cfm)
6000
SECCION (plg x plg):48X60
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.30

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (2)24x24; (2)24x12
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
12.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 42hx10w
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 156

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 6000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.53/1.4
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 42HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail

Motor Detail (per motor)

Type: FC
Size: 15-15
Construction: II
Bearing Options: EXTENDED LUBE
Fan RPM: 1477
BHP: 7.55
Fan BHP w/ Belt Loss: 7.96
Outlet Velocity (ft/min): 2621

Motor Type: TECO ODP Premium Efficiency


HP= 10.0.
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 215
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 25.0
Efficiency: 91.7

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.26

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

pg. 157

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(2)24X24;(2)24X12 Interior Galvanized Liner
12
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
2"
Exterior Galvanized Liner
Combined Filter Gauge
Prefilter Media:
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
42HX18W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.27
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
90-95% MERV14
High Eff. Filter Air Pressure Drop
0.58
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
90-95%MERV14
Spare Filter Quantity Set(s):
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.40
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 42HX18W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 158

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
15
37.5
48
12.5
left
2-1/8
1-3/8
1
none

6000
30
80
77
57.6
57.4
480

pg. 159

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

Cooling 6 rows 11 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

SUPPLY(in.wg)
0.3
0.27
0.1
0.65
1.4
0.26
0.27
0.1
0.58
0.2
0.4
4.53

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length width height weight


(in)
(in)
(in)
(lbs.)
26
60
48
358
10
60
48
141
19
60
48
675
36
60
48
706
12
60
48
133
12
60
48
110
18
60
48
233
26
60
48
358
159
60
48
2714

pg. 160

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.18
UNIDAD:
UMA-F-01
CAUDAL (cfm)
2700
SECCION (plg x plg):33X45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.6
Outside Air (OA)
2700
9.50HX31.0W
2.05
Front-LOW(Front)
(1)9.5X31
control
100%
cd60
galvanized
parallel
n/a
linked

Return/Mixed Air
2700
9.50HX31.0W
2.05
TOP
(1)9.5X31
control
100%
cd60
galvanized
parallel
n/a
linked

2"Pleated 30% (MERV 8)

8.89
(4)16X20
side
0.13
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27HX34W
Standard Door Latch, No Lock, Outward
Opening

pg. 161

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.23/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 27HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: permanent seal
Fan RPM: 2016
BHP: 3.3
Fan BHP w/ Belt Loss: 3.53
Outlet Velocity (ft/min): 2242

Motor Detail (per motor)


baldor ODP premium efficiency
HP= 5
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.20

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 162

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


(1)24X24;(1)12X24 Interior Galvanized Liner
Insulation: R-13 Foam
6
Insulation
Galvanized Floor Liner STD
Side
Gauge
2"
Exterior Galvanized Liner
Combined Filter Gauge
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
27HX18W
Multi-Point Door Latch, No
0.23
Lock, Outward Opening
0.1
Optimized Filter Arrangement
12" Rigid
90-95% MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.31
Opening: BOTTOM

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27HX13W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 163

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
9
22.5
33
5.2
left
1-5/8
1-1/8
1
none

2700
30
80
77
57.6
57.4
519

pg. 164

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

0.29
0.13
0.13
0.05

Cooling 6 rows 9 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.64
1.5
0.2
0.23
0.1
0.45
0.2
0.31
4.23

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
37
19
41
10
12
21
16
156

width
(in)
45
45
45
45
45
45
45
45

height
(in)
33
33
33
33
33
33
33
33

weight
(lbs.)
286
500
467
74
71
169
161
1728

pg. 165

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.19
UNIDAD:
UMA-F-02
CAUDAL (cfm)
2400
SECCION (plg x plg):33X42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.57
Outside Air (OA)
2400
9.50HX28.0W
1.85
Front-LOW(Front)
(1)9.5X28
control
100%
cd60
galvanized
parallel
n/a
linked

Return/Mixed Air
2400
9.50HX28.0W
1.85
TOP
(1)9.5X28
control
100%
cd60
galvanized
parallel
n/a
linked

2"Pleated 30% (MERV 8)

8.89
(4)16X20
side
0.11
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27HX34W
Standard Door Latch, No Lock, Outward
Opening

pg. 166

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.17/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 27HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: permanent seal
Fan RPM: 2016
BHP: 3.01
Fan BHP w/ Belt Loss: 3.22
Outlet Velocity (ft/min): 1993

Motor Detail (per motor)


baldor ODP premium efficiency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

pg. 167

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


(1)20X24;(1)12X24 Interior Galvanized Liner
Insulation: R-13 Foam
5.3
Insulation
Galvanized Floor Liner STD
Side
Gauge
2"
Exterior Galvanized Liner
Combined Filter Gauge
Pleated 30%
(Minihelic) (0 - 2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
27HX18W
Multi-Point Door Latch, No
0.23
Lock, Outward Opening
0.1
Optimized Filter Arrangement
12" Rigid
90-95% MERV14
0.45
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV14
1

pg. 168

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27HX13W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
11
5
22.5
30
4.7
left
1-5/8
7/8
1
none

pg. 169

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

2400
30
80
77
57.6
57.4
511

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

0.28
0.13
0.11
0.05

Cooling 5 rows 11 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.67
1.5
0.15
0.23
0.1
0.45
0.2
0.3
4.17

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
37
19
41
10
12
21
16
156

width
(in)
42
42
42
42
42
42
42
42

height
(in)
33
33
33
33
33
33
33
33

weight
(lbs.)
274
482
457
72
69
164
153
1671

pg. 170

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.20
UNIDAD:
UMA-F-03
CAUDAL (cfm)
4200
SECCION (plg x plg):33X42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.38
Outside Air (OA)
4200
15.25HX37.00W
3.92
Front-high (Front)
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
4200
15.25HX37.00W
3.92
TOP
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

17.78
(8)20x16
side
0.1
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36hx30w
Standard Door Latch, No Lock, Outward
Opening

pg. 171

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 4200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.84/1.2
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 36HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1632
BHP: 4.7
Fan BHP w/ Belt Loss: 5.03
Outlet Velocity (ft/min): 31778

Motor Detail (per motor)


baldor ODP premium efficiency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.35

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 172

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(4)30X16
8.9
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.25
0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
36HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.53
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.30
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36HX12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 173

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
9
32.5
39
8.8
left
1-5/8
1-1/8
1
none

4200
30
76
67
55
54.2
477

pg. 174

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.19
0.04
0.1
0.05
0.53
1.2
0.35
0.25
0.1
0.53
0.2
0.3
3.84

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length width height weight


(in)
(in)
(in)
(lbs.)
33
51
42
324
19
51
42
565
34
51
42
488
10
51
42
86
12
51
42
84
18
51
42
181
19
51
42
227
145
51
42
1955

pg. 175

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.21
UNIDAD:
UMA-F-04
CAUDAL (cfm)
3900
SECCION (plg x plg):36x60
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.28
Outside Air (OA)
3900
15.25hx46w
4.87
Front-low (Front)
(1)15.25x46
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
3900
15.25hx46w
4.87
TOP
(1)15.25x46
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

16
(8)24x12
side
0.1
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX28W
Standard Door Latch, No Lock, Outward
Opening
pg. 176

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.81/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1612
BHP: 4.2
Fan BHP w/ Belt Loss: 4.49
Outlet Velocity (ft/min): 2951

Motor Detail (per motor)


baldor ODP premium efficiency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.35

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 177

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(2)24X24
8
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.26
0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 2 in. w. c.)
Access Door on Left Side(Left)
30HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.56
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 178

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
9
11
27.5
48
9.2
left
2-1/8
1-1/8
1
none

3900
30
76
67
55
54.2
424

pg. 179

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

STATIC PRESSURE SUMMARY


Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

FM Filter / Mixing Box

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

RESPONSABLE: F.CH.

0.11
0.02
0.1
0.05

Cooling 5 rows 9 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.36
1.5
0.31
0.26
0.1
0.56
0.2
0.24
3.81

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
31
19
34
10
12
21
17
144

width
(in)
60
60
60
60
60
60
60
60

height
(in)
36
36
36
36
36
36
36
36

weight
(lbs.)
316
560
501
87
86
203
216
1969

pg. 180

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.22
UNIDAD:
UMA-F-05
CAUDAL (cfm)
1800
SECCION (plg x plg):36x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: Front(Front
Segment Air Pressure Drop (in. w.g.) 0.28

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge

fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)

fan segment option


0
1800
30
1.79/1.1
front(front)
rear(rear)

1" Spring Isolator


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx18w
Standard Door Latch, No Lock, Outward
Opening

fc
10-10
S
permanent
seal

1283
0.88
0.97
1495

pg. 181

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

motor detail (per motor)


Motor type: Baldor ODP premium efficency
HP
1
230/3/60
Voltage/Phase/Frequency:
hz
Insulation Class:
F
Motor RPM:
1800
Frame Size:
143
Location:
left(left)
Drive Type:
belt drive
Belt Drive Type:
fixed
Full Load Amps (FLA):
3
Efficiency:
85.50%

SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.41
Return/Exhaust Air Pressure Drop (in. w.g.) 0.41

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM

Outside Air(OA)

Mixed Air (MA)

Exhaust Air (EA)

Return Air (RA)

1800
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a

1800
21HX10W
1.46
midle-angled
(1)21x10
control
200%
CD61
Galvanized
parallel
n/a

1800
21HX11W
1.6
right(right)
(1)21x11
control
300%
CD62
Galvanized
parallel
n/a

1800
N/A
N/A
none
none
none
none
none
none
none
n/a

Economizer segment options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Exhaust Air Doors:
No Doors
Outside Air Doors:
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward Opening
birdscreen
pg. 182

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1800
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.23/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

pg. 183

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: permanent seal
Fan RPM: 1966
BHP: 1.95
Fan BHP w/ Belt Loss: 2.11
Outlet Velocity (ft/min): 1962

RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 11.8
Motor HP: 3.0
Motor Control Options
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet
Input
Rated Input Voltage: 3 Phase 208-240 VAC +/-10% 48/63Hz +/- 5%
Rated Input Current Amps: 11.80
Heat Loss in Watts 100% Load: 116.00
Efficiency (%): 98.00
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes

pg. 184

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(2)24X24
4
Side
4"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):

0.2
0.1

High Eff. Filter Depth:

21" Rigid

High Eff. Filter Media:


High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):

90-95% MERV15

Spare Filter Media:


Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Pre-Filter Gauge (Minihelic) (0-0.5
in. w. c.)
Access Door on Left Side(Left)
30HX20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement
Primary filter gauge(minihelic)(0-1
in wc)

0.48
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV15

pg. 185

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.28
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30HX14W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
7/8
1
none

pg. 186

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

1800
30
79.5
68.5
55.3
54.2
450

STATIC PRESSURE SUMMARY


Supply
(in.wg)
IP Inlet Plenum
FR-DWDI Return Fan
EE Economizer

FF Flat Filter
CC Variable Length Cooling
Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

Opening Pressure Drop


External Static Pressure - User
Entered Pressure Drop
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
Cooling 5 rows 10 fins
External Static Pressure - User
Entered Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
21" Bag 90-95% Eff, (MERV 15)

DP Discharge Plenum

Dirty Filter Allowance


Opening Pressure Drop

Return
(in.wg)
0.28
1.1
0.02
0.1
0.21
0.08

0.02
0.1
0.21
0.08
0.23
0.1
0.48
1.6
0.15
0.2
0.1
0.48
0.2
0.28
4.23

1.79

pg. 187

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
17
41
41
10
19
40
10
12
30
17
237

width
(in)
33
33
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36
36
36

weight
(lbs.)
153
406
327
83
475
529
74
74
220
153
2494

pg. 188

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.23
UNIDAD:
UMA-F-06
CAUDAL (cfm)
3200
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.33
Outside Air (OA)
3200
15.25Hx34W
3.6
Front-low (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
3200
15.25Hx34W
3.6
TOP
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

11.11
(2)24x20;(2)16x20
side
0.12
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36Hx29W
Standard Door Latch, No Lock, Outward
Opening

pg. 189

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3200
Altitude (ft.): 9
TSP/ESP (in. w.g.): 3.98/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1622
BHP: 3.29
Fan BHP w/ Belt Loss: 3.52
Outlet Velocity (ft/min): 2421

Motor Detail (per motor)


Baldor ODP premium effciency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.22

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 190

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


(1)24x24;(1)12x24 Interior Galvanized Liner
Insulation: R-13 Foam
6
Insulation
Galvanized Floor Liner STD
Side
Gauge
2
Exterior Galvanized Liner
Combined Filter Gauge
Pleated 30%
(Minihelic) (0-2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
36Hx18W
Multi-Point Door Latch, No
0.3
Lock, Outward Opening
0.1
Optimized Filter Arrangement
12" Rigid
90-95% MERV13
0.59
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV13
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.2
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36Hx12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 191

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
8
7
32.5
36
8.1
left
1-5/8
1-1/8
1
none

3200
9
76.5
67.5
58.1
56.4
395

BDX Tube Spacing: 1.25" x 1.08"

pg. 192

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


FM Filter / Mixing Box

Opening Pressure Drop


Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

Supply (in.wg)
0.13
0.03
0.12
0.05
0.24

Cooling 4 rows 8 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.8
0.22
0.3
0.1
0.59
0.2
0.2
3.98

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
32
17
34
10
12
18
19
142

width
(in)
48
48
48
48
48
48
48
48

height
(in)
42
42
42
42
42
42
42
42

weight
(lbs.)
306
499
478
84
82
178
217
1844

pg. 193

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.24
UNIDAD:
UMA-F-07
CAUDAL (cfm)
3700
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.42
Outside Air (OA)
3700
15.25Hx34W
3.6
Front-low (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
3700
15.25Hx34W
3.6
TOP
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

11.11
(2)24x20;(2)16x20
side
0.15
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36Hx29W
Standard Door Latch, No Lock, Outward
Opening

pg. 194

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3700
Altitude (ft.): 9
TSP/ESP (in. w.g.): 4.61/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1749
BHP: 4.5
Fan BHP w/ Belt Loss: 4.82
Outlet Velocity (ft/min): 2800

Motor Detail (per motor)


Baldor ODP premium effciency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.29

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

pg. 195

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(1)24x24;(1)12x24 Interior Galvanized Liner
6
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
2
Exterior Galvanized Liner
Combined Filter Gauge
Prefilter Media:
Pleated 30%
(Minihelic) (0-2 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
36Hx18W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.38
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
80-85% MERV13
High Eff. Filter Air Pressure Drop
0.76
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
80-85%MERV13
Spare Filter Quantity Set(s):
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.27
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36Hx12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 196

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
10
32.5
36
8.1
left
1-5/8
1-1/8
1
none

3700
9
76.5
67.5
57.5
55.9
457

BDX Tube Spacing: 1.25" x 1.08"

pg. 197

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


FM Filter / Mixing Box

Opening Pressure Drop


Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

Supply (in.wg)
0.18
0.04
0.15
0.05

Cooling 4 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 80-85% Eff, (MERV 13)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.39
1.8
0.29
0.38
0.1
0.76
0.2
0.27
4.61

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
32
17
34
10
12
18
19
142

width
(in)
48
48
48
48
48
48
48
48

height
(in)
42
42
42
42
42
42
42
42

weight
(lbs.)
306
508
478
84
82
178
217
1853

pg. 198

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.25
UNIDAD:
UMA-F-08/9
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
2
SECUENCIA DE SEGMENTOS:
DP<RF<XA<DI<FS<CC<<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FR
return segment fan
Segment Air Pressure Drop
(in. w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge

fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)

fan segment option


0
2000
30
1.94/1.1
front(front)
rear(rear)

1" Spring Isolator


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx18w
Standard Door Latch, No Lock, Outward
Opening

fc
10-10
S
permanent seal

1332
1.05
1.15
1661

pg. 199

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

motor detail (per motor)


Motor type: Baldor ODP premium efficency
HP
1.5
Voltage/Phase/Frequency:
230/3/60 hz
Insulation Class:
F
Motor RPM:
1800
Frame Size:
145
Location:
left(left)
Drive Type:
belt drive
Belt Drive Type:
fixed
Full Load Amps (FLA):
4.5
Efficiency:
86.50%

SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM

Outside Air(OA)

Mixed Air (MA)

Exhaust Air (EA)

Return Air (RA)

2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a

2000
21HX10W
1.46
midle-angled
(1)21x10
control
200%
CD60
Galvanized
parallel
n/a

2000
21HX11W
1.6
right(right)
(1)21x11
control
300%
CD60
Galvanized
parallel
n/a

2000
N/A
N/A
none
none
none
none
none
none
none
n/a

Economizer segment options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Exhaust Air Doors:
No Doors
Outside Air Doors:
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward Opening
birdsecreen
pg. 200

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.68/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30HX18W
Standard Door Latch, No Lock, Outward
Opening

pg. 201

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: permanent seal
Fan RPM: 2052
BHP: 2.38
Fan BHP w/ Belt Loss: 2.55
Outlet Velocity (ft/min): 2180

RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Motor HP= 3.0
Motor Control Options
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)

Motor Control
Electrical Details
Full Load Amps (FLA):
11.8

Environmental
Ambient Temperature
(F): 5 to 104
Storage Temperature
(F): -40 to 158
Humidity: MAX 95% RH
non-condensing
Altitude: 3,300 ft. without
derate (1% derate
for each additional 330
ft.)
Enclosure: NEMA 3R

Modbus RTU, Johnson N2, Siemens FLN, BACnet


input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):

3 Phase 208-240 VAC


+/-10% 48/63Hz +/- 5%
11.8
116
98%

Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.

pg. 202

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
4

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):

0.24
0.1

High Eff. Filter Depth:

21" Rigid

High Eff. Filter Media:

90-95%
MERV15

High Eff. Filter Air Pressure Drop


(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Prefilter gauge Minihelic(0-0.5 in
wg)
Access Door on Left Side(Left)
30Hx20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement
Primary filter gauge Minihelic(01in.wg)

0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1

pg. 203

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
7/8
1
none

pg. 204

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

2000
30
80.5
69.5
55.2
54.3
500

BDX Tube Spacing: 1.25" x 1.08"

STATIC PRESSURE SUMMARY


supply
(in.wg)
IP Inlet Plenum
FR-DWDI Return Fan
EE Economizer

FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter

DP Discharge Plenum

Opening Pressure Drop


External Static Pressure - User Entered
Pressure Drop
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
Cooling 6 rows 9 fins
External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
21" Bag 90-95% Eff, (MERV 15)
Dirty Filter Allowance
Opening Pressure Drop

return
(in.wg)
0.35
1.1
0.03
0.1
0.26
0.1

0.03
0.1
0.26
0.1
0.27
0.1
0.59
1.6
0.19
0.24
0.1
0.55
0.2
0.35
4.68

1.94

pg. 205

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
17
41
41
10
19
40
10
12
30
17
237

width
(in)
33
33
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36
36
36

weight
(lbs.)
153
416
327
83
483
529
74
74
220
153
2512

pg. 206

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.26
UNIDAD:
UMA-F-10
CAUDAL (cfm)
2900
SECCION (plg x plg):39x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.45
Outside Air (OA)
2900
15.25Hx34W
3.6
Front-high (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
2900
15.25Hx34W
3.6
bottom
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

12
(2)24x24;(2)12x24
side
0.1
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33Hx28w
Standard Door Latch, No Lock, Outward
Opening, birdscreen
pg. 207

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2900
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.73/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 33Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: permanent seal
Fan RPM: 1573
BHP: 2.76
Fan BHP w/ Belt Loss: 2.95
Outlet Velocity (ft/min): 2194

Motor Detail (per motor)


TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

pg. 208

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details

Filter Segment Options

Filter Area (ft)


Filter Loading:
Prefilter Depth:

(1)24x24,
(1)12x24
6
Side
4

Prefilter Media:

Pleated 30%

(Quantity)Filter Sizes:

(MERV 8)
Prefilter Air Pressure Drop (in. w.g.): 0.23
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.1
12" Rigid
90-95%
MERV14

Interior Galvanized Liner


Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge Minihelic( 0-2
in.wg)
Access Door on Left Side(Left)
30Hx20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33hX12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 209

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)
BDX Tube Spacing: 1.25" x 1.08"

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
30
36
7.5
left
1-5/8
7/8
1
none

2900
30
76.5
67
55.9
54.6
387

pg. 210

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


supply
(in.wg)
FM Filter / Mixing Box

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

0.11
0.03
0.1
0.05

Cooling 4 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.31
1.5
0.19
0.23
0.1
0.55
0.2
0.2
3.73

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
31
17
34
10
12
20
18
142

width height
(in)
(in)
48
39
48
39
48
39
48
39
48
39
48
39
48
39
48
39

weight
(lbs.)
369
517
478
92
92
209
216
1973

pg. 211

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.27
UNIDAD:
UMA-F-11
CAUDAL (cfm)
2700
SECCION (plg x plg):39x45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.44
Outside Air (OA)
2700
15.25Hx31W
3.28
Front-high (Front)
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
2700
15.25Hx31W
3.28
bottom
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

12
(2)24x24;(2)12x24
side
0.09
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33Hx28w
Standard Door Latch, No Lock, Outward
Opening
birdsccreen
pg. 212

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2700
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.95/1.8
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 33Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: AF
Size: 12-12
Construction: S
Bearing Options: extended lube
Fan RPM: 2628
BHP: 2.41
Fan BHP w/ Belt Loss: 2.58
Outlet Velocity (ft/min): 1626

Motor Detail (per motor)


TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.09

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 213

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details

Filter Segment Options

Filter Area (ft)


Filter Loading:
Prefilter Depth:

(1)24x24,
(1)12x24
6
Side
4

Prefilter Media:

Pleated 30%

(Quantity)Filter Sizes:

(MERV 8)
Prefilter Air Pressure Drop (in.
w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.2
0.1
12" Rigid
90-95%
MERV14

Interior Galvanized Liner


Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge Minihelic( 0-2
in.Wc)
Access Door on Left Side(Left)
33Hx20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.49
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Discharge Plenum Options
Segment Air Pressure Drop (in. w.g.) 0.21 Interior Galvanized Liner
Opening: bottom
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33hX12W
Multi-Point Door Latch, No Lock, Outward
Opening
pg. 214

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)
BDX Tube Spacing: 1.25" x 1.08"

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
10
30
33
6.9
left
1-5/8
1-1/8
1
none

2700
30
78
71.5
55.1
54.6
391

pg. 215

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY

FM Filter / Mixing Box

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

supply
(in.wg)
0.06
0.1
0.11
0.03
0.09
0.05
0.42

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.8
0.09
0.2
0.1
0.49
0.2
0.21
3.95

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
31
19
47
10
12
20
18
157

width
(in)
45
45
45
45
45
45
45
45

height
(in)
39
39
39
39
39
39
39
39

weight
(lbs.)
353
544
591
91
89
199
206
2073

pg. 216

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.28
UNIDAD:
UMA-F-12
CAUDAL (cfm)
2800
SECCION (plg x plg):39x45
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.45
Outside Air (OA)
2800
15.25Hx31W
3.28
Front-high (Front)
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unllinked

Return/Mixed Air
2800
15.25Hx31W
3.28
bottom
(1)15.25x31
control
100%
cd60
galvanized
parallel
n/a
unlinked

2"Pleated 30% (MERV 8)

12
(2)24x24;(2)12x24
side
0.09
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33Hx28w
Standard Door Latch, No Lock, Outward
Opening
birdsccreen
pg. 217

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2800
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.67/1.40
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Structural Steel Base
Access Door on Left Side(Left) 33Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1552
BHP: 2.58
Fan BHP w/ Belt Loss: 2.76
Outlet Velocity (ft/min): 2119

Motor Detail (per motor)


TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 218

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details

Filter Segment Options

Filter Area (ft)


Filter Loading:
Prefilter Depth:

(1)24x24,
(1)12x24
6
Side
4

Prefilter Media:

Pleated 30%

(Quantity)Filter Sizes:

(MERV 8)
Prefilter Air Pressure Drop (in.
w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.22
0.1
12" Rigid
90-95%
MERV14

Interior Galvanized Liner


Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge Minihelic( 0-2
in.Wc)
Access Door on Left Side(Left)
33Hx20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.52
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.22
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33hX12W
Multi-Point Door Latch, No Lock, Outward
Opening
pg. 219

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)
BDX Tube Spacing: 1.25" x 1.08"

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
11
8
30
33
6.9
left
1-5/8
7/8
1
none

2800
30
77
68.7
56.2
55.1
406

pg. 220

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY

FM Filter / Mixing Box

supply
(in.wg)
0.06
0.1
0.12
0.03
0.09
0.05

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length Cooling


Coil
Cooling 4 rows 11 fins
External Static Pressure - User Entered
FS-DWDI Supply Fan
Pressure Drop
DI Diffuser
Diffuser Air Pressure Drop
RF High Efficiency Filter
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
DP Discharge Plenum
Opening Pressure Drop
TOTAL

0.38
1.4
0.18
0.22
0.1
0.52
0.2
0.22
3.67

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
31
17
44
10
12
20
18
152

width
(in)
45
45
45
45
45
45
45
45

height
(in)
39
39
39
39
39
39
39
39

weight
(lbs.)
353
507
536
90
89
199
206
1980

pg. 221

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.29
UNIDAD:
UMA-F-13
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.53
Outside Air (OA)
2000
15.25Hx19W
2.01
Front-high (Front)
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
Linked

Return/Mixed Air
2000
15.25Hx19W
2.01
bottom
(1)15.25x19
control
100%
cd60
galvanized
parallel
n/a
Linked

2"Pleated 30% (MERV 8)

8
(2)24x24
side
0.1
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx38W
Standard Door Latch, No Lock, Outward
Opening
birdsccreen
pg. 222

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.15/1.40
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1920
BHP: 2.10
Fan BHP w/ Belt Loss: 2.25
Outlet Velocity (ft/min): 2180

Motor Detail (per motor)


TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
pg. 223

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

Access Segment Details


Segment Length: 12"

RESPONSABLE: F.CH.

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
4"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

24
0.1
12" Rigid
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge Minihelic( 0-2
in.Wc)
Access Door on Left Side(Left)
30Hx20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.58
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 224

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
27.5
21
4
left
1-5/8
5/8
1
none

2000
30
76
66.5
55.3
54.1
500

pg. 225

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY

FM Filter / Mixing Box

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

supply
(in.wg)
0.06
0.1
0.17
0.05
0.1
0.05

Cooling 5 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.56
1.4
0.19
0.24
0.1
0.58
0.2
0.35
4.15

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
41
19
39
10
12
23
17
161

width height
(in)
(in)
33
36
33
36
33
36
33
36
33
36
33
36
33
36
33
36

weight
(lbs.)
339
475
407
74
74
176
153
1698

pg. 226

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.30
UNIDAD:
UMA-F-14
CAUDAL (cfm)
3300
SECCION (plg x plg):42x48
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.5
Outside Air (OA)
3300
15.25Hx34W
3.6
Front-high (Front)
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
Unlinked

Return/Mixed Air
3300
15.25Hx34W
3.6
bottom
(1)15.25x34
control
100%
cd60
galvanized
parallel
n/a
Unlinked

2"Pleated 30% (MERV 8)

12
(2)24x24;(2)12X24
side
0.12
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36hX31w
Standard Door Latch, No Lock, Outward
Opening
birdsccreen
pg. 227

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3300
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.05/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 36Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-12
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1717
BHP: 3.81
Fan BHP w/ Belt Loss: 4.08
Outlet Velocity (ft/min): 1987

Motor Detail (per motor)


Baldor ODP premium effciency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.15

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
pg. 228

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)

Filter Segment Options


(1)24x24;(1)12x24 Interior Galvanized Liner
6
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Filter Loading:
Side
Gauge
Prefilter Depth:
4"
Exterior Galvanized Liner
combined filter gauge Minihelic(
Prefilter Media:
Pleated 30%
0-2 in.Wc)
Access Door on Left Side(Left)
(MERV 8)
36Hx20W
Multi-Point Door Latch, No Lock,
Prefilter Air Pressure Drop (in. w.g.): 0.28
Outward Opening
Prefilter Dirty Allowance (in. w.g.):
0.1
Optimized Filter Arrangement
High Eff. Filter Depth:
12" Rigid
High Eff. Filter Media:
90-95% MERV14
High Eff. Filter Air Pressure Drop
0.67
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
0.2
w.g.):
Pleated 30%
Spare Filter Media:
(MERV 8)
Spare Filter Quantity Set(s):
1
Spare Filter Media:
90-95%MERV14
Spare Filter Quantity Set(s):
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.22
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 36Hx12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 229

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
32.5
36
801
left
1-5/8
7/8
1
none

3300
30
75.5
65.5
56.4
54.6
407

pg. 230

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY

FM Filter / Mixing Box

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

supply
(in.wg)
0.06
0.1
0.14
0.03
0.12
0.05
0.33

Cooling 4 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
4" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.6
0.15
0.28
0.1
0.67
0.2
0.22
4.05

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
34
17
47
10
12
20
19
159

width
(in)
48
48
48
48
48
48
48
48

height
(in)
42
42
42
42
42
42
42
42

weight
(lbs.)
405
524
620
96
94
216
233
2188

pg. 231

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.31
UNIDAD:
ver listado
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
4
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge

fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)

fan segment option


0
2000
30
1.64/.80
front(front)
rear(rear)

1" Spring Isolator


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx18w
Standard Door Latch, No Lock, Outward
Opening

FC
9-9
S
permanent
seal

1410
1.03
1.12
2002

pg. 232

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

motor detail (per motor)


Motor type: Baldor ODP premium efficency
HP
1.5
230/3/60
Voltage/Phase/Frequency:
hz
Insulation Class:
F
Motor RPM:
1800
Frame Size:
145
Location:
left(left)
Drive Type:
belt drive
Belt Drive Type:
fixed
Full Load Amps (FLA):
4.5
Efficiency:
86.50%

SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM

Outside Air(OA)

Mixed Air (MA)

Exhaust Air (EA)

Return Air (RA)

2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a

2000
21HX10W
1.46
midle-angled
(1)21x10
control
100%
CD60
Galvanized
parallel
n/a

2000
21HX11W
1.6
right(right)
(1)21x11
control
100%
CD60
Galvanized
parallel
n/a

2000
N/A
N/A
none
none
none
none
none
none
none
n/a

Economizer segment options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Exhaust Air Doors:
No Doors
Outside Air Doors:
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward Opening
birdsecreen

pg. 233

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.18/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30Hx18W
Standard Door Latch, No Lock, Outward
Opening

pg. 234

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1927
BHP: 2.12
Fan BHP w/ Belt Loss: 2.27
Outlet Velocity (ft/min): 2180

RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 11.8
Motor HP: 3.0
Motor Control Options
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

pg. 235

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
4"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.24


Prefilter Dirty Allowance (in. w.g.):

0.1

High Eff. Filter Depth:

21" bag

High Eff. Filter Media:

90-95%
MERV15

High Eff. Filter Air Pressure Drop


(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Prefilter Gauge (Minihelic) (0 - 0.5
in. w. c.)
Access Door on Left Side(Left) 30H
x 20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement
Primary Filter Gauge (Minihelic) (0 1 in. w. c.)

0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: REAR-REAR

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 236

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
5/8
1
none

2000
30
80.5
69
55.1
54
500

pg. 237

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


supply
(in.wg)
IP Inlet Plenum
FR-DWDI Return Fan
EE Economizer

FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter

DP Discharge Plenum

Opening Pressure Drop


External Static Pressure - User Entered
Pressure Drop
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

return
(in.wg)
0.35
0.8
0.03
0.1
0.26
0.1

0.03
0.1
0.26
0.1
0.27
0.1
0.59

Cooling 6 rows 9 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop

1.1
0.19
0.24

4" Pleated 30% (MERV 8)


Dirty Filter Allowance - Prefilter
21" Bag 90-95% Eff, (MERV 15)
Dirty Filter Allowance
Opening Pressure Drop

0.1
0.55
0.2
0.35
4.18

1.64

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
17
39
41
10
19
40
10
12
30
17
235

width
(in)
33
33
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36
36
36

weight
(lbs.)
153
392
327
83
483
529
74
74
220
153
2488
pg. 238

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.32
UNIDAD:
ver listado
CAUDAL (cfm)
2000
SECCION (plg x plg):36x33
CANTIDAD:
3
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.35

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge

fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)

fan segment option


0
2000
30
1.64/.80
front(front)
rear(rear)

1" Spring Isolator


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx18w
Standard Door Latch, No Lock, Outward
Opening

FC
9-9
S
permanent
seal

1409
1.03
1.12
2002

pg. 239

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

motor detail (per motor)


Motor type: Baldor ODP premium efficency
HP
1.5
230/3/60
Voltage/Phase/Frequency:
hz
Insulation Class:
F
Motor RPM:
1800
Frame Size:
145
Location:
left(left)
Drive Type:
belt drive
Belt Drive Type:
fixed
Full Load Amps (FLA):
4.5
Efficiency:
86.50%

SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.49
Return/Exhaust Air Pressure Drop (in. w.g.) 0.49
AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM

Outside Air(OA)

Mixed Air (MA)

Exhaust Air (EA)

Return Air (RA)

2000
21HX11W
1.6
left(left)
(1)21X11
control
100%
CD60
Galvanized
parallel
n/a

2000
21HX10W
1.46
midle-angled
(1)21x10
control
100%
CD60
Galvanized
parallel
n/a

2000
21HX11W
1.6
right(right)
(1)21x11
control
100%
CD60
Galvanized
parallel
n/a

2000
N/A
N/A
none
none
none
none
none
none
none
n/a

Economizer segment options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Exhaust Air Doors:
No Doors
Outside Air Doors:
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward Opening
birdsecreen

pg. 240

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.27
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2000
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.18/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30Hx18W
Standard Door Latch, No Lock, Outward
Opening

pg. 241

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1927
BHP: 2.12
Fan BHP w/ Belt Loss: 2.27
Outlet Velocity (ft/min): 2180

RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 11.8
Motor HP: 3.0
Motor Control Options
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet
Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.19

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth
pg. 242

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x24
4
Side
4"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in. w.g.): 0.24


Prefilter Dirty Allowance (in. w.g.):

0.1

High Eff. Filter Depth:

21" bag

High Eff. Filter Media:

90-95%
MERV15

High Eff. Filter Air Pressure Drop


(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Prefilter Gauge (Minihelic) (0 - 0.5
in. w. c.)
Access Door on Left Side(Left) 30H
x 20W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement
Primary Filter Gauge (Minihelic) (0 1 in. w. c.)

0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV15
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.35
Opening: REAR-REAR

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 243

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
9
6
27.5
21
4
left
1-5/8
5/8
1
none

2000
30
80.5
69
55.1
54
500

pg. 244

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


supply
(in.wg)
IP Inlet Plenum
FR-DWDI Return Fan
EE Economizer

FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter

DP Discharge Plenum

Opening Pressure Drop


External Static Pressure - User Entered
Pressure Drop
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

return
(in.wg)
0.35
0.8
0.03
0.1
0.26
0.1

0.03
0.1
0.26
0.1
0.27
0.1
0.59

Cooling 6 rows 9 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop

1.1
0.19
0.24

4" Pleated 30% (MERV 8)


Dirty Filter Allowance - Prefilter
21" Bag 90-95% Eff, (MERV 15)
Dirty Filter Allowance
Opening Pressure Drop

0.1
0.55
0.2
0.35
4.18

1.64

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
17
39
41
10
19
40
10
12
30
17
235

width
(in)
33
33
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36
36
36

weight
(lbs.)
153
392
327
83
483
529
74
74
220
153
2488
pg. 245

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.33
UNIDAD:
UMA-F-17
CAUDAL (cfm)
2400
SECCION (plg x plg):36x42
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<EE<FR<IP
SEGMENTO IP
Inlet Plenum Details
Opening: bottom
Segment Air Pressure Drop (in. w.g.) 0.24

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FR
return segment fan
Segment Air Pressure Drop (in.
w.g.):
Air Flow (CFM):
Altitude (ft.):
TSP/ESP (in. w.g.):
Air Inlet
Fan Discharge

fan detail
type
size
construction
bearing option
fan rpm
BHP
fan BHPw/belt loss
outlet velocity (fpm)

fan segment option


0
2400
30
1.39/0.80
front(front)
rear(rear)

1" Spring Isolator


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30hx18w
Standard Door Latch, No Lock, Outward
Opening

FC
9-9
S
permanent
seal

1407
1.33
1.45
2403

motor detail (per motor)


pg. 246

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Motor type: Baldor ODP premium efficency


HP
1.5
230/3/60
Voltage/Phase/Frequency:
hz
Insulation Class:
F
Motor RPM:
1800
Frame Size:
145
Location:
left(left)
Drive Type:
belt drive
Belt Drive Type:
fixed
Full Load Amps (FLA):
4.5
Efficiency:
86.50%

SEGMENTO EE
Segment detail
Supply Air Pressure Drop (in. w.g.) 0.35
Return/Exhaust Air Pressure Drop (in. w.g.) 0.35

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM

Outside Air(OA)

Mixed Air (MA)

Exhaust Air (EA)

Return Air (RA)

2400
21HX16W
2.33
left(left)
(1)21X16
control
100%
CD60
Galvanized
parallel
n/a

2400
21HX14W
2.04
midle-angled
(1)21x14
control
100%
CD60
Galvanized
parallel
n/a

2400
21HX16W
2.33
right(right)
(1)21x16
control
100%
CD60
Galvanized
parallel
n/a

2400
N/A
N/A
none
none
none
none
none
none
none
n/a

Economizer segment options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Exhaust Air Doors:
No Doors
Outside Air Doors:
Access Door on Left Side(Left) 30H x 18W
Standard Door Latch, No Lock, Outward Opening
birdsecreen

pg. 247

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)20x24;(1)12x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
5.3
Filter Air Pressure Drop (in. w.g.): 0.23
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 2400
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.65/1.10
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30Hx18W
Standard Door Latch, No Lock, Outward
Opening

pg. 248

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1820
BHP: 2.45
Fan BHP w/ Belt Loss: 2.62
Outlet Velocity (ft/min): 2616

RESPONSABLE: F.CH.
Motor Detail (per motor)
TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency Drive
Full Load Amps (FLA): 11.8
Motor HP: 3.0
Motor Control Options l
Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks (LON)
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.26

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth
pg. 249

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

Filter Segment Options


(1)20x24;(1)12x24 Interior Galvanized Liner
5.3
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD
Side
Gauge
4"
Exterior Galvanized Liner
Prefilter Gauge (Minihelic) (0 Pleated 30%
0.5 in. w. c.)
Access Door on Left Side(Left)
(MERV 8)
30H x 20W
Multi-Point Door Latch, No Lock,
0.2
Outward Opening
0.1
Optimized Filter Arrangement
Primary Filter Gauge (Minihelic)
21" bag
(0 - 1 in. w. c.)
90-95% MERV15
0.48
0.2
Pleated 30%
(MERV 8)
1
90-95%MERV15
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.24
Opening: REAR-REAR

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 250

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
8
6
27.5
30
5.7
left
1-5/8
7/8
1
none

2400
30
81.5
70.5
55.3
54.5
421

pg. 251

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


supply
(in.wg)
IP Inlet Plenum
FR-DWDI Return Fan
EE Economizer

FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency
Filter

DP Discharge Plenum

Opening Pressure Drop


External Static Pressure - User Entered
Pressure Drop
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

return
(in.wg)
0.24
0.8
0.02
0.1
0.18
0.05

0.02
0.1
0.18
0.05
0.23
0.1
0.39

Cooling 6 rows 8 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop

1.1
0.26
0.2

4" Pleated 30% (MERV 8)


Dirty Filter Allowance - Prefilter
21" Bag 90-95% Eff, (MERV 15)
Dirty Filter Allowance
Opening Pressure Drop

0.1
0.48
0.2
0.24
3.65

1.39

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FR-DWDI Return Fan Segment
EE Economizer Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
17
39
46
10
22
43
10
12
30
17
246

width
(in)
42
42
42
42
42
42
42
42
42
42
42

height
(in)
36
36
36
36
36
36
36
36
36
36
36

weight
(lbs.)
181
430
406
95
545
596
82
83
254
181
2853
pg. 252

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.34
UNIDAD:
UMA-H-01
CAUDAL (cfm)
1200
SECCION (plg x plg):30x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: TOP
Segment Air Pressure Drop (in. w.g.) 0.20

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.17
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 253

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.49/1.4
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 24Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1965
BHP: 1.14
Fan BHP w/ Belt Loss: 1.25
Outlet Velocity (ft/min): 1650

Motor Detail (per motor)


BALDOR ODP premium effciency
HP= 1.5
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 4.5
Efficiency: 86.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.10

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

pg. 254

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x20
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.17
0.1
12" RIGID
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge minihelic (01 in.wg)
Access Door on Left Side(Left)
24HX18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.36
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: TOP

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24Hx12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 255

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
6
20
21
2.9
left
1-5/8
5/8
1
none

1200
30
80
77
54.9
54.8
414

pg. 256

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


SEGMENT
IP Inlet Plenum
FF Flat Filter

SUPPLY
(in.wg)
0.2
0.17
0.05

COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

0.54

Cooling 6 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.4
0.1
0.17
0.1
0.36
0.2
0.2
3.49

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
15
10
19
37
10
12
21
15
139

width
(in)
33
33
33
33
33
33
33
33
33

height
(in)
30
30
30
30
30
30
30
30
30

weight
(lbs.)
116
67
441
326
59
59
135
116
1319

pg. 257

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.35
UNIDAD:
UMA-H-02/03
CAUDAL (cfm)
1950
SECCION (plg x plg):36X33
CANTIDAD:
2
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: front (front)
Segment Air Pressure Drop (in. w.g.) 0.33

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 14W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x24
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
4.0
Filter Air Pressure Drop (in. w.g.): 0.26
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 258

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1950
Altitude (ft.): 30
TSP/ESP (in. w.g.): 4.61/1.6
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 30Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 10-7
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 2042
BHP: 2.29
Fan BHP w/ Belt Loss: 2.45
Outlet Velocity (ft/min): 2125

Motor Detail (per motor)


TECO ODP premium effciency
HP= 3.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 182
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 8.6
Efficiency: 89.5%

Motor Control Details


Motor Control Type: Variable Frequency
Drive
Motor HP= 3.0

Motor Control Electrical Details

Motor Control Options


Fused Disconnect
Isolated Manual Bypass
Additional Communications: LONworks
(LON)

Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158

RFI/EMI EMC Filter


Swinging DC Line Choke (equivalent to 5%
Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN,
BACnet

Altitude: 3,300 ft. without derate (1% derate

Full Load Amps (FLA): 11.8

Humidity: MAX 95% RH non-condensing

for each additional 330 ft.)


Enclosure: NEMA 3R

pg. 259

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):

3 Phase 208-240 VAC +/-10% 48/63Hz +/5%


11.8
116
98%

Output
Output Current Amps: 11.8
Overload Current Rating: 110% for 1 minute every 10 minutes
Drives are rated for use below 3,300 ft and 104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.18

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30H x 24W
10" Additional Core Growth
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 260

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x20
4
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.26
0.1
12" RIGID
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
combined filter gauge minihelic (0-2
in.wg)
Access Door on Left Side(Left)
30Hx18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.56
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.33
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 30Hx14W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 261

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
6
10
6
27.5
21
4
left
1-5/8
5/8
1
none

1950
30
80
77
56.6
56.4
488

pg. 262

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


SEGMENT
IP Inlet Plenum
FF Flat Filter

SUPPLY
(in.wg)
0.33
0.26
0.1

COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

0.69

Cooling 6 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

1.6
0.18
0.26
0.1
0.56
0.2
0.33
4.61

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

OVERALL

Length
(in)
20
10
19
40
10
27
21
17
164

width
(in)
33
33
33
33
33
33
33
33
33

height
(in)
36
36
36
36
36
36
36
36
36

weight
(lbs.)
171
83
486
529
74
164
164
153
1824

pg. 263

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.36
UNIDAD:
UMA-H-05
CAUDAL (cfm)
3200
SECCION (plg x plg):39x51
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<<CC<FM
SEGMENTO FM
Segment Detail
Segment Air Pressure Drop (in. w.g.):

AirFlow (CFM)
Opening (QTY) Size
Area per Opening (ft)
Location
Damper (QTY) Size
Damper Type
Configuration
Damper Model
Damper Material
Blade Orientation
Min. Allowed CFM
Damper Linkage
Filter media detail
Filter Type
Filter Area (ft)
Filter QTY/Size
Load Option
Filter APD (in. w.g.)
Dirty Filter Allowance
Spare Filter Type
Spare Filter QTY

0.46
Outside Air (OA)
3200
15.25Hx37.00W
3.92
Front-high (Front)
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
Unlinked

Return/Mixed Air
3200
15.25Hx37.00W
3.92
bottom
(1)15.25x37
control
100%
cd60
galvanized
parallel
n/a
Unlinked

2"Pleated 30% (MERV 8)

11.11
(2)24x20; (2)16x20
side
0.12
0.05
2"Pleated 30% (MERV 8)

filter mixing box segment option


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33Hx30W
Standard Door Latch, No Lock, Outward
Opening
birdsccreen
pg. 264

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO CC
Coil Segment Details
Coil Space: 7"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
17" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 3200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.79/1.5
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 33Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 12-9
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 1575
BHP: 3.12
Fan BHP w/ Belt Loss: 3.34
Outlet Velocity (ft/min): 2421

Motor Detail (per motor)


BALDOR ODP premium effciency
HP= 5.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 184
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 13.2
Efficiency: 89.5%

SEGMENTO DI
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.) 0.22

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

pg. 265

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO XA
Access Segment Details
Segment Length: 12"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
10" Additional Core Growth

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:

(1)20x24
6.7
Side
2"
Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.25
0.1
12" RIGID
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left)
33Hx18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.55
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33Hx12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 266

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Coils & Spacers Listed Starting In Direction Of Air Flow


Coil General/Physical Details
Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
4
10
8
30
39
8.1
left
1-5/8
7/8
1
none

3200
30
76
66.5
55.8
54.5
395

pg. 267

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY

FM Filter / Mixing Box

Standard Hood
Bird Screen
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 8)
Dirty Filter Allowance

CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY
(in.wg)
0.06
0.1
0.11
0.02
0.12
0.05

Cooling 4 rows 10 fins


External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.31
1.5
0.22
0.25
0.1
0.55
0.2
0.2
3.79

DIMENSIONS AND WEIGHTH SUMMARY

Section
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment
OVERALL

Length
(in)
33
17
34
10
12
18
18
142

width height
(in)
(in)
51
39
51
39
51
39
51
39
51
39
51
39
51
39
51
39

weight
(lbs.)
401
529
517
95
94
190
225
2051

pg. 268

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

RUBRO:
N2.AA-04.37
UNIDAD:
UMA-H-06
CAUDAL (cfm)
1200
SECCION (plg x plg):30x33
CANTIDAD:
1
SECUENCIA DE SEGMENTOS
DP<RF<XA<DI<FS<<CC<FF<IP
SEGMENTO IP
Inlet Plenum Details
Opening: front (front)
Segment Air Pressure Drop (in. w.g.) 0.20

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24Hx12W
Standard Door Latch, No Lock, Outward
Opening

SEGMENTO FF
Filter Media Detail
(Quantity)Filter Sizes: (1)24x20
Filter Loading: Side
Filter Depth: 2"
Filter Media Type: Pleated 30% (MERV 8)
Filter area (ft2).
3.3
Filter Air Pressure Drop (in. w.g.): 0.17
Dirty Filter Allowance (in. w.g.): 0.10
Spare Filter Media:
Spare Filter Quantity Set(s):
Pleated 30% (MERV 8): 1

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24Hx10W
Standard Door Latch, No Lock, Outward
Opening
Optimized Filter Arrangement

SEGMENTO CC
Coil Segment Details
Coil Space: 10"

Coil Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized

pg. 269

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO FS
Segment Details
Segment Air Pressure Drop (in. w.g.): 0.00
Air Flow (CFM): 1200
Altitude (ft.): 30
TSP/ESP (in. w.g.): 3.65/1.60
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
External Light Switch
Access Door on Left Side(Left) 24Hx18W
Standard Door Latch, No Lock, Outward
Opening

Fan Detail
Type: FC
Size: 9-6
Construction: S
Bearing Options: PERMANENT SEAL
Fan RPM: 2011
BHP: 1.2
Fan BHP w/ Belt Loss: 1.31
Outlet Velocity (ft/min): 1650

Motor Detail (per motor)


TECO ODP premium effciency
HP= 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Insulation Class: F
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%

Motor Control Details


Motor Control Electrical Details
Motor Control Type: Variable Frequency Drive Full Load Amps (FLA): 7.5
Motor HP= 2.0

Motor Control Options


Fused Disconnect
Isolated Manual Bypass

Environmental
Ambient Temperature (F): 5 to 104
Storage Temperature (F): -40 to 158

Additional Communications: LONworks (LON) Humidity: MAX 95% RH non-condensing


Altitude: 3,300 ft. without derate (1%
RFI/EMI EMC Filter
derate
Swinging DC Line Choke (equivalent to 5%
Input Line
for each additional 330 ft.)
Reactor)
Enclosure: NEMA 3R
Modbus RTU, Johnson N2, Siemens FLN,
BACnet

pg. 270

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

input
Rated Input Voltage:
Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):

3 Phase 208-240 VAC +/-10% 48/63Hz


+/- 5%
7.5
73
98%

Output
Output Current Amps: 7.5
Overload Current Rating: 110% for 1 minute
every 10 minutes
Drives are rated for use below 3,300 ft and
104F.
Use Derating Charts in Air-Mod Engineering Guide Form 100.42-EG1 (212) for use above
these limits.

SEGMENTO DI

Diffuser Segment Details


Segment Air Pressure Drop (in. w.g.) 0.10

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

SEGMENTO XA
Access Segment Details
Segment Length: 27"

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24H x 24W
Multi-Point Door Latch, No Lock, Outward
Opening
10" Additional Core Growth

pg. 271

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

SEGMENTO RF
Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:

(1)24x20
3.3
Side
2"

Prefilter Media:

Pleated 30%
(MERV 8)

Prefilter Air Pressure Drop (in.


w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop
(in. w.g.):
High Eff. Filter Dirty Allowance (in.
w.g.):
Spare Filter Media:
Spare Filter Quantity Set(s):
Spare Filter Media:
Spare Filter Quantity Set(s):

0.17
0.1
12" RIGID
90-95%
MERV14

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Combined Filter Gauge (Minihelic)
(0 - 1 in. w. c.)
Access Door on Left Side(Left) 24H
x 18W
Multi-Point Door Latch, No Lock,
Outward Opening
Optimized Filter Arrangement

0.36
0.2
Pleated 30%
(MERV 8)
1
9095%MERV14
1

SEGMENTO DP
Discharger Plenum Details
Segment Air Pressure Drop (in. w.g.) 0.20
Opening: bottom

Discharge Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 24H x 12W
Multi-Point Door Latch, No Lock, Outward
Opening

pg. 272

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

Coil General/Physical Details


Location:
Tag:
Application:
Coil Type:
Face Type:
Tube Diameter:
tube material
tube wall thickness
fouling factor
fin type
fin thickness
fin material
casing material
connection material
connectiion type
coating
rows
fins per inch
circuit
finned height(in)
finned length(in)
coil face area (ft2)
coil conn loc
suct connsize
liq conn size
distributor data
split inter
Air Side Performance
ari flow (cfm)
altitude (ft)
EAT-DB (F)
EAT-WB (F)
LAT-DB(F)
LAT-WB (F)
FV (FT/MIN)

RESPONSABLE: F.CH.

0
aircoil
cooling
dx
full
1/2" BDX
copper
0.016"
n/a
corrugated
0.008"
aluminium
galvanized
copper
swear
none
5
10
5
20
21
2.9
left
1-5/8
7/8
1
none

1200
30
80
77
57.2
56.9
414

pg. 273

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

STATIC PRESSURE SUMMARY


SEGMENT
IP Inlet Plenum
FF Flat Filter
CC Variable Length
Cooling Coil
FS-DWDI Supply Fan
DI Diffuser
RF High Efficiency Filter

DP Discharge Plenum

SUPPLY
(in.wg)
0.2
0.17
0.1

COMPONENT
Opening Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance
Cooling 5 rows 10 fins
External Static Pressure - User Entered
Pressure Drop
Diffuser Air Pressure Drop
2" Pleated 30% (MERV 8)
Dirty Filter Allowance - Prefilter
12" Rigid 90-95% Eff, (MERV 14)
Dirty Filter Allowance
Opening Pressure Drop
TOTAL

0.45
1.6
0.1
0.17
0.1
0.36
0.2
0.2
3.65

DIMENSIONS AND WEIGHTH SUMMARY

Section
IP Inlet Plenum Segment
FF Flat Filter Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
RF High Efficiency Filter Segment
DP Discharge Plenum Segment

Length
(in)
18
10
19
40
10
27
21
15
160

width height
(in)
(in)
33
30
33
30
33
30
33
30
33
30
33
30
33
30
33
30
33
30

weight
(lbs.)
141
74
447
486
66
153
149
125
1641

pg. 274

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: DIFUSORES, REJILLAS Y LOUVERS DE VENTILACION
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-09.01

al 20

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
El plenum de difusores y rejillas es construido en acero galvanizado, con un cuello de
dimetro especificado en los planos y tendr un regulador de flujo del tipo de hojas
paralelas opuestas, de fcil acceso y mantenimiento.
Los colores de rejillas y difusores estn indicados en el presupuesto referencial.
DIFUSORES DE SUMINISTRO
De acuerdo a lo que se indica en los planos, para los sistemas de aire acondicionado y
ventilacin mecnica mediante ventiladores, equipos de tipo paquete y unidades
manejadoras de aire, se instalarn difusores de volumen fijo, los cuales sern
construidos en perfiles de aluminio extruido, iguales al modelo JS-OB, fabricados por
AIR GUIDE Corp. o similares.
El difusor tendr montado un disco interior de dispersin de aire para obtener una
distribucin horizontal de 360.
Cada difusor de suministro tendr un regulador de flujo del tipo de hojas paralelas
opuestas, de fcil acceso y mantenimiento.
REJILLAS DE RETORNO
Las rejillas de extraccin y de retorno sern construidas en perfiles de aluminio
extruido iguales al modelo RA-OB fabricadas por AIR GUIDE Corp.
Cada rejilla de extraccin tendr un regulador de flujo del tipo de hojas paralelas
opuestas, de fcil acceso y mantenimiento.
A continuacin se adjunta un detalle de las dimensiones, especificaciones y
cantidades de este rubro en cada sistema de ventilacin:

pg. 275

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO

CANT. DESCRIP. USO

RESPONSABLE: F.CH.

# VIAS COLOR

DIMENS. OBSERV

AA-09.01

490

DIFUSOR

SUMINIST.

BLANCO

6"x6"

aleta fija, c/damper

AA-09.02

168

DIFUSOR

SUMINIST.

BLANCO

8"x8"

aleta fija, c/damper

AA-09.03

17

DIFUSOR

SUMINIST.

BLANCO

18"x18"

aleta fija, c/damper

AA-09.04

62

DIFUSOR

SUMINIST.

BLANCO

16"x16"

aleta fija, c/damper

AA-09.08

22

REJILLA

RETORN.

22"X14"

acero inoxidable, separac.


Aletas 3/4"+ damper de ac.
Inoxidable, aletas orientadas
lado menor.

AA-09.09

REJILLA

RETORN.

20"X10"

acero inoxidable, separac.


Aletas 3/4"+ damper de ac.
Inoxidable, aletas orientadas
lado menor.

AA-09.10

REJILLA

RETORN.

20"X10"

acero inoxidable, separac.


Aletas 3/4"+ damper de ac.
Inoxidable, aletas orientadas
lado menor.c/gua y filtro 2"

AA-09.11

46

REJILLA

RETORN.

BLANCO

AA-09.12

REJILLA

DESCARG

BLANCO

AA-09.13

47

REJILLA

DESCARG

BLANCO

20"X10"
6"X6"
8"X8"

aluminio +damper

48"X24"

tol galvanizado +filtro

tipo louver, aletas largas


tipo louver, aletas largas

AA-09.14

LOUVER

SUMINIST/
DESCARG.

AA-09.15

LOUVER

SUMINIST/
DESCARG.

36"X24

tol galvanizado +filtro

AA-09.16

51

LOUVER

SUMINIST/
DESCARG.

24"X24"

tol galvanizado +filtro

AA-09.17

40

LOUVER

SUMINIST/
DESCARG.

24"X12"

tol galvanizado +filtro

AA-09.18

27

LOUVER

SUMINIST/
DESCARG.

12"X12"

tol galvanizado +filtro

AA-09.19

LOUVER

SUMINIST/
DESCARG.

48"X36"

tol galvanizado +filtro

AA-09.20

LOUVER

SUMINIST/
DESCARG.

36"X36"

tol galvanizado +filtro

pg. 276

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: DUCTO FLEXIBLE CON/SIN AISLAMIENTO
UNIDAD DE MEDIDA Y PAGO: mts.

CODIGO: N2.AA-09.21

al 26

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
La manguera flexible ser aislada o sin aislamiento, el material ser compuesto de un
polister metalizado, lmina de aluminio y una pelcula de polister que encapsulan un
anillo helicoidal de acero. El material aislante ser lana de vidrio con foil de aluminio,
exterior al material antes indicado.
El ducto deber cumplir con normas de Underwriters Laboratories UL181 y NFPA 90A
& 90B y son exclusivamente para uso interior bajo sombra.
Los ductos sin aislamiento sern fabricados con forma circular con tres capas de
lminas de polister aluminizado recubriendo a ambos lados a una estructura helicoide
de alambre de acero y en longitudes de 25ft.
Los ductos con aislamiento sern similares en su construccin a los anteriores pero
adicionalmente tendrn una capa aislante trmica exterior con R-6.0 segn UL 181,
Class 1 Air Ducts, la capa de aislamiento estar compuesta por una lmina de lana de
vidrio tridireccional reforzada y una lmina exterior de material de polyester reforzada
para evitar la rasgadura.
INSTALACION
Las mangas de ducto flexible sern instaladas tratando de que estn longitudinalmente
extendidas y buscando el camino ms corto a seguir.
En el recorrido debern evitarse contacto con materiales o bordes cortantes, tuberas o
conductos.
El radio de curvatura en una trayectoria siempre deber ser mnimo igual al dimetro
del ducto.
No se deber instalar ducto flexible muy cerca de equipos o conductos que emanen
calor.
Los tramos de ductos flexibles podrn ser juntados a travs de mangas de lmina de
acero galvanizado con una longitud no menor a 4 y los collares exteriores sern
elaborados en el mismo material con una longitud mnima de 2
Todas las juntas sern selladas adicionalmente con cinta adhesiva especifica para
ductos y que cumpla con UL Standard 181B
En la situacin que el ducto flexible deba quedar suspendido, ser soportado en
tramos no mayores de 4
El collar que soporte el ducto colgante deber tener un mnimo de 1-1/2 y deber
instalarse de manera de no deformar el perfil circular del ducto no poner en riesgo su
integridad.
pg. 277

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

En el caso de los ductos con aislamiento el trabajo de unin se har en la parte interna
del ducto y luego el aislamiento deber quedar completamente sellado con la cinta
adhesiva apropiada, cuidando siempre de que la capa de aislamiento se conserve
completa.
RUBRO

DESCRIPCION

AISLAMIENTO

DIAMETRO

AA-09.21
AA-09.22
AA-09.23
AA-09.24
AA-09.25
AA-09.26

DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE
DUCTO FLEXIBLE

NO
NO
NO
NO
SI
SI

4"
6"
8"
10"
4"
14"

CANTIDAD
658
293
74
4
1,429
1,112

pg. 278

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: TUBERIA DE COBRE Y ACCESORIOS
UNIDAD DE MEDIDA Y PAGO: mts.

CODIGO: N2.AA-10.01

al 08

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
El Contratista construir todo el sistema de distribucin de refrigerante de acuerdo con
los planos del proyecto, para lo cual suministrar todos los materiales que sean
necesarios, cindose a las especificaciones de materiales y montaje detallados a
continuacin.
Adems, deber limpiar, proteger y mantener los sistemas hasta la entrega de la obra.
Tubera, accesorios y vlvulas de corte se emplearn de acuerdo a especificaciones
detalladas a continuacin, para tubos de dimetro nominal de a 1-5/8:
- Material:

Cobre al 99.90% ASTM B 280 o ASTM B 88

- Tipo:

Flexible hasta 1/2", Rgido tipo L,K los dems


dimetros

- Espesor de pared:

0.032 plg

- Fabricacin:

Fundicin de Cobre.

- Presin de trabajo:

400 psi

- Presin de prueba:

600 psi

Cada unin se realizar con soldadura oxiacetilnica con soldadura de plata al 15%.
El Contratista Mecnico suministrar la mano de obra especializada para efectuar el
montaje completo de la tubera y accesorios de cobre, aislamiento trmico, as como
tambin las conexiones elctricas necesarias de fuerza y control para su
funcionamiento, desde la salida de la unidad exterior hasta las unidades interiores.
Examinar los planos del sistema con el objeto de tener pleno conocimiento del
mismo, y notificar al Propietario de cualquier anomala, tanto en el diseo como en
los materiales, en su debida oportunidad, con el objeto de no causar ningn retraso en
la obra.
Todas las lneas de las tuberas deben instalarse con secciones completas, evitando
tramos cortos.
Se eliminar toda tensin indebida, evitando dobleces que entorpezcan el flujo normal.
Antes de empezar la instalacin de la red de tuberas deber tomarse mucho cuidado
en la limpieza de los bordes cortados y en sellar las mismas para evitar el ingreso de
suciedad en la red.
pg. 279

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

El aislamiento trmico deber instalarse de acuerdo a los espesores y materiales


especificados por el diseador y de acuerdo a las instrucciones del fabricante
Antes de empezar la soldadura se proceder a cargar las lneas de gas y lquido, con
Nitrgeno Seco a una presin de 0.01 a 0.1 Kg/cm, para prevenir la oxidacin de la
tubera en el momento de la soldadura.
La soldadura deber realizarse con oxiacetileno (Oxgeno: 3 5 Kg/cm, Acetileno:
0.1 0.2 Kg/cm), no se aceptar GLP debido a la poca penetracin de la soldadura.
AISLAMIENTO TERMICO DE TUBERIAS
Se aislarn las lneas de gas y de lquido, con cauelas de espuma elastomrica de
acuerdo a la siguiente especificacin:
CARACTERISTICAS GENERALES:
material elastomrica del tipo de celda cerrada (closed-cell) con
forma tubular
compuesto libre de fibras, libre de formaldehidos y bajo nivel de
VOCs
estructura que permita control de la condensacin
barrera de vapor incluida
proteccin que inhiba el desarrollo de: hongos, microbios, etc.
CUMPLIMIENTO DE NORMAS
NFPA 90A,90B
ASTM C534, type I Grade 1
UL 181
ASTM D1056, 2B1
ASTM E84,
NFPA 255
UL 723
El aislamiento de tubera y accesorios ser hermtico para evitar prdida de la barrera
de vapor y la condensacin de las lneas de conduccin de refrigerante.
Todas las vlvulas y accesorios debern estar tambin debidamente aisladas.
En los cruces de tuberas en juntas de construccin se instalarn juntas flexibles con
aislamiento.
CONDUCTIVIDAD TERMICA
A 24C
A 32C
PERMEABILIDAD AL VAPOR DE AGUA
permeabilidad
ABSORCION DE AGUA
% en volumen
rango de trabajo
Espesor de pared

F(W/Mk)
F(W/Mk)
Kg/(s*m*Pa)

C
pulg

0.036
0.037
0.725x10

-13

0.20%
-180 A 100
1/2

pg. 280

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 281

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO
AA-10.01
AA-10.02
AA-10.03
AA-10.04
AA-10.05
AA-10.06
AA-10.07
AA-10.08

DESCRIPCION
FLEXIBLE TIPO "L"
FLEXIBLE TIPO "L"
FLEXIBLE TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "L"
RIGIDA TIPO "K"

AISLAMIENTO
SI
SI
SI
SI
SI
SI
SI
SI

RESPONSABLE: F.CH.

DIAMETRO
1/4"
3/8"
1/2"
5/8"
3/4"
7/8"
1-1/8"
1-3/8"

CANTIDAD
1,466
2,181
2,431
2,236
931
491
2,194
294

pg. 282

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: REFRIGERANTE ADICIONAL R-410A
UNIDAD DE MEDIDA Y PAGO: Kg.

CODIGO: N2.AA-03.07

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
El R410A es una mezcla no azeotrpica compuesta de R125 y R32.
Es un producto qumicamente estable, con un bajo deslizamiento (Glide) de
temperatura y baja toxicidad. A pesar del carcter inflamable del R32, la formulacin
global del producto hace que este no sea inflamable, incluso en caso de fugas.
El producto deber contar con Certificacin AHRI calidad y pureza
CANTIDAD= 1007 Kg,
PROPIEDADES FISICAS
Mezcla binaria
Composicin (%)
Peso molecular (Kg/Kmol)

R-410A
R32 / R125
50 / 50

Temperatura ebullicin (C)

72.6
52.7

Deslizamiento temperatura (Glide) (C)

0.5

Temperatura crtica (C)

72.5

Presin crtica (bar)

49.5

Densidad del lquido (25C) (Kg/l)

1.07

Densidad del lquido (-25C) (Kg/l)

1.27

Densidad del vapor (kg/m3)

4.2

Presin del vapor (25C) (bar)

16.5

Lmite de inflamabilidad (% vol.)

Ninguno

Presin de vapor (-25C) (bar)

3.34

Solubilidad con el agua (25C) ppm

2500

Conductibilidad trmica del vapor (25C) (W/mK)

0.013

Conductibilidad trmica del lquido (25C) (W/mK)

0.091

Capacidad calor del vapor (25C) KJ/Kg K)

1.28

Capacidad calor del lquido (25C) (KJ/Kg K)

1.71

Calor de vaporizacin (KJ/Kg)

257

Presin del vapor (-25C) (bar)

3.34

Toxicidad (AEL) ppm

1000

pg. 283

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: CABLEADO DE FUERZA CONTROL
CODIGO: N2.AA-10.09

UNIDAD DE MEDIDA Y PAGO: mt.

al 15

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Se instalar el cableado de fuerza y control, desde las unidades exteriores de volumen
de refrigerante variable, hacia sus respectivas unidades interiores, as como tambin
entre las unidades internas y externas de los equipos Inverter sueltos, y el cableado
hacia los controles de temperatura de los diferentes equipos, con conductor tipo AWG
de acuerdo a la siguiente especificacin:
- Material:

Conductor de cobre

- Calibre:

AWG 12, AWG 16

- Especificacin:

ASTM B-3 / NEMA-WC-5

- Seccin aprox.

3.31 mm, 1.31 mm2

- Capacidad conduccin:

30 Amp, 15 Amp

- Tensin de Servicio mxima:

600 V.

- Recubrimiento:

Cloruro de polivinilo (PVC) de 60C, resistente a la


humedad.

- Accesorios:

Terminales tipo U para conexin a equipos.

El cableado de fuerza y control, especificado arriba, deber estar protegido por medio de
tubera conduit EMT, de acuerdo a la siguiente especificacin:
- Material:

Tubera Conduit Galvanizada.

- Especificaciones:

INEN 1374

- Presin de prueba:

4.0 kg/cm2 mnimo

- Flexin:

No ser mayor que el 5% en el tubo hmedo con


relacin a la flexin del tubo seco.

- Aplastamiento:

El dimetro promedio no cambiar en ms de 10%

- Impacto:

La mnima resistencia al impacto ser de 5.5 kg/m


a 0C.

- Uniones, y conectores:

Accesorios EMT.

pg. 284

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RUBRO

RESPONSABLE: F.CH.

DESCRIPCION

N2.AA-10.09 Cableado de fuerza 3x#12, Para Unidades Interiores VRF


Cableado de control 2x#16, Para Unidades Interiores
N2.AA-10.10 (Apantallado segn marca de equipos VRF)
Cableado de control 3x#16, para Unidades Interiores VRF
N2.AA-10.11 (Apantallado segn marca de equipos VRF)
Tubera EMT 3/4" para control y fuerza, incluye unin y
N2.AA-10.12 cajetines
N2.AA-10.13 Manguera Bx 3/4" metlica anillada para interiores
N2.AA-10.14 Manguera Bx 1" metlica sellada para exteriores
N2.AA-10.15 Cableado de fuerza 4x#12 Para Equipos Inverter Individuales

CANT
6,376
7,187
3,086
7,803
2,007
634
5

pg. 285

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: DUCTOS DE TOL GALVANIZADO CON Y SIN AISLAMIENTO TERMICO
UNIDAD DE MEDIDA Y PAGO: Kg.

CODIGO: 9636-37

CONTENIDO DEL RUBRO


Estos rubros corresponden a los elementos necesarios para la canalizacin de aire
que requiere ser inyectado o extrado de cada uno de los ambientes del hospital.
Esta especificacin proporciona los parmetros mnimos para la fabricacin,
transporte, instalacin, calibracin de flujos, puesta en marcha y pruebas. Incluyen
consumibles accesorios que sean necesarios para su correcto funcionamiento.
Los ductos tanto aislados como sin aislamiento responden a la misma especificacin
de construccin metlica e instalacin; el Rubro 9637 adicionalmente incluye el
aislamiento trmico respectivo

ESPECIFICACIN DUCTOS
SIN AISLAMIENTO: RUBRO 9636
RUBRO 9637 ANTES DEL AISLAMIENTO
El Contratista fabricar e instalar todos los sistemas de ductos de conformidad con
los planos de proyecto, para lo cual suministrar todos los materiales que sean
necesarios, cindose a las siguientes especificaciones de materiales, fabricacin y
montaje y aquellas establecidas en la normativa SMACNA.
En la fabricacin de ductos de aire acondicionado y ventilacin se emplear lmina lisa
de acero galvanizado ASTM A525 de primera calidad "lock-forming grade", de acuerdo
con los calibres indicados segn el tamao de los ductos.
En ningn caso se aceptar el empleo de lmina galvanizada que muestre deterioro
de sus condiciones y/o en los dobleces o quiebres.
Los espesores de lmina, estn determinados de la siguiente manera, ductos cuyo
lado mayor est comprendido entre:
LADO MAYOR

CALIBRE DE LAMINA

0" y 30"

24 USG (0.6mm)

31" y 54"

22 USG (0.7mm)

55" y 84"

20 USG (0.9mm)

Superior a 85"

18 USG (1.0mm)

Todos los codos debern tener un radio medio igual al lado del ducto. En sitios donde
por dificultades de espacio no se pueda obtener este radio mnimo, se instalarn guas o
deflectores internos en lmina galvanizada de acuerdo con el detalle de los planos y las
recomendaciones constructivas de las normas SMACNA.
pg. 286

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Las piezas de transicin entre ductos de dos secciones diferentes, sern fabricadas con
pendientes que no excedan 1:5 en cualquier cara del ducto y preferiblemente 1:7 en
donde ello sea posible.
Donde los planos indican, y en los que el Contratista considere necesarios, se instalarn
compuertas o reguladores de volumen de fcil manejo y acceso desde el exterior, para el
correcto balanceo del sistema. Toda compuerta ajustable tendr un dispositivo exterior
que indique su posicin.
Todas las dimensiones de los ductos de conduccin de aire que se muestran en los
planos o lminas de diseo se refieren al tamao interior libre necesario. El aislamiento
trmico en el caso del ducto aislado ser externo.
INSTALACION DE SOPORTES
Para todos los ductos horizontales se utilizarn soportes de acuerdo con los detalles de
los planos, es decir varilla roscada galvanizada de 5/16" y canal troquelado galvanizado,
para ductos de hasta 15", para ductos de ms de 16" se deber usar varilla roscada
galvanizada de 3/8". Los ductos verticales sern soportados utilizando perfiles de ngulo
de acero arriostrados a la estructura del edificio en cada uno de los pisos y sujetos de
manera apropiada.
El canal troquelado para soporte tendr las siguientes caractersticas fsicas, y ser de un
espesor de 2.6mm, o calibre 12. Para el adecuado soporte se debern usar (accesorios
galvanizados) arandelas planas cuadradas para facilitar el apriete de la tuercas que
sujetan el canal a la varilla roscada

UNIONES LONGITUDINALES
Las uniones longitudinales, en las esquinas de todos los ductos se harn utilizando la
unin tipo "Pittsburgh" fabricados en mquina formadora por rollos (roll forming) de
manera a garantizar la calidad y dimensiones de la junta. Se aceptarn nicamente
juntas longitudinales que cumplan lo especificado por la norma SMACNA.

pg. 287

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Para las uniones longitudinales que no correspondan a esquinas, se utilizar unin tipo
"Standing Seam" segn la norma SMACNA.
Todas las juntas debern ser hermticas y construidas en forma tal que los salientes
interiores apunten en la direccin del flujo de aire.
UNIONES TRANSVERSALES
Para el caso de Uniones Transversales de ductos, se utilizarn tres alternativas de
acuerdo a la aplicacin de la red de ductos a la que corresponde:
o C y S slip. Este tipo de juntas transversales se utilizarn para ductos cuya
aplicacin sea extraccin de baos, recirculacin de Fan Coils, recuperadores de
energa de rueda para oficinas, habitaciones de cuidado bsico, suministro de
aire con nivel de filtrado menor al 40%. Los perfiles S y C deber ser fabricado en
mquina formadora por rollos (roll forming) de manera a garantizar la calidad y
dimensiones segn SMACNA.
o TDC o TDF. Este tipo de junta se utilizar para sistemas de ventilacin y
climatizacin que atiendan a ambientes correspondientes a unidades
manejadoras de aire de doble pared, recuperadores de energa de placas y de
rueda entlpica y en ambientes de cuidado medio en adelante
o Bridado. Este tipo de ductos se utilizarn para la extraccin de aire con grasa y
humo de la cocina, y en los casos en los cuales lo indica la especificacin que se
muestra a continuacin.
UNIONES TRANSVERSALES TIPO C y S SLIP
Este tipo de uniones transversales sern elaboradas en proceso de conformado en
rodillos roll forming en el misma lmina galvanizada que se fabrica el ducto y
adicionalmente se deber aplicar sellante especfico para ductos de aire acondicionado y
ventilacin de manera a garantizar la hermeticidad de las mismas, a continuacin se
presenta el esquema constructivo de este tipo de junta.

Las uniones transversales entre secciones se fabricarn de la siguiente manera:

pg. 288

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015


LADO MAYOR

RESPONSABLE: F.CH.
UNION TRANSVERSAL

0" y 24"

S-Slip

25" y 40"

Bar-Slip de 1"

41" y 60"

Bar-Slip reforzada con platina de 1"

Superior a 60"

Unin bridada de ngulo de acero de 1"


x1/8

UNIONES TRANSVERSALES TIPO TDC o TDF


Son uniones clasificadas en el SMACNA como 25a/25b, las mismas que son
bsicamente bridas elaboradas en la misma lmina con la que se fabrica el ducto, para el
cierre de dichas juntas se utilizan empaques, y pernos. Para esto se dispone de juntas
esquineras que permiten empernar la junta y en la parte intermedia se colocan clips para
sellar el empaque. Se aplicar empaque y/o sellante en las juntas transversales para
garantizar la hermeticidad de los ductos.
A continuacin se presentan los esquemas SMACNA de este tipo de juntas:

UNIONES TRANSVERSALES TIPO BRIDADO


Son uniones transversales que utilizan perfiles de acero laminado en caliente como son
ngulos. Adicionalmente se utilizan empaques y pernos, para asegurar el cierre
adecuado y una alta hermeticidad de la red.
A continuacin se presenta el esquema SMACNA de este tipo de junta. Categorizada
como junta T-22

pg. 289

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

REFUERZO DE DUCTOS
Los ductos tendrn refuerzos de acuerdo a la siguiente tabla:
LADO MAYOR
0" y 15"
16" y 24"
25" y 41"
42" y 84"
Mayor a 85"

TIPO DE REFUERZO
Lamina acanalada cada 60cm
Lamina acanalada cada 40cm
Lamina acanalada cada 40cm y refuerzo de
ngulo de 1"x1"x1/8"
Lamina acanalada cada 40cm y refuerzo de
ngulo de 1"x1"x1/8
Lamina acanalada cada 40cm y refuerzo en
ngulo de 2"x2"x "

Los ngulos de refuerzo requeridos y los de uniones con brida sern remachados y no
atornillados a la lmina del ducto.
El proceso de acanalado de la lmina debe ser realizado en una mquina de rodillos
especial para este propsito, no se aceptar lmina con quiebre en diamante o sin el
reforzamiento especificado.
ESPECIFICACION TECNICA DEL AISLAMIENTO RUBRO 9637
Los ductos del sistema de aire acondicionado se debern aislar con lana de vidrio de
2." de espesor y 2 lbs./pie2 de densidad con lmina de papel de aluminio adherido al
aislante, montado por la parte exterior de los ductos de tol galvanizado. Se debern
utilizar zunchos de plstico de manera a asegurar el aislamiento y evitar la separacin
del aislamiento trmico de la pared del ducto.
Para las juntas del aislamiento se aplicar cinta adhesiva de aluminio de manera a
mantener la integridad de la membrana a prueba de vapor de agua.
Los ductos de extraccin y suministro, que estn expuestos a la intemperie, debern
llevar adicionalmente al aislamiento el impermeabilizante de asfalto con foil de aluminio,
en todas las caras.

pg. 290

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

MANO DE OBRA MINIMA CALIFICADA


Para la ejecucin de estos rubros se requiere el siguiente personal mnimo para cada
tipo de actividad:
SUPERVISOR DE INGENIERIA
Debe ser Ingeniero Mecnico con al menos 8 aos de experiencia en sistemas de
climatizacin y ventilacin. Deber estar disponible en obra el 100% del tiempo
durante la ejecucin del proyecto. Ser responsable de la revisin del diseo,
verificacin de flujos y cadas de presin, especificaciones tcnicas de ventiladores,
motores, transmisiones; balanceo de los sistemas puesta en marcha y entrega de los
mismos incluyendo las evidencias en base a los registros de los instrumentos
utilizados.
INGENIERO (S) RESIDENTE (S)
Debe ser Ingeniero Mecnico con al menos 4 aos de experiencia en sistemas de
climatizacin y ventilacin. Deber estar en obra el 100% del tiempo durante la
ejecucin del proyecto. Ser responsable de la revisin de los planos entregados por
el contratante correspondientes al diseo, verificar en obra las modificaciones y
proceder a verificar flujos, cadas de presin y verificar las especificaciones tcnicas
de los ventiladores respectivos (RPM, flujo y cada de presin esttica); elaborar los
planos de taller de cada red de ductos a ser fabricados e instalados; ser responsable
de la supervisin del montaje en obra. Elaborar los planos como construccin as
built para entrega a Fiscalizacin; elaborar las planillas de avance de obra de ductos
con los detalles de pesos incluyendo la soporteria respectiva y sus accesorios. La
verificacin de pesos se efectuar en una balanza calibrada y certificada por INEN.
JEFE DE TALLER DE CONSTRUCCION DE DUCTOS
Debe ser Tcnico en construccin de ductos con al menos 8 aos de experiencia, y al
menos 3 aos con el uso de mquinas conformadoras de rodillos roll former. Sera
responsable de calibrar las mquinas y herramientas para asegurar el cumplimiento
que las dimensiones, tolerancias de acuerdo a los planos, detalles entregados por el
Ing Residente y asegurar de esta manera la calidad del producto entregado para
instalacin.
JEFE DE MONTAJE DE DUCTOS
Debe ser Tcnico en construccin y montaje de ductos con al menos 8 aos de
experiencia. Sera responsable de asegurar la calidad del trabajo: alineamiento,
estanqueidad, en cada uno de los sistemas. Adems deber asegurar la proteccin
los ductos para evitar el ingreso de polvo y objetos extraos durante el proceso de
montaje.
AYUDANTES EN GENERAL
Deben ser personas que han trabajado en construccin y montaje de ductos con al
menos 2 aos de experiencia. Sern responsables de colaborar para asegurar la
calidad del trabajo en cada uno de los sistemas requeridos.
EQUIPO MINIMO NECESARIO

pg. 291

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Para la ejecucin de estos rubros se requiere el siguiente equipo mnimo para cada
tipo de actividad:
1. GRUPO DE INGENIERIA SUPERVIOR Y RESIDENTES
El equipo de ingeniera deber disponer de equipos para:
Computador personal de escritorio con la suficiente capacidad de trabajo para
procesar toda la informacin del proyecto sin causar retrasos al avance de
obra.
Medicin de caudales de aire en ductos.
Medicin de presin esttica
Medicin de espesores de lmina galvanizada
Medicin de flujos de aire en difusores y rejillas
Balanza calibrada y certificada para pesaje de ductos.
2. GRUPO DE CONSTRUCCION DE DUCTOS
Cada grupo de construccin deber disponer de los siguientes equipos:
Maquina elaboracin de junta tipo Pittsburg por conformado con rodillos.
Maquina elaboracin de perfiles S y C por conformado con rodillos
Mquina de rodillos para elaborar acanalado de refuerzo en la lmina
Dobladora de muelas calibrada segn el espesor de la lmina.
Cizalla de corte mecnica o hidrulica.
Rebordeadora con diferentes rodillos para elaboracin de cuellos, codos y
dems accesorios.
Kits completos de herramientas para fabricacin y montaje de ductos: picado,
doblez, y sellado de ductos.
3. GRUPO DE MONTAJE DE DUCTOS
Cada grupo de montaje deber disponer de los siguientes equipos:
Andamios y escaleras en buenas condiciones
Taladro de percusin de tipo roto martillo
Kits completos de herramientas para montaje y sellado de ductos.
Todo el personal deber cumplir con la normativa de seguridad industrial respectiva.
CUADRO DE PESOS APROXIMADOS DE DUCTOS
A continuacin se presenta el cuadro resumen de los pesos aproximados de los dos
tipos de ductos:

DUCTOS DE LAMINA GALVANIZADA

TOTAL (Kg)

PESO TOTAL
SIN AISLAMIENTO RUBRO 9636

PESO TOTAL
CON AISLAMIENTO RUBRO
9637

28,775.23

72,159.95
pg. 292

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 293

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: FILTROS DE AIRE ACONDICIONADO
UNIDAD DE MEDIDA Y PAGO: U.

CODIGO:

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Filtros de Aire 40% (MERV 6):
Los filtros de aire para los ventiladores de suministro de aire fresco de 40% de
eficiencia sern de tipo desechable construidos con un medio filtrante diseado para
una gran capacidad de captura de polvo y baja resistencia al paso de aire.
Estos filtros permitirn el paso de aire entre 300 y 700 pies/minuto con una resistencia
inicial mxima de 0.10" c.a.
En el caso en el que se especifiquen ventiladores de suministro con filtros
incorporados, los filtros de aire se instalarn de acuerdo a las especificaciones de
estos equipos.
Se aceptar los filtros de fibras multidireccionales o mantas filtrantes cuya
especificacin corresponda a un prefiltro.
Filtros de aire 30% de eficiencia (MERV 1):
Los filtros de aire de 30% de eficiencia sern del tipo permanente y lavable construidos
con un marco de aluminio y con el medio filtrante de por lo menos 6 capas de aluminio
expandido diseado para una gran capacidad de captura de polvo y baja resistencia al
paso de aire.
Estos filtros permitirn el paso de aire entre 300 y 700 pies/minuto con una resistencia
mxima de 0.18" c.a.
En el caso en el que se especifiquen ventiladores de suministro con filtros
incorporados, los filtros de aire se instalarn de acuerdo a las especificaciones de
estos equipos.
Cuando se especifique en los planos, se debern colocar bancos de filtros de alta
eficiencia respetando las siguientes especificaciones:
Filtros de 65% (MERV 10) y 95% (MERV 12) de eficiencia:
Los filtros de alta eficiencia sern construidos con fajas continuas de fibra fina plegada
con separadores de aluminio, sellados en fbrica en un marco de madera aglomerada
resistente al fuego (U.L. Class 1).
Estos filtros se montarn en un marco construido en chapa galvanizada con clips
retenedores y empaque para sello hermtico.
Los filtros sern iguales o similares al modelo RIGID AIR fabricado por FLANDERS
PRECISION AIR.
Los filtros tendrn una eficiencia promedio de 60%, 90% 95% de acuerdo a lo que se
especifique (ASHRAE Std 52-68) usando polvo atmosfrico.
pg. 294

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Cada filtro tendr un prefiltro lavable de 2" de espesor.


Cuando se especifique en los planos bancos de filtros de servicio lateral, se debern
suministrar bancos de filtros con una carcasa construida en tol galvanizado US gauge
16 con soporte para prefiltros de 2".
Las puertas de acceso tendrn empaques que impedirn cualquier fuga de aire, y que
permitan reemplazar los filtros con facilidad.
Los bancos de filtros llevarn incorporado manmetros diferenciales de presin para
un rango de 0 a 2c.a

pg. 295

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: ESPECIFICACIONES COMPLEMENTARIAS
UNIDAD DE MEDIDA Y PAGO: U.

CODIGO:

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Cdigos y Estndares
ASHRAE: American Society of Heating Refrigerating and Air Conditioning Engineers.
ASTM: American Society for Testing and Materials.
NPC: National Plumbing Code.
APC: American Plumbing Code
Planos:
Se proveern al Contratista los planos de ingeniera y diseos del sistema.
A medida que progrese la instalacin, el Contratista realizar los planos de "Obra Como
Construida" para ser entregados al Propietario.
El Contratista inspeccionar el sitio en que se realizarn los trabajos de esta
especificacin a fin de comprobar si est listo para proseguir con los trabajos e informar
al Fiscalizador sobre cualquier anomala que amenace perjudicar la bondad de dicho
trabajo.
Deber especficamente:
Examinar todos los estudios propios de esta instalacin, as como otros que deban
desarrollarse en forma conjunta a fin de proceder coordinadamente.
Revisar los estudios de esta instalacin tales como planos, especificaciones tcnicas,
cdigos y estndares, para que en base a este estudio plantee el programa de trabajo
total.
Evitar posibles interferencias con otros rubros de trabajo.
Proveer seguridades para el personal con el objeto de evitar cualquier accidente de
trabajo, y precauciones para evitar daos en estructuras, otras instalaciones, etc.
El Contratista ser responsable de la bondad de las instalaciones y equipos. Cualquier
comentario u observacin a las especificaciones de los materiales y equipos deber
comunicarlo al Propietario, ya que el contratista ser el responsable por el buen
funcionamiento del sistema.
El Contratista Elctrico suministrar la debida alimentacin, acometida elctrica, tablero
de breakers y arrancadores para todos los ventiladores y equipos de los sistemas de
Ventilacin Mecnica, listados en estas memorias.
El Contratista Mecnico se encargar de proporcionar la ingeniera necesaria para el
montaje, instalacin y puesta a punto de los tableros de arrancadores de acuerdo a las
caractersticas y ubicacin de los equipos y dispositivos que as lo requieran, desde los
breakers instalados por el Contratista Elctrico hasta los equipos.
pg. 296

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Dichos tableros debern cumplir con todas las normas y sern fabricados segn
especificaciones NEMA tipo 1, de uso general, formado por secciones verticales de
servicio sencillo, con todos sus lados cerrados inclusive el piso.
Los tableros de control elctrico de los ventiladores suministrados por el Contratista
elctrico, debern contar con los respectivos contactores trifsicos y protector trmico
automtico debidamente dimensionados, con pulsadores de arranque-parada asociados
con su luz indicadora verde-roja, respectivamente y su placa identificadora (EncendidoApagado START/STOP).
El contratista mecnico suministrar mano de obra especializada para efectuar el
montaje completo de los equipos de ventilacin mecnica, y hacer las conexiones
elctricas finales de los mismos.
El Contratista balancear y ajustar los sistemas de distribucin de aire como sigue:
Examinar los sistemas de manejo de aire con el objeto de determinar que estn libres
de obstrucciones.
Determinar que todas las compuertas y registros estn abiertos, que todas las partes
mviles estn lubricadas, que los filtros estn limpios y operando debidamente y
efectuar todas las actividades de inspeccin y mantenimiento necesarios para la
correcta operacin de los sistemas.
Instalar los accesorios necesarios en los ductos para poder realizar la medicin de flujo
de aire, presin esttica, en todos los ductos principales, a fin de garantizar el correcto
funcionamiento de los sistemas.
Demostrar que el equipo de manejo de aire trabaja de acuerdo con lo especificado.
Ajustar las poleas de dimetro variable y las compuertas de volumen. Cada unidad
terminal retirar la cantidad de CFM especificada en forma dispuesta.
Tabular los resultados de las pruebas en formatos previamente aprobados y
suministrar tres copias de cada uno para aprobacin y archivo.
Se pondr en marcha el sistema completo, se graduar y ajustar para poder efectuar las
pruebas completas.
Las tuberas de drenaje debern ser diseadas e instaladas por el Contratista
Hidrosanitario bajo las instrucciones del Contratista Mecnico y siguiendo las
siguientes normas bsicas:
Las tuberas horizontales que deban ser suspendidas, debern tener pendiente y
todas las entradas se conectarn a los ramales, de arriba hacia abajo, y donde esto no
sea posible, todos los ramales se conectarn a la lnea principal por arriba de sta.
Los dimetros de la tubera de drenaje los definir el Contratista Mecnico y dependern
de la capacidad de las unidades interiores, de acuerdo a la tabla siguiente:

pg. 297

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

CAPACIDAD

RESPONSABLE: F.CH.

TUBERIA DE DRENAJE

Menor a 18.000 BTU/hr

20 mm.

entre 18 y 34.000 BTU/h

25 mm

entre 34 y 68.000 BTU/h

30 mm

mayor a 68.000 BTU/h

40 mm

PRUEBAS Y PUESTA EN MARCHA


El Contratista Mecnico pondr en marcha el sistema completo, se ajustar y regular
todo el mecanismo para balancear el servicio, con las siguientes pruebas:
Para los equipos del sistema de ventilacin mecnica se realizarn las siguientes
pruebas como mnimo:
De velocidad, presin esttica y dinmica de succin y descarga en los motores.
De velocidad y volumen de aire que pasa por los ventiladores, de todo el
sistema.
Del amperaje de servicio de los motores y el accionamiento.
Los datos de resultado sern aceptables cuando no difieran en ms del 10% de las
constantes en el proyecto.
Todas las pruebas sern de cargo del Contratista Mecnico y se realizarn con
aparatos apropiados, cuantas veces sean necesarias, hasta conseguir un correcto
ajuste; cuando esto ocurra se anotarn los datos en un registro, que sern entregados
a la Fiscalizacin de la obra, conjuntamente con los planos de construccin.
Para los equipos del sistema de Aire Acondicionado, se realizarn las siguientes
pruebas como mnimo:
Del amperaje de servicio de los motores y el accionamiento.
De enfriamiento y temperaturas de diseo.
El Contratista probar toda la instalacin, luego de que se encuentre armada en su
totalidad, con Nitrgeno Seco a una presin de 28 Kg/cm durante 24 horas, con el fin
de levantar suficiente presin en el sistema para buscar fugas. En el caso de que se
presentaren fugas, se las corregir, y se repetir la prueba, hasta comprobar que han
desaparecido por completo.
El Contratista determinar que todas las vlvulas, registros, etc., estn abiertos, que
todas las partes mviles estn lubricadas, que los filtros estn limpios y operando
debidamente. Efectuar todas las labores de inspeccin y mantenimiento necesarias
para la correcta operacin del sistema, de acuerdo a esta especificacin, y de
acuerdo a las exigencias de la empresa.
Demostrar que el sistema de aire acondicionado trabaja de acuerdo a lo especificado,
y a satisfaccin de la contratante.
El Contratista deber incluir en la entrega las impresiones de los reportes del
programa de arranque del fabricante, con todos los parmetros de funcionamiento,
tales como:
Temperatura Exterior.
pg. 298

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Temperatura de entrada y salida de refrigerante en la unidad interior


Temperatura de salida de aire de la unidad interior
Temperatura del espacio acondicionado
Presin de alta y baja en el compresor
Amperaje del compresor.
Todas las pruebas sern de cargo del Contratista, y se realizarn con aparatos
apropiados cuantas veces sean necesarias, hasta conseguir un correcto ajuste.
ESPECIFICACIONES COMPLEMENTARIAS:
En el curso de la construccin, el Contratista Mecnico deber tomar todas las
precauciones necesarias para el impedir la entrada de materiales extraos a los
ductos y tuberas de cobre, que produzcan obstculo o deterioro, siendo su obligacin
realizar la revisin y limpieza de cada seccin, antes de continuar con otra.
Todo material deteriorado ser reemplazado por otro en buenas condiciones.
No se incluyen los siguientes trabajos:
Las lneas de alimentacin elctrica ni acometida de la cmara de
transformacin a los tableros de breakers.
Los trabajos de albailera que se requieran: mamposteras, hormigones,
enlucidos, etc., para el montaje.
El Contratista mecnico suministrar los planos detallados y pernos de anclaje; vigilar
la ejecucin y realizar las instalaciones y montaje suministrando por su cuenta: los
tableros elctricos, ductos y conductores necesarios.
El Contratista Mecnico ser responsable del cuidado y mantenimiento de todo el
equipo, respondiendo econmicamente por cualquier dao o deterioro que sufra sea
por falta de cuidado o mala instalacin, hasta que los trabajos sean entregados
definitivamente.
Los planos que se entregan son slo indicativos en lo que se refiere a los recorridos de
ductos y tubera. La localizacin exacta la deber hacer el Contratista, previa
aprobacin de la contratante y la fiscalizacin, analizando los elementos estructurales,
otras instalaciones, etc., realizando todos los ajustes necesarios antes de dar
comienzo a su trabajo, as como tambin coordinando con el resto de instalaciones, y
con la aprobacin de Fiscalizacin.

pg. 299

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: EQUIPO DE REFRIGERACION PARA CUARTO FRIO
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: N2.AA-07.01

al 04

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Unidades de refrigeracin equipadas con compresores hermticos destinadas a
aplicaciones de alta, mediana y baja temperatura.
UNIDADES CONDENSADORAS
Los condensadores debern ser diseados para operar en ambientes de alta
temperatura y humedad.
Los motores debern estar cubiertos y protegidos para un correcto funcionamiento en
ambientes hmedos y con presencia de suciedad.
Todas las unidades estarn pintadas con pintura electrosttica probada para
resistencia a la corrosin.
Todos los compresores tendrn vlvulas de servicio de succin y descarga para un
adecuado mantenimiento y operacin.
Los ventiladores de las unidades debern contar con rejillas metlicas con una
aplicacin de pintura electrosttica.
Todas las unidades irn montadas sobre soportes anti vibracin apropiados.
Los presostatos de alta y baja presin sern ajustables o del tipo sellado para evitar
escapes y/o alteraciones del set-point.
Todas las unidades contarn con su respectivo tanque de lquido y vlvula de servicio.
Los compresores contarn con un visor para verificar el nivel de aceite del carter y
adems vlvula de servicio tipo Schroeder para la toma de presin y recarga de aceite.
Todos los compresores contarn con protector trmico interno bimetlico.
Las unidades incluirn una caja elctrica de fcil acceso con kit de arranque completo
(capacitores y rel volumtrico)
UBICACIN
Las unidades condensadoras debern estar correctamente ubicadas en reas bien
ventiladas, en la cual el flujo de aire no tenga restricciones, es importante evitar
retornos en el flujo de aire, adems deber estar apropiadamente protegida contra la
intemperie.
CONEXIONES
Para el circuito de tuberas se utilizar exclusivamente tubera de cobre limpia y
deshidratada.
La tubera del compresor deber tener el grado de libertad suficiente en las 3
direcciones a fin de absorber vibraciones y evitando quedar muy cerca del compresor.
pg. 300

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

Los tramos de tubera tendern a ser simples y cortos, evitando puntos bajos en los
que el aceite pudiera acumularse.
En la lnea de succin las secciones horizontales deben tener un declive del 1% para
abajo en direccin al compresor.
Cuando el evaporador est situado por encima del compresor, se instalarn las lneas
de succin de manera que la refrigeracin lquida no migre para el compresor durante
el ciclo de parada.
La lnea de succin deber estar debidamente aislada para evitar condensacin y
sobrecalentamiento.
Todas las unidades contarn con filtros secadores correctamente dimensionados para
evitar una cada de presin exagerada en la lnea de lquido.
UNIDADES EVAPORADORAS
La unidad evaporadora ser de bajo perfil con una altura mxima de 14 pulgadas.
Deber contar con soportes para ser instalada bajo techo.
Los paneles laterales sern fcilmente removibles para tareas de mantenimiento as
como la bandeja de drenaje.
Los paneles sern construidos con lmina de aluminio texturada
El intercambiador de calor ser construido con tubera de cobre y aletas de aluminio.
Los motores de los ventiladores sern del tipo permanentemente sellado y con
proteccin trmica, cableados en fbrica.
Todos los modelos de evaporadores tendrn instaladas vlvulas para verificacin de la
presin de succin y el control de desempeo.
Todos los motores de los ventiladores sern de alta eficiencia y bajo consumo de
energa.
En cada unidad existirn rejillas metlicas de proteccin sobre las hlices de los
ventiladores las cuales debern estar recubiertas con pintura electrosttica.
El panel de conexin elctrica de las resistencias de deshielo estar ubicado en el
lateral opuesto de las conexiones de refrigerante de la unidad, permitiendo un
excelente acceso para mantenimiento.

pg. 301

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

DETALLE DE ESPECIFICACIONES
RUBRO
CANTIDAD
UNIDAD EVAPORADORA
Tipo de defrost
DIMENSIONES
frente
fondo
alto
CAPACIDAD
@25 F temp. Evap
Temp. evaporacin
SUMINISTRO ELECTRICO
Voltaje
VENTILADOR
No. De ventiladores
alcance
CONEXIONES
refrigerante
lquido
gas
drenaje
UNIDAD CONDENSADORA
Rango de operacin
potencia
presin de diseo baja
presin de diseo alta
suministro elctrico

plg.
plg.
plg.
BTU/hr.
C
volt/frec/ph

ft.

plg.
plg.
plg.
F
watt
psig
psig
volt/frec/ph

AA-07.01
1

AA-07.02
1

AA-07.03
4

AA-07.04
3

aire

aire

resistencia

resistencia

38
12-1/4
13 1/2

33
12-1/4
13 1/2

54
12-1/4
13-1/2

81
12-1/4
13-1/2

7500
0

6000
0

10200
0

16100
-15

230/60/1

115/60/1

230/60/1

230/60/1

2
18

1
15

2
18

4
22

R507
1/2
7/8
1

R507
1/2
7/8
1

R507
1/2
7/8
1

R404A
1/2
1-1/8
1

-10 a 45
1300
181
450
208/60/1

-10 a 45
1300
181
450
115/60/1

-10 a 45
1700
181
450
208/60/1

-10 a 45
2800
181
450
208/60/1

pg. 302

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: EQUIPO DE CALENTAMIENTO DE AIRE PARA DUCTOS
UNIDAD DE MEDIDA Y PAGO: u

CODIGO: 9580-9581

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Los equipos de calentamiento para ductos tendrn como elemento de calefaccin
resistencias elctricas y estarn certificados por UL adems de cumplir con todos los
requisitos establecidos en el cdigo NEC
Las estructuras y cubiertas de los equipos sern construidas en lmina de acero
galvanizada de calibre 20 o superior.
Los equipos contarn con un panel de control elctrico construido por separado en
lmina de acero galvanizado calibre 20 o superior.
Todo el cableado elctrico ser realizado en fbrica y cada unidad contendr impreso
el diagrama elctrico respectivo.
La unin con los ductos del circuito de aire acondicionado ser bridada con un ancho
de brida de 1 pulgada de acuerdo a las normas SMACNA
PROTECCION POR SOBRECALENTAMIENTO
Los equipos contarn con mnimo dos dispositivos que supriman el suministro de
energa en caso de sobrecalentamiento y su operacin ser en cascada es decir el
segundo dispositivo actuar en caso de falla del primero.
PROTECCCION POR SOBRECARGA DE CORRIENTE
Todos los equipos contarn con dispositivos para proteccin en caso de sobrecarga de
corriente del tipo fusible o breakers limitado a 60 amps mximo.
PROTECCION ANTE FALLO DEL FLUJO DE AIRE
Se requiere que todos los equipos tengan un esquema de control y los dispositivos
adecuados para que el equipo no sea energizado si el ventilador no lo est y adems
no existe flujo de aire en el ducto tal como recomiendan las normas UL y NEC
PROTECCION DE TRANSFORMADORES
Todos los transformadores debern contar con dispositivos de proteccin por
sobrecarga.
SWITCH DE DESCONEXION
Todos los equipos contarn con un dispositivo de desconexin remoto instalado cerca
de cada equipo.
INSTALACION
Todos los procedimientos de instalacin se harn cumpliendo con los estndares
establecidos por SMACNA en lo referente a ductos y UL y NEC en lo referente a la
instalacin elctrica.

pg. 303

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

En el lugar de la instalacin siempre se deber prever el espacio libre para las tareas
de mantenimiento.
Se deber verificar que el sentido del flujo del equipo corresponda al del ducto.
El equipo deber estar instalado mnimo a 4 pies de distancia de la unidad manejadora
de aire.
El equipo deber contar con una separacin no menor a 4 pies de cualquier dispositivo
de la red que pudiera producir turbulencias tales como, codos, transiciones etc.
El ducto podr ser reforzado de ser necesario para prevenir deflexin.
DETALLE DE UNIDADES
CANTIDAD
RUBRO
9580
9581

65
22

CAUDAL
(cfm)
600
1050

DIMENSIONES
(in x in.)
12x8
16x10

POTENCIA
(Kw)
2.9
5.08

ENERGIA
(volt/fr/ph)
208/60/3
460/60/3

pg. 304

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: EQUIPO DE AIRE ACONDICIONADO DE PRECISION TIPO AUTO CONTENIDO

ENFRIADO POR AIRE


UNIDAD DE MEDIDA Y PAGO: u

CODIGO:N2.AA-07.06

CONTENIDO DEL RUBRO


Suministro, transporte, instalacin, puesta en marcha y pruebas. Incluye bases y
consumibles

ESPECIFICACIN
Unidad de aire acondicionado tipo auto contenida de precisin y enfriada por aire para
aplicaciones de cuartos de control o computadores data centers.
El equipo deber contar con las siguientes caractersticas:
Controlar de manera precisa la temperatura, humedad y calidad de filtrado del
aire
Su tamao deber ser al mnimo adecuado para ser instalado dentro del Data
Center.
Acceso por la parte frontal a todos los componentes crticos del equipo.
Controles electrnicos de precisin que permitan una ptima eficiencia del
sistema.
Uso de compresores con tecnologa inverter y empleo de refrigerantes
ecolgicos del tipo R407 C
El sentido del flujo ser del tipo Downflow
Todo el circuito de tuberas de refrigeracin y cableado elctrico deber ser
montado y probado en fbrica.
La cabina ser de lmina de acero con recubrimiento apropiado a prueba de
corrosin.
Los ventiladores debern ser del tipo centrifugo de alabes orientados hacia
adelante.
El motor deber estar montado sobre una base ajustable que permita un fcil
acceso para las tareas de servicio Los motores elctricos debern tener
rodamientos del tipo cojinetes de bolas sellados y permanentemente
lubricados.
Todos los elementos de sujecin debern ser de materiales resistentes a la
corrosin
Las poleas del ventilador debern contar con dispositivos que permitan regular
la tensin de las bandas
Los equipos debern instalarse con bandas del tipo static-free
El suministro de energa ser de 220/3/60.

pg. 305

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

DETALLE DE ESPECIFICACIONES
CAPACIDAD (29C, 33%RH)
Total
BTU/HR.
Sensible
BTU/HR.
CAPACIDAD (24C, 45%RH)
Total
BTU/HR.
Sensible
BTU/HR.
VENTILADOR
Caudal
cfm
potencia
hp
presin esttica
pulg H2O
EVAPORADOR
Area
ft2
# de filas
velocidad de flujo
fpm
FILTROS
dimensin
mm
tipo
HUMIDIFICADOR
Tipo
capacidad
lb/hr.

67,900.00
67,900.00
60,500.00
56,600.00
2,800.00
2.00
0.30
6.67
4.00
405.00
724*749
MERV 8
infrarrojo
11.00

pg. 306

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

GRUPO: SISTEMA DE AIRE ACONDICIONADO Y VENTILACION


RUBRO: LAMPARA ULTRAVIOLETA PARA INSTALACION EN DUCTO DE EXTRACCION
CODIGO:N2.AA-11.09

UNIDAD DE MEDIDA Y PAGO: u

al 11

CONTENIDO DEL RUBRO


Los emisores debern ser ensamblados y probados completamente en fbrica. La
unidad ser del tipo base de doble extremo (double ended fixture), para montaje en
pared.
El emisor constara de base, fuente, reflector, sockets y emisor. La base estar
fabricada de acero inoxidable 304.
El reflector estar construido de aluminio pesado de acabado especular para una
reflectancia de 85% a una longitud de onda de 254 nm.
La base estar equipada con unos agujeros para conexin elctrica de en cada
lado para facilitar el cableado de alimentacin elctrica.
La fuente elctrica ser de clase P2 con un factor de potencia de 0.98 y una
conversin de potencia mayor a 90%.
El diseo de la fuente supresin del tipo RF y EMI.
La fuente estar diseada para una mxima produccin de fotones, irradiacin y
confiabilidad en ambientes fros entre 0 y 140 F y 100% humedad relativa.
La fuente ser para 220V, monofsico, 60Hz.
Los sockets sern del tipo doble pin, con doble seguro al girar, estarn construidos de
policarbonato resistente a rayos UV. El emisor ser del tipo de alta emisin, de ctodo
caliente, dimetro T5, con doble pin en los extremos.
El emisor ser capaz de producir una luz de 253.7 nm de longitud de onda, podr
operar con velocidades de aire de hasta 2000 FPM y temperaturas de aire de 35 a 140
F.
Esta unidad no producir ozono u otro contaminante secundario.
La unidad completa estar probada en un laboratorio independiente, el cual verificar
que desde un arco de 1 (emisor) produzca una salida no menor a 9 microwatt por
centmetro cuadrado (9 ms/cm2) a 1 metro de distancia en una corriente de aire de
400 FPM a 50 F.
El emisor deber cumplir con los estndares ANSI/UL 153, 1598, 1995 y los
estndares de la CSA y CE.
El fabricante de los emisores deber contar con certificacin ISO.

DETALLES DEL RUBRO


RUBRO

CANTIDAD POTENCIA

LONGITUD

(watt)

(In.)

AA-11.09

11

100

17

AA-11.10

100

22

AA-11.11

100

36
pg. 307

ESPECIFICACIONES TCNICAS:
PROYECTO: HOSPITAL

SISTEMAS DE AIRE ACONDICIONADO Y


VENTILACIN MECNICA

GENERAL GUASMO SUR - ZOFRAGUA

FECHA ACTUALIZACIN: Marzo/2015

RESPONSABLE: F.CH.

pg. 308