J. H. NEHER
MEMBER AIEE
compilations.
The calculation of the temperature rise
of cable systems under essentially steadystate conditions, which includes the effect
of operation under a repetitive load cycle,
as opposed to transient temperature rises
due to the sudden application of large
amounts of load, is a relatively simple
procedure and involves only the application of the thermal equivalents of Ohm's
and Kirchoff's Laws to a relatively simple
thermal circuit. Because this circuit
usually has a number of parallel paths
with heat flows entering at several points,
however, care must be exercised in the
method used of expressing the heat flows
and thermal resistances involved, and
differing methods are used by various engineers. The method employed in this
paper has been selected after careful con-
M. H. McGRATH
MEMBER AIEE
Nomenclature
(A F) = attainment factor, per unit (pu)
A, = cross-section area of a shielding tape
or skid wire, square inches
a = thermal diffusivity, square inches per
hour
CI= conductor area, circular inches
d = distance, inches
d,2 etc.= from center of cable no. 1 to center
of cable no. 2 etc.
d,2' etc. = from center of cable no. 1 to
image of cable no. 2 etc.
d1j etc. =from center of cable no. 1 to a
point of interference
point of interference
D = diameter, inches
D= inside of annular conductor
Dc=outside of conductor
D= outside of insulation
Ds=outside of sheath
D.= mean diameter of sheath
D= outside of jacket
DJ'= effective (circumscribing circle) of
several cables in contact
D= inside of duct wall, pipe or conduit
De= diameter at start of the earth portion
of the thermal circuit
Dz=fictitious diameter at which the effect
of loss factor commences
E=line to neutral voltage, kilovolts (kv)
*e=coefficient of surface emissivity
e =specific inductive capacitance of insulation
f=frequency, cycles per second
F, Fin1 = products of ratios of distances
F(x)=derived Bessel function of x (Table
III and Fig. 1)
G =geometric factor
GI =applying to insulation resistance (Fig. 2
of reference 1)
C2 = applying to dielectric loss (Fig. 2 of
reference 1)
Gb =applying to a duct bank (Fig. 2)
I=conductor current, kiloamperes
k,=skin effect correction factor for annular
and segmental conductors
kp=relative transverse conductivity factor
for calculating conductor proximity
effect
I= lay of a shielding tape or skid wire, inches
L=depth of reference cable below earth's
surface, inches
Lb = depth to center of a duct bank (or
backfill), inches
(If)=load factor, per unit
(LF) =loss factor, per unit
n=number of conductors per cable
n'=number of conductors within a stated
diameter
N=number of cables or cable groups in a
system
P=perinmeter of a duct bank or backfill,
inches
cos4-=power factor of the insulation
q,=ratio of the sum of the losses in the
conductors and sheaths to the losses
in the conductors
q,= ratio of the sum of the losses in the
conductors, sheath and conduit to
the losses in the conductors
R =electrical resistance, ohms
Rd d-c resistance of conductor
Rae= total a-c resistance per conductor
R, = d-c resistance of sheath or of the
parallel paths in a shield-skid wire
assembly
R-thermal resistance (per conductor losses)
thermal ohm-feet
= of insulation
jacket
RI=ofbetween
cable surface and surrounding
=ad
enclosure
Paper 57-660, recommended by the AIEE Insulated
Conductors Committee and approved by the AIEE
Technical Operations Department for presentation
at the AIEE Summer General Meeting, Montreal,
Que., Canada, June 24-28, 1957. Manuscript
submitted March 20, 1957; made available for
printing April 18, 1957.
J. H. NisaBR 15 with the Philadelphia Electric
Company, Philadelphia, Pa.. and M. H. MCGRATH
is with the General Cable Corporation, Perth
Amboy, N. J.
752
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
OcToiBE:R 1957
www.DownloadPaper.ir
0.09
-.
-i 2~~~~~~~~~~~~~~~~~~.
t.
1.2
0.07
t1
e-00
~~~~~~~~0-.05
~~~~~~~~~~~~~~0\000
~ 04~~~
t ~~~~0.002
__ _
<21.0
1.0-_X _L-22r 7
1.
.0
1)
s
cr-
40
z
0.2
F(p025
m_
i.
0.10
5 6 7689 10
2 2.5 3
15
R dc/k
30
20
9iN
.5
0.02
o010
40 50 60
: Fk0 0[ T 1Mi~ ~ o, 01
-1
:,
la
2.5
2.0
0.03
~~~~~~~~~0.06
ILL
-T-
.3 .l
or
asphalt
mastic
.2
and
conductor
between
pipe
between a steam
earth
and ambient
current
center
of
the
Ta
of ambient air
or
temperature of medium
AT=temperature rise, degrees centigrade
ATC=of conductor due to current produced
losses
A Td = of conductor due to dielectric loss
=T
nIof a cable due to extraneous heat
=
mean
source
r= inferred
W=losses developed in
conductor foot
OcToBim 1957
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
._.
cable, watts
per
Thus
duit
YC=due
to
Considerations of the
dI Circuit
General (
Therm
earth
T =of conductor
Tm
in the conductor
W,=ortiorn developed im the sheath or
shieldd
W =portioiIn developed in the pipe or con-
W-portioP a developed
duct
the
.7
RATIO Lb/P
A,,
Rea
.?
.5
covering
THE CALciULATION
Op
osd
foot through a thermal resistance expressed in thermal ohm feet (degrees centigrade feet per watt); in other words, the
radial rise in degrees centigrade for a heat
flow of one watt uniformly distributed
over a conductor length of one foot.
Since the losses occur at several positions in the cable system, the heat flow in
the thermal circuit will increase in steps.
It is convenient to express all heat flows in
terms of the loss per foot of conductor, and
AT- Wc(R
TEMPERATURE
the result of
thus
as
RISE
of
(1)
qsRs+qAR)
sum
753
www.DownloadPaper.ir
is the thermal resistance between the
conduit and ambient.
In practice, the load carried by a cable
is rarely constant and varies according to
a daily load cycle having a load factor
(f). Hence, the losses in the cable will
vary according to the corresponding
daily loss cycle having a loss factor (LF).
From an examination of a large number of
load cycles and their corresponding load
and loss factors, the following general relationship between load factor and loss
factor has been found to exist.I
(LF)=Q.3 (lf)+0.7 (If)2 per unit
(3)
In effect this means that the temperature rise from conductor to DA is made to
depend on the heat loss corresponding to
the maximum load whereas the temperature rise from diameter D. to ambient is
made to depend on the average loss over a
24-hour period. Studies indicate that the
procedure of assuming a fictitious critical
diameter D, at which an abrupt change
occurs in loss factor from 100% to actual
will give results which very closely
approximate those obtained by rigorous
transient analysis. For cables or duct
in air where the thermal storage capacity
of the system is relatively small, the maximum temperature rise is based upon the
heat flow dorresponding to maximum load
without reduction of any part of the
thermal circuit.
When a number of cables are installed
close together in the earth or in a duct
bank, each cable will have a heating effect
upon all of the others. In calculating
the temperature rise of any one cable, it is
convenient to handle the heating effects of
the other cables of the system by suitably
modifying the last term of equation 4.
This is permissible since it is assumed
that all the cables are carrying equal currents, and are operating on the same load
cycle. Thus for an N-cable system
A TC
=
Wc(Rg+qsRsa+qe[Rx+(LF) X
(fRxaM+N-1)fRPaD
Wc(Ri+qeRsa+qsR,')
(S)
(8)
J=.i -(Ta+ATd)
IRde(l1+ Yc)R?ca
kiloamperes
(9)
Circular Mil
Material
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
t, C
at 20 C
cpe
12.9
=Cl for 100% IACS copper
CI
conductor at 75 C
21.2
(10)
(IOA)
aluminum at 75 C (lOB)
where CI represents the conductor size in
circular inches and where Pr represents
the electrical resistivity in circular mil
ohms per foot. To determine the value of
resistance at temperature T multiply the
resistance at 20 C by (r+T)/(r+20)
where r is the inferred temperature of
zero resistance.
The resistance of the sheath is given
by the expressions
R, =
Ps
4Dsmt
for lead at 50 C
Rs =37-9
D8aM
=4.75
(IIA)
(hIB)
where Dsm is the mean diameter of the
sheath and I is its thickness, both in
inches
(12)
D,.m D,-t inches
expression
754
OCTOBER 1957
www.DownloadPaper.ir
Table Ii. Recommended Values of kc, and kp
tape
'
or
Conductor Construction
Coating
Treatment k
on Strands
round conductor of the same cross-sectional area and spacing. The Increased diameter of the
type and the removal of metal from the center decreases the skin effect but, for a given axial spacing, tends
to result in an increase in Proximity.
4. The values listed above for compact segmental refer to four segment constructions. The "uncostedtreated" values may also be taken as applicable to four segm'ent comnpact segmental with hollow core (approximately 0.75 inch clear). For "uncoated-treated" six segment hollow core compact segmental limited
test data indicates ks and kV vialues of 0.39 and 0.33 respectively.
Wc =I'RdC(1 +YC)
0.02...
0.04 ...
0.08 ...
0.02...
0.05 ...
0.09 ...
0.01 ...
0.02 ...
0.05...
0.02...
0.05...
0.03...
0.03
0.14... 0.15 ... 0.18... 0.17 ... 0.18... 0.19... 0.19... 0.20
0.24... 0.25 ... 0.26... 0.28 ... 0.29 ... 0.30... 0.31... 0.33
0.38... 0.39 ... 0.41 ... 0.43... 0.45 ... 0.47... 0.48... 0.50
0.58... 0.58 ... 0.81... 0.83... 0.65 ... 0.68 ... 0.70 ... 0.73
0.81... 0.84... 0.87 ... 0.90... 0.94... 0.97 ... 1.00 ... 1.03
1.14 ... 1.18... 1.22 ... 1.26... 1.30:.. 1.34 ... 1.38 ... 1.42
1.56..... 1... .6...
1.71... 1.76... 1.81... 1.86... 1.92
1.4... 1.97... 2.02... 2.08 ... 2.14 ... 2.20 ... 2.26 ... 2.32... 2.39 ... 2.45... 2.52
... 2.58... 2.65... 2.72... 2.79 ... 2.88... 2.93 ... 3.01... 3.08 ... 3.16... 3.24
(18) 1.51...
=1+qs
3.32... 3.40... 3.49... 3.57... 3.66... 3.75 ... 3.83... 3.92 ... 4.02... 4.11
1... 4.21 ... 4.30... 4.40... 4.50... 4.80... 4.70... 4.81 ... 4.91 ... 5.02 ... 5.13
1+Y
6.31
we
1.8 ... 5.24 ... 5.35... 5.47... 5.58... 5.70... 5.82... 5.94 ... 6.08.. 61...
... 8.57... 6.70... 6.83... 8.97... 7.11... 7.24... 7.38 ... 7.53 ... 7.67
1.9... 6.44
(19) 2.0...
9.21
89
8
...
9.05...
8.26...
8.42...
8
8.73...
7.98...
8.11
...
7.82...
57...
2.1 ... 9.38... 9.54... 9.71... 9.88... 10.05... 10.22 ... 10.40... 10.58... 10.76... 10.94
2.2... 11.13... 11.31 ... 11.50... 11.69 ... 11.88... 12.07... 12.27... 12.47... 12.67... 12.87
The factor Y, is the sum of two coiinpo- 2.3... 13.07 ... 13.27 ... 13.48 ... 13.68 ... 13.90 ... 14.11... 14.33... 14.54... 14.76... 14.98
15.21 ... 15.43 ... 15.66 ... 15.89 ... 16.12 ... 16.35... 18.58... 16.82 ... 17.16 ... 17.30
nents, Ya, due to skin effect and Yp, due 2.4...
2.5.., 17.54... 17.78 ... 18.03 ... 18.27 ... 18.52 ... 18.78... 19.03 ... 19.28 ... 19.54 ... 19.80
2.6... 20.08... 20.32... 20.58... 20.85 ... 21.12 ... 21.38... 21.65 ... 21.93 ... 22.20... 22.48
proxuimity effect.
2.7... 22.75... 23.03 ... 23.31 ... 23.60 ... 23.88... 24.17... 24.45... 24.74... 25.03 ... 25.33
2.8... 25.62... 25.92 ... 26.21 ... 26.51... 26.81 ... 27.11... 27.42... 27.72... 28.03 ... 28.34
2.9... 28.65... 28.96 ... 29.27 ... 29.58... 29.90 ... 30.21 ... 30.53 ... 30.85... 31.17 ... 31.49
(2)
watts per conductor foot
(2) 3.0 ... 31.81... 32.13 ... 32.45... 32.78... 33.11 ... 33.44 ... 33.77 ... 34.10 ... 34.43... 34.77
3.1 ... 35.10... 35.44... 35.78... 36.11 .. 36.45 ... 36.79... 37.13 ... 37.47 ... 37.82... 38.16
The skin effect may be determined from 3.2... 38.50... 38.85... 39.20... 39.55... 39.89 ... 40.24... 40.59 ... 40.94 ... 41.29... 41.65
3.3... 42.00... 42.35... 42.71... 43.08... 43.42 ... 43.78... 44.14 ... 44.49... 44.85... 45.21
the skin effect functilon F(x)
3.4... 45.57... 45.93 ... 46.29 ... 46.66... 47.02 ... 47.38... 47.74... 48.11... 48.47... 48.84
... 52.51
3.5... 49.20... 49.57 ... 49.94 ... 50.30... 50.67.. 51.04... 51.40... 51.77... 52.14
3.8 ... 52..88 ... 53.25... 53.62... 53.99... 54.36 ... 54.73... 55.10... 55.48... 55.85 ... 58.22
(21)
YCs= F(xs)
3.7 ... 56.59 ... 56.96... 57.33... 57.71 .. 58.08... 58.45... 58.82.... 59.20 ... 59.57... 59.94
6.80
Ifk
3.8 ... 60.31 ... 60.69... 81.08... 61.44 ... 61.81 ... 82.18... 82.56... 62.93 ... 63.30 ... 63.68
at 60 cyclc es 3.9 ... 84.05 ... 64.42 ... 64.80... 65.17 ... 65.55 ... 65.92... 88.29... 66.67... 67.04 ... 67.41
x8j=0.8'175.t 4.0... 67.79 ... 68.18 ... 68.53.;.. 68.91 ... 69.28... 69.65... 70.03... 70.40... 70.77 ... 71.14
4.1 ... 71.52 ... 71.89 ... 72.26... 72.63 ... 73.00... 73.38... 73.75... 74.12... 74.49... 74.86
(22) 4.2
75.97... 76.34... 76.71 ... 77.08 ... 77.45... 77.82 ... 78.19... 78.56
... 75.23 ... 75.60.
4.3 ... 78.93... 79.30... '79.67... 80.04... 80.41 ... 80.78 ... 81.14... 81.51 ... 81.88... 82.25
in which the factor k, depends upo: nte
82.61... 82.98... 83.35... 83.61... 84.08 ... 84.45 ... 84.81 ... 85.18 ... 85.55 ... 85.91
4.the
4.5.-. 86.28 ... 86.64... 87.01... 87.37... 87.73... 88.10 ... 88.46 ... 88.82... 89.19 ... 89.55
conductor construction. For soIliid or 4.6
.. 89.91 ... 90.28... 90.64 ... 91.00... 91.37... 91.73... 92.09 ... 92.45 ... 92.81... 93.17
conventional conductors approlpriate 4.7 ...
93.53... 93.89... 94.25 ... 94.61... 94.97... 95.33 ... 95.69... 98.05 ... 96.41 ... 96.77
... 97.13... 97.49 ... 97.85... 98.21... 98.57 ... 98.92 ... 99.28 ... 99.64... .100.00... .100.35
values of k8 will be found in Table II. The 4.8
4.9.. .100.71.. .101.07... .101.42... .101.78... .102.14... .102.49 ... 102.85... .103.21.. .103.56.. .103.92
C
..
k,
D..D(lc+2Do)2
in which D, and
D0, represent
(23)
the outer
and inner diameters of the annular conductor. In comparison wi'th the rigorous
Bessel function solution for the skin effect
in an isolated tubular conductor, it has
been found that the 60-cycle ski'n effect of
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
755
www.DownloadPaper.ir
Table IV. Mutual Reactance at 60 Cycles, Conductor to Sheath (or Shield)
Dam/2S
0.4.
0.3.
0.2.
O.1.
21.1 ...
27.7 ...
37 0 ...
52.9 ...
Ycp
F(xp)(
2~
)X
4F(Xt)F(x,) +0.27.]
=4( S
F(xp') (24A)
R,JRdc
approximately
(27A)
2.52SI
Xm=52.9 log -D
IS\
1-I
(2Rs
( 2S
)212 DS)
5
2S
when (5.2
D,m
(30)
R82/(Ra2+Xm2)
In computing average eddy current for
cradled configuration, S should be taken
equal to the axial spacing and not to the
geometric-mean spacing. Equations 30
and 30(A) may be used to compute the
eddy-current effect for single-conductor
cables installed in separate ducts.
Strictly speaking, these equations apply
only to three cables in eqwulateral configuration but can be used to estimate
losses in large cable groups when latter are
so oriented as to approximate a regular
polygon.
3RM
Yae8 Rdc
(2s/Dsm)2
(2s/Dam)4
+
+
52,
5.2R8\s
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
+1 41-1+1
(2s/Dsm )"
( 5.2Rf) +1
(31)
unity,
396 ( 2s\
RsRdc (5Dam)
approximately at 60 cycles (31A)
s=1.155T+0.6OXthe V gauge depth for
compact sectors
1.155T+0.58 D, for round conductors
(32)
756
5 Ds", 2
22
(27)
1 +(R8/Xm)'
Yc=R
396
RsRds 2S
OcrOBER 1957
www.DownloadPaper.ir
ances of approximately 10,000 or more
microhms per foot of cable. Even on
the assumption that the assembly resistance is halved because of contact with adjacent conductors and the lead sheath
computations made using equations 27
and 30 show that the resulting circulating
and eddy current losses are a fraction of
1% on sizes of practical interest. For this
reason it is customary to assume that the
losses in the shielding and binder tapes
of 3-conductor shielded paper lead cable
are negligible. In cases of nonleaded rubber power cables where lapped metallic
tapes are frequently employed, tube
effects may be present and may materially
lower the resistance of the shielding assembly and hence increase the losses to a
point where they are of practical significance.
An exact determination of the pipe loss
effect Yp in the case of single-conductor
cables installed in nonmagnetic conduit
or pipe is a rather involved procedure
as indicated in reference 7. Equation 31
may be used to obtain a rough estimate
of Yp for cables in cradled formation on
the bottom of a nonmagnetic pipe, however by taking the average of the results
obtained for wide triangular spacing
with s=(Dp-D,)/2 and for close triangle spacing at the center of the pipe
with s=0.578 D. The mean diameter of
the pipe and its resistance per foot should
be substituted for Dam and R8 respectively.
For magnetic pipes or conduit the
following empirical relationships8 may be
employed
1.54s-0.115D, (3-conductor cable)
Rdc
(33)
Y= 0.89S -0.11D(single-conductor,
Rdc
Y= 0.34S+0.175D
(single-conductor,
Rdc
cradled) (35)
These expressions apply to steel pipe8
and should be multiplied by 0.8 for iron
conduit."
The expressions given for Y, and Y.
above should be multiplied by 1.7 to find
the corresponding in-pipe effects for magnetic pipe or conduit for both triangular
and cradled configurations.
CALCuLATION OF DIELECTic Loss
log (2T+Dc)/Dc
OMrOBriR 1957
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
Material
thickness.
,o, C Cm/Watt
R=0.0104fin'(D )
thermal ohm-feet
(40)
A'
B'
757
www.DownloadPaper.ir
given in Table VII have been determined
from the experimental data given in references 10 and 11.
If representative values of Tm =60 C
are assumed, equation 41 reduces to
"'A
A,u -
thermal ohm-feet
(41A)
A,..
AmR
15.6n'
+0.0167Tm)I
[(AT/D.')""4+1.6f(1
Ds'
thermal ohm-feet (42)
In this equation AT represents the difference between the cable surface temperature T, and ambient air temperature Ta in
degrees centigrade, Tm the average of
these temperatures and e the coefficient of
emissivity of the cable surface. Assuming representative values of TJ=60 and
Ta=30 C, and a range in D.' of from 2
to 10 inches, equation 42 may be simplified
to
9.5n'
R.5='
1+1.7D.'(e+0.41)
thermal ohm-feet
(42A)
expression1l
thermal ohm-feet
(43)
R,' =0.012Asn'X
[log Dx+(LF) log [() F]]
thermal ohm-feet (44)
F-d12 (d13'\(dIN'\terms
(d12 )ld13 ) d,NI)
(46)
R0 = 0.012pcnI X
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
Ac)n'N(LF)Gb
758
OCTOIBER 1957
www.DownloadPaper.ir
from the cable, the outward flow of heat
from the core of the earth, and the inward heat flow solar radiation, and, when
present, the heat flow from interfering
sources. By employing as the ambient
temperature in the calculations the temperature at the depth of burial of the
hottest cable, the combined heat flow
from earth core and solarradiation sources
is superimposed upon that produced at
the surface of the hottest cable by the
heat flow from that cable and interfering
sources which are calculated separately
with all other heat flows absent. The
combined heat flow from earth core and
solar sources results in an earth temperature which decreaseswith depth in summer;
increases with depth in winter; remains
about constant at any given depth on the
average over a year; approximates constancy at all depths at midseason, and
in turn results in flow of heat from cable
sources to earth's surface, directly to surface in midseason and winter and indirectly to surface in summer.
Factors which tend to invalidate the
combined Kennelly-superposition principle method are departure of the temperature of the surface of earth from a true
isothermal (as evidenced by melting of
snow in winter directly over a buried
steam main) and nonuniformity of
thermal resistivity (due to such phenomena as radial and vertical migration
of moisture). The extent to which the
Kennelly-superposition principle method
is invalidated, however, is not of practical
importance provided that an over-all or
effective thermal resistivity is employed in
the Kennelly equation.
Special Conditions
Although the majority of cable temperature calculations may be made by
the foregoing procedure, conditions frequently arise which require somewhat
specialized treatment. Some of these
are covered herein.
EMERGENCY RATINGS
OCTOBER 1957
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
iTC'-
RdRdc(l+Yc)(1c+'-Y-)-(Ta+'
~~~RdA8l
Yc)Rc s'
= Tc-(Ta+ATd+ATfnt)
Rdc(l + Yc)R?ca'
kiloamperes (9A)
in which ATin, represents the sum of a
number of interference effects, for each
of which
A Tn [Wcq.(LF) + WdJR in
Fn
=(d1j')(d2i')(daj1).
.dNi' (N term)
(dF (d2i)(d3j) d
..
(d
...
(N
(50)
where the parameters apply to each system which may be considered as a unit.
For cables in duct
Rint = 0.012n'I[c log Fint+N(f3-AC)GX]
thermal ohm-feet (49A)
ATtnt
[Ty-Ta }
e
c. ti
Td)
kiloamperes (47)
where
AERIL CABLES
In the case of aerial cables it may be
desirable to consider both the effects of
solar radiation which increases the temperature rise and the effect of the wind
which decreases it.24 Under maximum
sunlight conditions, a lead-sheathed cable
will absorb about 4.3 watts per foot per
inch of profile"8 which must be returned
to the atmosphere through the thermal
resistance Rc/n'. This effect is conveniently treated as an interference
temperature rise according to the rela-
tionship
A Ting
=4.3DJ'Re/n'
thermal ohm-feet
(42B)
Rft
)(1
Ysa (;) I
12/
(52)
759
www.DownloadPaper.ir
ATec
Wc[RA+qa,IRas+R,,+(LF)RspI +
Condition
Rsd
ATPS 1/
+b+cTm]
(53)
where
A.d = the effective thermal resistance between cable and enclosure in thermal
ohm-feet
D,J'=the cable diameter or equivalent
diameter of three cables in inches
AT= the temperature differential in degrees
centigrade
P=the pressure in atmospheres
Tm=mean temperature of the medium in
degrees centigrade
n'=number of conductors involved
The constants a, b, and c in this equation
have been established empirically as follows:
Considering b+cT, as a constant for the
moment, the analysis given in reference
10 results in a value of a = 0.07. With a
thus established, the data given in reference
10 for cable in pipe, and in reference 11
for cable in fiber and transite ducts were
analyzed in similar manner to give the
values of b and c which are shown in Table
VIII.
0.d0.60+0.025(Da'?TmSAT)114
n'W (radiation)
to'0
n'WAT
(total)
15.6n'
Ds'1(AT/Ds')"/'+1.6e(l +0.0167Tm)]
with Tm=45 C
AT
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
3.5n'
6tn'W(total) Dhe(maVlohDmt+4.62B)
thermal ohm-feet (42B)
760
20
10
41.
(41)
AT
0.079.0.0016 ....
0.121 .0.0017 ....
+(B;
Average
0.0017 ......,.20
0.121 ...
Cable in metallic conduit ...................0.07 ..
20
0.036 .. 0,.,.O..0009.
Cable in fiber duct In air. ................. 0.07 ..
.
..0.0014 . , 20
7 ..0.043
..... 0.0
Cable In fiber duct in concrete ........
.. 20
,0.086 .0.0008 ..
..
Cable in transte duct in air ................0.07 .
Appendix I
OCTOBER 1 957
www.DownloadPaper.ir
Appendix 11
=-\/X2+y2
(59)
r2
-7rr,2/log 2
log rb = xy(r-
or
r2 Trrf5X7 /
log-m
lowg-t
ta
\ 71
w(t,'-71ri)
from which
rb - _-)
(60)
It is desirable to derive ra in terms of the
perimeter P of the duct bank. Thus
P =2(x+y) 4 ( +y/x)
2
and therefore
% (AM)
Neher Shankln Wiseman
I.
4. 5 pipe ..... 63/63 ...61/62 ... 63/65
II . 6.0 pipe.....56/56 ... 60/57 .... 53/60
III . 8.6 pipe.....56/56... 59/58 .. 54/63
IV . 10.6 pipe .....58/58 ... 61/59 ... 65/53
V . . 5 cable .....
80/80
VI . 1.5 cable.... 77/76.. .77/76 ... 77/77
Vii. 1. 9 cable....71/71
VIII.... 2.0 cable .....
63/62
IX . 2.0 cable .....
75/74
X . 3.4 cable .....
77/78
3.4 cable... .83/80.. 83/81
Xa*
XI . 3.7 cable....76/74.. 74/73
XII . 4.2 cable....70/66.. .70/67
XIII.... 4.5 cable.... 69/64.. .65/64....61/63
*
Aa'-Re.+A6x+(LF)(42 -R&2)
RcA<
I1-(AF)
(65)
1-(LF)
p(1
(61)
Appendix III
Empirical Evaluation of D2
In order to evaluate the effect of a cyclic
load upon the maximum temperature rise
of a cable system simply, it is customary to
assume that the heat flow in the final
Ds i.02X
Va#Xlength of cycle in hours inches
(45)
Table IX presents a comparison of the
values of per cent attainment factor for
sinusoidal loss cycles at 30% loss factor as
calculated by equations 45, 8, 62(A), and 63
and as they appear in Table II of the first
paper of reference 3.
Tc~81 C; R1c
-37.8
R,2.009(0.120)per foot at 50 C
(Eq. 11A)
(Table II)
Rd,/kp-62.6; F(x,')=0.003
14(0o192
YCP 2[
(Fig. 1)
0]0 0)30.002
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
Inches
Since
OCTrOBE,R1957
Description,
rb
log
System
(67)
s = 1.155(0.175+0.008)+0.60(0.539)
396
-157(37.6)1
2(0.534))2
2.009
q,2=qg
j--1
-.1
(Eq. 31A)
(Eq. 14)
(Eqs. 18-19)
761
www.DownloadPaper.ir
sector conductors, the equivalent diameter
of the conductor is taken equal to that of a
concentric round conductor, i.e., 0.681
inch for 350 MCM.)
%0-
/i
--.
I%
(I\
/..
I.49
\7
-.
(13
'
K'-
d13
1% 96'
Images
d42
d2z 96.5"
I d----
Ta =40 C (assumed)
I=
:87.5"
dg3 - 96"
(Eq. 6)
cl'3,-
78.5"
81-(40+0.8)
37.6[1.010(8.96)]
3.5(3)
2.129 -VO.84/2.129+0.62(0.41)1
=5.59 thermal ohm-feet (Eq. 42B)
thermal ohm-feet
A Ttn g = (4.3)(2.129) -
(Eq. 8)
= 17.1 C
Ta 30 C (assumed)
181 -(30+0.6+17.1)
(Eq. 47A)
Lb ' 43.5"
I-
(37.6)(1.010)(7.34)
69-Kv 1,500-MCM-Single-'
Conductor Oil"Filled Cable in Duct
Two identical cable circuits will be
considered in a 2 by 3 fiber and concrete
duct structure having the dimensions
shown in Fig. 3.
Tc 75 C; Rdc1=5 8.60
1.50
microhms per foot (Eq. 1OA)
T0=75C;
-= 130 microhms
Ro=
(2.243)(0.130)
1.543-0.600 1.543+1.200\'
1.543 +0.600 1.543 +0.600/
=0.72; kp=0.8 (Eq. 23 and Table II)
18"
Rde/k
5/2.243
Ycp=4(92
9.0/
(Eq. 24A)
0.075=0.007
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
69-kv 1,500-MCM
\'01
[l122(9.0))
(q 3A
0.006
1.082
(Table V);
8=1.006
E
(Eq. 14)
(Eqs. 18-19)
69/"3--40;
0.00276(40)2(3.5)(0.005)
cos
#=0.005
2.113
396
12.243
"~=130(8.60) \2(9.0)/
log -~1.543
=0.57 watt
per
762
on
conductor foot
(Eq. 36)
OC,rOBIER 1957
www.DownloadPaper.ir
ATd=0.57(0.45+1.75+0.24+4.63)=4.0 C
(Eq. 6)
1-543
=2.370.2
n'=1; R
=174
0.0104(480)(0.25) = 0.24
5.50-0.25
thermal ohm-foot (Eq. 40)
p.= 120 (asu med); 1.= 85 (Table VI);
L=L&=43.5 inches (Fig. 3)
96.5 (87.5)(78.5)
\9,I9 12.7\ 9 /12.7)
=42,200 (Fig. 3 and Eq. 46)
048;2718 =15
43.5
2(18+27)
Lbp
+
~~~8.3 (42,200)])
0.012(120 -85)(1)(6)(0.80)(0.87)
=6.79 thermal ohm-feet (Eq. 44A)
R8 (at unity loss factor)=8.44
thermal ohm-feet (Eq. 44A)
Rca' =0.90+1.006 (1.74+0.24+6.79)
=9.72 thermal ohm-feet (Eq. 8)
=6.2 C (Eq. 6)
Ta =25 C (assumed);
1 75-(25+6.2)
T7C ;
RdC
T12.9\
1234.5+70
2.00,0\
k234.5+75 /
4(0.00263)
/.6i\
( 1)
(S64
50)=62,900 microhms
4 ++2
r56
(78.5
/(12.7)
(Eq. 50)
Ring 0.012(1)X
[85 log 456 +3(120 -85)(0.87)]
= 3.81
OCToBm 1957
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
(-4(43.5)
92.4\1J
8.3
0.012(120 - 85)(1)(3)(0.80)(0.87)
3.74 thermal ohm-feet (Eq. 44A)
4
F~(96.4V87.5\
Vp
(0.34)(2.76)+(0.175)(8. 13)0.372
6.35
Rac/Rdc
1.171+0.011+0.372 =
(912 +50\
912+20/ =11,100 microhms
per foot at 50 C (Eq. 13)
(net)[(62.9)(111 1]1,000
R8
(Table II)
k,=0.435; kp=0.37
Rd,ks = 14.6; Ycs =0.052(1.7) = 0.088
S=2.66+0.10=2.76; Rde/kp=17.2;
F(xp')=0.035 (Fig. 1)
(Eq. 35)
1.554
(Eq. 14)
0.011+0.372
1.171
0.011
=1.009; q
qs = 1 + 1.171117
= 1.327
(Eqs. 18-19)
cos +=0.005
0.00276(80)2(3.5)(0.005)
log
2.642
DJ=2.661; Dp=8.125
= 0.696
(20.0)2(1.7) =0.011
YS = YSC (9.435)(6.35)
(550 log
8.60(1.082)(9.72)
[o5.5
, =3.5
23.8w
kiloampere (Eq. 9)
To illustrate the case where the cable
circuits are not identical, consider the
second circuit to have 750-MCM conductors. For the first circuit,
N=3; (LF)=0.80 (assumed);
= 52.9 log
XmXm=529
log (2.3)(2.76)
2.66
I2=
+1.74+0.24+8.44)
ATd=0.57(
1 + YC = 1+0.088+0.083 = 1.171
(9.31)(6.65)
=0.715-0.85912' (Eq. 9A)
0.487 kiloampere.
Gb=0.87 (Fig. 2)
Re' (at 80% loss factor) =(0.012)(85)(1) X
(log 3+0.80
5.5 log
( 1.632\'2(0.035)(1.7)=0.083
YC P = 4 ( 2.76/
2 )
n'=3; DJ'=2.15(2.66)-5.72;
3(2.1)
Rad = 5.72 +2.45 = 0.77 thermal
ohm-foot (Eq. 41A)
pd=100 (Table VI); t=0.50;
0.0104(100)(3)(0.50)
9.63-0.50
70-(25+7.4)
(6.35)(1.171)(6.17)
763
www.DownloadPaper.ir
References
Nov. 1932.
2. LOAD FACTOR AND EQUIVALENT HoURS
COMPARED, P. H. Buller, C. A. Woodrow. Electrical World, New York, N. Y., vol. 92, no. 2, 1928,
pp. 59-60.
3. SYMPOSIUm ON TBMPERATURE RISE OP CABLES,
AIRE Committee Report. AIEE Traxsactions,
vol. 72, pt. III, June 1953, pp. 530-62.
4. A-C RESISTANCE OF SSGMBNTAL CABLBS IN
STEEL PIPE, L. Meyerhoff, G. S. Eager, Jr. Ibid.,
vol. 68, pt. II, 1949, pp. 816-34.
S. PROXIMITY EFFBCT IN SOLID AND HOLLOW
ROUND CONDUCTORS, A. R. M. Arnold. Journal,
Institution of Electrical Engineers, London.
England, vol. 88, pt. It, Aug. 1941, pp. 349-59.
6. EDDY-CURRENT LOSsRS MULTI-CORB PAPERINSULATBD LEAD-COVBRBD CABLES, ARMORBD
AND UNARMORBD, CARRYING BALANCBD 3-PlASE
CURRENT, A. H. M. Arnold. Ibid., pt. I, Feb.
1941, pp. 52-63.
7. PIPE LOSsES IN NONmAGNRTIC PIPE, L.
Meyerhoff. AIEE Transactions, vol. 72, pt. III,
Dec. 1953, pp. 1260-75.
8.
A-C RESISTANCE OP PIPE-CABLE SYSTEMS
Discussion
issued in which a simple method is presented for the rapid calculation of cyclic
Table V gives specific inductive capacitance values for paper as: paper insulation
(solid type), 3.7 (IPCEA value); paper
insulation (other type), 3.3-4.2. Is it possible to list the other types and their
appropriate specific inductive capacitance
values or alternatively simply use an
average specific inductive capacitance value
of 3.7, for example, for all types of paper
IN
conditions obtaining.
In Great Britain the basic reference
document is ERA (The British Electrical
and Allied Industries Research Association)
report F/T1311 published in 1939, and in
1955 revised current rating tables for
solid-type cables up to and including 33 kv
were published in ERA report F/T183.
A more detailed report summarizing the
method of computing current ratings for
solid-type, oil-filled, and gas-pressure cables
is now being finalized and will be published
as ERA report FIT187 some time in 1958.
Until recent years current ratings in
Great Britain have usually been considered
on a continuous basis, but the importance
of taking into consideration cyclic ratings
has now been carefully studied, since continued high metal prices have forced cable
users to review carefully the effects of
cyclic loadings. A report has recently been
ratings.'
insulation?
Reference is made to the adoption of the
hypothesis suggested by Kennelly as the
17.
POR
737-48.
19. LossE
IN ARMORED SINGLE-CONDUCTOR,
LEAD-COVERED A-C CABLBS, 0. R. Schurig, H. P.
Kuehni, F. H. Buller. AIRE Transaction:, vol.
SELP-INDUCTION
Authorized licensd use limted to: IE Xplore. Downlade on May 10,2 at 19:54 UTC from IE Xplore. Restricon aply.
SINGLE'CONDUCTOR AR-
Single-core
Armored
.
Single-core
Three-core
..................
80 .
belted-type.....
Lead Sheathed
Armoured
or Un-
Unarmored
Aluminum
Aluminum
Sheathed
Armored
armored
80.
80 .
80.
60. .
80 .
80 .
80 .
60
80
80.80
. .60
80
Unarmored
..............
80 80
60 .
Sheathed
Armored
or Un-
armored
80
80
11 kv
70
.
. .50
70
.
.
Single-core
.................. 70
65 65
. 65 .50 ..
65
Three-core belted-type .......... 65 .
.50 70
70
70 .
70 .
Three-core screened-type ........ 70 .
22 kv
50 65
Single-core ..................... 65. .
50
.55
.
55
Three-core belted-type .......... 55 .
50. . 65
65
65 .
. 65 .
Three-core screened-type ........ 65
.65
.65 .
Three-core (SL$or SAC) ........ 65 . .65
.
33 kv (screened)
Single-core
Three-core ......
Three-core HSL ......
.....
65 .
65.
65
65.65
.
.
. .
.
.
65
50
50
764
OF
OCTOBER 1957