Professional Documents
Culture Documents
Department of Electrical and Electronics Engineering, Faculty of Engineering, University of Peradeniya, Sri Lanka
sarath d_ee.pdn.ac.lk1 ,tha
ee.pdn.ac.lk2,atpu
ee.pdn.ac.lk3,jbe dee.pdn.ac.lk4
II
Configuration of TCSC
The TCSC model presented in this paper consists of three
sub systems: TCSC power circuit, thyristor firing system
and firing angle controller. The TCSC power circuit made
up of parallel combination of a fixed capacitor and
Thyristor Controlled Reactor (TCR) as shown in Fig. 1. A
Metal Oxide Variastor (MOV) is connected in parallel with
capacitor for over voltage protection.
INTRODUCTION
DESIGN CONSIDERATIONS
151
First International Conference on Industrial and Information Systems, ICIIS 2006, 8 - 11 August 2006, Sri Lanka
B Controller circuit
In this model firing angle is defined with respect to the
voltage across the capacitor. Comparison of a triangular
ramp, which is synchronizing with the TCSC voltage and a
dc level, which is define by line current or voltage at
downstream to the TCSC is used to produce the firing pulse
at required angle. The voltage across the TCSC is step
down to a level compatible with the control circuit using a
transformer. The step-down voltage is rectified using a full
wave rectifier bridge and fed through a zero crossing
detector, which is producing a narrow pulse at zero
crossing. This pulse is connected to a triangular ramp signal
generator to produce a triangular ramp which is
synchronized with the TCSC voltage. The rms line current
and voltage at downstream bus was measured and fed to the
controller. A microcontroller was used to determine the
firing angle reference signal according to the current and
voltage feedbacks. By comparing the firing angle reference
I/
-' ~~~~i
Pc-pli
90
z -e
---T-
180
b-
Fig
-~agle (deg)
C Operating modes
According to the impedance characteristic of TCSC shown
in Fig. 2, two impedance regions can be identified:
Inductive and capacitive [5]. When the firing angle is
reaching resonance angle (,res) the impedance of the TCSC
can be infinitely large and that region should be avoided.
The allowable operations regions are defined using PI and
(32- When firing angle is increasing from 900 to (Ures~f3i)0
impedance is inductive and varies from minimum to
allowable maximum. When firing angle decreasing from
1800 to (U,res 32) impedance is capacitive and varies from
minimum to allowable maximum. Depending on the
application using these variable impedance characteristic
different operating modes can be defined. Depending on the
line current and voltage, two operation modes were defined,
(a) voltage compensation and (b) fault current limiting
operation. The voltage controller was designed such that
when the voltage is less than the set level, the TCSC is
switched to variable capacitive impedance mode, where as
when the voltage is higher than the set level, the TCSC is
switched to variable inductive impedance mode. When ever
there is a fault the TCSC was taken into high inductive
impedance region thus limiting the fault current. The
amount of current limiting can be controlled by adjusting
the firing angle.
III
Prototype Network
220
Overhead
Transmssionline
500H
single phase
11 kVA,220/55 V
source
X/
Si4ephase
TM former_
55 VA
0.85 pf
Load
Design Criteria
According to the minimum capacitive and inductive
reactance requirement of the distribution system, the
capacitor Xc and Inductor XL were selected. The resonance
angle (,res) was calculated and stability margins of PI and P32
was maintained to avoid unnecessary high impedance
operations. For a particular application using the current
and voltage values the operation modes need to be defined.
The scaling of current feed back signal and determination
Inductive
152
i~ ~ . 1
First International Conference on Industrial and Information Systems, ICIIS 2006, 8 - 11 August 2006, Sri Lanka
~ ~ ./ _
Gp2a(5Afdiv)
.............
raph 3 a (2 Adiv)
If
(bSimlaio
~~~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ . . . . . . . . . . . . .
Graph' 4 (2 A dv)
(a) Experimental
1n
n2aC
Gr
(lIciv
GIaph 2.b
(lAIciv)1
Graph 3.a i
\VdivI
fY.
I4
Grph3b
...2.0V1icv)
Graph 4.a,7
\ (20 Vliv)
Graph4.b
V >
(20idiv)
I
. . . . . . . . . . . . . . . . . . . . . . . ............. . . . . . . . . . . . . . . . . . l "Il ,"'
(a) Experimental
(b) Simulation
153
First International Conference on Industrial and Information Systems, ICIIS 2006, 8 - 11 August 2006, Sri Lanka
IV
CASE STUDY
8 Gf
Gid itifee d
%0
Shott circuit
level 625 MVA
Bus 1
I I Circuit
Breaker A
Dus 3
25 MVA
12.5/33kV
40 MW
0.90 PF
lagging
21 4 MVA,
12.5 kV DG
i-z-!
Bus 2
TCSC
33 kV Lynx
Over head line
5 km
15 MW
0.90 PF
Bus 4
lagging
5 Mw
0.90 PF lagpgng
B Application of TCSC
In the original network before connect a DG maximum
fault current through Circuit Breaker A was about 12.05
kA. Connection of the DG to bus 2 increases the fault level
at bus 1, thus exceeding the short circuit rating of the
Circuit Breaker A. The voltage profile at bus 2 was poor as
it is located far from the grid substation. Connection of DG
improves the voltage profile up to some level. The fault
current limiting performance and voltage compensation
performance of the TCSC was investigated. According to
the required current limiting capability, compensation
capability and the resonance angle of the TCSC the values
of the capacitor and the inductor were selected as 450 iF
and 16 mH respectively. The operating modes were
selected using current and voltage feedbacks as explained
in section Il-C. If the current is exceeds the rated short
circuit of the generator, it goes to FCL operation. In this
mode TCSC is increasing the inductive impedance from its
minimum value to high value as current increasing from
the rated short circuit current to the maximum fault
current. The current flow at sub transient region during a
sudden short circuit at TCSC upstream terminal was
selected as the maximum fault current. Under normal
operation, the TCSC was used as a voltage regulator to
regulate the voltage at bus 2. The PI controller was tuned
to maintain the voltage at 1.01 pu. Two separate simulation
33 kV Lynx
Over head line
10 km
33 kV Lynx
Over head liine
5 km
Value
27
21.4
18.7
12.5
0.128
0.233
0.351
1.287
0.055
7.93
C Performance as FCL
The fault current limiting performance was studied by
considering the fault current through circuit breaker A
during three phase balance fault at faults in line 1-3. Three
different network configurations were considered: (a)
before connecting the DG, (b) after connecting the DG and
(c) after connecting the DG in series with the TCSC. For
each case the fault was created at 1 km span of line length
starting from bus 1. As circuit breakers are more stressd on
the sub transient period, symmetrical values of the current
at sub transient period were taken as the fault current to
compare with the CB ratings. Fig. 7 illustrates the results
of the simulation study. The results show that application
of DG increase the fault current for all faults and it exceeds
the CB rating in the case of terminal fault. Application of
TCSC reduces the fault current to an acceptable level
which is lower than the circuit breaker rating. As TCSC is
only limiting the current from DG, percentage of total
current reduction is less. In the point of view of overcurrent protection, low current reduction is important as it
will ensure that the existing protection coordination will
not be affected [7].
154
First International Conference on Industrial and Information Systems, ICIIS 2006, 8 - 11 August 2006, Sri Lanka
14
V CONCLUSION
The application of a TCSC for distribution network was
studied. A simple power system was modeled with the
proposed TCSC circuitry and its control. The simulation
results were validated experimentally with the laboratory
prototype. Both studies confirm possibility of using the
TCSC both as an FCL and as a series compensator. An
application study was carried out with real scale distribution
network in PSCAD/EMTDC simulation package. The
TCSC connected in series with the DG solved the problems
associated with the fault current increasing while working
as a voltage compensator. As TCSC used as a voltage
regulator it allows to pump more DG power to the grid
without violating the voltage limits.
This research will be extended to investigate the feasibility
of the TCSC for all issues in the power systems, which are
related on connecting distributed generators to the
distribution network.
B efore C oret DG
X
2
X
O -
- -- - - Afterc
~~~~~~~ret ]DC; with TCSC
' <
CB -hr
icit 'Atig
~~~~~~~~~~-
08-
O 15
1 .1
2.5
3.6
4.15
Fig. 7 Variation of fault current through circuit breaker during fault in line
1-3
ACKNOWLEDGMENT
The author wishes to acknowledge the National Science
Foundation for supplying all the electronic components for
the experiment setup.
REFERENCES
C. Gama and R. Tenorio, "Improvements for power System
Performance: Modeling, Analysis and Benefits of TCSCs", Power
Engineering Society Winter Meeting, Vol 2, pp1462-1467, Jan 2000.
[2] M.N.Moschakis,, E.A Leonidaki, and N.D Hatziargyriou, "
Considerations for the application of Thyristor controlled series
capacitors to radial power distribution circuits" Power Tech
Conference Proceedings, 2003 IEEE Bologna, Vol. 3, pp 23-26
'June 2003
[1]
1.1
1.05
1-
~~~~~~~~~~~~~~~~
= 06.9 0 .9 -
0.85 0.8 -
-9
A
EIf comect
--
10
15
155