WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
TABLE OF CONTENTS
13.2
13.3
13.4
13.5
13.6
13.7
5. Dimensions .......................................................13
5.1
5.2
15.1
16.1
16.2
8.4
17.1
17.2
9.2
18.1
18.2
CS-PC9KKQ CU-PC9KKQ........................19
CS-PC12KKQ CU-PC12KKQ....................20
CS-PC18KKQ CU-PC18KKQ
CS-PC18KKQ-6 CU-PC18KKQ-6 .............21
CS-PC24KKQ CU-PC24KKQ
CS-PC24KKQ-6 CU-PC24KKQ-6 .............22
CS-PC9KKQ CU-PC9KKQ CS-PC12KKQ
CU-PC12KKQ.............................................23
CS-PC18KKQ CU-PC18KKQ
CS-PC24KKQ CU-PC24KKQ
CS-PC18KKQ-6 CU-PC18KKQ-6
CS-PC24KKQ-6 CU-PC24KKQ-6 .............24
Cooling Operation.......................................37
Soft Dry Operation......................................39
Automatic Operation...................................41
Indoor Fan Speed Control ..........................42
Outdoor Fan Speed Control .......................44
Vertical Airflow Direction Control................44
Horizontal Airflow Direction Control............46
Timer Control..............................................46
Random Auto Restart Control ....................46
Remote Control Signal Receiving Sound ...46
CS-PC9/12KKQ......................................... 53
CS-PC18/24KKQ CS-PC18/24KKQ-6...... 57
1. Safety Precautions
Read the following SAFETY PRECAUTIONS carefully before perform any servicing.
Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the
power plug and main circuit for the model installed.
The caution items stated here must be followed because these important contents are related to safety. The
meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction
will cause harm or damage, and the seriousness is classified by the following indications.
WARNING
CAUTION
Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation,
care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for
future reference.
WARNING
20. After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
contacts with fire.
21. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
22. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
23. Must not use other parts except original parts describe in catalog and manual.
CAUTION
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.
2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.
3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
2. Specification
Indoor
CS-PC9KKQ (PHILIPPINES)
CS-PC12KKQ (PHILIPPINES)
Outdoor
CU-PC9KKQ (PHILIPPINES)
CU-PC12KKQ (PHILIPPINES)
JIS
JIS
Phase, Hz
Single, 60
Single, 60
230
230
kW
2.65
3.54
BTU/h
9040
12070
Model
Capacity
9540
12740
4.0
5.5
Input Power
860
1240
Cooling
kJ/h
Running Current
W/W
3.08
2.85
kJ/hW
11.10
10.30
93
98
dB-A
36 / 26
40 / 29
Power Level dB
49 / -
53 / -
dB-A
49 / -
50 / -
Power Level dB
64 / -
65 / -
4.6 / 990
6.5 / 1450
23.0
33.0
Type
Motor Type
Induction (2 poles)
Induction (2 poles)
600
850
Cross-Flow Fan
Cross-Flow Fan
EER
Power Factor
Indoor Noise (H / L)
Outdoor Noise (H / L)
Compressor
Output Power
Indoor Fan
Type
Material
ASG20K1
ASG20K1
Motor Type
Induction (4 poles)
Induction (4 poles)
Input Power
52.3
52.3
Output Power
22
22
Outdoor Fan
Speed
Lo
rpm
650
750
Me
rpm
850
930
Hi
rpm
1030
1100
SHi
rpm
Type
Propeller Fan
Propeller Fan
Material
PP Resin
PP Resin
Motor Type
Induction (6 poles)
Induction (6 poles)
Input Power
68
79.9
Output Power
30
30
rpm
815
835
L/h (Pt/h)
1.6 (3.4)
2.0 (4.2)
6.3 (223)
7.6 (267)
Speed
Hi
Moisture Removal
Lo
Indoor Airflow
Outdoor
Airflow
8.3 (291)
9.4 (332)
10.0 (353)
10.4 (367)
29.2 (1030)
32.6 (1150)
Me
Hi
SHi
Hi
Control Device
Refrigeration
Cycle
Capillary Tube
Capillary Tube
Refrigerant Oil
cm
Refrigerant Type
g (oz)
Height(I/D / O/D)
mm (inch)
mm (inch)
mm (inch)
kg (lb)
9 (20) / 23 (50)
9 (20) / 29 (64)
mm (inch)
Standard length
m (ft)
7.5 (24.6)
7.5 (24.6)
m (ft)
3 (9.8) ~ 10 (32.8)
3 (9.8) ~ 15 (49.2)
m (ft)
5 (16.4)
5 (16.4)
g/m (oz/ft)
10 (0.1)
10 (0.1)
m (ft)
7.5 (24.6)
7.5 (24.6)
Inner Diameter
mm
16
16
Length
mm
550
550
Dimension
Piping
Weight
Drain Hose
Fin Material
Fin Type
Indoor Heat
Exchanger Row x Stage x FPI
Slit Fin
Slit Fin
2 x 15 x 21
2 x 15 x 21
Corrugated Fin
Slit Fin
1 x 19 x 17
1 x 24 x 17
22 x 482.6 x 567.4
Material
Polypropelene
Polypropelene
Type
One-touch
One-touch
Indoor
Indoor
10
10
Size (W x H x L)
mm
Fin Material
Outdoor
Fin Type
Heat
Exchanger Row x Stage x FPI
Size (W x H x L)
Air Filter
mm
Power Supply
Power Supply Cord
Thermostat
Protection Device
DRY BULB
WET BULB
DRY BULB
WET BULB
Maximum
32
23
32
23
Minimum
16
11
16
11
Maximum
43
26
43
26
Minimum
16
11
16
11
1.
Cooling capacities are based on indoor temperature of 27C Dry Bulb (80.6F Dry Bulb), 19.0C Wet Bulb (66.2F Wet Bulb) and outdoor air
temperature of 35C Dry Bulb (95F Dry Bulb), 24C Wet Bulb (75.2F Wet Bulb).
2.
Specifications are subjected to change without prior notice for further improvement.
Model
Indoor
CS-PC18KKQ (PHILIPPINES)
CS-PC24KKQ (PHILIPPINES)
Outdoor
CU-PC18KKQ (PHILIPPINES)
CU-PC24KKQ (PHILIPPINES)
NEW JIS
NEW JIS
Single, 60
Single, 60
Power Supply
Capacity
Running Current
Cooling
Input Power
EER
Power Factor
Indoor Noise (H / L)
Outdoor Noise (H / L)
220
230
kW
5.22
5.22
7.03
7.03
BTU/h
17800
17800
24000
24000
kJ/h
18800
18800
25310
25310
8.7
8.3
13.1
12.8
1870
1880
2790
2820
W/W
2.79
2.78
2.52
2.49
kJ/hW
10.1
10.0
9100
9000
98
98
97
96
dB-A
43 / 39
43 / 39
47 / 42
Power Level dB
dB-A
47 / 42
54 / -
55 / -
Power Level dB
60 / -
61 / -
9.6 / 2160
14.3 / 2870
38.0
63.0
Type
Motor Type
Induction (2 poles)
Induction (2 poles)
1200
1800
Output Power
Indoor Fan
230
Compressor
Type
Cross-Flow Fan
Cross-Flow Fan
Material
ASG20K1
ASG20K1
Motor Type
DC Motor (4 poles)
DC Motor (8 poles)
Input Power
Output Power
40
40
Lo
rpm
1060
1150
Me
rpm
1150
1240
Hi
rpm
1240
1390
SHi
rpm
Type
Propeller Fan
Propeller Fan
Material
PP Resin
PP Resin
Speed
Outdoor Fan
220
94.8
Motor Type
94.8
Induction (6 poles)
Input Power
Output Power
35
rpm
Speed
Lo
Hi
Indoor Airflow
Me
Hi
Outdoor
Airflow
Hi
76.2
rpm
Moisture Removal
Lo
Dimension
94.8
Induction (6 poles)
86.5
148.4
158.6
72
490
820
835
L/h (Pt/h)
510
850
870
2.9 (6.1)
4.0 (8.5)
13.8 (489)
15.5 (546)
15.0 (531)
16.7 (589)
16.2 (572)
18.7 (660)
Control Device
Refrigeration
Cycle
94.8
30.4 (1073)
30.8 (1090)
51.0 (1800)
52.5 (1850)
Capillary Tube
Capillary Tube
Refrigerant Oil
cm
Refrigerant Type
g (oz)
Height(I/D / O/D)
mm (inch)
mm (inch)
mm (inch)
Piping
Weight
kg (lb)
12 (26) / 56 (123)
mm (inch)
Standard length
m (ft)
5.0 (16.4)
5.0 (16.4)
m (ft)
3 (9.8) ~ 25 (82.0)
3 (9.8) ~ 25 (82.0)
m (ft)
20 (65.6)
20 (65.6)
g/m (oz/ft)
20 (0.2)
30 (0.3)
m (ft)
7.5 (24.6)
7.5 (24.6)
Inner Diameter
mm
14
14
Length
mm
550
550
Fin Material
Fin Type
Slit Fin
Slit Fin
2 x 15 x 21
2 x 15 x 21
Slit Fin
Slit Fin
2 x 24 x 17
1 x 34 x 17
Material
Polypropelene
Polypropelene
Type
One-touch
One-touch
Indoor
Indoor
16
20
Drain Hose
Indoor Heat
Exchanger Row x Stage x FPI
Size (W x H x L)
mm
Fin Material
Outdoor
Fin Type
Heat
Exchanger Row x Stage x FPI
Size (W x H x L)
Air Filter
mm
Power Supply
Power Supply Cord
Thermostat
Protection Device
DRY BULB
WET BULB
DRY BULB
WET BULB
Maximum
32
23
32
23
Minimum
16
11
16
11
Maximum
43
26
43
26
Minimum
16
11
16
11
1.
Cooling capacities are based on indoor temperature of 27C Dry Bulb (80.6F Dry Bulb), 19.0C Wet Bulb (66.2F Wet Bulb) and outdoor air
temperature of 35C Dry Bulb (95F Dry Bulb), 24C Wet Bulb (75.2F Wet Bulb)
2.
Specifications are subjected to change without prior notice for further improvement.
Indoor
CS-PC18KKQ-6 (MEXICO)
CS-PC24KKQ-6 (MEXICO)
Outdoor
CU-PC18KKQ-6 (MEXICO)
CU-PC24KKQ-6 (MEXICO)
NEW JIS
NEW JIS
Phase, Hz
Single, 60
Single, 60
220
220
Model
Capacity
Running Current
Cooling
Input Power
EER
Power Factor
7.03
24000
kJ/h
18800
25310
8.7
13.1
1870
2790
W/W
2.79
2.52
kJ/hW
10.1
9.1
98
97
dB-A
43 / 39
47 / 42
dB-A
54 / -
60 / -
Power Level dB
9.6 / 2160
14.3 / 2870
38.0
63.0
Type
Motor Type
Induction (2 poles)
Induction (2 poles)
1200
1800
Outdoor Noise (H / L)
Compressor
Output Power
Indoor Fan
5.22
17800
Power Level dB
Indoor Noise (H / L)
Type
Cross-Flow Fan
Cross-Flow Fan
Material
ASG20K1
ASG20K1
Motor Type
DC Motor (4 poles)
DC Motor (8 poles)
Input Power
94.8
94.8
Output Power
40
40
Lo
rpm
1060
1150
Me
rpm
1150
1240
Hi
rpm
1240
1390
SHi
rpm
Type
Propeller Fan
Propeller Fan
Material
PP Resin
PP Resin
Speed
Outdoor Fan
kW
BTU/h
Induction (6 poles)
Induction (6 poles)
Input Power
Motor Type
W
76.2
134.1
Output Power
35
72
Lo
rpm
Hi
rpm
820
800
Speed
Moisture Removal
Indoor Airflow
L/h (Pt/h)
4.0 (8.5)
13.8 (489)
15.5 (546)
15.0 (531)
16.7 (589)
16.2 (572)
18.7 (660)
30.8 (1090)
52.5 (1850)
Capillary Tube
Capillary Tube
Me
Hi
SHi
Outdoor
Airflow
2.9 (6.1)
Lo
Hi
Control Device
Refrigeration
Cycle
Refrigerant Oil
cm
Refrigerant Type
g (oz)
Height(I/D / O/D)
mm (inch)
mm (inch)
mm (inch)
kg (lb)
mm (inch)
Standard length
m (ft)
5.0 (16.4)
5.0 (16.4)
m (ft)
3 (9.8) ~ 25 (82.0)
3 (9.8) ~ 25 (82.0)
m (ft)
20 (65.6)
20 (65.6)
g/m (oz/ft)
20 (0.2)
30 (0.3)
m (ft)
7.5 (24.6)
7.5 (24.6)
Inner Diameter
mm
14
14
Length
mm
550
550
Dimension
Piping
Weight
Drain Hose
Fin Material
Fin Type
Indoor Heat
Exchanger Row x Stage x FPI
Slit Fin
Slit Fin
2 x 15 x 21
2 x 15 x 21
Slit Fin
Slit Fin
2 x 24 x 17
2 x 34 x 17
Material
Polypropelene
Polypropelene
Type
One-touch
One-touch
Indoor
Indoor
16
20
Size (W x H x L)
mm
Fin Material
Outdoor
Fin Type
Heat
Exchanger Row x Stage x FPI
Size (W x H x L)
Air Filter
mm
Power Supply
Power Supply Cord
Thermostat
Protection Device
DRY BULB
WET BULB
DRY BULB
WET BULB
Maximum
32
23
32
23
Minimum
16
11
16
11
Maximum
43
26
43
26
Minimum
16
11
16
11
1.
Cooling capacities are based on indoor temperature of 27C Dry Bulb (80.6F Dry Bulb), 19.0C Wet Bulb (66.2F Wet Bulb) and outdoor air
temperature of 35C Dry Bulb (95F Dry Bulb), 24C Wet Bulb (75.2F Wet Bulb)
2.
Specifications are subjected to change without prior notice for further improvement.
10
3.
Features
Quality Improvement
o Random auto restart after power failure for safety restart operation
o Gas leakage protection
o Prevent compressor reverse cycle
o Overload protector to protect compressor
o Noise prevention during soft dry operation
o Blue coated condenser for high resistance to corrosion
Operation Improvement
o 24-hour timer setting
11
Indoor Unit
4.2
Outdoor Unit
4.3
Remote Control
12
5. Dimensions
5.1
5.1.1
Indoor Unit
CS-PC9KKQ CS-PC12KKQ
13
5.1.2
14
5.2
Outdoor Unit
5.2.1
CU-PC9KKQ
5.2.2
15
5.2.3
CU-PC24KKQ CU-PC24KKQ-6
16
OUTDOOR
LIQUID
SIDE
CAPILLARY
TUBE
STRAINER
2-WAY
VALVE
INTAKE
AIR
TEMP
SENSOR
PIPE
TEMP
SENSOR
HEAT EXCHANGER
(CONDENSER)
HEAT EXCHANGER
(EVAPORATOR)
GAS
SIDE
3-WAY
VALVE
COMPRESSOR
17
7. Block Diagram
7.1
18
CS-PC9KKQ CU-PC9KKQ
19
8.2
CS-PC12KKQ CU-PC12KKQ
20
8.3
21
8.4
22
23
9.2
24
25
10.1.2
10.1.2.1
CS-PC9KKQ CS-PC12KKQ
10.1.2.2
26
10.1.3
27
11.1.3
11.1.2
Indoor Unit
Outdoor Unit
28
The mounting wall is strong and solid enough to prevent if from the vibration.
The centre of installation plate should be at more than at right and left of the wall.
The distance from installation plate edge to ceiling should more than .
From installation plate left edge to units left side is .
From installation plate right edge to units right side is .
B
: For left side piping, piping connection for liquid should be about
: For left side piping, piping connection for gas should be about
1
11.2.2
Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
Drill the piping plate hole with 70mm hole-core drill.
o Putting measuring tape at position as shown in the diagram above.
The hole centre is obtained by measuring the distance namely 128 mm for left and right hole
respectively. Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
o Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side. (refer to step 3)
1
2
3
29
11.2.3
11.2.3.1
11.2.3.2
For the right and right bottom
piping
11.2.3.3
11.2.4
1.
2.
Secure the connecting cable onto the control board with the holder.
This equipment must be properly earthed.
31
Secure the connecting cable onto the control board with the holder.
This equipment must be properly earthed.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoors respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than the other AC wires for safety reason.
11.2.5
11.2.5.1
1
2
3
Please cut using pipe cutter and then remove the burrs.
Remove the burrs by using reamer. If burrs are not removed, gas leakage may be caused. Turn the piping
end down to avoid the metal powder entering the pipe.
Please make flare after inserting the flare nut onto the copper pipes.
32
After selecting the best location, start installation according to indoor/outdoor unit installation diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (10mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
B
Model
PC9 ***
PC12***,
PC18***
PC24***,
PC28***, KC28***
A
474 mm
570 mm
612.5 mm
B
C
D
87 mm 18.5 mm 261 mm
105 mm 18.5 mm 320 mm
131 mm
19 mm
383 mm
11.3.2
CAUTION
11.3.2.1
Connecting the piping to
indoor unit
Please make flare after inserting flare nut (locate at
joint portion, of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
Align the center of piping and sufficiently tighten
the flare nut with fingers.
Further tighten the flare nut with torque wrench in
specified torque as stated in the table.
Spanner
or Wrench
11.3.2.2
Connecting the piping to
outdoor unit
Torque
wrench
33
11.3.3
1
2
3
4
5
6
7
8
Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o Be sure to connect the end of the charging hose with the push pin to the service port.
Connect the center hose of the charging set to a vacuum pump.
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
Tighten the service port caps of the 3-way valve at a torque of 18 Nm with a torque wrench.
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to OPEN
using a hexagonal wrench (4 mm).
Mount valve caps onto the 2-way valve and the 3-way valve.
o Be sure to check for gas leakage.
34
11.3.4
The remaining air in the Refrigerant cycle which contains moisture may cause malfunction on the compressor.
1 Remove the caps from the 2-way and 3-way valves.
2 Remove the service-port cap from the 3-way valves.
3 To open the valve, turn the valve stem of 2-way valve counter-clockwise approx. 90 and hold it there for ten
seconds, then close it.
4 Check gas-leakage of the connecting portion of the pipings.
o For the left piping, refer to 4 (A).
11.3.5
5 Secure the power supply cord and connecting cable onto the control board with the holder.
6 Attach the control board cover back to the original position with screw.
7 For wire stripping and connection requirement, refer to instruction of the indoor unit.
This equipment must be properly earthed.
Note: Isolating Devices (Disconnecting means) should have minimum 3.0mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
11.3.6
1
2
Pipe Insulation
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.
36
12.1.1
37
12.1.2
38
12.2.1
39
12.2.2
40
Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with
the setting temperature as shown in table below.
The setting temperature for all the operations can be changed one level up or one level down from the standard
temperature as shown in table below by pressing the temperature up or temperature down button at remote
control.
The operation mode judging temperature and standard setting temperature can be increased by 2C
permanently, by open the circuit of JX03 at indoor units printed circuit board.
41
12.4.1
CS-PC9KKQ
Hi
Me
HLo
CLo
LoSLo
12.4.2
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the
table.
o Fan speed rotates in the range of Hi and Me.
o Deodorizing Control will be activated.
(For PC9/12KKQ)
Cooling
Normal
Soft
Dry
Speed Mode
Normal
SHi
Manual
Hi
Me
Lo
Hi
Me
HLo
CLo
Lo-
SLo
Stop
Auto
Manual
Auto
Mode Judgment
Speed Mode
Normal
Soft
Dry
1030
850
690
650
610
590
CS-PC24KKQ /
CS-PC24KKQ-6
1390
1240
1210
1150
970
750
Normal
SHi
Manual
Auto
Hi
Me
Lo
Hi
Mode Judgment
Me
HLo
CLo
Lo-
SLo
42
Stop
12.4.3
Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
There are 3 types of fan speed settings: Lo, Me, Hi.
12.4.4
Immediate after the fan motor is started, rpm abnormal control is performed every second.
During fan motor on, if fan motor feedback 2550 rpm or < 50 rpm continuously for 10 seconds, the fan motor
error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7,
then air conditioner will stop operation.
43
Auto Control
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.
(For PC9/12KKQ)
Horizontal
Closing
position
/ 135
22
Closing
position
/ 148
28
44
12.6.2
Manual Control
When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and
the airflow direction louver move up and down in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired louver position.
When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
(For PC9/12KKQ)
Horizontal
11
Closing
position
/ 135
16
21
27
33
17
Closing
position
/ 148
22
28
33
39
45
12.8
12.8.1
If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when
the power is resumed.
It will start with previous operation mode and airflow direction.
If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to
operate will be decided randomly using 4 parameters: intake air temperature, setting temperature, fan speed and
air swing louver position.
This random Auto Restart Control is not available when Timer is set.
This control can be omitted by open the circuit of JX02 (refer printed circuit board indoor unit). (For PC18/24KKQ,
PC18/24KKQ-6 only)
12.10
OFF Timer
When the OFF Timer is set by using the remote control, the unit will stop operate according to the desired setting.
Notes:
1 By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2 To cancel the previous timer setting, press CANCEL button.
3 To activate the previous timer setting, press SET button.
4 If main power supply is switched off, the Timer setting will be cancelled.
12.9
ON Timer
When the ON Timer is set using the remote control, the unit will start to operate slightly before the set time, so
that the room will reach nearly to the set temperature by the set time.
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time
to detect the intake air temperature to determine the operation mode. The Power indicator will blink at this time.
12.8.2
Timer Control
Short beep sound will be heard when turn ON the air conditioner or enabling other operations.
Long beep sound will be heard when turn OFF the air conditioner or disabling other operations.
46
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:
o Cooling operation the compressor stops for 3 minutes (minimum) before resume operation.
o Soft Dry operation the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON (A) temperature and compressor OFF temperature (B) during the period.
This phenomenon is to reduce the built up humidity inside a room.
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted.
The reason for the compressor to force operation for minimum 60 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor
will start to operate 1.6 second later.
The reason of the difference is to reduce the starting current flow.
If the temperature of the indoor heat exchanger falls below 2C continuously for 4 minutes or more, the
compressor turns off. The fan speed setting remains the same.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of
refrigerant in liquid form returning to the compressor.
Compressor will restart again when the indoor heat exchanger temperature rises to 10C (Recovery).
Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
47
(For PC9/12KKQ)
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed
will be increased according to the indoor pipe temperature the figure below:
RPM shift
7.0C
+0
+20
+40
5.0C
3.0C
+70
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5C or less for continuously 2 minutes, compressor will stop and restart
automatically.
Time Delay Safety Control is activated before the compressor restart.
Compressor starts for 5 minutes
T 2.5C for 2 minutes
Compressor
OFF
Compressor
restart
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turns OFF with TIMER indicator
blinks.
The 5 Times counter can be reset when either one of the following condition happen:
o Unit is OFF by remote control or AUTO OFF/ON button.
o Indoor intake temperature Indoor piping temperature > 5C for 1 minute or more.
o Operation mode change.
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
TIMER LED blinking will be reset if:
o Indoor intake temperature Indoor piping temperature > 5C for 1 minute or more.
o Power supply reset.
48
Auto OFF/ON
Button Pressed
5 sec
Auto Operation
Auto OFF/ON
Button Pressed
5 sec
Stop
Stop
2 x Beep
- During Various Setting Mode, press any button at remote control to transmit and store the desired
transmission code to the EEPROM.
- After signal is received, the Various Setting Mode is cancelled and return to normal operation.
- If there is no code is transmitted of Auto OFF/ON button is not pressed within 20 seconds, the
Various Setting Mode will be cancelled.
49
To check current remote control transmission code and store the transmission code to EEPROM:
o Press Set button for more than 10 seconds
o Press Timer Set button until a beep sound is heard as confirmation of transmission code change
14.2.2
TIMER
14.2.5
RESET
14.2.4
CLOCK Button
14.2.3
SET Button
TIMER
To change remote control display from Degree Celsius (C) to Degree Fahrenheit (F)
o Press continuously for 10 seconds
50
0.4 ~ 0.6 (4 ~ 6)
12 ~ 16
Normal
More than 8C
(15 minutes after an
operation is started)
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Gas side
pressure
Cooling
Mode
High
Low
Low
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
capillary cube
51
15.1.1
Relationship between the condition of the air conditioner and pressure and
electric current
Condition of the
air conditioner
Cooling Mode
Low Pressure
High Pressure
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
strainer
Short circuit in the indoor unit
Heat radiation deficiency
of the outdoor unit
Inefficient compression
Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
15.1.2
Symptom
Electric current during operation becomes approximately 20% lower than the normal value.
The discharge tube of the compressor becomes abnormally hot (normally 70C to 90C).
The different between high pressure and low pressure becomes almost zero.
Locked compressor
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
The compressor has a humming sound.
52
16.1 CS-PC9/12KKQ
16.1.1
16.1.1.1
16.1.1.2
53
16.1.1.3
54
16.1.1.4
16.1.1.5
55
56
WARNING
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
16.2.1.1
16.2.1.2
57
16.2.1.3
58
16.2.1.4
16.2.1.5
59
60
Soft Dry
61
CS-PC9KKQ CU-PC9KKQ
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 7.5 m
230V
4.30
Current
(A)
4.15
4.00
3.85
3.70
3.55
30
31
32
33
34
35
36
37
38
39
40
41
38
39
40
41
38
39
40
41
38
39
40
41
Gas Side
Piping Pressure (MPa)
0.550
0.540
0.530
0.520
0.510
0.500
30
31
32
33
34
35
36
37
Cooling
Capacity (kW)
2.90
2.80
2.70
2.60
2.50
2.40
30
31
32
33
34
35
36
37
Outlet Air
Temperature (C)
15.6
15.4
15.2
15.0
14.8
14.6
30
31
32
33
34
35
36
37
62
Current
(A)
4.06
4.02
3.98
3.94
3.90
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
7.5
8.0
8.5
7.5
8.0
8.5
7.5
8.0
8.5
Gas Side
Piping Pressure (MPa)
0.560
0.550
0.540
0.530
0.520
0.510
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
Cooling
Capacity (kW)
2.80
2.75
2.70
2.65
2.60
2.55
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
Outlet Air
Temperature (C)
15.4
15.3
15.2
15.1
15.0
14.9
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
63
17.2.2
CS-PC12KKQ CU-PC12KKQ
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 7.5 m
230V
5.90
Current
(A)
5.70
5.50
5.30
5.10
4.90
30
31
32
33
34
35
36
37
38
39
40
41
38
39
40
41
38
39
40
41
38
39
40
41
Gas Side
Piping Pressure (MPa)
0.510
0.500
0.490
0.480
0.470
0.460
30
31
32
33
34
35
36
37
Cooling
Capacity (kW)
4.20
4.00
3.80
3.60
3.40
3.20
30
31
32
33
34
35
36
37
Outlet Air
Temperature (C)
15.0
14.6
14.2
13.8
13.4
13.0
30
31
32
33
34
35
36
37
64
Current
(A)
230V
5.65
5.60
5.55
5.50
5.45
5.40
5.35
5.30
3
10
11
12
13
14
15
11
12
13
14
15
11
12
13
14
15
11
12
13
14
15
Gas Side
Piping Pressure (MPa)
0.530
0.520
0.510
0.500
0.490
0.480
0.470
0.460
3
10
Cooling
Capacity (kW)
3.65
3.60
3.55
3.50
3.45
3.40
3.35
3.30
3
10
Outlet Air
Temperature (C)
14.3
14.2
14.1
14.0
13.9
13.8
13.7
13.6
3
10
65
17.2.3
CS-PC18KKQ CU-PC18KKQ
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 5 m
Current
(A)
220V
230V
9.80
9.50
9.20
8.90
8.60
8.30
8.00
7.70
30
31
32
33
34
35
36
37
38
39
40
41
39
40
41
39
40
41
39
40
41
Gas Side
Piping Pressure (MPa)
0.500
0.490
0.480
0.470
0.460
0.450
30
31
32
33
34
35
36
37
38
Cooling
Capacity (kW)
6.30
6.00
5.70
5.40
5.10
4.80
30
31
32
33
34
35
36
37
38
Outlet Air
Temperature (C)
15.80
15.60
15.40
15.20
15.00
14.80
14.60
14.40
30
31
32
33
34
35
36
37
66
38
Current
(A)
220V
230V
9.05
8.90
8.75
8.60
8.45
8.30
8.15
8.00
7.85
7.70
11
13
15
17
19
21
23
25
21
23
25
21
23
25
21
23
25
Gas Side
Piping Pressure (MPa)
0.490
0.480
0.470
0.460
0.450
0.440
0.430
0.420
11
13
15
17
19
Cooling
Capacity (kW)
5.30
5.20
5.10
5.00
4.90
4.80
4.70
4.60
11
13
15
17
19
Outlet Air
Temperature (C)
16.0
15.8
15.6
15.4
15.2
15.0
14.8
14.6
11
13
15
67
17
19
17.2.4
CS-PC18KKQ-6 CU-PC18KKQ-6
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 5 m
220V
10.50
Current
(A)
10.00
9.50
9.00
8.50
8.00
30
31
32
33
34
35
36
37
38
39
40
41
38
39
40
41
38
39
40
41
38
39
40
41
Gas Side
Piping Pressure (MPa)
0.520
0.510
0.500
0.490
0.480
0.470
30
31
32
33
34
35
36
37
Cooling
Capacity (kW)
5.80
5.60
5.40
5.20
5.00
4.80
30
31
32
33
34
35
36
37
Outlet Air
Temperature (C)
15.8
15.6
15.4
15.2
15.0
14.8
14.6
14.4
30
31
32
33
34
35
36
37
68
Current
(A)
220V
8.80
8.70
8.60
8.50
8.40
8.30
8.20
8.10
8.00
11
13
15
17
19
21
23
25
17
19
21
23
25
17
19
21
23
25
17
19
21
23
25
Gas Side
Piping Pressure (MPa)
0.500
0.490
0.480
0.470
0.460
0.450
0.440
0.430
11
13
15
Cooling
Capacity (kW)
5.30
5.20
5.10
5.00
4.90
4.80
4.70
4.60
11
13
15
Outlet Air
Temperature (C)
16.0
15.8
15.6
15.4
15.2
15.0
14.8
14.6
11
13
15
69
17.2.5
CS-PC24KKQ CU-PC24KKQ
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 5 m
220V
230V
14.50
Current
(A)
14.00
13.50
13.00
12.50
12.00
11.50
30
31
32
33
34
35
36
37
38
39
40
41
40
41
40
41
40
41
Gas Side
Piping Pressure (MPa)
0.410
0.400
0.390
0.380
0.370
0.360
0.350
30
31
32
33
34
35
36
37
38
39
Cooling
Capacity (kW)
7.60
7.40
7.20
(220V and 230V)
7.00
6.80
6.60
6.40
30
31
32
33
34
35
36
37
38
39
Outlet Air
Temperature (C)
13.6
13.4
13.2
13.0
12.8
12.6
12.4
30
31
32
33
34
35
36
37
70
38
39
Current
(A)
220V
230V
13.30
13.10
12.90
12.70
12.50
12.30
12.10
11.90
11
13
15
17
19
21
23
25
23
25
23
25
23
25
Gas Side
Piping Pressure (MPa)
0.390
0.380
0.370
0.360
0.350
0.340
0.330
0.320
11
13
15
17
19
21
Cooling
Capacity (kW)
7.40
7.20
7.00
6.80
6.60
6.40
6.20
6.00
11
13
15
17
19
21
Outlet Air
Temperature (C)
13.8
13.6
13.4
13.2
13.0
12.8
12.6
12.4
11
13
15
71
17
19
21
17.2.6
CS-PC24KKQ-6 CU-PC24KKQ-6
Cooling Characteristic
[Condition] Room temperature: 27C (DBT), 19C (WBT)
Cooling operation: At High fan
Piping length: 5 m
220V
14.50
Current
(A)
14.00
13.50
13.00
12.50
12.00
11.50
30
31
32
33
34
35
36
37
38
39
40
41
38
39
40
41
38
39
40
41
38
39
40
41
Gas Side
Piping Pressure (MPa)
0.410
0.400
0.390
0.380
0.370
0.360
30
31
32
33
34
35
36
37
Cooling
Capacity (kW)
7.60
7.40
7.20
7.00
6.80
6.60
6.40
30
31
32
33
34
35
36
37
Outlet Air
Temperature (C)
13.6
13.4
13.2
13.0
12.8
12.6
12.4
30
31
32
33
34
35
36
37
72
Current
(A)
220V
13.30
13.10
12.90
12.70
12.50
12.30
12.10
11.90
11
13
15
17
19
21
23
25
17
19
21
23
25
17
19
21
23
25
17
19
21
23
25
Gas Side
Piping Pressure (MPa)
0.400
0.390
0.380
0.370
0.360
0.350
0.340
0.330
11
13
15
Cooling
Capacity (kW)
7.40
7.20
7.00
6.80
6.60
6.40
6.20
6.00
11
13
15
Outlet Air
Temperature (C)
13.8
13.6
13.4
13.2
13.0
12.8
12.6
12.4
11
13
15
73
CS-PC9KKQ CS-PC12KKQ
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
74
REF.
NO.
1
CS-PC9KKQ
QTY
CHASSY COMPLETE
FAN MOTOR
CS-PC12KKQ
Philippines
REMARK
CWD50C1653
CWA921420
CWH02C1076
CWH551146
BEARING ASSY
CWH64K007
EVAPORATOR
CWB30C2968
CWB30C2970
CWT251026
CWT251061
CWT251062
HOLDER SENSOR
CWH32143
10
CWD933019
11
CWH102370
12
CWA28C2356
13
CWA73C4175
CWA73C4176
14
CWA745849
15
ELECTRONIC CONTROLLER-RECEIVER
CWA745300
16
CWA20C2875
17
INDICATOR HOLDER
CWD933021
18
SENSOR COMPLETE
CWA50C2401
19
CWE20C3084
20
VERTICAL VANE
11
CWE241287
21
CONNECTING BAR
CWE261152
22
CONNECTING BAR
CWE261153
23
CONNECTING BAR
CWE261154
24
CONNECTING BAR
CWE261155
25
CWA981240
26
HORIZONTAL VANE
CWE24C1268
27
CWH521096
28
CWH131350
29
CWH13C1183
30
CWA75C3623
31
CWE11C4250
32
CWE22C1508
33
GRILLE DOOR
CWE14C1029
34
E-ION FILTER
CWD001279
35
XTT4+16CFJ
36
CWH521194
37
DRAIN HOSE
CWH851174
38
CWH82C1705
39
INSTALLATION PLATE
CWH361097
40
FULCRUM
CWH621102
41
OPERATING INSTRUCTION
CWF567134
42
INSTALLATION INSTRUCTION
CWF613792
43
INSTALLATION INSTRUCTION
CWF613686
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
75
18.1.2
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
76
REF.
NO.
1
CS-PC18KKQ
QTY
CS-PC24KKQ
Philippines
CHASSY COMPLETE
CWD50C1654
FAN MOTOR
L6CBYYYL0037
L6CBYYYL0038
CWH02C1077
CWH551146
BEARING ASSY
CWH64K007
EVAPORATOR
CWB30C2550
CWB30C2773
CWT251026
REMARK
CWT251062
CWT251036
10
HOLDER SENSOR
CWH32143
12
CWD933031
13
CWH102370
14
CWA28C2393
CWA28C2394
15
CWA20C2851
CWA20C2853
16
CWA73C4212
CWA73C4208
17
CWA745303
19
ELECTRONIC CONTROLLER-INDICATOR
CWA745300
24
INDICATOR HOLDER
CWD933021
26
SENSOR COMPLETE
CWA50C2401
33
CWE20C3008
34
VERTICAL VANE
15
CWE241289
35
CONNECTING BAR
CWE261156
36
CONNECTING BAR
CWE261158
37
CONNECTING BAR
CWE261167
38
CONNECTING BAR
CWE261159
39
CONNECTING BAR
CWE261160
40
CWA981241
43
HORIZONTAL VANE
CWE24C1295
44
CWH521096
45
CWH131350
46
CWH13C1183
47
CWA75C3623
48
CWE11C4261
49
CWE22C1512
50
GRILLE DOOR
CWE14C1029
51
E-ION FILTER
CWD001283
52
XTT4+16CFJ
53
CWH521194
54
DRAIN HOSE
CWH851174
55
CWH82C1705
56
INSTALLATION PLATE
CWH361098
57
FULCRUM
CWH621103
60
OPERATING INSTRUCTION
CWF567134
61
INSTALLATION INSTRUCTION
CWF613792
62
INSTALLATION INSTRUCTION
CWF613686
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
77
REF.
NO.
1
CS-PC18KKQ-6
QTY
CS-PC24KKQ-6
Mexico
CHASSY COMPLETE
CWD50C1654
FAN MOTOR
L6CBYYYL0037
L6CBYYYL0039
CWH02C1077
CWH551146
BEARING ASSY
CWH64K007
EVAPORATOR
CWB30C2550
CWB30C2773
CWT251026
REMARK
CWT251062
CWT251036
10
HOLDER SENSOR
CWH32143
12
CWD933031
13
CWH102370
14
CWA28C2356
15
CWA20C2851
CWA20C2853
16
CWA73C4212
CWA73C4208
17
CWA745303
19
ELECTRONIC CONTROLLER-INDICATOR
CWA745300
24
INDICATOR HOLDER
CWD933021
26
SENSOR COMPLETE
CWA50C2401
33
CWE20C3008
34
VERTICAL VANE
15
CWE241289
35
CONNECTING BAR
CWE261156
36
CONNECTING BAR
CWE261158
37
CONNECTING BAR
CWE261167
38
CONNECTING BAR
CWE261159
39
CONNECTING BAR
CWE261160
40
CWA981241
43
HORIZONTAL VANE
CWE24C1295
44
CWH521096
45
CWH131350
46
CWH13C1183
47
CWA75C3623
48
CWE11C4720
49
CWE22C1512
50
GRILLE DOOR
CWE14C1029
51
AIR FILTER
CWD001283
52
XTT4+16CFJ
53
CWH521194
54
DRAIN HOSE
CWH851174
55
CWH82C1705
56
INSTALLATION PLATE
CWH361098
57
FULCRUM
CWH621103
60
OPERATING INSTRUCTION
CWF567134
61
INSTALLATION INSTRUCTION
CWF613792
62
INSTALLATION INSTRUCTION
CWF613686
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
78
CU-PC9KKQ
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
79
REF.
NO.
CU-PC9KKQ
QTY
Philippines
REMARK
CHASSY ASSY
CWD50K2107
CWG302403
CWD541075
CWH551217
FAN MOTOR
CWA951562
CWH55406J
CWH03K1020
CWH56053J
2R13C236BSC
10
CWH50077
11
CWH56000J
12
CONDENSER
CWB32C2798
13
CWB15K1271
14
STRAINER
CWB11025
15
HOLDER COUPLING
CWH351047
16
CWB021217
17
CWB011257
18
CWA67C5701
19
HOLDER - O.L.P.
CWH7041200
20
TERMINAL COVER
CWH171011
21
CWH7080300J
22
CWH151074
23
CWA28K1064J
24
CAPACITOR - COM.
DS371156CPNA
25
HOLDER CAPACITOR
CWH301038
26
CAPACITOR - F.M
DS441205NPQA
27
CWE041205A
28
CWE04C1079
29
CWE06K1048
30
CWE031041A
31
CWH13C1099
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
80
18.2.2
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
81
REF.
NO.
QTY
CU-PC12KKQ
CU-PC18KKQ
Philippines
CU-PC18KKQ-6
Mexico
REMARK
CHASSY ASSY
CWD50K2071
CWD50K2088
CWG302409
CWG302256
CWD541030
CWH551217
FAN MOTOR
CWA951329J
CWH55406J
CWH03K1006
CWH56053J
2P19S236A1L
2KS252F5AB04
10
CWH50077
CWH50055
11
CWH56000J
CWH561049
12
CONDENSER
CWB32C2797
CWB32C2794
13
CWB15K1273
CWB15K1103
14
STRAINER
CWB11025
CWB11004
15
HOLDER COUPLING
CWH351023
CWH351046
16
CWB021362
CWB021242
17
CWB011482
CWB011233
18
CWA67C7548
CWA67C7977
19
HOLDER - O.L.P.
CW7041200
20
TERMINAL COVER
CWH171011
21
CWH7080300J
22
CWH151023
23
CWA28K1064J
24
CAPACITOR - COM.
CWA312076
CWA312078
25
HOLDER CAPACITOR
CWH30057
CWH30060
26
CAPACITOR - F.M
DS441205NPQA
27
CWE041031A
28
CWE04C1100
CWE04C1121
29
CWE06K1034
30
CWE031014A
31
CWH13C1064
34
HANDLE
CWE161010
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
82
18.2.3
CU-PC24KKQ CU-PC24KKQ-6
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
83
REF.
NO.
1
QTY
CU-PC24KKQ
CU-PC24KKQ-6
Philippines
Mexico
CHASSY ASSY
CWD50K2100
CWD541065
CWH551217
FAN MOTOR
CWA951399J
CWH55252J
CWH03K1017
CWH561038J
REMARK
COMPRESSOR
2J39S236A1A
10
PACKING
CWB81043
11
CWH50055
12
CWH561049
13
CONDENSER
CWB32C2692
14
CWB15K1282
15
STRAINER
CWB11025
16
HOLDER COUPLING
CWH351036
17
CWB021175
18
CWB011484
21
TERMINAL COVER
CWH171012
22
CWH7080300J
23
CWH151051
24
CWA28K1064J
26
CAPACITOR - COM.
CWA312088
27
HOLDER CAPACITOR
CWH30071
28
CAPACITOR - F.M
DS441355NPQA
29
CWE041254A
30
CWE04C1101
31
CWE06K1043
32
CWE03K1009A
33
CWH131168
35
HANDLE
CWE161010
36
CWH131169A
37
HANDLE
CWE16000E
38
THERMOSTAT
CWA151061
43
CWG302407
(Note)
All parts are supplied from PHAAM, Malaysia (Vendor Code: 00029488).
O marked parts are recommended to be kept in stock.
Printed in Malaysia
SSTK0912-00
84