Emax or Tmax ?
Choice criteria
Choice criteria
Choice criteria
Ratings
Choice criteria
Ratings
Choice criteria
Choice criteria
Choice criteria
Choice criteria
Choice criteria
Ratings
Ultimate Short Circuit breaking capacity (Icu):
breaking capacity for which the prescribed conditions
according to a specified test sequence do not include the
capability of the C.B. to carry its rated current continuously
Choice criteria
Choice criteria
Choice criteria
Ratings
Service Short Circuit breaking capacity (Ics):
breaking capacity for which the prescribed conditions
according to a specified test sequence include the capability
of the C.B. to carry its rated current continuously
Choice criteria
main circuit breakers or circuit breakers for which a
long out-of-service period cannot be accepted (for
example naval installation)
Ics
CB selection
based on
Icu
IIcu
vs
I
vs
Icscs
cu
I fault 30 I n
<2%
I fault 0.5I k
< 1%
I fault 0.75 I k
10%
35%
I fault 10 I n
60%
I fault 5 I n
100% I fault I n
Choice criteria
Choice criteria
Choice criteria
Ratings
Rated short-time withstand current of a circuit-breaker (Icw):
is the value of short-time withstand current assigned to that
circuit-breaker by the manufacturer under specified test
conditions.
Iu>2500A
30 kA
IEC 60947-2 table 3
Choice criteria
IEC 60947-2 table 4
Category B
Circuit-breakers specifically for selectivity in short circuit
conditions in relation to other protection devices in load-side
series, i.e. with an intentional delay (adjustable) applicable in
short circuit conditions. These circuit-breakers do have a
specified rated short-time current.
Choice criteria
Example of use of category B circuit breakers
in electrical plant
IIcw
cw
Trafo 630kVA
Ucc%=4%
ACB E1B12
400V
22.7kA
MCCB S4
MCCB S3
Choice criteria
Choice criteria
Icm =
Choice criteria
Ratings
Rated Short Circuit making capacity (Icm):
making capacity for which the prescribed conditions according
to a specified test sequence include the capability of the C.B. to
make the current corresponding to that rated capacity at the
appropriate applied voltage
Choice criteria
IIcm
cm
Since the very limit of circuit breakers is the dynamics weve to look for a circuit
breaker whose making capacity is higher than 31.9 kA.