TECHNICAL SPECIFICATION OF 415V, ACDB/MCC

415V, AC MCC comply with all IS and IEC standard applicable.


Name plate details as : AC Distribution panel for 200KVA DG SET
3-5360-ACDB-6001,3-5360-ACDB-6002
4-5360-ACDB-6001,4-5360-ACDB-6002
1.

2.
3.
4.

Suitable for following system particulars


Voltage
3 phase 415V phase to Phase and 230 V phase to neutral, 50Hz.
System short circuit level
10KA
System earthing
Effectively grounded
Design ambient temperature
45C
Bus Bar rating
400A
In coming MCCB of 400 Amp with ON/OFF indication.
Incoming MCCB
Bus Bar arrangement
Suitable for 3 phases with full capacity neutral, separate Neutral
& Earthing bus bars.

R, Y, B colored heat shrinkable insulating sleeves


Bus bar joints with shrouds.
Main bus bars shall be located in separate independent air
insulated enclosure and segregated from all other compartments
of the cubicle.
Direct access or accidental contact bus bars and primary
connections shall not be possible.
5. Material of Bus bar
Aluminum
6. Maximum temperature of the Temperature rise over the reference ambient of 45C ove 45C
bus bars, droppers and contacts ambient temperature.
at continuous current ratings
under
designed.
ambient
temperature
7. Maximum ambient temperature 65 C
inside each module under
designed ambient temperature
8. Spacing between phase to Clearances as per IS and minimum as below
Phase to ground and phase to Phase to Phase 25 mm
neutral
Phase to Earth 19 mm
Minimum creep age distance 25 mm
9. Earthing points
Two Nos. Earthing terminal for connecting earthing flat of size
50X6 mm GI shall be provided along with continuous GI/Cu bus
bar of size equivalent to 120sqmm.
10. Constructional details
The panel shall be indoor dust , vermin , weather proof, metal
clad, air insulated, Floor mounted, and modular construction draw
out type cells with front & rear compartment of following rated Cells.

11. Mounting
12. Cable entry

Shrouds shall be provided for live parts connections.


Floor mounting and complete with mounting arrangement and
hardware.
Incoming and outgoing cable entry shall be provided from TOP
with Suitable gland plates,
a) Incomer-3.5Cx240 sqmm ,XLPE, Cu conductor, armored
cable(01 No per Panel)
b) Outgoing feeders -3.5Cx50 sqmm, XLPE, Cu conductor(6 nos
per Pane)

13. Locking arrangement

All doors locks are of panel key operated also Pad locking facility
is required for power switches in ON and OFF position with
provision of door interlock defeat.

14.
The MCC panel shall be provided with the following

15.
16.

17.
18.
19.

Incomer MCCB - 1 number/set

400 Amps, 415 V, 4P, 10 KA in accordance with IS60497,category-A duty.

L&T make Switch fuse unit of 125


Amp. (MCC cell)
04 No
L&T make Switch fuse unit of 63 Amp.
(MCC cell)
02 No
Digital Voltmeter /Ammeter/frequency
with inbuilt Selector Switch - 1 No/set

415V A.C with Neutral, 125 A, with 125A HRC fuse, ISI
marked
415V A.C with Neutral, 63 A, with 63A HRC fuse, ISI
marked

Dual Parameter Meter for V, A & Hz.


Range- 0 to 500V, 0 to 300 Amps, 45 to 55Hz, I/P-5A,
230V AC, 96x96mm, accuracy class-0.5, 3.5 digits or
more, self powered high quality meters comply with IS
13875 requirements
Digital PF/ KW/VAR meter with Dual Parameter Meter, 96x96mm, 4 digit or more, polarity
inbuilt selector switch 1 no/set
indication(lagging/leading), System-3P 4W with suitable
CT and PT ratio with Range of 0-250KVA, 0 to 1(lagging
leading), 0-200KW and self powered as per high quality
meters comply with IS 13875 requirements
accuracy=
Active Power (KW) (0.5% of FS)
Apparent Power (KVA) (0.5% of FS)
Reactive Power (KVAr) (1.0% of FS)
Power Factor 1deg Electrical.
CT - 3 Nos./set
500 /5 Amps for metering purpose.
Indications with Control Fuse -3 LED type, 230V AC, RYB for incomer supply
nos./set
Control Fuse - 2 Nos./set
2A HRC with 2A Link for supply to voltmeters and space
heaters
Wires for control and power circuit
1.1kv Insulated Flexible Copper wires of suitable rating
with factor of safety of 2(min.).
Space heater with thermostat control, Suitable rating/capacity
CFL Interior Lighting, Receptacle and
door limit switches
Type of Enclosure
IP 55 or higher
Name Plates and Labeling
AC Distribution panel for 200KVA DG SET
3-5360-ACDB-6001,3-5360-ACDB-6002
4-5360-ACDB-6001,4-5360-ACDB-6002
Sealing and gasket
Perimeter of all doors and removable covers shall be
gasketted all around with neoprene gaskets
. Interior /Exterior Paint Shade
Interior : Semi-glossy white/ RAL 7032
Exterior: Aircraft grey Shade 631of IS:5/RAL 7032
Sheet Material Thickness
2 mm thickness cold rolled sheet steel for load bearing
members and 1.6 mm for non load bearing members.

20. Compliance

Seismic Test Compliance certificate shall be issued.


Manufacturers test certificates for the CTs/Meters shall be
provided.

General Arrangement
4-5360-ACDB-6002

4-5360-ACDB-6003

3-5360-ACDB-6002

3-5360-ACDB-6003