Professional Documents
Culture Documents
With such an arrangement, the phase displacement between the currents gets compensated
with the oppositely connected C.T. secondaries. Hence currents fed to the pilot wires from both
the sides are in phase under normal running conditions and the relay is ensured to be inoperative.
3. The neutrals of C.T. star and power transformer stars are grounded.
4. Many transformers have tap changing arrangement due to which there is a possibility of flow of
differential current. For this, the turns ratio of C.T.s on both sides of the power transformer are
provided with tap for of C.T.s on both sides of the power transformer are provided with tap for their
adjustment.
For the sake of understanding, the connection of C.T. secondaries in delta for star side of
power transformer and the connection of C.T. secondaries in star for delta side of power
transformer is shown in the Fig.1(a) and (b).
Fig 1
The restraining coils are connected across the C.T. secondary windings while the operating
coils are connected between the tapping points on the restraining coils and the star point of C.T.
secondaries.
With the proper selection of turns ratio of C.T.s the coils are under balanced condition during
normal operating conditions. The C.T. secondaries carry equal currents which are in phase under
normal conditions. So no current flows through the relay and the relay is inoperative.
With an internal fault in power transformer windings, the balance in the C.T.s get disturbed.
The operating coils of differential relay carry currents proportional to the difference of current
between the two sides of a power transformer. This causes the relay operation which trips the
main circuit breakers on both the sides of the power transformer.
The basic requirements of the differential relay are,
1. The differential relay must not operate on load or external faults.
2. It must operate on sever internal faults.
The relay satisfying these requirements is used in Merz-Price protection.
It is important to note that this scheme gives protection against short circuit faults between
the turns i.e. interturn faults also. This is because when there is an interturn fault, the turns ratio
of power transformer gets affected. Due to this the currents on both sides of the power
transformer become unbalanced. This causes an enough differential current which floes through
the relay and the relay operates.
Example : A three phase power transformer having a line voltage ratio of 400 V to 33 kV is
connected in star-delta. the C.T.s on 400 V side have current ratio as 1000/5. What must be the
C.T. ratio on 33 kV side.
Assume current on 400 V side of transformer to be 1000 A.
Fig. 4