You are on page 1of 82

MV-90 5 - 35 kV Single Conductors

Description
Copper or aluminum stranded, thermo set insulated.

Contruction
Conductor
Copper or aluminum stranded, thermo set insulated.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield, 2.5 mils
(0.0635mm) thickness.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE).
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable
type jacket.
Moisture barrier against longitudinally migration.
Armor for Direct Burial

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C optional).
Overload 130C.
Short circuit 250C.
7

Rated Voltage
5, 8, 15, 25 and 35 kV.
Insulation Level
100% (133% and 173% optional).

Applications
Distribution of electric energy at Medium Voltage, installed at air,
underground ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 5-35 kV single conductors are manufactured in accordance
with the following standards:
ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay
stranded Copper Conductors.
ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay
stranded Aluminum 1350 Conductors.
UL 1072. Medium Voltage Power Cables MV90.
ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000
To 46000 Volts.
AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables
Rated 5 through 46 kV.

Certifications
CENTELSAs 5-35 kV single conductors are certified by:
UL 1072. File E167359.
ICONTEC (Colombia). NTC 2186 standard
CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE.
CIDET (Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE.
CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR.
CIDET (Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR.

Note: Configurations and sizes herein not specified are available upon request.

MV-90 5 kV Single Conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
22.44
23.48
24.39
26.57
28.98
32.84

1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

13.20
14.88
16.00
17.40
18.18
19.12
20.14
22.35
23.68
25.06
26.33
27.50
28.59
29.63
30.54
33.30
35.71
39.57

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

245
333
428
571
665
785
933
1169
1401
1615
1875
2133
2389
2644
2896
3452
4203
5452

192
249
294
359
398
448
508
632
725
816
916
1014
1111
1206
1298
1534
1806
2255

2.10
1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

3.43
2.16
1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.4010
0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

15795
13740
11824
10081
9319
8544
7838
7150
6512
5961
5531
5187
4902
4659
4465
4060
3691
3221

MV-90 5 kV Single Conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

134
169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690
744
794
841
883
924
960
1046
1141
1293

45
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80

520
586
630
685
716
753
793
880
932
987
1037
1083
1126
1167
1202
1311
1406
1558

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

164
224
287
384
447
528
627
786
942
1085
1260
1434
1606
1777
1946
2320
2825
3664

129
167
198
241
267
301
341
425
487
548
616
682
746
810
872
1031
1214
1515

0.641
0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

1.05
0.658
0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.6454
0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10

9815
8538
7347
6264
5791
5309
4870
4443
4046
3704
3437
3223
3046
2895
2774
2523
2293
2002

MV-90 8 kV Single Conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

CROSS
SECTION
(mm2)

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION
THICKNESS
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

INSULATION
JACKET
DIAMETER THICKNESS
(mm)
(mm)

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65
23.74
24.78
25.69
27.87
30.28
34.14

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

OVERALL
DIAMETER
(mm)

16.18
17.30
18.70
19.48
20.42
22.46
23.65
24.98
26.36
27.63
28.80
29.89
30.93
32.42
34.60
37.01
40.87

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

368
465
611
707
829
1030
1220
1455
1671
1934
2194
2452
2709
2999
3524
4280
5535

285
332
399
440
492
605
683
778
872
975
1075
1173
1270
1400
1606
1882
2338

1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

2.16
1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16338
14169
12171
11291
10388
9562
8752
7997
7341
6827
6414
6071
5778
5543
5052
4601
4027

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Single Conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115

INSULATION
JACKET
DIAMETER THICKNESS
(mm)
(mm)

435
479
534
565
602
642
689
741
796
846
892
935
976
1011
1097
1192
1344

60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80

OVERALL
DIAMETER
(mm)

637
681
736
767
804
884
931
984
1038
1088
1134
1177
1218
1276
1362
1457
1609

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

248
313
411
475
557
692
820
978
1123
1300
1474
1648
1820
2015
2368
2876
3720

191
223
268
295
330
406
459
523
586
655
722
788
854
941
1079
1265
1572

0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.658
0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

11

10152
8804
7563
7016
6455
5942
5438
4969
4562
4242
3985
3773
3590
3444
3139
2859
2502

MV-90 15 kV Single Conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
28.75
30.93
33.34
37.20

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79

22.78
23.56
24.50
25.52
26.71
28.04
29.42
30.69
32.44
33.53
34.57
35.48
37.66
40.07
45.50

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

768
869
997
1154
1349
1590
1813
2081
2383
2647
2909
3168
3703
4469
5900

556
601
660
729
813
914
1013
1122
1264
1368
1471
1569
1785
2071
2704

0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16393
15303
14175
13131
12097
11123
10268
9592
9044
8588
8195
7879
7214
6600
5809

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Single Conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
1055
1096
1132
1218
1313
1465

80
80
80
80
80
80
80
80
80
80
80
80
80
80
110

897
928
965
1005
1052
1104
1158
1208
1277
1320
1361
1397
1483
1578
1791

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

516
584
670
776
907
1069
1218
1398
1601
1779
1955
2129
2488
3003
3965

373
404
443
490
546
614
681
754
849
919
988
1055
1199
1392
1817

0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

12

10186
9509
8808
8160
7517
6912
6381
5960
5620
5337
5092
4896
4483
4101
3610

MV-90 25 kV Single Conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97
31.06
32.10
33.01
35.19
37.60
41.46

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

27.82
28.76
29.78
30.97
32.88
34.26
35.53
36.70
37.79
38.83
39.74
43.49
45.90
50.62

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1052
1186
1350
1552
1838
2071
2348
2622
2892
3161
3425
4125
4915
6309

785
849
924
1016
1162
1271
1389
1503
1614
1723
1827
2207
2518
3112

0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

19847
18509
17258
16006
14814
13758
12915
12227
11651
11150
10747
9893
9096
8060

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Single Conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

260
260
260
260
260
260
260
260
260
260
260
260
260
260

INSULATION
JACKET
DIAMETER THICKNESS
(mm)
(mm)

853
890
930
977
1030
1084
1134
1180
1223
1264
1300
1385
1480
1632

80
80
80
80
80
80
80
80
80
80
80
110
110
110

OVERALL
DIAMETER
(mm)

1095
1132
1173
1219
1295
1349
1399
1445
1488
1529
1565
1712
1807
1993

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

707
797
907
1043
1235
1391
1578
1762
1944
2125
2302
2772
3303
4240

527
571
621
683
781
854
933
1010
1085
1158
1228
1483
1692
2091

0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

13

12333
11501
10724
9946
9205
8549
8025
7598
7240
6929
6678
6147
5652
5008

MV-90 35 kV Single conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682

Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51
31.89
33.16
34.33
35.42
36.46
37.37
39.55
41.96
45.82

JACKET
THICKNESS
(mm)

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

OVERALL
DIAMETER
(mm)

33.70
34.72
35.91
37.24
38.62
39.89
41.06
42.15
43.19
44.10
48.71
51.12
54.98

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1445
1616
1827
2086
2327
2612
2893
3171
3447
3716
4526
5335
6675

1108
1190
1291
1410
1528
1653
1775
1892
2008
2118
2608
2937
3479

0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

22170
20773
19366
18016
16810
15841
15047
14378
13794
13323
12318
11374
10136

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Single conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

345
345
345
345
345
345
345
345
345
345
345
345
345

INSULATION
JACKET
DIAMETER THICKNESS
(mm)
(mm)

1062
1102
1149
1201
1256
1306
1352
1394
1435
1471
1557
1652
1804

80
80
80
80
80
80
80
80
80
80
110
110
110

OVERALL
DIAMETER
(mm)

1327
1367
1414
1466
1521
1571
1617
1660
1700
1736
1918
2013
2164

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

971
1086
1228
1402
1564
1756
1945
2131
2316
2498
3042
3585
4486

744
800
867
947
1027
1111
1193
1272
1350
1423
1753
1974
2338

0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

14

13776
12908
12034
11195
10446
9844
9350
8934
8572
8279
7654
7068
6298

46 - 69 kV Single Conductors

Description
Copper or aluminum stranded, thermo set insulated

Construction
Conductor
Soft Copper or 1350-H19 aluminum, compact stranded.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor.
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield, 2.5 mils
(0.0635mm) thickness.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE).
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable
type jacket.
Moisture barrier against longitudinally migration.
Armor for Direct Burial.

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C optional)
Overload 130C
Short circuit 250C
15

Rated Voltage
45 and 69 kV
Insulation Level
100% (133% and 173% optional only for 46 kV)

Applications
Distribution of electric energy at 46 and 69 kV, installed at air,
underground ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 46-69 kV single conductors are manufactured in
accordance with the following standards:
ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay
stranded Copper Conductors.
ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay
stranded Aluminum 1350 Conductors.
AEIC CS6. Specification for Ethylene Propylene Rubber Insulated
Shielded Power Cables Rated 5 through 69 kV.
AEIC CS7. Specification for Cross Linked Polyethylene Insulated
Shielded Power Cables Rated 69 through 138 kV.

Certifications
CENTELSAs 46 kV conductors are certified by CTL Laboratories.

Note: Configurations and sizes herein not specified are available


upon request.

16

46 kV Single conductors, 90C


(International Unit System) 100% Insulation Level
Standards: AEIC CS8 Specification for Extruded Dielectric,
Shielded Power Cables Rated 5 through 46 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

4/0
250
300
350
400
450
500
600
750
1000

12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

11.30
11.30
11.30
11.30
11.30
11.30
11.30
11.30
11.30
11.30

35.63
37.01
38.28
39.45
40.54
41.58
42.49
44.67
47.08
50.94

JACKET
THICKNESS
(mm)

2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79

OVERALL
DIAMETER
(mm)

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

2565
2821
3199
3495
3786
4075
4356
4945
5772
7141

1889
2022
2240
2376
2508
2636
2758
3027
3374
3944

0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

43.93
45.31
47.44
48.61
49.70
50.74
51.65
53.83
56.24
60.10

0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

21236
19901
18822
17932
17180
16522
15988
14845
13764
12335

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

46 kV Single conductors, 90C


100% Insulation Level
Standards: AEIC CS8 Specification for Extruded Dielectric,
Shielded Power Cables Rated 5 through 46 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

4/0
250
300
350
400
450
500
600
750
1000

475
520
570
616
659
700
736
813
908
1060

0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

445
445
445
445
445
445
445
445
445
445

1403
1457
1507
1553
1596
1637
1673
1759
1854
2006

JACKET
THICKNESS
(mm)

110
110
110
110
110
110
110
110
110
110

OVERALL
DIAMETER
(mm)

1729
1784
1868
1914
1957
1998
2033
2119
2214
2366

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1724
1896
2150
2349
2544
2738
2927
3323
3879
4799

1269
1359
1505
1597
1685
1772
1853
2034
2268
2651

0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

17

13196
12366
11696
11143
10676
10267
9935
9225
8553
7665

69 kV Single conductors, 90C


(International Unit System) 100% Insulation Level
Standards: AEIC CS7 Specification for Cross Linked Polyethylene
Insulated Shielded Power Cables Rated 69
through 138 kV, NTC 3599.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

500
600
750
1000

18.69
20.65
23.06
26.92

253.4
304.0
380.0
506.7

16.51
16.51
16.51
16.51

53.15
55.37
57.78
61.64

2.79
2.79
2.79
3.56

62.31
64.53
66.94
72.38

APPROXIMATE
TOTAL WEIGHT
(kg/km)
COPPER

5318
5945
6809
8496

DC RESISTANT AT 20C1
(ohm/km)

ALUMINUM

COPPER

ALUMINUM

3719
4027
4411
5299

0.0694
0.0578
0.0463
0.0347

0.113
0.0945
0.0756
0.0567

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.2683
0.2604
0.2521
0.2404

20509
19151
17879
16175

Notes: 1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 20 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

69 kV Single conductors, 90C


100% Insulation Level
Standards: AEIC CS7 Specification for Cross Linked Polyethylene
Insulated Shielded Power Cables Rated 69
through 138 kV, NTC 3599.

SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

500
600
750
1000

736
813
908
1060

0.393
0.471
0.589
0.785

650
650
650
650

2093
2180
2275
2427

110
110
110
140

2453
2540
2635
2850

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

3574
3995
4576
5709

2500
2706
2965
3561

0.0212
0.0176
0.0141
0.0106

0.0346
0.0288
0.0230
0.0173

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.4318
0.4191
0.4057
0.3869

Notes: 1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.

2. Inductive and capacitive reactance at 60 Hz and a 7.9 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

18

12744
11900
11110
10051

6 - 30 kV Single Conductors

Description
Copper or aluminum stranded, thermo set insulated

Construction
Conductor
Soft Copper or 1350-H19 aluminum, compact stranded.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor.
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield, 2.5 mils
(0.0635mm) thickness.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE)
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray Cable
type jacket.
Moisture barrier against longitudinally migration.
Armor for Direct Burial.

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C optional)
Overload 130C
Short circuit 250C
19

Rated Operating Voltage


6, 10, 15, 20 & 30 kV

Applications
Distribution of electric energy at Medium Voltage, installed at air,
underground ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 6-30 kV single conductors are manufactured in accordance
with the following standards:
IEC 60228 Conductors for insulated cables.
IEC 60502-2. Power Cables with extruded insulation for voltages form
6 to 30 kV.

Note: Configurations and sizes herein not specified are available


upon request.

20

3.6/6 (7.2) kV Single conductors, 90C

Standards: IEC 60502-2. Power Cables with extruded insulation


for voltages from 6 to 30 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

10
16
25
35
50
70
95
120
150
185
240
300
400
500

3.72
4.70
5.88
6.96
8.26
9.77
11.39
12.88
14.40
15.99
18.29
20.45
23.62
26.41

Notes:

CROSS
SECTION
(mm2)

10.0
16.0
25.0
35.0
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.60
2.60
2.60
2.60

9.55
10.53
11.71
12.79
14.09
15.60
17.22
18.93
20.45
22.04
24.55
27.35
30.94
34.15

1.40
1.40
1.50
1.50
1.60
1.60
1.70
1.70
1.80
1.80
1.90
2.00
2.20
2.30

OVERALL
DIAMETER
(mm)

14.43
15.41
16.80
17.88
19.39
20.90
22.73
24.44
26.16
27.75
30.47
34.06
38.02
41.44

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

292
367
482
596
767
982
1255
1525
1844
2199
2777
3462
4512
5545

229
266
324
375
452
540
656
768
898
1032
1263
1569
1988
2391

1.76
1.10
0.703
0.502
0.352
0.251
0.185
0.147
0.117
0.0951
0.0733
0.0586
0.0440
0.0352

2.87
1.80
1.15
0.821
0.575
0.411
0.302
0.239
0.192
0.155
0.120
0.0958
0.0718
0.0575

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3943
0.3766
0.3597
0.3470
0.3309
0.3182
0.3066
0.2964
0.2880
0.2801
0.2699
0.2611
0.2503
0.2418

16087
13941
12029
10697
9444
8318
7377
6592
6023
5525
5113
4909
4626
4458

1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage.
2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated.
4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

6/10 (12) kV Single conductors, 90C


Standards: IEC 60502-2. Power Cables with extruded insulation
for voltages from 6 to 30 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

16
25
35
50
70
95
120
150
185
240
300
400
500

4.70
5.88
6.96
8.26
9.77
11.39
12.88
14.40
15.99
18.29
20.45
23.62
26.41

16.0
25.0
35.0
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0

3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50
3.50

INSULATION
JACKET
DIAMETER THICKNESS
(mm)
(mm)

12.59
13.77
14.85
16.15
17.66
19.28
20.99
22.51
24.10
26.40
28.80
31.97
34.76

1.50
1.60
1.60
1.60
1.70
1.70
1.80
1.90
1.90
2.00
2.10
2.20
2.30

OVERALL
DIAMETER
(mm)

17.68
19.07
20.15
21.45
23.17
24.79
26.70
28.43
30.02
33.11
35.68
39.05
42.05

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

434
554
672
839
1069
1337
1624
1950
2310
2924
3557
4576
5586

333
396
451
523
627
738
867
1003
1143
1410
1665
2052
2432

1.10
0.703
0.502
0.352
0.251
0.185
0.147
0.117
0.0951
0.0733
0.0586
0.0440
0.0352

1.80
1.15
0.821
0.575
0.411
0.302
0.239
0.192
0.155
0.120
0.0958
0.0718
0.0575

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3766
0.3597
0.3470
0.3309
0.3182
0.3066
0.2964
0.2880
0.2801
0.2699
0.2611
0.2503
0.2418

Notes: 1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage.
2. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 7.5" separated.
4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

21

17650
15393
13797
12277
10892
9723
8736
8015
7380
6622
5982
5305
4826

8.7/15 (17.5) kV Single conductors, 90C

Standards: IEC 60502-2. Power Cables with extruded insulation


for voltages from 6 to 30 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

25
35
50
70
95
120
150
185
240
300
400
500

5.88
6.96
8.26
9.77
11.39
12.88
14.40
15.99
18.29
20.45
23.62
26.41

25.0
35.0
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0

4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50
4.50

15.74
16.82
18.12
19.63
21.25
22.96
24.48
26.07
28.37
30.77
33.94
36.73

1.60
1.70
1.70
1.80
1.80
1.90
1.90
2.00
2.10
2.20
2.30
2.40

21.04
22.33
23.63
25.34
26.96
28.88
30.40
32.78
35.25
37.85
41.23
44.22

Notes:

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

621
753
924
1160
1434
1727
2045
2462
3046
3692
4722
5742

464
532
609
719
834
970
1098
1295
1532
1799
2198
2588

0.703
0.502
0.352
0.251
0.185
0.147
0.117
0.0951
0.0733
0.0586
0.0440
0.0352

1.15
0.821
0.575
0.411
0.302
0.239
0.192
0.155
0.120
0.0958
0.0718
0.0575

INDUCTIVE CAPACITIVE
REACTANCE2 REACTANCE2
(ohm/km)
(ohm-km)

0.3597
0.3470
0.3309
0.3182
0.3066
0.2964
0.2880
0.2801
0.2699
0.2611
0.2503
0.2418

18169
16383
14666
13088
11742
10598
9757
9011
8116
7355
6547
5970

1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage.
2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated.
4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

12/20 (24) kV Single conductors, 90C


Standards: IEC 60502-2. Power Cables with extruded insulation
for voltages from 6 to 30 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

35
50
70
95
120
150
185
240
300
400
500

6.96
8.26
9.77
11.39
12.88
14.40
15.99
18.29
20.45
23.62
26.41

35.0
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0

5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50
5.50

18.86
20.16
21.67
23.29
25.00
26.52
28.11
30.41
32.81
35.98
38.77

1.70
1.80
1.80
1.90
1.90
2.00
2.10
2.20
2.20
2.30
2.50

24.37
25.87
27.38
29.21
30.92
33.23
34.99
37.49
39.89
43.27
47.33

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

833
1020
1249
1541
1827
2202
2587
3183
3819
4860
5989

612
704
808
942
1070
1256
1420
1669
1927
2336
2835

0.502
0.352
0.251
0.185
0.147
0.117
0.0951
0.0733
0.0586
0.0440
0.0352

0.821
0.575
0.411
0.302
0.239
0.192
0.155
0.120
0.0958
0.0718
0.0575

0.3470
0.3309
0.3182
0.3066
0.2964
0.2880
0.2801
0.2699
0.2611
0.2503
0.2418

18759
16881
15140
13645
12365
11419
10575
9557
8688
7758
7092

Notes: 1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage.
2. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 7.5" separated.
4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

22

18/30 (36) kV Single conductors, 90C

Standards: IEC 60502-2. Power Cables with extruded insulation


for voltages from 6 to 30 kV.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm2)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

50
70
95
120
150
185
240
300
400
500

8.26
9.77
11.39
12.88
14.40
15.99
18.29
20.45
23.62
26.41

50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0

8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00
8.00

25.10
26.61
28.23
29.94
31.46
33.05
35.35
37.75
40.92
43.71

1.90
2.00
2.10
2.10
2.20
2.20
2.30
2.40
2.60
2.60

31.02
33.32
35.11
36.82
38.54
40.13
42.64
45.24
49.69
52.48

Notes:

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C1 INDUCTIVE CAPACITIVE


REACTANCE2 REACTANCE2
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1264
1558
1864
2166
2519
2904
3520
4196
5369
6405

949
1116
1265
1409
1573
1737
2006
2303
2845
3251

0.352
0.251
0.185
0.147
0.117
0.0951
0.0733
0.0586
0.0440
0.0352

0.575
0.411
0.302
0.239
0.192
0.155
0.120
0.0958
0.0718
0.0575

0.3309
0.3182
0.3066
0.2964
0.2880
0.2801
0.2699
0.2611
0.2503
0.2418

1. Uo / U (Um) voltage designation means: Uo rated voltage phase to neutral, U rated voltage phase to phase and Um maximum voltage.
2. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
3. Inductive and capacitive reactance at 60 Hz, flat configuration, phases 19 cm separated.
4. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

23

21431
19403
17638
16109
14965
13936
12682
11599
10429
9582

MV-90 5 - 35 kV Three Conductors

Description
Three phases copper or aluminum stranded, thermo set insulated,
stranded and with common PVC jacket.

Contruction
Conductor
Soft Copper or 1350-H19 aluminum, compact stranded.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor.
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield,
2.5 mils (0.0635mm) thickness.
Filler
Flame retardant polyvinyl chloride PVC, applied over the three stranded
phases.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE)
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray
Cable type jacket.
Moisture barrier against longitudinally migration.
Ground conductors laid on interstices.
Armor for Direct Burial.
24

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C optional)
Overload 130C
Short circuit 250C
Rated Voltage
5, 8, 15, 25 and 35 kV.
Insulation Level
100% (133% and 173% optional).

Applications
Distribution of electric energy at Medium Voltage, installed at air, underground
ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 5-35 kV three conductors are manufactured in accordance with
the following standards:
ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded
Copper Conductors.
ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded
Aluminum 1350 Conductors.
UL 1072. Medium Voltage Power Cables MV90.
ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To
46000 Volts.
AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated
5 through 46 kV.

25

Certifications
CENTELSAs 5-35 kV single conductors are certified by:
UL 1072. File E167359.
ICONTEC (Colombia). NTC 2186 standard
CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE

Note: Configurations and sizes herein not specified are available


upon request.

MV-90 5 kV Three conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER SECTION THICKNESS DIAMETER
(mm)
(mm)
(mm)
(mm)

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
22.44
23.48
24.39
26.57
28.98
32.84
Notes:

26

DIAMETER
FILLER
OVER
THICKNESS
TRANDED
(mm)
PHASE (mm)

23.34
25.26
27.67
30.69
32.37
34.39
36.59
39.16
42.02
45.00
47.73
50.26
52.60
54.85
56.81
62.75
67.95
76.27

0.50
0.50
0.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

JACKET
THICKNESS
(mm)

2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
3.56
3.56
3.56

OVERALL
DIAMETER
(mm)

28.52
30.44
32.85
36.87
38.55
40.58
44.34
46.90
49.77
52.74
55.48
58.00
60.35
62.59
64.55
72.09
77.28
85.60

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1101
1339
1688
2297
2638
3072
3755
4423
5245
6023
6938
7842
8737
9628
10498
12786
-

941
1084
1284
1654
1828
2050
2466
2797
3196
3601
4032
4452
4863
5269
5655
6975
8145
10113

2.12
1.34
0.840
0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
-

3.47
2.18
1.37
0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

0.1638
0.1522
0.1416
0.1320
0.1246
0.1204
0.1165
0.1128
0.1093
0.1067
0.1042
0.1022
0.1006
0.0992
0.0981
0.0977
0.0954
0.0924

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

15795
13740
11824
10081
9319
8544
7838
7150
6512
5961
5531
5187
4902
4659
4465
4060
3691
3221

MV-90 5 kV Three conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

134
169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

Notes:

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690
744
794
841
883
924
960
1046
1141
1293

DIAMETER
OVER
TRANDED
PHASE (mm)

919
994
1089
1208
1274
1354
1441
1542
1654
1772
1879
1979
2071
2159
2236
2471
2675
3003

FILLER
JACKET
THICKNESS THICKNESS
(mm)
(mm)

20
20
20
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39

80
80
80
80
80
80
110
110
110
110
110
110
110
110
110
140
140
140

OVERALL
DIAMETER
(mm)

1123
1198
1293
1452
1518
1598
1746
1847
1959
2077
2184
2284
2376
2464
2542
2838
3043
3370

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

740
900
1134
1544
1773
2065
2524
2972
3525
4048
4663
5270
5872
6470
7055
8593
-

632
729
863
1112
1228
1378
1657
1880
2148
2420
2710
2992
3268
3541
3800
4687
5474
6796

0.647
0.407
0.256
0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
-

1.06
0.665
0.418
0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

27

0.2635
0.2449
0.2278
0.2125
0.2005
0.1937
0.1876
0.1815
0.1759
0.1717
0.1677
0.1645
0.1619
0.1597
0.1579
0.1572
0.1535
0.1487

9815
8538
7347
6264
5791
5309
4870
4443
4046
3704
3437
3223
3046
2895
2774
2523
2293
2002

MV-90 8 kV Three conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm)

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65
23.74
24.78
25.69
27.87
30.28
34.14
Notes:

DIAMETER
OVER
TRANDED
PHASE (mm)

28.06
30.47
33.49
35.17
37.20
39.39
41.96
44.83
47.80
50.54
53.06
55.41
57.65
60.86
65.56
70.75
79.07

FILLER
JACKET
THICKNESS THICKNESS
(mm)
(mm)

0.50
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

2.03
2.03
2.03
2.03
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
3.56
3.56
3.56

OVERALL
DIAMETER
(mm)

33.24
36.65
39.67
41.35
44.94
47.14
49.71
52.57
55.55
58.28
60.80
63.15
65.39
68.61
74.89
80.08
88.40

APPROXIMATE
TOTAL WEIGHT
(kg/km)
COPPER

ALUMINUM

1519
1972
2513
2863
3464
4011
4692
5529
6322
7251
8168
9075
9978
11042
13188
-

1265
1567
1870
2052
2442
2722
3067
3480
3901
4346
4778
5201
5619
6199
7377
8574
10584

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)
COPPER ALUMINUM

1.34
0.840
0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
-

2.18
1.37
0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

0.1601
0.1488
0.1386
0.1309
0.1263
0.1221
0.1180
0.1142
0.1112
0.1085
0.1063
0.1045
0.1030
0.1033
0.1010
0.0984
0.0951

16338
14169
12171
11291
10388
9562
8752
7997
7341
6827
6414
6071
5778
5543
5052
4601
4027

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Three conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115

435
479
534
565
602
642
689
741
796
846
892
935
976
1011
1097
1192
1344
Notes:

28

DIAMETER
OVER
TRANDED
PHASE (mm)

1105
1200
1318
1385
1464
1551
1652
1765
1882
1990
2089
2181
2270
2396
2581
2785
3113

FILLER
JACKET
THICKNESS THICKNESS
(mm)
(mm)

20
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39
39

80
80
80
80
110
110
110
110
110
110
110
110
110
110
140
140
140

OVERALL
DIAMETER
(mm)

1309
1443
1562
1628
1769
1856
1957
2070
2187
2295
2394
2486
2575
2701
2948
3153
3480

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1021
1325
1689
1924
2328
2696
3153
3716
4249
4873
5489
6099
6705
7421
8863
-

850
1053
1257
1379
1641
1830
2061
2339
2621
2920
3211
3495
3776
4166
4958
5762
7113

0.407
0.256
0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
-

0.665
0.418
0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

0.2577
0.2395
0.2231
0.2106
0.2032
0.1965
0.1899
0.1838
0.1790
0.1746
0.1711
0.1682
0.1657
0.1662
0.1625
0.1584
0.1531

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10152
8804
7563
7016
6455
5942
5438
4969
4562
4242
3985
3773
3590
3444
3139
2859
2502

MV-90 15 kV Three conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
28.75
30.93
33.34
37.20

DIAMETER
OVER
TRANDED
PHASE (mm)

40.08
41.76
43.79
45.99
48.55
51.42
54.39
57.13
60.90
63.25
65.49
67.45
72.15
77.34
85.66

FILLER
JACKET
THICKNESS THICKNESS
(mm)
(mm)

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
2.79
3.56
3.56
3.56
3.56
3.56
3.56

OVERALL
DIAMETER
(mm)

47.83
49.51
51.54
53.74
56.30
59.17
62.14
64.88
68.65
72.58
74.83
76.79
81.48
86.68
95.00

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

3245
3621
4097
4671
5383
6255
7084
8046
9178
10378
11321
12238
14191
-

2602
2810
3075
3382
3758
4205
4662
5140
5788
6504
6963
7395
8380
9640
11751

0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
-

0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

0.1522
0.1438
0.1386
0.1338
0.1290
0.1245
0.1210
0.1178
0.1167
0.1145
0.1126
0.1110
0.1082
0.1051
0.1012

16393
15303
14175
13131
12097
11123
10268
9592
9044
8588
8195
7879
7214
6600
5809

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Three conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
1055
1096
1132
1218
1313
1465

DIAMETER
OVER
TRANDED
PHASE (mm)

1578
1644
1724
1811
1912
2024
2141
2249
2398
2490
2578
2656
2841
3045
3373

FILLER
JACKET
THICKNESS THICKNESS
(mm)
(mm)

39
39
39
39
39
39
39
39
39
39
39
39
39
39
39

110
110
110
110
110
110
110
110
110
140
140
140
140
140
140

OVERALL
DIAMETER
(mm)

1883
1949
2029
2116
2217
2329
2446
2554
2703
2858
2946
3023
3208
3413
3740

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

2181
2433
2753
3139
3618
4204
4761
5407
6168
6974
7608
8224
9537
-

1749
1889
2066
2273
2525
2826
3133
3455
3890
4371
4679
4970
5631
6478
7897

0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
-

0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

29

0.2449
0.2315
0.2231
0.2153
0.2076
0.2004
0.1947
0.1895
0.1878
0.1843
0.1812
0.1787
0.1741
0.1692
0.1628

10186
9509
8808
8160
7517
6912
6381
5960
5620
5337
5092
4896
4483
4101
3610

MV-90 25 kV Three conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97
31.06
32.10
33.01
35.19
37.60
41.46
Notes:

DIAMETER
OVER
TRANDED
PHASE (mm)

50.95
52.97
55.17
57.73
61.85
64.82
67.56
70.08
72.43
74.67
76.63
81.33
86.52
96.70

FILLER
THICKNESS
(mm)

JACKET
OVERALL
THICKNESS DIAMETER
(mm)
(mm)

APPROXIMATE
TOTAL WEIGHT
(kg/km)
COPPER

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

2.79
2.79
2.79
2.79
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56

58.69
60.72
62.92
65.48
69.60
72.57
76.89
79.42
81.76
84.01
85.97
90.66
95.86
106.03

4601
5111
5723
6478
7585
8472
9761
10767
11757
12738
13688
-

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

ALUMINUM COPPER

3791
4089
4434
4852
5535
6050
6855
7377
7883
8379
8845
9909
11256
13926

0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
-

ALUMINUM

0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

0.1588
0.1530
0.1475
0.1421
0.1385
0.1342
0.1304
0.1273
0.1247
0.1225
0.1207
0.1172
0.1136
0.1103

19847
18509
17258
16006
14814
13758
12915
12227
11651
11150
10747
9893
9096
8060

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Three conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

260
260
260
260
260
260
260
260
260
260
260
260
260
260

853
890
930
977
1030
1084
1134
1180
1223
1264
1300
1385
1480
1632
Notes:

30

DIAMETER
FILLER
OVER
THICKNESS
TRANDED
(mm)
PHASE (mm)

2006
2085
2172
2273
2435
2552
2660
2759
2852
2940
3017
3202
3406
3807

39
39
39
39
39
39
39
39
39
39
39
39
39
39

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

110
110
110
110
140
140
140
140
140
140
140
140
140
140

2311
2390
2477
2578
2740
2857
3027
3127
3219
3307
3385
3569
3774
4174

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

3092
3435
3846
4353
5097
5693
6560
7236
7901
8561
9199
-

2548
2748
2980
3261
3720
4066
4607
4958
5297
5631
5944
6659
7565
9359

0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
-

0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

0.2556
0.2461
0.2374
0.2286
0.2228
0.2160
0.2099
0.2049
0.2007
0.1971
0.1942
0.1887
0.1828
0.1775

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

12333
11501
10724
9946
9205
8549
8025
7598
7240
6929
6678
6147
5652
5008

MV-90 35 kV Three conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06

53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51
31.89
33.16
34.33
35.42
36.46
37.37
39.55
41.96

DIAMETER
OVER
TRANDED
PHASE (mm)

63.62
65.81
68.38
71.25
74.22
76.96
79.48
81.83
84.07
86.03
92.58
97.77

FILLER
THICKNESS
(mm)

JACKET
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

APPROXIMATE
TOTAL WEIGHT
(kg/km)
COPPER

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56
3.56

72.95
75.15
77.71
80.58
83.55
86.29
88.81
91.16
93.40
95.36
101.91
107.11

6761
7424
8239
9227
10176
11249
12298
13329
14349
-

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

ALUMINUM COPPER

5739
6135
6614
7178
7754
8343
8908
9454
9990
10489
12036
13494

0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
-

ALUMINUM

0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764

0.1668
0.1608
0.1548
0.1491
0.1444
0.1402
0.1368
0.1339
0.1314
0.1294
0.1270
0.1228

22170
20773
19366
18016
16810
15841
15047
14378
13794
13323
12318
11374

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Three conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

336
376
423
475
520
570
616
659
700
736
813
908

0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589

345
345
345
345
345
345
345
345
345
345
345
345

1062
1102
1149
1201
1256
1306
1352
1394
1435
1471
1557
1652

DIAMETER
FILLER
OVER
THICKNESS
TRANDED
(mm)
PHASE (mm)

2505
2591
2692
2805
2922
3030
3129
3222
3310
3387
3645
3849

39
39
39
39
39
39
39
39
39
39
39
39

JACKET
OVERALL
THICKNESS DIAMETER
(mm)
(mm)

140
140
140
140
140
140
140
140
140
140
140
140

2872
2959
3060
3172
3289
3397
3496
3589
3677
3754
4012
4217

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C INDUCTIVE CAPACITIVE


REACTANCE REACTANCE
(ohm/km)
(ohm/km)
(ohm-km)

COPPER

ALUMINUM

COPPER

ALUMINUM

4544
4989
5537
6201
6839
7560
8265
8957
9643
-

3857
4123
4445
4824
5211
5607
5987
6354
6714
7049
8089
9068

0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
-

0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

31

0.2684
0.2588
0.2492
0.2400
0.2324
0.2257
0.2201
0.2155
0.2115
0.2082
0.2044
0.1976

13776
12908
12034
11195
10446
9844
9350
8934
8572
8279
7654
7068

MV-90 5 - 35 kV Triplexed Conductors

Description
Three phases copper or aluminum stranded, thermo set insulated.

Contruction
Conductor
Soft Copper or 1350-H19 aluminum, compact stranded.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor.
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield,
2.5 mils (0.0635mm) thickness.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE)
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray
Cable type jacket.
Moisture barrier against longitudinally migration.

32

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C optional)
Overload 130C
Short circuit 250C
Rated Voltage
5, 8, 15, 25 and 35 kV.
Insulation Level
100% (133% and 173% optional).

Applications
Distribution of electric energy at Medium Voltage, installed at air, underground
ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 5-35 kV three conductors are manufactured in accordance with
the following standards:
ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded
Copper Conductors.
ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded
Aluminum 1350 Conductors.
UL 1072. Medium Voltage Power Cables MV90.
ICEA S-97-682 Standard for Utility Shielded Power Cables Rated 5000 To
46000 Volts.
AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated
5 through 46 kV.

33

Certifications
CENTELSAs 5-35 kV Triplex conductors are certified by:
UL 1072. File E167359.
ICONTEC (Colombia). NTC 2186 standard
CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE
CIDET (Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE
CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR
CIDET (Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR

Note: Configurations and sizes herein not specified are available


upon request.

MV-90 5 kV Triplexed conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
22.44
23.48
24.39
26.57
28.98
32.84

1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

13.20
14.88
16.00
17.40
18.18
19.12
20.14
22.35
23.68
25.06
26.33
27.50
28.59
29.63
30.54
33.30
35.71
39.57

28.45
32.07
34.48
37.50
39.18
41.21
43.41
48.17
51.04
54.01
56.75
59.27
61.62
63.86
65.82
71.77
76.96
85.28

Notes:

34

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

742
1008
1296
1729
2015
2380
2828
3542
4246
4894
5682
6464
7239
8012
8775
10460
12736
16518

582
754
891
1086
1205
1357
1539
1916
2197
2472
2776
3074
3365
3653
3932
4648
5471
6832

2.12
1.34
0.840
0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
0.0467
0.0351

3.47
2.18
1.37
0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.1787
0.1702
0.1582
0.1471
0.1390
0.1340
0.1294
0.1284
0.1240
0.1204
0.1173
0.1147
0.1125
0.1107
0.1092
0.1078
0.1048
0.1008

15795
13740
11824
10081
9319
8544
7838
7150
6512
5961
5531
5187
4902
4659
4465
4060
3691
3221

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 5 kV Triplexed conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR
CROSS
DIAMETER
SECTION
(mm)
(sq inches)

134
169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690
744
794
841
883
924
960
1046
1141
1293

45
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80

520
586
630
685
716
753
793
880
932
987
1037
1083
1126
1167
1202
1311
1406
1558

1120
1263
1358
1476
1543
1622
1709
1896
2009
2126
2234
2333
2426
2514
2591
2825
3030
3357

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

498
677
871
1162
1354
1599
1901
2380
2854
3289
3819
4344
4865
5384
5897
7030
8559
11101

391
506
599
730
810
912
1035
1288
1476
1661
1866
2066
2261
2455
2642
3124
3677
4592

0.647
0.407
0.256
0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
0.0142
0.0107

1.06
0.665
0.418
0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

35

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.2876
0.2739
0.2545
0.2368
0.2237
0.2157
0.2083
0.2067
0.1995
0.1938
0.1887
0.1845
0.1811
0.1781
0.1757
0.1735
0.1686
0.1623

9815
8538
7347
6264
5791
5309
4870
4443
4046
3704
3437
3223
3046
2895
2774
2523
2293
2002

MV-90 8 kV Triplexed conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65
23.74
24.78
25.69
27.87
30.28
34.14

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

16.18
17.30
18.70
19.48
20.42
22.46
23.65
24.98
26.36
27.63
28.80
29.89
30.93
32.42
34.60
37.01
40.87

34.87
37.29
40.30
41.98
44.01
48.41
50.97
53.84
56.81
59.55
62.07
64.42
66.66
69.87
74.57
79.76
88.08

Notes:

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1116
1410
1852
2143
2512
3121
3696
4408
5063
5859
6647
7429
8207
9086
10678
12967
16772

862
1006
1209
1332
1490
1832
2070
2359
2642
2953
3257
3555
3849
4243
4866
5703
7086

1.34
0.840
0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
0.0467
0.0351

2.18
1.37
0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.1765
0.1641
0.1526
0.1442
0.1390
0.1376
0.1327
0.1280
0.1243
0.1209
0.1182
0.1159
0.1139
0.1137
0.1107
0.1074
0.1033

16338
14169
12171
11291
10388
9562
8752
7997
7341
6827
6414
6071
5778
5543
5052
4601
4027

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Triplexed conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR
CROSS
DIAMETER
SECTION
(mm)
(sq inches)

169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115

435
479
534
565
602
642
689
741
796
846
892
935
976
1011
1097
1192
1344

60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80

637
681
736
767
804
884
931
984
1038
1088
1134
1177
1218
1276
1362
1457
1609

1373
1468
1587
1653
1733
1906
2007
2120
2237
2344
2444
2536
2624
2751
2936
3140
3468

Notes:

36

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

750
948
1245
1440
1688
2097
2484
2962
3403
3938
4467
4993
5516
6106
7176
8714
11271

579
676
813
895
1001
1231
1391
1585
1775
1985
2189
2389
2586
2852
3270
3832
4762

0.407
0.256
0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
0.0142
0.0107

0.665
0.418
0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.2840
0.2640
0.2455
0.2321
0.2237
0.2215
0.2135
0.2060
0.2000
0.1945
0.1901
0.1865
0.1833
0.1830
0.1781
0.1729
0.1662

10152
8804
7563
7016
6455
5942
5438
4969
4562
4242
3985
3773
3590
3444
3139
2859
2502

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Triplexed conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

CROSS
SECTION
(mm)

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
28.75
30.93
33.34
37.20

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79

22.78
23.56
24.50
25.52
26.71
28.04
29.42
30.69
32.44
33.53
34.57
35.48
37.66
40.07
45.50

49.10
50.78
52.80
55.00
57.57
60.43
63.41
66.14
69.91
72.26
74.50
76.46
81.16
86.36
98.05

Notes:

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

2326
2633
3022
3497
4088
4818
5492
6305
7219
8019
8815
9598
11219
13541
17878

1683
1822
1999
2208
2463
2769
3071
3399
3829
4145
4456
4755
5407
6276
8192

0.528
0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
0.0467
0.0351

0.863
0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764
0.0573

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.1675
0.1586
0.1527
0.1473
0.1419
0.1367
0.1325
0.1288
0.1271
0.1245
0.1223
0.1205
0.1171
0.1134
0.1113

16393
15303
14175
13131
12097
11123
10268
9592
9044
8588
8195
7879
7214
6600
5809

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.2695
0.2552
0.2458
0.2370
0.2283
0.2200
0.2133
0.2073
0.2046
0.2004
0.1968
0.1939
0.1884
0.1826
0.1792

10186
9509
8808
8160
7517
6912
6381
5960
5620
5337
5092
4896
4483
4101
3610

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Triplexed conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR
CROSS
DIAMETER
SECTION
(mm)
(sq inches)

268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
1055
1096
1132
1218
1313
1465

80
80
80
80
80
80
80
80
80
80
80
80
80
80
110

897
928
965
1005
1052
1104
1158
1208
1277
1320
1361
1397
1483
1578
1791

1933
1999
2079
2165
2266
2379
2496
2604
2752
2845
2933
3010
3195
3400
3860

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

1563
1769
2031
2350
2747
3238
3691
4237
4852
5389
5924
6450
7539
9100
12015

1131
1225
1344
1484
1655
1861
2064
2284
2573
2786
2995
3196
3634
4218
5505

0.161
0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
0.0142
0.0107

0.263
0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233
0.0175

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

37

MV-90 25 kV Triplexed conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06

CROSS
SECTION
(mm)

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97
31.06
32.10
33.01
35.19
37.60

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79

Notes:

JACKET
DIAMETER
(mm)

27.82
28.76
29.78
30.97
32.88
34.26
35.53
36.70
37.79
38.83
39.74
43.49
45.90

DIAMETER
OVER
TRANDED
PHASE (mm)

59.96
61.98
64.18
66.75
70.86
73.84
76.57
79.09
81.44
83.68
85.64
93.72
98.91

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

3189
3595
4089
4703
5570
6274
7114
7944
8764
9579
10379
12500
14893

2378
2573
2800
3077
3520
3852
4208
4554
4890
5220
5536
6688
7628

0.419
0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701
0.0584
0.0467

0.684
0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115
0.0955
0.0764

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.1711
0.1648
0.1589
0.1530
0.1487
0.1440
0.1398
0.1364
0.1336
0.1311
0.1290
0.1279
0.1237

19847
18509
17258
16006
14814
13758
12915
12227
11651
11150
10747
9893
9096

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Triplexed conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750

CONDUCTOR
CROSS
DIAMETER
SECTION
(mm)
(sq inches)

299
336
376
423
475
520
570
616
659
700
736
813
908

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

JACKET
DIAMETER
(mm)

DIAMETER
OVER
TRANDED
PHASE (mm)

260
260
260
260
260
260
260
260
260
260
260
260
260

853
890
930
977
1030
1084
1134
1180
1223
1264
1300
1385
1480

80
80
80
80
80
80
80
80
80
80
80
110
110

1095
1132
1173
1219
1295
1349
1399
1445
1488
1529
1565
1712
1807

2361
2440
2527
2628
2790
2907
3015
3114
3206
3295
3372
3690
3894

Notes:

38

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER ALUMINUM

COPPER

ALUMINUM

2143
2416
2748
3160
3743
4216
4781
5338
5890
6437
6975
8401
10009

0.128
0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214
0.0178
0.0142

0.209
0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349
0.0291
0.0233

1598
1729
1882
2068
2366
2589
2828
3060
3286
3508
3721
4495
5127

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.2753
0.2652
0.2557
0.2462
0.2393
0.2318
0.2251
0.2196
0.2149
0.2109
0.2077
0.2059
0.1990

12333
11501
10724
9946
9205
8549
8025
7598
7240
6929
6678
6147
5652

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Triplexed conductors, 90C


(International Unit System) 100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

CONDUCTOR
DIAMETER
(mm)

1/0
2/0
3/0
4/0
250
300
350
400
450
500

8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69

Notes:

CROSS
SECTION
(mm)

53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4

INSULATION
THICKNESS
(mm)

8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76

INSULATION
DIAMETER
(mm)

26.97
27.99
29.18
30.51
31.89
33.16
34.33
35.42
36.46
37.37

JACKET
THICKNESS
(mm)

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

JACKET
DIAMETER
(mm)

33.70
34.72
35.91
37.24
38.62
39.89
41.06
42.15
43.19
44.10

DIAMETER
OVER
TRANDED
PHASE (mm)

72.63
74.83
77.39
80.26
83.23
85.97
88.49
90.84
93.08
95.04

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER

ALUMINUM

COPPER

ALUMINUM

4379
4896
5536
6320
7051
7916
8767
9609
10443
11261

3356
3607
3910
4271
4629
5010
5377
5734
6085
6418

0.332
0.263
0.209
0.166
0.140
0.117
0.100
0.0876
0.0779
0.0701

0.543
0.430
0.341
0.271
0.229
0.191
0.164
0.143
0.127
0.115

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.1767
0.1705
0.1642
0.1581
0.1531
0.1486
0.1449
0.1418
0.1391
0.1369

22170
20773
19366
18016
16810
15841
15047
14378
13794
13323

INDUCTIVE
REACTANCE
(ohm/km)

CAPACITIVE
REACTANCE
(ohm-km)

0.2844
0.2744
0.2642
0.2544
0.2463
0.2391
0.2332
0.2282
0.2238
0.2203

13776
12908
12034
11195
10446
9844
9350
8934
8572
8279

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Triplexed conductors, 90C


100% Insulation Level
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-97-682
Standard for Utility Shielded Power Cables Rated 5000 To 46000 Volts.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
Notes:

CONDUCTOR
CROSS
DIAMETER
SECTION
(mm)
(sq inches)

336
376
423
475
520
570
616
659
700
736

0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393

INSULATION
THICKNESS
(mm)

INSULATION
DIAMETER
(mm)

JACKET
THICKNESS
(mm)

345
345
345
345
345
345
345
345
345
345

1062
1102
1149
1201
1256
1306
1352
1394
1435
1471

80
80
80
80
80
80
80
80
80
80

JACKET
DIAMETER
(mm)

1327
1367
1414
1466
1521
1571
1617
1660
1700
1736

DIAMETER
OVER
TRANDED
PHASE (mm)

2859
2946
3047
3160
3277
3385
3484
3576
3665
3742

APPROXIMATE
TOTAL WEIGHT
(kg/km)

DC RESISTANT AT 20C
(ohm/km)

COPPER ALUMINUM

COPPER

ALUMINUM

2943
3290
3720
4248
4738
5320
5892
6457
7018
7568

0.101
0.0803
0.0637
0.0505
0.0427
0.0356
0.0305
0.0267
0.0237
0.0214

0.165
0.131
0.104
0.0825
0.0698
0.0582
0.0499
0.0436
0.0388
0.0349

2256
2424
2628
2870
3111
3367
3614
3854
4089
4313

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

39

MV-90 5 - 35 kV Single Conductors


URD Type (Underground Residential Distribution)

Description
Copper or aluminum stranded, thermo set insulated.

Contruction
Conductor
Soft Copper or 1350-H19 aluminum, compact stranded.
Conductor Shield
Cross linked polyethylene semiconductor.
Insulation
Cross linked polyethylene XLPE.
Insulation shield
Cross linked polyethylene removable semiconductor.
Insulation and shields are applied by true triple extrusion process.
Metallic shield
Copper tape helically and overlapped applied over insulation shield,
2.5 mils (0.0635mm) thickness.
Jacket
Flame retardant polyvinyl chloride PVC.
Options
EPR or XLPE-TR (Tree retardant XLPE)
Copper wires metallic shield.
Polyethylene Jacket, PVC SR (Sunlight Resistant) Jacket, PVC Tray
Cable type jacket.
Moisture barrier against longitudinally migration.

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations (105C
optional)
40

Overload 130C
Short circuit 250C
Rated Voltage
5, 8, 15, 25 and 35 kV.
Insulation Level
100% (133% and 173% optional).

Applications
Distribution of electric energy at Medium Voltage, installed at air, underground
ducts, raceways, direct buried or tray cables.

Standards
CENTELSAs 5-35 kV three conductors are manufactured in accordance with
the following standards:
ASTM B496, NTC-ICONTEC 2187. Compact round concentric lay stranded
Copper Conductors.
ASTM B400, NTC-ICONTEC 4334. Compact round concentric lay stranded
Aluminum 1350 Conductors.
UL 1072. Medium Voltage Power Cables MV90.
ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 46 kV
AEIC CS8. Specification for Extruded Dielectric, Shielded Power Cables Rated
5 through 46 kV.

Certifications
CENTELSAs 5-35 kV Single conductors are certified by:
UL 1072. File E167359.
ICONTEC (Colombia). NTC 2186 standard.
CIDET (Colombia). Cert. 00412. 15 kV Medium Voltage Copper, XLPE CIDET
(Colombia). Cert. 00413. 35 kV Medium Voltage Copper, XLPE.
CIDET (Colombia). Cert. 00414. 15 kV Medium Voltage Copper, EPR CIDET
(Colombia). Cert. 00415. 35 kV Medium Voltage Copper, EPR.

41

Note: Configurations and sizes herein not specified are available


upon request.

MV-90 5 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER SECTION THICKNESS DIAMETER
(mm)
(mm)
(mm)
(mm)

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
22.44
23.48
24.39
26.57
28.98
32.84
Notes:

42

CONCENTRIC NEUTRAL

JACKET
STRANDS STRANDS CROSS DIAMETER THICKNESS
No.
DIAMETER SECTION
No.
(mm)
(mm)
(mm)

6
6
6
9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
1.63
1.63
1.63
2.05
2.05
2.59
2.59

7.9
7.9
7.9
11.8
14.4
18.3
23.6
28.8
36.7
43.8
52.1
60.4
68.8
77.1
86.0
102.5
131.5
168.3

13.22
14.11
15.23
16.63
17.41
18.35
19.37
20.56
21.89
23.95
25.22
26.39
27.48
28.52
30.27
33.03
36.52
40.38

1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE


DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

15.74
17.42
18.54
19.94
20.72
21.66
22.68
24.89
26.22
28.28
29.55
30.72
31.81
32.85
34.61
37.37
40.85
44.71

311
402
494
671
788
943
1137
1424
1727
2010
2344
2677
3007
3337
3677
4380
5404
6984

2.10
1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.4010
0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

15795
13740
11824
10081
9319
8544
7838
7150
6512
5961
5531
5187
4902
4659
4465
4060
3691
3221

MV-90 5 kV Single Copper conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER SECTION THICKNESS DIAMETER
(sq inches)
(mm)
(mm)
(mm)

134
169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690
744
794
841
883
924
960
1046
1141
1293

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

6
6
6
9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

51
51
51
51
51
51
51
51
51
64
64
64
64
64
81
81
102
102

0.0122
0.0122
0.0122
0.0183
0.0223
0.0284
0.0365
0.0446
0.0568
0.0678
0.0808
0.0937
0.107
0.120
0.133
0.159
0.204
0.261

521
556
600
655
686
723
763
810
862
943
993
1039
1082
1123
1192
1301
1438
1590

45
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80

620
686
730
785
816
853
893
980
1032
1113
1163
1209
1252
1293
1362
1471
1608
1760

209
270
332
451
530
634
764
957
1160
1351
1575
1799
2021
2243
2471
2944
3632
4693

0.641
0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

43

0.6454
0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

9815
8538
7347
6264
5791
5309
4870
4443
4046
3704
3437
3223
3046
2895
2774
2523
2293
2002

MV-90 8 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65
23.74
24.78
25.69
27.87
30.28
34.14
Notes:

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

6
6
9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
1.63
1.63
1.63
2.05
2.05
2.59
2.59

7.9
7.9
11.8
14.4
18.3
23.6
28.8
36.7
43.8
52.1
60.4
68.8
77.1
86.0
102.5
131.5
168.3

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

15.41
16.53
17.93
18.71
19.65
20.67
21.86
23.19
25.25
26.52
27.69
28.78
29.82
32.15
34.33
37.82
41.68

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

18.72
19.84
21.24
22.02
22.96
25.00
26.19
27.52
29.58
30.85
32.02
33.11
34.15
36.49
38.67
42.15
46.01

435
530
709
828
984
1237
1473
1778
2063
2400
2735
3068
3399
3776
4450
5478
7065

1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16338
14169
12171
11291
10388
9562
8752
7997
7341
6827
6414
6071
5778
5543
5052
4601
4027

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Single Copper conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER
SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115

435
479
534
565
602
642
689
741
796
846
892
935
976
1011
1097
1192
1344
Notes:

44

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

6
6
9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

51
51
51
51
51
51
51
51
64
64
64
64
64
81
81
102
102

0.0122
0.0122
0.0183
0.0223
0.0284
0.0365
0.0446
0.0568
0.0678
0.0808
0.0937
0.107
0.120
0.133
0.159
0.204
0.261

607
651
706
737
774
814
861
913
994
1044
1090
1133
1174
1266
1352
1489
1641

60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80

737
781
836
867
904
984
1031
1084
1165
1215
1261
1304
1344
1436
1522
1659
1811

292
356
477
556
661
831
990
1195
1387
1613
1838
2062
2284
2538
2990
3681
4748

0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10152
8804
7563
7016
6455
5942
5438
4969
4562
4242
3985
3773
3590
3444
3139
2859
2502

MV-90 15 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
28.75
30.93
33.34
37.20

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
1.63
1.63
1.63
2.05
2.05
2.59
2.59

11.8
14.4
18.3
23.6
28.8
36.7
43.8
52.1
60.4
68.8
77.1
86.0
102.5
131.5
168.3

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

20.99
21.77
22.71
23.73
24.92
26.25
28.31
29.58
31.33
32.42
33.46
35.21
37.39
40.88
44.74

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79

25.32
26.10
27.04
28.06
29.25
30.58
32.64
33.91
35.66
36.75
37.79
39.55
41.73
45.21
50.63

866
990
1152
1356
1597
1907
2199
2542
2917
3256
3593
3940
4622
5661
7443

0.523
0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16393
15303
14175
13131
12097
11123
10268
9592
9044
8588
8195
7879
7214
6600
5809

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Single Copper conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
1055
1096
1132
1218
1313
1465

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

9
11
14
18
22
28
21
25
29
33
37
26
31
25
32

51
51
51
51
51
51
64
64
64
64
64
81
81
102
102

0.0183
0.0223
0.0284
0.0365
0.0446
0.0568
0.0678
0.0808
0.0937
0.107
0.120
0.133
0.159
0.204
0.261

826
857
894
934
981
1034
1114
1164
1233
1276
1317
1386
1472
1609
1761

80
80
80
80
80
80
80
80
80
80
80
80
80
80
110

997
1028
1065
1105
1152
1204
1285
1335
1404
1447
1488
1557
1643
1780
1993

582
665
774
911
1073
1282
1478
1708
1960
2188
2415
2648
3106
3805
5002

0.159
0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

45

0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

10186
9509
8808
8160
7517
6912
6381
5960
5620
5337
5092
4896
4483
4101
3610

MV-90 25 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97
31.06
32.10
33.01
35.19
37.60
41.46
Notes:

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

11
14
18
22
28
21
25
29
33
37
26
31
25
32

1.29
1.29
1.29
1.29
1.29
1.63
1.63
1.63
1.63
1.63
2.05
2.05
2.59
2.59

14.4
18.3
23.6
28.8
36.7
43.8
52.1
60.4
68.8
77.1
86.0
102.5
131.5
168.3

26.03
26.97
27.99
29.18
31.09
33.15
34.42
35.59
36.68
37.72
39.47
41.65
45.14
49.86

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

30.36
31.30
32.32
33.51
35.42
37.48
38.75
39.92
41.01
42.05
43.81
47.55
51.03
55.75

1165
1334
1543
1791
2146
2448
2800
3148
3493
3837
4189
5052
6118
7842

0.415
0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

19847
18509
17258
16006
14814
13758
12915
12227
11651
11150
10747
9893
9096
8060

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Single Copper conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER
SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

260
260
260
260
260
260
260
260
260
260
260
260
260
260

853
890
930
977
1030
1084
1134
1180
1223
1264
1300
1385
1480
1632
Notes:

46

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

11
14
18
22
28
21
25
29
33
37
26
31
25
32

51
51
51
51
51
64
64
64
64
64
81
81
102
102

0.0223
0.0284
0.0365
0.0446
0.0568
0.0678
0.0808
0.0937
0.107
0.120
0.133
0.159
0.204
0.261

1025
1062
1102
1149
1224
1305
1355
1401
1444
1485
1554
1640
1777
1963

80
80
80
80
80
80
80
80
80
80
80
110
110
110

1195
1232
1273
1319
1395
1476
1526
1572
1615
1656
1725
1872
2009
2195

783
896
1037
1204
1442
1645
1882
2116
2348
2579
2815
3395
4111
5270

0.126
0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

12333
11501
10724
9946
9205
8549
8025
7598
7240
6929
6678
6147
5652
5008

MV-90 35 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51
31.89
33.16
34.33
35.42
36.46
37.37
39.55
41.96
45.82

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

14
18
22
28
21
25
29
33
37
26
31
25
32

1.29
1.29
1.29
1.29
1.63
1.63
1.63
1.63
1.63
2.05
2.05
2.59
2.59

18.3
23.6
28.8
36.7
43.8
52.1
60.4
68.8
77.1
86.0
102.5
131.5
168.3

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

31.91
32.93
34.12
35.45
37.51
38.78
39.95
41.04
42.08
43.83
46.87
50.36
54.22

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

36.24
37.26
38.45
39.78
41.84
43.11
44.28
45.37
46.41
48.17
52.77
56.25
60.11

1583
1800
2057
2386
2696
3056
3412
3764
4114
4472
5443
6528
8200

0.329
0.261
0.207
0.164
0.139
0.116
0.0992
0.0868
0.0771
0.0694
0.0578
0.0463
0.0347

0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

22170
20773
19366
18016
16810
15841
15047
14378
13794
13323
12318
11374
10136

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Single Copper conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS INSULATION INSULATION


DIAMETER
SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

345
345
345
345
345
345
345
345
345
345
345
345
345

1062
1102
1149
1201
1256
1306
1352
1394
1435
1471
1557
1652
1804

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

14
18
22
28
21
25
29
33
37
26
31
25
32

51
51
51
51
64
64
64
64
64
81
81
102
102

0.0284
0.0365
0.0446
0.0568
0.0678
0.0808
0.0937
0.107
0.120
0.133
0.159
0.204
0.261

1256
1297
1343
1396
1477
1527
1573
1616
1657
1726
1845
1983
2134

80
80
80
80
80
80
80
80
80
80
110
110
110

1427
1467
1514
1566
1647
1697
1743
1786
1827
1896
2078
2215
2367

1064
1210
1382
1603
1812
2054
2293
2530
2765
3006
3658
4387
5511

0.100
0.0795
0.0630
0.0500
0.0423
0.0353
0.0302
0.0264
0.0235
0.0212
0.0176
0.0141
0.0106

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

47

0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

13776
12908
12034
11195
10446
9844
9350
8934
8572
8279
7654
7068
6298

MV-90 5 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
22.44
23.48
24.39
26.57
28.98
32.84
Notes:

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

6
6
6
6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
2.05
2.05

7.9
7.9
7.9
7.9
9.2
11.8
14.4
18.3
22.3
26.2
31.4
36.7
41.9
47.1
52.1
62.5
79.4
102.5

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

13.22
14.11
15.23
16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
29.43
32.19
35.44
39.30

1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

15.74
17.42
18.54
19.94
20.72
21.66
22.68
24.89
26.22
27.60
28.87
30.04
31.13
32.17
33.76
36.52
39.78
43.64

258
318
361
423
472
545
627
792
918
1042
1188
1333
1475
1616
1759
2086
2516
3171

3.43
2.16
1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.4010
0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

15795
13740
11824
10081
9319
8544
7838
7150
6512
5961
5531
5187
4902
4659
4465
4060
3691
3221

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 5 kV Single Aluminum conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

134
169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690
744
794
841
883
924
960
1046
1141
1293
Notes:

48

CONCENTRIC NEUTRAL
STRANDS
No.

6
6
6
6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
51
51
51
51
51
51
51
51
51
51
51
64
64
81
81

0.0122
0.0122
0.0122
0.0122
0.0142
0.0183
0.0223
0.0284
0.0345
0.0406
0.0487
0.0568
0.0649
0.0730
0.0808
0.0969
0.123
0.159

521
556
600
655
686
723
763
810
862
916
966
1012
1055
1096
1159
1267
1395
1547

45
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80

620
686
730
785
816
853
893
980
1032
1087
1137
1183
1226
1267
1329
1438
1566
1718

173
213
243
284
317
366
422
532
617
700
799
895
991
1086
1182
1402
1691
2131

1.05
0.658
0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.6454
0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

9815
8538
7347
6264
5791
5309
4870
4443
4046
3704
3437
3223
3046
2895
2774
2523
2293
2002

MV-90 8 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65
23.74
24.78
25.69
27.87
30.28
34.14

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

6
6
6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
2.05
2.05

7.9
7.9
7.9
9.2
11.8
14.4
18.3
22.3
26.2
31.4
36.7
41.9
47.1
52.1
62.5
79.4
102.5

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

15.41
16.53
17.93
18.71
19.65
20.67
21.86
23.19
24.57
25.84
27.01
28.10
29.14
31.31
33.49
36.74
40.60

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

18.72
19.84
21.24
22.02
22.96
25.00
26.19
27.52
28.90
30.17
31.34
32.43
33.47
35.64
37.82
41.08
44.94

351
396
461
512
586
727
840
969
1096
1244
1391
1535
1678
1858
2155
2590
3252

2.16
1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16338
14169
12171
11291
10388
9562
8752
7997
7341
6827
6414
6071
5778
5543
5052
4601
4027

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Single Aluminum conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

169
213
268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115

435
479
534
565
602
642
689
741
796
846
892
935
976
1011
1097
1192
1344

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

6
6
6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

51
51
51
51
51
51
51
51
51
51
51
51
51
64
64
81
81

0.0122
0.0122
0.0122
0.0142
0.0183
0.0223
0.0284
0.0345
0.0406
0.0487
0.0568
0.0649
0.0730
0.0808
0.0969
0.123
0.159

607
651
706
737
774
814
861
913
967
1017
1063
1106
1147
1233
1318
1447
1599

60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

737
781
836
867
904
984
1031
1084
1138
1188
1234
1277
1318
1403
1489
1617
1769

236
266
310
344
394
489
565
651
736
836
935
1032
1128
1249
1449
1741
2186

0.658
0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

49

0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

10152
8804
7563
7016
6455
5942
5438
4969
4562
4242
3985
3773
3590
3444
3139
2859
2502

MV-90 15 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
26.80
27.84
28.75
30.93
33.34
37.20
Notes:

CONCENTRIC NEUTRAL

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
2.05
2.05

7.9
9.2
11.8
14.4
18.3
22.3
26.2
31.4
36.7
41.9
47.1
52.1
62.5
79.4
102.5

20.99
21.77
22.71
23.73
24.92
26.25
27.63
28.90
30.65
31.74
32.78
34.37
36.55
39.80
43.66

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79

25.32
26.10
27.04
28.06
29.25
30.58
31.96
33.23
34.98
36.07
37.11
38.70
40.88
44.14
49.56

618
674
755
846
964
1098
1232
1386
1573
1723
1872
2021
2328
2774
3626

0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

16393
15303
14175
13131
12097
11123
10268
9592
9044
8588
8195
7879
7214
6600
5809

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Single Aluminum conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

268
299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
1055
1096
1132
1218
1313
1465
Notes:

50

CONCENTRIC NEUTRAL
STRANDS
No.

6
7
9
11
14
17
20
24
28
32
36
25
30
24
31

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
51
51
51
51
51
51
51
51
64
64
81
81

0.0122
0.0142
0.0183
0.0223
0.0284
0.0345
0.0406
0.0487
0.0568
0.0649
0.0730
0.0808
0.0969
0.123
0.159

826
857
894
934
981
1034
1088
1138
1207
1250
1291
1353
1439
1567
1719

80
80
80
80
80
80
80
80
80
80
80
80
80
80
110

997
1028
1065
1105
1152
1204
1258
1308
1377
1420
1461
1524
1609
1738
1951

415
453
507
568
648
738
828
931
1057
1158
1258
1358
1565
1864
2437

0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10186
9509
8808
8160
7517
6912
6381
5960
5620
5337
5092
4896
4483
4101
3610

MV-90 25 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

CONCENTRIC NEUTRAL
INSULATION INSULATION
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
THICKNESS DIAMETER STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
(mm)
(mm)
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97
31.06
32.10
33.01
35.19
37.60
41.46

7
9
11
14
17
20
24
28
32
36
25
30
24
31

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
2.05
2.05

9.2
11.8
14.4
18.3
22.3
26.2
31.4
36.7
41.9
47.1
52.1
62.5
79.4
102.5

26.03
26.97
27.99
29.18
31.09
32.47
33.74
34.91
36.00
37.04
38.63
40.81
44.06
48.78

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

30.36
31.30
32.32
33.51
35.42
36.80
38.07
39.24
40.33
41.37
42.96
46.71
49.96
54.68

849
936
1033
1159
1337
1481
1644
1804
1961
2116
2271
2755
3227
4025

0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

19847
18509
17258
16006
14814
13758
12915
12227
11651
11150
10747
9893
9096
8060

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Single Aluminum conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

299
336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

260
260
260
260
260
260
260
260
260
260
260
260
260
260

853
890
930
977
1030
1084
1134
1180
1223
1264
1300
1385
1480
1632

CONCENTRIC NEUTRAL
STRANDS
No.

7
9
11
14
17
20
24
28
32
36
25
30
24
31

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
51
51
51
51
51
51
51
64
64
81
81

0.0142
0.0183
0.0223
0.0284
0.0345
0.0406
0.0487
0.0568
0.0649
0.0730
0.0808
0.0969
0.123
0.159

1025
1062
1102
1149
1224
1278
1328
1374
1417
1458
1521
1607
1735
1921

80
80
80
80
80
80
80
80
80
80
80
110
110
110

1195
1232
1273
1319
1395
1449
1499
1545
1588
1629
1691
1839
1967
2153

571
629
694
779
899
995
1105
1212
1318
1422
1526
1851
2168
2705

0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

51

0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

12333
11501
10724
9946
9205
8549
8025
7598
7240
6929
6678
6147
5652
5008

MV-90 35 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

8.53
9.55
10.74
12.07
13.21
14.48
15.65
16.74
17.78
18.69
20.65
23.06
26.92

53.5
67.4
85.0
107.2
126.7
152.0
177.3
202.7
228.0
253.4
304.0
380.0
506.7

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51
31.89
33.16
34.33
35.42
36.46
37.37
39.55
41.96
45.82
Notes:

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

9
11
14
17
20
24
28
32
36
25
30
24
31

1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.29
1.63
1.63
2.05
2.05

11.8
14.4
18.3
22.3
26.2
31.4
36.7
41.9
47.1
52.1
62.5
79.4
102.5

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

31.91
32.93
34.12
35.45
36.83
38.10
39.27
40.36
41.40
42.99
46.03
49.28
53.14

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79

36.24
37.26
38.45
39.78
41.16
42.43
43.60
44.69
45.73
47.32
51.93
55.18
59.04

1185
1290
1424
1577
1729
1900
2067
2231
2393
2554
3146
3636
4384

0.537
0.426
0.338
0.268
0.227
0.189
0.162
0.142
0.126
0.113
0.0945
0.0756
0.0567

0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817
0.2766
0.2721
0.2683
0.2604
0.2521
0.2404

22170
20773
19366
18016
16810
15841
15047
14378
13794
13323
12318
11374
10136

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Single Aluminum conductor, 90C


100% Insulation Level, 33% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350
400
450
500
600
750
1000

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

336
376
423
475
520
570
616
659
700
736
813
908
1060

0.0829
0.105
0.132
0.166
0.196
0.236
0.275
0.314
0.353
0.393
0.471
0.589
0.785

345
345
345
345
345
345
345
345
345
345
345
345
345

1062
1102
1149
1201
1256
1306
1352
1394
1435
1471
1557
1652
1804
Notes:

52

CONCENTRIC NEUTRAL
STRANDS
No.

9
11
14
17
20
24
28
32
36
25
30
24
31

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
51
51
51
51
51
51
64
64
81
81

0.0183
0.0223
0.0284
0.0345
0.0406
0.0487
0.0568
0.0649
0.0730
0.0808
0.0969
0.123
0.159

1256
1297
1343
1396
1450
1500
1546
1589
1630
1692
1812
1940
2092

80
80
80
80
80
80
80
80
80
80
110
110
110

1427
1467
1514
1566
1621
1671
1717
1760
1801
1863
2044
2172
2324

797
867
957
1060
1162
1277
1389
1500
1608
1716
2114
2444
2946

0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494
0.0432
0.0384
0.0346
0.0288
0.0230
0.0173

0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533
0.4452
0.4378
0.4318
0.4191
0.4057
0.3869

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

13776
12908
12034
11195
10446
9844
9350
8934
8572
8279
7654
7068
6298

MV-90 5 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

3.40
4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07

8.4
13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

8.86
9.75
10.87
12.27
13.05
13.99
15.01
16.20
17.53

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

6
10
16
26
20
25
32
25
32

1.29
1.29
1.29
1.29
1.63
1.63
1.63
2.05
2.05

7.9
13.1
20.9
34.0
41.7
52.1
66.7
82.7
105.8

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

13.22
14.11
15.23
16.63
18.09
19.03
20.05
22.08
23.41

1.14
1.52
1.52
1.52
1.52
1.52
1.52
2.03
2.03

15.74
17.42
18.54
19.94
21.40
22.34
23.36
26.42
27.75

311
450
615
876
1044
1258
1539
1935
2378

2.10
1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164

0.4010
0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023

15795
13740
11824
10081
9319
8544
7838
7150
6512

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 5 kV Single Copper conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649

Standard for Concentric Neutral Cables Rated 5-46 kV.


SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

134
169
213
268
299
336
376
423
475

0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166

90
90
90
90
90
90
90
90
90

349
384
428
483
514
551
591
638
690

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

6
10
16
26
20
25
32
25
32

51
51
51
51
64
64
64
81
81

0.0122
0.0203
0.0325
0.0528
0.0646
0.0808
0.103
0.128
0.164

521
556
600
655
712
749
789
869
922

45
60
60
60
60
60
60
80
80

620
686
730
785
843
880
920
1040
1092

209
302
413
589
702
846
1034
1300
1598

0.641
0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

53

0.6454
0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864

9815
8538
7347
6264
5791
5309
4870
4443
4046

MV-90 8 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

4.29
5.41
6.81
7.59
8.53
9.55
10.74
12.07

13.3
21.2
33.6
42.4
53.5
67.4
85.0
107.2

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

11.05
12.17
13.57
14.35
15.29
16.31
17.50
18.83
Notes:

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

10
16
26
20
25
32
25
32

1.29
1.29
1.29
1.63
1.63
1.63
2.05
2.05

13.1
20.9
34.0
41.7
52.1
66.7
82.7
105.8

15.41
16.53
17.93
19.39
20.33
21.35
23.38
24.71

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03

18.72
19.84
21.24
22.70
23.64
25.68
27.72
29.05

483
650
914
1084
1300
1640
1983
2429

1.32
0.831
0.523
0.415
0.329
0.261
0.207
0.164

0.3835
0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023

16338
14169
12171
11291
10388
9562
8752
7997

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Single Copper conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

6
4
2
1
1/0
2/0
3/0
4/0

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

169
213
268
299
336
376
423
475

0.0206
0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166

15
15
15
15
15
15
15
15

435
479
534
565
602
642
689
741
Notes:

54

CONCENTRIC NEUTRAL
STRANDS
No.

10
16
26
20
25
32
25
32

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
64
64
64
81
81

0.0203
0.0325
0.0528
0.0646
0.0808
0.103
0.128
0.164

607
651
706
763
800
840
921
973

60
60
60
60
60
80
80
80

737
781
836
894
931
1011
1091
1144

325
437
614
728
874
1102
1333
1632

0.403
0.253
0.159
0.126
0.100
0.0795
0.0630
0.0500

0.6172
0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10152
8804
7563
7016
6455
5942
5438
4969

MV-90 15 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

6.81
7.59
8.53
9.55
10.74
12.07

33.6
42.4
53.5
67.4
85.0
107.2

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

26
20
25
32
25
32

1.29
1.63
1.63
1.63
2.05
2.05

34.0
41.7
52.1
66.7
82.7
105.8

20.99
22.45
23.39
24.41
26.44
27.77

2.03
2.03
2.03
2.03
2.03
2.03

25.32
26.78
27.72
28.74
30.78
32.11

1071
1247
1470
1759
2107
2558

0.523
0.415
0.329
0.261
0.207
0.164

0.3487
0.3372
0.3284
0.3199
0.3111
0.3023

16393
15303
14175
13131
12097
11123

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Single Copper conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

268
299
336
376
423
475

0.0521
0.0657
0.0829
0.105
0.132
0.166

175
175
175
175
175
175

655
685
722
763
809
862

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

26
20
25
32
25
32

51
64
64
64
81
81

0.0528
0.0646
0.0808
0.103
0.128
0.164

826
884
921
961
1041
1093

80
80
80
80
80
80

997
1054
1091
1131
1212
1264

719
838
988
1182
1416
1719

0.159
0.126
0.100
0.0795
0.0630
0.0500

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

55

0.5611
0.5427
0.5285
0.5148
0.5006
0.4864

10186
9509
8808
8160
7517
6912

MV-90 25 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

7.59
8.53
9.55
10.74
12.07

42.4
53.5
67.4
85.0
107.2

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
Notes:

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

20
25
32
25
32

1.63
1.63
1.63
2.05
2.05

41.7
52.1
66.7
82.7
105.8

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

26.71
27.65
28.67
30.70
32.61

2.03
2.03
2.03
2.03
2.03

31.04
31.98
33.00
35.04
36.95

1423
1651
1946
2302
2797

0.415
0.329
0.261
0.207
0.164

0.3372
0.3284
0.3199
0.3111
0.3023

19847
18509
17258
16006
14814

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Single Copper conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

299
336
376
423
475

0.0657
0.0829
0.105
0.132
0.166

260
260
260
260
260

853
890
930
977
1030
Notes:

56

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

20
25
32
25
32

64
64
64
81
81

0.0646
0.0808
0.103
0.128
0.164

1051
1089
1129
1209
1284

80
80
80
80
80

1222
1259
1299
1379
1455

956
1109
1308
1547
1880

0.126
0.100
0.0795
0.0630
0.0500

0.5427
0.5285
0.5148
0.5006
0.4864

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

12333
11501
10724
9946
9205

MV-90 35 kV Single Copper conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

8.53
9.55
10.74
12.07

53.5
67.4
85.0
107.2

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

25
32
25
32

1.63
1.63
2.05
2.05

52.1
66.7
82.7
105.8

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

32.59
33.61
35.64
36.97

2.03
2.03
2.03
2.03

36.92
37.94
39.98
41.31

1900
2203
2568
3037

0.329
0.261
0.207
0.164

0.3284
0.3199
0.3111
0.3023

22170
20773
19366
18016

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Single Copper conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

336
376
423
475

0.0829
0.105
0.132
0.166

345
345
345
345

1062
1102
1149
1201

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

25
32
25
32

64
64
81
81

0.0808
0.103
0.128
0.164

1283
1323
1403
1456

80
80
80
80

1454
1494
1574
1626

1277
1481
1726
2041

0.100
0.0795
0.0630
0.0500

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

57

0.5285
0.5148
0.5006
0.4864

13776
12908
12034
11195

MV-90 5 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65

21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3

CONCENTRIC NEUTRAL
INSULATION INSULATION
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
THICKNESS DIAMETER STRANDS STRANDS
CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
(mm)
(mm)
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29
2.29

10.87
12.27
13.05
13.99
15.01
16.20
17.53
18.91
20.18
21.35
Notes:

10
16
20
26
20
25
32
25
29
32

1.29
1.29
1.29
1.29
1.63
1.63
1.63
2.05
2.05
2.05

13.1
20.9
26.2
34.0
41.7
52.1
66.7
82.7
95.9
105.8

15.23
16.63
17.41
18.35
20.05
21.24
22.57
24.79
26.06
27.23

1.52
1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03

18.54
19.94
20.72
21.66
23.36
25.57
26.90
29.13
30.40
31.57

409
543
629
750
883
1109
1333
1577
1796
1984

1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162

0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817

11824
10081
9319
8544
7838
7150
6512
5961
5531
5187

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 5 kV Single Aluminum conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

213
268
299
336
376
423
475
520
570
616

0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275

90
90
90
90
90
90
90
90
90
90

428
483
514
551
591
638
690
744
794
841
Notes:

58

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

10
16
20
26
20
25
32
25
29
32

51
51
51
51
64
64
64
81
81
81

0.0203
0.0325
0.0406
0.0528
0.0646
0.0808
0.103
0.128
0.149
0.164

600
655
686
723
789
836
889
976
1026
1072

60
60
60
60
60
80
80
80
80
80

730
785
816
853
920
1007
1059
1147
1197
1243

275
365
423
504
594
745
896
1060
1207
1333

0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533

7347
6264
5791
5309
4870
4443
4046
3704
3437
3223

MV-90 8 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
250
300
350
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

5.41
6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65

21.2
33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92
2.92

12.17
13.57
14.35
15.29
16.31
17.50
18.83
20.21
21.48
22.65

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

10
16
20
26
20
25
32
25
29
32

1.29
1.29
1.29
1.29
1.63
1.63
1.63
2.05
2.05
2.05

13.1
20.9
26.2
34.0
41.7
52.1
66.7
82.7
95.9
105.8

16.53
17.93
18.71
19.65
21.35
22.54
23.87
26.09
27.36
28.53

1.52
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03

19.84
21.24
22.02
22.96
25.68
26.87
28.20
30.43
31.70
32.87

445
581
669
791
985
1157
1384
1630
1852
2042

1.36
0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162

0.3660
0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817

14169
12171
11291
10388
9562
8752
7997
7341
6827
6414

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 8 kV Single Aluminum conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
250
300
350
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

213
268
299
336
376
423
475
520
570
616

0.0328
0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275

115
115
115
115
115
115
115
115
115
115

479
534
565
602
642
689
741
796
846
892

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(sq inches)
(kg/km)

10
16
20
26
20
25
32
25
29
32

51
51
51
51
64
64
64
81
81
81

0.0203
0.0325
0.0406
0.0528
0.0646
0.0808
0.103
0.128
0.149
0.164

651
706
737
774
840
887
940
1027
1077
1123

60
60
60
60
80
80
80
80
80
80

781
836
867
904
1011
1058
1110
1198
1248
1294

299
391
449
532
662
778
930
1096
1245
1372

0.414
0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

59

0.5890
0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533

8804
7563
7016
6455
5942
5438
4969
4562
4242
3985

MV-90 15 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

6.81
7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65

33.6
42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

16.63
17.41
18.35
19.37
20.56
21.89
23.27
24.54
25.71
Notes:

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

16
20
26
20
25
32
25
29
32

1.29
1.29
1.29
1.63
1.63
1.63
2.05
2.05
2.05

20.9
26.2
34.0
41.7
52.1
66.7
82.7
95.9
105.8

20.99
21.77
22.71
24.41
25.60
26.93
29.15
30.42
32.17

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

25.32
26.10
27.04
28.74
29.93
31.26
33.49
34.76
36.51

738
831
960
1103
1281
1514
1766
1994
2224

0.854
0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162

0.3487
0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817

16393
15303
14175
13131
12097
11123
10268
9592
9044

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 15 kV Single Aluminum conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

2
1
1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

268
299
336
376
423
475
520
570
616

0.0521
0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275

175
175
175
175
175
175
175
175
175

655
685
722
763
809
862
916
966
1012
Notes:

60

CONCENTRIC NEUTRAL
STRANDS
No.

16
20
26
20
25
32
25
29
32

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
51
64
64
64
81
81
81

0.0325
0.0406
0.0528
0.0646
0.0808
0.103
0.128
0.149
0.164

826
857
894
961
1008
1060
1148
1198
1267

80
80
80
80
80
80
80
80
80

997
1028
1065
1131
1178
1231
1318
1368
1437

496
558
645
742
861
1017
1187
1340
1495

0.260
0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494

0.5611
0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

10186
9509
8808
8160
7517
6912
6381
5960
5620

MV-90 25 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649

Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
Notes:

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

7.59
8.53
9.55
10.74
12.07
13.21
14.48
15.65

42.4
53.5
67.4
85.0
107.2
126.7
152.0
177.3

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

6.60
6.60
6.60
6.60
6.60
6.60
6.60
6.60

21.67
22.61
23.63
24.82
26.15
27.53
28.80
29.97

CONCENTRIC NEUTRAL
STRANDS STRANDS CROSS
No.
DIAMETER SECTION
(mm)
(mm)

20
26
20
25
32
25
29
32

1.29
1.29
1.63
1.63
1.63
2.05
2.05
2.05

26.2
34.0
41.7
52.1
66.7
82.7
95.9
105.8

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(kg/km)

26.03
26.97
28.67
29.86
31.77
33.99
35.26
36.43

2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03

30.36
31.30
33.00
34.19
36.10
38.33
39.60
40.77

1006
1141
1291
1476
1753
2015
2252
2455

0.678
0.537
0.426
0.338
0.268
0.227
0.189
0.162

0.3372
0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817

19847
18509
17258
16006
14814
13758
12915
12227

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 25 kV Single Aluminum conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649

Standard for Concentric Neutral Cables Rated 5-46 kV.


SIZE
AWG /
kcmil

1
1/0
2/0
3/0
4/0
250
300
350
Notes:

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

299
336
376
423
475
520
570
616

0.0657
0.0829
0.105
0.132
0.166
0.196
0.236
0.275

260
260
260
260
260
260
260
260

853
890
930
977
1030
1084
1134
1180

CONCENTRIC NEUTRAL
STRANDS
No.

20
26
20
25
32
25
29
32

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
51
64
64
64
81
81
81

0.0406
0.0528
0.0646
0.0808
0.103
0.128
0.149
0.164

1025
1062
1129
1176
1251
1338
1388
1434

80
80
80
80
80
80
80
80

1195
1232
1299
1346
1421
1509
1559
1605

676
767
868
992
1178
1354
1513
1650

0.207
0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

61

0.5427
0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533

12333
11501
10724
9946
9205
8549
8025
7598

MV-90 35 kV Single Aluminum conductor, 90C


(International Unit System) 100% Insulation Level,
100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.

SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
DIAMETER SECTION
(mm)
(mm)

8.53
9.55
10.74
12.07
13.21
14.48
15.65

53.5
67.4
85.0
107.2
126.7
152.0
177.3

INSULATION INSULATION
THICKNESS DIAMETER
(mm)
(mm)

8.76
8.76
8.76
8.76
8.76
8.76
8.76

26.97
27.99
29.18
30.51
31.89
33.16
34.33
Notes:

CONCENTRIC NEUTRAL
JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
No.
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm)
(mm)
(kg/km)

26
20
25
32
25
29
32

1.29
1.63
1.63
1.63
2.05
2.05
2.05

34.0
41.7
52.1
66.7
82.7
95.9
105.8

31.91
33.61
34.80
36.13
38.35
39.62
40.79

2.03
2.03
2.03
2.03
2.03
2.03
2.03

36.24
37.94
39.13
40.46
42.69
43.96
45.13

1390
1548
1742
1992
2263
2508
2719

0.537
0.426
0.338
0.268
0.227
0.189
0.162

0.3284
0.3199
0.3111
0.3023
0.2945
0.2875
0.2817

22170
20773
19366
18016
16810
15841
15047

1. DC resistance calculated based on a 17.241 ohm-mm2/km resistivity for cooper and 28.172 ohm-mm2/km for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 19.5 cm separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

MV-90 35 kV Single Aluminum conductor, 90C


100% Insulation Level, 100% Concentric Neutral
Standards: UL 1072. Medium Voltage Power Cables MV90, ICEA S-94-649
Standard for Concentric Neutral Cables Rated 5-46 kV.
SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
250
300
350

CONDUCTOR CROSS
INSULATION INSULATION
DIAMETER SECTION THICKNESS DIAMETER
(mm)
(sq inches)
(mm)
(mm)

336
376
423
475
520
570
616

0.0829
0.105
0.132
0.166
0.196
0.236
0.275

345
345
345
345
345
345
345

1062
1102
1149
1201
1256
1306
1352
Notes:

62

CONCENTRIC NEUTRAL
STRANDS
No.

26
20
25
32
25
29
32

JACKET
OVERALL APPROXIMATE DC RESISTANT INDUCTIVE CAPACITIVE
STRANDS CROSS DIAMETER THICKNESS DIAMETER
TOTAL
REACTANCE REACTANCE
AT 20C
DIAMETER SECTION
No.
(mm)
(mm)
WEIGHT
(ohm/km)
(ohm-km)
(ohm/km)
(mm) (sq inches)
(kg/km)

51
64
64
64
81
81
81

0.0528
0.0646
0.0808
0.103
0.128
0.149
0.164

1256
1323
1370
1422
1510
1560
1606

80
80
80
80
80
80
80

1427
1494
1541
1593
1681
1731
1777

934
1040
1170
1339
1521
1686
1827

0.164
0.130
0.103
0.0817
0.0691
0.0576
0.0494

0.5285
0.5148
0.5006
0.4864
0.4739
0.4627
0.4533

1. DC resistance calculated based on a 10.371 ohm-cmil/ft resistivity for cooper and 16.946 ohm-cmil/ft for aluminum.
2. Inductive and capacitive reactance at 60 Hz and a 7.5 inches separation between phases in flat configuration.
3. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

13776
12908
12034
11195
10446
9844
9350

Covered Cable
for Treed Zones 5 - 46 kV

Description
ACSR thermo set covered.

Contruction
Conductor
ACSR cable, compressed.
Conductor Shield
Cross linked polyethylene semiconductor.
Blocking against moisture
Conductor filled with blocking compounds against moisture.
Conductor shield
Cross linked polyethylene semiconductor (for voltages greater than 5 kV).
Covering
Cross linked polyethylene XLPE tracking resistant.
One single layer for 5 kV Cables.
Two layers, inner layer natural XLPE, and external layer black XLPE.
Options
AAC or AAAC conductors.

Characteristics
Operating Temperature
Normal continuous operation 90C for wet or dry locations.
Overload 130C.
Short circuit 250C.
Rated Voltage
5, 8, 15, 25 and 35 kV.

63

Applications
Distribution of electric energy in treed Areas or Industrial Zones.
This cable offers more reliability in operation because of outage
reduction by accidental contacts between phases, phase and ground.
Maintenance and cutting trees cost also are reduced. The external
cover is sunlight resistant, corrosive and contaminants agent resistant
and tracking resistant.

Standards
CENTELSAs 5-35 kV Covered conductors are manufactured in
accordance with the following standards:
ASTM B232, NTC-ICONTEC 309. Aluminum Conductor Steel
Reinforced.
ABNT EB-2173 Overhead cables XLPR covered for use in treed areas,
15 and 25 kV Voltages.
CENTELSAs specifications for covered cables from 5 to 46 kV.

Note: Configurations and sizes herein not specified are available


upon request.

64

Covered Cable for treed zones 5 kV 90C


(International Unit System)
Standards: ABNT 2173 AND CENTELSAS Specifications.

ACSR
CODE

SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
266.8
336.4
Notes:

SWAN
SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN

STRANDS
ALUMINUM

STEEL

6
6
6
6
6
6
6
18
18

1
1
1
1
1
1
1
1
1

CONDUCTOR
DIAMETER
(mm)

6.16
7.78
8.73
9.81
11.01
12.36
13.88
15.00
16.84

CROSS SECTION
ALUMINUM
(mm)

21.2
33.6
42.4
53.5
67.5
85.0
107.2
135.2
170.5

STEEL
(mm)

3.5
5.6
7.1
8.9
11.2
14.2
17.9
7.5
9.5

COVERING
THICKNESS
(mm)

2.16
2.16
2.16
2.16
2.16
2.16
2.16
2.16
2.16

OVERALL
DIAMETER
(mm)

10.60
12.22
13.17
14.25
15.45
16.80
18.32
19.44
21.28

APPROXIMATE
TOTAL
WEIGHT
(kg/km)

DC RESISTANT
AT 20C
(ohm/km)

151
218
264
321
392
480
589
598
737

1.32
0.829
0.658
0.521
0.414
0.328
0.260
0.211
0.167

APPROXIMATE
TOTAL
WEIGHT
(lb/1000ft)

DC RESISTANT
AT 20C
(ohm/1000ft)

102
147
178
216
263
322
396
402
495

0.402
0.253
0.201
0.159
0.126
0.100
0.079
0.064
0.051

1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 5 kV 90C


Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

4
2
1
1/0
2/0
3/0
4/0
266.8
336.4

SWAN
SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN

Notes:

STRANDS
ALUMINUM

STEEL

6
6
6
6
6
6
6
18
18

1
1
1
1
1
1
1
1
1

CONDUCTOR
DIAMETER
(mils)

243
306
344
386
433
487
546
591
663

CROSS SECTION
ALUMINUM
(sq inches)

0.0328
0.0521
0.0657
0.0830
0.105
0.132
0.210
0.264
0.312

STEEL
(sq inches)

0.00547
0.00870
0.0110
0.0138
0.0174
0.0220
0.0116
0.0147
0.0173

COVERING
THICKNESS
(mils)

85
85
85
85
85
85
85
85
85

OVERALL
DIAMETER
(mils)

417
481
519
561
608
661
721
765
838

1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

65

Covered Cable for treed zones 15 kV 90C


(International Unit System)
Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

4
2
1
1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

SWAN
SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

STRANDS
ALUMINUM

STEEL

6
6
6
6
6
6
6
18
18
18
18
18
18

1
1
1
1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
DIAMETER
(mm)
ALUMINUM
STEEL
(mm)
(mm)

6.16
7.78
8.73
9.81
11.01
12.36
13.88
15.00
16.84
18.31
20.05
21.66
23.16
Notes:

21.2
33.6
42.4
53.5
67.5
85.0
107.2
135.2
170.5
201.5
241.7
282.1
322.3

3.5
5.6
7.1
8.9
11.2
14.2
17.9
7.5
9.5
11.2
13.4
15.7
17.9

CONDUCTOR
SHIELD
THICKNESS
(mm)

1st LAYER
COVERING
THICKNESS
(mm)

0.34
0.34
0.34
0.34
0.34
0.34
0.34
0.45
0.45
0.45
0.45
0.57
0.57

1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91

2nd LAYER
COVERING
THICKNESS
(mm)

1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91
1.91

OVERALL
DIAMETER
(mm)

16.06
17.68
18.63
19.71
20.91
22.26
23.78
25.14
26.98
27.25
28.99
30.82
32.32

APPROXIMATE
TOTAL
WEIGHT
(kg/km)

243
318
369
431
506
600
716
750
898
965
1120
1286
1439

DC RESISTANT
AT 20C
(ohm/km)

1.32
0.829
0.658
0.521
0.414
0.328
0.260
0.211
0.167
0.141
0.118
0.101
0.088

1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 15 kV 90C


Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

4
2
1
1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

ACSR
CODE

SWAN
SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

STRANDS
ALUMINUM

STEEL

6
6
6
6
6
6
6
18
18
18
18
18
18

1
1
1
1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
CONDUCTOR
SHIELD
DIAMETER
THICKNESS
(mils)
ALUMINUM
STEEL
(mils)
(sq inches) (sq inches)

243
306
344
386
433
487
546
591
663
721
790
853
912
Notes:

66

0.0328
0.0521
0.0657
0.0830
0.105
0.132
0.210
0.264
0.312
0.375
0.437
0.166
0.500

0.00547
0.00870
0.0110
0.0138
0.0174
0.0220
0.0116
0.0147
0.0173
0.0208
0.0243
0.0277
0.0278

13
13
13
13
13
13
13
18
18
18
18
22
22

1st LAYER
COVERING
THICKNESS
(mils)

75
75
75
75
75
75
75
75
75
75
75
75
75

2nd LAYER
COVERING
THICKNESS
(mils)

75
75
75
75
75
75
75
75
75
75
75
75
75

OVERALL
DIAMETER
(mils)

APPROXIMATE
TOTAL
WEIGHT
(lb/1000 ft)

632
696
733
776
823
876
936
990
1062
1073
1142
1214
1272

164
214
248
290
340
403
481
504
603
648
753
864
967

DC RESISTANT
AT 20C
(ohm/1000 ft)

0.402
0.253
0.201
0.159
0.126
0.100
0.079
0.064
0.051
0.043
0.036
0.031
0.027

1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 25 kV 90C


(International Unit System)
Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

2
1
1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

Notes:

STRANDS
ALUMINUM

6
6
6
6
6
6
18
18
18
18
18
18

STEEL

1
1
1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
DIAMETER
(mm)
ALUMINUM
STEEL
(mm)
(mm)

7.78
8.73
9.81
11.01
12.36
13.88
15.00
16.84
18.31
20.05
21.66
23.16

33.6
42.4
53.5
67.5
85.0
107.2
135.2
170.5
201.5
241.7
282.1
322.3

5.6
7.1
8.9
11.2
14.2
17.9
7.5
9.5
11.2
13.4
15.7
17.9

CONDUCTOR
SHIELD
THICKNESS
(mm)

1st LAYER
COVERING
THICKNESS
(mm)

0.34
0.34
0.34
0.34
0.34
0.34
0.45
0.45
0.45
0.45
0.57
0.57

3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18

2nd LAYER
COVERING
THICKNESS
(mm)

3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18

OVERALL
DIAMETER
(mm)

APPROXIMATE
TOTAL
WEIGHT
(kg/km)

22.84
23.79
24.87
26.07
27.42
28.94
30.30
32.14
32.41
34.15
35.98
37.48

471
528
598
683
786
914
958
1119
1188
1357
1536
1700

OVERALL
DIAMETER
(mils)

APPROXIMATE
TOTAL
WEIGHT
(lb/1000 ft)

899
937
979
1026
1079
1139
1193
1266
1276
1345
1417
1476

316
355
402
459
528
614
644
752
799
912
1033
1143

DC RESISTANT
AT 20C
(ohm/km)

0.829
0.658
0.521
0.414
0.328
0.260
0.211
0.167
0.141
0.118
0.101
0.088

1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 25 kV 90C


Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

2
1
1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

SPARROW
ROBIN
RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

Notes:

STRANDS
ALUMINUM

6
6
6
6
6
6
18
18
18
18
18
18

STEEL

1
1
1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
CONDUCTOR
SHIELD
DIAMETER
THICKNESS
(mils)
ALUMINUM
STEEL
(mils)
(sq inches) (sq inches)

306
344
386
433
487
546
591
663
721
790
853
912

0.0521
0.0657
0.0830
0.105
0.132
0.210
0.264
0.312
0.375
0.437
0.166
0.500

0.00870
0.0110
0.0138
0.0174
0.0220
0.0116
0.0147
0.0173
0.0208
0.0243
0.0277
0.0278

13
13
13
13
13
13
18
18
18
18
22
22

1st LAYER
COVERING
THICKNESS
(mils)

125
125
125
125
125
125
125
125
125
125
125
125

2nd LAYER
COVERING
THICKNESS
(mils)

125
125
125
125
125
125
125
125
125
125
125
125

1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

67

DC RESISTANT
AT 20C
(ohm/1000 ft)

0.253
0.201
0.159
0.126
0.100
0.079
0.064
0.051
0.043
0.036
0.031
0.027

Covered Cable for treed zones 35 kV 90C


(International Unit System)
Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

STRANDS
ALUMINUM

6
6
6
6
18
18
18
18
18
18

STEEL

1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
DIAMETER
(mm)
ALUMINUM
STEEL
(mm)
(mm)

9.81
11.01
12.36
13.88
15.00
16.84
18.31
20.05
21.66
23.16
Notes:

53.5
67.5
85.0
107.2
135.2
170.5
201.5
241.7
282.1
322.3

8.9
11.2
14.2
17.9
7.5
9.5
11.2
13.4
15.7
17.9

CONDUCTOR
SHIELD
THICKNESS
(mm)

1st LAYER
COVERING
THICKNESS
(mm)

0.34
0.34
0.34
0.34
0.45
0.45
0.45
0.45
0.57
0.57

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

2nd LAYER
COVERING
THICKNESS
(mm)

3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18
3.18

OVERALL
DIAMETER
(mm)

APPROXIMATE
TOTAL
WEIGHT
(kg/km)

24.87
26.07
27.42
28.94
30.30
32.14
32.41
34.15
35.98
37.48

598
683
786
914
958
1119
1188
1357
1536
1700

DC RESISTANT
AT 20C
(ohm/km)

0.521
0.414
0.328
0.260
0.211
0.167
0.141
0.118
0.101
0.088

1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 35 kV 90C


Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

STRANDS
ALUMINUM

6
6
6
6
18
18
18
18
18
18

STEEL

CROSS SECTION
CONDUCTOR
CONDUCTOR
SHIELD
DIAMETER
THICKNESS
(mils)
ALUMINUM
STEEL
(mils)
(sq inches) (sq inches)

1
1
1
1
1
1
1
1
1
1

386
433
487
546
591
663
721
790
853
912
Notes:

68

0.0830
0.105
0.132
0.210
0.264
0.312
0.375
0.437
0.166
0.500

0.0138
0.0174
0.0220
0.0116
0.0147
0.0173
0.0208
0.0243
0.0277
0.0278

13
13
13
13
18
18
18
18
22
22

1st LAYER
COVERING
THICKNESS
(mils)

175
175
175
175
175
175
175
175
175
175

2nd LAYER
COVERING
THICKNESS
(mils)

125
125
125
125
125
125
125
125
125
125

OVERALL
DIAMETER
(mils)

APPROXIMATE
TOTAL
WEIGHT
(lb/1000 ft)

979
1026
1079
1139
1193
1266
1276
1345
1417
1476

402
459
528
614
644
752
799
912
1033
1143

DC RESISTANT
AT 20C
(ohm/1000 ft)

0.159
0.126
0.100
0.079
0.064
0.051
0.043
0.036
0.031
0.027

1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 46 kV 90C


(International Unit System)
Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

ACSR
CODE

1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636

RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

Notes:

STRANDS
ALUMINUM

STEEL

6
6
6
6
18
18
18
18
18
18

1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
DIAMETER
(mm)
ALUMINUM
STEEL
(mm)
(mm)

9.81
11.01
12.36
13.88
15.00
16.84
18.31
20.05
21.66
23.16

53.5
67.5
85.0
107.2
135.2
170.5
201.5
241.7
282.1
322.3

8.9
11.2
14.2
17.9
7.5
9.5
11.2
13.4
15.7
17.9

CONDUCTOR
SHIELD
THICKNESS
(mm)

1st LAYER
COVERING
THICKNESS
(mm)

2nd LAYER
COVERING
THICKNESS
(mm)

OVERALL
DIAMETER
(mm)

APPROXIMATE
TOTAL
WEIGHT
(kg/km)

DC RESISTANT
AT 20C
(ohm/km)

0.34
0.34
0.34
0.34
0.45
0.45
0.45
0.45
0.57
0.57

5.72
5.72
5.72
5.72
5.72
5.72
5.72
5.72
5.72
5.72

4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45
4.45

29.91
31.11
32.46
33.98
35.34
37.18
37.45
39.19
41.02
42.52

799
892
1006
1144
1198
1374
1444
1626
1819
1994

0.521
0.414
0.328
0.260
0.211
0.167
0.141
0.118
0.101
0.088

1. DC resistance calculated based on a 28,1721 ohm-mm2/km resistivity for aluminum and 191,57 ohm-mm2/km for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

Covered Cable for treed zones 46 kV 90C


Standards: ABNT 2173 AND CENTELSAS Specifications.

SIZE
AWG /
kcmil

1/0
2/0
3/0
4/0
266.8
336.4
397.5
477
556.5
636
Notes:

ACSR
CODE

RAVEN
QUAIL
PIGEON
PENGUIN
WAXWING
MERLIN
CHICADEE
PELICAN
OSPREY
KINGBIRD

STRANDS
ALUMINUM

STEEL

6
6
6
6
18
18
18
18
18
18

1
1
1
1
1
1
1
1
1
1

CROSS SECTION
CONDUCTOR
CONDUCTOR
SHIELD
DIAMETER
THICKNESS
(mils)
ALUMINUM
STEEL
(mils)
(sq inches) (sq inches)

386
433
487
546
591
663
721
790
853
912

0.0830
0.105
0.132
0.210
0.264
0.312
0.375
0.437
0.166
0.500

0.0138
0.0174
0.0220
0.0116
0.0147
0.0173
0.0208
0.0243
0.0277
0.0278

13
13
13
13
18
18
18
18
22
22

1st LAYER
COVERING
THICKNESS
(mils)

2nd LAYER
COVERING
THICKNESS
(mils)

OVERALL
DIAMETER
(mils)

APPROXIMATE
TOTAL
WEIGHT
(lb/1000 ft)

DC RESISTANT
AT 20C
(ohm/1000 ft)

225
225
225
225
225
225
225
225
225
225

175
175
175
175
175
175
175
175
175
175

1178
1225
1278
1338
1391
1464
1474
1543
1615
1674

537
600
676
769
805
923
971
1093
1222
1340

0.159
0.126
0.100
0.079
0.064
0.051
0.043
0.036
0.031
0.027

1. DC resistance calculated based on a 16.964 ohm-cmil/ft resistivity for aluminum and 115,23 ohm-cmil/ft for galvanized steel.
2. Data herein indicated are approximate and are subject to normal manufacturing tolerances.

69

Medium Voltage Cables Ampacity


Ampacity (Amperes)
Triplexed conductors
Air Installation.
40C Ambient Temperature.
90C and 105C Conductor Temperature.
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

CROSS
SECTION
(mm)

COPPER CONDUCTOR
2001 - 5000 Volts

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ALUMINUM CONDUCTOR

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90 C

105 C

90 C

105 C

90 C

105 C

90 C

105 C

65
90
120
160
185
215
250
290
335
375
465
580
750
880

74
99
130
175
205
240
275
320
375
415
515
645
835
980

100
130
170
195
225
260
300
345
380
470
580
730
850

110
140
195
225
255
295
340
390
430
525
650
820
950

50
70
90
125
145
170
195
225
265
295
365
460
600
715

57
77
100
135
160
185
215
250
290
325
405
510
665
800

75
100
130
150
175
200
230
270
300
370
460
590
700

84
110
150
175
200
230
265
305
335
415
515
660
780

1. NEC Table 310-67.


2. NEC Table 310-68.

Ampacity (Amperes)
Single conductors
Air Installation.
40C Ambient Temperature.
90C and 105C Conductor Temperature.
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

CROSS
SECTION
(mm)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

COPPER CONDUCTOR
2001 - 5000 Volts

5001 - 15000 Volts

ALUMINUM CONDUCTOR
5001 - 15000 Volts

15001 - 35000 Volts

90 C

105 C

90 C

105 C

90 C

105 C

90 C

105 C

90 C

105 C

90 C

105 C

83
110
145
190
225
260
300
345
400
445
550
695
900
1075

93
120
160
215
250
290
330
385
445
495
615
775
1000
1200

110
150
195
225
260
300
345
400
445
550
685
885
1060

125
165
215
250
290
335
385
445
495
610
765
990
1185

225
260
300
345
395
440
545
680
870
1040

250
290
330
380
445
490
605
755
970
1160

64
85
115
150
175
200
230
270
310
345
430
545
710
855

71
95
125
165
195
225
260
300
350
385
480
605
790
950

87
115
150
175
200
235
270
310
345
430
535
700
840

97
130
170
195
225
260
300
350
385
480
600
780
940

175
200
230
270
310
345
430
530
685
825

195
225
260
300
345
380
475
590
765
920

Notes:

70

1. NEC Table 310-69.


2. NEC Table 310-70.

15001 - 35000 Volts

2001 - 5000 Volts

Ampacity (Amperes)
Three conductors cable
Air Installation.
40C Ambient Temperature.
90C and 105C Conductor Temperature.
CROSS
SECTION
(mm)

SIZE
AWG /
kcmil

COPPER CONDUCTOR
2001 - 5000 Volts
90 C

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

59
79
105
140
160
185
215
250
285
320
395
485
615
705

ALUMINUM CONDUCTOR

5001 - 35000 Volts

105 C

90 C

66
88
115
154
180
205
240
280
320
355
440
545
685
790

93
120
165
185
215
245
285
325
360
435
535
670
770

2001 - 5000 Volts

5001 - 35000 Volts

105 C

90 C

105 C

90 C

105 C

105
135
185
210
240
275
315
360
400
490
600
745
860

46
61
81
110
125
145
170
195
225
250
310
385
495
585

51
68
90
120
140
160
185
215
250
280
345
430
550
650

72
95
125
145
170
190
220
255
280
345
425
540
635

80
105
145
165
185
215
245
285
315
385
475
600
705

1. NEC Table 310-71.


2. NEC Table 310-72.

Ampacity (Amperes)
Triplexed or three conductors cable
Installation in insulated duct at air.
40C Ambient Temperature.
90C and 105C Conductor Temperature.
SIZE
AWG /
kcmil

CROSS
SECTION
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

Notes:

COPPER CONDUCTOR
2001 - 5000 Volts

ALUMINUM CONDUCTOR

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90 C

105 C

90 C

105 C

90 C

105 C

90 C

105 C

55
75
97
130
155
180
205
240
280
315
385
475
600
690

61
84
110
145
175
200
225
270
305
355
430
530
665
770

83
110
150
170
195
225
260
295
330
395
480
585
675

93
120
165
190
215
255
290
330
365
440
535
655
755

43
58
76
100
120
140
160
190
215
250
305
380
490
580

48
65
85
115
135
155
175
210
240
280
340
425
545
645

65
84
115
130
150
175
200
230
255
310
385
485
565

72
94
130
150
170
200
225
260
290
350
430
540
640

1. NEC Table 310-73


2. NEC Table 310-74

71

Ampacity (Amperes)
Three conductors cable
Installation in insulated duct at air.
40C Ambient Temperature.
90C and 105C Conductor Temperature.
SIZE
AWG /
kcmil

CROSS
SECTION
(mm)

COPPER CONDUCTOR
2001 - 5000 Volts
90 C

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

72

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

52
69
91
125
140
165
190
220
255
280
350
425
525
590

1. NEC Table 310-75.


2. NEC Table 310-76.

105 C

58
77
100
135
155
185
210
245
285
315
390
475
585
660

ALUMINUM CONDUCTOR

5001 - 35000 Volts


90 C

83
105
145
165
195
220
250
290
315
385
470
570
650

2001 - 5000 Volts

5001 - 35000 Volts

105 C

90 C

105 C

90 C

105 C

92
120
165
185
215
245
280
320
350
430
525
635
725

41
53
71
96
110
130
150
170
200
220
275
340
430
505

46
59
79
105
125
145
165
190
225
245
305
380
480
560

64
84
115
130
150
170
195
225
250
305
380
470
550

71
94
125
145
170
190
220
255
280
340
425
520
615

Ampacity (Amperes)
Three single conductors
IInstallation in underground electrical ducts (Three conductors by each electrical duct).
20C Ambient Temperature (Earth).
100% Load Factor.
RHO 90.
90C and 105C Conductor Temperature.
COPPER CONDUCTOR
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

CROSS
SECTION
(mm)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 1


2001 - 5000 Volts

THREE CIRCUITS - FIGURE 2

5001 - 35000 Volts

2001 - 5000 Volts

SIX CIRCUITS - FIGURE 3

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

90C

105C

90C

105C

64
85
110
145
170
195
220
250
290
320
385
470
585
670

69
92
120
155
180
210
235
270
310
345
415
505
630
720

90
115
155
175
200
230
260
295
325
390
465
565
640

97
125
165
185
215
245
275
315
345
415
500
610
690

56
73
95
125
140
160
185
210
235
260
315
375
460
525

60
79
100
130
150
175
195
225
255
280
335
405
495
565

77
99
130
145
165
185
210
240
260
310
370
440
495

83
105
135
155
175
200
225
255
280
330
395
475
535

48
62
80
105
115
135
150
170
195
210
250
300
365
410

52
67
86
110
125
145
160
185
210
225
270
325
395
445

64
82
105
120
135
150
170
190
210
245
290
350
390

68
88
115
125
145
165
185
205
225
265
310
375
415

ALUMINUM CONDUCTOR
SIZE
AWG /
kcmil

CROSS
SECTION
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 1


2001 - 5000 Volts
90C

Notes:

50
66
86
115
130
150
170
195
225
250
305
370
470
545

105C

54
71
93
125
140
160
185
210
245
270
325
400
505
590

THREE CIRCUITS - FIGURE 2

5001 - 35000 Volts


90C

70
91
120
135
155
175
200
230
250
305
370
455
525

105C

75
98
130
145
165
190
215
245
270
330
400
490
565

2001 - 5000 Volts


90C

44
57
74
96
110
125
145
160
185
205
245
295
370
425

105C

47
61
80
105
120
135
155
175
200
220
265
320
395
460

SIX CIRCUITS - FIGURE 3

5001 - 35000 Volts


90C

60
77
100
110
125
145
165
185
200
245
290
355
405

105C

65
83
105
120
140
155
175
200
220
260
315
385
440

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

38
48
62
80
91
105
115
135
150
165
195
240
290
335

41
52
67
86
98
110
125
145
165
180
210
255
315
360

50
64
80
90
105
115
130
150
165
195
230
280
320

54
69
88
99
110
125
145
160
175
210
250
305
345

1. NEC Table 310-77.


2. NEC Table 310-78.

73

Ampacity (Amperes)
Three conductors cable
Installation in underground electrical ducts (One conductor by each
electrical duct).
20C Ambient Temperature (Earth).
100% Load Factor.
RHO 90.
90C and 105C Conductor Temperature.
COPPER CONDUCTOR
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

CROSS
SECTION
(mm)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 1


2001 - 5000 Volts

THREE CIRCUITS - FIGURE 2

5001 - 35000 Volts

2001 - 5000 Volts

SIX CIRCUITS - FIGURE 3

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

59
78
100
135
155
175
200
230
265
290
355
430
530
600

64
84
110
145
165
190
220
250
285
315
380
460
570
645

88
115
150
170
195
220
250
285
310
375
450
545
615

95
125
160
185
210
235
270
305
335
400
485
585
660

53
69
89
115
135
150
170
195
225
245
295
355
430
485

57
74
96
125
145
165
185
210
240
265
315
380
465
520

75
97
125
140
160
185
205
230
255
305
360
430
485

81
105
135
155
175
195
220
250
270
325
385
465
515

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

46
60
77
98
110
125
145
165
185
200
240
290
350
390

50
65
83
105
120
135
155
175
200
220
270
310
375
420

63
81
105
115
130
150
170
190
205
245
290
340
380

68
87
110
125
145
160
180
200
220
275
305
365
405

ALUMINUM CONDUCTOR
SIZE
AWG /
kcmil

CROSS
SECTION
(mm)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 1


2001 - 5000 Volts

THREE CIRCUITS - FIGURE 2

5001 - 35000 Volts

2001 - 5000 Volts

SIX CIRCUITS - FIGURE 3

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

90C

105C

90C

105C

46
61
80
105
120
140
160
180
205
230
280
340
425
495

50
66
86
110
130
150
170
195
220
245
310
365
460
535

69
89
115
135
150
170
195
220
245
295
355
440
510

74
96
125
145
165
185
210
240
265
315
385
475
545

41
54
70
90
105
120
135
155
175
190
230
280
345
400

44
58
75
97
110
125
145
165
185
205
250
300
375
430

59
75
100
110
125
140
160
180
200
240
285
350
400

64
81
105
120
135
155
175
195
215
255
305
375
430

36
46
60
77
87
99
110
130
145
160
190
230
280
320

39
50
65
83
94
105
120
140
155
170
205
245
305
345

49
63
80
90
105
115
130
150
160
190
230
275
315

53
68
86
98
110
125
140
160
170
205
245
295
335

Notes:

74

1. NEC Table 310-79.


2. NEC Table 310-80.

Ampacity (Amperes)
Single conductor
Installation in direct buried.
20C Ambient Temperature (Earth).
100% Load Factor.
RHO 90.
90C and 105C Conductor Temperature.
COPPER CONDUCTOR
SIZE
AWG /
kcmil

CROSS
SECTION
(mm2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT, THREE CONDUCTORS - FIGURE 4


2001 - 5000 Volts

5001 - 35000 Volts

TWO CIRCUITS, SIX CONDUCTORS - FIGURE 5


2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

110
140
180
230
260
295
335
385
435
470
570
690
845
980

115
150
195
250
280
320
365
415
465
510
615
745
910
1055

130
170
210
240
275
310
355
405
440
535
650
805
930

140
180
225
260
295
335
380
435
475
575
700
865
1005

100
130
165
215
240
275
310
355
400
435
520
630
775
890

110
140
180
230
260
295
335
380
430
470
560
680
835
960

120
160
195
225
255
290
330
375
410
495
600
740
855

130
170
210
240
275
315
355
405
440
530
645
795
920

ALUMINUM CONDUCTOR
SIZE
AWG /
kcmil

CROSS
SECTION
(mm2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT, THREE CONDUCTORS - FIGURE 4


2001 - 5000 Volts
90C

105C

85
110
140
180
205
230
265
300
340
370
445
540
665
780

90
115
150
195
220
250
285
320
365
395
480
580
720
840

5001 - 35000 Volts


90C

100
130
165
185
215
245
275
315
345
415
510
635
740

TWO CIRCUITS, SIX CONDUCTORS - FIGURE 5


2001 - 5000 Volts

5001 - 35000 Volts

105C

90C

105C

90C

105C

110
140
175
200
230
260
295
340
370
450
545
680
795

80
100
130
165
190
215
245
275
310
340
410
495
610
710

85
110
140
180
200
230
260
295
335
365
440
530
655
765

95
125
155
175
200
225
255
290
320
385
470
580
680

100
130
165
190
215
245
275
315
345
415
505
625
730

1. NEC Table 310-81.


2. NEC Table 310-82.

75

Ampacity (Amperes)
Three conductor cable
Installation in direct buried.
20C Ambient Temperature (Earth).
100% Load Factor.
RHO 90.
90C and 105C Conductor Temperature.
COPPER CONDUCTOR
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

CROSS
SECTION
(mm2)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 6


2001 - 5000 Volts

TWO CIRCUITS - FIGURE 7

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

85
105
135
180
200
230
260
295
335
365
440
530
650
730

89
115
150
190
215
245
280
320
360
395
475
570
700
785

115
145
185
210
240
270
305
350
380
460
550
665
750

120
155
200
225
255
290
330
375
410
495
590
720
810

80
100
130
165
185
215
240
275
310
340
410
490
595
665

84
105
140
180
200
230
260
295
335
365
440
525
640
715

105
135
170
195
220
250
280
320
350
420
500
605
675

115
145
185
210
235
270
305
345
375
450
535
650
730

ALUMINUM CONDUCTOR
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

76

CROSS
SECTION
(mm2)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT - FIGURE 6


2001 - 5000 Volts

TWO CIRCUITS - FIGURE 7

5001 - 35000 Volts

2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

65
80
105
140
155
180
205
230
260
285
345
420
520
600

70
88
115
150
170
190
220
250
280
310
375
450
560
650

90
115
145
165
185
210
240
270
300
360
435
540
620

95
125
155
175
200
225
260
295
320
390
470
580
665

60
75
100
130
145
165
190
215
245
265
320
385
480
550

66
83
110
140
155
180
205
230
260
285
345
415
515
590

80
105
135
150
170
195
220
250
275
330
395
485
560

95
115
145
165
185
210
240
270
295
355
425
525
600

1. NEC Table 310-83.


2. NEC Table 310-84.

Ampacity (Amperes)
Triplexed conductors
Installation in direct buried.
20C Ambient Temperature (Earth).
100% Load Factor.
RHO 90.
90C and 105C Conductor Temperature.
COPPER CONDUCTOR
SIZE
AWG /
kcmil

CROSS
SECTION
(mm2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT, THREE CONDUCTORS - FIGURE 8


2001 - 5000 Volts

5001 - 35000 Volts

TWO CIRCUITS , SIX CONDUCTORS- FIGURE 9


2001 - 5000 Volts

90C

105C

90C

105C

90C

105C

90
120
150
195
225
255
290
330
375
410
490
590
725
825

95
130
165
205
240
270
310
360
405
445
580
635
780
885

115
150
190
215
245
275
315
360
390
470
565
685
770

120
160
205
230
260
295
340
385
410
505
605
740
830

85
110
140
180
205
235
265
300
340
370
445
535
650
740

90
115
150
195
220
250
285
320
365
395
480
575
700
795

5001 - 35000 Volts


90C

105
140
175
200
225
255
290
325
355
425
510
615
690

105C

115
150
190
215
240
275
315
350
380
455
545
660
745

ALUMINUM CONDUCTOR
SIZE
AWG /
kcmil

8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
750
1000
Notes:

CROSS
SECTION
(mm2)

8.36
13.3
21.1
33.6
42.2
53.5
67.4
85.0
107
127
177
253
380
507

ONE CIRCUIT, THREE CONDUCTORS - FIGURE 8


2001 - 5000 Volts

5001 - 35000 Volts

TWO CIRCUITS , SIX CONDUCTORS- FIGURE 9


2001 - 5000 Volts

5001 - 35000 Volts

90C

105C

90C

105C

90C

105C

90C

105C

70
90
120
155
175
200
225
255
290
320
385
465
580
670

75
100
130
165
190
210
240
275
310
350
420
500
625
725

90
115
145
165
190
215
245
280
305
370
445
550
635

95
125
155
175
205
230
265
305
325
400
480
590
680

65
85
110
140
160
180
205
235
265
290
350
420
520
600

70
95
120
150
170
195
220
250
285
310
375
455
560
645

85
105
135
155
175
200
225
255
280
335
405
485
565

90
115
145
170
190
215
245
275
300
360
435
525
605

1. NEC Table 310-85.


2. NEC Table 310-86.

77

Installations Considered in Ampacities Tables

7.5

FIGURE 1
Electrical duck bank, one electrical duct

7.5

7.5

FIGURE 2
Electrical duck bank (27x11.5),
three electrical ducts

Electrical duck bank (27x27),


three electrical ducts

7.5
7.5
7.5

7.5

7.5

7.5
FIGURE 3
Electrical duck bank (19x27),
three electrical ducts

78

Electrical duck bank (27x19),


three electrical ducts

7.5

7.5

FIGURE 4
Buried single-conductor cables, one circuit

7.5

7.5

24

7.5

7.5

FIGURE 5
Buried single-conductor cables, two circuits

24
FIGURE 6
Buried Three-conductor cable

FIGURE 7
Buried Three-conductor cables

24
FIGURE 8
Buried Triplexed cables, one circuit

FIGURE 9
Buried Triplexed cables, two circuits

Relleno (tierra u hormign)

Conducto elctrico

Tierra

Cable o cables

79

Ampacities at Ambient temperature


different from the tables

Ampacities at Ambient temperature different from the Tables can be calculated


by:

I2 = I1

TC - TA2 - TD
TC - TA1 - TD

Where:
I1 = Ampacity at Temperature Ambient TA1 (From Tables).
I2 = Ampacity at Temperature Ambient TA2 (To be calculated).
TC = Conductor temperature (C).
TA1 = Temperature Ambient from Tables.
TA2 = Different Temperature Ambient.
TD = Dielectric loss temperature rise.

80

Short Circuit Currents for MV Cables


Maximum acceptable short circuit current for MV Cables can be calculated by:

I=Ak

log

T2 +
T1 +
t

Where:
I = Ampacity at Temperature Ambient TA1 (From Tables).
A = Conductor Section in mm.
K = 341 for copper, 224 for aluminum.
T1 = Maximum Operation Temperature (90C for conductor and 85C for jacket).
T2 = Maximum Acceptable Short Circuit Temperature (250C for conductor and 200C
for shield).
= 234 for copper, 228 for aluminum.
t = Short circuit duration in seconds.

81

Short Circuit Currents for Copper Conductor

1000
900
800
700
600

1 cycle (1/60 sec)

500
400

2 cycles (1/30 sec)

300

4 cycles (1/15 sec)

200

8 cycles (2/15 sec)


16 cycles (4/15 sec)
30 cycles (1/2 sec)

100
90
80

60 cycles (1 sec)

CURRENT (kA)

70
60

100 cycles (5/3 sec)

50
40
30

20

10
9
8
7
6
5
4
3

1
10

20

30

40

50

60

70 80 90

100

150

200

250 300 350 400

CONDUCTOR SECTION (mm2)

82

500 600

800

1000

Short Circuit Currents for Aluminum Conductor

1000
900
800
700
600
500
400

1 cycle (1/60 sec)

300

2 cycles (1/30 sec)


200

4 cycles (1/15 sec)


8 cycles (2/15 sec)

100

16 cycles (4/15 sec)

90

CURRENT (kA)

80
70

30 cycles (1/2 sec)

60
50

60 cycles (1 sec)

40

100 cycles (5/3 sec)

30

20

10
9
8
7
6
5
4
3

1
10

20

30

40

50

60

70 80 90

100

150

200

250 300 350 400

500 600

800

1000

CONDUCTOR SECTION (mm2)

83

Short Circuit Currents for Copper Shields

100.0
90
80
70
60
50
40

30

20

10.0
9

CURRENT (kA)

8
7
6
5

1 cycle (1/60 sec)

2 cycles (1/30 sec)


3

4 cycles (1/15 sec)


2

8 cycles (2/15 sec)


16 cycles (4/15 sec)
1.0

30 cycles (1/2 sec)

0.9
0.8
0.7

60 cycles (1 sec)

0.6
0.5

100 cycles (5/3 sec)

0.4
0.3

0.2

0.1
1

8 9

10

15

20

25

CONDUCTOR SECTION (mm2)

84

30 35 40

50

60 70 80 90

100

Medium Voltage Cables Designs


Single Conductors, Copper Tape Shield.

Soft copper or aluminum 1350 H19 compacted conductor


XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
Metallic Shield. Copper tape
Flame retardant polyvinyl chloride PVC Jacket

Single Conductors, Copper Wires Shield.

Soft copper or aluminum 1350 H19 Compacted Conductor


XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
Metallic Shield. Copper Wires
Flame retardant polyvinyl chloride PVC Jacket

85

Three Conductors, Copper Tape Shield.

Soft copper or aluminum


1350 - H19 compacted conductor
XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
Metallic Shield. Copper tape
Flame retardant polyvinyl chloride PVC Filler
Flame retardant polyvinyl chloride PVC Jacket

Triplexed Conductors, Copper Tape Shield.

Soft copper or aluminum


1350 - H19 compacted conductor
XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
Metallic Shield. Copper tape
Flame retardant polyvinyl chloride PVC Jacket

86

Single Conductors, 33% Concentric Neutral

Soft copper or aluminum


1350 - H19 compacted conductor
XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
33% Concentric neutral, copper wires
Flame retardant polyvinyl chloride PVC jacket

Single Conductors, 100% Concentric Neutral

Soft copper or aluminum


1350 - H19 compacted conductor
XLPE Conductor shield
XLPE Insulation
XLPE Insulation shield
100% Concentric neutral, copper wires
Flame retardant polyvinyl chloride PVC jacket

87

Cables for Treed Areas

Compressed ACSR
Blocking Compound against moisture
Blocking Tape against moisture
XLPE Conductor shield
XLPE covering, inner layer
XLPE Track resistant covering, outer layer

88

You might also like