Design Calculation Sheet

Project no.:
Subject:

S0514
ACC Design Criteria

Date:

23-Mar-05

1.1) Climatic conditions


Outside temperature

42 C
22.2C
15C

Daily temp range

12C

Summer DB
Summer WB
Winter DB

1.2) Indoor temperature condition


Area

Summer

All spaces
Toilets
Stores
Mechanical room

DB C
22
22
22
27

Winter
DB C
% RH
22
50
22
22
-

% RH
50
50
50
-

1.3) External load


External Walls
Partition Walls
Flooring/Ceiling Partition
Roof
Glazing
U value
SC

U=
U=
U=
U=
=
=

2.6
0.37

1.4) Internal load


i) People number criteria
Space
Exams
Reception
Office
Corridor

People Criteria
4 people
7 m/person
6.5 m/person
2.7 m/person

Activity level
office work
office work
office work
office work

ii) Internal heat dissipation


S.N.
1
2
3
4
5
6
7
8

Room Function
Exam Room
Dialysis Room
X-ray Room
Office
Treatment Room
Nurse Station
Waiting Area
Electrical Spaces

W or W/m2
100 W
8.33 W/m2
500 W
300 W
60 W/m2
300 W
150 W
1500 W

0.317
1.8
1.5
0.345
W/m^2/K
W/m^2/K

W/m^2/K
W/m^2/K
W/m^2/K
W/m^2/K

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
ACC Design Criteria

Date:

iii) Lighting load


S.N.
1
2
3
4
5
6
7
8
9

Room Function
Exam Room
Dialysis Room
X-ray Room
Office
Corridor & Lobby
Treatment Room
Nurse Station
Waiting Area
Electrical Spaces

W/m2
30
75
20
30
15
30
30
15
20

iv) Partitions
Unconditioned temperature for partitions is 30C
1.4) Fresh air
Ventilation

Min Total Air

Min Air Changes


of

Changes Per Hour

Fresh Air

X - ray treatment room

Treatment room

Pharmacy

Exam room

Offices

10 l/s/person

Corridors

Dark room

10

Food preparation center

10

Lobby

10 l/s/person

Toilets

10

10*

Waiting room / lounges

10 l/s/person

Equipment storage

Lockers

2.5 L/s/m2

Janitors

10

Nurse station

Utilities

10

10*

Reception

Coffee shop

Prayer area

10 l/s/person

Space

Ablution

10

10*

Stores

0.75 L/s/m2

Film reading (radiology)

Daylight processing (radio)

Dispensing (pharmacy)

Pantry

10

2*

Drug stores

(*) Sign indicates rooms with 100% exhaust

23-Mar-05

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
ACC Design Criteria

Date:

Air Pressure and Air Circulation Condition

Exhausted to
outdoor

Space

Pressure Relation

X - ray treatment room

Treatment room

Pharmacy

Exam room

Offices

Corridors

Dark room

Food preparation center

Lobby

Toilets

Waiting room

Equipment storage

Lockers

Janitors

Nurse station

Soiled Utilities

Reception

Coffee shop

Prayer area

Ablution

Lounge

Stores

P/N

Film reading (radiology)

Daylight processing (radio)

Dispensing (pharmacy)

Pantry

Drug stores

P = Positive

N = Negative

= Continuous directional control not required

Air Recirculated

*
*
*
*
*

*
*
*

E = Equal

23-Mar-05

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
Oncology Design Criteria

Date:

23-Mar-05

1.1) Climatic conditions


Outside temperature

42 C
22.2C
15C

Daily temp range

12C

Summer DB
Summer WB
Winter DB

1.2) Indoor temperature condition


Area

Summer
DB C
22
22
22
27

All spaces
Toilets
Stores
Mechanical
room

Winter
DB C
% RH
22
50
22
22
-

% RH
50
50
50
-

1.3) External load


External Walls
Partition Walls
Flooring/Ceiling Partition
Roof
Glazing
U value
=
SC
=

U=
U=
U=
U=
2.6
0.37

W/m^2/K
W/m^2/K

1.4) Internal load


i) People number criteria
Space
Patients room
Waiting
Corridor

People Criteria
3 people
20 people
9 m/person

Activity level
office work
office work
office work

ii) Internal heat dissipation


S.N.

Room Function

Treatment Room

Office

Waiting areas

Electrical Spaces

W or W/m2
60 W/m
200 W
200 W
1000 W

S.N.

Room Function

W/m2

Patient Room

15

Treatment Room

30

Office

30

Corridor & Lobby

15

Electrical Spaces

20

iii) Lighting load

iv) Partitions

0.317
1.8
1.5
0.441

W/m^2/K
W/m^2/K
W/m^2/K
W/m^2/K

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
Oncology Design Criteria

Date:

23-Mar-05

Unconditioned temperature for partitions is 30C


1.4) Fresh air
Ventilation
Space

Min Total Air


Changes Per Hour
6
4
2
10
6
2
10
4
10
4
10
10

Patient room
Pharmacy
Offices
Corridors
Lobby
Toilets
Waiting room / lounges
Equipment storage
Lockers
Janitors
Nurse station
Utilities
Reception
Prayer area
Ablution
Stores
Pantry

Min Air Changes of


Fresh Air
2
2
10 LPS/person
2
10 LPS/person
10*
10 LPS/person
*
2.5 L/s/m2
*
2
10*
2
10 LPS/person
10*
0.75 L/s/m2
2

(*) Sign indicates rooms with 100% exhaust


Air Pressure and Air Circulation Condition

Space

Pressure Relation

Air Recirculated

Patient room

Patient
isolation room
Pharmacy
Offices
Corridors
Lobby
Toilets
Waiting room
Equipment
storage
Lockers
Janitors

Nurse station
Soiled Utilities

E
N

Reception
Prayer area

E
E

*
*

N
E
P/N
N

*
*

Ablution
Lounge
Stores
Pantry
P = Positive

E
E
N
E

*
*
*
*
*
*
*

N
N

N = Negative

Exhausted to
outdoor

*
*
*

E = Equal

= Continuous directional control not required

*
*

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
Laboratory Design Criteria

Date:

23-Mar-05

1.1) Climatic conditions


Outside temperature

43.9 C
17.8C
15C

Daily temp range

14 K

Summer DB
Summer WB
Winter DB

1.2) Indoor temperature condition


Area

Summer
DB C
22
22
22
27

All spaces
Toilets
Stores
Mechanical room

Winter
% RH
50
50
50
-

DB C
22
22
22
-

% RH
50
-

1.3) External load


External Walls
Partition Walls
Flooring/Ceiling Partition
Roof
Glazing

U=
U=
U=
U=
U value =
SC =

1.4) Internal load


i) People number criteria
Space
Patients room
Waiting
Corridor

People Criteria
3 people
20 people
9 m/person

Activity level
office work
office work
office work

ii) Internal heat dissipation


S.N.

Room Function

Watts

Biochemistry & Clinical research

2000

Specimen Preparation

300

Glass Wash

500

Office

250

Multi-purpose Room

500

Electrical Spaces

1000

S.N.

Room Function

W/m2

Biochemistry & Clinical research

30

Specimen Preparation

50

Glass Wash

45

Office

30

Corridor & Lobby

15

Multi-purpose Room

20

Electrical Spaces

20

iii) Lighting load

iv) Partitions
Unconditioned temperature for partitions is 30C

0.317
1.8
1.5
0.441

W/m^2/K
W/m^2/K
W/m^2/K
W/m^2/K
2.6 W/m^2/K
0.37 W/m^2/K

Sheet No.:

Computed by:
Checked by:
Approved by:

Design Calculation Sheet


Project no.:
Subject:

S0514
Laboratory Design Criteria

Date:

23-Mar-05

1.4) Fresh air


Ventilation
Space
Research room
Multipurpose room
Laboratory general
Animal House
Washing disinfection
Incubator
Specimen preparation
Electron Microscope
PCR
Offices
Corridors
Lobby
Toilets
Waiting room / lounges
Equipment storage
Lockers
Janitors
Utilities
Reception
Prayer area
Ablution
Stores
Pantry
Glass Washing

Min Total Air


Changes Per Hour
6
6
6
6
6
6
6
6
6
2
10
6
2
10
10
4
10
10
10

Min Air Changes of


Fresh Air
10 LPS/person
2
10 LPS/person
10*
10 LPS/person
*
2.5 L/s/m2
*
10*
2
10 LPS/person
10*
0.75 L/s/m2
2
-

(*) Sign indicates rooms with 100% exhaust


Air Pressure and Air Circulation Condition
Space

Pressure Relation

Research room

Multipurpose room

Laboratory general

Animal House

Washing disinfection

Incubator

Specimen preparation

Electron Microscope

PCR

Offices

Corridors

Lobby

Toilets

Waiting room

Equipment storage

Lockers

Janitors

Soiled Utilities

Reception

Prayer area

Ablution

Lounge

Stores

P/N

Pantry

P = Positive

N = Negative

= Continuous directional control not required

Air Recirculated

Exhausted to outdoor

*
*

*
*
*
E = Equal

Sheet No.:

Computed by:
Checked by:
Approved by: