FOREWORD
This Indian Standard (Part 2) was adopted by the Bureau of Indian Standards on 22 August 1989,
after the draft finalized by the Hydroelectric Power House Structures Sectional Committee had
been approved by the River Valley Division Council.
Pumped storage is a system wherein economical electrical energy, usually available at night or on
weekend days, is used to pump water from a lower to a higher elevation. In that process, electrical
energy from the system is converted to potential energy in the form of stored water. As and when
needed, water is released from storage through hydraulic turbines to generate high value
electrical energy during periods of maximum demand, usually during day time.
In fact all the reaction turbines may be used for reversible pumping and generating mode,
however, in most of the cases Francis type units find application. The reversible Francis type
pump turbine is essentially a centrifugal pump, which with certain modifications, performs as a
turbine when operating in the opposite direction. The conventional Francis turbine runner with its
large number and too short length of blades is not well adopted due to cavitation consideration
when operating in the reverse direction as a pump.
In the reversible turbines head variation should be limited and kept between 110 percent to 80
percent of rated head for smooth operation.
This edition 1.1 incorporates Amendment No. 1 (July 1993). Side bar indicates modification of the
text as the result of incorporation of the amendment.
For the purpose of deciding whether a particular requirement of this standard is complied with,
the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded
off in accordance with IS 2 : 1960 Rules for rounding off numerical values ( revised ). The number
of significant places retained in the rounded off value should be the same as that of the specified
value in this standard.
Indian Standard
1 SCOPE
2 REFERENCES
2.1 The following Indian Standards
necessary adjuncts to this standard:
IS No.
are
Title
IS 4410
Glossary of terms relating to
(Part 10) : 1987 river valley projects: Part 10
Hydro-electric power station
including water conductor
system ( first revision )
IS 7418 : 1974
IS 4461 : 1976
3 TERMINOLOGY
3.0 For the purpose of this standard the
definitions given in IS 4410 (Part 10) : 1987 and
IS 7418 : 1974 and following shall apply.
4.1 Speed
As the rated generating capacity is the most
significant requirement, the speed of rotation is
selected on the basis of rated output during
turbining. The statistical relationship between
head and turbine specific speed is given in
Fig. 1. Corresponding to rated head, the
turbine specific speed is obtained and speed of
rotation is calculated by the following equation:
n P t 1.358
nst = -----------------------------------54
Ht
where
nst = specific speed of pump turbine when
operating in turbining mode,
n = rated speed in revolutions/minute,
Pt = turbine output in kW, and
Ht = rated head acting in metres.
FIG. 1
FIG. 2
Qp
nsp = n
----------------3
Hp 4
where
where
Hs = suction height below minimum tail
water level in metres
Hb = barometric pressure =
elevation of power station in
metres of water column
10.3
900
HV = vapour pressure = 0.4 m from mean
sea water level at 30C and
2
may
be
4.4 Runner
60
Dg = -----
V
-----rn
where
Vr = max peripheral rotor velocity, and
n = rated speed of machine.
3
FIG. 7
FIG. 9
Do = Dg 1 + -------
2P
where
P = number of pair of poles.
W
--------------------Lc = K D g 2 n
o
where
W = rated kVA, and
Ko = output coefficient
Fig. 13).
= Dg 1 + ------- + 1.2 m
2P
6
(obtained
from
FIG. 12
where
Kb = 0.65 for a load of 50 t/arm of the
bracket,
= 0.75 for a load of less than 100 t/arm
and more than 50 t/arm of the bracket,
and
FIG. 14
d) Provision
of
width
equipments in the floors.
for
auxiliary
ANNEX A
( Clause 6.4.3.2 )
TYPICAL EXAMPLE FOR CALCULATING THE OVERALL
DIMENSIONS OF POWER HOUSE
A-1 DATA
Unit Capacity
:
100 MW
Maximum Head (Turbine):
105 m
Rated Head
:
100 m
Minimum Head
:
75 m
Maximum Pumping Head :
110 m
Rated Pumping Head
:
105 m
Minimum Pumping Head :
80 m
Generator Capacity
: 111 111 kVa
Power Factor : 09
Pump output
105
5 percent margin over Pmax = ---------- 130.741 MW
100
Capacity of motor generator = 137.279 MW
Pumping turbine setting
Hs = Hb Hp Hv
from graph (Fig. 4) for nsp 54 = 0.26
Hb = Barometric pressure at power house
level taken 10 m
HV = Vapour pressure at power house level
taken 0.4 m
Hs = 10 0.26 105 0.4
= 10 27.3 0.4 = 17.7 metres
5/4
190 100
n = -----------------------------------------------100 000 1.358
= 163 rev/min (Nearest synchronous
speed 157.9, 166.7) taking 166.7
rev/min
Rated pump discharge
n sp H p3/4
Qp = ----------------------------n
54 105 3/4
= ----------------------------= 10.625
166.7
Qp = 112.90 m3/sec
12
Do = Dg 1 + -------
2F
60 2 9.81 105
D1 = ------------------------------------------------------ 1.07 m
3.14 166.7
= 5.564 = 5.6 m
Dimension of spiral case
recommended velocity (refer Fig. 7)
at 105 metres
= 10 m/sec.
3.141 59
= 7.9 1 + ----------------------- = 8.589 4
2 18
= 8.6 m
iv) Stator frame diameter =
Df = Do + 1.2 m
= 8.6 + 1.2 = 9.8 m
112.9 4
-----------------------10 n
= 3 791 mm
Assume = 3 800 mm
A = 3 800 mm
Inlet diameter D =
Generator parameters
60 50
i) Pair of poles P = -----------------166.7
= 18
axial load
60 V r
ii) Air gap diameter Dg = ------ -----
n
= 352+428+60
= 840 tonnes
60
69
= ----------------------- --------------3.141 59 166.7
13
Standard Mark
The use of the Standard Mark is governed by the provisions of the Bureau of Indian
Standards Act, 1986 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been produced
to comply with the requirements of that standard under a well defined system of inspection,
testing and quality control which is devised and supervised by BIS and operated by the
producer. Standard marked products are also continuously checked by BIS for conformity to
that standard as a further safeguard. Details of conditions under which a licence for the use of
the Standard Mark may be granted to manufacturers or producers may be obtained from the
Bureau of Indian Standards.
Date of Issue
Amd. No. 1
July 1993
Telegrams: Manaksanstha
(Common to all offices)
Regional Offices:
Central
Eastern
Telephone
323 76 17
323 38 41
60
38 43
20 25
Branches : A H M E D A B A D . B A N G A L O R E . B H O P A L . B H U B A N E S H W A R . C O I M B A T O R E .
FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR.
LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISHAKHAPATNAM.