Professional Documents
Culture Documents
Synopsis
The presence of remanent flux in current-transformer cores can affect the behaviour of associated protective
schemes and metering equipment.
At the instant of interruption of a system fault, the core flux density in current transformers carrying
the fault current may be very high, perhaps even at saturation level, and remanent flux densities up to the
maximum possible for the particular core material may be left. The paj>,er considers the subsequent operation of such transformers, and it is shown that some residual flux may remain in a core indefinitely, since
the passage of normal load current may not bring about complete demagnetisation.
It is concluded that the large flux variations, which are normally present in the cores of metering
transformers, will cause such large amounts of any residual flux present to be eliminated that the accuracy
will only be affected to a negligible degree. In protective current transformers, however, where the normal
flux variations are small, any residual-flux reduction will tend to be small, and protective schemes must
be designed to allow for any effects which remanent flux may cause.
1
Introduction
Paper 4984 J, first received 28th July and in final form 20th December
196S
Mr. Bruce and Dr. Wright are with the Department of Electrical and
Electronic Engineering, University of Nottingham, Nottingham,
England
magnetising
force H
Fig. 1
Hysteresis loop of core material
time
Fig. 2
71
magnetising
force
H
Fig. 3
S 0-4
Experimental study
0-2
04
06
peak value of alternating flux density, Wb/m2
(0
1-6
0-8
03
0-6
0-9
peak value of alternating flux density,Wb/m2
(ii)
0-4
0-2
0-4
peak value of alternating flux density, Wb/m2
Fig. 4
0-6
(iii)
917
The shapes of these graphs are dependent on the magnetisation characteristics and hysteresis loops of the particular
materials considered. In each case, relatively largefluxdensities
are required to remove all the residual magnetism present.
Metering current transformers usually operate at large
flux densities, and a large proportion of any residual magnetism
left in them will be removed. The effect on their accuracy
will normally be negligible. To demonstrate this, a Mumetalcored current transformer was tested while operating with a
peak alternating flux density of 0-3Wb/m2, first, after the
core had been demagnetised, and then with a residual magnetism of 0-33Wb/m2. It was found that, in the latter case,
the exciting current was only of the ord* of 3 % greater than
that required under normal conditions. Taking as an example
a metering current transformer of class AM, which has a
maximum ratio error limit of 1 0 % , and a phase error
limit of 30', a 3 % increase in exciting current on such a
transformer operating at these limits would cause a change
in the respective errors of approximately 0 03% and 0-9'.
The flux variation in protective current transformers may
be very small during normal load conditions, and, consequently, a considerable amount of residual flux may remain
in them. This flux will only become significant when the
associated protective equipment is required to deal with the
next power-system fault. If this next fault is within the protected zone, the effect of the residual flux on the protectiveequipment fault setting will be the factor which is of interest.
The magnitude of this effect will depend on the type of
protective equipment in use. To give an indication of the
possible changes in setting, two extreme cases are considered:
If low-impedance relays are used in the scheme, the flux
swings in the current-transformer cores, at the fault-setting
current level, will tend to be small, and the reduction in the
residual flux will be negligible. The incremental permeability
will be low and the exciting current will be increased above
the expected value. It was found that a Stalloy-cored transformer operating at a peak alternating flux density of
0 03Wb/m2, after a remanence of 0-74Wb/m2had been left
in the core, required an exciting current 58% greater than
that required to support the same flux with the core demagnetised. Although this increase is large, the effect on the
transformer secondary current will be small, as the exciting
current is not likely to exceed 2-3 % of the primary current.
The protective setting would thus rise by not more than about
2% of its nominal value, a change which would be of no
practical importance.
If high-impedance relays were used in the protective
equipment, the transformer-core flux swings would be large
at the fault setting current, and most of the residual flux
would be destroyed. The incremental permeability would not,
in these circumstances, be appreciably below that obtained
with zero residual flux; e.g. the above Stalloy-cored transformer operating with a peak alternating-flux density of
0-3Wb/m2, after a residual flux density of 0-74Wb/m2 had
been left in its core, required an exciting current 7-5%
greater than normal. Since most of the primary current acts
as exciting current when high-impedance relays are in use,
the protective fault setting rises by almost the same amount
as the exciting current. Increases up to 7 5 % of the nominal
setting may thus be expected. Again, this increase would
normally be of little importance.
If the next fault, after residual flux has been left in a core,
is external to the protected zone, and the required flux swing
is in the same direction as the residual flux, the available
swing before saturation is reached will be much reduced. For
those schemes where saturation must not occur, the transformers must be made large to overcome this effect; e.g. if a
residual flux of 60% of the saturation level can be retained,
a core would have to be provided of 2-$- times the size
which would be needed if residual flux could not be left,
since only 40% of the flux swing can be regarded as always
being available.
918
Fig. 5
BjH diagram showing successive minor hysteresis loops when primary
current is gradually (a) increased, (b) decreased
Initial remanence = 0-61 Wb/m2
Peak values of alternating flux density in the minor loops = 0,0 022,0 044,0 066,
0-11 Wb/m*
magnetising
force
H
Fig. 6
Minor hysteresis loops generated on energising the primary circuit
flux
density
B
initial magnetisation
curve y - "
TR
magnetising
force
H
Fig. 7
Additional magnetisation produced when the primary circuit is
energised
PROC. 1EE, Vol. 113, No. 5, MA Y 1966
3.3
I p ,5A r.m.s.
H,At/n
300
100
0-9
"m:,\mi mm'
Referring to Fig. 6, consider that residual magnetism represented by OR has been left in a current transformer core,
and that the primary circuit is then closed at a time such that
the initial flux swing required is from peak to peak of its
steady-state value. In the case of an upward flux swing, a
vvTvvTvJ
1
,!
0 6
/ *
B,Wb/m2 0-3
0
-0-3
-06
iD,5A rms.
... .
, +100r
[
H,At/m
0-6
, 0-3
B,Wb/m
0
-0-3
-O6
i
I 'V
I
.V.VAV//J
,,,
....
'
I p ,5A nm.s.r
wvwvw
0-6
03
B,Wb/m2 0
-0-3
-06
Fig. 8
Oscillograms and B\H diagrams showing the transients produced on energising the primary circuit
Core material: Stalloy
Initial remanence <= 0 _ _ ..
Primary circuit X\R = 5-4
Supply frequency = 50c/s
a, b Resistive burden
Peak value of steady-state alternating flux density = 0Transient flux of same sense as remanence
c, d Conditions as for (a) and (6), except transient flux is of opposite sense to the initial remanence
e, f Inductive burden
Peak value of steady-state alternating flux density = 0-08 Wb/m2
Transient flux of opposite sense to remanence
919
Experimental study
920
Conclusions
The presence of remanent flux in current-transformer
cores can significantly affect the performance of balanced
forms of power-system protective equipment, and, while
present, would affect the accuracy of metering transformers as it would cause the permeability of the core to be
reduced.
It was shown in Section 2 that residual flux densities up
to the maximum possible for the particular core material
may be left in a current transformer, following the clearance
of a system fault. Higher values of remanence will, in general,
be left when burdens are of high power factor, since
greater flux densities are likely at the instant of fault
interruption.
It was found that the most satisfactory method of measuring
the residual flux in a core, and thereby studying the way in
which it decays in normal operation, was to use the destructive
method described in Section 3.1. Although this was not an
ideal method, it was found to be much more accurate than
the incremental permeability method which has been used for
this type of work in the past.
The remanent flux in a core is reduced when an alternating
current is passed through the windings of a transformer. The
degree of reduction is dependent on the magnitude of the
alternating flux produced; it is not affected by the secondarycircuit power factor, provided that the current is increased
gradually. Once equilibrium has been established, subsequent
variation of the current does not produce any further reduction in the amount of residual flux, provided that it does not
exceed the value at which equilibrium was reached.
When the primary circuit of a current transformer, in
which residual flux has been left, is energised, the final
equilibrium position of the minor hysteresis loop will depend
on the flux variation required during the transient period.
If the remanence is small or the initial flux swing large, the
equilibrium condition may be centred about a remanent flux
greater, or even of the opposite sense, than the original value.
In general, however, unless the initial remanence is very
small or the primary-circuit X/R is large, a reduction in
residual magnetism will be produced, although the reduction
may be dependent on the point on wave of switching.
The speed at which thefluxreduction occurs is affected by
the core material, but equilibrium, for any given set of conditions, is virtually achieved in a few seconds, the longer-term
small reductions probably being due to factors such as
magnetostriction.
Large alternating flux variations are needed to effect complete removal of the residual flux in a core, and, as such
variations are not likely in protective transformer cores,
protective schemes must allow for the possibility of large
residual fluxes being present. As, however, thefluxvariations
in metering current transformers are usually large, the amount
of residual flux which may be present in them will be very
small, and measurements show that the decrease in accuracy
due to this will generally be negligible.
5
References