Users Guide
TM
OMEGA
Internet e-mail
info@omega.com
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928
FAX: (514) 856-6886
e-mail: canada@omega.com
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen,
The Netherlands
Tel: (31) 20 6418405 FAX: (31) 20 6434643
Toll Free in Benelux: 06 0993344
e-mail: nl@omega.com
Germany/Austria:
Daimlerstrasse 26, D-75392
Deckenpfronn, Germany
Tel: 49 (07056) 3017 FAX: 49 (07056) 8540
Toll Free in Germany: 0130 11 21 66
e-mail: germany@omega.com
Czech Republic:
ul. Rude armady 1868, 733 01 Karvina-Hranice,
Czech Republic
Tel: 420 (69) 6311899 FAX: 420 (69) 6311114
e-mail: czech@omega.com
France:
9, rue Denis Papin, 78190 Trappes
Tel: (33) 130-621-400 FAX: (33) 130-699-120
Toll Free in France: 0800-4-06342
e-mail: france@omega.com
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter
specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
M2982/0798
http://www.omega.com
e-mail: info@omega.com
CN9400
Dual Display Autotune Temperature Controller
INDEX
SAFETY INFORMATION
ULTIMATE SAFETY ALARMS
Do not use SP2 as the sole alarm where personal injury or damage
may be caused by equipment failure.
S a f e t y
INSTALLATION
CONFIGURATION
All functions are front selectable, it is the responsibility of the
installing engineer to ensure that the configuration is safe. Use the
program lock to protect critical functions from tampering.
I n f o r m a t i o n
A1
A1
A3
1a
2
2
3
3
3
3
4
5
5
5
5
5
5
5
6
6
7
8
9
9
9
9
11
11
I n d e x
SAFETY INFORMATION
FUNCTIONS MENU
QUICK START
Quick Start Set-up
INTRODUCTION
The controllers
OVERVIEW
Installation
Set-up
Autotune
Cycle-time
SET-UP
Power-up
Select input sensor
Select display units
Allocate output device
Enter initial configuration
Set main setpoint
MENU NAVIGATION
Using program mode
AUTOTUNE 7
Tune program
Tune at setpoint program
PROPORTIONAL CYCLE-TIME
Cycle-time selection methods
Cycle-time recommendations
Autotune calculated cycle-time
PROGRAMMER
Ramp-Soak
A2
INDEX
SAFETY INFORMATION
ULTIMATE SAFETY ALARMS
Do not use SP2 as the sole alarm where personal injury or damage
may be caused by equipment failure.
S a f e t y
INSTALLATION
CONFIGURATION
All functions are front selectable, it is the responsibility of the
installing engineer to ensure that the configuration is safe. Use the
program lock to protect critical functions from tampering.
I n f o r m a t i o n
A1
A1
A3
1a
2
2
3
3
3
3
4
5
5
5
5
5
5
5
6
6
7
8
9
9
9
9
11
11
I n d e x
SAFETY INFORMATION
FUNCTIONS MENU
QUICK START
Quick Start Set-up
INTRODUCTION
The controllers
OVERVIEW
Installation
Set-up
Autotune
Cycle-time
SET-UP
Power-up
Select input sensor
Select display units
Allocate output device
Enter initial configuration
Set main setpoint
MENU NAVIGATION
Using program mode
AUTOTUNE 7
Tune program
Tune at setpoint program
PROPORTIONAL CYCLE-TIME
Cycle-time selection methods
Cycle-time recommendations
Autotune calculated cycle-time
PROGRAMMER
Ramp-Soak
A2
FUNCTIONS MENU
it
y
ex
pla
.5)
todis
ity t (0
au
m
r
itiv dEr.
m
a
ing (6)
s
l
a
g
;
a
n
r
a
k
3
g
r
Y
se .0 x
L32
ve
loc LEV
-A on
pro ; StA
tive to 1
y a 1 to
le
le
rity E;
ab Off;
pla dir;
ab Auto
riva 0.1
cu non
De
Dis
Se
Dis
Dis
L
AL
n
do
Setpoint 1
Output
indicator
(green)
d.2
.2r
1
d;
d
r; 1
2i
i.
i; 1
s
r f/
a
2
.2
s
t
t enso
n.2
t ; 1u.
ice d *
ice (re
ts ; 1r
ale
en
en
ev
ev lY
ou
LED ; 1
tpu d.2d
tm
tm 5% s
l sc tor
t d lY; SS
t d Sd; r
/P 1i.2n
rn- dn.SC
s
u
u
u
u
u
O
i
o
jus 25% r ful
j
2
1
b C;
tp E; r
tp E; S
d
;
d
e
e
;
r
o
o
on on
u
a
u
o
n
s
s
A
t
t
d
r
r
ro 0.0 sens
an 0.0
ve 1n.2
t M Off;
ve 1r.2
nso uP.S
1 o non
2 o non
Re
Se
Re
SP
Sp
SP
Ze
Se
;
Ct3
t2; oS2
C
a
g
;
t
ion
;
r
de
Da Ct1 uS
ers nit
ito
L
ne Ctb; oS1;
e v ult u
AL
on hi; lo
r
u
a
M
T
s
E;
T
ftw Con
ad VAr;
ad CtA; Ct4;
SE non
So
RE
Re
Re
LEVL 3 SP1.D SP2.D BURN REU.D REU.L SPAN ZERO CHEK READ TECH UER
CONFIGURE OUTPUT
SAFETY SETTINGS
C A L I B R AT I O N
RSET
INSTRUMENT ADJUSTMENTS
P E R F O R M A N C E D ATA
r
l
d;
;
so
na
ho
An
% ortio
sen
Lt.
nly
;b l
r
t
s
;
o
o
%
%
%
u
L
n ee
so
t ad
. oo
de old;
um ax to ale
t
nit Ar
t
p rop
um in to
V
o
t
u
i
o
u
u
e
m
t
r
m
d
i
u
h
p
e
C
d
sen
y u F; b SEt
m ;
t
g
p
r
x
m
m
;
tp
tp
o
sc
lu
ni
ut
ou 0%
al 0% only
mo dV.hi S,Lo;
pla C; ; rh;
so 1 de
ma nsor full
ou 0%
mi nsor le
ou 0%
P2 LtCH
s
p
u
S
e
i
1
2
e
2
e
r
1
n
.
0
0
n
l Se
l Se sca
F
P
;
a
0
1
1
y
e
SP
to
to
or
SP
Ph
ti E
t d E;
SP
nd E;
ca
ca
it S 00
in nonE S.hi;
pla 1 or
t s 0.0 sens
co non nLin
t s 0.0 full
lec non
lec non PSi;
ad 0 to
1 m 0 to mod Limit 100
F
Lim 1
Se
Ma
Se
Se
Se
Se
Dis
Re
SP
PL.2
MANUAL ADJUSTMENTS
SP2 MODES
RANGING
CONFIGURE INPUT
)
s
p
in)
ec
)
st
yst r f/
or
t.S
or
5s
c
1.5
5m
)/h so
)
/Hy ens
r
;A
sec
ff 1 se
t) in (
te) c (2
in
ain sen
ch nd (
nt scale
set nd
ain % s )
1)
te /hou
o
i
a
e
arK
g
/
a
m
r
e
P
k
a
s
G
e
P
o
(
8
m
r
r
r
(
n
/
o
S
%
0 F
ff to 81
A
s
0
g
A
r
p full
a E;
l
(
re 60
o
d
5
0
o
t
d
b
o
e
p
4
e
P
(
a
b
d
p
0
/
t
n
l
2
1
r
k
6
e
n
)
)
n
4
d
r
n
m
s
x
e to
1
r le
u
nu
ff
ap .0 x
tim 20
ba to C/3.
ba to 8F
loc
Ra 90
e o 0.1 )
/on ho
e
o1
eo ;t
e o 0.
P2 so
tim
ma 50% t = o
off off;
tive to 5
tive 1 to
int on
int 99
tim off; sec
un on
rop deg s (2
t S en sca
ycl off;
tim 0 t
rop deg C/1 gral f; 0.1
t(
.
jus +/ s full
tot oFF;
riva 0.5
riva Off;
f/
ak Off;
e Of
tpo Off;
fse 0 to (In
tpo 0 to
mp On;
2 C On.
1 P 0.1 (10
2 p 0.1
cle On. (20
So
Ra
SP
De
Ad
Se
Int
Au
Of
De
SP
Se
SP
Cy
SP1 SETTINGS
ss
re
dd
ta
en 255
m
u
str 0 to
In
PROGRAM ENTRY
0:
1
80
8O
:4
1:1
00 9k2
at
vity n
4
e
rm 1:18E
cti
at 0: 2 0: 1
o
r
f
x a ff; o
n
d 20 60
a
R
t
8
u
/
9
1
1
O
Da
Ba
Tx
A3
USER-PROTECTED SETTINGS
F u n c t i o n s
2;
M e n u
LEV
COMMS SETTINGS
SP2 SETTINGS
To
To
To
To
To
To
To
Notes:
Press
Press
Press
Press
Press
Press
Press
together
together
together briefly
QUICK START
2 Select unit.
Press and hold and use the or buttons to scroll
through the unit selection list until the
correct unit is displayed. Release the
buttons.
The display will read selected unit e.g.
UNIT
*C
PARK
SPI.D
0
NONE
To display setpoint
Press and hold The displays will now read unit
(eg. C ) and 0
Q u i c k
Press once
*C
0
To enter setpoint
Press and hold and use button to increase or
button to decrease the reading and
scroll to required setpoint value. (The
digit roll-over rate increases with time).
S t a r t
Note:
SPI.D
THE CONTROLLER IS NOW OPERATIONAL
WITH FACTORY SETTINGS
SSD
Note:
1b
INTRODUCTION
I n t r o d u c t i o n
TUNE
PARK
OVERVIEW
INSTALLATION
AUTOTUNE
SET-UP
Note:
O v e r v i e w
CYCLE-TIME
O v e r v i e w
Note:
Autotune calculated
After Autotune has been run and completed the calculated cycletime can be manually accepted or adjusted to suit the switching
device. For selection method see Select Autotune Calculated
Cycle-time.
Each level within the multi-level menu offers different functions, see
FUNCTIONS MENU for menu of main functions. Each function has a
range of user selections or options, see FUNCTION LIST for
functions and options details.
Factory set
To use the 20 sec factory set cycle-time no action is needed
whether Autotune is used or not.
The controller has two modes, program mode and operating mode.
When in program mode the controller can be programmed with
settings and functions to suit the application. When in operating
mode the controller uses the setting and functions entered in the
program mode to control the application and also displays both the
process variable and setpoint temperatures. For full details on how
to program the controller see VIEWING AND SELECTING
FUNCTIONS.
Note:
SET-UP
3 TO SELECT SP1
(Main setpoint output device)
POWER-UP
On power-up the controller will display the self test
sequence and brief display blanking
INPT
NONE
SP1>D
NONE
SP1>D
SSD
INPT
TCS
2 TO SELECT C/F
Press and release the button, the controller will now
display
UNIT
NONE
S e t - u p
PARK
0
M e n u
N a v i g a t i o n
MENU NAVIGATION
The facilities of the controller are selected from the multi-level menu
using the front panel mounted buttons.
Each level within the multi-level menu offers different functions, see
FUNCTIONS MENU page A3. Each function has a range of user
selections or options, see FUNCTION LIST pages 1622
In operating mode, the upper (green) display reads process
temperature (PV) and the lower (orange) display reads setpoint
temperature (SP).
When in program mode, settings of each function, shown in the
upper display, can be made by selecting an appropriate option
from the lower display.
To change levels
Press and hold to scroll through the functions until LEUL is
displayed. Release to display current level. Press and hold the
button, then press to increase or to decrease the level.
Release buttons when required level is obtained.
TUNE
OFF
Note:
AUTOTUNE
Select the most appropriate method of Autotune , Tune or
Tune at Setpoint, to suit the application.
TUNE PROGRAM
Temp
Setpoint
DAC
PID
Cycle
75% SP
11/4 on/off tuning
cycles
New PID
values
entered
Start TUNE
Time
(100% output)
TUNE
OFF
TUNE
A u t o t u n e
The TUNE program should be run with the load cool. The output is
cycled at 75% of the setpoint value to avoid any overshoot during
the tuning cycle. The warm-up characteristics are monitored and set
DAC which minimises overshoot on subsequent warm-ups.
Tuning
TUNE
ON
The TUNE program will now start. The upper display will
alternate between tune and the process temperature as it
climbs to setpoint.
The lower display will read the setpoint value e.g.
TUNE
232
Note:
Note:
A u t o t u n e
Setpoint
Prop band
13/4 on/off tuning
cycles
Tuning
PID
New PID
values
entered
Time
(100% output)
TUNE
OFF
TUNE
AT.SP
Note:
The TUNE AT SETPOINT program will now start. The upper display
will alternate tune and the process temperature.
The lower display will read the setpoint value.
PROPORTIONAL CYCLE-TIME
Factory set
To use the 20 sec factory set cycle-time no action is needed
whether autotune is used or not.
CYCLE-TIME RECOMMENDATIONS
Output
Device
Factory
Setting
Recommended
Minimum
Load max
(resistive)
Internal relay
rLY/rLY1
20 seconds
10 seconds
2A/250 Vac
Internal relay
rLY2
20 seconds
10 seconds
1A/250 Vac
Solid state
drives
SSd/SSd1/SSd2
20 seconds
0.1 seconds
Externally
fitted SSR
(n/a)
CYC.T
CYC.T
20
c y c l e - t i m e
P r o p o r t i o n a l
CYC.T
A16
Select
Press and hold the button, then press to increase
or to decrease the displayed cycle-time. Release
buttons when required value is displayed.
Select
or index to another function then exit program mode.
CYC.T
Factory setting
Manual settings
CYC.T
A--
Note:
CYC.T
10
The controller will now run Autotune and will accept the
calculated cycle-time.
.1
O
N
.O
F
A-
Proportional
cycle-time
TUNE
OFF
ON/OFF
Autotune calculated
cycle-time
TUNE
PROGRAMMER
RAMP-SOAK
Deg.
Target
setpoint
Deg.
Soak
Ramp /hour
Ramp /hour
Target
setpoint
Soak
Time
Time
TUNE
OFF
Press to scroll to
Notes
SPRR
0
SOAK
P r o g r a m m e r
--
SP2 deviation alarms follow the ramp setpoint and can be used to
alarm out of limits ramp rate.
Set Ramp On
WARNING
The Soak timer is triggered when the ramp setpoint reaches the
target setpoint. If the ramp rate is set too fast for the process, the
Soak timer will be triggered before the process temperature reaches
the target setpoint.
(Off) : On : hold
Press to scroll to
SPRN
OFF
11
S e t p o i n t
SP2.A
Deviation
low alarm
Deviation
band alarm
SP
setpoint
SP
setpoint
FS.hi sets off alarm signal when the temperature rises above
setpoint to a pre-set temperature above scale minimum.
FS.Lo sets off alarm signal when the temperature falls below
setpoint to a pre-set temperature above scale minimum.
bAnd sets off alarm signal when temperature rises above or falls
below a pre-set temperature above or below the setpoint.
NONE
Alarm
state
SP
setpoint
S e c o n d
dV.Lo sets off alarm signal when temperature falls below a pre-set
temperature below the setpoint.
Y
Y
Select level 1
and set the required setpoint value (y).
Y= SP2
set value
Full scale
high alarm
Full scale
low alarm
SP
setpoint
SP
setpoint
Index to
and adjust the setting.
BND.2
Check
is set to on.oF (for alarm).
CYC.2
12
SET.2
SP2.B
In level 1 select
and then set the setpoint (SP2) value (y).
SET.2
Alarm type
Deviation
ON-OFF
operating mode
SP2
Output state
SP2
LED state
Proportional
operating mode
SP2
Output state
SP2
LED state
DV.HI
DV.LO
BAND
BAND
Full scale
S e c o n d
FS.HI
S e t p o i n t
FS.LO
SP
setpoint
SP
setpoint
SP
setpoint
SP
setpoint
Strategy
Output ON
(Relay or SSd energised)
Without sequence
alarm
Alarms on
power up
Output OFF
(Relay or SSd de-energised)
LED ON
Alarm
enabled
Alarm operates
normally
SP2.A
In level 1 select
and then set the required proportional band.
BND.2
NO.AL
ON
13
ERROR MESSAGES
SENSOR FAULT
Action:
Note:
DATA
HAND
TUNE
AT.SP
TECH
CT.A
FAIL
0
CYC.T
Temp
PID
DAC
ON.OF
Setpoint
oS 2
oS 1
Tuning
Ct 2
INPT
Ct 1
E r r o r
M e s s a g e s
TUNE
14
Ct 4
uS
Ct 3
Ct b
Ct A
Cycle
75% SP
New PID
values
entered
Start TUNE
TECH
Time
(100% output)
ON
Note:
Poor control may be due to incorrectly sized heaters.
SP1.P (Level 2) constantly displays the output
percentage power applied, which at normal setpoint
should ideally be within 20 - 80% to achieve stable
control.
Control
CHEK
Press and hold and press once, the lower display will
alternate between VAr and the maximum hi displayed
in degrees (e.g. 320.3)
Press and hold and press once, the lower display will
alternate between VAr and the minimum Lo displayed
in degrees (e.g. 319.7)
Variance
VAr 0.1
CHEK
OFF
CHEK
ON
Lo
Minimum
Time
Accuracy
READ
Temp
CHEK
SP1.P
Improving
15
FUNCTION LIST
(Levels 1 to 4)
LEVEL 1
F u n c t i o n
L i s t
Function
16
Options
Function
Options
INT.T
SELECT AUTOTUNE
TUNE
Too short
(overshoots and oscillates)
DER.T
BAND
0.1 to * C/F
[10C/18F]
SP1 proportional band/Gain or Hysteresis
* 25% sensor maximum
Proportional control eliminates the cycling of on-off
control. Heater power is reduced, by time
proportioning action, across the proportional band.
Too narrow
(oscillates)
Too wide
(slow warm up and response)
increase BAND
decrease BAND
Too short
(slow warm up and response,
under corrects)
DAC
Too long
(slow warm up and response)
* disturbance
Too long
(oscillates and over corrects)
Too small
(overshoots)
Too large
(slow stepped warm up)
LEVEL 1 (continued)
Options
CYC.T
OFST
[0] to * C/F
SP1 offset/manual reset
* 50% bAnd. Applicable in proportional and ON/OFF
mode with integral disable: Int.t oFF.
SP>LK
SPRR
SPRN
on [oFF] hoLd
Switches the ramp on or off, or hold at last ramp value
SOAK
Options
SET.2
0 to * C/F [0]
Adjust SP2 setpoint
* Deviation Alarms DV.hi, DV.Lo, bAnd
25% sensor maximum (see figure 7).
* Full scale alarms FS.hi, FS.Lo
sensor range f/s (see figure 8)
BND.2
CYC.2
L i s t
[oFF] on
Lock main setpoint
Locks the setpoint preventing unauthorised
adjustment.
Function
F u n c t i o n
Function
17
LEVEL 2
Function
SP2.B
Function
Options
Options
F u n c t i o n
L i s t
SP1.P
HAND
PL.1
PL.2
DISP
[1] 0.1
Select display resolution: for display of process
temperature, setpoint, OFSt, Set.2, hi.SC, LoSC.
HISC
LO.SC
INPT
UNIT
SP2.A
18
LEVEL 3
BURN
OUTPUT CONFIGURATION
Function
Options
[uP.SC]
dn.SC
1u.2d
1d.2u
SP1
Upscale
Downscale
Upscale
Downscale
SP2
Upscale
Downscale
Downscale
Upscale
SP1.D
SP2.D
[1r.2d]
1d.2d
1r.2r
1d.2r
SP1
Reverse
Direct
Reverse
Direct
SP2
Direct
Direct
Reverse
Reverse
L i s t
REU.D
F u n c t i o n
Note: Read only after initial configuration. rSET ALL full reset to
factory settings required to change SP1.D subsequently.
19
LEVEL 3 (continued)
Function
F u n c t i o n
L i s t
REU.L
20
Options
[1n.2n]
1i.2n
1n.2i
1i.2i
SPAN
SP1
Normal
Invert
Normal
Invert
TECH
SP2
Normal
Normal
Invert
Invert
ZERO
CHEK
[oFF] on
Select control accuracy monitor
READ
[Var]
hi
Lo
Read control accuracy monitor
Function
VER
RSET
Options
[Ct A] CT b Ct 1 Ct 2 Ct 3
Ct 4 oS 1 uS oS 2
Read Autotune tuning cycle data (see figure, page 14)
[nonE] ALL
Resets all functions to factory settings
Caution:
LEVEL 4
Access to level 4 is gained through
Press and hold and
for 10 seconds.
Function
VER in level 3.
[Auto] StAY
Program mode auto-exit switch
Auto-exit returns display to normal if 60 seconds of
key inactivity, select StAY to disable
NO.AL
[oFF] on
Disable SP2 alarm annunciator -ALSelect on to disable -AL-
DIS.S
dir 1 to 32 [6]
Display sensitivity
dir = direct display of input
1 = maximum, 32 = minimum sensitivity
DER.S
LOCK
NONE
LEV.3
LEV.2
ALL
L i s t
PROG
F u n c t i o n
Options
LOCK
ALL
Note:
IMPORTANT NOTE FOR OEMs: For safety and to protect settings from tampering
USE THE SOFTWARE SECURITY LOCK.... THEN REMOVE THIS SECTION.
21
rLY1 (2A)
SSd1
(+)
SSd2
(-)
(+)
(-)
22
rLY2 (1A)
CN9411
CN9422
Note:
Terminals
Product
Code
SP1D
RLY1
ADVANCED SETTINGS
From cold (normal procedure on a new installation)
Enter setpoint and allow the process to reach the setpoint using
factory settings for heating only.
Autotune at setpoint
Make the following pre-settings:
Level 1 set
TUNE to At.SP
Autotune uses the same calculated bAnd value for both SP1
(heating) and SP2 (cooling). In some processes, regular temperature
oscillations occur when cooling.
S e t t i n g s
A d v a n c e d
BND.2
23
S e t t i n g s
CYC.2
ZERO
Adjust
to make an equal adjustment across the full scale
of the controller and
to make a correction when the error increases/
decreases across the scale.
SPAN
SET.2
1
ZERO function
A d v a n c e d
24
Instrument reading
Controller reading
396 400
1.2 Adjust
= 396
= 400
= (-)4
ZERO
To make a correction when there are different errors across the scale.
Adjust using the
SPAN function
Note:
T1
58
60
E1(-) 2
SPAN
T2
385
400
E2 (-) 15
S e t t i n g s
A d v a n c e d
Notes: (1)
25
14 15
5Vdc 15mA
1 ohm
INPT
NONE
SP1.D
Supply
Linear Range
Lin 1
Lin 2
Lin 3
Lin 4
Lin 5
16
Outputs
420 mA
from transducer
26
10 11 12 13
A d v a n c e d
S e t t i n g s
Nom. Scale
Span
0 100
0 100
0 1000
0 1000
0 2000
Select
then select the process unit, C, F, Bar, PSI,
Ph, or rh. If the required unit is not shown
select Set.
HI.SC =
HI.SC
SPAN =
SPAN
Max. Scale
Settings
0 400
-25 to 400
0 to 3000
-250 to 3000
0 to 3000
UNIT
MECHANICAL INSTALLATION
The unit is sleeve mounted with the front bezel assembly rated
NEMA4/IP66 provided that:
the panel is smooth and the panel cutout is accurate;
the mounting instructions are carefully followed.
20 mm
(0.79)
M e c h a n i c a l
10 mm
(0.39)
I n s t a l l a t i o n
27
I n s t a l l a t i o n
M e c h a n i c a l
28
MINIMUM SPACING
MOUNTING
To mount a Controller proceed as follows:
1
Cleaning
Wipe down with damp cloth (water only)
116.2
(4.57)
44.8
(1.76)
Model CN9400
44.8
(1.76)
Dimensions in mm (inches)
51.0
(2.0)
includes
gasket
106.7 (4.2)
with gasket fitted
51.0 (2.0)
includes gasket
ELECTRICAL INSTALLATION
Designed for use with the following supply voltages:
2
3
INDUCTIVE LOADS
Either of the available outputs may be chosen for the main setpoint
(SP1), the remaining device being automatically allocated to the
second setpoint (SP2).
See example illustrated on page 30.
CAUTION:
Snubber leakage current can cause some electro-mechanical
devices to be held ON. Check with the manufacturers
specifications.
I n s t a l l a t i o n
E l e c t r i c a l
OUTPUT DEVICES
Dual relay or dual SSd model options CN9411 / CN9422 are fully
detailed on page 22.
29
I n s t a l l a t i o n
E l e c t r i c a l
MODEL CN9412
TYPICAL CONNECTION DIAGRAM
The SSR driver output is allocated to SP1 and wired to switch the
load (heater) using an SSR
F1 Fuse:
F2 Fuse:
S1 Switch:
Sensor
Output Output
SP2
SP1
16
Supply
Open in
alarm
state
S1
Line
Neutral
14 15
5Vdc 15mA
Sensor
F2
30
10 11 12 13
F1
SSR
Load
SENSOR SELECTION
Sensor range
Linearity
32 to 3272 F
32 to 1112 F
32 to 1472 F
-58 to 2192 F
32 to 1472 F
-58 to 2192 F
32 to 2912 F
32 to 2912 F
-273 / 482 F
Pt-30%Rh/Pt-6%Rh
Chromel/Con
Iron/Constantan
Chromel/Alumel
Fe/Konst
NiCrosil/NiSil
Pt-13%Rh/Pt
Pt-10%Rh/Pt
Copper/Con
2.0 *
0.5
0.5
0.25*
0.5
0.25*
2.0*
2.0*
0.25*
-200 / 400 C
-273 / 752 F
Pt100/RTD-2
0.25*
setpoint limits
0 - 400
-25 - 400
0 - 3000
-250 - 3000
0 - 3000
Resistance thermometer
rtd
0 - 20mV
0 - 100
4 - 20mV
0 - 100
0 - 1000
0 - 1000
0 - 2000
0.5%
0.5%
0.5%
0.5%
0.5%
S e l e c t i o n
0 to 1800 C
0 to 600 C
0 to 800 C
-50 to 1200 C
0 to 800 C
-50 to 1200 C
0 to 1600 C
0 to 1600 C
-200 / 250 C
S e n s o r
Option/Sensor type
Thermocouples
tc b
B
tc E
E
tc J
J
tc K
K
tc L
L
tc n
N
tc r
R
tc s
S
tc t
T
31
SPECIFICATION
S p e c i f i c a t i o n
Thermocouple
9 types
Standards:
CJC rejection:
External resistance:
Resistance thermometer
RTD-2/Pt100 2 wire
Standards:
Bulb current:
Linear process inputs
mV range:
DIN 43760
(100 0C/138.5 100C Pt)
0.2mA maximum
0 to 50mV
Keypad:
Output devices
SSd/SSd1/SSd2:
32
IPTS/68/DIN 43710
20:1 (0.05/C) typical
100 maximum
= sensor maximum
0.25%SM 1C
input 10Hz, CJC 2 sec.
Negligible effect up to 140dB,
60dB, 50-60Hz
150ppm/C SM
22C 2C, rated voltage after 15
minutes settling time.
Environmental
Humidity:
Altitude:
Installation:
Pollution:
Protection:
EMC emission:
EMC immunity:
Ambient:
Mouldings:
Weight:
3 elastomeric buttons
Max 80%
up to 2000M
Categories ll and lll
Degree ll
NEMA 4X, lP66
EN50081-1 FCC Rules 15 subpart J
Class A
EN50082-2
0-50C (32-130F)
flame retardant polycarbonate
130g (4.2 oz)
QUICK START
WARRANTY / DISCLAIMER
S t a r t
Note:
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 37 months from date of purchase.
OMEGA Warranty adds an additional one (1) month grace period to the normal three (3) years product warranty to cover handling and shipping time.
This ensures that OMEGAs customers receive maximum coverage on each product.
INPT
NONE
INPT
Q u i c k
NONE
Proportional cycle-time
(Typical setting for relay output)
DAC Derivative approach control
(Average setting for minimum overshoot)
20 secs
PARK
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a Basic Component under 10 CFR 21 (NRC), used in or
with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear
installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic
WARRANTY/ DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
INPT
TC.S
Press once
UNIT
NONE
1a
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any
omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information
provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of
defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive
and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict
liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be
liable for consequential, incidental or special damages.
1.5
Note:
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGAs Customer Service Department will issue an Authorized Return (AR) number
immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. OMEGAs
WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside
of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows
evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGAs control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGAs policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and
engineering.OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
Copyright 1996 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic
medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.
omega.com
Users Guide
TM
OMEGA
Internet e-mail
info@omega.com
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928
FAX: (514) 856-6886
e-mail: canada@omega.com
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen,
The Netherlands
Tel: (31) 20 6418405 FAX: (31) 20 6434643
Toll Free in Benelux: 06 0993344
e-mail: nl@omega.com
Germany/Austria:
Daimlerstrasse 26, D-75392
Deckenpfronn, Germany
Tel: 49 (07056) 3017 FAX: 49 (07056) 8540
Toll Free in Germany: 0130 11 21 66
e-mail: germany@omega.com
Czech Republic:
ul. Rude armady 1868, 733 01 Karvina-Hranice,
Czech Republic
Tel: 420 (69) 6311899 FAX: 420 (69) 6311114
e-mail: czech@omega.com
France:
9, rue Denis Papin, 78190 Trappes
Tel: (33) 130-621-400 FAX: (33) 130-699-120
Toll Free in France: 0800-4-06342
e-mail: france@omega.com
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New
Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter
specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
M2982/0798
http://www.omega.com
e-mail: info@omega.com
CN9400
Dual Display Autotune Temperature Controller