SOUND ATTENUATION
SECTION AC-242
Page 1
1.0
GENERAL
1.1
DESCRIPTION
.1
1.2
1.3
WORK INCLUDED
.1
.2
Sound-Lining.
SUBMITTALS
.1
Shop Drawings
.1
Sound attenuators.
.2
Sound-Lining.
.3
.4
Non-hardening caulking.
.5
Certified Tests:
Submit certified test data from independent laboratory for pressure
drop, generated noise level and insertion loss in compliance with
ASTM E477-84 or BS 4718: 1971 or international standard
equivalent.
.6
.7
Certified Tests:
.1
1.4
QUALITY ASSURANCE
.1
Acoustical Criteria
.1
KENCANA SQUARE
SOUND ATTENUATION
SECTION AC-242
Page 2
Type of Area
Range of NC
Criteria
Office
Board Room
20-30
Conference Rooms
30-40
Executive Office
30-40
30-45
35-45
Halls
35-40
Corridors
40-45
40-60
Equipment Rooms
8 hr/day exposure
<90 dBA
3 hr/day exposure
<97 dBA
.3
Mechanical Performance
.1
KENCANA SQUARE
SOUND ATTENUATION
SECTION AC-242
Page 3
Octave
Bands
(Hz)
NC-30
NC-35
NC-40
NC-45
NC-50
63
58
62
66
68
70
125
52
56
60
63
66
250
45
49
54
58
62
500
41
46
51
56
61
1K
38
43
48
53
58
2K
37
42
47
52
57
4K
36
41
46
51
56
8K
37
42
47
52
57
2.0
PRODUCT
2.1
ACOUSTIC INSULATION
.1
Suitable Acoustic Insulation on all vibration equipment, parts and all other
necessary connections shall be included in the tender. The acoustic
treatment shall be capable of reducing all noise transmitted from the
Plantroom ductwork and etc., to noise level not exceeding the noise
criterion curves as given in the current edition of the ASHRAE Guide and
Data Book And AS2107 recommendation.
.2
Notwithstanding the above, all supply and return ductwork of G.I. sheet
metal construction shall be internally lined with 50 mm thick duct liner
especially made from glass fibres or resin bonded fibreglass with
Neoprene or similar facing having a density of 2 lb/ft3 for a minimum
distance of 6 metres from the unit. Perforated GI sheet having minimum
opening of 40 % shall be firmly fixed to the liner. The lining and its method
of fixing shall be suitable for air velocities up to 15 m/s without erosion of
the lining and to the approval of the Engineer. Ductwork acoustically
treated shall have its external dimensions increased by 100 mm from
those shown on the drawings to maintain the required internal
dimensions.
.3
Unless the work is strictly adhered to the two paragraphs above, and to
the satisfaction of the Engineer, the work shall not be passed satisfactory
and no certificate of taking over shall then be issue.
.4
2.2
SOUND ATENUATORS
.1
.2
.3
Media:
.4
.1
Ignitability (0-20)
.2
.3
.4
.5
.6
Internal Construction
.1
3.0
EXECUTION
3.1
INSTALLATION
3.1
.1
.2
with
manufacturers
TEST
.1
After installation: The noise level should be measured with Type 1 sound
level meter integrated with octave band filter from 31.5 Hz to 8kHz and
complies to NF EN 60651 / NF EN 60804 standards.