PREDMET:
OBJEKAT:
INVESTITOR:
MINISTARSTVO
ZA
PROSTORNO
UREENJE,
BR. PREDMETA:
IZ-IGBL-IN-EE-2589-05/15
UESNICI U IZRADI:
VOA PROJEKTA:
DIREKTOR
.................................................................
SADRAJ
1.UVOD................................................................................................................................... 8
2.OPTI PODACI O OBJEKTU I LOKACIJI..........................................................................10
3.ORGANIZACIJA PROJEKTA.............................................................................................19
4.OPIS I PROCJENA POSTOJEEG STANJE.....................................................................20
4.1.Fasadne, krovne i podne obloge................................................................................20
4.2.Vanjska bravarija i stolarija........................................................................................30
4.3.Sistem grijanja, ventilacije i klimatizacije....................................................................33
4.3.1Centralni sistem zagrijavanja objekta..................................................................34
4.3.2Sistem ventilacije................................................................................................39
4.3.3Sistem klimatizacije.............................................................................................39
4.4.Sistem pripreme tople potrone vode (PTV)..............................................................39
4.5.Elektroenergetski sistem............................................................................................40
4.5.1Elektrina rasvjeta...............................................................................................41
4.5.2Potroai elektrine energije u termotehnikim sistemima..................................43
4.5.3Ostali potroai elektrine energije......................................................................45
5.ANALIZA EVIDENTIRANE POTRONJE ENERGIJE I VODE...........................................46
5.1.Elektina energija......................................................................................................49
5.2.Toplotna energija.......................................................................................................51
5.3.Voda.......................................................................................................................... 56
6.BAZNA LINIJA.................................................................................................................... 60
6.1.Model potronje elektrine energije...........................................................................62
6.2.Model potronje toplotne energije..............................................................................66
6.2.1Modeliranje potronje toplotne energije...............................................................66
6.2.2Modelovanje potrebne toplotne energije za stambene objekte JZU Modria.......67
6.2.3Modelovanje potronje toplotne energije za kompleks JZU Modria...................71
6.3.Model potronje vode................................................................................................72
6.3.1Modeliranje potronje vode za kompleks JZU Modria.......................................72
6.3.2Modeliranje potronje vode za stambene objekte JZU Modria..........................73
6.4.Model emisije ugljen-dioksida (CO2)..........................................................................74
7.PRIJEDLOG MJERA ENERGETSKE EFIKASNOSTI........................................................75
7.1.Vanjski omota objekta..............................................................................................75
7.1.1MJERA br.1- Zamjena vanjske bravarije..............................................................76
7.1.2MJERA br.2- Ugradnja toplotne izolacije- Pozicija fasadnog zida........................77
3
SPISAK TABELA
Tabela 1: Geografska lokacija objekta...................................................................................10
Tabela 2: Statiki podaci o objektima iz obuhvata energetskog pregleda..............................12
Tabela 3: Statiki podaci o ostalim objektima........................................................................13
Tabela 4: Statiki podaci sistema zagrijavanja objekata........................................................13
Tabela 5: Indikatori potronje elektrine i toplotne energije i vode za Kompleks JZU Modria
.............................................................................................................................................. 14
Tabela 6: Indikatori potronje elektrine i toplotne energije i vode za stambene objekte.......14
Tabela 7: Pregled postojeih graevinskih konstruktivnih elemenata....................................29
Tabela 8: Pregled postojeih pozicija vanjske stolarije i bravarije..........................................30
Tabela 9: Pregled povrina vanjskog omotaa po zonama i pozicijama................................31
Tabela 10: Reim rada centralnog sistema grijanja...............................................................33
Tabela 11: Specifikacija grejnih tijela.....................................................................................38
Tabela 12: Grupe potroaa elektrine energije....................................................................40
Tabela 13: Vrsta rasvjete, instalisana snaga..........................................................................41
Tabela 14: Instalisana snaga rasvjetnih tijela po tipovima.....................................................42
Tabela 15: Potroai elektrine energije u termotehnikim sistemima po zonama................43
Tabela 16: Potroai elektrine energije u termotehnikim sistemima...................................44
Tabela 17: Ostali potroai elektrine energije......................................................................45
Tabela 18: Referentne vrijednosti potronje vode, elektrine i toplotne energije za kompleks
JZU Modria.......................................................................................................................... 47
Tabela 19: Referentne vrijednosti potronje vode, elektrine i toplotne energije za stambene
objete JZU Modria............................................................................................................... 48
Tabela 20: Referentna potronja elektrine energije u kompleksu JZU Modria....................49
Tabela 21: Profil potronje elektrine energije u stambenim objektima..................................50
Tabela 22: Mjesena potronja energenta.............................................................................51
Tabela 23: Profil godinje potronje toplotne energije za 2012,2013 i 2014 godinu...............51
Tabela 24: Referentne vrijednosti potronje uglja u kompleksu JZU Modria........................53
Tabela 25: Profil potronje ugljena na mjesenom nivou za kompleks JZU Modria.............54
Tabela 26: Profil mjesene potronje vode za 2012, 2013 i 2014 godinu..............................56
Tabela 27: Struktura cijene vode...........................................................................................57
Tabela 28: Profil godinje potronje vode za 2012, 2013 i 2014 godinu................................57
Tabela 29: Referentna mjesena potronja vode za kompleks JZU Modria.........................58
Tabela 30: Bazna linija za kompleks JZU Modria.................................................................60
1. UVOD
Pod pojmom energetska efikasnost podrazumevamo efikasnu upotrebu energije u svim
sektorima krajnje potronje energije: industriji, saobraaju, uslunim delatnostima,
poljoprivredi i zgradarstvu. Vano je istai da se energetska efikasnost nikako ne smije
posmatrati kao tednja energije. Naime, tednja uvijek podrazumjeva odreena odricanja,
dok efikasna upotreba energije nikada ne naruava uslove rada i ivljenja.
Dalje, poboljanje efikasnosti potronje energije ne podrazumeva samo primenu tehnikih
reenja. tavie, svaka tehnologija i tehnika oprema, bez obzira koliko efikasna bila, gubi to
svoje svojstvo ukoliko ne postoje edukovani ljudi koji se njome znaju sluiti na najefikasniji
mogui nain.
Prema tome, moe se rei da je energetska efikasnost prvenstveno stvar svesti ljudi i
njihovoj volji za promenom ustaljenih navika prema energetski efikasnijim reenjima, nego
to je to stvar kompleksnih tehnikih reenja.
Zgrade su najvei pojedinani potroai energije, sa tendencijom porasta u skladu sa
porastom standarda stanovnitva. U Evropskoj uniji se oko 41% energije troi u zgradarstvu,
sledi industrija sa udelom od 31%, a na treem mestu nalazi se saobraaj (28%).
Pored toga, zgrade su i veliki zagaivai ivotne sredine, jer takav trend dovodi do poveanja
potronje energije i emisije ugljen-dioksida.Upravo zato,energetska efikasnost u zgradarstvu
jeste oblast koja ima najvei potencijal za smanjenje potronje energije.
Potronja energije u zgradi zavisi od karakteristika same zgrade (njenog oblika i
konstrukcionih materijala), karakteristika energetskih sistema u njoj (sistema
grejanja,elektrinih ureaja i rasvete, i dr.), ali i od klimatskih uslova oblasti u kojoj se zgrada
nalazi.
Osnovni pojmovi za analizu potronje energije u zgradama su:
toplotni gubici i dobici,
koeficijent prolaza toplote,
stepen-dani grejanja,
stepen korisnog delovanja.
Ovi kriterijumi su kljuni za odreivanje energetskog (toplotnog) bilansa zgrade. Samu
zgradu trebamo posmatrati kao sistem pa je kao takvu i analizirati. Energetski bilans zgrade
podrazumeva sve energetske gubitke i dobitke te zgrade. Pri tome obino govorimo o
toplotnom bilansu zgrade, odnosno razmatramo koliko je energije potrebno da bi se
zadovoljile toplotne potrebe zgrade. Vano je zapamtiti da je potreba za toplotnom energijom
uvek usko vezana za toplotne gubitke zgrade. Naime, dok god su toplotni dobici energije
dovoljni za pokrivanje toplotnih gubitaka, u zgradi e se odravati eljeni uslovi toplotne
ugodnosti.
8
Lokacija
44
`
57
47,94
18
20
44,96332
18,34231
Tabela 1: Geografska lokacija objekta
10
32,32
Elv.
m
105
105
JZU Bolnica smjetena je u selu Garevac pored Modrie u kompleksu sa vie zasebnih
objekata.
11
Broj:
BEEP
Naziv objekta:
Adresa objekta:
OPIS
Osnovne informacije
Namjena objekta:
Smjenski rad:
Broj mjeseci rada u godini:
Broj osba u toku rada objekta:
Bolnica
Da (3 smjene)
12
66
Klimatizacija objekta:
Ljetna temperatura ambijenta objekta:
Grijanje objekta:
Temperatura objekta u sezoni
grijanja:
Broj stepen dana
Broj dana grijanja, Z
KGH:
DA
26,0C
DA
22,0C
2.919
188
P/P+1
ZONA 1 (Bosna)
ZONA 2 (Drava)
GRADNJA: ZONA 3 (Drina)
ZONA 4 (Ibar)
ZONA 5 (Neretva)
ZONA 6 (Sutjeska)
ZONA 7 (Una)
ZONA 8 (Vrbas)
ZONA 9 (Zeta)
167,8
128,7
167,8
128,7
200,2
200,2
167,8
200,2
113,1
Ukupno za
energetski
pregled:
Grejna povrina m
1.474,5
Grejna zapremina m
3.962,3
1950/1981
415,0
Visina H
(m)
2,8
2,5
2,8
2,5
2,8
2,8
2,8
2,8
2,5
2,7
12
Bruto
191,9
141,1
191,9
141,1
223,5
223,5
191,9
223,5
124,5
1.652,9
4.443,8
Statiki podaci u vezi sa ostalim objektima kompleksa JZU Modria koji nisu u obuhvatu
energetskog pregleda su dati u sledeoj tabeli:
Ostali
objekti:
Radna terapija
Upravna zgrada
Kuhinja sa trpezarijom
Farma svinja
Mjeaona stone hrane
Magacin
Ukupno ostali objekti:
267,0
273,0
451,0
382,0
100,8
50,0
1.523,8
2,7
2,7
2,7
2,5
2,7
2,7
2,6
720,9
737,1
1.217,7
955,0
272,2
135,0
4.037,9
NE ZADOVOLJAVAJU
NE ZADOVOLJAVAJU
Izvor toplote:
Sistem
grijanja:
90/70 0C
Sistem daljinskog grijanja
Kotlovnica:
Sistem regulacije kotlovnice:
Alternativni izvori energije:
Kotlovi na ugalj
Grejna tijela:
3x
NE
NE
320,0 kW
Regulacija temperature u
prostorijama:
NE
13
Sliku potronje vode i energije u objektu nam daju indikatori potronje koji predstavljaju
potronju po jedinici karakteristine veliine. Za karakteristine veliine su usvojeni korisna
povrina objekata i broj korisnika objekata.
U ovom sluaju e biti prikazani indikatori potronje za itav kompleks JZU Modria i za
stambeni dio JZU Modria.
Pregled specifine potronje (indikatori potronje) po karakteristinim veliinama za sve
objekte kompleksa je dat u sledeoj tabeli:
Kompleks
JZU
Modria
Elektrina
energija
Referentna godinja
potronja
470.468 kWh/god.
2.998,3
m2
156,91
kWh/(m2god.)
315,0
osoba
1493,55
kWh/
(osobigod.)
Korisna
povrine
zgrade
2.998,3
m2
710,18
kWh/(m2 god.)
Broj osoba
315,0
osobe
51,39
140,79
m3/(osobigod.)
L/(osobidan)
2.129.331 kWh/god.
16.188
m3/god.
Indikator potronje
Tabela 5: Indikatori potronje elektrine i toplotne energije i vode za Kompleks JZU Modria
Pregled specifine potronje (indikatori potronje) po karakteristinim veliinama za
stambene objekte je dat u sledeoj tabeli:
Stambeni
objekti
JZU
Modria
Elektrina
energija
Toplotna
energija
Voda
Referentna godinja
potronja
1.474,5
m2
29,74
kWh/(m2god.)
66
osoba
664,39
kWh/
(osobigod.)
Korisna
povrine
zgrade
1.474,5
m2
715,23
kWh/(m2 god.)
Broj osoba
66
osobe
25,23
m3/(osobigod.)
69,14
L/(osobidan)
43.850
kWh/god.
43.850
1.054.603 kWh/god.
1.665
m3/god.
Indikator potronje
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
15
SCENARIO "B":
ID
9
10
11
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
Ugradnja sistema toplotnih pumpi za svaki objekat posebno. Toplotne pumpe su tip
voda-voda prosjene nominalne snage zagrijavanja 17,0 kWt odnosno prosjene
nominalne elektrine snage Pe= 4,5 kWe kompletne sa instalacijom za primarnog
kruga. Za svaki objekat e se izgraditi po jedna izvorina buotina dubine 8-12
metara. Za sve objekte e biti izgraene 2 (dvije) upojne buotine. Spajanje
toplotnih pumpi na postojei sistem grijanja e biti vren na postojeim toplovodnim
prikljucima. Kao rezervna opcija e biti predvieno zagrijavanje na postojei
sistem daljinskog grijanja.
Ugradnja termoregulacionih ventila na 108 grejnih tijela. Mjera podrazumijeva
uklanjanje postojeih ventila, sanacija prikljunog mjesta na radijatoru, montaa
zaptivnog seta i montaa termoregulacionog ventila sa termoglavom.
Ugradnja solarnih sistema za zagrijavanje PTV za svaki objekat posebno.
Predviena je ugradnja solarnih paketa sa jednim solarnim kolektorom povrine 2,6
m2, bojlerom za pripremu PTV sa prikljukom za solar i dodatnim elektrozagrijaem
i kompletne mjerno regulacione opreme sa recirkulacionom pumpom i
ekspanzionom posudom.
Revitalizacija sistema fluorescentne rasvjete
Revitalizacija sijalica sa arnom niti
Ugradnja vremenskih prekidaa za eliminisanje stand-by gubitka svih printera i
fotokopirnih ureaja
16
SCENARIO "C":
ID
9
10
11
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
Zamjena postojeih kotlova na ugalj snage 2x314,5 kW kotlovima na drvo, drvni
otpad ili pelet snage 2x350 kW. Mjera podrazumjeva demontau i uklanjanje
postojeih kotlova, ugradnju predloenog kotla na drvo, drvni otpad ili pelet,
akumulatora toplote zapremine 10,0 m3 i ugradnju kompletne pratee mjernoregulacione opreme, sistema za loenje, sistema za prikupljanje i odvoz pepela
itd
Rekonstrukcija cijevovoda sistema daljinskog grijanja. Ova mjera podrazumjeva
demontau postojee cijevne instalacije i montau novih predizolovanih cijevi.
Predizolovane cijevi su sa izolacijom od tvrde PUR pjene u PEHD oklopu
predviene za podzemnu ugradnju.
Ugradnja termoregulacionih ventila na 108 grejnih tijela. Mjera podrazumijeva
uklanjanje postojeih ventila, sanacija prikljunog mjesta na radijatoru, montaa
zaptivnog seta i montaa termoregulacionog ventila sa termoglavom.
Ugradnja solarnih sistema za zagrijavanje PTV za svaki objekat posebno.
Predviena je ugradnja solarnih paketa sa jednim solarnim kolektorom povrine 2,6
m2, bojlerom za pripremu PTV sa prikljukom za solar i dodatnim elektrozagrijaem
i kompletne mjerno regulacione opreme sa recirkulacionom pumpom i
ekspanzionom posudom.
Revitalizacija sistema fluorescentne rasvjete
Revitalizacija sijalica sa arnom niti
Ugradnja vremenskih prekidaa za eliminisanje stand-by gubitka svih printera i
fotokopirnih ureaja
17
18
3. ORGANIZACIJA PROJEKTA
Objekat:
JZU Bolnica za hroninu psihijatriju, Modria
Lokacija:
Jake Modria
Adresa:
amaki put bb, Garevac
Kontakt osoba: Predrag Tadi
Telefon:
+ 387 65 237 374
fax:
+ 387 53 818 389
e-mail:
kontakt@bolnicamodrica.net
Datum pregleda:14.11.2015. 20.11.2015.
Energetski pregled je izraen za Ministarstvo prostornog planiranja, graevinarstva i
ekologije s ciljem identifikacije prihvatljivih mjera energetske obnove zgrade.
19
Vanjski zid
SZ1
175,8 m2
Kosi ventilisani
krov
ST1
101,5 m2
OBJEKAT DRAVA
21
Vanjski zid
SZ1
112,1 m2
Kosi ventilisani
krov
ST1
128,7 m2
OBJEKAT DRINA
22
Vanjski zid
SZ1
175,8 m2
Kosi ventilisani
krov
ST1
101,5 m2
OBJEKAT IBAR
23
Vanjski zid
SZ1
112,1 m2
Kosi ventilisani
krov
ST1
128,7 m2
OBJEKAT NERETVA
24
Vanjski zid
SZ1
210,5 m2
Kosi ventilisani
krov
ST1
116,6 m2
OBJEKAT SUTJESKA
25
Vanjski zid
SZ1
210,5 m2
Kosi ventilisani
krov
ST1
116,6 m2
OBJEKAT UNA
26
Vanjski zid
SZ1
175,8 m2
Kosi ventilisani
krov
ST1
101,5 m2
OBJEKAT VRBAS
27
Vanjski zid
SZ1
210,5 m2
Kosi ventilisani
krov
ST1
116,6 m2
OBJEKAT ZETA
28
Vanjski zid
SZ1
106,0 m2
Kosi ventilisani
krov
ST1
113,1 m2
U daljem toku energetskog pregleda e svaki objekat biti posmatran kao zasebna zona. Na
svim objektima su identifikovane sledee graevinski konstruktivni elementi vanjskog
omotaa:
SPOLJNI ZID - NEVENTILISANI
SZ1, U=1,941 W/m2K
1. KRENI MALTER
2. PUNA OPEKA 1600
3. CEMENTNI MALTER
1,5000 cm
20,0000 cm
2,0000 cm
1,5000 cm
12,0000 cm
30,0000 cm
1,5000 cm
POD NA TLU
U=2,353 W/m2K
1. POLIETILENSKA FOLIJA
2. BETON SA KAMENIM AGREGATIMA 1800
3. BETON SA KAMENIM AGREGATIMA 2500
4. LJUNAK, SUVI
0,5000 cm
5,0000 cm
12,0000 cm
PO1
SZ1
ST1
Postojee konstrukcije
-
U
W/mK
2,353
1,941
2,448
Umax.
W/mK
0,400
0,400
0,200
29
30
ZONA
Vanjska stolarija
i bravarija
Pod na tlu
(Prizemlje)
Objekat
Bosna-ZONA 1
Drava-ZONA 2
Drina-ZONA 3
Ibar-ZONA 4
Neretva-ZONA 5
Sutjeska-ZONA 6
Una-ZONA 7
Vrbas-ZONA 8
Zeta-ZONA 9
UKUPNO
Bravarija
63,5
31,4
63,5
31,4
50,2
50,2
63,5
50,2
26,5
430,4
PO1
66,3
128,7
66,3
128,7
106,9
106,9
66,3
106,9
113,1
890,1
Vanjski zid
(Fasadni zid
prizemlja i
spratova)
SZ1
175,8
112,1
175,8
112,1
210,5
210,5
175,8
210,5
106,0
1.489,1
Kosi ventilisani
krov
ST1
101,5
128,7
101,5
128,7
116,6
116,6
101,5
116,6
113,1
1.024,8
24%
11%
PO1
SZ1
38%
ST1
27%
31
15%
SZ1
ST1
35%
32
Vrijeme rada
06:00 - 18:00
06:00 - 18:00
23:00 - 06:00
18C
33
4.3.1
Generalno stanje kotlova je jako loe. Na kotlovima se sprovode mjere redovnog i tekueg
odravanja meutim zbog starosti, kvarovi su sve uestaliji i nemogue je nabaviti originalne
rezervne dijelove te su esto potrebna neadekvatna, improvizovana rjeenje da bi se kotlovi
odrali u radu. Ovakvim neadekvatnim rjeenja se uspijeva odrati proces proizvodnje
toplotne energije meutim uz znatno smanjenu efikasnost.
1987
1987-1994
poslije
1994
Poboljan kondenzacijski kotlovi
poslije
1999
91
92
1
1
97,5
98
1
1
20
20
94
103
20
37
kp = 0,60;
mp = 0,80;
rp = 0,85;
RADIJATORI lankasti
ZONA
0001
0002
0003
0004
0005
0006
0007
0008
0009
UKUPNO:
kom.
9
0
9
0
9
9
9
9
0
54
Broj
lanaka
kom.
94
94
94
94
94
94
564
Limeni
kom.
4
10
4
10
5
5
4
4
8
54
Ukupan
Broj radijatora sa
Uinak Procentu
broj
Toplotni uinak
ugraenim TRV
radijatora alni udio
radijatora
kom.
kom.
kW
W/m2
%
13
0
24,3
145,0
12,98%
10
0
14,0
108,8
7,47%
13
0
24,3
145,0
12,98%
10
0
14,0
108,8
7,47%
14
0
25,4
127,0
13,57%
14
0
25,4
127,0
13,57%
13
0
24,3
145,0
12,98%
13
0
24,3
121,5
12,98%
8
0
11,2
99,0
5,98%
108
0
187,4
127,1 100,00%
8
13
13
14
ZONA
14
10
13
10
13
0
10
Broj radijatora
38
12
14
16
4.3.2
Sistem ventilacije
4.3.3
Sistem klimatizacije
39
Elektrina rasvjeta
Potroai elektrine energije u termotehnikim sistemima
Kancelarijska oprema
Kuhinjska oprema
Kuni ureaji
Broj ureaja
192
24
4
8
9
237
40
6,3%
15,9%
12,2%
Termotehnii
sistemi
2,4%
Kancelarijska
oprema
Kuhinjska
oprema
Kuni ureaji
63,2%
4.5.1
Elektrina rasvjeta
Broj svjetiljki
Instalirana
snaga [kW]
33
2,622
21
138
192
0,45
8,28
11,352
Fluorescentn
a rasvjeta
(elektromagn
etska
prigunica) 4,0%
23,1%
Fluokompakt
na rasvjeta
72,9%
Sijalice sa
arnom niti
Broj svjetiljki
9
24
3
18
138
192
0,4
2,2
0,0
0,4
8,3
11,4
42
4.5.2
Elektrina grejna tijela su grejna tijela na elektrinu energiju kojima se vri dodatno
zagrijavanje prostora (El. uljni radijatori, el. grijalice);
Elektrini ureaji za zagrijavanje sanitarne vode (bojleri na el. energiju);
Klima ureaji (split klimatski sistemi za rashlaivanje i dogrijavanje prostora);
ZONA 6
ZONA 7
ZONA 8
ZONA 9
Broj ureaja
1
2
2
1
1
2
1
1
2
1
2
1
1
1
2
1
1
1
Naziv ureaja
Klima ureaj
El bojler
El bojler
Klima ureaj
El bojler
El bojler
Klima ureaj
Grijalica 1,5kW
El bojler
El bojler
El bojler
El bojler
El bojler
Klima ureaj
El bojler
El bojler
Klima ureaj
El bojler
Snaga ureaja
[W]
Ukupno [kW]
1800
2000
2000
1800
2000
2000
1800
1500
2000
1500
2000
1500
2000
1800
2000
1500
1800
2000
1,8
4,0
4,0
1,8
2,0
4,0
1,8
1,5
4,0
1,5
4,0
1,5
2,0
1,8
4,0
1,5
1,8
2,0
Tip
Elektrina grejna tijela
Decentralni sistem pripreme PTV
Klima ureaji
Ukupno
Broj
1
18
5
24
Klima ureajima
18
1
Broj ureaja
0
10
12
14
16
18
20
3,3%
20,0%
Decentralni
sistem
pripreme
PTV
Klima
ureajima
76,7%
4.5.3
Pod ostale potroae ubrajaju se: kuhinjska oprema, kancelarijska oprema i kuanski ureaji.
U narednoj tabeli dat je prikaz broja ureaja i instalisane elektrine snage na ostale
potroae.
Tip potroaa
Kancelarijska oprema
Kuhinjska oprema
Kuanski ureaji
Ukupno
Broj ureaja
4
8
9
21
45
46
ENERGIJA I
VODA
za kompleks JZU
Modria
Jedinica
Elektrina energija
Toplotna energija
Voda
kWh
kWh
m3
REFERENTNE VRIJEDNOSTI
Godinja
Godinji
Godinja
Godinja
potronja
trokovi bez
potronja
emisija CO2
energije
PDV-a
[jedinica/god.] [kWh/god.]
[KM/god.]
[t/god.]
470.468,00 470.468,00
52.588,74
350,31
2.129.330,70 2.129.330,70 117.072,52
1.156,99
16.187,54
0,00
21.938,99
11,51
UKUPNO: 2.599.798,70 191.600,25
1.518,82
Tabela 18: Referentne vrijednosti potronje vode, elektrine i toplotne energije za kompleks
JZU Modria
Elektrina energija
Toplotna energija
Voda
61,1%
Slika 24: Struktura godinjih trokova za energiju i vodu u kompleksu JZU Modria
Ukupni referentni troak za vodu i elektrinu i toplotnu energiju na godinjem nivou za
kompleks JZU Modria iznosi 191.600,25 KM bez PDV.
Najvei dio trokova pripada potronji toplotne energije u iznosu od 61,1%, zatim elektrine
energije u iznosu od 27,4% i najmanji dio pripada potronji vode u iznosu od 11,5%.
U ukupnoj potronji toplotne i elektrine energije koja iznosi 2.599.798,7 kWh dominantna je
potronja toplotne energije sa ueem od 81,9% u odnosu na elektrinu energiju sa udjelom
od 18,1%.
47
ENERGIJA I
VODA
za stambene
objekte JZU
Modria
Jedinica
Elektrina energija
Toplotna energija
Voda
kWh
kWh
m3
REFERENTNE VRIJEDNOSTI
Godinja
Godinji
Godinja
Godinja
potronja
trokovi bez
potronja
emisija CO2
energije
PDV-a
[jedinica/god.] [kWh/god.]
[KM/god.]
[t/god.]
43.850,00
43.850,00
4.901,54
32,65
1.054.603,07 1.054.603,07 57.983,03
573,03
1.665,47
0,00
2.257,21
1,18
UKUPNO: 1.098.453,07 65.141,77
606,86
Tabela 19: Referentne vrijednosti potronje vode, elektrine i toplotne energije za stambene
objete JZU Modria
3,5%
Elektrina energija
Toplotna energija
Voda
89,0%
Slika 25: Struktura godinjih trokova za energiju i vodu u stambene objekte JZU Modria
Ukupni referentni troak za vodu i elektrinu i toplotnu energiju na godinjem nivou za
stambene objekte JZU Modria iznosi 65.141,77 KM bez PDV.
Najvei dio trokova pripada potronji toplotne energije u iznosu od 89,0%, zatim elektrine
energije u iznosu od 7,5% i najmanji dio pripada potronji vode u iznosu od 3,5%.
U ukupnoj potronji toplotne i elektrine energije koja za stambene objekte iznosi
1.054.603,1 kWh dominantna je potronja toplotne energije sa ueem od 96,0% u odnosu
na elektrinu energiju sa udjelom od 4,0%.
48
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Agust
Septembar
Oktobar
Novembar
Decembar
Ukupno
49
Broj ureaja
Rasvjeta
Termotehnii sistemi
Kancelarijska oprema
Kuhinjska oprema
Kuni ureaji
Ukupno
192
24
4
8
9
237
11,352
45,0
1,7
8,7
4,5
71,252
Potronja elektrine
energije [kWh]
11.748,0
25.513,5
782,0
3.871,5
1.935,0
43.850,0
Rasvjeta
Termotehnii
sistemi
8,8%
1,8%
26,8%
Kancelarijska
oprema
Kuhinjska
oprema
Kuni ureaji
58,2%
50
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO
2012
Utroen Ukupni
a
troak
koliina energent
energent a bez
a
PDV-a
[tona]
[KM]
118
19.195
87
14.144
75
12.241
147
29
150
607
17.528
3.475
17.842
84.425
2013
Ukupni Utroen Ukupni
troak
a
troak
energent koliina energent
a s PDV- energent a bez
om
a
PDV-a
[KM]
tona
[KM]
22.458
118
14.081
16.549
59
7.028
14.322
117
13.914
29
3.489
20.508
4.066
20.875
98.778
105
76
76
581
12.466
9.068
9.068
69.113
2014
Ukupni Utroen Ukupni
troak
a
troak
energent koliina energent
a s PDV- energent a bez
om
a
PDV-a
[KM]
tona
[KM]
16.474
102
12.186
8.223
116
13.804
16.279
50
5.950
4.082
25
2.975
14.586
10.609
10.609
80.863
115
96
155
660
13.685
11.482
18.445
78.527
Ukupni
troak
energent
a s PDVom
[KM]
14.257
16.151
6.962
3.481
16.011
13.434
21.581
91.876
KOMPLEKS JZU
Modria
Godina
2012
2013
2014
REFERENTNA
VRIJEDNOST:
[tona]
607
581
660
[KM]
84.425,44
69.113,38
78.526,91
[KM]
98.777,77
80.862,65
91.876,48
[tona/god.]
1,086
1,039
1,180
Prosjena
mjesena
potronja
energenta
[tona/mj.]
101,18
96,80
109,98
646,81
76.970,76
90.055,79
1,157
107,80
Godinja
potronja
energenta
Godinja
emisija CO2
Tabela 23: Profil godinje potronje toplotne energije za 2012,2013 i 2014 godinu
51
2012
2013
2014
60
40
20
0
700
120.000,00
600
100.000,00
500
80.000,00
400
60.000,00
300
40.000,00
200
20.000,00
100
0
0,00
2012
2013
2014
52
[MWh]
80
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Referentna vr.:
Referentna
potronja
energenta
[tona]
118,20
87,10
75,38
25,00
115,00
76,20
149,93
646,81
Referentna potronja i
trokovi
Referentni trokovi s
PDV-om
[KM]
14.065,80
10.364,90
8.970,22
2.975,00
[KM]
16.456,99
12.126,93
10.495,16
3.480,75
[tona]
211,43
155,80
134,84
44,72
13.685,00
9.067,80
17.842,03
76.970,76
16.011,45
10.609,33
20.875,18
90.055,79
205,71
136,30
268,19
1.156,99
Emisija CO2
[tona]
160,00
140,00
120,00
Referentna potronja
energenta [tona]
100,00
80,00
60,00
40,00
20,00
0,00
53
Ostali objekti
[tona]
Radna terapija
Upravna zgrada
Kuhinja sa trpezarijom
Farma svinja
Mjeaona stone hrane
Magacin
Ukupno ostali objekti:
36
37
58
42
20
7
200
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO:
[tona]
129,3
111,0
97,7
40,2
Ostali
objekti
JZU
[tona]
40,0
34,3
30,2
12,4
41,3
93,4
133,9
646,8
12,8
28,9
41,4
200,0
Kompleks
JZU
Emisija CO2
Gubici
Stambeni
objekti
[tona]
25,3
21,7
19,1
7,9
[tona]
64,1
55,0
48,4
19,9
Ostali
objekti
JZU
[tona]
71,5
61,4
54,0
22,2
8,1
18,3
26,2
126,5
20,4
46,3
66,3
320,3
22,8
51,7
74,1
357,8
Gubici
Stambeni
objekti
[tona]
45,2
38,8
34,2
14,1
[tona]
114,6
98,3
86,6
35,6
14,4
32,7
46,8
226,2
36,6
82,8
118,6
573,0
Tabela 25: Profil potronje ugljena na mjesenom nivou za kompleks JZU Modria
Iz prethodne tabele se vidi da su enormni gubici u vanjskoj cijevnoj mrei. Za podmirivanje
gubitka u vanjskoj cijevnoj mrei potrebno je utroiti 126,5 tona ugljena. Ukoliko se uzme u
obzir starost mree, stanje izolacije, duina podzemnih cijevnih instalacija, nivo podzemnih
voda za oekivati je visoku potronju energenta potrebnog za pokrivanje gubitaka.
54
[tona]
100,0
80,0
Kompleks JZU
60,0
Gubici
40,0
Stambeni objekti
20,0
0,0
30,9%
49,5%
19,6%
5.3. Voda
Snabdijevanje objekata u kompleksu JZU Modria sanitarnom vodom se vri iz gradskog
vodovodnog sistema putem jednog mjernog mjesta.
Gradskim vodovodom upravlja javno komunalno preduzee AD VIK Modria.
Na lokaciji postoji jedno vodomjerno brojilo :
ifra potroaa 4320
Sanitarna voda se u objektu troi:
Kuhinja za pripremu hrane i odravanje istoe u kuhinji;
Sanitarnim vorovima;
Kotlovnica s (dopunjavanje sistema centralnog grijanja);
Farma svinja.
Detaljna ema vodovodnog sistema za distribuciju sanitarne i hidrantske vode nije poznata.
Pored sistema za sanitarnu vodu u bolnici postoji i hidrantski sistem.
Za potrebe preliminarnog energetskog pregleda izvrena je analiza potronje vode za
prethodne tri godine (2012, 2013 i 2014).
Godina
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO:
2012
2013
2014
Ukupni Ukupni
Ukupni Ukupni
Utroen
Utroen Ukupni Ukupni
troak troak
troak troak
Utroena koliina
a
a
troak
troak
vode vode s
vode vode s
VODE
koliina
koliina vode bez vode s
bez
PDVbez
PDVVODE
VODE PDV-a PDV-om
PDV-a
om
PDV-a
om
[m3]
[KM]
[KM]
[m3]
[KM]
[KM]
[m3]
[KM]
[KM]
1.118
1.516
1.765
1.545
2.092
2.435
1.439
1.949
2.268
1.259
1.706
1.985
1.258
1.705
1.984
1.681
2.276
2.649
1.087
1.474
1.716
1.307
1.771
2.061
1.375
1.863
2.168
1.201
1.628
1.895
1.669
2.260
2.630
1.404
1.902
2.213
1.395
1.889
2.199
1.232
1.670
1.943
1.474
1.996
2.323
2.074
2.807
3.266
1.191
1.614
1.879
1.118
1.516
1.764
2.044
2.766
3.219
979
1.328
1.546
1.248
1.691
1.968
1.684
2.280
2.653
2.269
3.070
3.572
1.258
1.705
1.984
1.383
1.874
2.180
1.263
1.712
1.992
1.170
1.586
1.846
1.529
2.071
2.410
1.718
2.326
2.707
991
1.344
1.565
1.269
1.720
2.001
1.224
1.659
1.931
984
1.335
1.554
1.565
2.119
2.466
1.143
1.550
1.803
1.245
1.687
1.964
17.609
20.852
Tabela 26: Profil mjesene potronje vode za 2012, 2013 i 2014 godinu
Analiza troka za sanitarnu vodu je raena na osnovu mjesenih rauna.
56
24.266
JZU Modria
Profil mjesene potronje sanitarne vode
3.000
2012
2013
2.500
2014
2.000
1.500
1.000
500
0
Slika 31: Profil mjesene potronje vode za 2012, 2013 i 2014 godinu
Primjetna je neto vea potronja vode u periodu jundecembar 2012 godine. Uzrok
poveane potronje su bili kvarovi na mrei koji su sanirani.
Pregled strukture cijene vode je dat u narednoj tabeli.
[%]
17,00%
17,00%
17,00%
[KM/m3]
0,221
0
0,0085
0,2295
Jedinina
cijena s
PDV-om
[KM/m3]
1,521
0
0,0585
1,5795
Godina
2012
2013
2014
REFERENTNA VRIJEDNOST:
Godinja potronja
vode
[m3]
17.609
16.798
15.387
16.187,54
Prosjena
mjesena
potronja
vode
[KM]
[tona/god.] [m3/mj.]
27.755,79
12,521
1.467,38
26.482,30
11,945
1.399,83
24.265,62
10,942
1.282,25
25.531,03
11,511
1.348,96
Godinji
Godinji
Godinja
troak vode troak vode emisija
bez PDV-a s PDV-om
CO2
[KM]
23.850,82
22.756,48
20.851,63
21.938,99
Tabela 28: Profil godinje potronje vode za 2012, 2013 i 2014 godinu
57
20.000
18.000
16.000
14.000
12.000
10.000
8.000
6.000
4.000
2.000
0
29.000,00
28.000,00
27.000,00
26.000,00
25.000,00
24.000,00
23.000,00
22.000,00
2012
2013
2014
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO:
58
JZU Modria
1.800,00
1.800,00
1.600,00
1.600,00
1.400,00
1.400,00
1.200,00
1.200,00
1.000,00
1.000,00
800,00
800,00
600,00
600,00
400,00
400,00
200,00
200,00
0,00
0,00
Referentna godinja potronja vode za kompleks JZU Modria iznosi 16.187,54 [m 3]. Ovako
visokoj potronji vode doprinose u prvom redu farma svinja i kuhinja.
Ukupna emisija ugljen-dioksida za referentnu potronju sanitarne vode iznosi 11,5
[tona/godinu].
Za stambene objekte je predviena potronja u skladu sa vaeim normama i iznosi za 66
stanovnika na godinjem nivou 1.667,47 [m3]. U ovu koliinu vode nije uzeta u obzir
pripadajua koliina koja se troi u kuhinji za pripremu hrane.
Ukupna koliina potrone tople vode (PTV) zagrijane na temperaturu od 50 [ 0C] u stambenim
objektima iznosi 476,33 [m3].
59
6. BAZNA LINIJA
Za definisanje efikasnosti sprovoenja pojedinih mjera energetske efikasnosti potrebno je
odrediti baznu liniju.
Bazna linija predstavlja polazne vrijednosti indikatora potronje toplotne energije elektrine
energije, i vode i emisije ugljen dioksida koje se sprovoenjem mjera energetske efikasnosti
umanjuju.
Zadatak sprovoenja mjera energetske efikasnosti je ciljna linija.
Ciljna linija predstavlja konane vrijednosti indikatora potronje elektrine energije, toplotne
energije i vode i emisije ugljen dioksida nakon sprovoenja mjera energetske efikasnosti.
Razlika vrijednosti indikatora potronje elektrine energije, toplotne energije i vode i emisije
ugljen dioksida izmeu bazne linije i ciljne linije predstavlja utedu odnosno efekat
sprovoenja mjera energetske efikasnosti.
U preliminarnom pregledu e biti razmatrane mjere koje e se sprovoditi na
stambenim objektima i na sistemu daljinskog daljinskog grijanja za itav kompleks. Iz
toga razloga e biti postavljene dvije bazne linije.
ENERGIJA I
VODA
Jedinica
Elektrina energija
Toplotna energija
Voda
kWh
kWh
m3
ENERGIJA I
VODA
Jedinica
Elektrina energija
Toplotna energija
Voda
kWh
kWh
m3
Za potrebe formiranja bazne linije neohodno je izraditi modele potronje elektrine energije,
toplotne energije i vode i emisije ugljen dioksida.
61
iznosi
rada,
svrhu
opcija
Potronja elektrine
energije [kWh]
Udio godinje
potronje elektrine
energije [%]
Rasvjeta
192
11,352
11.748,0
Termotehnii sistemi
24
45,0
25.513,5
Kancelarijska oprema
1,7
782,0
Kuhinjska oprema
8,7
3.871,5
Kuni ureaji
4,5
1.935,0
237
71,252
43.850,0
Potroa
Ukupno
6,3%
15,9%
12,2%
Termotehnii
sistemi
2,4%
Kancelarijska
oprema
Kuhinjska
oprema
Kuni ureaji
63,2%
Broj
1
18
34,5
22.575,0
5
24
9,0
45,0
1.215,0
25.514
6,8%
4,8%
Decentralni
sistem pripreme
PTV
Klima ureajima
88,5%
63
Model potronje
elektrine energije
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Ukupno
Referentna
potronja
elektrine
energije
[kWhe]
4.501,43
4.070,82
4.266,00
3.730,81
3.295,17
2.991,32
2.885,26
2.848,72
3.168,97
3.670,60
3.949,84
4.471,05
43.850,00
Referentni
trokovi bez
PDV-a
Referentni
trokovi s PDVom
Emisija CO2
[KM]
557,05
566,37
501,28
520,30
350,43
314,97
290,45
274,42
270,87
304,14
464,56
486,70
4.901,54
[KM]
651,74
662,65
586,50
608,75
410,00
368,51
339,83
321,08
316,92
355,84
543,54
569,44
5.734,80
[tona]
3,35
3,03
3,18
2,78
2,45
2,23
2,15
2,12
2,36
2,73
2,94
3,33
32,65
MJESEC
64
Model potronje elektrine energije za itav kompleks JZU Modria je izraen na osnovu
dostavljenih rauna.
Model potronje
elektrine energije
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Ukupno
Referentna
potronja
elektrine
energije
[kWhe]
48.296,00
43.676,00
45.770,00
40.028,00
35.354,00
32.094,00
30.956,00
30.564,00
34.000,00
39.382,00
42.378,00
47.970,00
470.468,00
Referentni
trokovi bez
PDV-a
Referentni
trokovi s PDVom
Emisija CO2
[KM]
5.976,56
6.076,58
5.378,24
5.582,30
3.759,77
3.379,30
3.116,30
2.944,31
2.906,15
3.263,13
4.984,30
5.221,79
52.588,74
[KM]
6.992,58
7.109,60
6.292,54
6.531,29
4.398,93
3.953,78
3.646,07
3.444,84
3.400,20
3.817,86
5.831,63
6.109,50
61.528,82
[tona]
35,96
32,52
34,08
29,80
26,32
23,90
23,05
22,76
25,32
29,32
31,55
35,72
350,31
MJESEC
Qgs=
24et e b ySDQh
( t ut s )sistema106
( MWh/god .)
SD= 2919
24e t e b ySDQ h
Qgr =
( MWh/god .)
(t u t s )regulacijemree 106
Daljinski sistem
zagrijavanja
KOTLOVNICA
3x320,0 kW
Energent
/Ugalj Miljevina/
OBJEKTI
24et e b ySDQhn
QHnd =
(MWh/god .)
(t u t s )106
66
6.2.2
Modria
Potrebnom toplotnom energijom je potrebno podmiriti transmisione toplotne gubitke toplote i
ventilacione toplotne gubitke.
Model toplotne energije za postojee stanje stambenih objekata
Datum
HDD
Raunski gubici
toplotne energije
Dobici
toplotne
energije
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO
22,0 0C
584
501
441
181
0
0
0
0
0
186
422
604
2919
QhHT /MWh/
210,0
180,2
158,6
65,3
0,0
0,0
0,0
0,0
0,0
67,0
151,7
217,4
1050,1
Qhgn /MWh/
3,6
4,3
5,0
4,9
4,6
4,5
4,6
5,0
5,0
4,8
3,9
3,4
29,9
Modelovana
potronja
toplotne
energije
Qhnd /MWh/
206,4
175,9
153,6
60,4
0,0
0,0
0,0
0,0
0,0
62,2
147,7
214,0
1020,2
67
Datum
HDD
Mjesec
22,00 C
tona
Qhg /MWh/
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO
584
501
441
181
0
0
0
0
0
186
422
604
2919
64
55
48
20
0
0
0
0
0
20
46
66
320
210,9
181,0
159,3
65,6
0,0
0,0
0,0
0,0
0,0
67,3
152,3
218,3
1054,6
Raunski
gubici
toplotne
energije
QhHT
/MWh/
210,0
180,2
158,6
65,3
0,0
0,0
0,0
0,0
0,0
67,0
151,7
217,4
1050,1
Dobici
toplotne
energije
Qhgn
/MWh/
3,6
4,3
5,0
4,9
4,6
4,5
4,6
5,0
5,0
4,8
3,9
3,4
29,9
Modelovana
potronja
toplotne
energije
Qhnd /MWh/
206,4
175,9
153,6
60,4
0,0
0,0
0,0
0,0
0,0
62,2
147,7
214,0
1020,2
Profil distribucije potrebne toplotne energije i toplotnih dobitaka u objektu je dat u sledeem
dijagramu.
250,0
200,0
150,0
100,0
50,0
0,0
68
Transmisioni
gubici
Ventilacioni
gubici
MWh
84
69
84
69
92
92
84
92
62
727
MWh
33
23
33
23
40
40
33
40
20
285
Dodatak na
ponovno
zagrijavanje
MWh
4
3
4
3
5
5
4
5
3
38
Dobici
toplotne
energije
MWh
3
3
3
3
4
4
3
4
3
30
UKUPNO
MWh
118
93
118
93
133
133
118
133
82
1.020
Transmisioni
gubici
Ventilacioni
gubici
27,1%
Dodatak na
ponovno
zagrijavanje
69,3%
69
Najvei udio u toplotnim gubicima zauzimaju transmisioni gubici kroz omota objekta sa
69,3% uea zatim ventilacioni gubici sa 27,1% i na kraju toplota potrebna za ponovno
zagrijavanje sa 3,6%.
Ventilacioni gubici nastaju usljed podhlaivanja objekta zbog dobavljenog svjeeg hladnog
vazduha u procesu obavezne ventilacije i infiltracije kroz pozicije vanjskog omotaa objekta.
Transmisioni gubici nastaju prolaskom toplote iz unutranjosti objekta prema vanjskoj okolini
kroz pozicije vanjskog omotaa.
Struktura transmisionih gubitaka je data u narednoj tabeli.
Toplotni gubici po pozicijama vanjskog omotaa [MWh]
Pozicija
Vanjska stolarija i
bravarija
ZONA
0001
0002
0003
0004
0005
0006
0007
0008
0009
UKUPNO
VSB
22
11
22
11
17
17
22
17
9
147
Spoljanji zidneventilisana
fasada
SZ1
3
5
3
5
4
4
3
4
5
37
Ravni
neventilisani krov
Pod na tlu
ST1
35
22
35
22
42
42
35
42
21
297
PO1
24
31
24
31
28
28
24
28
27
246
20,3%
33,8%
5,1%
VSB
PO1
SZ1
ST1
40,9%
70
6.2.3
Datum
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
UKUPNO
Specifina
modelovana
Referentna potronja Modelovana potronja
potronja
energenta
toplotne energije
toplotne
energije
tona
Qhnd /MWh/
kWh/(m2god.)
129,3
425,8
288,8
111,0
365,4
247,8
97,7
321,7
218,2
40,2
132,4
89,8
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
0,0
41,3
135,8
92,1
93,4
307,5
208,6
133,9
440,7
298,9
646,8
2.129,3
1.444,1
Emisija CO2
tona
231,37
198,52
174,80
71,92
0,00
0,00
0,00
0,00
0,00
73,81
167,09
239,48
1.156,99
71
Prikaz modelirane mjesene potronje i trokova sanitarne vode za kompleks JZU Modria
dat je u narednoj tabeli.
Mjesec
1.439,00
1.258,83
1.307,00
1.404,00
1.394,73
1.191,00
1.248,00
1.684,00
1.263,00
1.529,00
1.224,00
1.245,00
16.187,54
Jan.
Feb.
Mart
April
Maj
Jun
Jul
Avg.
Sept.
Okt.
Nov.
Dec.
Model
1.950,28
1.706,09
1.771,38
1.902,84
1.890,28
1.614,16
1.691,42
2.282,32
1.711,74
2.072,25
1.658,88
1.687,35
21.938,99
Emisija CO2
[tona]
2.269,59
1.985,43
2.061,40
2.214,39
2.199,77
1.878,45
1.968,35
2.656,00
1.992,00
2.411,54
1.930,49
1.963,62
25.531,03
1,023
0,895
0,929
0,998
0,992
0,847
0,887
1,197
0,898
1,087
0,870
0,885
11,511
Ukupna godinja
potronja vode
Godina
[m3]
2012
2013
2014
REFERENTNA
VRIJEDNOST:
17.609
16.798
15.387
23.850,82 27.755,79
22.756,48 26.482,30
20.851,63 24.265,62
12,521
11,945
10,942
1.467,38
1.399,83
1.282,25
16.187,54
21.938,99 25.531,03
11,511
1.348,96
72
16.187,54 [m3/god.]
21.938,99 [KM].
11,5 [tona].
6.3.2
73
1.665,,47 [m3/god.]
2.257,21 [KM].
1,18 [tona].
EM =E EFs[ kg /god .]
gdje su:
E[kWh /god .]
EFs[kg /kWh]
Wvoda[kg / god .]
74
7.1.1
Oznaka
irina
b
Visina
h
ID
PR1N
PR2N
PR3N
PR4N
PR5N
PR6N
PR7N
PR8N
PR9N
VR1N
VR2N
VR3N
VR4N
m
3,20
2,60
2,20
1,00
0,80
0,80
2,00
0,60
1,40
1,40
1,00
1,10
0,80
m
1,40
1,40
1,40
1,40
0,80
1,40
4,00
0,80
1,40
2,55
2,40
2,10
2,10
Povrina Povrina
Ukupna
ispuna staklo
povrina
Asj
As
m
0,448
0,36
0,31
0,14
0,06
0,11
0,80
0,05
0,20
0,36
0,96
0,23
0,17
m
4,032
3,28
2,77
1,26
0,58
1,01
7,20
0,43
1,76
3,21
1,44
2,08
1,51
m
4,48
3,64
3,08
1,40
0,64
1,12
8,00
0,48
1,96
3,57
2,40
2,31
1,68
Koeficijent
propusnosti
sunevog
zraenja b
%
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
0,61
Umax.
W/mK
1,49
1,50
1,50
1,50
1,50
1,50
1,43
1,50
1,50
1,50
1,50
1,50
1,30
W/mK
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
1,50
76
7.1.2
7.1.3
78
7.1.4
MJERA
br.4-Zamjena
postojeeg
sistema
zagrijavanja
sa
7.1.5
7.1.6
MJERA
br.6-
Rekonstrukcija
cjevovoda
sistema
daljinskog
zagrijavanja
Mjera podrazumjeva kompletnu zamjenu cijevi vanjskog cijevnog sistema daljinskog grijanja
predizolovanim cijevima.
Prilokom sanacije cijevnog sistema bit e sanirani graevinski elementi trase toplovoda
(kanali i ahtovi), ugraen sistem za monitoring iscurenja, mjerna oprema za nadzor
temperature i pritiska.
Ukupna duina toplovodne mree je 333 metra odnosno ukupna duina cijevi 666 metara
razliitog profila.
79
7.1.7
7.1.8
Mjera podrazumjeva ugradnju odvojenih solarnih sistema (za svaki bjekat posebno) za
zagrijavanje PTV. Za realizaciju ove mjere potrebno je na svaki objekat ugraditi solarni panel
povrine 2,6 m2, kompletan sa upravljakim modulom u kojem se pored mjerno-regulacioe
opreme nalaze ekspanziona posuda i cirkulaciona pumpa. Uz solarni paket potrebno je
ugraditi i bojler PTV kapaciteta 80-120 litarakoji e biti postavljen umjesto postojeih
elektrinih bojlera.
7.1.9
Ovom mjerom predlae se zamjena postojeih fluo cijevi odgovarajuim LED cijevima i to:
fluo cijevi od 58W (1500mm) mijenjaju se LED cijevima 25W (1500 mm), fluo cijevi od 36W
(1200mm) mijenjaju se odgovarajuim LED cijevima 20W (1200mm) i fluo cijevi od 18W
(600mm) mijenjaju se LED cijevima 10W (600mm).
Pri ovom proraunu uzeto je da prosjeni vijek trajanja LED cijevi 30 000 h, dok je prosjeni
vrijek trajanja fluo cijevi priblino 8 000 h.
80
81
Potrebna
toplotna
energija
ZONA
0001
0002
0003
0004
0005
0006
0007
0008
0009
UKUPNO
Transmisioni
gubici
Ventilacioni
gubici
MWh
22,3
17,7
22,3
17,7
24,0
24,0
22,3
24,0
15,8
190,0
MWh
15,1
10,5
15,1
10,5
18,0
18,0
15,1
18,0
9,2
129,5
Dodatak na
ponovno
zagrijavanje
MWh
4,3
3,3
4,3
3,3
5,1
5,1
4,3
5,1
2,9
37,8
Dobici
toplotne
energije
MWh
3,2
2,7
3,2
2,7
3,4
3,4
3,2
3,4
2,7
28,1
UKUPNO
MWh
41,7
31,5
41,7
31,5
47,1
47,1
41,7
47,1
27,9
329,2
Tabela 44: Ukupni toplotni gubici nakon primjene predloenih mjera poveanja energetske
efikasnosti u dijelu graevinske konstrukcije
10,6%
53,2%
36,3%
Transmisioni gubici
Ventilacioni gubici
Dodatak na ponovno
zagrijavanje
82
energetske
Pozicija
Vanjska stolarija i
bravarija
Spoljanji zidneventilisana
fasada
Ravni
neventilisani krov
Pod na tlu
ZONA
0001
0002
0003
0004
0005
0006
0007
0008
0009
VSB
9,3
4,6
9,3
4,6
7,3
7,3
9,3
7,3
3,9
SZ1N
2,7
5,3
2,7
5,3
4,4
4,4
2,7
4,4
4,7
ST1N
8,3
5,3
8,3
5,3
10,0
10,0
8,3
10,0
5,0
PO1E
2,0
2,5
2,0
2,5
2,3
2,3
2,0
2,3
2,2
UKUPNO (MWh)
62,8
36,9
70,4
20,0
Tabela 45: Transmisioni gubici nakon primjene predloenih mjera poveanja energetske
efikasnosti
83
10,5%
33,0%
VSB
PO1
SZ1N
ST1N
37,1%
19,4%
84
ID MJERA
Mainske mjere
Elektro mjere
Investicija Investicija
Toplotna
Uteda
El. energija
Voda
Uteda sa
bez PDV-a sa PDV
energija
bez PDV-a
[kWh/god.]
[m3/god.]
PDV
[KM]
[KM]
[kWh/god.]
[KM/god.]
Smanjenje
emisije
JPP
CO2
[god.]
[tona/god.]
137715
161127
240105
13201
15445
116,25
10,43
68500
80146
227086
12485
14608
109,95
5,49
59438
69543
225588
12403
14512
109,22
4,79
153000
179010
310925
8406
9835
150,54
18,20
-77731
85
76955
90037
166267
9141
10696
80,50
8,42
83916
98182
221241
12164
14232
107,12
6,90
7020
8213
18290
1006
1177
8,86
6,98
24120
28220
22575
2523
2952
16,81
9,56
1955
2287
1495
189
221
1,11
10,35
2760
3229
7025
1079
1262
5,23
2,56
45
53
165
25
29
0,12
1,80
86
10. PREGLED
PREDLOENIH
SCENARIJA
POVEANJA
ENERGETSKE EFIKASNOSTI
Kombinovanjem predloenih mjera za poveanje energetske efikasnosti formiraju se grupe
aktivnosti (scenarija) ijom se primjenom smanjuje potronja elektrine i toplotne energije u
objektu i smanjuje uticaj sistema na okolinu (smanjuje se emisija ugljen dioksida,
kontaminirane vode i drugih polutanata).
Za objekte JZU Modria prdloena su 3 (tri) scenarija:
SCENARIO "A":
ID
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
87
SCENARIO "B":
ID
9
10
11
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
Ugradnja sistema toplotnih pumpi za svaki objekat posebno. Toplotne pumpe su tip
voda-voda prosjene nominalne snage zagrijavanja 17,0 kWt odnosno prosjene
nominalne elektrine snage Pe= 4,5 kWe kompletne sa instalacijom za primarnog
kruga. Za svaki objekat e se izgraditi po jedna izvorina buotina dubine 8-12
metara. Za sve objekte e biti izgraene 2 (dvije) upojne buotine. Spajanje
toplotnih pumpi na postojei sistem grijanja e biti vren na postojeim toplovodnim
prikljucima. Kao rezervna opcija e biti predvieno zagrijavanje na postojei
sistem daljinskog grijanja.
Ugradnja termoregulacionih ventila na 108 grejnih tijela. Mjera podrazumijeva
uklanjanje postojeih ventila, sanacija prikljunog mjesta na radijatoru, montaa
zaptivnog seta i montaa termoregulacionog ventila sa termoglavom.
Ugradnja solarnih sistema za zagrijavanje PTV za svaki objekat posebno.
Predviena je ugradnja solarnih paketa sa jednim solarnim kolektorom povrine 2,6
m2, bojlerom za pripremu PTV sa prikljukom za solar i dodatnim elektrozagrijaem
i kompletne mjerno regulacione opreme sa recirkulacionom pumpom i
ekspanzionom posudom.
Revitalizacija sistema fluorescentne rasvjete
Revitalizacija sijalica sa arnom niti
Ugradnja vremenskih prekidaa za eliminisanje stand-by gubitka svih printera i
fotokopirnih ureaja
88
SCENARIO "C":
ID
9
10
11
MJERA
Zamjena postojee stolarije novim PVC prozorima sa dvostrukim ostakljenjem
niskoemisionim staklom 4/16ar/c4 Ug manji ili jednak 1.1 W/mK, sa
niskoemisionim premazom, g=0,62 i Uw = 1.3 W/mK. U stavku je ukljuena
demontaa postojeih pozicija, ugradnja spoljanje i unutranje klupice. Obraun je
po povrini pozicija.
Termika izolacija fasade ETICS sistemom kamena mineralna vuna debljine 7,5 cm
( = 0,036 W/mK ). Ukljuivo lijepljenje po ivicama i takasto po povrini prema
uputstvu proizvoaa ETICS sistema, privrivanje plastinim privrsnicama, ivini
i ugaoni profili, polimer-cementno ljepilo, tekstilno-staklena alkalno otporna mreica,
impregnirajui sloj i zavrna obrada silikatnim malterom. Prilagoditi prozorske
klupice novoj debljini zida. Kod prozora i vanjskih vrata ukljuivo zidarska obrada
ivica, brtvljenje svih spojeva. Obraun po povrini ETICS sistema, bez povrine
prozora i dodatka za obradu paleta.
Termika izolacija stropa (krova) iznad negrijanog prostora stambenih jedinica.
Izolovanje se vri tvrdim ploama kamene vune d=18 cm ( = 0,04
W/mK)poloenim po postojeoj konstrukciji. Nabavka i izvedba zatitne
paropropusne vodonepropusne folije. U cijenu uraunato isenje podloge od
neistoe, premaz i zavrni sloj hidroizolacije te obrada postojeih odvodnih
elemenata.
Zamjena postojeih kotlova na ugalj snage 2x314,5 kW kotlovima na drvo, drvni
otpad ili pelet snage 2x350 kW. Mjera podrazumjeva demontau i uklanjanje
postojeih kotlova, ugradnju predloenog kotla na drvo, drvni otpad ili pelet,
akumulatora toplote zapremine 10,0 m3 i ugradnju kompletne pratee mjernoregulacione opreme, sistema za loenje, sistema za prikupljanje i odvoz pepela
itd
Rekonstrukcija cijevovoda sistema daljinskog grijanja. Ova mjera podrazumjeva
demontau postojee cijevne instalacije i montau novih predizolovanih cijevi.
Predizolovane cijevi su sa izolacijom od tvrde PUR pjene u PEHD oklopu
predviene za podzemnu ugradnju.
Ugradnja termoregulacionih ventila na 108 grejnih tijela. Mjera podrazumijeva
uklanjanje postojeih ventila, sanacija prikljunog mjesta na radijatoru, montaa
zaptivnog seta i montaa termoregulacionog ventila sa termoglavom.
Ugradnja solarnih sistema za zagrijavanje PTV za svaki objekat posebno.
Predviena je ugradnja solarnih paketa sa jednim solarnim kolektorom povrine 2,6
m2, bojlerom za pripremu PTV sa prikljukom za solar i dodatnim elektrozagrijaem
i kompletne mjerno regulacione opreme sa recirkulacionom pumpom i
ekspanzionom posudom.
Revitalizacija sistema fluorescentne rasvjete
Revitalizacija sijalica sa arnom niti
Ugradnja vremenskih prekidaa za eliminisanje stand-by gubitka svih printera i
fotokopirnih ureaja
89
90
91
92
93
94
95
96
97
Temperatura
LJ 0C
Z 0C
0,0
0,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
26,0
22,0
Vlanost
%
0,0
72,0
72,0
72,0
72,0
72,0
72,0
72,0
72,0
72,0
VENTILACIJA
n h-1
m3/h os.
0,0
0,0
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
1,0
17,5
P/P+1
GR.
0
DA
DA
DA
DA
DA
DA
DA
DA
DA
VEN.
0
NE
NE
NE
NE
NE
NE
NE
NE
NE
KLI. RAS.
W/m2
0
DA
8
DA
8
DA
8
DA
8
DA
8
DA
8
DA
8
DA
8
DA
8
ZONA
Aktivnost
Laka
Smjena
6
6
6
6
6
6
6
6
6
ZONA 1
ZONA 2
ZONA 3
ZONA 4
ZONA 5
ZONA 6
ZONA 7
ZONA 8
ZONA 9
Aktivnost
Srednja
I
2
Teka
Laka
Smjena
6
6
6
6
6
6
6
6
6
2
2
2
2
2
66
54
ZONA
ZONA 1
ZONA 2
ZONA 3
ZONA 4
ZONA 5
ZONA 6
ZONA 7
ZONA 8
ZONA 9
Gradnja
srednja
srednja
srednja
srednja
srednja
srednja
srednja
srednja
srednja
98
Srednja
II
H,gn
0,98
0,98
0,98
0,98
0,98
0,98
0,98
0,98
0,98
Teka
99
Zoniranje objekta:
Objekat je podijeljen u 9 (devet) zone.
Spratnost objekta:
ZONA 1 (Bosna)
ZONA 2 (Drava)
ZONA 3 (Drina)
ZONA 4 (Ibar)
ZONA 5 (Neretva)
ZONA 6 (Sutjeska)
ZONA 7 (Una)
ZONA 8 (Vrbas)
ZONA 9 (Zeta)
100
Visina H [m]
2,8
2,5
2,8
2,5
2,8
2,8
2,8
2,8
2,5
101
102
103
104
105
106
107
108
109
U=
1
dj 1 1
1
i + j + + e
2
i [W /(m K )]
e [W /( m K )]
8
6
12
25
11
d j [m]
j [W /(mK )]
1
[W /(m2 K)]
[kg/m3 ]
ti [ C ]
t e[ C ]
p[ Pa]
pp= p i [ Pa]
pp= p e [Pa]
i=60
[%]
110
e =90
[%]
r i= id i
c i [J /(kgK )]
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
TD
T24h
HDD 22,0
HDD18
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Ref.
2,4
3,6
9,1
14,1
18,6
22
24,1
24,1
18,6
14,3
8,8
3,9
13,6
0,8
1,8
7,2
12,2
16,8
20,5
22,6
22,2
16,8
12,4
6,8
2,1
11,9
584
501
441
181
0
0
0
0
0
186
422
604
2919
462
392
327
118
0
0
0
0
0
119
310
482
2208
TD
T24h
HDD18
HDD20
700
600
HDD 22,0
500
400
300
200
100
0
127
22,5
625
561
523
297
203
134
82
73
213
300
447
652
23,0
640
575
538
310
216
145
92
81
226
314
462
668
2014
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
17,0
408
320
241
142
99
32
11
19
51
155
273
419
17,5
423
334
255
154
109
37
14
23
59
168
288
435
18,0
438
348
269
166
119
43
18
28
68
180
303
450
18,5
454
362
282
179
130
50
23
32
77
193
317
466
19,0
470
376
297
192
141
58
28
38
88
206
332
481
19,5
485
390
311
205
153
65
34
45
100
220
347
497
20,0
501
404
326
219
165
73
40
52
112
233
361
512
20,5
516
418
340
233
177
82
47
61
124
247
376
528
21,0
532
432
355
247
189
91
54
69
137
260
391
543
21,5
547
446
370
261
202
100
62
79
151
274
406
559
22,0
563
460
386
276
215
110
71
88
165
289
421
574
22,5
578
474
401
291
229
120
79
99
178
303
436
590
23,0
594
488
416
306
242
131
88
109
192
317
451
605
2015
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
17,0
444
409
299
182
61
29
8
7
63
17,5
459
423
314
193
69
34
10
9
71
18,0
474
437
329
205
78
39
12
12
80
18,5
490
451
344
217
87
45
15
16
89
19,0
505
465
359
230
97
51
18
19
99
19,5
521
479
374
243
107
58
21
24
108
20,0
536
493
390
256
118
65
25
30
119
20,5
552
507
405
269
128
73
30
36
130
21,0
568
521
421
282
140
81
36
42
141
21,5
583
535
436
296
152
90
41
49
152
22,0
598
549
451
310
163
98
47
57
164
22,5
614
563
467
325
176
108
54
64
176
23,0
629
577
482
339
188
117
61
73
188
Protokol prorauna
Dh=0
Dh=(Tbase-Tmin)/4
Dh=(Tbase-Tmin)/2-(Tmax-Tbase)/4
Dh=Tbase-(Tmax+Tmin)/2
17,5
17,5
447
378
312
110
18,0
18,0
462
392
327
118
18,5
18,5
478
406
341
126
19,0
19,0
493
420
356
134
19,5
19,5
509
434
371
142
20,0
20,0
525
448
386
151
20,5
20,5
540
462
401
160
21,0
21,0
555
476
416
168
21,5
21,5
571
490
431
177
22,0
22,0
587
504
447
187
22,5
22,5
602
518
462
196
23,0
23,0
617
532
477
205
111
295
467
119
310
482
128
324
497
137
339
513
146
354
529
154
368
544
164
383
559
173
397
575
182
412
591
192
427
606
201
442
621
210
457
637
2118
2208
2298
2390
2483
2574
2666
2759
2853
2947
3041
3134
Wh/m2d
Hh
Wh/m2d
H(90)
1060,0
1540,0
1890,0
2420,0
3460,0
3370,0
4660,0
3210,0
5620,0
2840,0
6280,0
2680,0
6430,0
2910,0
5660,0
3410,0
3870,0
3390,0
2580,0
3130,0
1340,0
1950,0
847,0
1260,0
3650,0
2680,0
130
Broj
ureaja
1
2
1
ZONA 1
ZONA 2
ZONA 3
ZONA 4
ZONA 5
1
1
2
2
1
1
1
1
2
1
1
1
2
1
1
1
ZONA 6
ZONA 7
ZONA 8
ZONA 9
Potroai
elektrine
energije
1
2
2
1
1
1
1
1
1
2
1
1
1
1
1
2
1
Naziv ureaja
Klima ureaj
El bojler
Reo
Mikrotalasna
pe
Raunar
Televizor
El bojler
Klima ureaj
El bojler
Televizor
Ve maina
El bojler
Televizor
Klima ureaj
Grijalica 1,5kW
El bojler
El bojler
Reo
Mikrotalasna
pe
Friider
Televizor
El bojler
El bojler
Reo
Televizor
El bojler
Televizor
Klima ureaj
El bojler
El bojler
Klima ureaj
El bojler
Reo
Friider
Raunar
tampa
Snaga
Ukupno [kW]
ureaja [W]
Tip potroaa
Broj radnih
sati [h]
1800
2000
1200
1,8
4,0
1,2
Split sistem
Bojler 80 l
Kuhinjska oprema
150
700
445
1000
1,0
Kuhinjska oprema
445
450
250
2000
1800
2000
250
2500
2000
250
1800
1500
2000
1500
1200
0,5
0,5
4,0
1,8
2,0
0,3
2,5
4,0
0,3
1,8
1,5
4,0
1,5
1,2
Kancelarijska oprema
Kuni ureaji
Bojler 80 l
Split sistem
Bojler 80 l
Kuni ureaji
Kuni ureaji
Bojler 80 l
Kuni ureaji
Split sistem
Grijalica
Bojler 80 l
Bojler 10 l
Kuhinjska oprema
460
430
700
150
700
430
430
700
430
150
1149
700
350
445
1000
1,0
Kuhinjska oprema
445
650
250
2000
1500
1800
250
2000
250
1800
2000
1500
1800
2000
1200
650
450
350
0,7
0,5
4,0
1,5
1,8
0,3
2,0
0,3
1,8
4,0
1,5
1,8
2,0
1,2
0,7
0,9
0,4
Kuhinjska oprema
Kuni ureaji
Bojler 80 l
Bojler 10 l
Kuhinjska oprema
Kuni ureaji
Bojler 80 l
Kuni ureaji
Split sistem
Bojler 80 l
Bojler 10 l
Split sistem
Bojler 80 l
Kuhinjska oprema
Kuhinjska oprema
Kancelarijska oprema
Kancelarijska oprema
445
430
700
350
445
430
700
430
150
700
350
150
700
445
445
460
460
45
59,9
131
536
H T ,ie = Ak U k f k + l l l f l = Ak (U k + U WB ) f k [ W / K ]
k
Ak [m ]
fk
U k [W /m2 K ]
l [W / mK ]
l l [m]
fk
1,00
0,80
0,40
0,90
0,90
0,50
0,30
U WB=0,10[ W /m K ]
U WB=0,05[W / m K ]
U WB=0,02[W /m K ]
2
132
H T ,iue = Ak U k bu + l l l bu [W / K ]
k
bu = i nt ,iu
i nt ,i
e
u [0C ]
H T ,ig [W / K ]
H T ,ig = f g 1 f g 2 Ak U ekuiv G W [W / K ]
f g 1=1,45
i nt , im ,e
f g 2=
i nt , i
e
nivou;
Faktor smanjenja temperaturne razlike izmeu srednje vanjske i
vanjske temperature;
m ,e =11,6[ C ]
U ekuiv [W /m K ]
B, m
0
2
4
6
8
10
12
14
16
18
20
1
0,44
0,38
0,33
0,29
0,26
0,24
0,22
0,20
0,19
0,18
2
0,58
0,48
0,40
0,35
0,31
0,28
0,25
0,23
0,22
0,20
1
0,8
0
0,25
0,5
1
2
0,6
0,4
0,2
0
2
B=
Ak
[m]
0,5P
10
12
Karakteristini parametar;
133
14
16
18
20
Ak [m2 ]
P [m]
Povrina poda;
Obim poda;
1,15 za hgw<3; Korekcijski faktor uticaja podzemnih voda;
Dubina podzemnih voda;
GW= 1 za hgw>3;
hgw [m]
H T ,ij [W / K ]
H T ,ij = Ak U k f ij [W / K ]
k
f ij = i nt ,i ads
i nt , i
e
ads [ C ]
susjedne prostorije;
a c p,a V ue
Koeficjent ventilacionih gubitaka;
[W / K ]
3600
Gustoa vazduha;
a [kg/ m3 ]
c p,a V ue [kgK ]
Specifini toplotni kapacitet vazduha;
V ue [W / K ]
Zapreminski protok vazduha izmeu grijanog prostora i okoline;
H Ve=
V i =V inf ,i +V min ,i [ m / h]
V inf ,i
Maksimalan protok vazduha u prostoriju usljed infiltracije spoljanjeg
vazduha kroz zazore;
n 50 [h1 ]
Graevina
Stamb. objekat
Ostali tipovi zg.
134
ei
Koeficijent zatienosti;
Klasa zatienosti
Bez zatite
Srednja zatita
Visoka zatita
Koeficijent zatienosti; ei
Grijani prostor bez Grijani prostor
otvora
jednim vanj. otv.
0
0,03
0
0,02
0
0,01
V i nt [m ]
135
NAZIV
ZONA 1
Proj. temp.
0
C
22
0002
Spec. gubici
ZONA 2
22
Spec. gubici
0003
ZONA 3
22
Spec. gubici
0004
ZONA 4
22
Spec. gubici
0005
ZONA 5
22
Spec. gubici
0006
ZONA 6
22
Spec. gubici
0007
ZONA 7
22
Spec. gubici
0008
ZONA 8
22
Spec. gubici
0009
ZONA 9
22
Spec. gubici
310,5
112,9
52.098,0
319,3
127,7
41.095,8
310,5
112,9
52.098,0
319,3
127,7
41.095,8
292,2
106,3
58.505,7
292,2
106,3
58.505,7
310,5
112,9
52.098,0
292,2
106,3
58.505,7
323,6
129,4
36.597,4
450.600,0
POSTOJEE
STANJE
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
18. DODATAK 8 PRORAUN TOPLOTNIH GUBITAKA I DOBITAKASTANJE NAKON ZAMJENE VANJSKE STOLARIJE I BRAVARIJE I
POSTAVLJANJA TERMOIZOLACIJE
REKAPITULACIJA TOPLOTNIH GUBITAKA:
ID.
0001
NAZIV
ZONA 1
Proj. temp.
0
C
22
Spec. gubici
0002
ZONA 2
22
Spec. gubici
0003
ZONA 3
22
Spec. gubici
0004
ZONA 4
22
Spec. gubici
0005
ZONA 5
22
Spec. gubici
0006
ZONA 6
22
Spec. gubici
0007
ZONA 7
22
Spec. gubici
0008
ZONA 8
22
Spec. gubici
0009
ZONA 9
22
Spec. gubici
SCENARIO
106,6
38,8
17.882,6
105,2
42,1
13.533,0
106,6
38,8
17.882,6
105,2
42,1
13.533,0
101,0
36,7
20.211,8
101,0
36,7
20.211,8
106,6
38,8
17.882,6
101,0
36,7
20.211,8
105,9
42,4
11.977,1
153.326,2
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W/m2
W/m3
W
W
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
Godina
2012
2013
2014
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Dobavljena
koliina uglja
Utroena
toplotna
energija
[tona]
[MWh]
[MWh]
[KM/tona]
118,2
87,1
75,4
389,1
286,7
248,2
0,0
0,0
0,0
0,0
0,0
0,0
484,9
96,1
493,6
389,5
194,4
384,9
96,5
0,0
0,0
0,0
0,0
0,0
344,9
250,9
250,9
337,1
381,9
164,6
82,3
0,0
0,0
0,0
0,0
0,0
378,6
317,6
510,3
389,1
286,7
248,2
0,0
0,0
0,0
0,0
0,0
0,0
484,9
96,1
493,6
389,5
194,4
384,9
96,5
0,0
0,0
0,0
0,0
0,0
344,9
250,9
250,9
337,1
381,9
164,6
82,3
0,0
0,0
0,0
0,0
0,0
378,6
317,6
510,3
162,39
162,39
162,39
162,39
162,39
162,39
162,39
162,39
162,39
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
119,00
147,3
29,2
149,9
118,3
59,1
116,9
29,3
104,8
76,2
76,2
102,4
116,0
50,0
25,0
115,0
96,5
155,0
Ukupno ENERGENT
za
- jedinina
obraun
cijena
175
UKUPNO - iznos
bez PDV-a
[KM]
[KM]
22.458,00
16.549,00
14.322,20
0,00
0,00
0,00
0,00
0,00
0,00
20.507,64
4.065,75
20.875,18
16.474,42
8.222,57
16.279,26
4.082,01
0,00
0,00
0,00
0,00
0,00
14.585,73
10.609,33
10.609,33
14.257,15
16.150,68
6.961,50
3.480,75
0,00
0,00
0,00
0,00
0,00
16.011,45
13.434,30
21.580,65
19.194,87
14.144,44
12.241,20
0,00
0,00
0,00
0,00
0,00
0,00
17.527,90
3.475,00
17.842,03
14.080,70
7.027,84
13.913,90
3.488,90
0,00
0,00
0,00
0,00
0,00
12.466,44
9.067,80
9.067,80
12.185,60
13.804,00
5.950,00
2.975,00
0,00
0,00
0,00
0,00
0,00
13.685,00
11.482,31
18.445,00
Godina
2012
2013
2014
Mjesec
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Januar
Februar
Mart
April
Maj
Jun
Jul
Avgust
Septembar
Oktobar
Novembar
Decembar
Utroena
koliina vode
Ukupno za
obraun
[m3]
1.118
1.259
1.087
1.201
1.395
2.074
2.044
1.684
1.383
1.529
1.269
1.565
1.545
1.258
1.307
1.669
1.232
1.191
979
2.269
1.263
1.718
1.224
1.143
1.439
1.681
1.375
1.404
1.474
1.118
1.248
1.258
1.170
991
984
1.245
[m3]
1.118
1.259
1.087
1.201
1.395
2.074
2.044
1.684
1.383
1.529
1.269
1.565
17.609
1.258
1.307
1.669
1.232
1.191
979
2.269
1.263
1.718
1.224
1.143
1.439
1.681
1.375
1.404
1.474
1.118
1.248
1.258
1.170
991
984
1.245
VODA jedinina
cijena
[KM/m3]
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
1,58
176
PDV
VODA - ukupni
iznos s PDV-om
[%]
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
17,00%
[KM]
1.764,52
1.985,34
1.715,72
1.895,06
2.198,84
3.266,34
3.218,84
2.653,28
2.180,41
2.409,78
2.001,32
2.466,34
2.434,92
1.984,04
2.061,02
2.629,72
1.943,19
1.878,78
1.545,73
3.572,32
1.991,89
2.706,70
1.930,62
1.803,37
2.268,39
2.648,57
2.167,85
2.213,40
2.323,37
1.764,10
1.968,33
1.984,04
1.845,79
1.564,58
1.553,58
1.963,62
22. DODATAK
12
KARAKTERISTIKE
ENERGENTA/
UGALJ
MILJEVINA
ENERGENT
Mjera
Mrki ugalj
tona
BAS 1002
Karakteristika
Jedinica
Standard
kJ/kg
kWh/kg.
MWh/toni
Vrijednost
11.851,3
3,29
3,29
Hemijski sastav
C
35,50
FORMIRANJE CIJENE
ENERGIJE
Prosjena cijena energeta:
H
1,03
O
6,70
tona
Mrki ugalj
N
0,94
S
2,78
W
28,22
139,23 KM /toni
Amortizacija:
25,00%
Odravanje:
5,00%
A
24,83
54,98 KM
177