You are on page 1of 8

Mobrey Squing 2

Vibrating fork point level measurement

Squing 2 vibrating fork level switch


Squing 2 is a liquid point level switch designed using the tuning fork principle. The Squing 2 continuously monitors
changes in its vibrating forks natural resonant frequency. When the Squing 2 is used as a low alarm, the liquid in
the vessel drains down past the fork resulting in a change of its frequency; this is detected by the electronics which
switches the output state. When used as a high alarm, the liquid rises in the vessel, contacts with the forks and again
the output switches.

Easy terminal
access

Visible
heartbeat LED

Magnetic
test point
Two M20
conduit entries

Short fork length


for minimum
intrusion and pipe
mounting

" or 1"
thread

Explosion proof
EExd models

Features
n " and 1" Threaded (BSPT, BSPP, NPT) as standard or extended
lengths to 3m/10 feet
n Choice of international flanges and range of hygienic fittings
n Versatile switch outputs Relay, direct load switching, PLC/PNP
n Hazardous area approval for explosion proof (Exd) and intrinsically safe
(Exia) applications by ATEX, FM, CSA & IECEx
n Halar/PFA coating for chemical resistance
n Continuous operating temperature up to 150C and pressure up to
100 bar g
n No mechanical parts maintenance free

Short Fork Technology


Using short fork technology pioneered by Mobrey and many years of
application experience, the Squing 2 is designed for use in virtually
all applications. Extensive research has maximised the operational
effectiveness of the fork design while keeping in mind the practical
consideration of a level switch that is suitable for most liquids, including
coatings, aerated liquids, and slurries.
Special features
Squing 2 has a status indicating heart-beat LED which can be seen at all
times through a lens in the cover. The LED will flash (once per second)
when the Squing 2 is off and will be constantly lit when the Squing 2 is
on. The LED gives an indication that the Squing 2 is functioning correctly
and gives a local visual indication of the state of the wetside.
A mode switch allows the Squing 2 to be set to switch from wet to dry
(typically low alarm) or from dry to wet (typically high alarm). You may
also select a time delay from 0.3, 1, 3, 10, or 30 seconds.

IP66 housings in
plastic, aluminium
and stainless steel

Extension
up to
3m/10ft

A magnetic test point on the side of the housing allows the user to
perform a functional test of the Squing 2. By touching a magnet on the
target the Squing 2 output will change state for as long as the magnet is
present.

1" (DN40)
or larger

Applications
Overfill protection
Spillage caused by overfilling can be hazardous to the environment and
people, resulting in lost product and incurring costs of clean up operations.
Squing 2 is a failsafe limit level switch with built-in highly visible heartbeat
LED to reassure you that it is always ready to detect and signal overfill at
any time.
Provided as standard, the magnetic test point on the unit allows for
simple on-site functional test providing re-assurance of operation without
removing the unit from your tank.

Failsafe
Manual test facility
Heartbeat LED

Limit detection
Often batch processing tanks contain stirrers/agitators to ensure the
mixing and product fluidity. With the standard user selectable time
delay from 0.3 to 30 seconds, there is no chance of false switching due
to splashing caused by stirrers/agitators.
A choice from a range of different electronics provides the benefit of
trouble-free integration into your existing system especially as existing
wiring can be utilised.

Pipe installation (pump protection)


Short forks for minimum intrusion wetside allows simple low cost
installation at any angle into your pipes or vessels. With the forks
projecting in only 69mm, the Squing 2 can be installed in small
diameter pipes. By selecting the option of direct load switching
electronics, Squing 2 is ideal for reliable pump control and can be used
to protect against pump dry running.
With a range of housings types rated IP66/67 the Squing 2 can be
installed in almost any environment.

Time delay switching option


Resistance to false switching
Choice of electronic outputs

Small forks
Low cost
Reliable
IP66/67

High and low level alarm


Maximum and minimum detection in tanks containing many types
of liquid is measured using Squing 2. The robust Squing 2 operates
continuously at temperatures up to 150C and operating pressure
to 100 bar g making it perfect for use as a high or low level alarm.
Available with industry standard flanges to ANSI and BS standards
from stock, or other international standards to order and with forks
constructed in various materials such as stainless steel, Alloy C (UNS
N10002), or with ECTFE (Halar)/PFA coatings.

Hygienic applications
With the option of highly polished forks with a surface finish (Ra)
better than 0.8m, the Squing 2 meets the principle design criteria
of 3A and EHEDG for equipment used in the manufacture of hygienic
applications like food, beverage, and pharmaceutical. Manufactured
in stainless steel the Squing 2 is robust enough to withstand steam
cleaning (CIP) routines at temperatures up to 150C.
Working in viscous liquids and liquids with high solids content, the
Squing 2 will ignore low/medium density foams and aeration.

Range of process
connections
High temperature
High pressure
Plastic or aluminium
housing

Hygienic surface finish


Extended forks
Install anywhere

Technical specification
Electronics
Standard two core cable with any power supply from 24 to 260V ac (24 to 60V dc) is
used to connect Squing 2 in series with the load and achieve direct load switching. The
output acts as a simple SPST switch that changes with liquid presence. Alternatively use
the switching function of the SPCO relay electronics output. Squing 2 also has the option
of electronics to be interfaced directly to a PLC using the PNP transistor output model
(three-wire).
Intrinsically Safe (IS) Squing 2 to ATEX EExia approval interfaces directly with standard
NAMUR (DIN 19234, IEC 60947-5-6) isolation amplifiers.
SIL2 Certification
The Intrinsically Safe version of the Squing 2 has been assessed and rated SIL2 for use as a
Type B safety related subsystem in accordance with IEC61508, when configured as a high
level alarm only in conjunction with a Namur barrier.

Mounting options
Threaded mounting
Standard threads
Maximum operating pressure
Maximum operating temperature
Minimum operating temperature
Maximum ambient temperature

", 1", BSPT, BSPP, NPT


100b (-40 to +50C) derates to 80b (at 150C)
+150C wetside
-40C wetside/dryside
+80C (at 60C wetside)

Notes:
Max. length E = 3000mm.
Extended models with " and 1" threads,
" min E = 95mm, 1" E = 94mm
Accessories:
For use with extended length Squing (1" models only), a stainless steel
adjustable clamp gland is available.
This is threaded 1" BSPP for connection to the vessel, and allows the
extended length Squing to be raised or lowered then clamped in position.
Note: this limits max. operating pressure to 1.3bar (SK304)

* Nominal switching point,


vertically mounted

Mounting options
Flange mounting
Standard flanges
Maximum operating pressure

Maximum operating temperature
Minimum operating temperature
Maximum ambient temperature

ANSI, DIN, Mobrey (see ordering codes overleaf)


100b (-40 to +50C)
80b (at 150C) or flange rating, whichever is the lower
+150C wetside
-40C wetside/dryside
+80C (at 60C wetside)

Notes:
Max. length E = 3000mm. Min. E = 89mm
Options:
For use with corrosive liquids having condensing vapours, flanged Squing can be supplied
with the wetside fully Halar/PFA co-polymer coated.
Maximum extended length E = 1000mm.

Hygienic fitting
Standard fittings
Maximum operating pressure
Maximum operating temperature
Minimum operating temperature
Maximum ambient temperature
Notes:

Tri-Clover , SMS, DIN 11581, 'O' Ring seal (1" BSPP)


30 bar
+150C wetside
-40C wetside/dryside
+80o C (at 60C wetside)
Max. length E = 3000mm
Triclover min E = 105mm

Options:
Hand polished wetside to a finish better than 0.8m meets the principal design criteria
of3A and EHEDG hygienic approvals.
Accessories:
For use with 2" (51mm) Tri-clover Squing 2, a mounting kit comprising vessel fitting,
Nitrile seal and clamp ring is available (SK266)
For use with 'O' ring seal Squing, a fitting boss with Fluorocarbon (FPM/FKM) 'O' ring is
available (SK267)

* Nominal switching point, vertically mounted

Ordering information
Code Product
T Squing 2
Code Material
D 316L Stainless steel (1.4404)
E 316L Stainless steel 3.1B Certs (1.4404)
F Halar/PFA, 316L stainless steel (1.4404)
G Halar/PFA, 316L stainless steel 3.1B Certs. (1.4404)
C1 Alloy C (UNS N10002), solid Alloy C276 (UNS N10276)
Code Size
1 1"
2 2" / DN50 / 51mm
3 3" / DN80
4 4" / DN100
5 "
6 1.5" / DN40 / 38mm
7 DN65
8 A Flange
9 G Flange
Code Fitting
A BSPT (R)
B BSPP (G)
D NPT
G #150 RF
H #300 RF
J #600 RF
K PN10/16
L PN25/40
M PN63
N PN100
P BSPP Hygienic fitting
Q Mobrey
R Tri-Clover clamp
S SMS hygienic fitting
T Tuchenhagen
V DIN 11851
Code Electronic type
B PNP/PLC low voltage (3 wire) 24 to 60V dc
R Relay (SPCO)
S Direct load switching (mains 2 wire)24 to 264Vac 50/60Hz, 24 to 60Vdc
C 2 3 IS NAMUR (EExia)
Code Surface finish
1 Standard
2 4 Hand polished (Ra <0.8m)
Code Approvals and housing
NA Standard (no approvals), M20 conduits, glass nylon
ND Standard (no approvals)," NPT conduits, glass nylon
GY FM and CSA (Unclassified, safe area), " conduits, aluminium
GT FM and CSA (Unclassified, safe area), " conduits, 316 stainless steel
AA 5 ATEX and FM (IS), M20 conduits, glass nylon
AD 5 ATEX and FM (IS), " NPT conduits, glass nylon
CA 5 CSA (IS) and Non Incendive, M20 conduits, glass nylon
CD 5 CSA (IS) and Non Incendive, " NPT conduits, glass nylon
t t t t t t

Ordering information
HA 5
IECEx (IS), M20 conduits, glass nylon
HD 5 IECEx (IS), " NPT conduits, glass nylon
EX 6 ATEX (Exd), M20 conduits, aluminium
ES 6 ATEX (Exd), M20 conduits, 316 stainless steel
FY 6 FM (Exd), " conduits, aluminium
FT 6 FM (Exd), " conduits, 316 stainless steel
DY 6 CSA (Exd), " conduits, aluminium
DT 6 CSA (Exd), " conduits, 316 stainless steel
JX 6 IECEx (Exd), M20 conduits, aluminium
JS 6 IECEx (Exd), M20 conduits, 316 stainless steel
Code Length
A 7 Standard length (44 mm)
H Standard length flange (102 mm)
B 8 Ext 150mm
C 8 Ext 300mm
D 8 Ext 500mm
L 9 Semi-ext (116 mm)
Specific extended fork Length
E 10 Extended, customer specified length in millimetres

t t t t t

NA

Typical ordering information

Notes:
Only in conjunction with threaded fitting A and D.
2
Only in conjunction with approval and housing AA, AD, CA, CD, HA and HD.
3
Conforms to SIL 2 of IEC 61508 as a Type B safety related subsystem when ordered as
T***C*A**, T***C*C**, T***C*H** and configured as a high level alarm in conjunction with a Namur barrier.
4
Only in conjunction with hygienic fitting P, R, S, V or T.
5
Only in conjunction with electronic type C.
6
Not in conjunction with electronic type C. Not available with length L.
7
Not available with flanged models. For flanged models use length H.
8
Not available with hygienic fitting R. Extended lengths for this must be ordered as T**R****E****.
9
Only available with material TD and TE and threaded fittings 1A, 1B and 1D.
10
Halar/PFA coating is available up to 1000mm maximum. Halar/PFA coating is NOT available on threaded options.
1

Specifications
Construction
Housing/Enclosure
Threaded connections
Hygienic connections
Extended lengths
Coating
Ingress protection

Aluminium alloy ASTM B26 356-T6, B360.0, stainless steel 316L (M20 or " cable entry)
Nylon PA66 30% GF (M20 or " NPT cable entry)
R " and 1" (BSPT); G " and 1" (BSPP); " and 1" NPT
TriClover, SMS, BSPP flush mount, Tuchenhagen, DIN 11851
Flanges to ANSI B16.5 (1.5 or larger) and BS4504 (DN40 or larger)
Available to max 3m.
Halar (ECTFE) / PFA co-polymer (1000mm max.).
Hand polished to better than 0.8m in accordance with EHEDG and 3A
IP66/67

Operating conditions
Wetside temperature range
Ambient temperature range
Wetside pressure range
Liquid specific gravity range
Liquid viscosity range
Switching point (water)
Hysteresis (water)
Switching delay
Electrical connections
Electrical connections

-40oC to +150o C
-40oC to +80o C (derated to 50o C at 150o C wetside)
-0.25 bar g to +100 bar g at 50o C
0.6 to 2.0
0.2 to 10,000 cps
13mm from tip (vertical) / from edge (horizontal) of fork
+/- 1mm nom.
User selectable 0.3, 1, 3, 10, 30 seconds delay dry to wet / wet to dry

Direct load switching (two wire) 24 to 264V ac 50/60Hz, 24 to 60V dc


Solid state PNP output for direct interface to PLCs (three wire) 24 to 60V dc
SPCO single relay for voltage free contacts
Intrinsically Safe (IS) NAMUR to DIN 19234, IEC 60947-5-6

Approvals/certificates
E.M.C. Directive
L.V. Directive
Approvals/Certs

Pending

EN61326 Emissions to Class B. Immunity to industrial location requirements


EN61010-1
Pollution degree 2, Category II (264V max)
Pollution degree 2, Category III (150V max)
ATEX: II 1 G D, EExia IIC T5; II 1/2 G D, EExd IIC T6
FM: XP/I/1/ABCD/T6 Ta = 75C; T4 Ta = 125C; Type 4X

IS/I/1/ABCD/T* Ta = 80C; IP6X; I/0/AEx ia IIC T* Ta = 80C
CSA: CLI, Div1, Gps. A, B, C, D; Exia IIC T5; CLI Div2, Gps. A, B, C, D

CLI, Div1, Gps. A, B, C, D; Exd IIC T6
SIL2 of IEC61508 as a type B safety related subsystem when configured as a high level
alarm in conjunction with a Namur barrier.
IECEx (Exd, tD), IECEx (Exia, iaD)

A faulty or failed Squing 2 will be replaced with a new unit provided that the fault or failure is reported either directly or via an
accredited Agent, within a period of 1 year from the date of supply, and the product has been installed and used in accordance with
instruction manual IP2025.
Emerson Process Management reserves the right to examine such product and to refuse replacement at its discrection if the above
conditions are not met.
The Emerson logo is a trade mark and service mark of Emerson Electric Co.
Rosemount is a registered trademark of Rosemount Inc.
Mobrey is a registered trademark of Mobrey Ltd.
All other marks are the property of their respective owners
We reserve the right to modify or improve the designs or specifications of product and services at any time without notice.

International:

Americas:

Emerson Process Management


Mobrey Measurement

Emerson Process Management


Rosemount Inc.

158 Edinburgh Avenue, Slough,


Berks UK SL1 4UE
T +44 (0)1753 756600
F +44 (0)1753 823589
www.mobrey.com

8200 Market Boulevard


Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (International) 952) 906-8888
F (952) 949-7001

Literature reference number: IP2024, Rev AA, February 2009

You might also like